• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
Dry contact for thermostat Owner’s & installation manual
TABLE OF CONTENTS
n Safety Precautions .............................................................3~5
n Name of each part ..................................................................6
n Installation Method .............................................................7~8
Installation.................................................................................................7
n Setting and using method ................................................9~20
1. Power supply and indoor unit connection ...........................................9
2. Setting of Contact Signal Input ..........................................................10
3. Setting of ‘SETTING_SW’..................................................................11
4. Setting of ‘TEMP_SW’ .......................................................................14
5. Installation of thermostat....................................................................15
6. Indoor unit monitoring ........................................................................20
2 Dry contact for thermostat
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage.
n Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
n Installation
Don’t touch with the hands
while the power is on.
• Cause fire, electric shock,
explosion or injury.
Product installation must
be referred to a service
center or installation shop.
• Cause fire, electric shock,
explosion or injury.
Request installation from
installation shop or service
center when reinstalling
the product.
• Cause fire, electric shock,
explosion or injury.
Servic
Centere
Servicer
Cente
Installation manual 3
ENGLISH
Safety Precautions
Safety Precautions
Do not install the product
in the place where rain can
get to the product.
• Cause product failure
Do not install the unit in
humid locations.
• Cause product failure
Do not install in a place
that cannot withstand the
weight of the product.
• The product may get
damaged or may break.
Do not install the product
to a place that generates
oil, steam, salt, sulfuric
gas, etc.
• Cause the product’s
deformation or failure.
Do not put the product
closer to fire.
• Cause fire
Use standardized Product.
• Cause product failure
Standardized
product
n Operation
Do not change or extend
power lines arbitrarily.
• Cause fire or electric shock.
Do not give a shock to the
product.
• If you give a shock to the
product, it may cause the
product’s failure.
4 Dry contact for thermostat
Do not use a heater near
the power line.
• Cause fire or electric shock.
Safety Precautions
• Cause electric shock or
breakdown.
If the product has been
inundated, you must refer to
a service center or
installation shop.
• It can cause a fire.
Children and elderly use the
product under the
guardian’s supervision.
• Cause accidents and product
failures.
Servic
Centere
Do not use for special
purpose / place such as
conserving flora and fauna,
precision instruments, art.
Remove the power plug
when cleaning.
• Otherwise, it can cause property
damage.
• Cause fire or electric shock.
Do not disassemble, repair,
or modify the product.
Do not touch with wet
hands.
• Cause fire or electric shock.
Do not place heavy objects
on the power line.
• Cause fire or electric shock.
• Cause fire or electric shock.
P
STO
Installation manual 5
ENGLISH
Do not spill water inside of
the product.
Name of each part
Name of each part
Front Case
Rear Case
8
7
9
2
11
6
10
5
4
1
3
ISO View
PCB
Side
Side
* Others :
Screw 4 EA(For installation)
Clamp 4 EA(For installation)
Cable(1 EA)
(For Connecting with indoor unit)
Installation Manual
DRY CONTACT FOR THERMOSTAT
1. CN_INDOOR
2. CHANGE_OVER_SW
3. CN_OUT(O1,O2)
4. CN_OUT(E3,E4)
5. TEMP_SW
6. SETTING_SW
7. CN_Ther/oper
8. CN_MODE
9. CN_WIND
10. DISPLAY_LED
11. RESET_SW
: Connector for indoor unit
: Switch to select External Voltage or Non Voltage for input contact signal
: Output terminal to show whether the indoor unit is operating (Relay contact)
: Output terminal to show whether there is an error with the indoor unit (Relay contact)
: Switch to set the desired temperature of the indoor unit
: Switch to select whether to use set function of Dry contact
: Input terminal for thermo & operation signal
: Input terminal for Mode signal
: Input terminal for Wind signal
: LED to display the status of Dry contact Module
: Reset switch
6 Dry contact for thermostat
Installation Method
ENGLISH
Installation Method
Installation
1) Loosen and remove two screws that secure the
product.
2) Position the rear case to the direction towards to the
connector for convenient cable arrangement.
3) Secure the rear case on the installation place using the
supplied fixing screws.
4) Remove knock out shapes on the rear case (4-sided)
according to the connector’s size and direction.
Installation manual 7
Installation Method
5) Connect the connection wires properly according to the connection method. (Refer to the instruction
and set-up description)
6) Set the switch according to the setting method. (Refer to the instruction and set-up description)
7) Tighten the fixing screws on the top and bottom of the case.
1. Install the product on flat surface and install anchoring screws at more than 2 places. Otherwise
the central controller may not be anchored properly.
2. Do not tighten anchoring screws too tightly. It may cause deformation of the case.
3. Do not deform the case at random. It may cause malfunction of the central controller.
8 Dry contact for thermostat
Setting and using method
After change any Dry contact setting, then you must press RESET switch to reflect the setting.
1. Power supply and indoor unit connection
n When using the Dry contact for communication independently
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
CN_PI485
RESET_SW
CN_INDOOR
Indoor unit
PCB
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Installation manual 9
ENGLISH
Setting and using method
Setting and using method
2. Setting of Contact Signal Input
opno
tpkksl
sv~
jvvs
olh{
jvtt
mhu
v—Œ™ˆ›–•
{Œ”ˆ“
jvtt
n For input contact closure only(No power input)
Thermostat
LG does not
supply this section
(Field supply)
CHANGE
OVER_SW
NOT
USE
CN_Ther/Oper
CN_MODE
VOLT
CN_WIND
CHANGEOVER_SW
NON
VOLT
RESET_SW
Do not input the voltage signal in
"NON VOLT" setting mode otherwise
it will cause serious damage
SETTING_SW
CN_PI485
CN_INDOOR
Notes
DISPLAY_LED
TEMP_SW
CN_OUT
HIGH
MIDDLE
LOW
COOL
HEAT
COMM
FAN
Operation
Themal
COMM
n For input contact voltage : DC 12 V, 24 V~
Connect separate
External voltage of
DC 12 V, 24 V~
CHANGE
OVER_SW
NOT
USE
CN_Ther/Oper
CN_MODE
VOLT
CN_WIND
CHANGEOVER_SW
CN_PI485
CN_INDOOR
NON
VOLT
RESET_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT
10 Dry contact for thermostat
Thermostat
LG does not
supply this section
(Field supply)
Setting and using method
n Using ‘SETTING_SW’ , select the Option of control Function
as described below
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
CN_PI485
CN_INDOOR
RESET_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT
SETTING_SW
<SETTING_SW Function>
No.
WIND Signal
en/disable
Thermal
en/disable
Oper Mode
en/disable
Dry Contact Control
Priority
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Disable
Enable 1)
Enable
Enable
Enable
Enable
Enable
Enable
Enable
Disable
Disable
Disable
Disable
Enable2)
Enable
Enable
Enable
Disable
Disable
Disable
Disable
Enable
Enable
Enable
Enable
Disable
Disable
Enable3)
Enable
Disable
Disable
Enable
Enable
Disable
Disable
Enable
Enable
Disable
Disable
Enable
Enable
Disable
Enable4)
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
Disable
Enable
1) Enable CN_WIND signal – Amount of wind flow (Low, Middle, High) signal enable
2) Enable Thermo ON/OFF input signal
- Desired Temperature 18 ℃ in cooling mode
- Desired Temperature 30 ℃ in heating mode
- No function in FAN mode
3) Enable CN_MODE signal – Operation mode (Cool, Heat, Fan) signal enable
4) Enable Thermostat priority control mode – Indoor’s remote-controller signal will be disregarded
Notes
• Information of ‘SETTING_SW’ is sensed only initial step by Dry contact module therefore , once the
configuration changed , Reset of Dry contact module is required.
• After power input or unit’s reset , wait 25~30 sec(Display LED 10 times blinking) for unit stabilization
then Dry contact module will operate normally.
Installation manual 11
ENGLISH
3. Setting of ‘SETTING_SW’
Setting and using method
n Flow Chart for ‘SETTING_SW’
-. When not using WIND signal
Use WIND Signal?
NO
Set the switch ‘0 ~ 7’
YES
Use Thermal function?
NO
Set the switch ‘0 ~ 3’
Set the switch ‘4 ~ 7’
YES
YES
Use Operation mode?
Use Operation mode?
NO
NO
Set the switch ‘0 ~ 1’
Set the switch ‘2 ~ 3’
Use Dry Contact
Control Priority?
Use Dry Contact
Control Priority?
YES
NO
Switch 0
Set the switch ‘4 ~ 5’
Use Dry Contact
Control Priority?
NO
Switch 1
YES
Switch 2
Set the switch ‘6 ~ 7’
Switch 3
Use Dry Contact
Control Priority?
NO
YES
Switch 4
NO
Switch 5
YES
Switch 6
Switch 7
-. When using WIND signal
Use WIND Signal?
YES
Set the switch ‘8 ~ F’
YES
Use Thermal function?
NO
Set the switch ‘8 ~ B’
Set the switch ‘C ~ F’
YES
YES
Use Operation mode?
Use Operation mode?
NO
NO
Set the switch ‘8 ~ 9’
Set the switch ‘A ~ B’
Use Dry Contact
Control Priority?
NO
Switch 8
Set the switch ‘C ~ D’
Use Dry Contact
Control Priority?
YES
Switch 9
NO
Switch A
Set the switch ‘E ~ F’
Use Dry Contact
Control Priority?
YES
Switch B
NO
Switch C
Use Dry Contact
Control Priority?
YES
Switch D
NO
Switch E
YES
Switch F
Notes
• When you change a function with remote control without setting Dry_contact control priority the display
condition between remote control and controller can be different.
12 Dry contact for thermostat
Setting and using method
HIGH
MIDDLE
LOW
COOL
HEAT
COMM
FAN
Operation
Themal
COMM
CN_Ther/Oper
CN_MODE
CHANGEOVER_SW
CN_WIND
SETTING_SW
85
RESET_SW
SETTING
_SW
2,3,6,7,A,B,E,F
Others
SETTING
_SW
8,9,A,B,C,D,E,F
Others
SETTING
_SW
4,5,6,7,C,D,E,F
Others
FAN
0
0
0
0
1
1
1
1
Low
0
0
0
0
1
1
1
1
Thermal
0
0
1
1
-
CN_MODE input
HEAT
0
0
1
1
0
0
1
1
CN_WIND input
Middle
0
0
1
1
0
0
1
1
CN_Ther/Oper input
SETTING_SW
COOL
0
1
0
1
0
1
0
1
High
0
1
0
1
0
1
0
1
Operation
0
1
0
1
-
Function
NA
COOL
HEAT
NA
FAN
NA
NA
NA
NA
Function
NA
High
Middle
NA
Low
NA
NA
NA
NA
Function
Thermal Off + Stop
Thermal Off + Run
Thermal On + Stop
Thermal On + Run
NA
Notes
1) Thermal On : This input will change automatically desired temperature
Desired Temperature 18 °C In cooling mode
Desired Temperature 30 °C In heating mode
No function In FAN mode
Installation manual 13
ENGLISH
n Function table for the selection of ‘SETTING_SW’ and the
input signal
Setting and using method
4. Setting of ‘TEMP_SW’
n When setting the desired temperature of the Dry contact
Module
: When operating the indoor unit using Dry contact module’s desired temperature, set the desired
temperature according to the ‘TEMP_SW’ setting.
If Thermostat priority control mode is disabled, the desired temperature can be reset by other controller
- Use the ‘TEMP_SW’ to set the temperature as shown below.
CN_WIND
TEMP
(°C)
Not use Dry Contact
module's Desired 18
temp function
19
20
21
22
1
2
3
4
5
'TEMP SW'
setting
SETTING_SW
DISPLAY_LED
0
TEMP
(°C)
23
24
25
26
27
28
29
30
'TEMP SW'
setting
6
7
8
9
A
B
C
D
*. E, F : Reserved
TEMP_SW
CN_OUT
14 Dry contact for thermostat
Setting and using method
n When interlocking with thermostat, select the option of
control function as described below.
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
SETTING_SW
CN_INDOOR
CN_PI485
RESET_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
TEMP_SW
CN_OUT
<Switch Function>
TEMP_SW
SETTING_SW
0
1
F
2
3
4
5
Thermostat mode
WIND Signal en/disable
Conventional AC Unit Thermostat
Disable
Enable
Heat Pump Thermostat_O
Terminal
Disable
Heat Pump Thermostat_B
Terminal
Disable
Enable
Enable
1) When interlocking with thermostat, set TEMP_SW to F.
2) Enable CN_WIND signal – Amount of wind flow(Low, Middle, High) signal enable
Notes
• Information of ‘SETTING_SW’ is sensed only initial step by Dry contact module therefore , once the
configuration changed , Reset of Dry contact module is required.
• After power input or unit’s reset , wait 25~30 sec(Display LED 10 times blinking) for unit stabilization
then Dry contact module will operate normally.
• Do not use desired temperature setting function when interlocking with thermostat.
Installation manual 15
ENGLISH
5. Installation of thermostat
Setting and using method
n Details of Installation for thermostat
1) In case of Occupancy sensor,
- When motion is detected by the sensor, Indoor unit is enabled.
- Otherwise, Indoor unit is disabled.
2) In case of Emergency Stop or Security option.
- When emergency condition occurs, Indoor unit is disabled.
- Otherwise, Indoor unit is enabled.
24 V~
H
N
C R
Security
Emergency Stop
Occupancy Sensor
CN_Ther/Oper
Reference Cases
CN_MODE
CN_WIND
CHANGEOVER_SW
CN_PI485
CN_INDOOR
RESET_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT
16 Dry contact for thermostat
Setting and using method
Thermostat
LG does not supply this section
(Field supply)
H
N
24 V~
ENGLISH
n For conventional thermostat signal input
H H H
HIGH
MIDDLE
LOW
COOL
FAN
HEAT
Operation
COMM
C R GW Y
CHANGE
OVER_SW
NOT
USE
CN_Ther/Oper
CN_MODE
VOLT
CN_WIND
CHANGEOVER_SW
SETTING_SW
CN_PI485
CN_INDOOR
NON
VOLT
RESET_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Thermostat Fan & System Switch
FAN
MODE
Operation
[Auto / On] [Cool / Heat / Off]
0
OFF
1
RT > SP
1
Cool
Auto
RT < SP
1
RT < SP
1
Heat
RT > SP
1
FAN
1
RT > SP
1
Cool
RT < SP
1
ON
RT < SP
1
Heat
RT > SP
1
Input
FAN
[G]
0
1
0
1
0
1
1
1
1
1
HEAT
[W]
0
0
0
1
0
0
0
0
1
0
COOL
[Y]
0
1
0
0
0
0
1
0
0
0
IDU Response
[Mode / Thermal / Fan]
Disable Operation
Enable
Cool / On / On
Enable
Heat/ On/On
Enable
Fan/ Off/ On
Cool/ On/ On
Fan/ Off/ On
Heat/ On/ On
Fan/ Off/ On
Notes
• IDU Fan logic, depending on model selected, may delay IDU fan operation momentarily during a cold
start heat call. This function allows IDU coil to warm up prior to operating fan in some IDU models.
• Thermostats that use resistive anticipation are not supported at this time.
• Verify documentation of desired thermostat so that the logic is same as shown in the table above.
Installation manual 17
Setting and using method
n For heat pump thermostat with O terminal signal input
Thermostat
LG does not supply this section
(Field supply)
H
N
24 V~
H H H
HIGH
MIDDLE
LOW
COOL
FAN
Operation
COMM
Thermal
C R Y G O
CHANGE
OVER_SW
NOT
USE
CN_Ther/Oper
CN_MODE
VOLT
CN_WIND
CHANGEOVER_SW
SETTING_SW
CN_PI485
CN_INDOOR
NON
VOLT
RESET_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Thermostat Fan & System Switch
FAN
[Auto / On]
-
Auto
ON
MODE
Operation
[Cool / Heat / Off]
0
OFF
1
RT > SP
1
Cool
RT < SP
1
RT < SP
1
Heat
RT > SP
1
FAN
1
RT > SP
1
Cool
RT < SP
1
RT < SP
1
Heat
RT > SP
1
Input
Thermal
[Y]
0
1
0
1
0
0
1
0
1
0
FAN
[G]
0
0
0
0
0
1
1
1
1
1
COOL
[O]
0
1
1
0
0
0
1
1
0
0
IDU Response
[Mode / Thermal / Fan]
Disable Operation
Enable
Cool / On / On
Enable
Heat/ On/On
Enable
Fan/ Off/ On
Cool/ On/ On
Fan/ Off/ On
Heat/ On/ On
Fan/ Off/ On
Notes
• Thermostats that close contacts "O" or "B" during Cool or Heat call only have not been verified. "O"
and/or "B" contact closure must be maintained during respective cycle / mode selection.
• IDU Fan logic, depending on model selected, may delay IDU fan operation momentarily during a cold
start heat call. This function allows IDU coil to warm up prior to operating fan in some IDU models.
• Thermostats that use resistive anticipation are not supported at this time.
• Verify documentation of desired thermostat so that the logic is same as shown in the table above.
18 Dry contact for thermostat
Setting and using method
Thermostat
LG does not supply this section
(Field supply)
H
N
24 V~
H H H
HIGH
MIDDLE
LOW
FAN
HEAT
Operation
COMM
Thermal
C R Y G B
CHANGE
OVER_SW
NOT
USE
CN_Ther/Oper
CN_MODE
VOLT
CN_WIND
CHANGEOVER_SW
SETTING_SW
CN_PI485
CN_INDOOR
NON
VOLT
RESET_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Thermostat Fan & System Switch
FAN
[Auto / On]
-
Auto
ON
MODE
Operation
[Cool / Heat / Off]
0
OFF
1
RT > SP
1
Cool
RT < SP
1
RT < SP
1
Heat
RT > SP
1
OFF
1
RT > SP
1
Cool
RT < SP
1
RT < SP
1
Heat
RT > SP
1
Input
Thermal
[Y]
0
1
0
1
0
0
1
0
1
0
FAN
[G]
0
0
0
0
0
1
1
1
1
1
HEAT
[B]
0
0
0
1
1
0
0
0
1
1
IDU Response
[Mode / Thermal / Fan]
Disable Operation
Enable
Cool / On / On
Enable
Heat/ On/On
Enable
Fan/ Off/ On
Cool/ On/ On
Fan/ Off/ On
Heat/ On/ On
Fan/ Off/ On
Notes
• Thermostats that close contacts "O" or "B" during Cool or Heat call only have not been verified. "O"
and/or "B" contact closure must be maintained during respective cycle / mode selection.
• IDU Fan logic, depending on model selected, may delay IDU fan operation momentarily during a cold
start heat call. This function allows IDU coil to warm up prior to operating fan in some IDU models.
• Thermostats that use resistive anticipation are not supported at this time.
• Verify documentation of desired thermostat so that the logic is same as shown in the table above.
Installation manual 19
ENGLISH
n For heat pump thermostat with B terminal signal input
Setting and using method
6. Indoor unit monitoring
n Monitoring whether the indoor unit is operating: Refer to
below and connect to the control device that you want to
control.
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
SETTING_SW
CN_PI485
CN_INDOOR
RESET_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Field Supply
Operation Display
Power
AC or DC
(Depends on Operation display power type)
n Monitoring indoor unit error: Refer to below and connect to
the control device that you want to control.
CN_Ther/Oper
CN_MODE
CN_WIND
CHANGEOVER_SW
CN_PI485
CN_INDOOR
RESET_SW
SETTING_SW
DISPLAY_LED
TEMP_SW
CN_OUT
Field Supply
Error Display
Power
AC or DC
(Depends on Error display power type)
Field supply power should not use more than DC 12 V(3A), 24 V~(3A)