LG | PQDSBC.ENCXLEU | LG PQDSBC.ENCXLEU Owner’s Manual

Visit us at : http://www.lgservice.com
LG
LG
Dry contact for communication
Owner's & installation manual
Models: PQDSBC
IMPORTANT
• Please read this manual completely before
installing the product.
• Installation work must be performed in
accordance with the national wiring standards
by authorized personnel only.
• Please retain this installation manual for future
reference after reading it thoroughly.
Dry contact for communication Owner’s &installation manual
TABLE OF CONTENTS
■ Safety Precautions .............................................................3~4
■ Name of each part ..................................................................5
■ Installation Method .............................................................6~7
Installation inside of the indoor unit..........................................................6
Installation outside of the indoor unit .......................................................7
■ Setting and using method ................................................8~18
1. Power supply and indoor unit connection............................................8
2. Setting of Contact Signal Input ............................................................9
3. Setting the desired temperature ........................................................10
4. Control mode setting..........................................................................11
5. Indoor unit monitoring ........................................................................15
2 Dry contact for communication
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions
must be followed.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage.
■ Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
■ During installation
Do not touch the board
when the power is
connected.
• It can cause a fire, electric
shock, explosion, injury and
problem to the product.
Always request for
installation of the product
to the service center or
the installation service
provider.
• It can cause a fire, electric
shock, explosion and injury.
When reinstalling the
previously installed product,
request for service to the
service center or the
installation service provider.
• It can cause a fire, electric
shock, explosion and injury.
ter
Service center
c
rvi
Se
Do not install the product where it can
be exposed to rain.
• It can cause problems to the product.
en
ec
Do not install the product in a humid
location.
• It can cause problems to the product.
Owner’s & installation manual 3
Safety Precautions
■ During use
Do not modify or extend the
power cord.
• It can cause a fire and
electric shock.
Do not pour water inside the
product.
• It can cause an electric
shock and problem to the
product.
Do not use any flaming
devices near the product.
• It can cause a fire.
When the product is
submersed in water, always
request for service to the
service center or the
installation service provider.
• It can cause a fire and
electric shock.
ter
e
rvic
Se
Do not give impact to the
product.
• It can cause problems to the
product.
4 Dry contact for communication
cen
Do not use any heating
devices near the power cord.
• It can cause a fire and
electric shock.
Make the children and the
elderly use the product with
the help of a guardian.
• It can cause a safety
accident and problems to the
product.
Name of each part
Name of each part
(Front case)
(Rear case)
9
8
7
CHANGE
OVER_SW
CN_OUT
NOT
USB
VOLT
NON
VOLT
3
e
6
5
TEMP
SETTING
11
1
(Top)
10
2
4
(Internal PCB board)
(Side)
(Side)
DRY CONTACT FOR COMMUNICATION (DRY_CONTACT FOR COMMUNICATION)
1. CN_INDOOR
: Connect communication wire between indoor unit and Dry contact for communication
and supply power to Dry contact for communication
2. CN_PI485
: PI485 connector
3. CHANGE_OVER_SW : Switch to select voltage (5V-12V) of contact point
4. CN_CONTROL
: Contact point signal input
5. CONTROL_MODE_SW : Switch to select the control mode
6. SETTING_SW
: Switch to select whether to use set function of Dry contact for communication
7. TEMP_SETTING
: Switch to set the desired temperature of the indoor unit
8. CN_OUT (O1, O2)
: Connector to show whether the indoor unit is operating
9. CN_OUT (E3, E4)
: Connector to show whether there is an error with the indoor unit
10. DISPLAY_LED
: LED to display the status of the Dry contact for communication
11. RESET_SW
: Reset switch
Owner’s & installation manual 5
Installation Method
Installation Method
Installation inside of the indoor unit
Loose 4 screws anchoring PCB and then separate the rear case and PCB
Connect the connection wires according to the instructions. (Please refer to Setting and Using
Method)
Perform the switch setting according to switch setting method. (Please refer to Setting and Using
Method)
Fix PCB on suitable space inside of the indoor unit.
1. Install the product on flat surface and install anchoring screws at more than 2 places. Otherwise
the central controller may not be anchored properly.
2. Do not tighten anchoring screws too tightly. It may cause deformation of the case.
3. Do not deform the case at random. It may cause malfunction of the central controller.
6 Dry contact for communication
Installation Method
Installation outside of the indoor unit
Anchor the rear case of Dry Contact for
communication on the installation surface at
holes using anchor screws.
Please cut the pole which is located in side of the front case properly.
Connect connection wires according to the
instructions.
(Reference to Setting and Using Method)
Then, connect wire to PCB after going
through hole of .
Perform the switch setting according to switch setting method. (Reference to Setting and Using Method)
Join the front case and the rear case, anchor
the front case at holes using anchor screws.
DRY C
ONTA
CT UN
IT
1. Install the product on flat surface and install anchoring screws at more than 2 places. Otherwise
the central controller may not be anchored properly.
2. Do not tighten anchoring screws too tightly. It may cause deformation of the case.
3. Do not deform the case at random. It may cause malfunction of the central controller.
Owner’s & installation manual 7
Setting and using method
Setting and using method
You must press the RESET switch when you are completed with all the settings to reflect the
settings.
1. Power supply and indoor unit connection
■ When using the Dry contact for communication independently
Indoor unit
PCB
CN_INDOOR
■ When using with the central controller (Only when the indoor
unit PCB is a non-communication model)
Indoor unit
PCB
CN_INDOOR
CN_PI485
PI485: Connect to central controller
8 Dry contact for communication
Setting and using method
2. Setting of Contact Signal Input
■ For no power contact point signal input
LG does not
supply this section
(Local supply)
■ For power contact point signal input
LG does not
supply this section
(Local supply)
Owner’s & installation manual 9
Setting and using method
3. Setting the desired temperature
■ When setting the desired temperature of the Dry contact for
communication
: When operating the indoor unit, set the desired temperature according to the TEMP_SW setting.
SETTING_SW
When the indoor unit is unlocked, the desired temperature can be reset by other controller
1) Turn on the TEMP_SETTING switch of SETTING_SW.
2) Use the TEMP_SW to set the temperature as shown below.
Desired temperature setting table
TEMP SW
0
setting
1
2
3
4
5
6
7
Temperature
setting(°C) 18
19
20
21
22
23
24
25
TEMP SW
8
setting
9
A
B
C
D
E
F
Temperature
setting(°C) 26
27
28
29
30
30
30
30
1) Turn off the TEMP_SETTING switch of SETTING_SW.
SETTING_SW
■ When not using the desired temperature setting of Dry
contact for communication
➲ When operating the indoor unit initially in Dry contact for communication, set the desired
temperature to 18°C.
10 Dry contact for communication
Setting and using method
4. Control mode setting
■ Use the CONTROL_MODE_SW to set the control mode you
want from 0~D.
CONTROL_MODE_SW
➲ Indoor control priority
Central control > Dry contact for communication > Wired/Wireless remote controller, indoor unit
button
➲ Dry contact for communication controls the indoor unit according to the applicable mode when there
is a change in input of A and B.
■ Description of each control mode
1) Cancel mode for use of dry contact for communication
CONTROL_
MODE S/W
0
Input A
Input B
Operating mode
OFF
OFF
ON
OFF
The indoor unit cannot be controlled through the
Dry contact for communication
OFF
ON
No change in indoor unit condition
ON
ON
➲ Set this when the Dry contact for communication is connected but not used.
Owner’s & installation manual 11
Setting and using method
2) General mode
CONTROL_
MODE S/W
1
2
3
4
5
6
Input A
Input B
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit prior operating condition maintained, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit operating, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit stopped, locked
OFF
ON
Indoor unit prior operating condition maintained, unlocked
ON
ON
Indoor unit operating, unlocked
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit stopped, locked
OFF
ON
Indoor unit prior operating condition maintained, unlocked
ON
ON
Indoor unit prior operating condition maintained, unlocked
OFF
OFF
Indoor unit prior operating condition maintained, locked
ON
OFF
Indoor unit prior operating condition maintained, locked
OFF
ON
Indoor unit prior operating condition maintained, locked
ON
ON
Indoor unit prior operating condition maintained, unlocked
OFF
OFF
Indoor unit prior operating condition maintained, locked
ON
OFF
Indoor unit prior operating condition maintained, locked
OFF
ON
Indoor unit prior operating condition maintained, locked
ON
ON
Indoor unit operating, unlocked
12 Dry contact for communication
Operating mode
Setting and using method
3) Fan level setting mode
CONTROL_
MODE S/W
Input A
Input B
OFF
OFF
Indoor unit operating at low level, locked
ON
OFF
Indoor unit operating at low level, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
OFF
OFF
Indoor unit operating at low level, locked
ON
OFF
Indoor unit operating at low level, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit prior operating condition maintained, unlocked
7
8
Operating mode
➲ When the indoor unit is operating in Dry contact for communication, the fan level can be changed by
other controller when the fan level is set to low level and the indoor is in unlocked condition.
4) Power save mode
CONTROL_
MODE S/W
9
A
Input A
Input B
Operating mode
OFF
OFF
Indoor unit operating in power save mode, locked
ON
OFF
Indoor unit operating in power save mode, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit operating not in power save mode, unlocked
OFF
OFF
Indoor unit operating in power save mode, locked
ON
OFF
Indoor unit operating in power save mode, unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
➲ When setting 9, A mode, the TEMP_SETTING must always be set to ON.
➲ Power save mode: Adjust the set temperature to +3°C for cooling and -3°C for heating.
Owner’s & installation manual 13
Setting and using method
5) Compressor stop mode
CONTROL_
MODE S/W
Input A
Input B
OFF
OFF
Indoor unit operating (Compressor in stop mode), locked
ON
OFF
Indoor unit prior operating condition maintained
(Compressor not in stop mode), unlocked
OFF
ON
Indoor unit stopped, locked
ON
ON
Indoor unit stopped, locked
B
Operating mode
➲ Compressor stop mode: The compressor is stopped during cool/heat operation.
6) Operating mode selection mode
CONTROL_
MODE S/W
C
D
Input A
Input B
Operating mode
OFF
OFF
Indoor unit stopped, unlocked
ON
OFF
Indoor unit in cool/high operation, unlocked
OFF
ON
Indoor unit in heat/high operation, unlocked
ON
ON
Indoor unit in fan/high operation, unlocked
OFF
OFF
Indoor unit stopped, locked
ON
OFF
Indoor unit in cool/high operation, locked
OFF
ON
Indoor unit in heat/high operation, locked
ON
ON
Indoor unit in fan/high operation, locked
➲ Power save mode: Adjust the set temperature to +3°C for cooling and -3°C for heating.
14 Dry contact for communication
Setting and using method
5. Indoor unit monitoring
■ Monitoring whether the indoor unit is operating: Refer to
below and connect to the control device that you want to
control.
Local Supply
Power
AC or DC
Operation Display
(Depends on Operation
display power type)
■ Monitoring indoor unit error: Refer to below and connect to
the control device that you want to control.
Local Supply
Error Display
Power
AC or DC
(Depends on Error
display power type)
Owner’s & installation manual 15
P/No.: MFL42540202
Printed in Korea