Installation/Owner's Manual
Caution
• Read this manual thoroughly before installing the product.
• Only the certified professional should install this product.
• Keep this manual for referring during the operation later.
Advanced Control Platform
Contents
1. ACP FUNCTIONS & SPECIFICATION .............1-1
Functions of ACP ............................................................................................................1-1
Denomination of ACP .....................................................................................................1-4
Components of ACP .......................................................................................................1-6
Hardware specification of ACP......................................................................................1-7
2. INSTALLING ACP .............................................2-1
Before installing the ACP ...............................................................................................2-2
• Using the single ACP as web server ........................................................................2-3
• Connecting the single ACP to the AC Manager ......................................................2-5
• Connecting more than on ACPs to the AC Manager ..............................................2-7
Setting the indoor unit address .....................................................................................2-8
• Setting the address by the wired remote controller ...............................................2-9
• Setting the address by the wireless remote controller.........................................2-10
Setting the PI485 and Connecting the cable .............................................................2-12
• Setting the PI485 DIP switch ...................................................................................2-12
• Connecting the 2PIN connector..............................................................................2-14
• Connceting RS485 cable to PI485...........................................................................2-16
Installing the ACP and Connecting the cable.............................................................2-19
• Fixing the ACP at the installation site ....................................................................2-19
• Connecting RS485 cable to ACP ............................................................................2-20
• Connecting Ethernet cable to ACP.........................................................................2-23
• Connecting Power adaptor to ACP.........................................................................2-24
Configuring the ACP network ......................................................................................2-25
• Before configuring the ACP environment..............................................................2-25
• Setting the IP address..............................................................................................2-29
• Setting the gateway address...................................................................................2-30
• Setting the net mask address .................................................................................2-31
• Checking the network environment .......................................................................2-32
2
ACP
Setting the functions of the ACP .................................................................................2-33
• Before setting the functions of the ACP ................................................................2-33
• Selecting Peak or Demand ......................................................................................2-34
• Selecting the ACCS display language....................................................................2-36
• Setting whether to use the schedule function or not ...........................................2-38
• Setting whether to use the wattage display function or not ................................2-40
• Setting error history display ..................................................................................2-42
Configuring the ACCS access .....................................................................................2-43
• Chceking the MS JAVA VM installation .................................................................2-43
• Checking the MS Explorer security setting ...........................................................2-45
Entering the indoor unit & ventilator information......................................................2-49
• If the ACP is connected to the AC Manager ..........................................................2-49
• If the ACP is not connected to the AC Manager....................................................2-50
Making sure and checking the ACP installation ........................................................2-67
3. ACP OPERATION BY USING THE LG ACCS .............3-1
Accessing the ACCS.......................................................................................................3-1
Reviewing the initial ACCS screen................................................................................3-4
Controlling the air conditioner.......................................................................................3-7
Controlling the ventilator .............................................................................................3-14
Setting the schedule .....................................................................................................3-21
• Reviewing the schedule setup screen ...................................................................3-21
• Example for setting the schedule ...........................................................................3-32
Controlling the peak operation rate ............................................................................3-44
Controlling the demand electric power.......................................................................3-51
Monitoring the air conditioner status..........................................................................3-56
Reviewing the error history..........................................................................................3-58
Reviewing the power consumption (interconnecting with the power display).......3-61
Setting the system ........................................................................................................3-66
4. REFERENCE ....................................................4-1
Troubleshooting..............................................................................................................4-1
Guide for the open source software..............................................................................4-2
UTP cable connection chart...........................................................................................4-3
Installation/Owner's Manual
3
Note for safety
Note for safety
In order to prevent the user's injury or the damage of the product, keep the followings to use the
product.
■ The service center or the professional installation agency cettified by our company should
perform the installation because the professional technique is required to install.
■ The installer should be responsible for all problems related the installation occurred by the
installation work without the installation certification, for which our company does not offer the
free-of-charge service.
■ Using the product ignoring the note for safety may cause the misoperation of the product,
which may cause the body's injury or the damage of the product. The note for safety is
classified into two following items:
WARNING
For causing the critical injury to the body.
CAUTION
For the body's injury or the damage of the product.
■ The symbols used at this manual have the following meanings:
It should not be followed.
It should be carefully kept to perform.
4
ACP
Note for safety
WARNING
■ When installing
Any question about the
product should be asked to
the service center or the
professional installation
agency.
Consult the service center
or the professional
installation agency about
reinstalling the installed
product.
The standardized part.
• The non-professional may
cause accident, electric
shock, explosion or injury.
• The non-professional may
cause accident, electric
shock, explosion or injury.
• The non-standard part
may cause electric shock,
explosion, injury or failure.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
4
LG-NET 4
5
FDD
9
10
11
12
13
14
15
16
17
18
19
20
TX
RX
TX
RX
TX
RX
TX
RX
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
TX
RX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
1
MENU/
SELECT
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
TX
RX
1
2
TX
RX
TX
RX
DO
2
DO
Run
3
Power
4
TX
RX
Run
3
Power
4
1
2
DO
Run
3
4
Power
Consult the service center
or the professional
installation agency about
reinstalling the installed
product
The flammable gas or the
combustible substance
such as gasoline, benzene
and thinner should not be
used near the power cord.
Do not disassemble, repair
or modify the product at
random.
• The non-professional may
cause electric shock,
explosion or injury.
• It may cause explosion or
fire.
• It may cause electric
shock or fire.
LG-NET 1
LG-NET 2
1
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
2
TX
RX
TX
RX
TX
RX
TX
RX
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
ACT
LNK
Ethernet 2
ACT
LNK
LG-NET 3
LG-NET 4
5
7
8
9
10
11
12
13
14
15
16
17
18
19
20
TX
RX
TX
RX
Ethernet 1
DI
3
4
FDD
Ext.
Ethernet 1
MENU/
SELECT
Ethernet 2
Console
Console
TX
RX
TX
RX
TX
RX
TX
RX
6
6
TX
RX
TX
RX
ACT
LNK
ACT
LNK
TX
RX
LG-NET 1
TX
RX
LG-NET 2
1
1
2
DO
Run
3
4
2
DI
LG-NET 3
3
4
Power
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
1
2
DO
7
Run
8
3
4
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Power
x
Wa Thinner
Ext.
MENU/
SELECT
ACT
LNK
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
Ethernet 2
TX
RX
Run
3
4
Power
Installation/Owner's Manual
5
Note for safety
Do not install the product at the wet place.
• It may cause to degrade the insulating ability and may cause fire.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
MENU/
SELECT
TX
RX
Run
3
Power
4
■ When using
Do not change or extend the
power cord.
Do not place any heating
device near the product.
Do not use any heating
device near the power cord.
• It may cause fire or
electric shock.
• It may cause fire.
• It may cause fire or
electric shock.
LG-NET 1
LG-NET 2
1
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
2
DI
LG-NET 3
3
4
LG-NET 4
5
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
Console
TX
RX
TX
RX
TX
RX
TX
RX
6
TX
RX
TX
RX
1
2
DO
Run
3
4
1
2
DO
Power
Run
3
4
Power
Do not let water flow into the
product.
Do not put heavy weight on
the power cord.
Do not put heavy weight on
the product.
• It may cause electric
shock and failure.
• It may cause fire or
electric shock.
• It may cause the failure of
the product.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
LG-NET 1
Console
TX
RX
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
Console
7
TX
RX
1
2
8
DO
Run
3
4
1
2
DO
Run
3
4
Power
Power
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
Ethernet 1
MENU/
SELECT
Ethernet 2
Console
1
2
DO
Run
3
4
6
ACP
Power
TX
RX
TX
RX
ACT
LNK
ACT
LNK
TX
RX
Note for safety
If the product is flooded,
consult the service centre or
the professional installation
agency.
Let the children or the old
and the weak be controlled
by the guardian to use.
Do not give any shock to the
product.
• It may cause fire or
electric shock.
• It may cause accident or
failure.
• Any shock to the product
may cause failure.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
ACT
LNK
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
Ethernet 2
TX
RX
Run
3
4
Power
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
7
8
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
Ethernet 1
MENU/
SELECT
Ethernet 2
Console
Console
TX
RX
1
2
DO
TX
RX
TX
RX
ACT
LNK
ACT
LNK
TX
RX
Run
3
4
1
2
DO
Power
Run
3
Power
4
CAUTION
■ When using
Do not use strong detergent such as
solvent, but a soft cloth.
Grab the head of the plug of the power cord
to pull when disconnecting the plug, and do
not touch the plug with wet hands.
• It may cause fire or to deform the product.
• It may cause fire or electric shock.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
TX
RX
Run
3
x
Wa Thinner
4
Power
Installation/Owner's Manual
7
1. ACP Functions & Specification
1. ACP Functions & Specification
The ACP(Advanced Control Platform) is the central controller which can control up to 256 indoor units
of the airconditioner at one place individually or totally. The ACP can monitor or control to operate the
airconditioner and the ventilator installed at each room of the building from the place such as the
control room of a building, the administrative room of a school.
Functions of ACP
Main functions of the ACP are as follows:
Using the external button of the ACP to set the environment
The following functions can be set by using the external buttons of the ACP.
• Set the network environment (IP address, net mask, gateway)
• Set one of Peak/Demand function to use
• Set the language displayed on the LG ACCS screen
• Set whether to use the schedule feature or not
• Set whether to use the watthour meter feature or not.
1-1
ACP
1. ACP Functions & Specification
Built-in Web server
Various functions of contents can be used when the IP address of the ACP is entered at the address
window by using the Internet Explorer without installing a separate PC program to automatically
execute the central control program at the ACP web server.
Also, the demand control feature to control the demand power is controlled by directly connecting the
ACP to the demand controller without installing a separate PC program.
LG-NET 1
LG-NET 2
1
DI
2
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
Internet
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
ACT
LNK
Ethernet 2
ACT
LNK
Console
Internet
Explorer
1
DO
2
TX
RX
TX
RX
Ethernet 1
TX
RX
Run
3
Power
4
ACP
➲ Control 256 indoor units of the airconditioner at
maximum
➲ Monitoring the error and operation state
➲ Controlling the peak/demand electric power
➲ Setting the system
Interconnecting with the AC Manager
Various features offered by the AC Manager are offered by connecting the AC Manager program
installed at the PC to the ACP. Especially, when using the schedule feature of the AC Manager,
because the ACP has its own engine, even though the user turns off the PC where the AC Manager is
installed, the ACP can perform the schedule featre by itself.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
HUB
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
TX
RX
Run
3
Power
4
AC Manager
ACP
Installation/Owner's Manual
1-2
1. ACP Functions & Specification
Interconnecting with the simple central controller
The 16-room simple central controller can be interconnected with the ACP. When the ACP centrally
controlling all airconditioners and the simple central controller at each floor of the building are used
together, the airconditioner can be controlled more easily.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
Multi V
TX
RX
TX
RX
TX
RX
TX
RX
00
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
DO
TX
RX
Run
Power
ACP
L1 2 3 4
3
4
ACP
(0.1)
(0.F)
Central control (0.0)
address
(0.1)
(0.F)
Multi V
L1 2 3 4
1-3
Central control (0.0)
address
PI485
ON KSDO4H
Simple central controller
ON KSDO4H
2
TX
RX
TX
RX
PI485
1. ACP Functions & Specification
Denomination of ACP
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
1
4
5
6
LG-NET 4
7
8
10
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
1
11
2
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
2
TX
RX
TX
RX
TX
RX
TX
RX
3
4
5
6
TX
RX
7
DO
Run
3
8
Power
4
9
1 Buttons and LCD
Buttons and the LCD to display the network environment setting and other information
2 RS485 communication port (for PI485 connection)
RS485 communication port connecting to the PI485 to connect the airconditioner and the
ventilator (4EA in total)
3 RS485 communication port (for external extension)
RS485 communication port spar for exter extension (2EA in total)
4 Ethernet port (for connecting the Internet and the AC Manager)
The Ethernet port for connecting the Internet and the AC Manager
5 Ethernet port (spare)
Ethernet port spare for the function extension of the ACP
6 RS232 port
RS232 port for updating the software of the ACP
Installation/Owner's Manual
1-4
1. ACP Functions & Specification
7 Reset switch
Switch for resetting the ACP by the software
8 Power switch
Switch for turning on/off the ACP
9 Adaptor connection port
Port for DC 12V to connect the adaptor supplying the power
10 External input signal terminal
Port for connecting the external input signal (20EA in total). Input terminal not requiring the
power.
11 External output signal terminal
Connection port spare for the function extension of the ACP (4EA in total)
Note: External input/output signal terminal
9 external input signal terminal and 10 external output signal terminal are configured at the
PQCPB11A0E only. These terminals are used to connect the AC Manager to set the fire control
function. These terminal are used to set the indoor unit to operate or stop for responding High or Low
signal of each external input signal.
In case of PQCPA11A0E model, a separate IO Kit (Model: PQCPE11A0E) can be purchased and
installed to use for connecting the external signal.
1-5
ACP
1. ACP Functions & Specification
Components of ACP
The following components are contained within the packaging box of the ACP. Open the packaging
box of the ACP to make sure that all components are contained.
237mm
180mm
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
Ext.
MENU/
SELECT
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
273mm
250mm
9
10
11
12
13
14
15
16
17
18
19
20
LG
TX
RX
Run
3
4
Power
57mm
ACP
(Advanced Control Platform)
ACP
Installation/Owner's Manual
Adaptor for Power supply
Power Cord
Input: 100~240V
AC 50/60Hz 1.5A
Output: DC 12V
3.33A, 40W MAX
International Standard
IEC320 C14 Type
Caution: Using the standardized part
We are not responsible for any problem caused by using the adaptor other than the
standardized one offered by us, so using any non-standard part should be prohibited.
You can consult the LG System Air Conditioner Support Division about the applicable
product.
Notice : In Australia, purchase the power code
In Australia, the power code from local area.
The power code is not included in the package
Installation/Owner's Manual
1-6
1. ACP Functions & Specification
Hardware Specification of ACP
Item
CPU
PXA255-400MHz Xscale
RAM
128MB (32x4) SDRAM
ROM
• 512KB NOR Flash – Boot image
• 128MB (64x2) NAND Flash – Program image, Database, others
RS-232 Console
Communication port
LED
LCD
Description
For updating the program (for developing)
• RS485 port: PI485 communication port 4EA, External device
connection port 2EA
• RS-232 communication port: Port for updating the program 1EA
• Ethernet port: for Internet connectioin 1EA (10Base-T) Spare 1EA
For the PQCPB11A0E model, the following ports are supplied as default.
• External input port: 20EA (Pulse contable, DC 12V)
• External output port: 4EA (Relay output, 5V)
For the PQCPA11A0E model, the IO Kit (PQCPE11A0E) should be
separately purchased for connecting the above port
20EA (for displaying RS communication status, Ethernet communication
status, RS232 communication status, Power operation status)
16x2 Character, displaying Network environment setting and information
Note: License policy
This product follows the GPL(General Public License) for using the embedded Linux.
1-7
ACP
2. Installing ACP
2. Installing ACP
This chapter describes how to install the ACP to use.
Caution: Installing the ACP
The ACP installation work needs the professional technique. Therefore, the
installation described at this chapter should be performed by the certified
installation professional.
Consult the service center or the professional installation agency certified by us about
any question or request related to the installation.
In order to use the ACP, the environment for the ACP, the indoor unit and the ventilator to
communicate should be built and the indoor unit should be registered.
In order to use the ACP, the installation should be performed by the following order.
STEP 1. Check the environment before installing the ACP
Before installing the ACP, check the network configuration according to the
interconnection between the ACP and the external device.
STEP 2. Set the indoor unit address and Connecting the PI485
Set the address of the ACP not overlapped with the connecting indoor unit and connect
the PI485.
STEP 3. Install the ACP and set the environment and the function
Install the ACP and set the network environment and the function.
STEP 4. ACCS access and Information input
Set the access environment at the LG ACCS, the ACP operation program and enter the
air conditioner information.
STEP 5. Make sure and check the ACP installation
Make sure and check that the ACP is normally installed.
Installation/Owner's Manual
2-1
2. Installing ACP
Before installing the ACP
ACP provides 4 RS485 ports to connect the indoor unit. Maximum of 16 units can be connected to
PI485 for outdoor unit in 1 RS385 port, and maximum of 31 units for SINGLE/Ventilator PI485.
256 indoor units at maximum can be connected to one ACP. All of 256 indoor units may be connected
to one RS485 port, which is the maximum number of units for the ACP to connect. But, in order to
improve the communication performce of the RS485, we recommend to distribute them to four ports.
Note: Change the number of connections of RS485
If it is inevitable to change the above specification, call the system air conditioner support division
By considering three following cases using the ACP, perform the installation after carefully considering
how to use.
• Install the single ACP to use as web server
• Connect the single ACP to the AC Manager to use
• Connect more than one ACP to the AC Manager via the hub to use
2-2
ACP
2. Installing ACP
Using the single ACP as web server
When one ACP is used as web server, the ACP should be connected with the network structure as
shown at the following examples.
Using the hub
If it is connected via the hub, the network can be configured as shown at the following example.
LAN
(Direct Cable)
Hub
Multi V
00
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
01
02
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
TX
RX
L1 2 3 4
2
DO
ON KSDO4H
1
Run
3
Power
4
PI485
Multi V
ACP
10
11
12
L1 2 3 4
ON KSDO4H
PI485
Multi V
20
21
22
L1 2 3 4
ON KSDO4H
PI485
30
31
Multi
32
33
L1 2 3 4
ON KSDO4H
Simple central controller
(possible to connect
when necessary)
PI485
Installation/Owner's Manual
2-3
2. Installing ACP
Not using the hub
If it is connected without the hub, the network can be configured as shown at the following example.
Multi V
00
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
ACT
LNK
ACT
LNK
TX
RX
L1 2 3 4
DO
ON KSDO4H
1
2
02
TX
RX
TX
RX
Ethernet 1
Ethernet 2
Console
01
TX
RX
TX
RX
TX
RX
TX
RX
Run
3
Power
4
PI485
Multi V
ACP
10
11
12
L1 2 3 4
ON KSDO4H
PI485
Multi V
20
21
22
L1 2 3 4
ON KSDO4H
PI485
30
31
Multi
32
33
L1 2 3 4
2-4
ACP
ON KSDO4H
Simple central controller
(possible to connect
when necessary)
PI485
2. Installing ACP
Connecting the single ACP to the AC Manager
When one ACP is connected to the AC Manager without the hub, the ACP should be
connected with the network structure as shown at the following examples.
Using the hub
If it is connected via the hub, the network can be configured as shown at the following example.
AC Manager
Hub
LAN
(Direct Cable)
Multi V
00
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
01
02
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
TX
RX
L1 2 3 4
DO
ON KSDO4H
1
2
Run
3
Power
4
PI485
Multi V
ACP
11
10
12
L1 2 3 4
ON KSDO4H
PI485
Multi V
20
21
22
L1 2 3 4
ON KSDO4H
PI485
30
31
Multi
32
33
L1 2 3 4
ON KSDO4H
Simple central controller
(possible to connect
when necessary)
PI485
Installation/Owner's Manual
2-5
2. Installing ACP
Not using the hub
If it is connected without the hub, the network can be configured as shown at the following example.
AC Manager
LAN
Cross cable
Multi V
00
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
01
02
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
TX
RX
L1 2 3 4
2
DO
ON KSDO4H
1
Run
3
Power
4
ACP
PI485
Multi V
11
10
12
L1 2 3 4
ON KSDO4H
PI485
Multi V
20
21
22
L1 2 3 4
ON KSDO4H
PI485
30
31
Multi
32
33
L1 2 3 4
2-6
ACP
ON KSDO4H
Simple central controller
(possible to connect
when necessary)
PI485
2. Installing ACP
Connecting more than on ACPs to the AC Manager
When more than one ACP are connected to the AC Manager via the hub, the ACP should be
connected with the network structure as shown at the following examples.
LAN
Direct cable
Hub
AC Manager
Multi V
ACP
L1 2 3 4
01
02
10
11
12
20
21
22
30
31
32
ON KSDO4H
00
PI485
Multi V
L1 2 3 4
ON KSDO4H
PI485
Simple central controller
(possible to connect
when necessary)
Multi V
L1 2 3 4
ON KSDO4H
PI485
ACP
Multi
L1 2 3 4
ON KSDO4H
Simple central controller PI485
(possible to connect
when necessary)
Installation/Owner's Manual
2-7
2. Installing ACP
Setting the indoor unit address
By considering the entire installation configuration connecting to one ACP, set the address to each
indoor unit not to be overlapped. 00~FF in hexadecimal can be set to the indoor unit address.
The following example sets the address to the indoor unit.
Multi V
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
1
2
DO
TX
RX
TX
RX
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
L1 2 3 4
FDD
02
ON KSDO4H
7
01
TX
RX
TX
RX
TX
RX
TX
RX
6
8
00
PI485
Multi
TX
RX
10
Run
11
12
3
Power
4
ACP
L1 2 3 4
ON KSDO4H
Ventilator
30
L1 2 3 4
ON KSDO4H
PI485
Ventilator
31
L1 2 3 4
ON KSDO4H
PI485
When the ACP is interconnected with the AC Manager, the ventilator can be together installed and
controlled. The above figure shows the example that sets 30 and 31 to the ventilators as address and
connects to the ACP.
Caution: Connecting the ventilator to the RS485
The ventilator and the air conditioner can not be connected together to the same
RS485 communication cable. When connecting the ventilator to the RS485
communication cable, the cable other than the RS485 communication cable
connecting the air conditioner should be used.
The next section describes how to set the address to each indoor unit by using the wired or wireless
remote controller according to the given number.
2-8
ACP
2. Installing ACP
Setting address with wired remote controller
AUTO SWING
OPERATION
SET TEMP
Room Temp
Operation unit
Program
03
Timer
Cancel
Program
Week
SUB FUNCTION
AUTO Heater
Defrost
JET
Filter
ZONE
1 2
HI
MED
LO
Time
Timer
On Off
Set no. Time 01
FAN SPEED
Preheat
Humidify
Out door
3 4
Program set
05
07
09
11
13
15
17
19
21
23
Holiday
Plasma
Set/Clr
Hour
Min
RESET
Set/Ctl
1. Press Week Program & Set/Clr keys at the same time.
2. Set the indoor unit address using the temperature controller.
Allowed Range : 00-FF
EX)
3
A
Group No. Indoor Unit No.
3. Complete the address setting to press the week Program & Set/Clr keys at the same time for 3
seconds.
❈ Some remote controllers may not be suported by above functions, a coording to the production date
of wired/wireless remote conrollers. As it has no concem with customers' use, use the remote
controller available for the address setting during installation.
Installation/Owner's Manual
2-9
2. Installing ACP
Setting address with wireless remote controller
You can set the address of the indoor unit through the
wireless remote controller that controls the indoor
unit. To set the address of the indoor unit with the
wireless remote controller, proceed as follows.
1. With the [Power Cool] button pressed, press the
[RESET] button. The [Power Cool] button must be
pressed for more than 3 seconds.
2. Use the [Temperature Adjustment] button to set the
address of the indoor unit.
Temperature
adjustment
ON
OFF
SET
CANCEL
Group No.
Indoor unit No.
PLASMA
3. After setting the address, press the [Operate/Stop]
button once toward the indoor unit.
4. When the set address is displayed on the indoor
unit, the address setting is complete.
Reference: Address display time and method
The address display time and method may differ
by the type of the indoor unit.
5. When you reset the remote controller, it switches
from the address setting mode to general operation
mode.
Reference: Type of remote controller
When using a different type of remote controller
from the one described above, refer to the user
manual of the applicable remote controller.
2-10
ACP
2. Installing ACP
Information: Checking the set address
You can check the set address by using the
wireless remote controller. To check the set
address, proceed as follows.
1. With the [Wind Up/Down] button pressed,
press the [RESET] button. The [Wind
Up/Down] button must be pressed for more
than 3 seconds.
2. Press the [Operate/Stop] button once toward
ON
OFF
SET
CANCEL
the indoor unit. The set address will be shown
on the display part of the indoor unit. The
address display time and method can differ by
the type of indoor unit.
PLASMA
3. Reset the remote controller again to use it in
general operation mode.
Installation/Owner's Manual
2-11
2. Installing ACP
Setting the PI485 and Connecting the cable
After setting the address of the indoor unit, install the PI485 and set the DIP switch. And then, connect
the RS485 cable for communicating with the ACP.
Note: Installing the PI485
Installing the PI485 deponds on the outdoor unit. So, install the PI485 by referring to the PI485
manual or the installation technique information.
Setting the PI485 DIP switch
After installing the PI485 suitable to the product, the DIP switch should be set. The DIP switch of the
PI485 can be checked at the following place.
ON KS D O4H
L1 2 3 4
ON KSDO4H
Dip switch
Setting
ON KS D O4H
1, 4 ON
2, 3 OFF
ON KS D O4H
2, 4 ON
1, 3 OFF
Product type
- Multi V product(CRUN, LRA product excluded)
- MPS product with the common PCB applied
- MPS inverter product
- MPS product with the common PCB not applied
ON KS D O4H
1, 2, 3, 4 ON
ON KS D O4H
3, 4 ON
2-12
ACP
- Multi V CRUN, LRA product
- Single indoor unit (connected to the PI485 for the
indoor unit)
- Ventilator (connected to the PI485 for ventilating)
2. Installing ACP
Note: PCB part number
The MPS product with the common PCB applied has the following PCB part number:
• PCB P/NO. : 6871A20910A ~ Z
• PCB P/NO. : 6871A20917A ~ Z
• PCB P/NO. : 6871A20918A ~ Z
Caution: Setting the PI485 DIP switch
If the air conditioner selection switch is incorrectly set, the air conditioner may
incorrectly operate.
For more information about installing the PI485, see the PI485(M) manual.
Tip: Checking the PI485 DIP switch setting
It can be checked whether the indoor unit address and the DIP switch of the PI485 are correctly set
as follows:
• The LED01G blinks as many as the number of the connected indoor units.
• The LED02G and the LED03G continue to blink alternately. (When the LRA/CRUN is
connected, the LED02G may blink more than the LED03G.)
LED03G
L1 2 3 4
ON KSDO4H
ON KS D O4H
LED02G
LED01G
If the LED is abnormally different from the above description, check again the indoor unit address
setting and the DIP switch setting.
Installation/Owner's Manual
2-13
2. Installing ACP
Connecting the 2PIN connector
If you want to use the individual lock function for setting mode, wind flow, and temperature lock by the
central control, the 2PIN connector should be connected to the CN_DRY terminal of the PI485
according to the product type.
L1 2 3 4
ACP
ON KSDO4H
2-14
2. Installing ACP
The following figure shows the example of the central control for connecting the 2PIN connector to the
CN_DRY terminal.
1) 'Heating operation, 20°C , Strong wind, Temperature lock' function is ordered by the central control
such as ACP or AC Manager, which is transferred to the remote controller.
2) If the user changes the temperature to 25°C by the remote controller, the related command is
transferred to the outdoor unit and the remote controller displays the 25°C setting.
3) The outdoor unit receives the related command and transferrs it to the PI485.
4) The PI485 cancels this command and transferrs the previous central control command again. And, the
remote controller displays again the 20°C temperature transferred by the central control command.
Multi V
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
Ethernet 1
MENU/
Ethernet 2
SELECT
Console
TX
RX
TX
RX
ACT
LNK
ACT
LNK
TX
RX
L1 2 3 4
ON KSDO4H
1
2
DO
Run
3
Power
4
ACP
1) Set ‘Heating, 20°C, Strong wind, Temperature lock’
2) Change temperature to 25°C
3) Heating, 25°C, Strong wind
4) Heating, 20°C, Strong wind
5) Heating, 20°C, Strong wind
6) Return to Heating, 20°C, Strong wind
On the other hand, let's see an example of connecting the 2PIN connector to CN_DRY terminal.
When a command is given for function of "Heat operation, 20°C setting, high fan level, temperature
lock" through the central control, the applicable command is transmitted through the remote
controller. "HL (Hard Lock)" message showing the central control status is displayed on the remote
controller. If the user sets the temperature to 25°C, the command is blocked at the remote controller.
Multi V
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
L1 2 3 4
ON KSDO4H
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
SELECT
ACT
LNK
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
Ethernet 2
MENU/
TX
RX
Run
3
4
Power
Set ‘Heating, 20°C, Strong wind, Temperature lock’
The remote controller displays ‘HL’ message
It is not possible for the user to operate.
Installation/Owner's Manual
2-15
2. Installing ACP
Connceting RS485 cable to PI485
In order to connect the PI485 and the ACP, two RS485 cables should be connected to the BUS_A and
the BUS_B of the PI485. Connect the RS485 cables by referring to the following figure.
L1 2 3 4
ON KSDO4H
When connecting more than one PI485 to one ACP, connect the BUS_A/BUS_B of the PI485 to the
BUS_A/BUS_B of the other PI485 respectively.
2-16
ACP
2. Installing ACP
The following figure shows the example for connecting more than one PI485 to one ACP.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
TX
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
FDD
Ext.
MENU/
SELECT
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
RX
TX
RX
Run
3
L1 2 3 4
ON KSDO4H
L1 2 3 4
ON KSDO4H
+10V GND BUS_A BUS_B
L1 2 3 4
ON KSDO4H
+10V GND BUS_A BUS_B
ACP
+10V GND BUS_A BUS_B
Power
4
Installation/Owner's Manual
2-17
2. Installing ACP
Tip: Connection setup when using the simple central controller together with the ACP
The simple central controller can be used with the ACP. Connect the simple central controller to the
ACP as follows:
Note: Checking the LGAP Label
Check the LGAP Label at the right side of the case of the simple central controller. Only the product
with the label can be together connected to the ACP.
The VCC and the GND terminals of the simple central controller should be connected to the wire
from the PI485 or the separate adaptor. For more information, see the manual for the simple central
controller.
1. Connect the BUS-A and the BUS-B ports of the PI485 to the terminals C and D of the simple
central controller by using the RS485 communication cable.
2. Set the rotary switch of the simple central controller to match with the group number of the indoor
unit to be controlled. For example, in order to control the indoor units with the addresses 00~0F,
set the rotary switch to 0.
3. Set the DIP switch No. 1 of the simple central controller to OFF (slave) and No. 2 to ON (LGAP mode).
L1 2 3 4
ON KSDO4H
RS485
CN-POWER
GND
GND
CN-COM B
CN-POWER
D
CN-COM A
S2
S1
S4
L
LED2
C
LED4
LED3
IC1P
+
S5
+
S6
+
+
LED7
LED8
S3
+
LED5
+
LED13
LED14
S9
+
LED9
LED10
+
+
LED13
+
LED14
LED17
ON KSDO4H
L1 2 3 4
S19
ACP
+
S19
TX1
S12
S11
LED12
LED11
S14
S15
LED15
S15
ON KSDO4H
L1 2 3 4
2-18
+
+
LED16
PWB:6870A10001A
ASM:6711A20005E
+
LED17
S10
S18
S16
2. Installing ACP
Installing the ACP and Connecting the cable
After setting the PI485, the ACP should be installed at the suitable place and the RS485 cable should
be connected to communicate with the PI485. And, the Ethernet cable should be connected for
connecting to the Internet or the AC Manager.
Fixing the ACP at the installation site
The ACP is basically designed to be installed at the wall to use. Install the ACP at the suitable place
as the following description. Here, the installation method of the ACP is described with the example
installing the ACP at the wall.
1. Decide the space to install the ACP. Before installing the ACP, check whether the place is suitable
for connecting the ACP and the RS485 cable.
2. Use the screw driver to fix them at the wall. It can be fixed as shown at the following figure
according to the installation place.
1
2
DI
3
4
5
6
LG-N
7
8
ET 1
LG-N
9
10
11
12
13
14
15
16
17
18
19
20
LG-N
LG-N
ET 2
ET 3
ET 4
FDD
Ext.
MENU
SELE /
CT
Ethe
rnet
Ethe
rnet
1
2
3
DO
Cons
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
1
ACT
LNK
2
ACT
LNK
ole
4
TX
RX
Run
Powe
r
Installation/Owner's Manual
2-19
2. Installing ACP
Connecting RS485 cable to ACP
After fixing the ACP at the installation place, the RS485 cable connecting the PI485 to the ACP.
Connect the RS485 cable to the ACP as follows:
1. The end of the RS485 cable connecting to the BUS_A of the PI485 of the connector possible to be
connected to the ACP to the TX. Next, connect the end of the RS485 cable connecting to the
BUS_B of the PI485 to the RX.
RS485 - TX
RS485 - RX
Caution: Connecting the RS485 communication cable
Because the connection of the RS485 communication cable has a polarity, be careful
that the connection of two cables is not changed.
2. The RS485 cable connecting to the PI485 to the LG-NET port (RS485 port) of the ACP. Connect
the connector connecting the RS485 cable to one of the ports LG-NET1~LG-NET4. The number of
LG-NET ports is 1~4 and it is possible to connect to any of them to use.
1
2
DI
3
4
5
6
7
LG-N
ET
1
LG-N
ET
2
8
9
10
11
12
13
14
15
16
17
18
19
20
LG-N
ET 3
LG-N
ET
4
FDD
Ext.
MENU
SELE /
CT
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
Ethe
rnet
1
Ethe
rnet
1
2
DO
2
Cons
ole
3
4
Run
Powe
r
2-20
ACP
ACT
LNK
ACT
LNK
TX
RX
2. Installing ACP
Tip: Connecting the RS485 of the ACP
64 outdoor units at maximum can be connected to one port of the RS485 of the ACP and 256
indoor units at maximum can be connected to one ACP. When there are many outdoor units to
connect, connect the outdoor units suitably from LG-NET1 to LG-NET4 with the BUS form.
Otherwise, the ACP may cause the malfunction.
The following figure shows the example for separately connecting the LG-NET1 and the LG-NET2
with the BUS form.
Multi V
RX
L1 2 3 4
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
Ext.
Ethernet 2
ACT
LNK
Console
RX
PI485
L1 2 3 4
ACT
LNK
Multi V
TX
RX
ON KSDO4H
MENU/
SELECT
TX
RX
TX
RX
Ethernet 1
Multi V
TX
L1 2 3 4
FDD
9
10
11
12
13
14
15
16
17
18
19
20
PI485
ON KSDO4H
8
Multi V
ON KSDO4H
TX
PI485
Multi V
1
2
DO
Run
3
Power
4
L1 2 3 4
ON KSDO4H
L1 2 3 4
Multi V
ON KSDO4H
PI485
ACP
PI485
L1 2 3 4
ON KSDO4H
PI485
Simple central
controller
Installation/Owner's Manual
2-21
2. Installing ACP
The following figure shows the example of the incorrect connection of the RS485 of the ACP.
Multi V
Multi V
L1 2 3 4
ON KSDO4H
L1 2 3 4
ON KSDO4H
PI485
PI485
Multi V
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
Multi V
TX
6
7
8
FDD
Ext.
ACT
LNK
Console
1
2
DO
RX
L1 2 3 4
ACT
LNK
Ethernet 2
ON KSDO4H
Ethernet 1
L1 2 3 4
MENU/
SELECT
TX
RX
TX
RX
ON KSDO4H
9
10
11
12
13
14
15
16
17
18
19
20
PI485
PI485
Multi V
TX
RX
Multi V
Run
3
Power
4
L1 2 3 4
ACP
ON KSDO4H
L1 2 3 4
PI485
Simple central
controller
2-22
ON KSDO4H
ACP
PI485
2. Installing ACP
Connecting Ethernet cable to ACP
After connecting the ACP and the RS485 cable, the Ethernet cable should be connected to the ACP.
The ACP can be connected to the hub via the Ethernent cable or directly to the AC Manager.
Connecting the ACP and the hub
The ACP is connected to the basic Internet network installed at the field, generally to the hub. In this
case, the Ethernet cable should be connected by the direct cable.
Use the Ethernet cable (direct cable) to connect to the Ethernet 1 port of the ACP.
Connecting the ACP and the AC Manager
It is the case installing the AC Manager to the separate PC and directly connecting the ACP to the PC.
In this case, the Ethernet cable should be connected by the cross cable.
Use the Ethernet cable (cross cable) to connect to the Ethernet 1 port of the ACP.
Caution: Ethernet cable type
It should be identified whether the Ethernet cable to be connected is the direct cable or
the cross cable. Also, connect the cable by using the LAN tester to check whether the
cable has any problem. For more information about the direct cable and the cross
cable, see Chapter 4. UTP cable connection chart.
1
2
TX
RX
DI
3
4
5
6
LG-NE
T1
7
8
LG-NE
T2
9
10
11
12
13
14
15
16
17
18
19
20
LG-NE
T3
LG-NE
T4
FDD
MENU
/
SELEC
T
Ext.
Ethern
et 1
Ethern
et 2
1
2
3
DO
Conso
le
4
TX
RX
TX
RX
TX
RX
TX
RX
1
ACT
LNK
2
ACT
LNK
Connecting to the hub
: Direct cable
e
TX
RX
Connecting to the AC Manager
: Cross cable
TX
RX
TX
RX
ACT
LNK
ACT
LNK
TX
RX
Run
n
Power
er
Note: Ethernet 2 port
Because the Ethernet 2 is the spare port, it is not used to connect to the hub and the AC Manager.
Check the location of the Ethernet 1 port and the Ethernet 2 port and connect them correctly.
Installation/Owner's Manual
2-23
2. Installing ACP
Connecting Power adaptor to ACP
After connecting the Ethernet cable, the power adaptor should be connected for supplying the power
to the ACP.
1. Connect the power adaptor supplied with the ACP product to the power adaptor connection port of
the ACT as shown at the below figure.
1
2
DI
3
4
5
6
LG-NE
7
8
LG-NE
LG-NE
3
T3
T4
Ext.
Ethern
2
T2
FDD
MENU
SELE /
CT
Ethern
1
T1
LG-NE
9
10
11
12
13
14
15
16
17
18
19
20
et 1
et 2
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
K
Cons
ole
TX
RX
ACT
LNK
ACT
LNK
Run
DO
Conso
le
4
TX
RX
Powe
r
Run
Powe
r
2. After connecting the power adaptor, connect the power cord connected to the power adaptor to the
outlet.
2-24
ACP
2. Installing ACP
Configuring the ACP network
After connecting the ACP to various devices via the cable, the network environment of the ACP should
be set by driving the ACP. The following information should be set for using the ACP.
• IP address of the ACP
• Gateway address
• Net mask address
Caution: Setting the network environment information
If the above information is not entered, the communication error may be occurred or it
may be impossible to control by the ACP. So, be careful to correctly input.
Beforing configuring the ACP environment
The network environment of the ACP can be set by the LCD and the buttons at the front side of the ACP.
The current ACP information and the menu are displayed at the LCD, and the menu can be changed
and selected by pressing 'MENU/SELECT' button and Up/Down/Left/Right ( , , , ) buttons.
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
Ethernet 1
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
Run
3
4
TX
RX
TX
RX
TX
RX
MENU/
SELECT
Power
Installation/Owner's Manual
2-25
2. Installing ACP
Turning on the ACP
Turn on the ACP to set the network environment of the ACP.
Cons
ole
1
DI
2
3
4
5
6
LG-NE
7
8
LG-NE
9
10
11
12
13
14
15
16
17
18
19
20
LG-NE
LG-NE
MENU
SELE /
CT
T3
T4
Ext.
Ethern
1
T2
FDD
Ethern
2
T1
et 1
et 2
Conso
DO
le
3
4
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
TX
RX
Run
ACT
LNK
Powe
r
ACT
LNK
TX
RX
Run
Powe
r
When the power switch is turned on, the ACP booting screen is displayed on the LCD as shown at the
below figure, and when booting is completed, the initial ACP screen is displayed.
ACP booting screen
Initial ACP screen
LG Electronics
Wait for booting
ACP
After booting
SW ver. 2.77.2
Note: Software version
The software version of the current ACP is displayed
at the initial ACP screen. Also, the software version
may be different according to the manufacturing date
of the ACP.
2-26
ACP
ACP
SW ver. 2.77.2
2. Installing ACP
Entering into the environment setup mode
Press 'MENU/SELECT' button of the ACP to enter into the environment setup mode of the ACP.
When the 'MENU/SELECT' button is pressed for the first time, the menu to set the IP address is
displayed as shown below.
[MENU] ➞
Set IP Address
MENU/
SELECT
Select the desired function by pressing the left/right button ( ,
( , ) is pressed, the menu is changed as shown below.
Enter the IP address
[MENU] ➞
Set IP Address
Offered later (not at present)
[MENU] ➞
Set Update Svr
Select Peak or Demand
[MENU] ➞
Set PeakDemand
Set the consumed power display function
[MENU] ➞
Set PDI
Error record display setting
[MENU] ➞
Set Log
). Whenever the left/right button
Enter Gateway address
← [MENU] ➞
Set GW Address
Enter Netmask
[MENU] ➞
Set Netmask
Select ACP web server display
language (Korean, English)
[MENU] ➞
Set Language
Set Schedule function
[MENU] ➞
Set SCH
Menu to display the set network Info
[MENU]
Information
Press the 'MENU/SELECT' button at the desired function to enter into the setup screen for the related
mode.
Installation/Owner's Manual
2-27
2. Installing ACP
How to set the network address
The network address consists of four 3-digit numbers. In case of setting the network address, the
name of the related address is displayed on the LCD of the ACP. Press Up/Down/Left/Right ( , ,
, ) button to set.
Press Up/Down ( , ) button to increase/decrease the number of the digit where the cursor is
placed, and press Left/Right ( , ) button to move the digit of the network address.
When pressing the down( ) button
[Set IP Address]
192.168.000.000
[Set IP Address]
192.167.000.000
MENU/
SELECT
When pressing the right( ) button
[Set IP Address]
192.168.000.000
[Set IP Address]
192.168.000.000
MENU/
SELECT
Also, in order the sum of three numbers not to exceed 255, the first digit of each address is set only
when the second digit is set to less than or equal to 4. At the following example, '1' can not be
changed to '2.' In this case, it can be changed after '6', the next digit, is set to less than or equal to '4.'
[Set IP Address]
192.168.000.000
[Set IP Address]
192.148.000.000
2-28
ACP
Cannot be set!!
Possible to set
after setting the
next digit to less
than or equal to 4.
2. Installing ACP
Setting the IP address
In order for the user to use the functions of the ACP via the web, the unique IP address should be
given to the ACP. Set the IP address as follows:
1. Press the 'MENU/SELECT' button of the ACP. [MENU] screen is displayed as shown at below.
Press the 'MENU/SELECT' button again. The screen to enter the IP address is displayed.
MENU/
SELECT
2. Use Up/Down/Left/Right (
Click
MENU
/SELECT
button
[MENU] ➞
Set IP Address
[Set IP Address]
192.168.000.000
) button to enter the desired IP address.
[Set IP Address]
192.168.002.101
MENU/
SELECT
Example to set IP address
3. After entering the IP address, press the 'MENU/SELECT' button to set the entered IP address. But,
there is no 'MENU/SELECT' button pressed for a specific period (about 5 seconds), it returns to the
initial screen with the entered IP address not applied to the system, and the existing set IP address
is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
Installation/Owner's Manual
2-29
2. Installing ACP
Setting the gateway address
After setting the IP address, the gateway address should be set. Set the gateway address as follows:
1. Press the 'MENU/SELECT' button of the ACP and then press Left/Right (
, ) button to display
the following Gateway setup screen. Press the 'MENU/SELECT' button again. The screen to enter
the gateway address is displayed.
MENU/
SELECT
2. Use Up/Down/Left/Right (
Click
MENU
/SELECT
button
[MENU]
Set GW Address
[Set GW Address]
192.168.000.000
) button to enter the desired gateway address.
[Set GW Address]
165.186.002.001
MENU/
SELECT
Example to set Gateway address
3. After entering the gateway address, press the 'MENU/SELECT' button to set the entered gateway
address. But, there is no 'MENU/SELECT' button pressed for a specific period (about 5 seconds), it
returns to the initial screen with the entered gateway address not applied to the system, and the
existing set gateway address is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
2-30
ACP
2. Installing ACP
Setting the netmask address
After setting the gateway address, the netmask address should be set. Set the netmask address as follows:
1. Press the 'MENU/SELECT' button of the ACP and then press Left/Right (
, ) button to display
the following Netmask setup screen. Press the 'MENU/SELECT' button again. The screen to enter
the netmask address is displayed.
MENU/
SELECT
2. Use Up/Down/Left/Right (
Click
MENU
/SELECT
button
[MENU]
Set Netmask
[Set Netmask]
192.168.000.000
) button to enter the desired net mask address.
[Set Netmask]
255.255.255.000
MENU/
SELECT
Example to set Netmask address
3. After entering the netmask address, press the 'MENU/SELECT' button to set the entered netmask
address. But, there is no 'MENU/SELECT' button pressed for a specific period (about 5 seconds), it
returns to the initial screen with the entered netmask address not applied to the system, and the
existing set netmask address is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
Installation/Owner's Manual
2-31
2. Installing ACP
Checking the network environment
When the IP address, the gateway address, and the netmask address are set, the essential network
environment setup of the ACP is completed. So, make sure that all settings are successfully completed.
Check the network environment setting as follows:
Press the 'MENU/SELECT' button of the ACP and then press Left/Right ( , ) button to display the
following Information screen. Press the 'MENU/SELECT' button again. The currently set network information
can be checked.
Click
MENU
/SELECT
button
MENU/
SELECT
[MENU]
Information
[MAC Address]
001B:1987:7B14:1023
Each different information is displayed on the LCD screen about every 3 seconds. It is displayed as follows:
MAC address
IP address
[MAC Address]
001B:1987:7B14:1023
[IP Address]
165.168.002.101
Netmask address
Gateway address
[Netmask Address]
255.255.255.000
[Gateway Address]
255.255.255.000
Update server address (not at present)
[Update Server]
None
2-32
ACP
2. Installing ACP
Setting the functions of the ACP
The following functions can be set by using the menu of the ACP:
• Select Peak or Demand
• Select the web display language
• Set the schedule to use
• Set the wattage display to use
Before setting the functions of the ACP
The function setting of the ACP should be changed depending on the case that only the ACP is used
or the case that the ACP is interconnected with the external devices such as AC Manager, Wattmeter
and Demand controller.
In general, the function of the ACP should be set and used as follows:
ACP only
ACP interconnected
with AC Manager
ACP interconnected
with Demand controller
Select Peak or Demand
Set to Peak function
Set to Demand function
Set to Demand
function
Schedule
Set the schedule
function to use
Set the schedule
function not to use
Set the schedule
function to use
Wattage display
Set to use if interconnected woth the wattmeter or set not to use if not.
Caution: Setting the wattage display to use
If the ACP and the wattmeter are not connected, the wattage display function should
be set not to use. If it is set to use, be careful of it because the control speed of the
ACP is getting slow.
Installation/Owner's Manual
2-33
2. Installing ACP
Selecting Peak or Demand
The ACP offers the function to manage the wattage consumed by the connected air conditioner, by
which the electric charges can be effectively saved. The ACP offers two functions to limit the peak
wattage of the air conditioner as follows:
• Peak: The peak wattage of the air conditioner can be managed by setting the peak wattage to the ACP.
• Demand: The ACP and the Demand Controller are connected without any separate software.
When the current wattage exceeds the target value, the wattage of the air conditioner can be
restricted by interconnecting with other power device to set the total target wattage.
One of these methods can be selected and used at the ACP. And, if it is set by the menu of the ACP,
the UI screen is differently displayed when accessing the web screen to set the function. The ACP
should be set to the Demand function for the following cases:
• Interconnecting with the Demand Controller of the professional Demand control company
• Interconnecting with the AC Manager
Note: Default value
The default value when shipped from the factory is set to Peak.
Change the wattage control method as follows:
1. Press the 'MENU/SELECT' button of the ACP and then press Left/Right (
, ) button to display
the following Peak/Demand setup screen. Press the 'MENU/SELECT' button again. The screen to
set Peak or Demand method is displayed.
MENU/
SELECT
2-34
ACP
Click
MENU
/SELECT
button
[MENU]
Set PeakDemand
[Set PeakDemand]
PK(0)/DMD(1):0
2. Installing ACP
2. Use Up/Down (
, ) button to set the desired wattage control method. Press the Up ( ) button to
set the Peak method, or press the Down ( ) button to set the Demand method.
[Set PeakDemand]
PK(0)/DMD(1):1
MENU/
SELECT
Example for setting Demand to use
3. When the 'MENU/SELECT' button is pressed, the set wattage control method is applied to the
system. But, there is no 'MENU/SELECT' button pressed for a specific period (about 5 seconds), it
returns to the initial screen with the set control method not applied to the system, and the existing
set method is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
Installation/Owner's Manual
2-35
2. Installing ACP
Selecting ACCS display language
The ACP offers the web server function. So, when the user accesses the ACP by using the Internet
Explorer at the computer connecting to the ACP, the LG ACCS (Advanced Centralized Control
System), the control program to use the functions of the ACP, is displayed.
Note: How to use the LG ACCS
For more information on the method to use the LG ACCS, see Chapter 3. ACP operation by using
the ACCS
The following figure is the initial screen of the LG ACCS program.
The LG ACCS is offered with the Korean version and the English version, which can be changed by
the user's setting. Change the language setting of the LG ACCS as follows:
1. Press the 'MENU/SELECT' button of the ACP and then press Left/Right (
, ) button to display
the following language setup screen. Press the 'MENU/SELECT' button again. The screen to set
the display language is displayed.
MENU/
SELECT
2-36
ACP
Click
MENU
/SELECT
button
[MENU]
Set Language
[Set Language]
KR(0)/EN(1):0
2. Installing ACP
2. Use Up/Down (
, ) button to set the desired language. Press the Up ( ) button to display in
English (1), or press the Down ( ) button to display in Korean (0).
[Set Language]
KR(0)/EN(1):1
MENU/
SELECT
Example for setting the LG ACCS
to display in English
3. When the 'MENU/SELECT' button is pressed, the set display language is applied to the system.
But, there is no 'MENU/SELECT' button pressed for a specific period (about 5 seconds), it returns
to the initial screen with the set display language not applied to the system, and the existing set
method is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
Installation/Owner's Manual
2-37
2. Installing ACP
Setting whether to use the schedule function or not
The LG ACCS, the operation program of the ACP, offers the schedule setup function for the indoor
unit of the air conditioiner connected to the ACP to automatically operate at the specified time.
Whether to use the schedule function at the ACP or not should be set.
Caution: Deciding whether to use the schedule function or not
When the ACP and the AC Manager are interconnected, the ACP has the preemptive
priority to use the schedule function of the AC Manager, so it should be set not ot use
the schedule function of the ACP. When only the ACP is operated, the schedule
function of the ACP can be used.
Set whether to use the schedule function as follows:
1. Press the 'MENU/SELECT' button of the ACP and then press Left/Right (
, ) button to display
the following schedule function setup screen. Press the 'MENU/SELECT' button again. The screen
to set whether to use the schedule function or not is displayed.
MENU/
SELECT
Click
MENU
/SELECT
button
[MENU]
Set SCH
[Set SCH]
NOT(0)/USE(1):0
2. Use Up/Down (
, ) button to set whether to use the schedule function or not. Press the Up ( )
button to use the schedule function, or press the Down ( ) button not to set the schedule function.
[Set SCH]
NOT(0)/USE(1):1
MENU/
SELECT
2-38
ACP
Example for setting to use the
schedule function
2. Installing ACP
3. When the 'MENU/SELECT' button is pressed, whether to use the schedule function or not is
applied to the system. But, there is no 'MENU/SELECT' button pressed for a specific period (about
5 seconds), it returns to the initial screen with the setting not applied to the system, and the existing
set method is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
Installation/Owner's Manual
2-39
2. Installing ACP
Setting whether to use the wattage display function or not
The LG ACCS, the operation program of the ACP, offers the wattage display interconnection function
to check and manage the wattage of the indoor unit of the air conditioner connected to the ACP.
Caution: Wattage display interconnection
In order to use the wattage display interconnection function, the wattmeter should be
connected and interconnected with the PI485 connecting to the ACP. See the related
product manual for the installation and the operation of the wattmeter and the PI485.
In order to use the wattage display interconnection function with the wattmeter installed, whether to
use it at the ACP or not should be set. Set whether to use the wattage display interconnection function
as follows:
Set whether to use the wattage display interconnection function as follows:
1. Press the 'MENU/SELECT' button of the ACP and then press Left/Right (
, ) button to display
the wattage display setup screen. Press the 'MENU/SELECT' button again. The screen to set
whether to use the wattage display or not is displayed.
MENU/
SELECT
Click
MENU
/SELECT
button
[MENU]
Set PDI
[Set PDI]
NOT(0)/USE(1):0
2. Use Up/Down (
, ) button to set whether to use the wattage display function or not. Press the Up
( ) button to use the wattage display function, or press the Down ( ) button not to set the wattage
display function.
[Set PDI]
NOT(0)/USE(1):1
MENU/
SELECT
2-40
ACP
Example for setting to use the
wattage display function
2. Installing ACP
3. When the 'MENU/SELECT' button is pressed, whether to use the wattage display function or not is
applied to the system. But, there is no 'MENU/SELECT' button pressed for a specific period (about
5 seconds), it returns to the initial screen with the setting not applied to the system, and the existing
set method is used.
ACP
SW ver. 2.77.2
MENU/
SELECT
Installation/Owner's Manual
2-41
2. Installing ACP
Setting error history display
LG ACCS, operating program of ACP, provides error history function to monitor various types of errors
occurring in between the air condition and indoor unit connected to ACP. For the error history function,
the user can select conveniently whether to display in LG ACCS or not.
The user must set whether to use the error history function in ACP. To set to use the error history
function, proceed as follows.
1. After pressing the 'MENU/SELECT' button of ACP, press the left and right (
, ) button to display
the setting screen of the error history function as shown below. Once again, press the
'MENU/SELECT' button. The screen to set whether to use the error history function will be
displayed.
MENU/
SELECT
Click
MENU
/SELECT
button
[MENU]
Set LOG
[Set LOG]
NOT(0)/USE(1):0
2. Use the up and down (
, ) button to set whether to use the error history function. When you
press the up ( ) button, it will be set to use the error history function and down ( ) button not to
use the error history function.
[Set LOG]
NOT(0)/USE(1):1
MENU/
SELECT
Example of setting to use
the error history function
3. When you press the 'MENU/SELECT' button, setting of whether to use the error history function
will be applied to the system. But if the 'MENU/SELECT' button is not pressed within a certain
period of time (5 seconds), the setting will not be applied to the system and the system will return
to the initial screen. The system will use the method set by the existing setting.
ACP
SW ver. 2.77.2
MENU/
SELECT
2-42
ACP
2. Installing ACP
Configuring the ACCS access
The user can use the LG ACCS program at the computer connected with the ACP via the network to
control the functions of the ACP. The LG ACCS (Advanced Centralized Control System) is the function
control program of the ACP developed with the Java. The LG ACCS is automatically executged when
the user accesses the ACP by using the Internet Explorer with no separate program installed.
Chceking the MS JAVA VM installation
The MS JAVA Virtual Machine should be installed for accessing the LG ACCS program of the ACP.
Because it is not automatically installed since the Windows XP version, the user using the Windows
XP or higher version should manually install the MS JAVA Virtual Machine.
1. Execute [Start]
[Program]
[Internet Explorer] at the Windows.
2. When the Internet Explorer is executed, execute [Tools]
[Internet Option] at the menu.
The 'Internet Option' window is displayed as follows:
Installation/Owner's Manual
2-43
2. Installing ACP
3. After selecting the [Advanced] tab at the 'Internet Option' window, check whether there is the
'Microsoft VM' item or not. If it is possible to check at the checkbox, the VM(Virtual Machine) is
already installed at the Windows.
Check only the 'Use Java JIT Compiler (system rebooting required)' item at the 'Microsoft VM' item
and unselect all other items. If 'JAVA (Sun)' item exists at 'Microsoft VM' item and it is checked, it
should be unselected.
Click
Check whether to
check or not
Deselect 'JAVA (Sun)'
Caution: If Microsoft Java Virtual Machine is not installed
If the Java Virtual Machine of the Microsoft is not installed, 'msjavx86.exe' file should
be downloaded and installed by the search site.
2-44
ACP
2. Installing ACP
Checking the MS Explorer security setting
For the stable operation of the LG ACCS (Advanced Centralized Control System), the security setting
of the Microsoft Internet Explorer, a web browser, should be changed.
Change the security setting of the Microsoft Internet Explorer by the following procedure. Here, it is
described by the example changing the setting at the Windows XP operating environment.
1. Execute [Start]
[Program]
[Internet Explorer] at the Windows.
2. When the Internet Explorer is executed, execute [Tools]
[Internet Option] at the menu. The
'Internet Option' window is displayed as follows:
Installation/Owner's Manual
2-45
2. Installing ACP
3. After selecting the [Security] tab at the 'Internet Option' window, press [Custom Level] at the
bottom. 'Security setup' window is displayed.
Click
Click
4. When the 'Security setup' window is displayed, find out 'Microsoft VM' and check 'Custom'
When [Java Custom Settings] button is displayed later, click it. Then, 'Internet' window is displayed.
Click
Click
2-46
ACP
2. Installing ACP
5. After selecting 'Edit Right' tab at the Internet window, set 'Run Unsigned Content' item to 'Enable.'
Press [OK] button to exit 'Internet' window.
Click
Click
6. Press [OK] button at the previous 'Security setup' window. 'Warning!' window for checking the
security setting is displayed. Press [Yes] button.
Click
Click
Installation/Owner's Manual
2-47
2. Installing ACP
7. Finally, press [OK] button at the 'Internet Options' window. Now, the security setup to use the LG
ACCS is completed.
Click
2-48
ACP
2. Installing ACP
Entering the indoor unit & ventilator information
When the installation at the previous steps is completed, finally, the information of the outdoor unit, the
indoor unit, and the ventilator connected to the ACP should be entered. The air conditioner can be
controlled by using the ACP only after this information is entered.
There are two methods to enter the information of the outdoor unit, the indoor unit, and the ventilator
depending on the condition as follows:
• When the ACP is connected to the AC Manager, register the information by using the AC Manager
• When the ACP is not connected to the AC Manager, register the information by using the LG
ACCS program of the ACP
If the ACP is connected to the AC Manager
When the AC Manager is installed at the specific PC to connect to the ACP, the information set at the
AC Manager is automatically entered into the ACP. So, the ACP can control the air conditioner even if
the information of the outdoor unit, the indoor unit, and the ventilator is not entered.
Note: How to use the AC Manager
For more information to use the AC Manager, see the Owner's manual of the AC Manager.
Installation/Owner's Manual
2-49
2. Installing ACP
If the ACP is not connected to the AC Manager
When the ACP is not connected to the AC Manager, the information of the indoor unit and the ventilator
can be entered by using the LG ACCS (Advanced Centralized Control System) program of the ACP.
Accessing the LG ACCS
In order to enter the indoor unit information by using the LG ACCS program of the ACP, you should
access the LG ACCS, first of all.
Access the LG ACCS at the PC connected to the internal network to which the Internet or the ACP
can be connected as follows:
1. Execute the Internet Explorer at the PC connected to tye ACP via the Internet or the internal network.
And then, enter the IP address set at the ACP into the address window, and press [Enter] key.
Enter ACP access IP
Note: ACP access IP
If you don't know the access IP of the ACP, check the ACP setup IP by referring to Chapter 2.
Configuring the ACP network – Checking the network environment.
2-50
ACP
2. Installing ACP
2.
When the IP address is correctly entered, the following LG ACCS Login screen is displayed. Enter
the ID and the password and then click [Login] button.
Set the ID to 'admin' and the password to 'digital21' for the first access to the ACP.
Input
Click
3. When the login is successfully done, the following access procedure will be executed.
Installation/Owner's Manual
2-51
2. Installing ACP
4.
When the login is successfully done, the initial screen of the LG ACCS is displayed as shown at the
below. Click [System setup] button, the last mentu.
The system setup screen to set the system is displayed.
Click
2-52
ACP
2. Installing ACP
Setting the air conditioner
Set the indoor unit of the air conditioner as follows. The setup method is described by the assumption
that 5 indoor units of the air conditionere are connected to each of four groups. Set the group number
(indoor unit number) to 0, 1, 2, and 3.
1. Click 'Air conditioner setup' tab at 'System setup' menu of the LG ACCS.
Click "System Setup"
menu
2. In order to set the air conditioner, first of all, enter the outdoor unit information (group number) of
the air conditioner. Each outdoor unit information is used as the information of the physical group
connecting the indoor unit. Click [Outdoor unit input] at 'System setup' screen of the LG ACCS to
display the window for setting the group number.
Click [Outdoor
unit input]
button to
display ‘Outdoor
unit information
input’ window.
Installation/Owner's Manual
2-53
2. Installing ACP
3. Click [Default input] button. The outdoor unit information (group number) is automatically entered.
Click [Default input] button to
enter the default values
4. Except the outdoor units as many as the number of the outdoor units (the number of groups) to set
according to the air conditioner installation plan, delete all remaining outdoor units by pressing
button. Here, because we assume that four groups in total are set and the group number is set
to 0, 1, 2, and 3, leave only four groups as shown at the below figure.
Delete all outdoor units escept
the outdoor units as many as
the number of groups to set
2-54
ACP
2. Installing ACP
5.
Enter the setting value suitable for each item. When you click the item to set, the related item
changes to yellow, whose setting value can be modified. See the following table for the description
on the item to set.
Modify the Setting value
for each item
Item
G/W No.
Outdoor unit No. (Group No.)
Name
Type
Description
Leave as it is with no setting.
Enter the number for identifying the outdoor unit (group).
Leave the default value as it is with no setting.
Select the module type of the outdoor unit.
- UAC: Unified air conditioner (it means the outdoor unit for the unitified
air conditioner.)
Model
Maximum consumed
power (W)
Enter the model name of the outdoor unit.
Set the maximum wattage for the outdoor unit to consume.
Installation/Owner's Manual
2-55
2. Installing ACP
6.
When you click [Done] button, 'Outdoor unit information input' window is closed and it returns to
the previous screen. Click [Default input] button at 'Air conditioner setup' tab. The groups as many
as the number of set outdoor units are automatically created and the information of the air
conditioner included at the group is also created.
Click [Default input] button to
create the group(s) and the air
conditioner (s) as many as set
outdoor units(group No.)
7.
Leave the indoor units as many as the number of the air conditioners to set for each group, and
delete the remaining indoor units by pressing
button. As five indoor units of the air conditioner
are connected for each group, all units are deleted except five indoor units information.
Delete the indoor units except
the planned indoor units
2-56
ACP
2. Installing ACP
8.
Enter the air conditioner group name and the information of the indoor unit. When each displayed
item is clicked, it's color is changed to yellow for its contents to be directly entered or the list box is
displayed. Enter the setting value suitable for each item. See the following table for the description
on the setting item.
Enter and modify the air conditioner
group name and the indoor unit
information. However, we recommend
to use 'Physical address' item as set.
Item
Group name
Description
Enter the air conditioner group name for the user to easily recognize.
Enter the indoor unit type. Indoor types to set are as follows:
• UAC: Unified air conditioner
• SGL: Single type air conditioner
Type
Caution: Set to UAC type
The indoor unit type should be set to UAC (unified air
conditioner) type. At present, the SGL (single type air
conditioner) type can not be set.
Air conditioner name
Enter the air conditioner name for the user to easily recognize.
Installation/Owner's Manual
2-57
2. Installing ACP
Dip switch
Description
Physical address
Enter the physical address of the indoor unit. The physical address
consists of three numbers.
The first number and the second number are the G/W number and the
outdoor unit number respectively, which can be set within the
information entered from the existing [G/W information] and [outdoor
unit information].
The third number is the indoor unit number, which can not be set
overlapped within the same indoor unit number and should be set
within the range of 0~15.
If the user directly enters the physical address, it can be easily entered
incorrectly. So, [Default value] button should be used to enter.
Model name
Maximum consumed power
Enter the model name of the indoor unit.
Enter the maximum consumed power for the indoor unit to use. The maximum
consumed power depends on the model.
9. For the remaining three groups, set the number of the indoor units and the item by the procedure
same to Step 7 and 8.
10. When all items are set, press [Save] button to save. Press [Save] button to display the window to
confirm to save the setting information. Press [OK] button to save the setting information.
Press [Save] button to the setting.
When the confirmation window is
displayed, press [OK] button.
2-58
ACP
2. Installing ACP
11. The saving process is performed. When the air conditioner setup is successfully done, the group
and the air conditioner information set at present can be checked.
Possible to check the set
group and air conditioner
information
Installation/Owner's Manual
2-59
2. Installing ACP
Note: Physical and Logical group
At the ACP, the connected air conditioners can be grouped by using the concept “Physical group”
and “Logical group.”
The physical group is the outdoor unit physically connecting the indoor unit. The example of the
physical group is setting the address to the indoor unit at the installation step. However, the logical
group is used for the convenient control regardless to the physical connection.
Physical group (Ex: three floors)
Multi V
L1 2 3 4
Class 3, 2nd grade, 3rd floor Class 1, 3rd grade, 3rd Class 2, 3rd grade, 3rd floor
ON KSDO4H
PI485
Multi V
L1 2 3 4
ON KSDO4H
Class 4, 1st
grade, 2nd floor
PI485
Class 1, 2nd
grade, 2nd floor
Class 2, 2nd
grade, 2nd floor
Multi V
L1 2 3 4
ON KSDO4H
Class 1, 1st
grade, 1st floor
Class 2, 1st
grade, 1st floor
Class 3, 1st
grade, 1st floor
PI485
Logical group (Ex: 1st grade)
For describing the difference between the physical group and the logical group by the example of
the school, as shown at the above figure, the logical group can be said the set of the air
conditioners connected to the same outdoor unit. However, the logical group can be configured
even when the air conditioners at the 1st grade classrooms are connected to the different outdoor
units regardless to the physical connection.
2-60
ACP
2. Installing ACP
Setting the ventilator
Set the ventilator as follows. In this case, the method for setting the ventilator is described by the
assumption that five ventilators are connected to two groups (Group number 0 and 1) respectively.
1. Click 'Ventilating setup' tab at 'System setup' menu of the LG ACCS.
Click ‘System setup’
menu. And then, click
‘Ventilating setup’ tab.
2. To set up the ventilator, you must first enter the group number of
the ventilator. The information of each
outdoor unit is used as the physical group information connecting the ventilator. When you click on
[Enter ventilator group] button in the 'System setting' screen of LG ACCS, the window to set the group
number is displayed.
Click [Vent Group Input]
button to display ‘Vent
Group information input’
window.
Installation/Owner's Manual
2-61
2. Installing ACP
3. Click [Default input] button. The group number (outdoor unit number) is automatically entered.
Click [Default input] button to
enter the default value
4. Leave the item(s) as many as the number of groups to set according to the installation plan of the
ventilator, and press
button to delete all remaining outdoor units. Here, because two groups
(group number 0 and 1) are assumed to be set in total, leave only two groups as shown at the below
figure.
Leave the group(s) as
many as the number of
groups to set and delete
the remaining groups.
2-62
ACP
2. Installing ACP
5.
Enter the setting value suitable to each item. When the item to be set is clicked, the related item is
changed to yellow and its setting value can be modified. See the below table for the description on
the item to set.
Modify the setting
value for each item
Item
Description
Group number
Enter the number to classify the ventilator group.
When the number is entered through the [Input default value] button, it
is good to keep the number as it is.
Name
Do not set up the name and keep the default value.
Installation/Owner's Manual
2-63
2. Installing ACP
6. When [Done] button is clicked, 'Outdoor unit information input' window is closed and it returns to
the previous screen. Click [Default input] button at 'Ventilating setup' tab. The group(s) are
automatically created as many as the number of the set outdoor units, and the information about
the ventilator included at the group is created.
Press [Default input] button to create the
groups and the ventilators as many as
the number of outdoor units (group No.)
7. Leave the item(s) as many as the number of ventilators to set for each group, and press
button
to delete all remaining ventilators. Here, because five ventilators are assumed to be connected to
each group, only five ventilator information is left and all remaining ones are deleted.
Delete the ventilators
except the planned
ventilators
2-64
ACP
2. Installing ACP
8. Enter the ventilator group name and the information of the ventilator. When each displayed item is
clicked, it's color is changed to yellow for its contents to be directly entered or the list box is
displayed. Enter the setting value suitable for each item. See the following table for the description
on the setting item.
Enter and modify the ventilator group
name and the ventilator information.
However, we recommend to use
'Physical address' item as set.
Item
Group name
Type
Ventilator name
Physical address
Model name
Maximum consumed power
Description
Enter the ventilator group name for the user to easily recognize.
Leave this information as it is without changing.
Enter the ventilator name for the user to easily recognize.
Enter the physical address of the ventilator. When [Default input]
button is pressed, it is automatically created by inheriting the higher
information.
Physical address is composed of 4 numbers.
The first and second number is the G/W number and ventilator group
number, respectively. This can be set only within the entered
information from existing [G/W information] and [Ventilator group input]
menu. The third number is the ventilator number, which cannot be
duplicated within the same ventilator group number and must be set
within the range of 0~15. The fourth number is the Master and Slave
setting. This value is set to 0 (Master) and must not be changed.
Enter the model name of the ventilator.
Enter the maximum consumed power for the ventilator to use. The
maximum consumed power depends on the model.
Installation/Owner's Manual
2-65
2. Installing ACP
9. For the remaining one group, set the number of the ventilators and the item by the procedure same
to Step 7 and 8.
10. When all items are set, press [Save] button to save. Press [Save] button to display the window to
confirm to save the setting information. Press [OK] button to save the setting information.
Press [Save] button to the
setting. When the confirmation
window is displayed, press
[OK] button.
11. The saving process is performed. When the ventilator setup is successfully done, the group and
the ventilator information set at present can be checked at the 'Ventilating' menu.
2-66
ACP
2. Installing ACP
Making sure and checking the ACP installation
After installing the ACP, the condition of the ACP can be checked by the following flow chart.
Checking whether the indoor unit of the air conditioner is connected or not
First, it should be checked whether the indoor unit of the air conditioner is connected or not by
executing the LG ACCS of the ACP. Check the condtion of the ACP by the following flow chart.
Air conditioner is not found
at the ACCS of the ACP
Are all indoor
units not connected?
Yes
No
Is it not connected
per outdoor unit?
Successful
Perform the PING test at the
command prompt window of the
PC
• Check the IP and the gateway
address of the ACP
• Check whether the LAN cable is
normal or not
• Hub used: Direct cable
• Hub not used: Cross cable
• Check whether it is possible for the IP
of the PC to communicate with the
ACP or not (The first three digits of
the private IP should be same to
communicate)
Yes
No
PI485 LED02G
and 03G are continuously
blinking?
Yes
The LED
of the LG-NET of the ACP
blinks?
No
Yes
Recheck after resetting the ACP
And then, check whether to replace
the ACP or not if any defect is
found
Check the polarity of the related
PI485 A/B line
Check the product number of
outdoor unit and the product
No
Recheck the installation wiring of the
related PI485
Check the related PI485 DIP switch
Check whether the indoor/outdoor
communication is normal or not
Check the address setting of the
indoor unit
16 or more indoor
Yes
units are connected to one
outdoor unit?
Check the PI485 model name
PNF-P14A1M should be used
No
Recheck the address setting of
the indoor unit
Check whether the
indoor/outdoor communication
is normal or not
Installation/Owner's Manual
2-67
2. Installing ACP
Monitoring the ACP condition after the lock all and the temperature lock
Execute the LG ACCS of the ACP to select all indoor units and execute the lock all function. And then,
after performing the temperature lock function again, monitor the ACP condition. Check the ACP
condtion according to the following flow chart.
After selecting all indoor
units, perform the lock all
and the temperature lock
Lock all or Temperature
lock of some indoor units
are deselected
Is it not performed
per outdoor unit?
Yes
Are all indoor units
the Multi V super?
No
No
Insert the CN-Dry into the related
PI485 of the outdoor unit, not the
Super product
Are all indoor units the
Multi V super?
No
Insert the CN-Dry into the
related PI485 of the outdoor
unit, not the Super product
2-68
ACP
Yes
Yes
Is the Lock all
deselected?
Yes
No
Yes
Check the product number of the
PI485 and replace it with the
product with the function applied.
Chec the version of the outdoor unit
Chec the version of the outdoor unit Yes
and perform the program
and perform the program onboarding
onboarding Version 33 or higher
Version 33 or higher
3. ACP operation by using the LG ACCS
3. ACP operation by using the LG ACCS
The LG ACCS is the UI program of the web server which can operate the ACP. This chapter
describes the function and the procedure to use the LG ACCS for operating the ACP.
Accessing the ACCS
In order to enter the indoor unit information by using the LG ACCS program of the ACP, first of all, the
LG ACCS should be accessed.
In order to access the LG ACCS, perform the following procedure at the PC connecting the internal
network where can be connected to the ACP.
1. Execute the Internet Explorer at the PC connecting the ACP via the Internet or the internal network.
And, enter the IP address set to the ACP into the address window, and press [Enter] key.
Enter ACP access IP
Note: ACP access IP
If the access IP of the ACP is not known, check the ACP setup IP by referring to 'Chapter 2.
Configuring the ACP network – Checking the network environment setting.'
Installation/Owner's Manual
3-1
3. ACP operation by using the LG ACCS
2. When the IP address is correctly entered, the following LG ACCS Login screen is displayed. Enter
the ID and the password and then click [Login] button.
Set the ID to 'admin' and the password to 'digital21' for the first access to the ACP.
Input
Click
3. When the login is successfully done, the following access procedure will be executed.
3-2
ACP
3. ACP operation by using the LG ACCS
4. The initial screen of the LG ACCS is displayed as shown at the below. When you click the button of
the function to control, the screen is changed to use the related function.
Click
Installation/Owner's Manual
3-3
3. ACP operation by using the LG ACCS
Reviewing the initial ACCS screen
The LG ACCS(Advanced Centralized Control System) is the program which is automatically executed
when accessing the ACP web server. The user can control the indoor unit and the ventilator of the air
conditioner connected to the ACP and monitor various status information by using the LG ACCS.
When accessing the AG ACCS, the following LG ACCS program will be executed.
2
1
3
3-4
ACP
4
5
3. ACP operation by using the LG ACCS
1 Menu selection buttons
You can select the menu at the menu selection button to perform the functions such as controlling and
monitoring. The ACP consists of the following eight menus.
Item
Description
Air conditioner / Perform the operation change, the Lock all, and the
temperature lock of the air conditioner connected to the ACP.
Ventilating / Perform the operation change and the Lock all of the
ventilator connected to the ACP.
Schedule / Start and stop the indoor unit of the air conditioner
connected to the ACP according to the reserved schedule.
Peak power / Set the peak operation ratio by setting the operation ratio
of the whole air conditioner for the operation ratio of the air conditioner
not to exceed the setting value. If this function is set to the ACP, the
demand power control function can not be used simultaneously.
Demand / Set the demand power control function by monitoring the
whole power of the indoor unit of the air conditioner at reat time not to
exceed the target power. If this function is set to the ACP, the peak
operation ratio control function can not be used simultaneously.
Monitoring / Monitor the operation and error status of all air
conditioners connected to the ACP.
Error history / View the history of the errors occurred at the air
conditioner connected to the ACP.
Wattage / Wattage consumed at the air conditioner connected to the
ACP.
System setup / Register, change, or delete the information about the
air conditioner and the ventilator connected to the ACP.
2 LG ACCS window buttons
You can exit or minimize the LG ACCS window.
Item
Description
Minimize the LG ACCS window to be displayed at the task bar at the
bottom only.
Not used.
Exit the LG ACCS setup and the LG ACCS window.
Installation/Owner's Manual
3-5
3. ACP operation by using the LG ACCS
3 Message window
It displays the message about the operation information and the error information of the indoor unit of
the air conditioner.
4 Current time window
It displays the current time (year, month, day, day of the week, time).
5 Peak operation ratio control & Network status window
It displays the execution status of the peak operation ratio control mode and the air status of the
network as icon.
Item
Icon
Description
Displayed when the peak operation ratio control mode
is being executed
Peak operation ratio
Displayed when the peak operation ratio control mode
is being stopped
No icon displayed when the peak operation ratio
control is not installed
Displayed when the error is occurred at the network
connection.
Network connection
status
Displayed when the network is successfully connected
and being normally operated.
Displayed when trying to connect the network.
3-6
ACP
3. ACP operation by using the LG ACCS
Controlling the air conditioner
You can use the LG ACCS to control the functions such as selecting the air conditioner group or the air
conditioner, the operation mode, the air flow, the air direction, the lock, the temperature control, and the stop.
The air conditioner control function has the following advantages:
• Manage all installed air conditioiners by using the computer screen with the central control method.
• Easily operate and monitor.
• Perform the integrated management by the group setup.
Click 'Air conditioner' menu at the top of the LG ACCS to control the air conditioner. Click 'Air
conditioner' menu to display the air conditioner control screen as shown at the below.
1
2
3
Installation/Owner's Manual
3-7
3. ACP operation by using the LG ACCS
1 Air conditioner operation status window
It displays the operation status of each air conditioner, the operation mode, the temperature of the
space with the indoor unit installed, and the desired temperature.
Group name & Operation status lamp
The name of the selected group and the status of each air conditioner belonging to the group are
displayed at the top of the air conditioner operation status window.
The operation status of up to 16 air conditioners is displayed at one screen. If there are more than 16
air conditioners installed, press
or
to check the status of the other air conditioners.
The color of the lamp displays the status of the air conditioner. The color displays the air conditioner
status as follows:
Lamp color
(green)
Status
On
Description
The current air conditioner normally operates.
(red)
Blinking
(grey)
On
The current air conditioner stopped.
On
The current air conditioner is under the peak operation
ratio control status.
(yellow)
The current air conditioner has the error occurred.
Operation mode
At the operation mode, if the air conditioner is currently
operating, the operation mode is displayed as icon.
Item
Icon
Description
The current air conditioner performs the cold
operation.
The current air conditioner performs the
dehumidification operation.
Normal operation
The current air conditioner performs the ventilation
operation.
The current air conditioner performs the heating
operation.
3-8
ACP
3. ACP operation by using the LG ACCS
Item
Icon
Description
The current air conditioner is at the peak operation
ratio control status.
Normal operation
The current air conditioner performs the artificial
intellitent operation. The artificial intelligent operation is
the automatic operation for the air conditioner by itself
to set and operate the operation mode and the air flow
of the air conditioner according to the room
temperature.
The current air conditioner has the error occurred.
Error status
The error caused by the network is occurred.
Current & desired temperature
The temperature of the space where the air conditioiner is installed is displayed at the current
temperature. However, if the error lamp is turned ON, the number of the current temperature does not
display the temperature, but the error code.
The desired temperature set at the air conditioner is displayed at the desired temperature. The desired
temperature is not displayed if the air conditioner performs the ventilation or the dehumidification
operatioin or at the error condition.
Installation/Owner's Manual
3-9
3. ACP operation by using the LG ACCS
2 Selecting the air conditioner group or the air conditioner window
This window displays the list of the air conditioner group or the air conditioner set at the system. Also,
the air group and the air conditioner for controlling the air conditioner can be selected.
Select/Deselect All button
[Select All] button and [Deselect All] button are located at
'Group' list and 'Air conditioner' list. It is convenient to select or
deselect all air conditioner groups or air conditioners at the list. However, the air conditioner group and
the air conditioner located at the top of the list are selected as default.
Air conditioner group list & Air conditioner list
The list of the air conditioner group set at the
ACP is displayed at 'Group.' Whe a specific
air conditioner group is selected from the air
conditioner group list, the list of the air
conditioners belonging to the related air
conditioner group is displayed at 'Air
conditioner' located at the right side.
When the air conditioner group to select is
clicked at the list, the related group is
selected, and when it is again clicked, the
selection of the related group is deselected.
Also, more than one group can be selected
by clicking more than one air conditioner
group.
'Air conditioner' displays the list of the air conditioners belonging to a specific air conditioner group of
the ACP.
When you click the air conditioner to select at the list, the related air conditioner is selected, and when
you click it again, the related air conditioner is deselected. Also, you can select more than one air
conditioner by clicking more than one air conditioner.
3-10
ACP
3. ACP operation by using the LG ACCS
3 Controlling & monitoring the air conditioner window
It displays the air conditioner control setting selected from the list of the air conditioner group and the
air conditioner list to control.
Operation mode
The operation method of the air conditioner can be set at the operation mode. The operation modes to
set are as follows:
Item
Description
It operates the cold operation. The cold operation can set the desired
temperature to 18°C ~ 30°C
Note: Setting the desired temperature
Because too much cooling is harmful for health, set the suitable
desired temperature. About 5°C is better for the difference
between the indoor temperature and the outdoor temperature.
If the desired temperature is higher than the indoor temperature
during the cold operation, it does not operate the cold operation,
but the ventilation.
It drives the heating operation. The heating operation can set the
desired temperature to 18°C ~ 30°C
Note: Setting the desired temperature
The excessive heating is harmful for the health, so set the
suitable desired temperature. About 5°C is better for the
difference between the indoor temperature and the outdoor
temperature. If the desired temperature is lower than the indoor
temperature during the heating operation, it does not operate the
heating operation, but the ventilation.
The dehumidification eliminates moisture. It can effectively eliminate
moisture during the rainy season or at the high humidity condition.
When it is selected, the desired temperature can not be set.
It circulates the fresh air. The ventiliation only may be used in Spring
and Autumn. When it is selected, the desired temperature can not be
set.
It evaluates the indoor condition and maintains the optimal condition
automatically.
Installation/Owner's Manual
3-11
3. ACP operation by using the LG ACCS
Air flow
It controls the air flow. The types of air flow to set are as follows:
Air flow
Description
It sets to ventilate with a small of air flow.
It sets to ventilate at the medium level of air flow.
It sets to ventilate at the high level of air flow.
It sets to automatically ventilate at the suitable level of air flow for the
environment with the indoor unit installed.
Air direction
It sets the air direction of the current air conditioner to Up & down or Left & right.
Icon
Description
It executes the air direction operation of the air conditioner.
It stops the air direction operation of the air conditioner.
Lock
It sets the lock function of the air conditioner. When the lock function is set, the air conditioner can not
be controlled by the wirless or wired remote controller. Use the lock function not for the user
individually, but to centrally control the air conditioner
Type
Icon
Description
Control not to set the temperature by using the wireless or wired remote controller.
Temperature lock
Set the temperature lock.
Deselect the set temperature lock.
Control not to set the entire function of the air conditioner by using the
wireless or wired remote controller.
Lock all
Set the Lock All function for the entire air conditioner.
Deselect the set Lock All functioin.
3-12
ACP
3. ACP operation by using the LG ACCS
Desired temperature
Set the desired indoor temperature of the air
conditioner. The desired temperature can be set
by clicking
or
.
The desired temperature can be set for both the
cooling and the heating with the range of
18°C~30°C.
Click
to switch to
for displaying the
temperature. The desired temperature can be
set in Fahrenheit with the range of 64°F~86°F.
Starting & Stopping the operation
Click 'Start' or 'Stop' button to start or stop the air conditioner.
Icon
Description
Operate the air conditioner according to the set value.
Stop the operating air conditioner.
Note: Changing the control setting
After selecting more than one air conditioner with different control conditioin, when the
control setting of the air conditioner is changed, it is applied to all of the currently
operating
air conditioners with the same setting. But, it is not applied to the stopped air
conditioner even when the control setting is changed. However, for the case of the lock
function, it is applied to the stopped air conditioner.
Note: When using each lock function at the Multi model
When using each lock function at the indoor unit (wall mounted, ART COOL, ART
COOL Mirror) model of the Multi model, use the temperature lock, the mode lock and
the airflow lock at a time.
Installation/Owner's Manual
3-13
3. ACP operation by using the LG ACCS
Controlling the ventilator
You can use the LG ACCS to control the functions such as selecting the ventilating group and the
ventilator, the operation mode, the air flow, the additional function and the lock.
The ventilation control function has the following advantages:
• It can centrally control all the installed ventilators by the computer screen.
• It can easily operate and monitor.
• It can perform the integrated control by the group setting.
Click 'Ventilating' menu at the top of the LG ACCS for controlling the ventilator. Click 'Ventilating'
menu to display the following screen for controlling the ventilator.
2
1
3
3-14
ACP
3. ACP operation by using the LG ACCS
1 Select Ventilating group & Ventilator window
The list for the ventilating group and the ventilator set at the system is displayed on this window. Also,
the ventilating group and the ventilator can be selected for controlling the ventilator.
Select & Deselect All button
These buttons are located at 'Group' list and 'Ventilating' list. It is
convenient to select or deselect all of the ventilating groups or
ventilators from the list. However, the ventilating group and the ventilator located at the top of the list
are not deselected, because they are selected as default.
Air conditioner group list and Air conditioner list
The list of the ventilating group set at the
ACP is displayed at 'Group.' When you
select a specific ventilating group from the
ventilating group list, the list of the
ventilator(s) belonging to the related
ventilating group is displayed at 'Ventilator'
located at the right side.
When you click the ventilating group to
select from the list, the related group is
selected, and when you click it again, the
related group is deselected. Also, more than
one group can be selected together by
clicking them. The list of the ventilator(s) belonging to a specific ventilating group of the ACP is
displayed at 'Ventilating.'
When you click the ventilator to select from the list, the related ventilator is selected, and when you
click it again, the related ventilator is deselected. Also, more than one ventilator can be selected
together by clicking them.
Installation/Owner's Manual
3-15
3. ACP operation by using the LG ACCS
2 Ventilator operation status window
This window displays the information such as operation mode of each ventilator, air directioin, lock
feature and additional function.
Group name & Operation status lamp
The name of the selected ventilating group and the status of each ventilator belonging
to the group are displayed with the lamp at the left side of the ventilator operation
status window.
The operation status of up to 12 ventilators is displayed on one screen. When more
than 12 ventilators are set, the status of the other ventilators can be checked by
pressing
or
.
The color of the lamp displays the status of the ventilator. The color displays the ventilator status as
follows:
Lamp color
(green)
Status
On
Description
The current ventilator normally operates.
(red)
Blinking
(grey)
On
The current ventilator stopped.
On
The current ventilator is under the peak operation ratio
control status.
(yellow)
Blinking
The current ventilator has the error occurred.
The current ventilator is sending data.
Operation mode
At the operation mode, if the ventilator is currently operating, the operation mode is
displayed as icon.
The following operation modes are displayed on the screen.
Icon
Description
Operation at the electric heat mode.
Operation at the normal mode.
Operation at the automatic mode.
3-16
ACP
3. ACP operation by using the LG ACCS
Air flow
The air flow from the ventilator is displayed with the icon.
The air flow icons displayed on the screen are as follows:
Icon
Description
Weak air flow.
Strong air flow.
Air flow at maximu.
Automatic air flow according to the indoor environment.
Lock
The Lock function of the ventilator can be set not by the user individually but by
centrally. The icon displays whether the lock function is set or not. The lock icons
displayed on the screen are as follows:
Icon
Description
Weak air flow.
Strong air flow.
Additional functions
Various additional functions can be set to the ventilator. The icon displays whether the
additional function is set or not.
The additional icons displayed on the screen are as follows:
Icon
Description
Poswer saving in operation.
Quick function in operation.
Heater function in operation.
Plasma function in operation.
Note: Additional function
It may not be performed depending on the product.
Installation/Owner's Manual
3-17
3. ACP operation by using the LG ACCS
Filter
The Lock function of the ventilator can be set not by the user individually but by centrally.
The icon displays whether the lock function is set or not. The lock icons displayed on the
screen are as follows:
Icon
Description
It displays when it's time to clean the filter. When this icon is
displayed, the filter should be cleaned.
3 Controlling & Monitoring the ventilator window
This window displays the information such as operation mode of each ventilator, air directioin, lock
feature and additional function.
It displays the control setting of the
ventilator selected from the ventilating
group list and the ventilator list, which
can be controlled.
Operation mode
It can set the operation mode of the ventilator. The operation modes to set are as follows:
Mode
Description
Set both the air supply and the exhaust to be ventilated via the electric
heat exchanger. It is used in Summer and Winter with much difference
of temperature and humidity between the indoor and the outdoor.
Set the exhausting air to be ventilated not via the electric heat
exchanger. It is used in Spring and Autumn with litt difference of
temperature and humidity between the indoor and the outdoor.
Set to automatically maintain the indoor temperature and the outdoor
temperature at the optimum condition by measuring them. The indoor
air balance can be constantly maintained by automatically controlling
the exhaust and the air supply.
3-18
ACP
3. ACP operation by using the LG ACCS
Air flow
It controls the air flow. The types of air flow to set are as follows:
Air flow
Description
It sets to ventilate with a small of air flow.
It sets to ventilate at the high level of air flow.
It sets to ventilate at the highest level of air flow.
It sets to automatically ventilate at the suitable level of air flow for the
environment with the indoor unit installed.
Additional functions
Various additional functions can be set to the ventilator. The types of additional functions to set are as follows:
Icon
Description
It performs the power saving function. It finds out the best efficiency of
the ventilator and operates it to save the consumed power.
It performs the quick ventilation. It prevents the polluted air or moisture
of the indoor from being dispersered to other rooms.
It performs the heater function. It heats the air in Winter.
It is the air cleaning function supplying anion to refresh. It treats virus
or fungus as well as influenza (representative cold virus) in the room by
considering the health as well as the environment.
Note: Additional function
It may not be performed depending on the product.
Installation/Owner's Manual
3-19
3. ACP operation by using the LG ACCS
Lock
It sets the lock function of the ventilator. When the lock function is set, the ventilator can not be
controlled by the wirless or wired remote controller. Use the lock function not for the user individually,
but to centrally control the ventilator.
Icon
Description
Set the ventilator lock.
Deselect the ventilator lock.
Starting & Stopping the operation
Click 'Start' or 'Stop' button to start or stop the selected ventilator.
Button
Description
Operate the ventilator according to the set value.
Stop the operating ventilator.
Note: Changing the control setting
After selecting more than one ventilator with different control conditioin, when the
control setting of the ventilator is changed, it is applied to all of the currently operating
ventilators
with the same setting. But, it is not applied to the stopped ventilator even when the
control setting is changed. However, for the case of the lock function, it is applied to
the stopped ventilator.
3-20
ACP
3. ACP operation by using the LG ACCS
Setting the schedule
It is the function to perform the reserved operation at the specified time by specifying the operation of
the air conditioner. For example, for the case of the school, the air conditioner automatically strats and
stops at the specified time by setting the schedule to attending school and returning home.
The unnecessary operation and management cost of the air conditioner can be reduced by this
schedule function, and it can effectively save the energy because it is used only when necessary.
Note: Saving after the system setup
Be careful to change the system information at 'System setup' menu and save it
because it initializes all schedule information.
Reference: Schedule maintenance time
When setting the schedule, 1~3 minute schedule setting is maintained for time the actual schedule
is set.
For example, when you set the schedule for the unit to be turned off at 5:00, the operation is turned
off from 5:00 to 5:03. Therefore even when you try to operate the unit with the wired remote
controller, it may be turned off.
Reviewing the schedule setup screen
Click 'Schedule' menu at the top of the LG ACCS for setting the schedule. Click 'Schedule' menu to
display the schedule setup screen as follows:
4
6
2
3
1
5
Installation/Owner's Manual
3-21
3. ACP operation by using the LG ACCS
1 Pattern setup button and Mode change button
The schedule set by the user should be stored and applied as pattern. The setup mode and the view
mode are classified at the schedule menu to minimize the maloperation of the user.
Pattern setup button
The schedule set by the user should be stored and applied as pattern. The setup mode and the view
mode are classified at the schedule menu to minimize the maloperation of the user.
Click [Pattern setup] button to display the
Pattern setup window to set the pattern.
Each pattern saves the weekly schedule set,
edited and saved by the user. If there is no
change after applying the schedule,
following schedule that has been set
(pattern) will be applied repeatedly in the
following week.
If you save the pattern and select the right schedule before operating the schedule, you can operate
and apply the schedule. Maximum of 10 patterns can be saved and can be utilized as shown in the
following examples.
• Pattern 1: Save schedule pattern mainly used in spring/fall
• Pattern 2: Save schedule pattern mainly used in summer
• Pattern 3: Save schedule pattern mainly used in winter
• Pattern 4: Save schedule pattern used only in the morning at school during summer vacation
When the user does not designate the pattern, the default pattern of 'Pattern 1' is selected.
To delete the pattern, select the pattern and click on the [Delete] button. The schedule detail saved in
the applicable pattern will be initialized.
3-22
ACP
3. ACP operation by using the LG ACCS
Mode change button
The schedule set by the user should be stored and applied as pattern. The setup mode and the view
mode are classified at the schedule menu to minimize the maloperation of the user.
When [View mode] button is displayed at the bottom of 'Schedule' menu,
the current schedule is set to the view mode. The schedule can not be set
and saved at the view mode, and the functions only for checking the set
schedule and applying it to the system can be performed.
It'd better use this mode except setting the schedule.
When [Setup mode] button is displayed at the bottom of the 'Schedule'
menu, the current schedule is set to the setup mode. At the setup mode,
the functions such as setting and saving the schedule can be performed,
but the schedule can not be applied to the system. Use this mode only for
setting the schedule.
Note: Checking whether to save when changing the mode
When the mode is change to the view mode during setting the schedule, all schedules
being setting are cancelled. Before changing to the view mode, decide whether to save
the schedule or not.
Installation/Owner's Manual
3-23
3. ACP operation by using the LG ACCS
2 Select Air conditioner group & Air conditioner window
It displays the list of the air conditioner group and the air conditioner set at the system. Also, the air
conditioiner group and the air conditioner can be selected for setting the schedule.
Select & Deselect All button
The schedule set by the user should be stored and applied as pattern. The setup mode and the view
mode are classified at the schedule menu to minimize the maloperation of the user.
These buttons are located at 'Group' list and 'Air conditioner' list.
It is convenient to select or deselect all of the air conditioner
groups or air conditioners from the list. However, the air conditioner group and the air conditioner
located at the top of the list are not deselected, because they are selected as default.
Air conditioner group list and Air conditioner list
The list of the air conditioner group and the air
conditioner set at the ACP is displayed at
'Group' and 'Air conditioner.' When you select
a specific air conditioner group from the air
conditioner group list, the list of the air
conditioner(s) belonging to the related air
conditioner group is displayed at 'air
conditioner' located at the right side.
If the schedule menu operates at the setup
mode, when you click the air conditioner group
or the air conditioner to select from the list, the
related group or the air conditioner is selected,
and when you click it again, the related group
or air conditioner is deselected.
More than one air conditioner group or air conditioner can be selected together by clicking them.
However, at the view mode, only one group or air conditioner can be selected.
3-24
ACP
3. ACP operation by using the LG ACCS
3 Schedule control setup window
It displays the list of the air conditioner group and the air conditioner set at the system. Also, the air
conditioiner group and the air conditioner can be selected for setting the schedule.
At this window, the operation can be set for
the air conditioner to be controlled at the
specified time according to the schedule.
The following operations can be controlled.
Operation mode
The operation method of the air conditioner can be set at the operation mode. The operation modes to
set are as follows:
Item
Description
It operates the cold operation. The cold operation can set the desired
temperature to 18°C ~ 30°C.
Note: Setting the desired temperature
Because too much cooling is harmful for health, set the suitable
desired temperature. About 5°C is better for the difference
between the indoor temperature and the outdoor temperature.
If the desired temperature is higher than the indoor temperature
during the cold operation, it does not operate the cold operation,
but the ventilation.
It drives the heating operation. The heating operation can set the
desired temperature to 18°C ~ 30°C.
Note: Setting the desired temperature
The excessive heating is harmful for the health, so set the
suitable desired temperature. About 5°C is better for the
difference between the indoor temperature and the outdoor
temperature. If the desired temperature is lower than the indoor
temperature during the heating operation, it does not operate
the heating operation, but the ventilation.
The dehumidification eliminates moisture. It can effectively eliminate
moisture during the rainy season or at the high humidity condition.
When it is selected, the desired temperature can not be set.
It circulates the fresh air. The ventiliation only may be used in Spring
and Autumn. When it is selected, the desired temperature can not be
set.
Installation/Owner's Manual
3-25
3. ACP operation by using the LG ACCS
Air flow
It controls the air flow. The types of air flow to set are as follows:
Air flow
Description
It sets to ventilate with a small of air flow.
It sets to ventilate at the medium level of air flow.
It sets to ventilate at the high level of air flow.
It sets to automatically ventilate at the suitable level of air flow for the
environment with the indoor unit installed.
Air direction
It sets the air direction of the current air
conditioner. It can set the direction of the air
conditioner to be changed to left & right or up &
down.
Click [Air direction setup] button to display the
window to set the air direction. When you set the
air direction and click [Done] butto, the air
direction is set.
Lock
It sets the lock function of the air conditioner.
When the lock function is set, the air conditioner
can not be controlled by the wirless or wired
remote controller. Use the lock function not for
the user individually, button to centrally control
the air conditioner.
Click [Lock setup] button to display the window to
set the Lock function. When you set the Lock
function and click [Done] button, the lock function
is set.
3-26
ACP
3. ACP operation by using the LG ACCS
Desired temperature
Set the desired indoor temperature of the air conditioner. The desired temperature can
or
be set by clicking
. The desired temperature can be set for both the cooling
and the heating with the range of 18°C ~ 30°C.
The desired temperature can not be set at the Dehumidification mode and the Ventilation
mode.
4 Weekly operation schedule display window
It displays the weekly operation schedule and the operation time. Also, it can handle the specific date
as exceptional schedule.
Operation time display
It displays the operation start time and the
operation stop time of the period selected
from the weekly operation schedule table.
Schedule display window
At the view mode, the current set schedule is
displayed at the schedule display window.
However, at the setup mode, the period to set
the schedule can be selected.
One column of the display window corresponds
to 10 minutes, and, at the setup mode, more
than one period can be deleted by clicking the
set period again.
The time with the schedule set is displayed in
sky blue while the period selected by clicking is
displayed in green.
When you select the period with the schedule
set, the setting of the related schedule is
displayed at the schedule control setup window
at the left of the screen.
Installation/Owner's Manual
3-27
3. ACP operation by using the LG ACCS
5 Save the setting button & Apply/Cancel the schedule button
Use [Delete All] or [Save the setting] button to initialize the schedule or set and save the schedule at
the system. Also, [Apply the schedule] and [Cancel the schedule] buttons are used to apply and
cancel the saved schedule to the system.
Delete All button
Click [Delete All] button to delete all schedule information being
edited at the setup mode. Also, all schedule time information
displayed at the schedule display window are deleted.
Save the setting button
It saves the information set at the schedule screen. All set information
can be saved only by clicking [Save the setting] button. Especially, if
you click [View mode] button without pressing this button to save after
setting the schedule at the setup mode, the schedule information set
up to now may be cancelled, so be carefull.
Apply & Cancel the schedule button
Click [Apply the schedule] button to apply the schedule saved
as pattern to the system to be performed. Because applying
the schedule is not performed at the setup mode on the
system screen, this button cannot be pressed. When the
schedule is applied, it is changed to the pattern name with
[Pattern setup] button applied, and [Apply schedule] button is
changed to [Cancel the schedule] button.
When you click [Cancel the schedule] button, the schedule
operation currently being operated is stopped. Also, the button
displaying the applied schedule pattern is changed to [Pattern
setup] button.
3-28
ACP
3. ACP operation by using the LG ACCS
6 Exception handling schedule button
It is the function excluding the specified date
from the set weekly operation schedule. The
other schedule can be set to the excluded date
suitable to the related date.
When you click [Exception handling schedule]
button, the exception handling schedule
screen is displayed as shown at the left. At this
time, [Exception handling schedule] button is
changed to [Exit the exception handling]
button.
In order to exit from the exception handling
schedule screen to the previous screen, press
[Exit the exception handling] button.
Exception handling schedule & Exit the exception handling button
When you click [Exception handling schedule] button, the
exception handling schedule screen to set the exception handling
schedule is displayed. At this time, [Exception handling schedule]
button is changed to [Exit the exception handling] button.
When you click [Exit the exception handling] button, it exits the
current exception handling schedule screen and returns to the
schedule setup screen. At this time, [Exit the exception handling]
button to [Exception handling schedule] button.
Installation/Owner's Manual
3-29
3. ACP operation by using the LG ACCS
Exception handling list
The exception handling list displays the
currently set exception handling schedule.
Date selection window
You can enter the date to set the exception
handling schedule and the title, and add a new
one or delete/find the existing exception handling
schedule.
In order to set the exception handling schedule,
use
,
button at the Select date window to
select the year and the month.
When you enter the title for the exception handling
schedule into 'Title input' field and click [Add]
button, the exception handling date is displayed on
the screen. And then, when you click [Save]
button, the related setting is applied to the system.
In order to delete the existing setting, after specifying the related data at the calendar, when the
exceptional schedule title to delete is displayed at 'Title input' field, click [Delete] button. And then,
when you click [Save] button, the related schedule is deleted from the system.
When you specify the exception handling title at the Date selection window and click [Find] button, the
related exception handling schedule is displayed at the exception handling schedule display screen at
the right of the screen.
3-30
ACP
3. ACP operation by using the LG ACCS
Exception handling schedule display window
The method to specify the schedule at the exception handling date is same
to the general schedule setup.
At the view mode, the schedule about the exception handling schedule is
displayed at the exception handling schedule display window. While, at the
setup mode, you can select the period to set the exception handling
schedule.
In order to schedule for the exception handling schedule, you should check
the exception handling schedule at the exception handling list and specify
the related data at the Date selection window.
Make sure that the title of the exception handling schedule is displayed at
'Title input' field of the Date selection window and the related date is
displayed at 'Schedule' item at the exception handling schedule display
window. If the date is not displayed, you should specify the exception
handling schedule by the Date selection window first.
One column of the display window corresponds to 10 minutes, and, at the
setup mode, more than one period can be deleted by clicking the set period
again.
You can delete the priod by clicking the period again.
The time with the exception handling schedule set is displayed in sky blue
while the period selected by clicking is displayed in green.
When you select the period with the exception handling schedule set, the
setting of the related schedule is displayed at the schedule control setup
window at the left of the screen.
Stop All window
It can stop all air condition system at the specified
time. It is optional, so it is not the essential item to
be set for setting the exception handling schedule.
In order to perform this function, click [Setup] radio
button, set the time, and click [Done] button. But, in
order to deselect this function, click [Deselect] radio button and then [Done] button.
It has the priority higher than the schedule or the exception handling schedule, so all air conditioners
are stopped at the specified time even when the air conditioner operates according to the schedule.
However, it operates only when the specified schedule is applied and operates (it does not operate at
the schedule stopped condition).
Installation/Owner's Manual
3-31
3. ACP operation by using the LG ACCS
Example for setting the schedule
This section describes the method for setting the schedule and the exception handling schedule
based on the group with the name '1st grade.'
Setting the schedule for the 1st grade class
The following example shows the procedure for applying the following setting to the system as
schedule.
• Target group: '1st grade' group
• Time: 9~11, 1~3 a.m.
• Operation: Cooling, Air flow 'Middle', Temperature '23°C', Lock function set
• Saving pattern: Pattern5
1. When you click 'Schedule' menu at the LG ACCS screen, the following screen is displayed. Click
[View mode] button to switch to the schedule setup mode. When you click [View mode] button, it is
switched to the setup mode and the [View mode] button is changed to [Setup mode] button.
Chick View mode to switch
to Setup mode
3-32
ACP
3. ACP operation by using the LG ACCS
2. Specify the pattern to save the schedule. In this example, the schedule is specified to the Pattern5.
Click [Pattern setup] button, click Pattern5' item at the displayed Pattern setup' window, and click
[Set] button. If the pattern is not selected, it is saved at Pattern1' as default.
Click 'Pattern5' and the
[Set] button
3. Now, select the target to which the schedule is applied. Here, because it is applied to all '1st grade'
group, all air conditioners are selected by pressing [Select All] button.
Select the group. and click
[Select All] button to
specify all
Installation/Owner's Manual
3-33
3. ACP operation by using the LG ACCS
4.
Now, specify the operation for the schedule to perform. Set 'Cooling operation' as operation,
'Middle' as air flow, and '23°C as desired temperature.
Specify the schedule operation
(Cooling, Middle air flow.
Desired temperature 23°C)
5. Set the Lock function for the user not to individually set the air conditioner. When you click [Lock
setup] button, the Lock setup window to set the lock function is displayed. Click 'Set' radio button
and then [Done] button.
After clicking [Lock setup] button,
select 'Set' at the Lock setup
window. Click [Done] button.
3-34
ACP
3. ACP operation by using the LG ACCS
6. Select the time to apply the schedule. At the schedule setup window at the right side of the screen,
select '9~11 a.m.' and '1~3 p.m.' from Monday to Friday by clicking or dragging.
Specify the schedule time
by clicking or dragging
7. Now, press [Save the setting] button to save the set schedule. When you click [Save the setting]
button, the window to confirm saving is displayed. Click [Done] button to save the schedule.
After elicking [Save the
setting] button, click [Done]
button when confirming to
save
Installation/Owner's Manual
3-35
3. ACP operation by using the LG ACCS
8. Now, press [Setup mode] button to switch to the view mode. When you click each air conditioner
name of the 1st grade, you can find that the same schedule is applied to each group. Also, you can
find wich operation is set by clicking the schedule time.
You can check the schedule
by clicking the air conditioner
You can check the setting
by clicking the schedule
Screen switched to the view mode
by clicking [Setup mode] button
9. When you click [Apply the schedule] button, the set schedule operates. [Apply the schedule] button
is changed to [Cancel the schedule] button. [Pattern setup] button is displayed with the currently
applied pattern number.
It shows that the [Pattern]
is applied and operates
3-36
ACP
The schedule operates by
clicking the [Apply the
schedule]button
3. ACP operation by using the LG ACCS
Setting the exception handling schedule
The method to set the exception handling schedule is similar to the method to set the schedule. The
following example shows the procedure for applying the following exception handling schedule to the
system.
• Target group: '1st grade' group
• Date: 2007. 7. 6.
• Exception handling title: 'Discretional holiday'
• Time: 9~12 a.m.
• Operation: Cooling, 'Weak' as air flow, '25°C' as temperature
• Total stopped time: 12:00
1. When you click [Exception handling schedule] button at 'Schedule' menu screen, the screen to set
the exception handling is displayed. At this time, the [Exception handling schedule] button is
changed to [Exit the exception handling] to exit from setting the exception handling schedule.
Click [Excetion handling
schedule] button to display
the exception handling setup
window
[Exception handling
schedule] button is changed
to [Exit the exception
handling] button
Installation/Owner's Manual
3-37
3. ACP operation by using the LG ACCS
2. Select the data for adding the exceptional date from the calendar. And then, when you enter the
exceptional schedule titlem into 'Title input' field and click [Add] button, the exception schedule is
added to the list. Here, the exception schedule with the title 'Discretional holiday' to 2007.7.6.
Select the date from the
calendar
Enter the exception handling
schedule title, and click [Add]
button
The added schedule is
displayed at the list.
3. The exception schedule title is added to the list, but it is not saved at the system. Click [Save]
button to save the exception handling title at the system. If you do not click [Save] button, the
related information is deleted when switching to the other screen.
Press [Save] button to
save the exception
schedul
3-38
ACP
3. ACP operation by using the LG ACCS
4. Now, apply the schedule to the exception handling schedule. First, check the date at the exception
handling schedule list, and then select the date from the calendar. The related exception handling
schedule title is displayed at 'Title input' field, and make sure that the related date is displayed at
'Schedule' field.
Check
'Schedule' field
After checking the
exception handling
schedule from the list,
click the related date from
the calendar.
Check 'Title input' field.
5. Click [View mode] button to switch to the schedule setup mode. When you click the [View mode]
button, it is switched to the setup mode and [View mode] button to [Setup mode] button.
Changed from View
mode to Setup mode
Installation/Owner's Manual
3-39
3. ACP operation by using the LG ACCS
6. Select the target to which the exception handling schedule is applied. Here, because it is applied to
all '1st grade' group, all air conditioners are selected by pressing [Select All] button.
Select the group, and
click [Select All] button to
specify all
7. Now, specify the operation for the schedule to perform. Set 'Cooling operation' as operation, 'Weak'
as air flow, and '25°C as desired temperature.
Specify the schedule operation
(Cooling, Weak air flow, Desired
temperature 25°C)
3-40
ACP
3. ACP operation by using the LG ACCS
8. Select the time to apply the schedule. At the schedule setup window at the right side of the screen,
select '9~12 a.m.' by clicking or dragging.
Specify the schedule time
by clicking or dragging
9. Set to stop all air conditioners at 12:00. Set '12:00' at 'Stop All' item and click [Done] button.
After setting 'Stop All'
time, click [Done]
button.
Installation/Owner's Manual
3-41
3. ACP operation by using the LG ACCS
10. Now, press [Save the setting] button to save the set exception handling schedule. When you click
[Save the setting] button, the window to confirm saving is displayed. Click [Done] button to save
the exception handling schedule.
After clicking [Save the setting]
button, click [Done] button when
confirming to save
11. Now, press [Setup mode] button to switch to the view mode. When you click each air conditioner
name of the 1st grade, you can find that the same schedule is applied to each group. Also, you
can find wich operation is set by clicking the schedule time.
You can check the
schedule by clicking the
air conditioner
Screen switched to the view mode
by clicking [Setup mode] button
3-42
ACP
3. ACP operation by using the LG ACCS
12. When setting the exception handling schedule is completed, click [Exit the exception handling]
button to close the exception handling setup window and return to the previous schedule view
screen.
Click [Exit the exception
handling] button to return to
the previous screen
Installation/Owner's Manual
3-43
3. ACP operation by using the LG ACCS
Controlling the peak operation ratio
It maintains the consumed power to be kept lower than or equal to the target power by monitoring the
wattage of the air conditioner. It can control to save the energy by forcefully starting or stopping the air
conditioner according to the specified peak operation rule.
It has the following advantages:
• Centrally control all installed air conditioners by using the computer screen.
• Monitor and control the peak operation ratio for 24 hours a day.
• Easily perform controlling and monitoring.
• Set the peak control function by wattage (kW) or operation ratio (%).
• Control the operation switching period (5~15 minutes) of the air conditioner.
• Set the exceptional air conditioner not to apply the peak operation ratio control function.
Note: Peak operation ratio control & Demand control
The ACCS offers the peak operation ratio control function and the demand control function to
reduce the power cost by operating all air conditioners less than or equal to the permitted demand
power. One of the peak operation ratio control function or the demand power control function can
be used depending on the function setting of the ACP, but two functions cannot be used together.
This section describes the method for controlling the peak operation ratio. For more information
about the demand control function, see Chapter 3. 'Controlling the demand power'.
The air conditioner forcefully operating by the peak operation ratio control function operates at the
ventilating mode during the cooling operation while the operation stops during the heating operation.
But, the user's inconvenience due to setting the peak operation period is minimized.
When the air conditioner forcefully operates by the peak operation ratio control function, the air
conditioiner cannot be individually managed because the automatic central control is used. However,
when the current operation uses the power less than or equal to the target operation ratio setting, the
air conditioner can be individually managed.
Caution: When the ACP is interconnected with the AC Manager
When the ACP is interconnected with the AC Manager, set Demand as ACP setting.
The ACP operates according to the demand setting of the AC Manager.
3-44
ACP
3. ACP operation by using the LG ACCS
In order to control the peak operation ratio, click 'Peak power' menu at the top of the LG ACCS. When
you click 'Peak power' menu, the following air conditioner control screen is displayed.
1
3
4
2
5
6
Note: When there is no peak power menu
If the ACCS menu does not have 'Peak power' menu but 'Demand' menu, it is set for the setting of
the ACP to use the demand power control function. In order to use the peak power control function,
change the setting of the ACP by referring to Chapter 2. “Setting the ACP functions – Selecting
Peak or Demand.”
Caution: When the peak power function is used
When the peak power function is used, the function should be used or set after the
current information about 'Current operation ratio/Current power' and 'Operation stats'
item. The wattage information may be delaed to be displayed according to the network
environment.
Installation/Owner's Manual
3-45
3. ACP operation by using the LG ACCS
1 Wattage monitor
The following peak control setting information and operation information are displayed at the wattage
monitor.
• Function operation status
• Current wattage and operation ratio
• Desired wattage and operation ratio
• Operation switching period
Function operation information
At the function operation status, the operation status of the current peak control is displayed.
The types of the displayed operation status are as follows:
Operation status
Description
Displayed when the current wattage is higher than the setting value of
the peak operation ratio control function. In this case, the air conditioner
operates at the condition to start or stop with the peak operation period
according to the peak operation ratio control function.
Displayed when the peak operation ratio control function is stopped.
Displayed when the setting value of the peak operation ratio control
function is higher than the wattage. In this case, the air conditioner can
not be operated or stopped with the peak operation period and operates
at the condition for monitoring that the wattage is getting higher than the
setting value.
Current wattage and operation ratio
It displays to which percentage of the entire operation ratio the
operation ratio of the current air conditioner reaches. Also, it
displays the current wattage in kW.
Desired wattage and operation ratio
It displays to which percentage of the entire air conditioner
operation ratio the operation ratio of the desired air conditioner
reaches. Also, it displays the desired wattage in kW per hour.
3-46
ACP
3. ACP operation by using the LG ACCS
Operation switching period
It displays the period for stopping the peak operation. For example, if it is set to 5
minutes period, the air conditioners with the peak operation are switched every 5
minutes, which controls the time for all air conditioners to stop constantly.
The operation switching period can be controlled within the range of 5~15 minutes.
2 Setting the current operation status and the power control (graph)
The graph for displaying the current operation status and
setting the power control function is displayed at the left
side of the peak operation ratio control screen. The operator
can use this graph to check the power when all current
installed air conditioners operate 100% and to set the target
power.
In order to change the peak operation ratio, drag
the target power.
to set
Note: Changing the peak operation ratio
In order to change the peak operation ratio, except the method using
number input method described at the following section.
, it can be set by the
Installation/Owner's Manual
3-47
3. ACP operation by using the LG ACCS
3 Setting the power control (text)
The setup item to set the wattage in kW or % is
displayed at the right side of the peak operation ratio
control screen.
If it exceeds the setting value, the air conditioner
operates with the peak operation function periodically
according to the peak power operation rule.
Desired power
It sets the desired wattage in kW per hour to operate the peak
operation function. It can be adjusted to the half of the
maximum usage by 1kW.
When the value is set by kW, the desired operation ratio(%) is
also changed according to the setting value.
Desired operation ratio
It sets the desired wattage in percentage to operate the peak
operation function. It can be set within the range of 0~100% of
the maximum wattage, which can be controlled by 1%.
When the value is set by %, the desired power (kW) is
changed according to the setting value.
Operation switching period
It sets the peak operation period. It can be set within the range
of 5~15 minutes, which can be controlled by 1 minute.
3-48
ACP
3. ACP operation by using the LG ACCS
4 Peak excluded air conditioner
Press [Peak excluded air conditioner] to set the air conditioner not to apply
the peak operation control function. When you click [Peak control air
conditioner] button, the following setup screen is displayed.
In order to set the air conditioner not to apply the peak operation control function, select the air
conditioner at 'All air conditioners' at the left side of the setup screen, and click [Exclude] (
)
button. The related air conditioner is displayed at 'Peak excluded air conditioner' at the right side of the
screen.
However, in order to apply the peak operation control functioin to the air conditioner, select the air
conditioner from 'Peak excluded air conditioner', and press [Apply] (
) button. The related air
conditioner is displayed at 'All air conditioners' at the left side of the screen.
Note: Changing the setting value of the desired wattage and
operation ratio
The setting values of the desired wattage and the desired operation ratio are changed according to
the setting of the peak excluded air conditioner. As the number of the peak excluded air
conditioners is getting higher, the number of air conditioners individually operated by the user may
be getting higher. In this case, the other air conditioners not peak excluded may operate more
frequently.
Caution: Initializaing the peak excluded air conditioiner
When you execute 'Save' after setting the system information at 'System setup' menu,
the existing information of the peak excluded air conditioner is initialized, so be careful.
Installation/Owner's Manual
3-49
3. ACP operation by using the LG ACCS
5 Saving the setting
It saves the setting values of the peak operation
ratio control up to now.
When you press [Save] button, the window to
conform saving is displayed. When you want to
save the setting, click [Done] button, but click
[Cancel] button to cancel.
Note: Setting the peak
Set the peak at the peak operation condition, or perform the peak operation after setting the peak.
After setting the peak, if the peak operation is not performed, the actual peak operation ratio is not
set.
6 Starting & stopping
It starts the peak operatioin ratio control function. When the peak operation ratio
control is being operated, the button is displayed in green.
It stops the peak operation ratio control function. When the peak operation ratio
control is stopped, the button is displayed in green.
3-50
ACP
3. ACP operation by using the LG ACCS
Controlling the demand power
It maintains the consumed power to be kept lower than or equal to the target power by monitoring the
wattage of the air conditioner. It can control to save the energy by using the demand controller
connected to the ACP forcefully to start or stop the air conditioner.
It has the following advantages:
• Precise management by controlling the automatic operation ratio of the air conditioner with the
demand controller.
• Monitor and control the peak power for 24 hours a day.
• Easily perform controlling and monitoring.
Note: Peak operation ratio control & Demand control
The ACCS offers the peak operation ratio control function and the demand control function to
reduce the power cost by operating all air conditioners less than or equal to the permitted demand
power. One of the peak operation ratio control function or the demand power control function can
be used depending on the function setting of the ACP, but two functions cannot be used together.
This section describes the method for controlling the demand power. For more information about
the peak operation ratio function, see Chapter 3. 'Controlling the peak operation ratio'.
When the air conditioner forcefully operates by the demand power control function, the air conditioiner
cannot be individually managed because the automatic central control is used. However, when the
current operation uses the power less than or equal to the target operation ratio setting, the air
conditioner can be individually managed.
Installation/Owner's Manual
3-51
3. ACP operation by using the LG ACCS
In order to control the demand power, click 'Demand power' menu at the top of the LG ACCS. When
you click 'Demand power' menu, the following air conditioner control screen is displayed.
1
2
3
Note: When there is no demand menu
If the ACCS menu does not have 'Demand' menu but 'Peak power' menu, it is set for the setting of
the ACP to use the peak control function. In order to use the demand power function, change the
setting of the ACP by referring to Chapter 2. “Setting the ACP functions – Selecting Peak or
Demand.”
3-52
ACP
3. ACP operation by using the LG ACCS
1 Wattage monitor
The following demand control setting information and operation information are displayed at the
wattage monitor.
• Function operation status
• Current wattage and operation ratio
• Desired wattage and operation ratio
• Operation switching period
Function operation information
At the function operation status, the operation status of the current demand control is displayed. The
types of the displayed operation status are as follows:
Operation status
Description
Displayed when the current wattage is higher than the setting value of
the demand control function. In this case, the air conditioner operates at
the condition to start or stop according to the demand control function.
Displayed when the demand control function is stopped.
Displayed when the setting value of the demand control function is
higher than the wattage. In this case, the air conditioner can not be
operated or stopped and operates at the condition for monitoring that
the wattage is getting higher than the setting value.
Current wattage and operation ratio
It displays to which percentage of the entire operation ratio the
operation ratio of the current air conditioner reaches. Also, it
displays the current wattage in kW.
Desired wattage and operation ratio
It displays to which percentage of the entire air conditioner
operation ratio the operation ratio of the desired air conditioner
reaches. Also, it displays the desired wattage in kW per hour.
Installation/Owner's Manual
3-53
3. ACP operation by using the LG ACCS
Operation switching period
It displays the period for stopping the peak operation. For example, if it is set to 5
minutes period, the air conditioners with the peak operation are switched every 5
minutes, which controls the time for all air conditioners to stop constantly.
The operation switching period can be controlled within the range of 5~15 minutes.
2 Setting the current operation status and the power
The graph for displaying the current operation status and setting the
power control function is displayed at the left side of the demand
control screen. The operator can use this graph to check the power
when all current installed air conditioners operate 100% and to check
the set target power.
Caution: Setting the demand control
Because the demand control is set by the externally connected demand controller, the
items such as desired power, desired operation ratio and operation switching period
can not be set wihin the LG ACCS program.
3-54
ACP
3. ACP operation by using the LG ACCS
3 Setting the power control (text)
The setup item to set the wattage in kW or % is displayed at the right
side of the peak operation ratio control screen.
If it exceeds the setting value, the air conditioner is forcefully operated
periodically according to the peak power operation rule.
Desired power
It displays the desired power in kW per hour to operate the
peak operation function.
Desired operation ratio
It displays the desired power in % to operate the peak
operation function.
Operation switching period
It displays the period to forcefully stop the operatioin.
Caution: Setting the demand control
Because the demand control is set by the externally connected demand controller, the
items such as desired power, desired operation ratio and operation switching period
can not be set wihin the LG ACCS program.
Installation/Owner's Manual
3-55
3. ACP operation by using the LG ACCS
Monitoring the air conditioner status
You can see the operation status and the error status of each air conditioner set all air conditioner
groups at the LG ACCS at a glance. In order to view the status information of the air conditioner,
click 'Monitoring' menu at the top of the LG ACCS. When you click 'Monitoring' menu, the following
monitoring screen is displayed.
The following information is displayed at the monitoring screen.
Item
Air conditioner name
Operation mode
Air flow
Air direction
Lock all
3-56
ACP
Description
Name of air conditioner currently registred at the system.
Operation mode of set air conditioner.
Air force of set air conditioner.
Whether to set the air direction or not.
Whether to set Lock All or not.
3. ACP operation by using the LG ACCS
Item
Description
Temperature lock
Whether to set the temperature lock function or not.
Room temperature
The indoor temperature of the place where the current air conditioner is installed.
Desired temperature
The desired temperature to set the indoor temperature.
Start/Stop
The operation status of the air conditioner.
Remarks
The error code is displayed if the error is occurred.
- Network Error (NE)
- System Error (SE)
Installation/Owner's Manual
3-57
3. ACP operation by using the LG ACCS
Reviewing the error history
The LG ACCS saves and records the information of the error occurred from all indoor units of the air
conditioners connected to the ACP. You can see this error history at 'Error history' menu of the LG
ACCS.
In order to view the error history of the air conditioner, click the 'Error history' menu at the top of the
LG ACCS. When you click 'Error history' menu, the following error history screen is displayed.
2
1
3
3-58
ACP
3. ACP operation by using the LG ACCS
1 Querying the error history
You can set and query the information about the error occurred
within the desired period. The start date and the end date of the
period to query can be set by pressing each calendar button
(
) within the query period.
After setting the query period, when you click the [Query] button
(
), the information about the error occurred within
the period is displayed.
2 Saving and Printing
[Confirm to delete] button is used to safely delete the error displayed at the error
history list within the system. After pressing
button to delete the error
displayed at the error history list, press [Confirm to delete] button to completely
delete the related error within the ACP. If [Confirm to delete] button is not pressed
after pressing
button to delete the error, it is deleted from the current screen
but it will be again displayed at the later error search.
When you press [Print] button, the queried error history can be saved as the file with
the Excel format.
Installation/Owner's Manual
3-59
3. ACP operation by using the LG ACCS
3 Error history list
It displays the history list of
the errors occurred within the
query period.
Item
Description
The type of occurred error is displayed as icon.
Icon
Error occurred from the network.
Error occurred from the system (outdoor & indoor unit).
Date
Date when the error was occurred.
Time
Time when the error was occurred.
Index
Address of the indoor unit of air conditioner (the last digit of the physical address)
Air conditioner name
3-60
Name of group and air conditioner with the error occurred.
Error code
Code number for the occurred error.
Contents
Description for the occurred error.
ACP
3. ACP operation by using the LG ACCS
Reviewing the wattage (incteconnecting with the power display)
The LG ACCS offers the power display interconnection function to check and manage the wattage of
all indoor units of the air conditioners connected to the ACP. If this function is used, when the outdoor
unit is shared with officetel, residential-commercial building, and school, it can be effectively controlled
because the wattage for each indoor unit is displayed.
Because the power display interconnection function remotely reads the wattage without the separate
inspection program, it can easily check the wattage on which the billing can be done.
Caution: Power display interconnection
In order to use this function, the wattmeter should be interconnected with the PI385
connected to the ACP. For the power display interconnection function, the ACP and
the wattmeter should be connected to the PI485 via the BUS. For more information
about installing and using the wattmeter and the PI485, see the manual of the related
product.
AC Manager
Outdoor Unit
LG-NET 1
LG-NET 2
1
2
DI
LG-NET 3
3
4
LG-NET 4
5
TX
RX
TX
RX
TX
RX
TX
RX
6
7
8
FDD
9
10
11
12
13
14
15
16
17
18
19
20
Ext.
MENU/
SELECT
ACT
LNK
Ethernet 2
ACT
LNK
Console
1
2
DO
TX
RX
TX
RX
Ethernet 1
TX
RX
Run
3
Power
4
Indoor Unit
ACP
Power display
Wattmeter
Installation/Owner's Manual
3-61
3. ACP operation by using the LG ACCS
In order to use the power display interconnection function to check the wattage, click 'Wattage' menu
at the top of the LG ACCS. When you click 'Wattage' menu, the following wattage screen is displayed.
1
3
2
1 Wattage monitor
The wattage monitor displays the total wattage of the air conditioner groups connected to the ACP and
the wattage for each group.
2 Wattage by group list
The wattage can be queried by group. The wattage within the specific period set by the user is
classified and displayed by group.
3-62
ACP
3. ACP operation by using the LG ACCS
Displaying the wattage query period
It displays the query period set by the user. Press the print button (
period to print the displayed wattage by group with the Excel format.
) at the right side of the query
Group list
It displays the list of the groups set at the system.
Wattage by indoor unit list
It displays the wattage by indoor unit list. The information for each item is as follows:
Item
Description
Details
Air
conditioner
Current
wattage (W)
Total wattage
(kWh)
Click
button to display the detailed
history of each air conditioner
Indoor unit name of air conditioner
Wattage of current indoor unit
Accumulated wattage of indoor unit of the air
conditioner within the period specified by the user.
Installation/Owner's Manual
3-63
3. ACP operation by using the LG ACCS
Detailed history for each air conditioner
Click
button to display the detailed
history of each air conditioner as follws:
Besides the accumulated wattage of
each air conditioiner, the daily wattage
within the query period can be queried
at the detailed history of each air
conditioner.
3 Setting the wattage query period
You can set the period to query the wattage at the right side of the 'Wattage' screen.
Query period display
It displays the set query period.
'Start' calendar
The start date of the query period can be set at 'Start' calendar.
3-64
ACP
3. ACP operation by using the LG ACCS
'End' calendar
The end date of the query period can be set at 'End' calendar.
Apply & Cancel button
When you click [Apply] button after setting the query period, the wattage within the
set query period is displayed at 'Wattage' screen.
When you click [Cancel] button, all settings up to now are cancelled and it returns
to the previous screen.
Installation/Owner's Manual
3-65
3. ACP operation by using the LG ACCS
Setting the system
For the following cases, the air conditioner or the ventilator should be registered at or deleted from the
system by the LG ACCS.
• Installing the ACP for the first time
• Adding a new air conditioner or ventilator
• Changing the existing air conditioner or ventilator information
• Deleting the existing air conditioner or ventilator
The air conditioner can be registered or deleted at 'System setup' menu of the LG ACCS.
Caution: Setting the system
'System setup' menu is used for installing the product. Because the product should be
installed by the professional engineer with knowledge about the air conditioner, the
user should not operate this menu at random.
Caution: Interconnecting the ACP with the AC Manager
When the ACP is interconnected with the AC Manager, if the system is set by the LG
ACCS of the ACP, it may cause the maloperation of the air conditioner. When
interconnecting the ACP with the AC Manager, set the system by the AC Manager.
3-66
ACP
3. ACP operation by using the LG ACCS
In order to register, delete or modify the air conditioner at the system, click 'System setup' menu of the
LG ACCS. When you click 'System setup' menu, the following system setup screen is displayed.
1
2
3
4
5
6
7
Note: Air conditioner setup and the ventilating setup
The air conditioner setup is almost same to the ventilating setup. Here, the system setup function is
described based on the air conditioner setup.
Installation/Owner's Manual
3-67
3. ACP operation by using the LG ACCS
1 Group input window
A new group is added or the information of the existing group can be changed or deleted at the Group
input window. Also, the group information and the indoor unit (or ventilator) information can be
conveniently entered by using the default input button.
Group
It displays the list of the air conditioner (or ventilator) group set at
the ACP. When a specific air conditioner group is selected from
the air conditioner group list, the list of the air conditioiner
belonging to the related air conditioner group is displayed at 'Air
conditioner (or ventilator) information input' at the right side.
Click the blank column to add a new group. The related column is
displayed in yellow, at which the group name can be entered.
At this time, the group number is automatically entered, so be
careful.
The existing group may be modified by the same method. Click
the group to modify, and when the related column is changed to
yellow, modify the group name.
In order to delete the group, click the group name to delete, and
when the related column is changed to yellow, delete the group
name.
Caution: Deleting the indoor unit
information
When the group is deleted, all information belonging
to the related group is deleted, so be careful.
Default input button
When you click the [Default input] button, the indoor unit information is automatically entered as many
as the number of indoor units to enter based on the previously entered outdoor unit information.
If there are many indoor units to be registered to the group, it can be easier to set the air conditioner
by pressing [Default input] button and then changing or deleting the group name and the indoor unit
information.
3-68
ACP
3. ACP operation by using the LG ACCS
2 Air conditioner (or ventilator) information input window and Temporary saving window
You can add, modify or delete the indoor unit or the ventilator.
Air conditioner information input
You can set a new indoor unit or ventilator information at this window.
First, in order to add a new indoor unit or ventilator, click the related input column. When it is changed
to the yellow input window, enter the information of each item.
Modifying the existing indoor unit or ventilator is same. Click the information field of the indoor unit or
ventilator to modify, and when it is changed to the yellow input window, modify the existing
information.
In order to delete the existing indoor unit or ventilator information, click
side. The related information is deleted.
button located at the left
Installation/Owner's Manual
3-69
3. ACP operation by using the LG ACCS
The information to set at the air conditioner (or ventilator) is as follows:
Item
Description
Type
Type of indoor unit or ventilator.
The indoor unit types to set are as follows:
• UAC: Unified air conditioner
This item is not set for the ventilator.
Physical address
Model name
Maximum
consumed power
Enter the physical address of the indoor unito or the ventilator.
When [Default input] button is pressed, it is automatically created by
inheriting the higher information.
The physical address consists of three numbers.
The first number and the second number are the G/W number and the
outdoor unit number respectively, which can be set only within the
information entered from the existing [G/W information] and [outdoor
unit information]. The third number is the indoor unit or ventilator
number, which can not be set overlapped within the same outdoor unit
number and should be set within the range of 0~15.
Enter the model name of the indoor unit or ventilator.
Enter the maximum consumed power for the indoor unit or ventilator to
use. The maximum consumed power depends on the model.
Caution: Maximum consumed power
Fi the peak/demand control function is used, the maximum consumed power for each
indoor unit should be essentially entered. The consumed power of the air conditioner
can be controlled not to exceed the setting value.
How to display the consumed power of indoor unit
Consumed power of the nth indoor unit
(Consumed power of outdoor unit +Total consumed power of indoor unit) *
Consumed power of the nth indoor unit
=
Total consumed power of indoor unit
3-70
ACP
3. ACP operation by using the LG ACCS
Temporary saving window
It is convenient to use this window to move the indoor unit or the ventilator to the other group or to
change the order.
After specifying the air conditioner or the ventilator, press
saving window. Press
button to move it to the temporary
button to apply the temporarily saved air conditioner or ventilator again.
In order to delete the temporarily saved air conditioner or ventilator, click
The related information is deleted.
button at the left side.
Caution: Maximum consumed power
When the system setting is saved, the temporarily saved information of the indoor unit
or ventilator is deleted. So, the information of all air conditioners at the temporary
saving window should be moved to the air conditioner information input window of
each group before saving.
3 Entering the outdoor unit information
Besides the information of the indoor unit
and the ventilator, the outdoor unit
information can be entered at 'System setup'
menu.
When you click [Outdoor unit input] button
located at the right side of the screen, the
outdoor unit information input window is
displayed.
First, in order to add a new outdoor unit,
click the related input column. When the
input window is changed to yellow, enter
information of each item.
Modifying the existing indoor unit or
ventilator is same. Click the information
column of the indoor unit or ventilator to
modify, and when the input window is changed to yellow, modify the existing information.
In order to delete the existing air conditioner or ventilator information, click
side. The related information is deleted.
button at the left
Installation/Owner's Manual
3-71
3. ACP operation by using the LG ACCS
Caution: Deleting the outdoor unit
When the outdoor unit information is deleted, the information of the indoor unit
connected the related outdoor unit is also deleted.
Item
G/W Number
Description
Leave as it is with not modified.
Outdoor unit number
Enter the outdoor unit number. It should not be set overlapped, which
should be set as the number of 0~7.
When [Default input] button is pressed, it is automatically created by
inheriting the higher information.
Name
Enter the outdoor unit name for the user to easily recognize. (ex: 1st
floor)
Type
Enter the type of the outdoor unit.
The types to set are as follows:
• UAC: Unified air conditioner
Model name
Maximum
consumed power
Enter the model name of the outdoor unit.
Enter the maximum consumed power for the indoor unit or ventilator to
use. The maximum consumed power depends on the model.
Note: Physical and Logical group
Each outdoor unit information is used as the information of physical group connecting the indoor
unit.
However, the air conditioner group or the ventilating group is used as logical group information. The
logical group information is used as the managerial aspect regardless to the physical connection.
For example, at the school, even when air conditioners at the 1st grade classroom are connected to
the different outdoor units, the user can create and manage the logical group '1st grade classroom'
by editing the air conditioner group information.
3-72
ACP
3. ACP operation by using the LG ACCS
4 Enter ventilator information
You can enter the ventilator group information from the 'System setting'
menu.
When you click on [Enter ventilator group] button
located on the right side of the screen, ventilator
group input window will be displayed.
First, to add a new ventilator group, you must click
on the applicable input block. When the input
window switches to yellow color, enter the
information of each item.
Editing existing ventilators is applied in the same
way. Click on the information block of the ventilator
to edit and when it changes to yellow color, edit the
existing information.
To delete the existing ventilator information, click on
the X button located on the left side. The applicable
information will be deleted.
Caution: Delete ventilator
When you delete the ventilator group information, the ventilator information included in
the applicable ventilator group will all be deleted.
Information to center to set the ventilator group is as follows.
Item
Group number
Name
Description
Enter the ventilator group number. The ventilator group number must
not be duplicated and must be set within the range of 0~7.
When you press the [Enter default value] button, you can easily create
the number by receiving the higher level information.
Enter the name of the ventilator group that the user can easily
recognize. (Example. 1 floor)
Installation/Owner's Manual
3-73
3. ACP operation by using the LG ACCS
5 Entering the administrator information
The administrator information can be
entered at 'System setup' menu. The
administrator information is the right to log
in to the LG ACCS.
When you click [Administrator information]
at the right side of the screen, the IP/PW
input window is displayed.
Enter the ID for the user to access at the
'ID' field and set the user's password at the
'PW' field, and then click [Save] button to
save the setting information of the ID and
the password.
Click [Cancel] button to cancel without
saving the setting value.
The [A/S] button is not used at present. It
will be updated later.
6 Time synchronization button
[Time synchronization] button aligns (synchronizes) the time of the
user's PC with the system time of ACP. The schedule function of ACP
must be executed at accurate time according user setting. If you are
operating ACP for the first time or when the time set for ACP is not
accurate during use, click on the [Time synchronization] button to
synchronize the time between the user PC and ACP.
3-74
ACP
3. ACP operation by using the LG ACCS
7 Last save state button & Save button
[Last save state] button and [Save] button to set whether to apply the setting to the system or not are
located at the bottom of the 'System setup' menu.
Last save state button
Click [Last save state' button not to change the information.
When you click [Last save state] button, the
window for confirming to execute the
command is displayed, and when you click
[Confirm] button, all information set up to
now is cancelled and it returns to the
previous save state.
Caution: Deleting the indoor unit information
When you click [Confirm] button at the confirmation window, the not saved information
of the setting up to now is returned to the last save status, so be careful.
Installation/Owner's Manual
3-75
3. ACP operation by using the LG ACCS
Save button
Click [Save] button to change the information.
When you click [Save] button, the window
for confirming to execute the command is
displayed. Click [Confirm] button to confirm
the command. Click [Cancel] button to
cancel the command and return to the
previous condition.
When you click [Confirm] button, all
information set up to now is saved and the
saving process is informed to the user by
the confirmation window.
Caution: Initializing the information of other functions
When saving is done at 'System setup' menu, all existing information such as
schedule, peak operation ratio control (peak excluded air conditioner) and error log are
initialized.
3-76
ACP
3. ACP operation by using the LG ACCS
Note: Procedure for setting the system (air conditioiner and
ventilator)
1. Click [Air conditioner setup] tab, and then click [Outdoor unit input] button at the right side of the
screen. When you click [Default input] button at the 'Outdoor unit information input' window, the
outdoor unit information (group number) is entered as default. And then, delete the number of the
not-installed outdoor unit (group number), and modify the outdoor unit name for the user to easily
know.
2. Press [Air conditioner setup] tab, and then press [Default input] button at the botton left of the
screen. The indoor unit information is entered as default. And then, delete the number of the notinstalled indoor unit, and modify the indoor unit name for the user to easily know.
3. Click [Ventilating setup] tab, and then click [Outdoor unit input] button at the right side of the
screen. When you click [Default input] button at the 'Outdoor unit information input' window, the
outdoor unit information (group number) is entered as default. And then, delete the number of the
not-installed outdoor unit (group number), and modify the outdoor unit name for the user to easily
know.
4. Press [Ventilating setup] tab, and then press [Default input] button at the botton left of the screen.
The group number of the ventilator is entered as default. And then, delete the number of the notinstalled ventilator, and modify the ventilator name for the user to easily know. Especially,
because the physical address may be incorrectly entered when it is entered at the connection of
the ventilator, the ventilator should be set according to the setting order.
For more information, see Chapter 2. 'Entering the Indoor unit & Ventilator information.'
Installation/Owner's Manual
3-77
4. Reference
4. Reference
Troubleshooting
If any unexpected problem is occurred when using the ACP, see the following list to find out the solution.
If there is no solution to find, visit http://www.lgservice.com to let us know about it.
If Tx or RX LED of Ports 1~4 of the EE-NET is not blinking when installing the
product.
When installing the product, if TX or RX LED of the ports 1~4 of the LG-NET is not blinking, set and
execute the group of the indoor/outdoor unit.
If the GUI of the EE ACCS, the application program of the ACP, does not operrate
If the GUI of the EE ACCS, the application program of the ACP, does not operate, close the Explorer
window and execute a new Explorer to connect again.
When network error status (Code 242) is displayed on ventilator in LG ACCS of ACP
When the network error status is continuously displayed on the ventilator as shown below through LG
ACCS, the web server program of ACP, check the following details.
1. Check whether the BUS_A and BUS_B of RS485 cable are connected incorrectly.
2. Check whether there is any communication error between the remote controller and indoor unit.
3. Check whether the DIP switch of PI485 is set incorrectly.
4. Check whether the indoor unit address of the central control is not set up.
4-1
ACP
4. Reference
Guide for Open source software
The following GPL/LGPL execution files and libraries used at this product conform to the GPL/LGPL
license contract.
GPL execution file
Linux kernel 2.4
fdisk
Irzsz
Sysvinit
Inetutils
e2fsprogs
Bash
net-tools
boa http server
busybox
stupid-ftpd
tinylogin
traceroute
EEPL library
glibc
linuxthreads
ncurses
zlib
If you request the source code to the EE electronics via the following e-mail, you can receive the CDROM containing it by paying the cost including media cost and transportation cost.
da_opensource @lge.com
This proposal is valid for three years after receiving this product from the EE electronics.
The source of the GPL/LGPL license can be downloaded at http://www.systemaircon.com
Some of softwares used at this product conform to the following copyright.
Copyright ®œ1998-2002 Daniel Veillard. All Rights Reserved
Installation/Owner's Manual
4-2
4. Reference
UTP cable connection chart
UTP cable
Twisted
copper line
The Unshielded Twisted Pair (UTP) cable is
a sort of the signal line connecting the LAN
environment. Two copper lines insulated for
reducing the electromagnetic induction
between two lines are twisted to form the
twisted pair.
The UTP cable consists of 8 wires, of which four lines (No. 1 and 2 for receiving (Rx) and No. 3 and 6
for transmitting (Tx)) are actually used for the data transmission at the general LAN environment. It
can be largely classified two types according to the method for connecting the line for receiving and
transmitting.
Direct cable
It is also called the 1:1 straight cable used for connecting the other equipment at the network.
Cross cable
It is used for the 1:1 connection between the same equipments at the network.
4-3
ACP
P/No.: MFL37115820
Printed in Korea
After reading this manual, keep it in a place easily accessible to the user for future reference.