LG UU18WC Owner's Installation manual

Add to my manuals
23 Pages

advertisement

LG UU18WC Owner's Installation manual | Manualzz
ENGLISH
ITALIANO
ESPAÑOL
FRANÇAIS
INSTALLATION MANUAL
DEUTSCH
AIR
CONDITIONER
ΕΛΛΗΝΙΚΆ
ČEŠTINA
www.lg.com
P/NO : MFL68907803
LIMBA ROMÂNĂ
For more information, Refer to the CD or LG Web site (www.lg.com).
POLSKI
[Representative] LG Electronics Inc. EU Representative : LG Electronics European Shared Service Center B.V.
Krijgsman 1, 1186 DM Amstelveen, The Netherlands
[Manufacturer] LG Electronics Inc. Changwon 2nd factory 84, Wanam-ro, Seongsan-gu, Changwon-si,
Gyeongsangnam-do, KOREA
NEDERLANDS
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
Ɠ This product contains Fluorinated Greenhouse Gases. (R410A)
Single Inverter Outdoor Unit
Original instruction
TIPS FOR SAVING ENERGY
2
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
•
•
•
•
•
•
Excessive cooling may be harmful to your health and may consume more electricity.
Block sunlight with blinds or curtains while you are operating the air conditioner.
Keep doors or windows closed while you are operating the air conditioner.
Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
Speed up the fan to cool or warm indoor air quickly, in a short period of time.
Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them labeled on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
3
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations
and ensure peak performance of your product
! WARNING
Serious injury or death can result if directions are ignores.
! CAUTION
Minor injury or product damage can result if directions are ignored.
! WARNING
• Installation or repairs made by unqualified persons can result in hazards to
you and others.
Refrigeration work must be performed by a qualified person who is "F-Gas"
registered.
• Installation work must be performed in accordance with the National
Electric Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a qualified
service technician familiar with safety procedures and equipped with the
proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result
in equipment malfunction, property damage, personal injury and/or death.
Installation
• Do not use a defective or underrated circuit breaker. Use the correctly
rated breaker and fuse. There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an
Authorized Service Center. Do not disassemble or repair the product by
yourself. There is risk of fire or electric shock.
• Always ground the product as per the wiring diagram. Do not connect the
ground wire to gas or water pipes lightening rod or telephone ground wire.
There is risk of fire or electric shock.
• Install the panel and the cover of control box securely. There is risk of fire
or electric shock due to dust , water etc.
• Use the correctly rated breaker or fuse. There is risk of fire or electric
shock.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not modify or extend the power cable. If power cable is damaged or
has deteriorated, then it must be replaced. There is risk of fire or electric
shock.
• For installation, removal or reinstall , always contact the dealer or an
Authorized Service Center. There is risk of fire, electric shock, explosion,
or injury.
• Do not install the product on a defective installation stand. Be sure that
the installation area does not deteriorate with age. It may cause product to
fall.
• Never install the outdoor unit on a moving base or a place from where
it can fall down.
The falling outdoor unit can cause damage or injury or even death of a person.
• In outdoor unit the step-up capacitor supplies high voltage electricity to the
electrical components. Be sure to discharge the capacitor completely
before conducting the repair work.
A charged capacitor can cause electrical shock.
• When installing the unit, use the installation kit provided with the product.
Otherwise the unit may fall and cause severe injury.
• Indoor/outdoor wiring connections must be secured tightly and the cable
should be routed properly so that there is no force pulling the cable from
the connection terminals. Improper or loose connections can cause heat
generation or fire.
• Safely dispose off the packing materials. Like screws, nails, batteries, broken things etc after installation or svc and then tear away and throw away
the plastic packaging bags. Children may play with them and cause injury.
• Be sure to check the refrigerant to be used. Please read the label on the
product. Incorrect refrigerant used can prevent the normal operation of the
unit.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened. Otherwise, it
may cause fire, electric shock, explosion or death.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air
purge. Do not compress air or Oxygen and do not use Flammable gases.
Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
IMPORTANT SAFETY INSTRUCTIONS
5
ENGLISH
Operation
• When the product is soaked (flooded or submerged) in water , contact an
Authorized Service Center for repair before using it again. There is risk of
fire or eletric shock.
• Be sure to use only those parts which are listed in the svc parts list.
Never attempt to modify the equipment. The use of inappropriate parts
can cause an electrical shock, excessive heat generation or fire.
• Do not touch , operate, or repair the product with wet hands. Hold the
plug by hand when taking it out. There is risk of electric shock or fire.
• Do not place a heater or other heating appliances near the power cable.
There is risk of fire and electric shock.
• Do not allow water to run into electric parts. Install the unit away from
water sources. There is risk of fire, failure of the product, or electric shock.
• Do not store or use or even allow flammable gas or combustibles near the
product. There is risk of fire.
• Do not use the product in a tightly closed space for a long time. Perform
ventilation regularly. Oxygen deficiency could occur and hence harm your
health.
• Do not open the front grille of the product during operation. (Do not touch
the electrostatic filter, if the unit is so equipped.) There is risk of physical
injury, electric shock, or product failure.
• If strange sound, smell or smoke comes from product. Immediately turn
the breaker off or disconnect the power supply cable. There is risk of electric shock or fire.
• Ventilate the product room from time to time when operating it together
with a stove, or heating element etc. Oxygen deficiency can occur and
hence harm your health.
• When the product is not to be used for a long time, disconnect the power
supply plug or turn off the breaker. There is risk of product damage or failure, or unintended operation.
• Take care to ensure that nobody especially kids could step on or fall onto
the outdoor unit. This could result in personal injury and product damage.
• Take care to ensure that power cable could not be pulled out or damaged
during operation. There is risk of fire or electric shock.
• Do not place ANYTHING on the power cable. There is risk of fire or electric shock.
• When flammable gas leaks, turn off the gas and open a window for ventilation before turning on the product. Do not use the telephone or turn
switches on or off. There is risk of explosion or fire.
6
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
! CAUTION
Installation
• Two or more people must lift and transport the product. Avoid personal
injury.
• Do not install the product where it will be exposed to sea wind (salt spray)
directly. It may cause corrosion on the product.
• Install the drain hose to ensure that the condensed water is drained away
properly. A bad connection may cause water leakage.
• Keep level even when installing the product. To avoid vibration or noise.
• Do not install the product where the noise or hot air from the outdoor unit
could damage or disturb the neighborhoods. It may cause a problem for
your neighbors and hence dispute.
• Always check for gas (refrigerant) leakage after installation or repair of
product. Low refrigerant levels may cause failure of product.
• Please install safely at a place that can sufficiently endure the weight of
the product.
If the strength is not sufficient, the product may fall and cause injury.
Operation
• Do not use the product for special purposes, such as preserving foods,
works of art, etc. It is a consumer air conditioner, not a precision refrigeration system. There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow. It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents or splashing water etc. There is risk of fire, electric shock, or damage to the plastic
parts of the product.
• Do not touch the metal parts of the product when removing the air filter.
There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units) There is risk
of personal injury and failure of product.
• Always insert the filter securely after cleaning. Clean the filter every two
weeks or more often if necessary. A dirty filter reduces the efficiency.
• Do not insert hands or other objects through the air inlet or outlet while
the product is operating. There are sharp and moving parts that could
cause personal injury.
• Be cautious when unpacking and installing the product. Sharp edges could
cause injury.
• If the refrigerant gas leaks during repair, do not touch the leaking refrigerant gas. The refrigerant gas can cause frostbite (cold burn).
IMPORTANT SAFETY INSTRUCTIONS
7
ENGLISH
• Do not tilt the unit when removing or uninstalling it. The condensed water
inside can spill.
• Do not mix air or gas other than the specified refrigerant used in the system. If air enters the refrigerant system, an excessively high pressure
results, causing equipment damage or injury.
• If the refrigerant gas leaks during the installation, ventilate the area immediately. Otherwise it can be harmfull for your health.
• Dismantling the unit, treatment of the refrigerant oil and eventual parts
should be done in accordance with local and national standards.
• Replace all batteries in the remote control with new ones of the same
type. Do not mix old and new batteries or different types of batteries.
There is risk of fire or product failure.
• Do not recharge or disassemble the batteries. Do not dispose off batteries
in a fire. They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well
with clean water. Do not use the remote if the batteries have leaked. The
chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor.
Do not use the remote if the batteries have leaked. The chemicals in batteries could cause burns or other health hazards.
• Do not let the air conditioner run for a long time when the humidity is very
high and a door or a window is left open. Moisture may condense and wet
or damage furniture.
• Do not expose your skin or kids or plants to the cool or hot air draft. This
could harm to your health.
• Do not drink the water drained from the product. It is not sanitary and
could cause serious health issues.
• Use a firm stool or ladder when cleaning, maintaining or repairing the
product at height. Be careful and avoid personal injury.
8
TABLE OF CONTENTS
ENGLISH
TABLE OF CONTENTS
2 TIPS FOR SAVING ENERGY
9 INSTALLATION
10 INSTALLATION OF OUTDOOR UNIT
11 CONNECTING PIPES
11
12
13
Preparation of Piping
Connection of piping - Outdoor
Forming the piping
14 WIRING CONNECTION
14
14
16
Electrical Wiring
Connecting Cables between Indoor Unit
and Outdoor Unit
Connecting the cable to Outdoor Unit
17 LEAKAGE TEST AND
EVACUATION
17
17
18
Preparation
Leakage test
Evacuation
19 TEST RUNNING
21 INSTALLATION GUIDE AT
THE SEASIDE
21 SEASONAL WIND AND
CAUTIONS IN WINTER
INSTALLATION
ENGLISH
INSTALLATION
Installation Tools
Figure
more than
30cm
9
Name
Figure
Name
Screw driver
Multi-meter
Electric drill
Hexagonal wrench
Measuring tape, Knife
Ammeter
Hole core drill
Gas-leak detector
Spanner
Thermometer,
Level
Torque wrench
Flaring tool set
more than
30cm
10 INSTALLATION OF INDOOR, OUTDOOR UNIT
ENGLISH
INSTALLATION OF OUTDOOR UNIT
You need to select adequate installation location considering the following conditions, and make
sure to acquire the consent of the user.
Installation Places
- If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat
radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows
around front, back and side of the unit are
respected.
- Do not place animals and plants in the path of the
warm air.
- Take the air conditioner weight into account and
select a place where noise and vibration are minimum.
- Select a place so that the warm air and noise from
the air conditioner do not disturb neighbors.
Su
nro
of
More than
300mm
More than
300mm
Fe
ob nce o
sta r
cle
s
More than 600mm
More than 700mm
- Select a place that can sufficiently endure the weight and vibration of the outdoor unit and
where even installation is possible.
- Select a place that has no direct impact of snow or rain
- Select a place with no danger of snowfall or icicle drop
- Select a place without weak floor or base such as decrepit part of the building or with a lot of
snow accumulation
- Install at a place with fluent water draining to prevent damage from localized heavy rain and
avoid frequent flooded area.
Piping length and the elevation
• Single Operation
Model
UU18WC
UU24WC
UU30WC
UU36WC
Pipe Size mm(inch)
Length A(m)
Gas
Liquid
Standard
Max.
Standard
Max.
Ø12.7 (1/2)
Ø15.88 (5/8)
Ø15.88 (5/8)
Ø15.88 (5/8)
Ø6.35 (1/4)
Ø9.52 (3/8)
Ø9.52 (3/8)
Ø9.52 (3/8)
7.5
7.5
7.5
7.5
30
30
35
40
5
5
5
5
30
30
30
30
If installed tube is shorter than 7.5 m,
additional charging is not necessary.
Additional Refrigerant
= [A-7.5 (m)] x Additional refrigerant (g/m)
Additional
refrigerant
(g/m)
20
40
40
40
Elevation B(m)
Indoor unit
Outdoor unit
A
B
A
Outdoor unit
Indoor unit
B
CONNECTING PIPESINSTALLATION OF INDOOR, OUTDOOR UNIT
11
ENGLISH
CONNECTING PIPES
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following
procedure.
Cut the pipes and the cable.
- Use the accessory piping kit or the pipes purchased locally.
- Measure the distance between the indoor
and the outdoor unit.
- Cut the pipes a little longer than measured
distance.
- Cut the cable 1.5m longer than the pipe
length.
Copper
tube
Slanted Uneven Rough
90°
Pipe
Burrs removal
- Completely remove all burrs from the cut
cross section of pipe/tube.
- Put the end of the copper tube/pipe to downward direction as you remove burrs in order
to avoid to let burrs drop in the tubing.
Reamer
Point down
Putting nut on
- Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring
work)
Flaring work
- Carry out flaring work using dedicated flaring
tool for R-410A as shown below.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
"A"
mm
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8
Firmly hold copper tube in a bar(or clamp) as
indicated dimension in the table above.
Flare nut
Copper tube
Handle
Bar
"A"
Bar
Yoke
Cone
Copper pipe
Clamp handle
Red arrow mark
Smooth all round
Inside is shining without scratches.
= Improper flaring =
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the
flared section and do flaring work again.
Even length
all round
Inclined Surface Cracked Uneven
damaged
thickness
12 CONNECTING PIPES
ENGLISH
Connection of piping Outdoor
- When connecting in a downward direction,
knock out the knock-out hole of the base
pan. (refer to figure 2)
- Align the center of the piping and sufficiently
tighten the flare nut by hand.
- Finally, tighten the flare nutTorque
with torque
wrench
wrench until the wrench clicks.
(250mm)
When tightening the flare nut with torque
wrench ensure the direction for tightening
follows the arrow on the wrench.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Torque
kg·m
1.8~2.5
3.4~4.2
5.5~6.6
6.6~8.2
<Figure 2>
Knock-out
Base pan
Preventing foreign objects from entering
(Figure3)
- Plug the pipe through-holes with putty or
insulation material(procured locally)to stop up
all gaps,as shown in the figure 3.
Outdoor unit
<Figure 3>
Gas side piping
(Bigger Dia.)
Liquid side piping
Liquid side piping
(Smaller Dia.)
Torque wrench
Gas side piping
Tubing Cover
Connecting wire
Drain hose
Continuous
Torque
wrench
(250mm)
Connection pipe
Resin, Clay, Putty or insulating material
(produced locally)
! CAUTION
Insects or small animals entering the outdoor unit may cause a short circuit in the
electrical box.
* When tighten the pipe, hold the haxagonal
body.
OU
TD
UNOOR
IT
CONNECTING PIPES 13
Form the piping by wrapping the connecting
portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
- If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the ground. Secure the drain
hose appropriately.
In cases where the Outdoor unit is installed
above the Indoor unit perform the following.
1 Tape the piping and connecting cable from
down to up.
2 Secure the taped piping along the exterior
wall. Form a trap to prevent water entering
the room.
3 Fix the piping onto the wall by saddle or
equivalent.
In cases where the outdoor unit is installed
below the indoor unit perform the following.
1 Tape the piping, drain hose and connecting
cable from down to up.
2 Secure the tapped piping along the exterior
wall using saddle or equivalent.
Seal a small opening
around the pipings
with gum type sealant.
sealer.
Trap
OU
TD
UNOOR
IT
Seal a small
opening around
the pipings with
gum type sealant.
sealer.
Taping
Drain hose
Plastic
band
Pipings
Connecting
cable
OU
TD
UNOOR
IT
Power supply
cord
• Trap is required to prevent water from entering
into electrical parts.
Seal a small opening
around the pipings
with gum type sealer.
Trap
OU
TD
UNOOR
IT
Trap
ENGLISH
Forming the piping
14 WIRING CONNECTION
ENGLISH
WIRING CONNECTION
Electrical Wiring
Perform the electrical wiring work according
to the electrical wiring connection.
- All wiring must comply with local requirements.
- Select a power source that is capable of supplying the current required by the air conditioner.
- Use a recognized ELCB(Electric Leakage
Circuit Breaker) between the power source
and the unit. A disconnection device to adequately disconnect all supply lines must be
fitted.
- Model of circuit breaker recommended by
authorized personnel only
ELCB
Main
power source
Switch box
Outdoor
Indoor
Model
Phase(Ø)
ELCB
UU18WC
1
15A
UU24WC
1
20A
UU30WC
1
20A
UU36WC
1
25A
Connecting Cables between Indoor Unit and Outdoor Unit
- Connect the wires to the terminals on the control board individually according to the outdoor
unit connection.
- Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of
indoor unit respectively
1(L) 2(N)
POWER SUPPLY
1(L) 2(N)
3
TO INDOOR UNIT
UU18WC/UU24WC/UU30WC
1(L) 2(N)
1(L) 2(N)
POWER SUPPLY
UU36WC
3
TO INDOOR UNIT
WIRING CONNECTION 15
The power cord connected to the outdoor unit should comply to IEC 60245 or HD 22.4 S4
(This equipment shall be provided with a cord set complying with the national regulation.)
NORMAL CROSS-SECTIONAL AREA
1 Phase(Ø)
Model
Phase(Ø)
Area(mm2)
UU18WC
1
2.5
UU24WC
1
2.5
UU30WC
1
2.5
UU36WC
1
2.5
GN
/Y
L
20
mm
3 Phase(Ø)
GN
/
YL
20
mm
The connecting cable connected to the outdoor unit should comply to IEC 60245 or HD
22.4 S4 (This equipment shall be provided with a cord set complying with the national regulation.)
GN
/Y
NORMAL
CROSS-SECTIONAL
AREA 0.75mm2
L
20
mm
When the connection line between the indoor unit and outdooor unit is over 40m, connect
the telecommunication line and power line separately.
If the supply cord is damaged, it must be replaced by a special cord or assembly available
from the manufacturer of its service agent.
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power wire
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
! WARNING
Make sure that the screws of the terminal are free from looseness.
ENGLISH
! CAUTION
16 WIRING CONNECTION
ENGLISH
Connecting the cable to Outdoor Unit
Remove the side panel for wiring connection.
Use the cord clamp to fix the cord.
Earthing work
- Case 1 : Terminal block of Outdoor Unit have
mark.
Connect the cable of diameter 1.6mm2 or more to the earthing terminal provided in the
control box and do earthing.
- Case 2 : Terminal block of Outdoor Unit don't have
mark.
Connect the cable of diameter 1.6mm2 or more, to the panel of control box, marked as
and fasten with earth screw
Connecting cable
terminal
Power cord
terminal
Connecting
cable terminal
Power cord
terminal
Cord clamp
Cord clamp
Cord clamp
Cover control
Tubing Cover
* Make sure the rubber
bushes are Properly
used in knock-out holes
after connecting main
Power cable
UU18WC/UU24WC/UU30WC
UU36WC
! CAUTION
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that They won’t be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
• The Power cord connected to the unit should be selected according to the specifications
on 13 page.
LEAKAGE TEST AND EVACUATION 17
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
- Pressure in the system rises.
- Operating current rises.
- Cooling (or heating) efficiency drops.
- Moisture in the refrigerant circuit may freeze and block capillary tubing.
- Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.
Preparation
- Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units
have been properly connected and all wiring for the test run have been completed. Remove the
service valve caps from both the gas and the liquid side on the outdoor unit. Check that both the
liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
- Connect the manifold valve (with pressure gauges) and dry nitrogen gas cylinder to this service
port with charge hoses.
! CAUTION
Be sure to use a manifold valve for leakage test. If it is not available, use a stop valve for this
purpose. The "Hi" knob of the manifold valve must always be kept close.
- Pressurize the system to no more than 3.8 MPa with dry nitrogen gas and close the cylinder
valve when the gauge reading reached 3.8 MPa Next, test for leaks with liquid soap.
! CAUTION
To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must
be higher than its bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
ENGLISH
LEAKAGE TEST AND EVACUATION
18 LEAKAGE TEST AND EVACUATION
ENGLISH
1 Do a leakage test of all joints of the tubing
(both Indoor unit and outdoor unit) and
both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe
off the soap with a clean cloth.
2 After the system is found to be free of
leaks, relieve the nitrogen pressure by
loosening the charge hose connector at
the nitrogen cylinder. When the system
pressure is reduced to normal, disconnect
the hose from the cylinder.
Indoor unit
Outdoor unit
Manifold valve
Lo
Pressure
gauge
Hi
Charge hose
Nitrogen gas
cylinder (in vertical
standing position)
Evacuation
- Connect the charge hose end described in the
preceding steps to the vacuum pump to evacuate the tubing and indoor unit. Confirm the
"Lo and Hi" knob of the manifold valve is open.
Then, run the vacuum pump. The operation
time for evacuation varies with tubing length
and capacity of the pump. The following table
shows the time required for evacuation.
- When the desired vacuum is reached, close
the "Lo and Hi" knob of the manifold valve
and stop the vacuum pump.
Required time for evacuation when 11.36 l/h
vacuum pump is used
If tubing length is less
If tubing length is
than 10 m (33 ft)
longer than 10 m (33 ft)
30 min. or more
60 min. or more
0.07 kPa or less
Indoor unit
Finishing the job
- With a service valve wrench, turn the valve
stem of liquid side valve counter-clockwise
to fully open the valve.
- Turn the valve stem of gas side valve counter-clockwise to fully open the valve.
- Loosen the charge hose connected to the
gas side service port slightly to release the
pressure, then remove the hose.
- Replace the flare nut and its bonnet on the
gas side service port and fasten the flare nut
securely with an adjustable wrench. This
process is very important to prevent leakage
from the system.
- Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
This completes air purging with a vacuum
pump.
The air conditioner is now ready to test run.
Outdoor unit
Manifold valve
Lo
Hi
Open
Vacuum pump
Pressure
gauge
Open
TEST RUNNING 19
ENGLISH
TEST RUNNING
1 Precautions In Test Running
- The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
! CAUTION
• For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
• Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
- The test run is started by pressing the room temperature checking button and down timer
button for 3 seconds at the same time.
- To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
- After completing work, be sure to measure and record trial run properties, and store measured
data, etc.
- Measuring items are room temperature, outside temperature, suction temperature, blow out
temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and
noise, operating pressure, piping temperature, compressive pressure.
- As to the structure and appearance, check following items.
□Is the circulation of air adequate?
□Is the draining smooth?
□Is the heat insulation complete
(refrigerant and drain piping)?
□Is there any leakage of refrigerant?
□Is the remote controller switch operated?
□Is there any faulty wiring?
□Are not terminal screws loosened?
M4......118N.cm{12kgf.cm}
M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm}
M8......588N.cm{60kgf.cm}
2 Connection of power supply
- Connect the power supply cord to the independent power supply.
Circuit breaker is required.
- Operate the unit for fifteen minutes or more.
3 Evaluation of the performance
- Measure the temperature of the intake and discharge air.
- Ensure the difference between the intake temperature
and the discharge one is more than 8°C (Cooling) or
reversely (Heating).
Thermometer
20 TEST RUNNING
ENGLISH
! CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1 Never fail to have an individual power specialized for the air conditioner. As for the method of
wiring, be guided by the circuit diagram pasted on the inside of control box cover.
2 Provide a circuit breaker switch between power source and the unit.
3 The screw which fasten the wiring in the casing of electrical fittings are liable to come loose
from vibrations to which the unit is subjected during the course of transportation. Check
them and make sure that they are all tightly fastened. (If they are loose, it could give rise to
burn-out of the wires.)
4 Specification of power source
5 Confirm that electrical capacity is sufficient.
6 Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage
marked on the name plate.
7 Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8 Never fail to equip a leakage breaker where it is wet or moist.
9 The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point there of fuse breaking, disturbance to the normal function of a overload protection device.
- Proper starting power is not given to the compressor.
10 Use only 1 remote-controller contained in indoor unit, when using simultaneous operation
system as shown below.
After setting the ESP value in the Ceiling Concealed Duct Type Indoor Unit, the main power
turns off and then remove the remote controller. (Only for synchro combination, over
36kBtu/h)
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual
(air filter cleaning, temperature control, etc.).
INSTALLATION GUIDE AT THE SEASIDE 21
ENGLISH
INSTALLATION GUIDE
AT THE SEASIDE
Windbreak
! CAUTION
• Air conditioners should not be installed
in areas where corrosive gases, such as
acid or alkaline gas, are produced.
• Do not install the product where it could
be exposed to sea wind (salty wind)
directly. It can result corrosion on the
product. Corrosion, particularly on the
condenser and evaporator fins, could
cause product malfunction or inefficient
performance.
• If outdoor unit is installed close to the
seaside, it should avoid direct exposure
to the sea wind. Otherwise it needs
additional anticorrosion treatment on the
heat exchanger.
Sea wind
- It should be strong enough like concrete to
prevent the sea wind from the sea.
- The height and width should be more than
150% of the outdoor unit.
- More than 70cm of space should be kept
between outdoor unit and the windbreak for
easy air flow.
Place with fluent water draining
- Install at a place with fluent water draining to
prevent damage from localized heavy rain and
avoid frequent flooded area.
Selecting the location (Outdoor Unit)
If the outdoor unit is to be installed close to
the seaside, direct exposure to the sea wind
should be avoided. Install the outdoor unit on
the opposite side of the sea wind direction.
Sea wind
Sea wind
In case, to install the outdoor unit on the
seaside, set up a windbreak not to be exposed
to the sea wind.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on
the heat exchanger by using water.
SEASONAL WIND AND
CAUTIONS IN WINTER
- Sufficient measures are required in a snow
area or severe cold area in winter so that
product can operate well.
- Get ready for seasonal wind or snow in winter even in other areas.
- Install a suction and discharge duct not to let
in snow or rain.
- Install the outdoor unit not to come in contact
with snow directly. If snow piles up and
freezes on the air suction hole, the system
may malfunction. If it is installed at snowy
area, attach the hood to the system.
- Install the outdoor unit at the higher installation console by 50cm than the average snowfall (annual average snowfall) if it is installed
at the area with much snowfall.
- Where snow accumulated on the upper part
of the Outdoor Unit by more than 10cm,
always remove snow for operation.
22
ENGLISH

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement