INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : ART COOL MIRROR
http://www.lghvac.com
www.lg.com
P/NO : MFL61995002
IMPORTANT!
Please read this instruction sheet completely before installing the product.
This air conditioning system meets strict safety and operating standards. As the installer or service person,
it is an important part of your job to install or service the system so it operates safely and efficiently.
WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
Installation of all field wiring and components MUST conform with local building codes or, in the absence of local
codes, with the National Electrical Code 70 and the National Building Construction and Safety Code or Canadian
Electrical code and National Building Code of Canada.
• The information contained in the manual is intended for use by a qualified service technician familiar with safety
procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property
damage, personal injury and/or death.
CAUTION: Improper installation, adjustment, alteration, service or maintenance can void the warranty.
The weight of the condensing unit requires caution and proper handling procedures when lifting
or moving to avoid personal injury. Use care to avoid contact with sharp or pointed edges.
Safety Precautions
• Always wear safety eye wear and work gloves when installing equipment.
• Never assume electrical power is disconnected. Check with meter and equipment.
• Keep hands out of fan areas when power is connected to equipment.
• R-410A causes frostbite burns.
• R-410A is toxic when burned.
NOTE TO INSTALLING DEALER: The Owners Instructions and Warranty are to be given to the owner
or prominently displayed near the indoor Furnace/Air Handler Unit.
Special warnings
When wiring:
Electrical shock can cause severe personal injury or death. Only a qualified,
experienced electrician should attempt to wire this system.
• Do not supply power to the unit until all wiring and tubing are completed or reconnected and checked.
• Highly dangerous electrical voltages are used in this system. Carefully refer to the wiring diagram and these
instructions when wiring. Improper connections and inadequate grounding can cause accidental injury or death.
• Ground the unit following local electrical codes.
• Connect all wiring tightly. Loose wiring may cause overheating at connection points and a possible fire hazard.
• The choice of materials and installations must comply with the applicable local/national or international standards.
When transporting:
Be careful when picking up and moving the indoor and outdoor units. Get a partner to help, and
bend your knees when lifting to reduce strain on your back. Sharp edges or thin aluminum fins on
the air conditioner can cut your finger.
When installing...
... in a wall: Make sure the wall is strong enough to hold the unit's weight.
It may be necessary to construct a strong wood or metal frame to provide added support.
... in a room: Properly insulate any tubing run inside a room to prevent "sweating" that can cause
dripping and water damage to wall and floors.
... in moist or uneven locatinons: Use a raised concrete pad or concrete blocks provide a solid,
level foundation for the outdoor unit. This prevents water damage and abnormal vibration.
... in an area with high winds: Securely anchor the outdoor unit down with bolts and a metal
frame. Provide a suitable air baffle.
... in a snowy area(for Heat Pump Model): Install the outdoor unit on a raised platform that is
higher than drifting snow. Provide snow vents.
When connecting refrigerant tubing
• Keep all tubing runs as short as possible.
• Use the flare method for connecting tubing.
• Check carefully for leaks before starting the test run.
When servicing
• Turn the power OFF at the main power box(mains) before opening the unit to check or repair
electrical parts and wiring.
• Keep your fingers and clothing away from any moving parts.
• Clean up the site after you finish, remembering to check that no metal scraps or bits of wiring have
been left inside the unit being serviced.
2
Indoor Unit
Artcool Deluxe Type Indoor Unit Installation Manual
TABLE OF CONTENTS
Installation Requirements
Required Parts
Required Tools
Installation Parts ....................4
Installation ...............................7
Selection of the best location
................................................7
Piping Method........................8
❏ Installation guide map
❏ Four type "A" screws & plastic
anchors
❏ Connecting cable
❏ Level gauge
❏ Screw driver
❏ Electric drill
❏ Hole core drill
❏ Horizontal meter
❏ Pipes: Gas side
Liquid side
(Refer to Product Data)
❏ Insulation materials
❏ Additional drain pipe
❏ Flaring tool set
❏ Specified torque wrenches
(different depending on model No.)
❏ Spanner .......Half union
Drain Piping .........................13
❏ A glass of water
❏ Screw driver
Wiring Connection ...............13
❏ Hexagonal wrench
❏ Gas-leak detector
❏ Vacuum pump
❏ Gauge manifold
Installation of Wireless
Remote Controller ...............15
Installation of Wired Remote
Controller..............................15
Group Control Setting..........17
❏ Two type "B" screws
❏ Owner's manual
❏ Thermometer
❏ Holder Remote Controller
Installation Manual 3
ENGLISH
Safety Precautions.................5
Installation Parts
Installation Parts
S8
SE
Installation Plate
S8
SE
Installation plate(1EA)
Installation plate(1EA)
Type "A" screws and
plastic anchors(4 EA)
4
Installation Plate
Indoor Unit
Type "B" screw (2 EA)
Type "A" screws and
plastic anchors(4 EA)
Type "B" screw (2 EA)
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed.
n Be sure to read before installing the air conditioner.
n Be sure to observe the cautions specified here as they include important items related to safety.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the
following indications.
This symbol indicates the possibility of death or serious injury.
n Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
n Installation
Do not use a defective or underrated circuit breaker. Use this
appliance on a dedicated circuit.
For electrical work, contact the dealer, seller, a qualified electrician, or
an Authorized Service Center.
Always ground the product.
• There is risk of fire or electric shock.
• Do not disassemble or repair the
product. There is risk of fire or electric shock.
• There is risk of fire or electric shock.
Install the panel and the cover
of control box securely.
Always install a dedicated circuit and breaker.
Use the correctly rated breaker
or fuse.
• There is risk of fire or electric shock.
• Improper wiring or installation may
cause fire or electric shock
• There is risk of fire or electric shock.
Do not modify or extend the
power cable.
Do not let the air conditioner
run for a long time when the
humidity is very high and a door
or a window is left open.
Be cautious when unpacking
and installing the product.
• There is risk of fire or electric shock.
• Moisture may condense and wet or
damage furniture.
• Sharp edges could cause injury. Be especially careful of the case edges and the
fins on the condenser and evaporator.
For installation, always contact
the dealer or an Authorized
Service Center.
Do not install the product on a
defective installation stand.
Be sure the installation area
does not deteriorate with age.
• There is risk of fire, electric shock,
explosion, or injury.
• It may cause injury, accident, or
damage to the product.
• If the base collapses, the air conditioner
could fall with it, causing property damage, product failure, and personal injury.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air
or oxygen and do not use flammable gases. Otherwise, it may cause fire or explosion.
• There is risk of fire or failure of product.
Installation Manual 5
ENGLISH
This symbol indicates the possibility of injury or damage to properties only.
Safety Precautions
■ Operation
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
■ Installation
Always check for gas (refrigerant) leakage after installation or
repair of product.
Install the drain hose to ensure
that water is drained away properly.
Keep level even when installing
the product.
• Low refrigerant levels may cause
failure of product.
• A bad connection may cause water
leakage.
• To avoid vibration or water leakage.
Do not install the product where
the noise or hot air from the outdoor unit could damage the
neighborhoods.
Use two or more people to lift
and transport the product.
Do not install the product where
it will be exposed to sea wind
(salt spray) directly.
• It may cause a problem for your
neighbors.
• Avoid personal injury.
• It may cause corrosion on the product.
Corrosion, particularly on the condenser and evaporator fins, could
cause product malfunction or inefficient
operation.
If you eat the liquid from the
batteries, brush your teeth and
see doctor. Do not use the
remote if the batteries have
leaked.
• The chemicals in batteries could
cause burns or other health
hazards.
6
Indoor Unit
Installation
Installation
Read completely, then follow step by step.
Selection of the best location
• There should not be any heat source or steam
More than
100mm(3-15/16 inch)
More than
200mm(7-7/8 inch)
More than
100mm(3-15/16 inch)
More than
2300mm
(90-9/16 inch)
S8 chassis
The mounting wall should be strong and solid
enough to protect it from the vibration.
Installation Plate
Mount the installation plate on the wall with four
Type "A" screws.
(If mounting the unit on the concrete wall, consider using anchor bolts.)
• Always mount the Installation plate horizontally
by aligning the marking-off line by means of the
thread and a level.
Chassis
Hook
Type “A”
SE chassis
Installation Plate
Chassis
Hook
Type “A”
The lower left and the right side of Installation Plate
Ø70mm
(2-3/4 inch)
Ø70mm
(2-3/4 inch)
Installation plate
133mm
(5-1/4inch)
Left rear piping
100mm
(3-15/16inch)
Right rear piping
Ø70mm
(2-3/4 inch)
Installation plate
110mm
(4-5/16 inch)
SE chassis
110mm
(4-5/16 inch)
S8 chassis
Ø70mm
85mm(3-3/8 inch)
Left rear piping
65mm(2-9/16 inch) (2-3/4 inch)
Right rear piping
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt. The installation parts (and the unit) should be taken
appropriate anti-corrosion measures.
Installation Manual 7
ENGLISH
near the unit.
• There should not be any obstacles to prevent the
air circulation.
• A place where air circulation in the room will be
good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the
wall, ceiling, fence, or other obstacles.
Installation
Drill a Hole in the Wall
WALL
Outdoor
5-7mm
Indoor
(3/16~5/16 inch)
• Drill the piping hole with a ø70mm hole core drill.
Drill the piping hole at either the right or the left
with the hole slightly slanted to the outdoor side.
Piping Method
■ Preparing the indoor unit's piping and drain hose for
installation through the wall.
■ Remove the plastic tubing retainer(see illustration
below) and pull the tubing and drain hose away from
chassis.
■ Replace the plastic tubing holder in the original position.
3. Tape the tubing, drain hose and the connecting
cable. Be sure that the drain hose is located at the
lowest side of the bundle. Locating at the upper
side can cause drain pan to overflow inside the
unit.
Tape
Connecting
pipe
Drain hose
Connecting cable
NOTICE : If the drain hose is routed inside the room,
insulate the hose with an insulation material* so that dripping from "sweating"(condensation) will not damage furniture or floors.
For right rear piping
1. Route the indoor tubing and the drain hose in the
direction of rear left.
Drain hose
2. Insert the connecting cable into the indoor unit
from the outdoor unit through the piping hole.
■ Do not connect the cable to the indoor unit.
■ Make a small loop with the cable for easy connection
later.
*Foamed polyethylene or equivalent is recommended.
4. Indoor unit installation
■ Hook the indoor unit onto the upper portion of the
installation plate.(Engage the two hooks of the rear
top of the indoor unit with the upper edge of the
installation plate.) Ensure that the hooks are properly
seated on the installation plate by moving it left and
right.
Connecting
cable
Drain hose
Press the lower left and right sides of the unit against
the installation plate until the hooks engage into their
slots(clicking sound).
8
Indoor Unit
Installation
5. Connecting the pipings to the indoor unit and drain
hose to drain pipe.
■ Align the center of the pipings and sufficiently tighten
the flare nut by hand.
■ Wrap the area which accommodates the rear piping housing section with vinyl tape.
Indoor
unit pipe
Wrap with vinyl tape
Connection
pipe
Vinyl tape
(wide)
Connecting cable
Indoor unit tubing
Flare nut
Pipings
Pipe
Vinyl tape(narrow)
■ Tighten the flare nut with a wrench.
Spanner (fixed)
Torque
wrench
Indoor
unit tubing
■ Bundle the piping and drain hose together by
wrapping them with vinyl tape over the range within which they fit into the rear piping housing section.
Wrap with vinyl tape
Pipe
Vinyl tape(wide)
■ Mount the clamp on the boss with a type "B"
screw.(optional)
Type "B" screw
Drain hose
Drain hose
Clamp
Boss
■ When extending the drain hose at the indoor
unit, install the drain pipe.
Drain pipe
Indoor unit
drain hose
Vinyl tape(narrow)
Adhesive
6. Wrap the insulation material around the connecting portion.
■ Overlap the connection pipe insulation material
and the indoor unit pipe insulation material. Bind
them together with vinyl tape so that there is no
gap.
Plastic bands
If the split type Indoor unit is installed in a wall having hole or opening near by or back side of the unit,
then the air from other side of the wall can come
inside the condition space through that hole/ opening. That air can cause unwanted dew/ water
droplet formation when it comes in contact with
body of the indoor unit. So all hole or opening on
the wall must be blocked very well to avoid water
dropping from the body of the unit.
For left rear piping
1. Route the indoor tubing and the drain hose to the
required piping hole position.
Insulation material
2. Insert the piping, drain hose and the connecting
cable into the piping hole.
Connecting cable
Drain pipe
Installation Manual 9
ENGLISH
Flare nut
Connection
pipe
Installation
3. Insert the connecting cable into the indoor unit.
■ Don't connect the cable to the indoor unit.
■ Make a small loop with the cable for easy connection later.
■ When extending the drain hose at the indoor unit,
install the drain pipe.
Drain hose
4. Tape the drain hose and the connecting cable.
• Connecting cable
Indoor unit drain hose
Vinyl tape(narrow)
Adhesive
5. Indoor unit installation
■ Hang the indoor unit from the hooks at the top of
the installation plate.
■ Insert the spacer etc. between the indoor unit and
the installation plate and separate the bottom of
the indoor unit from the wall.
Indoor unit
Spacer
6. Connecting the pipings to the indoor unit and
the drain hose to drain pipe.
■ Align the center of the pipings and sufficiently
tighten the flare nut by hand.
Flare nut
Pipings
■ Tighten the flare nut with a wrench.
Spanner (fixed)
Flare nut
Connection
pipe
Indoor
unit tubing
10
Insulation material
■ Wrap the area which accommodates the rear piping housing section with vinyl tape.
Vinyl tape
(wide)
80mm
Torque
wrench
Plastic bands
Connection
pipe
Installation plate
Indoor unit tubing
7. Wrap the insulation material around the connecting portion.
■ Overlap the connection pipe heat insulation and
the indoor unit pipe heat insulation material. Bind
them together with vinyl tape so that there is no
gap.
Indoor Unit
Indoor
unit piping
Wrap with vinyl tape
Pipe
Connecting
cable
Vinyl tape
(narrow)
Installation
■ Bundle the piping and drain hose together by
wrapping them with cloth tape over the range
within which they fit into the rear piping housing
section.
9. Set the pipings and the drain hose to the back of
the chassis with the tubing holder.
■ Hook the edge of tubing holder to tap on chassis
and push the bottom of tubing holder to be
engaged at the bottom of chassis.
Pipe
Drain hose
Vinyl tape
(narrow)
Wrap with
vinyl tape(wide)
10. Indoor unit installation
■ Remove the spacer.
■ Ensure that the hooks are properly seated on the
installation plate by moving it left and right.
Connecting
cable
Drain hose
Piping for
passage through
piping hole
Press the lower left and right sides of the unit
against the installation plate until the hooks engage
into their slots(clicking sound).
If the split type Indoor unit is installed in a wall having hole or opening near by or back side of the unit,
then the air from other side of the wall can come
inside the condition space through that hole/ opening. That air can cause unwanted dew/ water
droplet formation when it comes in contact with
body of the indoor unit. So all hole or opening on
the wall must be blocked very well to avoid water
dropping from the body of the unit.
Installation Manual 11
ENGLISH
8. Reroute the pipings and the drain hose across
the back of the chassis.
Tubing holder
Installation
CAUTION
Installation Information (For left piping)
• Good case
For left piping. Follow the instruction below.
■ Press on the upper side of clamp. (Ⓐ)
■ Unfold the tubing to downward slowly. (Ⓑ)
12
Indoor Unit
CAUTION
• Bad case
■ Following bending type from right to left could cause
problem of pipe damage.
Installation
Drain Piping
Connecting area
drain hose
1. To remove the front panel from the indoor unit,
remove the front panel from the indoor unit
cabinet.
■ Set the air direction louvers up-and-down to the
position(horizontally) by hand.
■ Remove the securing screws that retain the front
panel. Pull the lower left and right sides of the grille
toward you and lift it off.
Leakage
checking
Drain pan
■ The drain hose should point downward for easy drain flow.
Downward slope
Front panel
■ Do not make drain piping.
2. To check the drainage.
■ Pour a glass of water on the evaporator.
■ Ensure the water flows through the drain hose of the indoor
unit without any leakage and goes out the drain exit.
Accumulated
drain water
Air
Do not raise
Water
leakage
Water
leakage
Tip of drain hose
dipped in water
Water
leakage
Waving
Less than
50mm gap
Ditch
Wiring Connection
Connect the wires to the terminals on the control
board individually according to the outdoor unit
connection.
• Ensure that the color of the wires of outdoor unit
and the terminal No. are the same as those of
indoor unit respectively.
Remote control cord
Connecting caable
SODU
Terminal Block Indoor
1(L1) 2(L2)
3
4
B
A
IDU
-
-
INTERNET DRY1 DRY2 GND 12V Outdoor unit
B
A
-
INDOOR POWER INPUT
Installation Manual 13
ENGLISH
Drain
hose
Leakage
checking
Installation
Connection method of the connecting cable(Example)
Lock nut
Conduit
mounting
plate
Conduit
Lock nut
1(L1) 2(L2)
3(A)
4(B)
Conduit
Power Supply
High Voltage
(208/230V)
Conduit
mounting
plate
Transmission
WARNING : Loose wiring may cause the terminal to overheat or result in unit
malfunction.
A fire hazzard may also exist.
Therefore, be sure all wiring is tightly connected.
CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power circuit specifically for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control cover.
2) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from
vibrations to which the unit is subjected during the course of transportation. Check them and make
sure that they are all tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3) Specification of power source.
4) Confirm that electrical capacity is sufficient.
5) See to that the starting voltage is maintained at more than 90 percent of the rated voltage marked
on the name plate.
6) Confirm that the cable thickness is as specified in the power source specification.
(Particularly note the relation between cable length and thickness.)
7) In a wet or moist area, always install an earth leakage circuit breaker.
8) The following would be caused by voltage drop.
• Vibration of a magnetic switch, which will damage the contact point, fuse breaking, disturbance of the
normal function of the overload.
9) The means for disconnection from a power supply shall be incorporated in the fixed wiring and
have an air gap contact separation of at least 3mm in each active(phase) conductors.
14
Indoor Unit
Installation
Installation of Wireless Remote Controller
How to mount onto a wall
ENGLISH
How to insert the batteries
1. Remove the battery cover by pulling it according to the arrow direction.
2. Insert new batteries making sure that the (+) and (-) of battery are
installed correctly.
3. Reattach the cover by sliding it back into position.
NOTICE
1. Always use/replace both batteries of same type.
2. If the system is not to be used for a long time, remove the batteries
to save their working life.
3. If the display screen of remote controller starts, fading replace both
of the batteries.
Installation of Wired Remote Controller
1. Please fix tightly using provided screw after placing remote controller
setup board on the place where you like to setup.
- Please set it up not to bend because poor setup could take place if setup
board bends.
Please set up remote controller board fit to the reclamation box if there is a
reclamation box.
2. Can set up Wired remote controller cable into three directions.
- Setup direction: the surface of wall reclamation, upper, right
- If setting up remote controller cable into upper and right side, please set up after removing remote controller
cable guide groove.
2
❈ Remove guide groove with long nose.
① Reclamation to the surface of the wall
② Upper part guide groove
③ Right part guide groove
2
3
3
1
<Wire guide grooves>
Installation Manual 15
Installation
3. Please fix remote controller upper part into the
setup board attached to the surface of the wall, as
the picture below, and then, connect with setup
board by pressing lower part.
- Please connect not to make a gap at the remote controller and setup board’s upper and lower, right and left
part.
<Connecting order>
Wall
Side
When separating remote controller from setup
board, as the picture below, after inserting into the
lower separating hole using screw driver and then,
spinning clockwise, remote controller is separated.
- There are two separating holes. Please individually
separate one at a time.
- Please be careful not to damage the inside
components when separating.
Wall
Side
<Separating order>
Wall
Side
Wall
Side
4. Please connect indoor unit and remote controller using connection cable.
Please check if connector is normally connected.
Indoor
Unit side
Connecting cable
5. Please use extension cable if the distance between wired remote controller and indoor unit is more
than 10m.
When installing the wired remote controller, do not bury it in the wall.
(It can cause damage in the temperature sensor.)
Do not install the cable to be 50m or above.
(It can cause communication error.)
• When installing the extension cable, check the connecting direction of the connector of the
remote controller side and the product side for correct installation.
• If you install the extension cable in the opposite direction, the connector will not be connected.
• Specification of extension cable: 2547 1007 22# 2 core 3 shield 5 or above.
• Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum
cable usage.
16
Indoor Unit
Installation
Group Control Setting
1. Group Control 1
■ Wired remote controller 1 + Indoor units
LGAP Network System
Slave
Display Error Message
Slave
Slave
GND
Signal
12 V
Only connect serial signal and GND lines
between slave indoor unit
Master
1. It is possible to 16 indoor units(Max) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
The Master indoor unit is possible to recognize Dry Contact and Central controller only.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.
6. In case of Group Control, be limited additional functions of indoor unit.
- Selection of operation options (stop/mode/temperature)
- Control of flow rate (strong/middle/weak)
- Time reservation function
- Elevation grille
❈ All kind of indoor units be set possible using a wireless remote controller, except cassette and duct types.
Refer to wireless remote controller manual for setting group control.
❈ It is possible to connect indoor units since Feb. 2009.
In the other cases, please contact LGE.
Installation Manual 17
ENGLISH
Master
Installation
2. Group Control 2
■ Wired remote controllers + Indoor units
LGAP Network System
Master
Slave
Slave
Slave
GND
Signal
12 V
Don’t connect serial 12V line
Display Error Message
Master
Slave
#1
#N
1. It is possible to control N indoor units by wired remote controller M units. (M+N≤17 Units)
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
Other than those, it is same with the Group Control 1.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
The Master indoor unit is possible to recognize Dry Contact and Central controller only.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.
6. In case of Group Control, be limited additional functions of indoor unit.
- Selection of operation options (stop/mode/temperature)
- Control of flow rate (strong/middle/weak)
- Time reservation function
- Elevation grille
❈ All kind of indoor units be set possible using a wireless remote controller, except cassette and duct types.
Refer to wireless remote controller manual for setting group control.
❈ It is possible to connect indoor units since Feb. 2009.
In the other cases, please contact LGE.
18
Indoor Unit
Installation
3. 2 Remote Control
■ Wired remote controller 2 + Indoor unit 1
LGAP Network System
Display Error Message
Master
Slave
#1
#N
1. It is possible to connect two wired remote controllers with one indoor unit.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case of any error occurs at indoor unit, display on the wired remote controller.
6. There isn’t limits of indoor unit function.
4. Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA +Wired remote controller
❈ PZCWRCG3 cable used for connection
Indoor unit 1 EA +Wired remote controller 2EA
❈ PZCWRC2 cable used for connection
S lave
Mas te r
PZC WRC 2
PZC WRC G3
Maste r
Maste r
S lave
• Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum
cable usage.
Installation Manual 19
ENGLISH
GND
Signal
12 V
Master
Memo
20
Indoor Unit
US
1. Please call the installing contractor of your product, as warranty service will be provided by them.
2. If you have service issues that have not been addressed by the contractor, please call 1-888-865-3026.