Air conditioner
Installation manual
AR09HSSDPWK/EE, AR12HSSDPWK/EE
•• Thank you for purchasing this Samsung air conditioner.
•• Before operating this unit, please read this Installation manual carefully and retain it for future
reference.
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 1
2016/5/6 10:31:55
Contents
Installation
3
Safety Information on Installation
3
Preparation
5
Step 1.1 Choosing the installation location
Step 1.2 Checking and preparing accessories and tools
Step 1.3 Drilling a hole through the wall
Step 1.4 Taping the pipes, cables, and drain hose
Indoor Unit Installation
9
Step 2.1 Disassembling the cover panel
Step 2.2 Disassembling the installation plate
Step 2.3 Connecting the power and communication cables (assembly cable)
Step 2.4 Optional: Extending the power cable
Step 2.5 Installing and connecting the drain hose
Step 2.6 Optional: Extending the drain hose
Step 2.7 Optional: Changing the direction of the drain hose
Step 2.8 Installing and connecting the assembly pipes to the refrigerant pipes (assembly pipe)
Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe)
Step 2.10 Fixing the installation plate
Step 2.11 Fixing the indoor unit to the installation plate
Step 2.12 Assembling the cover panel
Outdoor Unit Installation
17
Step 3.1 Fixing the outdoor unit in place
Step 3.2 Connecting the power and communication cables and the refrigerant pipes
Step 3.3 Evacuating the air
Step 3.4 Adding refrigerant
Step 3.5 Important information regulation regarding the refrigerant used
Installation Inspection
21
Step 4.1 Performing the gas leak tests
Step 4.2 Running the Smart Install mode
Step 4.3 Performing final check and trial operation
Step 4.4 Display Error and Check Method
For information on Samsung’s environmental commitments and product specific regulatory
obligations e.g. REACH visit: samsung.com/uk/aboutsamsung/samsungelectronics/
corporatecitizenship/data_corner.html
2 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 2
2016/5/6 10:31:55
Installation
Safety Information on Installation
Carefully follow the precautions listed below because
they are essential to guarantee the safety of both the air
conditioner and the workers.
regularly. These operations should be performed by
qualified personnel only.
• The unit contains moving parts, which should always
be kept out of the reach of children.
• Always disconnect the air conditioner from the power
supply before servicing it or accessing its internal
components.
• Do not attempt to repair, move, alter or reinstall the
unit. If performed by unauthorised personnel, these
operations may cause electric shocks or fires.
• Verify that installation and testing operations are
performed by qualified personnel.
• Do not place containers with liquids or other objects
on the unit.
• Verify that the air conditioner is not installed in an
easily accessible area.
• All the materials used for the manufacture and
packaging of the air conditioner are recyclable.
General information
• The packing material and exhaust batteries of the
remote control (optional) must be disposed of in
accordance with current laws.
• Carefully read the content of this manual before
installing the air conditioner and store the manual in
a safe place in order to be able to use it as reference
after installation.
• For maximum safety, installers should always carefully
read the following warnings.
• Store the operation and installation manual in a safe
location and remember to hand it over to the new
owner if the air conditioner is sold or transferred.
• This manual explains how to install an indoor unit
with a split system with two SAMSUNG units. The use
of other types of units with different control systems
may damage the units and invalidate the warranty.
The manufacturer shall not be responsible for damages
arising from the use of non compliant units.
• The manufacturer shall not be responsible for damage
originating from unauthorised changes or the improper
connection of electric and requirements set forth in the
“Operating limits” table, included in the manual, shall
immediately invalidate the warranty.
• The air conditioner should be used only for the
applications for which it has been designed: the indoor
unit is not suitable to be installed in areas used for
laundry.
• In order to help prevent electric shocks, fires or
injuries, always stop the unit, disable the protection
switch and contact SAMSUNG’s technical support if
the unit produces smoke, if the power cable is hot or
damaged or if the unit is very noisy.
• Always remember to inspect the unit, electric
connections, refrigerant tubes and protections
Installation of the unit
• IMPORTANT: When installing the unit, always
remember to connect first the refrigerant tubes, then
the electrical lines. Always disassemble the electric
lines before the refrigerant tubes.
• Upon receipt, inspect the product to verify that it has
not been damaged during transport. If the product
appears damaged, DO NOT INSTALL it and immediately
report the damage to the carrier or retailer (if the
installer or the authorised technician has collected the
material from the retailer.)
• After completing the installation, always carry out a
functional test and provide the instructions on how to
operate the air conditioner to the user.
• Do not use the air conditioner in environments with
hazardous substances or close to equipment that
release free flames to avoid the occurrence of fires,
explosions or injuries.
• Our units must be installed in compliance with the
spaces indicated in the installation manual to ensure
either accessibility from both sides or ability to
perform routine maintenance and repairs. The units’
components must be accessible and that can be
disassembled in conditions of complete safety either
for people or things. For this reason, where it is not
observed as indicated into the Installation Manual, the
cost necessary to reach and repair the unit (in safety,
as required by current regulations in force) with slings,
Installation
• Do not use the units if damaged. If problems occur,
switch the unit off and disconnect it from the power
supply.
• The air conditioner contains a refrigerant that has
to be disposed of as special waste. At the end of its
life cycle, the air conditioner must be disposed of in
authorised centres or returned to the retailer so that it
can be disposed of correctly and safely.
English 3
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 3
2016/5/6 10:31:55
trucks, scaffolding or any other means of elevation
won’t be considered in-warranty and will be charged
to end user.
• When installing the outdoor unit at the seaside, make
sure that it is not directly exposed to sea breeze. If
you cannot find an adequate place free from direct
sea breeze, construct a protection wall or a protective
fence.
–– Install the outdoor unit in a place (such as near
buildings etc.) where it can be protected from sea
breeze. Failure to do so may cause a damage to the
outdoor unit.
Sea breeze
Sea breeze
Power supply line, fuse, or circuit
breaker
• Always make sure that the power supply is compliant
with current safety standards. Always install the air
conditioner in compliance with current local safety
standards.
• Always verify that a suitable grounding connection is
available.
• Verify that the voltage and frequency of the power
supply comply with the specifications and that the
installed power is sufficient to ensure the operation of
any other domestic appliance connected to the same
electric lines.
• Always verify that the cut-off and protection switches
are suitably dimensioned.
Outdoor unit
Sea
Sea
Outdoor unit
• If you cannot avoid installing the outdoor unit at the
seaside, construct a protection wall around to block the
sea breeze.
• Construct a protection wall with a solid material such
as concrete to block the sea breeze. Make sure that the
height and the width of the wall are 1.5 times larger
than the size of the outdoor unit. Also, secure a space
larger than 600 mm between the protection wall and
the outdoor unit for exhausted air to ventilate.
Sea breeze
Sea
• Verify that the air conditioner is connected to the
power supply in accordance with the instructions
provided in the wiring diagram included in the manual.
• Always verify that electric connections (cable entry,
section of leads, protections…) are compliant with
the electric specifications and with the instructions
provided in the wiring scheme. Always verify that all
connections comply with the standards applicable to
the installation of air conditioners.
Protection wall
Outdoor unit
Outdoor unit
Protection wall
• Install the unit in a place where water can drain
smoothly.
Installation
• If you have any difficulty finding installation location
as prescribed above, contact your manufacturer for
details.
• Be sure to clean the sea water and the dust on the heat
exchanger of the outdoor unit and apply a corrosion
inhibitor on it. (At least once in a year.)
4 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 4
2016/5/6 10:31:55
Preparation
Step 1.1 Choosing the installation
location
• Snow-proof hood installation is recommended for
heavy snowing region (recommend).
• For low ambient model.
Overview of installation location requirements
(Unit : mm)
300 or more
Snow-proof hood
100 mm or more
(recommended)
125 mm
or more
(recommended)
Wall Mounting Bracket
125 mm
or more
(recommended)
Drain hose hole
You can select the direction of
draining (left or right).
At least 500
Minimum clearances for the outdoor unit
Maximum pipe height: 8 m
Maximum pipe length: 15 m
Wall
Make at least one round to
reduce noise and vibration.
300
Minimum clearance in mm
600
Air flow direction
The actual units may look different from
the images depicted here.
(Unit : m)
CAUTION
• Comply with the length and height limits described in
the figure above.
1500
2000
150
300
1500
Make a U-trap (A) on the
pipe (which is connected to
the indoor unit) at outer wall
and cut the bottom part of
the insulation (about 10 mm)
to prevent rainwater from
getting inside through the
insulation.
600
Installation
Cut insulation to have
rainwater drained
8
300
Indoor
Unit
CAUTION
15
1500
3
300
Minimum Maximum Maximum
Outdoor
Unit
Outer wall
(Unit: mm)
Pipe height
300
AR09HSSDPWK/EE
AR12HSSDPWK/EE
Side view
When installing 1 outdoor unit (6 cases)
500
Model
Pipe length
Top view
• Installation minimum be done above 500 mm from the
ground (must).
English 5
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 5
2016/5/6 10:31:57
Step 1.2 Checking and preparing
accessories and tools
When installing more than 1 outdoor unit (5 cases)
(Unit: mm)
Accessories
600
3000
3000
200
600
Installation plate (1)
Remote control (1)
Remote control battery (2)
User Manual (1)
Installation Manual (1)
Smart A/C application Manual
(1)
Cap screw (2)
Remote Control Holder (1)
M4 x 16
Tapped Screws (2)
Guide Left(1)
300
1500
600
Accessories in the indoor unit package
1500
300
1500
600
500
500
300
600
600
300
300
CAUTION
• If the outdoor unit is installed with any insufficient
clearance, it may generate sound and affect the whole
product.
Guide Right(1)
Installation
• Be sure to install the outdoor unit in a level place
where its vibration does not affect the whole product.
6 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 6
2016/5/6 10:31:58
Optional accessories
NOTE
Insulated assembly pipe,
Ø 6.35 mm (1)
Insulated assembly pipe,
Ø 12.70 mm (1)
18
Insulated assembly pipe,
Ø 9.52 mm (1)
09/12
Insulated assembly pipe,
Ø 15.88 mm (1)
24
Drain Hose, 2 m long (1)
Foam Insulation(1)
• A flare nut is attached to the end of each pipe of an
evaporator or a service port. Use flare nuts when
connecting the pipes.
• Wire assembly cables are optional. If they are not
supplied, use standard cables.
• The drain plug and the rubber legs are included only
when the air conditioner is supplied without assembly
pipes.
• If these accessories are supplied, they are in the
accessory package or outdoor unit package.
Tools
Pipe clamp A (3)
Pipe clamp B (3)
Vinyl tape (2)
PE T3 foam tube insulation (1)
General tools
• Vacuum pump
(Backward flowing
prevention)
• Manifold gauge
• Stud finder
Putty 100 g (1)
Drain plug (1)
• Torque wrench
• Pipe cutter
• Reamer
M4 x 25 tapped screw (6)
• Pipe bender
• Spirit level
• Screwdriver
• Spanner
• Drill
• L-wrench
• Measuring tape
Cement nail (6)
Tools for test operation
3-wire power cable (1)
2-wire assembly cable (1)
• Thermometer
• Resistance meter
• Electroscope
3-wire assembly cable (1)
Step 1.3 Drilling a hole through the
wall
Accessories in the outdoor unit package
1 Determine the position of a 65 mm hole in
consideration of the possible directions of the pipe
bundle and the minimum distances between the hole
and the installation plate.
Installation
Rubber leg (4)
Before fixing the installation plate to a wall and then fixing
the indoor unit to the installation plate, a window frame,
or a gypsum board, you must determine the position of a
hole (with 65 mm inner diameter) through which the pipe
bundle (consisting of power and communication cables,
refrigerant pipes, and drain hose) will pass and then drill
that hole.
English 7
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 7
2016/5/6 10:32:00
2 Drill the hole.
CAUTION
Left
Right
• Be sure to drill only one hole.
• Make sure that the hole slants downwards so that the
drain hose slants downwards to drain water well.
Rear right or left
Bottom right
Wall
<Possible directions of the pipe bundle>
Indoor unit
CAUTION
• If changing the pipe direction from left to right, do not
drastically bent it but slowly turn it in the opposite
direction as shown. Otherwise, the pipe may be
damaged in the process.
Pipe bundle hole
Drain hose
<The hole slants downwards>
Step 1.4 Taping the pipes, cables, and
drain hose
1 Wrap foam insulation on parts without insulation on
the ends of the refrigerant pipes, as shown in the
figure. This wrapping minimises condensation problem.
Insulation
<Minimum distances between the hole and the
installation plate>
(Unit : mm)
Model
A
B
C
D
AR09HSSDPWKNEE
AR12HSSDPWKNEE
36
190
81
36
Refrigerant pipes
Pipe bundle hole: Ø 65 mm
2 Wind the refrigerant pipes, power cable,
communication cable and drain hose with vinyl tape to
make a pipe bundle.
Installation plate
Refrigerant pipes
(assembly pipe)
Vinyl tape
Installation
Power and communication cables
(assembly cable)
Drain hose
8 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 8
2016/5/6 10:32:00
Indoor Unit Installation
Please scan this QR code for detail
video of indoor unit installation.
2
1
Step 2.1 Disassembling the cover
panel
1 Remove the cap screws, then the screws.
4
Cap screw
Screw
Phillips screwdriver
Flat-head screwdriver
Step 2.2 Disassembling the
installation plate
2 Unlock the side hooks ( , ), then centre hooks ( ).
Then unlock the bottom hooks ( ) to pull out the
cover panel.
A
A
B
C
B
Installation
Centre hook (A)
Bottom/Side hook (B/C)
English 9
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 9
2016/5/6 10:32:01
Step 2.3 Connecting the power and
communication cables (assembly
cable)
• When performing electrical and earthing works,
be sure to comply with the 'technical standards of
electrical installations' and the 'wiring regulations' in
the local regulations.
• Tighten the terminal block screw to 1.2-1.8 N•m (1218 kgf•cm).
NOTE
Control box
• Each wire is labelled with the corresponding terminal
number.
• Use shield cable (Category 5; less than 50pF/m) for
noisy environmental site.
Before
connecting
Correct
Upside down
Damaged
Non-circular
• Power supply cords of parts of appliances for outdoor
use shall not be lighter than polychloroprene sheathed
flexible cord. (Code designation IEC: 60245 IEC 66/
CENELEC: H07RN-F, IEC: 60245 IEC 57/CENELEC:
H05RN-F)
• Power & Communication cable shall not exceed 30m.
After
connecting
Correct
(Front view)
Correct
(Side view)
Upside down
Non-fitted
1(L)2(N)
CAUTION
• For the terminal block wiring, use a wire with a
ring terminal socket only. Regular wires without a
ring terminal socket may become a hazard due to
overheating of the electrical contact during installation.
<Circular terminal>
• If you need to extend the pipe, be sure to extend the
cable too. The maximum length of each of the cable
and pipe used should not exceed 15 metres.
F1 F2
• Do not connect two or more different cables to extend
the length. This connection may cause fire.
• Each circular terminal must match the size of its
corresponding screw in the terminal block.
• After connecting the cables, make sure that terminal
numbers on the indoor and outdoor units match.
Fasten the screws for the wire holders.
Installation
Model
AR09HSSDPWK/EE
AR12HSSDPWK/EE
Power cable
(Outdoor unit)
3G X 1.5 mm²,
H07RN-F
Outdoor-to-indoor
power cable
3G X 1.0 mm²,
H07RN-F
Communication
cable
2 X 0.75 mm²,
H05RN-F
Type GL
16A
• Ensure that power and communication cables are
separated, they must not be in the same cable.
WARNING
• Connect the wires firmly so that wires cannot be pulled
out easily. (If they are loose, it could cause burn-out of
the wires.)
10 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 10
2016/5/6 10:32:02
Step 2.4 Optional: Extending the
power cable
1 Prepare a compressor and the following tools.
Tools
Spec
Crimping pliers
MH-14
Connection sleeve
(mm)
20xØ7.0 (HxOD)
Insulation tape
Width 18 mm
Contraction tube
(mm)
50xØ8.0 (LxOD)
4 Using a compressor, compress the two points and flip
it over and compress another two points in the same
location.
5 The compression dimension should be 8.0.
Shape
Compression
dimension
• After compressing it, pull both sides of the wire to
make sure it is firmly pressed.
Method 1
2 As shown in the figure, peel off the shields from the
rubber or wire of the power cable.
Compress it 4 times
5 mm
5 mm
• Peel off 20 mm of the wire shields of the tube
installed already.
CAUTION
• For information about the power cable
specifications for indoor and outdoor units, refer
to the installation manual.
• After peeling off the tube wire, you must insert a
contraction tube.
Method 2
Compress it 4 times
6 Wrap it with the insulation tape twice or more and
position your contraction tube in the middle of the
insulation tape.
A total of three or more layers of insulation is required.
Method 1
Method 2
Insulation tape
Insulation tape
Power cable (provided by us)
40 mm
20
20
35 mm
20
60
120
180
Contraction tube
(Unit: mm)
Wire tube power cable
20
7 Apply heat to the contraction tube to contract it.
(Unit: mm)
3 Insert both sides of core wire of the power cable into
the connection sleeve.
• Method 2: Twist the wire cores together and push
it into the sleeve.
Method 1
Connection sleeve
Method 2
Connection sleeve
• Make sure that the connection parts are not
exposed to outside.
• Be sure to use insulation tape and a contraction
tube made of approved reinforced insulating
materials that have the same level of withstand
voltage with the power cable. (Comply with the
local regulations on extensions.)
Installation
• Method 1: Push the core wire into the sleeve from
both sides.
8 After tube contraction work is completed, wrap it with
the insulation tape to finish.
Insulation tape
English 11
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 11
2016/5/6 10:32:03
WARNING
CAUTION
• In case of extending the electric wire, please DO NOT
use a round-shaped pressing socket.
–– Incomplete wire
connections can cause
• Make sure that the indoor unit is in upright position
when you pour water to check for leakage. Make sure
that the water does not overflow onto the electrical
part.
• If the diameter of the connection hose is smaller than
the product's drain hose, water leakage may occur.
electric shock or a fire.
Step 2.5 Installing and connecting the
drain hose
1 Install the drain hose.
• Inadequate installation may cause water leakage.
• If the drain hose is routed inside the room, insulate the
hose so that dripping condensation does not damage
the furniture or floors.
• Do not box in or cover the drain hose connection.
Drain hose connection must be easily accessible and
serviceable.
Step 2.6 Optional: Extending the drain
hose
Drain hose
Assembly pipe
Connection hose
Drain hose (A)
Extension drain hose (B)
Wall
40~45mm
Indoor unit
Drain hose
Slant downwards
Slant upwards
Dipped in water
(A)
Drain hose
5 cm
less
Bent
Too small
clearance
(B)
Extension drain hose
Ditch
Too small
clearance
20 mm or more
Foam insulation
Installation
2 Pour water into the drain pan. Check whether the hose
is well drained.
Vinyl tape
12 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 12
2016/5/6 10:32:04
Step 2.7 Optional: Changing the
direction of the drain hose
Drain pan outlet
Rubber cap
Pour water in the direction of arrow.
Step 2.8 Installing and connecting
the assembly pipes to the refrigerant
pipes (assembly pipe)
Connect indoor and outdoor units with field-supplied
copper pipes by means of flare connections. Use insulated
seamless refrigeration grade pipe only, (Cu DHP type
according to ISO1337), degreased and deoxidized, suitable
for operating pressures of at least 4200 kPa and for burst
pressure of at least 20700 kPa. Under no circumstances
must sanitary type copper pipe be used.
There are 2 refrigerant pipes of different diameters:
• The smaller one is for the liquid refrigerant
• The larger one is for the gas refrigerant
<Front view>
A short liquid refrigerant pipe and a short gas refrigerant
pipe are already fitted to the air conditioner. The
connection procedure for the refrigerant pipes varies
according to the exit position of each pipe when facing
the wall:
Direction of the drained water
Left(A)
Right(B)
1 <Front view>
Underside(C)
<Side view>
CAUTION
Screw
2 <Assembling the
hanger screw>
Guide right
or left

• Make sure that the indoor unit is in upright position
when you pour water to check for leakage. Make sure
that the water does not overflow onto the electrical
part.
3 <Side view>
2 Smooth the cut edges.
Installation
1 Cut out the appropriate knock-out piece (A, B, C) on
the rear of the indoor unit unless you connect the pipe
directly from the rear.
English 13
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 13
2016/5/6 10:32:04
3 Remove the protection caps of the pipes and connect
the assembly pipe to each pipe. Tighten the nuts first
with your hands, and then with a torque wrench,
applying the following torque:
Outer diameter (mm)
Torque (N•m)
Torque (kgf•cm)
ø 6.35
14 to 18
140 to 180
ø 9.52
34 to 42
350 to 430
ø 12.70
49 to 61
500 to 620
ø 15.88
68 to 82
690 to 830
Step 2.9 Shortening or extending the
refrigerant pipes (assembly pipe)
Pipe cutter
Pipe
NOTE
• If you want to shorten or extend the pipes, see
Step 2.9 Shortening or extending the refrigerant
pipes (assembly pipe) on page 14.
Oblique
90°
Rough
Burr
4 Cut off the remaining foam insulation.
5 If necessary, bend the pipe to fit along the bottom
of the indoor unit. Then pull it out through the
appropriate hole.
D
90°±2°
A
• The pipe should not project from the rear of the
indoor unit.
45°±2°
L
• The bending radius should be 100 mm or more.
R 0.4 to 0.8
6 Pass the pipe through the hole in the wall.
7 Fix the indoor unit on the wall.Pass the cables, pipes
and hose through the knock-out hole which would be
connected to the outdoor unit .
8 Use 2 screws to fix the indoor unit as shown in the
picture 2.
9 Assemble the Guide into the position of A or B as
shown in the picture 3.
Pipe
Flare
D
(Unit: mm)
Outer diameter (D)
Depth (A)
Flare dimension (L)
ø 6.35
1.3
8.7 to 9.1
ø 9.52
1.8
12.8 to 13.2
ø 12.70
2.0
16.2 to 16.6
ø 15.88
2.2
19.3 to 19.7
NOTE
• The pipe will be insulated and fixed permanently into
position after finishing the installation and the gas leak
test. For further details. see Step 4.1 Performing the
gas leak tests on page 21.
Installation
CAUTION
• Tighten the flare nut with a torque wrench according
to specified method. If the flare nut is over-tightened,
the flare may break and cause refrigerant gas leakage.
• Do not box in or cover the pipe connection. All
refrigerant pipe connection must be easily accessible
and serviceable.
Flare nut
Indoor outlet pipe
Connecting pipe
(Unit: mm)
Outer diameter (mm) Torque (N•m)
Torque (kgf•cm)
ø 6.35
14 to 18
140 to 180
ø 9.52
34 to 42
350 to 430
ø 12.70
49 to 61
500 to 620
ø 15.88
68 to 82
690 to 830
14 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 14
2016/5/6 10:32:05
Step 2.10 Fixing the installation plate
CAUTION
• If you need a pipe longer than specified in piping
codes and standards, you must add refrigerant to the
pipe. Otherwise, the indoor unit may freeze.
• While removing burrs, put the pipe face down to make
sure that the burrs do not get in to the pipe.
Liquid service port
<High pressure>
You can install the indoor unit on a wall, window frame, or
gypsum board.
WARNING
• Make sure that the wall, window frame, or gypsum
board can withstand the weight of the indoor unit. If
you install the indoor unit in a place where it is not
strong enough to withstand the unit's weight, the unit
could fall and cause injury.
When fixing the indoor unit on a wall
Gas service port
<Low pressure>
Fix the installation plate to the wall giving attention to the
weight of the indoor unit.
Plastic anchor
Wall
20 mm
(Unit : mm)
Correct
Model
A
B
C
D
AR09HSSDPWKNEE
AR12HSSDPWKNEE
36
190
81
36
Pipe bundle hole: Ø 65 mm
Inclined
Cracked
Uneven
thickness
Damaged
surface
<Flare nut>
NOTE
CAUTION
• Tighten the flare nut at the specified torque. If the flare
nut is over-tightened, it may break to cause leakage of
refrigerant gas.
When fixing the indoor unit on a window frame
1 Determine the positions of the wooden uprights to be
attached to the window frame.
2 Attach the wooden uprights to the window frame
giving attention to the weight of the indoor unit.
3 Attach the installation plate to the wooden upright
using tapping screws.
When fixing the indoor unit on a gypsum board
Installation
• Excessive torque may cause gas leakage. When
extending the pipe with welding or brazing, ensure
that nitrogen is used during the welding or brazing
process. The joint must be accessible and serviceable.
NOTE
• If you mount the plate to a concrete wall using plastic
anchors, make sure that gaps between the wall and the
plate, created by projected anchor, is less than 20 mm.
1 Use stud finder to find out locations of the studs.
2 Fix the plate hanger on two studs.
English 15
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 15
2016/5/6 10:32:05
CAUTION
• If you fix the indoor unit on a gypsum board, use
only specified anchor bolts on reference positions.
Otherwise, the gypsum surrounding the joints may
crumble over time and cause the screws to be loosened
and stripped. This may lmead to physical injury or
equipment damage.
A
B
A
B
D
C
• Search for other spots if there are less than two studs,
or the distance between the studs are different from
the plate hanger.
C
• Fix the installation plate without inclining to one side.
2
Step 2.11 Fixing the indoor unit to the
installation plate
D
1
B
B
CAUTION
• Make sure that the pipe bundle does not move when
you install the indoor unit onto the installation plate.
Step 2.12 Assembling the cover panel
C
1 Lock the side hooks (D), then centre hooks (B). Then
lock the bottom hooks (C) to engage the cover panel
in place.
C
2 Fasten the screw (A- ), then assemble the cap screws
(A- ).
Installation
1
A
A
2
16 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 16
2016/5/6 10:32:05
Outdoor Unit Installation
Step 3.1 Fixing the outdoor unit in
place
Optional: Fixing the outdoor unit to a wall with
a rack
Soft rubber designed to cut off vibration from
rack to wall (not supplied with product)
Y
X
Rubber leg
(Unit : mm)
Model
X
Y
AR09HSSDPWKXEE
AR12HSSDPWKXEE
612
317
Soft rubber designed to cut off residual vibration
from outdoor unit to rack (not supplied with product)
1 Place the outdoor unit as directed on the top of the
unit to let the discharged air out properly.
2 Fix the outdoor unit in level to an appropriate support
using anchor bolts.
NOTE
• Secure the rubber legs to help prevent the generation
of noise and vibration.
• If the outdoor unit is exposed to strong winds, install
shield plates around the outdoor unit so that the fan
can operate correctly.
NOTE
• Make sure that the wall can support the weights of the
rack and the outdoor unit.
• Install the rack close to the column as much as
possible.
Step 3.2 Connecting the power
and communication cables and the
refrigerant pipes
L
N
F1
Power cable
(three wires)
Communication cable
(two wires)
CAUTION
Installation
Outdoor-to-indoor
power cable
(three wires)
F2
• Be sure to fix the power cables and communication
cable with a cable clamp.
English 17
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 17
2016/5/6 10:32:06
1 Leave the system in the standby mode.
WARNING
Control box
Remove the screw for the
control box cover
Remove the gas and liquid
service port caps
• Do not turn on the system! This is necessary for
better vacuum operation (full OPEN position of
Electronic Expansion Valve).
2 Connect the charging hose of the low pressure side
of manifold gauge to a gas service port as seen in the
picture.
For connecting the
refrigerant pipes
3
15 minutes
Valve
Gas service port
<Low pressure>
4
Vacuum
Pump
(Backward flowing prevention)
Liquid service port <Low pressure>
5
Liquid service port
<High pressure>
Connect the gas and liquid
refrigerant pipes
Step 3.3 Evacuating the air
Installation
The outdoor unit is loaded with sufficient R-410A
refrigerant. Do not vent R-410A into atmosphere: it is a
fluorinated greenhouse gas, covered by Kyoto Protocol,
with a Global Warming Potential (GWP) = 2088. You
should evacuate the air in the indoor unit and in the
pipe. If air remains in the refrigerant pipes, it affects the
compressor. It may cause reduction of cooling capacity and
malfunction. Use a vacuum pump.
CAUTION
• When installing, make sure there is no leakage. When
recovering the refrigerant, ground the compressor first
before removing the connection pipe. If the refrigerant
pipe is not properly connected and the compressor
works with the stop valve open, the pipe inhales the air
and it makes the pressure inside of the refrigerant cycle
abnormally high. It may cause explosion and injury.
Liquid service port <High pressure>
3 Open the valve of the low pressure side of manifold
gauge anticlockwise.
4 Evacuate the air in the connected pipes using the
vacuum pump for about 15 minutes.
• Make sure that pressure gauge shows -0.1 MPa
(-76 cmHg, 5 torr) after about 10 minutes. This
procedure is very important to avoid a gas leak.
• Close the valve of the low pressure side of
manifold gauge clockwise.
• Turn off the vacuum pump.
• Check for 2 minutes if there is any pressure
change.
• Remove the hose of the low pressure side of
manifold gauge.
5 Set a valve cork of liquid and gas service port to the
open position.
18 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 18
2016/5/6 10:32:06
Step 3.4 Adding refrigerant
If you use a pipe longer than the length specified in
the piping codes and standards, you must add 15g of
refrigerant R-410A for each extra metre. If you use a pipe
shorter than the length specified in the piping codes and
standards, the evacuating time is normal. Refer to the
Service Manual for further details.
CAUTION
• The remaining air in the Refrigeration cycle, which
contains moisture, may cause malfunction of the
compressor.
• Always contact the service centre or a professional
installation agency for product installation.
R-410A is a mixed type of refrigerant. It is necessary for
recharging under conditions of liquid. When recharging
refrigerant from the refrigerant cylinder to the equipment,
take the following instructions:
Before recharging, check whether the cylinder has
a siphon or not. There are two ways to recharge the
refrigerant:
Siphon
Charge the refrigerant
standing the cylinder upright.
Charge the refrigerant turning
the cylinder upside down.
<Cylinder with siphon>
<Cylinder without siphon>
Step 3.5 Important information
regulation regarding the refrigerant
used
This product contains fluorinated greenhouse gases. Do
not vent gases into the atmosphere.
CAUTION
• Inform user if system contains 5 tCO2e or more of
fluorinated greenhouse gases. In this case, it has to be
checked for leakage at least once every 12 months,
according to regulation n°517/2014. This activity has
to be covered by qualified personnel only. In case
situation above (5 tCO2e or more of R-410A), installer
(or recognized person which has responsibility for
final check) has to provide a maintenance book, with
all the information recorded according to REGULATION
(EU) No 517/2014 OF THE EUROPEAN PARLIAMENT
AND OF THE COUNCIL of 16 April 2014 on fluorinated
greenhouse gases.
1 Please fill in the following with indelible ink on the
refrigerant charge label supplied with this product and
on this manual.
•
the factory refrigerant charge of the product,
•
the additional refrigerant amount charged in
the field and
•
+ the total refrigerant charge. on the
refrigerant charge label supplied with the product.
Refrigerant type
GWP value
R-410A
2088
• GWP=Global Warming Potential
NOTE
• If R-410A refrigerant is charged with gas, the
composition of the charged refrigerant changes and
the characteristics of the equipment vary.
• Calculating tCO2e : kg x GWP / 1000
Indoor unit
• During the measuring operation of refrigerant quantity
added, use electronic scales. If cylinder doesn't have
siphon, upset it.
Outdoor unit
Kg
tCO2e
Installation
Unit
①, a
②, b
①+②, c
English 19
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 19
2016/5/6 10:32:07
NOTE
aFactory refrigerant charge of the product: see unit
name plate
bAdditional refrigerant amount charged in the field
(Refer to the above information for the quantity of
refrigerant replenishment.)
C Total refrigerant charge
d Refrigerant cylinder and manifold for charging
CAUTION
• The filled-out label must be adhered in the proximity
of the product charging port (e.g. onto the inside of the
stop valve cover).
Installation
20 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 20
2016/5/6 10:32:07
Installation Inspection
Step 4.1 Performing the gas leak tests
1 Before inspecting the leakage, use a torque wrench
to close the cap for the stop valve. (Comply with a
tightening torque for each size of the diameter, and
tighten the cap firmly to prevent any leakage.)
Test parts for the
indoor unit
Tightening torque for body
cap (Refer to the table)
Spindle
Charging core
Step 4.2 Running the Smart Install mode
R-22: Thread of the screw - 7/16-2OUNF
R-410A: Thread of the screw -1/2-2OUNF
Tightening torque for charging port cap (Refer to the table)
Outer diameter
(mm)
Tightening torque
Body cap
(N•m)
ø 6.35
20 to 25
ø 9.52
20 to 25
ø 12.70
25 to 30
ø 15.88
30 to 35
Over ø 19.05
35 to 40
Charging port cap (N•m)
1 Make sure that the air conditioner is in the standby
status.
2 Hold down the
(Power),
(Mode), and
(SET)
buttons on the remote control simultaneously for 4
seconds.
3 Wait until Smart Install mode succeeds or fails. It takes
approximately 7 to 13 minutes.
• While Smart Install mode is proceeding:
Type
Display
10 to 12
LED Display
LED1
LED2
LED3
( 1 N•m = 10 kgf•cm )
2 Insert inert gas into the pipes connected to indoor and
outdoor units.
Indoor
unit
indicator
3 Test leakage on the connection parts of the indoor and
outdoor units with soap lather or liquid.
The progress
is displayed
as a number
between 0
and 99 on the
indoor unit
display.
The LEDs on the
indoor unit display
blink in sequence,
then all of them blink
simultaneously. These
operations repeat.
• When Smart Install mode succeeds: Smart Install
mode ends with ringing sound, and the air
conditioner is in standby status.
• When Smart Install mode fails: An error message
is displayed on the indoor unit display, and Smart
Install mode ends.
NOTE
• Smart Install mode can be operated only with the
supplied remote control.
Installation
Test parts for the
indoor unit
• During the Smart install mode procedure, remote
control cannot be operated.
English 21
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 21
2016/5/6 10:32:08
When error occurs, take necessary measures by referring to the following table. For more information on necessary
measures for errors, refer to the service manual.
Error indicator
LED Display
LED 1 LED 2
Display
LED 3
/
Error
Measures for the installer to take
/
,
display and
all LEDs blink.
Communication
error between
indoor and outdoor
units
• Check the connection wire between the
indoor and outdoor units (whether the
power cable or communication cable is
crossed or not).
Error on indoor
temperature sensor
• Check the connection of the connector.
Error on indoor
heat exchanger
• Check the connection of the connector.
Error on indoor fan
motor
• Check the connection of the connector.
EEPROM/Option
error
• Re-set options.
Refrigerant flow
blocking error
• Check if the stop valve is completely
open.
• Remove foreign substance. (Check for the
cause that restrains motor.)
,
• Check if there is any blockage in the
refrigerant pipe which connects the
indoor and outdoor units.
• Check for refrigerant leak.
Installation
This LED pattern
appears when an
error occurs on the
outdoor unit.

: Off,
: Blinking,
Lack of refrigerant
(for inverter models
only)
• Check if a sufficient amount of refrigerant
is additionally charged for the pipe
longer than specified in piping codes and
standards.
• Check for refrigerant leak between valve
and pipe connection.
: On
22 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 22
2016/5/6 10:32:08
Step 4.3 Performing final check and
trial operation
1 Check the following:
4 Turn off the air conditioner and switch mains supply
off.
5 Disconnect tubing. After disconnection, protect valves
and tubing ends from dust.
• Strength of the installation site
• Tightness of pipe connection to detect gas leak
• Electric wiring connection
• Heat-resistant insulation of the pipe
• Drainage
• Grounding conductor connection
• Correct operation (Take the following steps.)
2 Press the
(Power) button on the remote control to
check the following:
CAUTION
• Compressor damage may occur if the compressor is
run at a negative suction pressure.
Pumping down for removing the product
1 Hold down the
(Power) button on the indoor unit
for 5 seconds. Beep sounds immediately to indicate
that the product is ready for pump down procedure.
• The indicator on the indoor unit lights up.
2 Let the compressor run for more than 5 minutes.
• The airflow blade opens and the fan gears up for
operation.
3 Release the valve caps on High and Low pressure side.
3 Press the
(Mode) button to select Cool or Heat
mode. Then take the following sub-steps:
• In Cool mode, use the Temperature button to set
the set temperature to 16 °C.
• In Heat mode, use the Temperature button to set
the set temperature to 30 °C.
• Check whether, approximately 3 to 5 minutes
later, the outdoor unit starts, and a cool or warm
air blows out.
4 Use L-wrench to close the valve on the high pressure
side.
5 After approximately 1 minute, close the valve on the
low pressure side.
6 Stop operation of the air conditioner by pressing
the
(Power) button on the indoor unit or remote
control.
7 Disconnect the pipes.
• After 12 minutes of stationary condition, check
the indoor unit air treatment.
1
4 Press the
(Air swing) button to check whether the
airflow blades work properly.
5 Press the
1 minute
(Power) button to stop the trial operation.
Pumping down refrigerant
Pump-down is an operation intended to collect all the
system refrigerant in the outdoor unit. This operation must
be carried out before disconnecting the refrigerant tubing
in order to avoid refrigerant loss to the atmosphere.
Liquid service port
<High pressure>
Gas service port
<Low pressure>
1 Shut off the liquid valve with the Allen wrench.
3 After 2 minutes of operation, shut the suction valve
with the same wrench.
Installation
2
2 Turn on the air conditioner in cooling with fan
operating at high velocity. (Compressor will
immediately start, provided 3 minutes have elapsed
since the last stop.)
Off
English 23
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 23
2016/5/6 10:32:09
Step 4.4 Display Error and Check Method
Indoor Display Error and Check Method
ERROR MODE
Indoor
Outdoor
DESCRIPTION
YEL
GRN
RED
○
◎
●
Normal operation
●
●
●
Power on reset(1sec.)
○
○
○
Power off / VDD NG
dF
○
◎
●
When dF shows on the 88 segment of the Indoor unit, this means that the system is in defrost mode.
Note that during this operation period, system performance will be reduced.
E101
○
○
○
●
●
E102
●
Communcation error (IndoorOutdoor)
E121
Indoor room temperature sensor error
E122
Evap-In temperature sensor error
E154
Fan error (Indoor)
E162
EEPROM error (Indoor)
E163
Option setting error
Installation
E203
◎
●
●
1min. Time out Communcation (Inv micomMain micom)
E221
◎
○
◎
Outdoor temperature sensor error
E231
◎
●
◎
Outdoor Coil temperature sensor error
E251
◎
◎
○
Discharge temperature sensor error
E416
◎
○
Discharge over temperature
E422
●
●
●
○
EEV or Valve Close error-Self diagnosis
E440/
E441
●
◎
○
Out of the Limit of the operation(Outdoor temperature)
E458
●
○
○
Fan error (Outdoor)
E461
○
◎
○
Compressor starting error
E462
●
◎
●
Compressor trip error / PFC over current
E464
○
○
◎
IPM over current (O.C)
E465
◎
●
○
Compressor V-limit error
E466
○
◎
DC-Link voltage under/over error
E467
●
●
Compressor rotation error(comp. wire missing error)
E468
◎
◎
Current sensor error
E469
●
●
◎
◎
DC-Link voltage sensor error
E470
○
○
EEPROM error (Outdoor)
E471
●
●
○
◎
OTP error
◎
AC line zero cross signal error
●
Heat-Sink sensor error
◎
H/W DC-Link over
◎
PFC over load
●
Input current sensor error
○
Heat-Sink overheat error
●
○
Gas-Leak error
○
○
Capacity miss match error
●
○
E472
●
●
E474
◎
◎
E483
○
●
E484
○
●
E485
◎
◎
E500
◎
E554
●
●
E556
◎
24 English
A3050 EE Better IM_DB68-06139A-00_EN_A5.indd 24
2016/5/6 10:32:09
Record of Installation:
It is recommended that your receipt be stapled to this page for proof of purchase date and/or for
warranty purposes should it be required.
Please ensure that the following information is recorded once the installation has been completed:
Purchase Information:
Date of Purchase:
Dealer Company Name
Dealer Company Address
Product Information (Data can be found on the product mark plates):
Model Code
Outdoor Serial Number
Software Version
Model Code
Indoor Serial Number
Software Version
Installation Information:
Date of Installation:
Location/Address:
Installation Company Name
Installation Company Address
Recommended Installation Guidance (On the behalf of the customer):
Yes
No
Has the customer been provided guidance regarding the maintenance of the
product?
Has the customer been provided guidance regarding the operation of the
product?
In order to ensure the correct installation and operation of this product, it is recommended that a
service visit be arranged within a reasonable period of time.
In the event of a service issue, please refer to the troubleshooting guide of the relevant supporting
manuals. It is recommended that a skilled service technician be contacted for support. Should urgent
support be required then, using the information provided, contact the local Samsung office via email
or telephone so that support can be initiated via our approved service centres (ASC'S) within 24hrs.
It is also recommended that the product be registered with the manufacturer shortly after the date of
installation. Please register your product at the following location:
www.samsung.com/warranty