Samsung | AM090HNMPKH/TK | Samsung AM128HNMPKH/TK User Manual

Setting an indoor unit address and installation option
DB68-07047A-00
Setting an indoor unit MCU port address
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
4. Assign an indoor unit MCU port address by wireless remote controller.
- The initial setting status of indoor unit ADDRESS(MAIN/RMC/MCU port) is “0A0000-100000-200000-300000”. Seg 15 ~ 18 are option for MCU address.
Notice: Also set the MCU and Indoor units address by using Add-on > Change address on S-NET Pro 2. (For more information, see the S-NET Pro 2 Help.)
Option
Explanation
SEG13
PAGE
SEG14
-
SEG15
Setting MCU PORT address
SEG16
10-digit of MCU address
SEG17
1-digit of MCU
SEG18
MCU PORT address
Remote Controller
Display
Indication and
Details
Indication
Details
Indication
0
2
1
Details
No MCU port
MCU port address
setting mode
Indication
Details
Indication
Details
Indication
Details
0~1
10-digit
0~9
1-digit
A~F
PORT
Location
Example> If you want to set the indoor unit to ‘A’ port of MCU #1. (0A0000 – 100000 – 20101A -30000)
Setting an indoor unit installation option. (suitable for the condition of each installation location)
1. Check whether power is supplied or not.
- When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. The panel(display) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air conditioner.
Added 02 series installation option
1. SEG 3 is Evaporator Drying. When Cooling or dry mode is off. The indoor fan operate in setting minutes.
2. SEG 4 is Minimizing fan operation when thermostat off. Fan stops or operates Ultra low in Coolong when thermostat is off.
3. SEG 15 is Free Cooling control. For free cooling control, Economizer controller is required.
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option
Explanation
Indication and
Details
SEG3
Evaporator Drying
Indication
Details
0
Disuse
2
Use (5min)
(*1)
4
Use (10min)
(*1)
6
Use (30min)
(*1)
Indication
0
1
2
3
4
5
6
7
8
9
A
B
SEG4
SEG15
Use of external room temperature
Setting the output of external control
Details
Details
Use of External room
Minimizing fan operation when Indication
temperature sensor
thermostat is off
Default
Default
0
External control (Thermo On)
Use
Disuse
Disuse
Use (Heating)
1
External control (Operation On)
Use
Use (Heating)
Disuse
Use (Cooling)
2
External heater signal
Use
Use (Cooling)
Disuse
Use (Heating / Cooling)
3
External heater signal
Use
Use (Heating / Cooling)
Disuse
Use (Cooling Ultra Low Fan)
4
Cooling operation signal
Use
Use (Cooling Ultra Low Fan)
Disuse
Use (Heating / Cooling Ultra Low Fan)
5
Free Cooling control (Cooling Thermo On)
Use
Use (Heating / Cooling Ultra Low Fan)
6
Free Cooling control (Cooling/Dry Thermo On)
Added 05 series installation option
1. SEG 3 is Cooling only indoor unit for HR. When Indoor unit is directly connected with HR outdoor unit without MCU unit.
2. SEG 23 is forcing FAN Operation for Heating and Cooling mode.
Option No. : 05XXXX-1XXXXX-2XXXXX-3XXXXX
Option
Explanation
Indication and
Details
SEG3
Use of Auto Chahge Over or Cooling only for HR only
Indication
Details
0
Disuse
1
Use Auto Change Over for HR only
2
Use Cooling only indoor unit for HR
DVM 실내기 주소설정 간지_EN_DB68-07047A-00_A4.indd 2
Indication
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
SEG23
Forcing FAN Operation for Heating and Cooling
Details
Cooling Fan Setting
Heating Fan Setting
Disuse
Disuse
Disuse
Use (Fan: User setting)
Disuse
Use (Fan: High)
Disuse
Use (Fan: Low)
Use (Fan: User setting)
Disuse
Use (Fan: User setting)
Use (Fan: User setting)
Use (Fan: User setting)
Use (Fan: High)
Use (Fan: User setting)
Use (Fan: Low)
Use (Fan: High)
Disuse
Use (Fan: High)
Use (Fan: User setting)
Use (Fan: High)
Use (Fan: High)
Use (Fan: High)
Use (Fan: Low)
Use (Fan: Low)
Disuse
Use (Fan: Low)
Use (Fan: User setting)
Use (Fan: Low)
Use (Fan: High)
Use (Fan: Low)
Use (Fan: Low)
2016-12-29 오후 3:27:07