advertisement
▼
Scroll to page 2
of 80
Flex Series R410A GMV Multi VFR System-Indoor Unit (For North America) Compact Panel Cassette Type Indoor Unit Owner's Manual Air Conditioners Model: ISMI-C15 Thank you for choosing Air Conditioners, please read this owner’s manual carefully before operation and retain it for future reference. If you have lost the Owner’s Manual, please contact the local agent or visit www.Impecca.com for an electronic version. Impecca reserves the right to interpret this manual which will be subject to any change due to product improvement without further notice. Impecca reserves the final right to interpret this manual. v. 1.1 User Notice ◆ When operating, the entire capacity of the cooperating indoor unit should be not larger than 150% of outdoor unit. Otherwise, it will cause the shortage of cooling (heating) capacity. ◆ A Breaker(or fuse) need to be installed in every indoor unit, and the capacity should in according with indoor unit’s electrical parameter; all the indoor units are required to be centralized controlled by a total Switch, this Switch can cut off the electric power supply in case of emergency. The Breaker(or fuse) on each indoor units have the function of short circuit prevention and abnormal overload avoiding, it should be connected in normal situation. The total switch controlling the power supply of all the indoor units. Before clearing and maintenance job being carried out to the indoor units, it is very important to turn off the total power supply switch. ◆ In order to turn on the units successfully, the main power switch should be opened 8 hours before the operation. ◆ After receiving the turn off signal, every indoor unit will continue to work for 20-70sec to make use of the rest cool air or the rest heat air in the heat exchanger, while preparing for the next operation. And this is normal. ◆ When the selected operating mode of the indoor unit are clash with the operating mode of the outdoor unit, the malfunction light will blink after 5s on the indoor unit or remote controller showing that the operation clash, then the indoor unit will stop. At this time, change the operation mode of the indoor unit to the one that would not clash with the outdoor operating mode to make the operation normal. The cooling mode is not clash with the dry mode, while the fan mode is not clash with any mode. ◆ The appliance shall not be installed in the laundry. ◆ An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring. ◆ Information regarding transport/storage temperature (-25-55°C) is missing. ◆ Main switch provided by end user: main switch handle should be black or gray, it can be locked in “OFF” position with padlock. ◆ The main disconnection device should be explained in user manual and the height should be recommended at 0.6-1.7m. over current protection is required(UL 1995,CSA C22.2). ◆ The cooling range of the unit is the outdoor environment temp.-5~48°C DB, the heating range of the unit( only for the heat pump type unit) is the outdoor environment temp. -15~27°C WB. This product must not be disposed together with the domestic waste. This product has to be disposed at an authorized place for recycling of electrical and electronic appliances. Thank you for your selecting of Impecca air conditioner, please read this usage and install instruction carefully and keep it well in order to use this unit correctly. Contents 1 Safety Information�������������������������������������������������������������������������������������1 2 Install of The Compact Panel Cassette Type Indoor Unit�������������������������� 2 2.1 Schematic diagram of installation spaces��������������������������������������������������������� 2 2.2 Select install location of the indoor unit������������������������������������������������������������� 2 2.3 Important notice������������������������������������������������������������������������������������������������ 3 2.4 Dimension of ceiling opening and location of the hoisting screw (M10)������������ 3 2.5 Main body of hoisting air conditioner����������������������������������������������������������������� 3 2.6 Connection of the refrigerant pipe��������������������������������������������������������������������� 4 2.7 Drainage hose��������������������������������������������������������������������������������������������������� 5 2.8 Electrical wiring������������������������������������������������������������������������������������������������� 7 2.9 Install the panel������������������������������������������������������������������������������������������������� 8 3 Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit�� 10 4 Working Temperature Range������������������������������������������������������������������� 11 5 Malfunction Debarring�����������������������������������������������������������������������������12 5.1 Check the following items before contacting maintenance center������������������ 12 5.2 Instruction�������������������������������������������������������������������������������������������������������� 13 5.3 The following circumstance are not malfunction��������������������������������������������� 13 5.4 After-sales Service������������������������������������������������������������������������������������������ 13 6 Maintenance Method�������������������������������������������������������������������������������14 6.1 Cleaning air filter��������������������������������������������������������������������������������������������� 14 6.2 Clean air inlet grille������������������������������������������������������������������������������������������ 15 6.3 Install and change of air purifier���������������������������������������������������������������������� 15 6.4 Clean Outlet vent and Surface Panel�������������������������������������������������������������� 16 6.5 Maintenance before or after usage season����������������������������������������������������� 16 Safety Information 1 Safety Information Please read this manual carefully before use this unit, and operate it correctly according to the guide in this manual. Please take specially note to the meaning of these two marks: Warning!: This mark means that it may cause casualty or badly heart if the operation is incorrect. Note!: This mark means that it may cause casualty or property loss if the operation is incorrect. Warning: ◆◆Do not adopt fuse with unsuitable capacity or adopt iron thread instead of fuse, otherwise malfunction or fire may happened. ◆◆Cut down the main power switch immediately if malfunction (such as smell the burning odor etc.) happened. ◆◆Maintain ventilation to prevent oxygen leakage in room. ◆◆Don’t insert finger or stick like things into discharge vent or outlet grill. ◆◆Please make sure that the unit is installed in the place that can bear the weight of it adequately. If the place is not strong enough, the air conditioner may drop and cause casualty event. ◆◆Don’t spray or smear any oil paint or insecticide on the surface of unit, otherwise, fire may be leaded. (1). Do not refit the conditioner. Please contact the agency or prefect ional personnel to repair or move the conditioner. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring. Note!: ◆◆Please check and make sure that the cord, drainage pipe and tubes are connected in the correct way to prevent leakage of water, refrigerant, electric shock or fire. ◆◆The main power must connectable to the earth in order to assure the conditioner earthing effectively and to prevent electric shock. Please don’t connect the earthing line with the gas pipe, water pipe, lightening rod or the connecting line of telephone. ◆◆The air conditioner should be turned off at least after 5 mins’ operation; otherwise it would affect the duration of the unit. ◆◆Don’t let the children operate the air conditioner. ◆◆Please don’t operate the unit by wet hand. ◆◆Please turn off the main power of the unit before cleaning the conditioner or change the filter. ◆◆Please cut off the main power if the conditioner will be used for a long time. 1 Install of The Compact Panel Cassette Type Indoor Unit 2 Install of The Compact Panel Cassette Type Indoor Unit 2.1 Schematic diagram of installation spaces H >20 Wall surface Wall surface Wall surface ≥1500 ≥2500 ≥1500 unit:mm Model H ISMI-C15 260 Ground surface Fig.1 2.2 Select install location of the indoor unit (1). Obstruct should put away from the intake or outlet vent of the indoor unit so that the airflow can be blown though all the room. (2). Make sure that the installation had accord with the requirement of the schematic diagram of installation spaces. (3). Select the place where can stand 4 times of the weight of the indoor unit and would not increase the operating noise and oscillate. (4). The horizontally of the installation place should be guaranteed. (5). Select the place where easy drain condensated coagulated water, and easy connect with outdoor unit. (6). Make sure that there are enough space for care and maintenance. Make sure that the weight between the indoor unit and ground is above 2500mm. (7). When installing the steeve bolt, check if the install place can stand the weight 4 times of the unit’s. If not, reinforce before installation. (Refer to the install cardboard and find where should be reinforced) Note! There will be lots of lampblack and dust stick on the acentric, heat exchanger and water pump in dining room and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the water pump. The following treatment should be taken under this circumstance: (8). Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft of the lampblack by the air conditioner. (9). Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air conditioner. 2 Install of The Compact Panel Cassette Type Indoor Unit 2.3 Important notice ◆◆To guarantee the good performance, the unit must be installed by professional personnel according with this instruction. ◆ Please contact the local Impecca special nominated repair department before installation. Any caused by the unit that is installed by the department that is not special nominated malfunction by Impecca would not deal with on time by the inconvenience of the business contact. 2.4 Dimension of ceiling opening and location of the hoisting screw (M10) 650 570 400 570 604 650 Fig.2 Install dimension of mode ◆◆The drilling of holes in the ceiling must be done by the professional personnel. Ceiling (160) Installation stands for main body of the unit Above 20 Fig.3 Notes: The dimension for the ceiling openings with * marks can be as large as 610mm. But the overlapping sections of the ceiling and the decorated surface boards should be maintained at no less than 20mm. 2.5 Main body of hoisting air conditioner (1). The primary step for install the indoor unit. ◆◆When attach the hoisting stand on hoisting screw, do use nut and gasket individually at the upper and lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket break off. (2). Use install cardboard. ◆◆Please refer to the install cardboard about the dimension of ceiling opening. ◆◆The central mark of the ceiling opening is marked on the install cardboard. 3 Install of The Compact Panel Cassette Type Indoor Unit ◆◆Install the install cardboard on the unit by bolt (3 piece), and fix the angle of the drainage pipe at the outlet vent by bolt. (3). Adjust the unit to the suitable install place. (Refer to the fig.3) (4). Check if the unit is horizontal. ◆ Inner drainage pump and bobber switch are included in the indoor unit, check if 4 angle of every unit are horizontal by water lever. (If the unit is slant toward the opposite of the coagulate water flow, there may be malfunction of the bobber switch and lead water drop.) (5). Backout the gasket anchor board used to prevent gasket break off and tighten the nut on it. (6). Backout the install cardboard. Fig.4 Note!: Please do tighten the nuts and bolts to prevent air conditioner break off. 2.6 Connection of the refrigerant pipe ◆ When connect the pipe to the unit or backout it from the unit, please do use both spanner and torque wrench. as shown in fig.5. ◆ When connect, smear both inside and outside of the flare nut with freeze motor oil, screw it by hand and then tighten it with spanner. ◆ Refer to form 1 to check if the wrench had been tightened (too tight would mangle the nut and lead leakage). ◆ Examine the connection pipe to see if it had gas leakage, then take the treatment of heat insulation, as shown in the fig.5. ◆ Only use median sponge to entwine the wiring interface of the gas pipe and heat preservation sheath of the gas collection tube. 4 Install of The Compact Panel Cassette Type Indoor Unit Smear freeze motoroil here Median sponge (attachment) (entwine the wiring interface with seal mat) Thread fasten(x4) Torque wrench Heat preservation sheath of liquid inlet tube (attachment) (for liquid tube) Spanner Flare nut Wiring interface Gas collection tube Liquid inlet tube Heat preservation sheath of gas collection tube (attachment)(for gas tube) Fig.5 Form 1: The tightening torque needed for tightening nut Diameter(Inch) Surface thickness(mm) Tightening torque (N·m) φ1/4’’ ≥ 0.5 15-30 (N·m) φ3/8’’ ≥ 0.71 30-40 (N·m) φ1/2’’ ≥1 45-50 (N··m) φ5/8’’ ≥1 60-65 (N·m) φ3/4’’ ≥1 70-75 (N··m) 2.7 Drainage hose (1). Install the drain hose ◆ The diameter of the drain hose should be equal or bigger than the connection pipe’s. ( The diameter of polythene pipe: Outer diameter 25mm Surface thickness ≥ 1.5mm) ◆ Drain hose should be short and drooping gradient should at less 1/100 to prevent the formation of air bubble. ◆ If drain hose cannot has enough drooping gradient, drain raising pipe should be added. ◆ To prevent bent of the drain hose, the distance between hoisting stand should is 1 to 1.5m. Fig.6 ◆ Use the drain hose and clamp attached. Insert the drain hose to the drain vent, and then tighten the clamp. ◆ Entwine the big sponge on the clamp of drain hose to insulate heat. ◆ Heat insulation should be done to indoor drain hose. 5 Install of The Compact Panel Cassette Type Indoor Unit Sponge(attachment) Clamp(attachment) Clamp Sponge (gray) Drain hose Below 4mm Fig.7 Drain stepup pipe note ◆ The install height of the drain raising pipe should less than 280mm. ◆ The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm. Fig.8 Instruction ◆ The slant gradient of the attached drain hose should be within 75mm so that the drain hole doesn’t has to endure the unnecessary outside force. Fig.9 ◆ Please install the drain hose according to the following process if several drain hoses join together. Fig.10 (2). Check the smoothness of drain after installation. ◆ Check the drain state by immitting 600cc water slowly from the outlet vent or test hole. ◆ Check the drain in the state of refrigerating after installation of the electric circuit. 6 Install of The Compact Panel Cassette Type Indoor Unit Fig.11 2.8 Electrical wiring Note:The power of the entire indoor unit must be connected in outdoor unit. ◆ About the electrical wiring, please see the circuit diagram attached with the unit. ◆ All the installation of electrical wiring must be done by professional personnel. ◆ Please do take the earthing treatment. Wiring method of connection unit and controller ◆ Connection wiring (communication): ① Open electric box cover, drag the wiring (communication)from the rubber plug A, and impact them well individually by impact fastener. ② Wiring according to the indoor side circuit diagram. ◆ Fix the impact fastener after connection. ◆ Entwine the small sponge on the electric wire( do entwine it to prevent condensation). ◆ Impact tightly by impact fastener after connection and then fit on the electric box. ◆ Connect the 3 cord rubber wire to the counter terminal of the 3 way terminal board. The power cord reference Power cord standard recommending table Fig.12 Power cord standard recommending table Power Supply (V, Ph, Hz) Min. Sectional Area of Min. Sectional Area of Earth Wire(AWG) 208~203V-1Ph-60Hz UL1015 AWG 18*1 7 Power Cord(AWG) UL1015 AWG 18*3 Install of The Compact Panel Cassette Type Indoor Unit 2.9 Install the panel (1). Set the panel to the indoor unit body by matching the position of the swing flap motor of the panel to the piping position of the panel to the piping position of the indoor unit as shown by fig.13. (2). Install the panel ① .Install the panel on the indoor unit temporarily. When install, hang the latch on the hook that is located on the opposite side of the swing flap on the panel of the indoor unit. (2 positions) ② .Hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not to let the swing motor lead wire get caught in the sealing material.) ③ .Screw the 4 hexagon head screws under the latches in about 15mm. (The panel would rise) ④ .Adjust the panel by turning it toward the direction pointed by the arrow as shown in fig.13, so that the adjust board connect the ceiling well. ⑤ .Tighten the screws until the thickness of the sealing material between panel and indoor unit reduced to 5-8mm. Fig.13 Notes: ① .Improper screwing of the screws may cause the troubles shown in fig.14. 8 Install of The Compact Panel Cassette Type Indoor Unit Air leak Air leak from ceiling Water condensatation, water drop Fig.14 ② .If gap still exist between ceiling and decoration panel after tightening the screws, readjust the height of the indoor unit. (As shown in fig.15) If the raising lever and drain hose are not affect, can adjust the height of indoor unit by the hole on the corner of panel. Gaps are not allowed Fig.15 ※ After fixing, be sure no gap left between the ceiling and the panel. ③ .Wiring of the decoration panel (Fig.16) Connect the joints for swing flap motor lead wire (at 2 places) installed on the panel. At body At body At pane Fig.16 9 At pane Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit 3 Constitutes and Names of Parts of Compact Panel Cassette Type Indoor Unit 10 Working Temperature Range 4 Working Temperature Range Working Temperature Range Indoor side state Outdoor side stae Dry bulb temp. ℃ Wet bulb temp. ℃ Dry bulb temp. ℃ Wet bulb temp. ℃ Rated Cooling 27 19 35 24 Max. cooling 32 23 48 26 Min. cooling 21 15 18 — Rated Heating 20 15 7 6 Max. heating 27 — 24 18 Min. heating 20 15 - 15 - 16 11 Malfunction Debarring 5 Malfunction Debarring Warning! ◆ Cut down the main power switch immediately if malfunction (such as smell the burning odor etc.) happened, and then contact service center. If the abnormal state is maintained, the unit may be damaged or electric shock or fire may be happened. ◆ Do not refit the conditioner. Please contact service center to repair or move the conditioner. 5.1 Check the following items before contacting maintenance center Phenomena Reason Remedial Measures Blow of fuse or breaker Change fuse or close breaker Power cut Air conditioner doesn’t run at all Don’t connect with power Low batteries of wireless remote controller Connect power well Change new batteries Signal could be received within remote control area 8m Air conditioner runs Blockage in inlet or outlet vent of indoor or outdoor unit Blockage in inlet or outlet vent of indoor or outdoor unit Improper of temp. setting Low setting of fan speed Incorrect of wind direction heating supply Wireless remote controller exceed but stops immediately Abnormal cooling or Restart when there is power Door or window opened Direct sun burn Clean out blockage Clean out blockage Adjust settings in wireless remote controller Adjust settings in wireless remote controller Adjust settings in wireless remote controller Close Hang curtain or jalousie before windows Too many people in room Too many heater in room Filter blocked by dirt 12 Clean filter Malfunction Debarring 5.2 Instruction If problem still cannot found out after above checking, please contact service center and instruct phenomena and model. 5.3 The following circumstance are not malfunction “Malfunction” Air conditioner doesn’t Reason Start up unit immediately after The overload protects switch turned off makes it run after 3 minutes delay. run When opening power Mist is blown from air When cooling conditioner Slight click sound heard once Noise is heard from air conditioner Run for about 1 minute without other actions The high humidity air in room is cooled rapidly Sound of initialization for electric begin running expand valve Hissing sound heard continuously The sound for gas refrigerant when cooling flowing in the unit Hissing sound heard when staring The sound for gas refrigerant or stopping stops flow Slight hissing sound heard when Sound for running of drainage running or after running Creak sound heard when running or after running Dust be blown for air Started up after long time’s doesn’t conditioner runs system The grating sound caused by expands of panel and other parts for the change of temperature Dust in indoor unit be blown out This is because when air Odor gives out from air conditioner When running conditioning, odors or cigarette smoke from the room that was sucked in is discharged again. 5.4 After-sales Service When having quality or other problems when purchasing air conditioner, please contact the local service center. 13 Maintenance Method 6 Maintenance Method When air conditioner won’t be used for a long time, please cut off the main power supply of air conditioner. Warning! ◆ Do turn off the unit and cut off the main power supply when cleaning the air conditioner, otherwise electric shock or harm may happen. ◆ It is forbidden to wash air conditioner by water rinsing, otherwise electric shock may happen. 6.1 Cleaning air filter Air filters should be cleaned by professionals with proper operation to ensure personal safety. When the usage environment has lots of dust, air filter should be cleaned more frequently (about once 6 months). (1). Open air inlet grille Loosen two screws on the air inlet grille with a screwdriver. And pull the 2 handle on air inlet grille at the same time with the direction showed by arrow in fig.17, pull down slowly. (Reverse when closing) (2). Disassembly air filter As shown in fig.18, pull the handle behind air inlet grille, raise it and disassembly. Then discharge the 3 purifier fixed on filter. purifier Fig.17 Fig.18 (3). Clean Adopts cleaner or water to wash filter; if the filter is too dirty ( like oil stain on it ), adopts warm water ( lower than 45℃ ) with neutral scourer to clean it, then dry it in the shade. Note ! Do not clean the filter by hot water whose temp. is higher than 45 ℃ to prevent fade or deformation. Do not burn it on fire or the filter would catches fire or deformation. (4). Install air filter Fix the 3 purifiers on filter, install filter on the several bulges on top of air inlet grille, pull the handle behind air inlet grille toward inside to fix filter. As shown in fig.19. 14 Maintenance Method (5). Close air inlet grille (Refer to the 1st step) Maintenance Method Fig.19 Fig.20 6.2 Clean air inlet grille (1). Open air inlet grille (the same with the 1st step of Clean Air Filter) (2). Take out air filter (the same with the 2nd step of Clean Air Filter) (3). Take out air inlet grille Open air inlet grille for an angle of 45°, as shown in fig.20, rise it. (4). Clean Clean it by pubescence brush, water and neutral cleaning, then throw water or dry it. Note ! Do not use water above 45℃ to wash the panel to prevent fade or deformation. (5). Install air inlet grille (refer to 3rd step) (6). Install air filter (refer to the 4th step of Clean Air Filter) (7). Close air inlet grille (refer to the 1st step) 6.3 Install and change of air purifier (1). Open air inlet grille (the same the 1st step of Clean Air Filter) (2). Disassembly purifier As shown in fig.21, disassembly air filter, screw out fixing bolts fixed on purifier on filter, then purifier could be disassembly. (3). Take out the package sack of static fiber net filter, then install the filter in stand of purifier, and fix purifier on air filter. (4). Install air filter (the same with the 4th step of Clean Air Filter) Air filter Purifier filter Stand for purifier Fix bolt of purifier Fig.21 15 Maintenance Method Function and usage period for air purifying ◆ Could adsorb CO, CO2, benzene, aldehydes and odor of gasoline etc.. ◆ Could adsorb deleterious material that is smaller than 1μm in air, as dust, pollen, bacteria, and virus. ◆ Usage period is 6 months to 1 year. If it is necessary to be changed, purchase new purifier in the nearest Impecca special engaged maintenance center. 6.4 Clean Outlet vent and Surface ◆ Clean the surface panel by soft dry cloth or wet cloth with neutral scourer. Panel ◆ It is forbidden to clean surface panel by gasoline, benzene, diluents, cleansing powder etc.. ◆ If the guide louver is too dirty, it may be removed to be cleaned. (As narrated below) Disassembly and install of guide louver (1). Disassembly guide louver Screw bolts in both end of guide louver to loose. Note ! Do not wipe guide louver powerfully when cleaning, otherwise fluff on surface would fall off. (2). Install guide louver Rotate guide louver slightly could install the protruding edge of both end into grooves on both end of guide louver, and then tighten bolts. 6.5 Maintenance before or after usage season Check before the usage season ◆ Check if there is blockage in inlet or outlet vent of air conditioner. ◆ Check if the earthing wire had earthed reliably. ◆ Check if the air filter had been installed well. ◆ In order to start up the air conditioner smoothly after long time’s turned off, turn on the main power supply 8 hours before turning on the air conditioner. Maintenance after usage season ◆ Clean filter and body of air conditioner. ◆ Cut off the main power supply of air conditioner. ◆ The cooling or heating capacity and sound level are tested before leaving factory. ◆ If the parameter changed, refer to the data offered on nameplate. 6.6 CUSTOMER SUPPORT Before contacting customer support, please see the troubleshooting guide above. Visit our website to contact us, find answers to Frequently Asked Questions, and for other resources which may include an updated version of this user's guide. WWW.IMPECCA.COM If you wish to contact us by phone, please be sure to have your model number and serial number ready and call us between 9:00am and 6:00pm ET, at +1 866-954-4440. Keep tabs on Impecca's newest innovations & enter contests via our social network feeds: www.facebook.com/Impecca/ www.instagram.com/impecca/ @impeccausa 16 © 2016 Impecca, a division of LT Inc., Wilkes Barre, PA. Flex Series R410A GMV Multi VRF Cassette Type Indoor Unit (For North America) Owner's Manual Commercial Air Conditioners Model: ISMI-C24 Thank you for choosing Commercial Air Conditioners, please read this owner’s manual carefully before operation and retain it for future reference. User Notice ◆ The total capacity of the indoor units which runs at the same time can not exceed 150% of that of outdoor units; otherwise, the cooling (heating) effect of each unit would be poor. ◆ A breaker (or fuse) needs to be installed in every indoor unit, and the capacity should be in accordance with indoor unit’s electrical parameter; all the indoor units are required to be centralized controlled by a main switch, this switch can cut off the electric power supply in case of emergency. The breaker (or fuse) on each indoor unit has the function of preventing short circuit and avoiding abnormal overload, it should be connected in normal situation. The main switch controls the power supply of all the indoor units. Before cleaning and maintaining the indoor units, it is very important to turn off the main power supply switch. ◆ In order to turn on the units successfully, the main power switch should be opened 8 hours before the operation. ◆ It is a normal phenomenon that the indoor unit will still run for 20-70 seconds after the indoor unit receives the "stop" signal so as to make full use of after-heat for the next operation. ◆ When the running modes of the indoor and outdoor units conflict, it will be indicated on the display of the wired controller in five seconds and then the indoor unit will stop. At this time, change the operation mode of the indoor unit to the one that would not clash with the outdoor operating mode to make the operation normal. The HEAT mode conflicts with each of the COOL mode, DRY mode and FAN mode, while the COOL mode, DRY mode and FAN mode are compatible between each other. ◆ The appliance shall not be installed in moist places, such as laundry. ◆ An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring. ◆ Main switch is provided by end user. Main switch knob should be in black or gray, it can be locked on “OFF” with padlock. ◆ The instruction of main power switch should be included in user manual and the recommended installing height should be at 0.6-1.7m. And also over current protection is required (UL 1995,CSA C22.2). ◆ The outdoor ambient temperature of the unit under cooling mode ranges from -5~48°C DB. The outdoor ambient temperature of the unit (only for the heat pump type unit) under heating mode ranges from -15~27°C WB. ◆ This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. This product must not be disposed together with the domestic waste. This product has to be disposed at an authorized place for recycling of electrical and electronic appliances. Thank you for selecting Impecca air conditioner. Before use, please read this manual carefully and keep it properly for furthur reference. Contents 1 Safety Precautions������������������������������������������������������������������������������������������ 1 2 Installation of the Cassette Type Indoor Unit��������������������������������������������������� 2 2.1 Schematic Diagram of Installation Spaces������������������������������������������������������������ 2 2.2 Installation Location of the Indoor Unit������������������������������������������������������������������� 2 2.3 Important Notice:���������������������������������������������������������������������������������������������������� 3 2.4 Dimension of Ceiling Opening and Location of the Hoisting Screw (M10)������������ 3 2.5 Main Body of Hoisting Air Conditioner������������������������������������������������������������������� 4 2.6 Connection of the Refrigerant Pipe������������������������������������������������������������������������ 4 2.7 Drain Hose������������������������������������������������������������������������������������������������������������� 5 2.8 Electrical wiring������������������������������������������������������������������������������������������������������ 7 2.9 Install the Panel����������������������������������������������������������������������������������������������������� 9 3 Parts and Components of Cassette Type Indoor Unit ��������������������������������� 12 4 Working Temperature Range������������������������������������������������������������������������� 13 5 Trouble Shooting������������������������������������������������������������������������������������������� 14 6 Maintenance Method������������������������������������������������������������������������������������� 16 6.1 Cleaning Air Filter������������������������������������������������������������������������������������������������� 16 6.2 Clean Air Inlet Grille��������������������������������������������������������������������������������������������� 17 6.3 Install and Change of Air Purifier������������������������������������������������������������������������� 17 6.4 Clean Outlet Vent and Surface Panel������������������������������������������������������������������ 18 6.5 Maintenance before or after Seasonal Use��������������������������������������������������������� 18 Flex Series for North America 1 Safety Precautions Please read this manual carefully before using this unit, and operate it correctly according to the guide in this manual. Please take special attention to the meaning of these two marks: Warning! It indicates improper operation which will lead to human casualty or severe injury. Note! It indicates improper operation which will lead to injury or property damage. Warning: ◆ Do not adopt fuse with unsuitable capacity or adopt iron wire instead of fuse, otherwise malfunction or fire may happen. ◆ Turn off the main power switch immediately if malfunction (such as smell the burning odor etc.) happens. ◆ Keep good ventilation in the room to avoid oxygen deficit. ◆ Don’t insert finger or stick-like objects into the air inlet/outlet grille. ◆ Please install the unit in a place where is strong enough to withstand the weight of the unit; otherwise, the unit would fall down and cause injury or death. ◆ Don’t apply or spray and paint or insecticide on the surface of unit, otherwise, fire may happen. ◆ Never refit the unit and contact the sales agent or the professional installation personnel for the repair or relocation of the unit. An all-pole disconnection switch having a contact separation of at least 3mm in all poles should be connected in fixed wiring. Note: ◆ Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant leakage, electric shock, or fire etc. ◆ The main power supply must be earthed soundly to avoid the hazard of electric shock and never connect this earth wire to the gas pipe, running water pipe, lightening rod or phone cable's earth lead. ◆ Turn off the unit after it runs at least five minutes; otherwise its service life will be shortened. ◆ Don’t allow children operate the air conditioner. ◆ Don’t allow children operate the air conditioner. ◆ Please turn off the main power of the unit before cleaning the conditioner or change the filter. ◆ Please cut off the main power if the conditioner will not be used for a long time. 1 Flex Series for North America 2 Installation of the Cassette Type Indoor Unit 2.1 Schematic Diagram of Installation Spaces H >20 Wall surface Wall surface Wall surface unit:mm Model H ISMI-C24 260 Ground surface Fig.1 2.2 Installation Location of the Indoor Unit (1). Obstruct should be taken away from the inlet or outlet of the indoor unit so that the airflow can be blown though all the room. (2). Ensure the installation work is done as per the schematic diagram of installation spaces. (3). Select a place where is strong enough to withstand 4 times of the weight of the indoor unit; otherwise it would incur vibration and noise. (4). Ensure the installation place is at horizontal level. (5). Select a place where the condensate water is easily drained out and the drain pipe can be easily connected with outdoor unit. (6). Make sure that there is enough space for care and maintenance. Make sure that the distance between the indoor unit and ground is above 1800mm. (7). When installing the steeve bolt, check if the installing place can stand 4 times of the weight of the units. If not, reinforce before installation. (Refer to the installation cardboard and find where should be reinforced) Note! There will be lots of lampblack and dust sticking on the acentric, heat exchanger and water pump in dining room and kitchen, which would reduce the capacity of heat exchanger, lead water leakage and abnormal operation of the water pump. The following treatment should be taken under this circumstance: 1). Ensure that the smoke trap above cooker has enough capacity to obviate lampblack to prevent the indraft of the lampblack by the air conditioner. 2 Flex Series for North America 2). Keep the air conditioner far from the kitchen so that the lampblack would not be indraft by the air conditioner. 2.3 Important Notice: ◆ To guarantee the good performance, the unit must be installed by technician according with this instruction. ◆ Please contact the local Impecca special nominated repair department before installation. Any caused by the unit that is installed by the department that is not special nominated malfunction by Impecca would not deal without time by the inconvenience of the business contact. 840(Indoor unit) 780(Gaps between hoisting screw rods) 890*(Ceiling opening) 950(Decorated surface boards) 2.4 Dimension of Ceiling Opening and Location of the Hoisting Screw (M10) Refrigerant pipe Hoisting screw (X4) 680(Gaps between hoisting screw rods) 840(Indoor unit) 890(Ceiling opening) 950(Decorated surface boards) A Fig.2 Install Dimension of Model ISMI-C24 ◆ The drilling of holes in the ceiling must be done by the technicians. Ceiling (160) Installation stands for main body of the unit Above 20 Fig.3 Notes: The dimension for the ceiling openings with * marks can be as large as 910mm. But the overlapping sections of the ceiling and the decorated surface boards should be maintained at no less than 20mm. 3 Flex Series for North America 2.5 Main Body of Hoisting Air Conditioner (1). The primary step for installing the indoor unit. ◆ When attach the hoisting stand with hoisting screw, do use nut and gasket respectively at the upper and lower of the hoisting stand to fix it. The use of gasket anchor board can prevent gasket from breaking off. (2). Use installation cardboard ◆ Please refer to the installation cardboard about the dimension of ceiling opening. ◆ The central mark of the ceiling opening is marked on the installation cardboard. ◆ Install the installation cardboard on the unit by bolts (3 pieces), and fix the angle of the drainage pipe at the outlet vent by bolt. (3). Adjust the unit to the suitable install place. (Refer to the Fig.4) (4). Check if the unit is horizontal. ◆ Inner drainage pump and float switch are included in the indoor unit, check if 4 angle of every unit are horizontal by water level. (If the unit is slant toward the opposite of the coagulate water flow, there may be malfunction of the float switch and lead water drop.) (5). Back-out the gasket anchor board used to prevent gasket from breaking off and tighten the nut on it. (6). Back-out the installation cardboard. Nut(supplied at scene) Gasket(attachment) Insert Hoisting stand Gasket anchor board(attachment) Tighten(double nuts) [Fix the hoisting stand firmly] [Fix the gasket firmly] Bolt of one of the angle of outlet pipe is fix on the angle of the drainage solt Center of the ceiling Install cardboard opening Water lever Polyethylene pipe Bolt(attachment) Bolt(attachment) [Fix the install cardboard] Fig.4 Note! ● Please do tighten the nuts and bolts to prevent air conditioner from falling down. 2.6 Connection of the Refrigerant Pipe ◆ When connect the pipe to the unit or remove it from the unit, please do use both spanner 4 Flex Series for North America and torque wrench. as shown in Fig.5. ◆ When connect, smear both inside and outside of the flare nut with freeze motor oil, screw it by hand and then tighten it with spanner. ◆ Refer to Table 1 to check if the nut has been tightened (tighten too greatly would damage the nut and lead to leakage). ◆ Examine the connection pipe to see if it has gas leakage, then take the treatment of heat insulation, as shown in the Fig.5. ◆ Only use medium-sized sponge to entwine the wiring interface of the gas pipe and heat insulation of the gas collection tube. Smear freeze motoroil here Median sponge (attachment) (entwine the wiring interface with seal mat) Thread fasten(X4) Torque wrench Heat preservation sheath of liquid inlet tube (attachment) (for liquid tube) Spanner Gas collection tube Wiring interface Flare nut Heat preservation sheath of gas collection tube (attachment)(for gas tube) Liquid inlet tube Fig.5 Table 1: The moment of torque for tightening nut Diameter(Inch) Surface thickness(mm) Moment of torque (N·m) φ1/4’’ ≥ 0.5 15-30 (N·m) φ3/8’’ ≥ 0.71 30-40 (N·m) φ1/2’’ ≥1 45-50 (N··m) φ5/8’’ ≥1 60-65 (N·m) φ3/4’’ ≥1 70-75 (N··m) If the specification of the outdoor unit pipe joint does not conform to that of the indoor unit, then the joint specification of the outlet pipe of the indoor unit takes precedence. A reducing nipple shall be installed at the joint of the outdoor unit so as to make the joint of the outdoor unit compatible with that of the indoor unit. 2.7 Drain Hose (1). Install the drain hose ◆ The diameter of the drain hose should be equal or larger than that of connection pipes. ( The diameter of polythene pipe: Outer diameter: 25mm; Surface thickness ≥1.5mm) ◆ Drain hose should be short and drooping gradient should at least 1/100 to prevent the 5 Flex Series for North America formation of air bubble. ◆ If drain hose cannot has enough drooping gradient, drain raising pipe should be added. ◆ To prevent bent of the drain hose, the distance between hoisting stand and the drain hose should be 1 to 1.5m. 1-1.5m (Correct)1/100 or more gradient (Wrong) Fig.6 ◆ Use the drain hose and clamp attached. Insert the drain hose to the drain vent, and then tighten the clamp. ◆ Wrap clamp with sponge on the drain hose to insulate heat. ◆ Heat insulation should be done to indoor drain hose. Sponge(attachment) Clamp(attachment) Clamp Sponge (gray) Drain hose Below 4mm Fig.7 Drain Stepup Pipe Note ◆ The installation height of the drain raising pipe should less than 280mm. ◆ The drain raising pipe should form a right angle with the unit, and distance to unit should not beyond 300mm. Roof Within 300mm 1-1.5m Drain hose(attachment) Hoisting stand Drain raising hose 220mm CeilingC Below 500mm Below 280mm lamp(attachment) Fig.8 Instruction ◆ The fall of the attached drain hose should be within 75mm so that the joint of the drain pipe doesn’t have to endure the unnecessary outside force. 6 Below 500mm Drain hose(attachment) Below 75mm Flex Series for North America Fig.9 ◆ Please install the drain hose according to the following process if several drain hoses join together. Above 100mm T-tie in join drain hose The specs of the selected jion drain hose should fits the running capacity of the unit Fig.10 (2). Check the drain state after installation ◆ Check the drain state by immitting 600ml water slowly from the outlet vent or test hole. ◆ Check the drain state under cooling mode after electric circuit installation work is done. Drain hose [Way of immiting] Drain vent for repair use (plasticstopper is included) (drain the waterin waterspout by this outlet vent) Above 100m Test hole cover Test hole [Immiting water from the rest hole] Plastic water pot (The length of the pipe should be about 100mm) [Immiting water from the outlet vent terminal] Fig.11 2.8 Electrical wiring Note:The power of the entire indoor unit must be connected with outdoor unit. ◆ About the electrical wiring, please see the circuit diagram attached with the unit. ◆ All the installation of electrical wiring must be done by technicians. ◆ Please do take the earthing treatment. Wiring Method of Connection Unit and Controller 7 Flex Series for North America ◆ Connection wiring (communication): ① Open electric box cover(1), drag the wiring (communication)from the rubber plug A, and impact them well individually by impact fastener. ② Wiring according to the indoor side circuit diagram. ◆ Fix the impact fastener after connection. ◆ Wrap the small-sized sponge on the electric wire (do entwine it to prevent condensation). ◆ Impact tightly by impact fastener after connection and then fit on the electric box (1) and (2). ◆ Put the 4-core cable through the hole of the chassis and the bottom of the appliance upward, and then connect the power line and the communication line from the outdoor unit to the corresponding terminals N(1), 2, 3 , and grounding terminal of the indoor unit. Wiring shall be done properly as per the wiring diagram. (Note: Be sure the wring terminals A/B/C/D and piping joints A/ B/C/D of the indoor unit match with that of the outdoor unit respectively). To indoor unit Power supply 3 way terminal board 4 core rubber wire To indoor unit Impact fastener Cable-cross loop Electric box cover(2) Do seal here to prevent water inleakage from here Cable-cross loop Electric box cover(1) Fig.12 GWHD(36)ND3AO INDOOR UNIT D POWER INDOOR UNIT C INDOOR UNIT B INDOOR UNIT A N L XT XT OUTDOOR UNIT 8 XT2 Flex Series for North America GWHD(42)ND3AO INDOOR UNIT E XT6 G INDOOR UNIT D XT5 G G INDOOR UNIT B OUTDOOR UNIT INDOOR UNIT C XT4 XT3 G INDOOR UNIT A XT2 G L N POWER XT1 2.9 Install the Panel 1. Set the panel to the indoor unit body by matching the position of the swing flap motor of the panel to the piping position of the panel to the piping position of the indoor unit as shown by Fig.13. 2. Install the panel (1). Install the panel on the indoor unit temporarily. When install, hang the latch on the hook that is located on the opposite side of the swing flap on the panel of the indoor unit. (2 positions) (2). Hang the remaining 2 latches to the hooks on the sides of the indoor unit.(Be careful not to let the swing motor lead wire get caught in the sealing material.) 9 Flex Series for North America (3). Screw the 4 hexagon head screws under the latches in about 15mm. (The panel would rise) (4). Adjust the panel by turning it toward the direction pointed by the arrow as shown in Fig.13, so that the adjust board connect the ceiling well. (5). Tighten the screws until the thickness of the sealing material between panel and indoor unit reduced to 5-8mm. Hook Latch Piping position Swing flap motor Sealing material Indoor unit Ceiling 5mm to 8mm Air outlet vent Decoration panel Fig.13 Notes: ① .Improper screwing of the screws may cause the troubles shown in Fig.14. 10 Flex Series for North America Air leak Air leak from ceiling Water condensatation, water drop Fig.14 ② .If gap still exist between ceiling and decoration panel after tightening the screws, readjust the height of the indoor unit. (As shown in Fig.15) If the raising lever and drain hose are not affect, can adjust the height of indoor unit by the hole on the corner of panel. Gaps are not allowed Fig.15 ※ After fixing, be sure that there is no gap between the ceiling and the panel. ③ .Wiring of the decoration panel (Fig.16) Connect the joints for swing flap motor lead wire (at 2 places) installed on the panel. At body At body At pane Fig.16 11 At pane Flex Series for North America 3 Parts and Components of Cassette Type Indoor Unit Drainage equipment (inside type) Discharge cindensate water from indoor unit when cooling Drainage hose Guide louver (placed in air outlet vent) Air outlet vent Connecting pipe Air filter, purifire (in air inlet grille) Air inlet grille Fig.17 ISMI-C24 12 Flex Series for North America 4 Working Temperature Range Working Temperature Range Indoor side state ℉(℃) Wet bulb Dry bulb temp. ℉(℃) temp. ℉(℃) Outdoor side state ℉(℃) Dry bulb temp. ℉(℃) Wet bulb temp. ℉(℃) Rated. Cooling 80.0(26.7) 67.0(19.4) 95.0(35.0) 75.0(23.9) Max. cooling 80.0(26.7) 67.0(19.4) 115.0(46.1) 75.0(23.9) Min. cooling 67.0(19.4) 57.0(13.9) 67.0(19.4) 57.0(13.9) Rated. Heating 70.0(21.1) 60.0(15.6) 47.0(8.3) 43.0(6.1) Max. heating 80.0(26.7) — 75.0(23.9) 65.0(18.3) Low Ambient heating 70.0(21.1) 60.0(15.6) 5.0(-15.0) 3.2(-16.0) 13 Flex Series for North America 5 Trouble Shooting Warning! ◆ Cut down the main power switch immediately if malfunction (such as smell the burning odor etc.) happens, and then contact service center. If the abnormal state is maintained, the unit may be damaged or electric shock or fire may happen. ◆ Do not refit the conditioner. Please contact service center to repair or move the conditioner. ★ Check the following items before contacting maintenance center Phenomena Air conditioner doesn’t run at all Air conditioner runs but stops immediately Abnormal cooling or heating Reason Remedial Measures Blow of fuse or breaker Change fuse or close breaker Power cut Restart when there is power supply Don’t connect with power Connect power well Low batteries of wireless remote controller Change new batteries Wireless remote controller exceed remote control area Signal could be received within 8m Blockage in inlet or outlet vent of indoor or outdoor unit Clean out blockage Blockage in inlet or outlet vent of indoor or outdoor unit Clean out blockage Improper of temp. setting Adjust settings in wireless remote controller Low setting of fan speed Adjust settings in wireless remote controller Incorrect of wind direction Adjust settings in wireless remote controller Door or window opened Close Direct sun burn Hang curtain or jalousie before windows Too many people in room Too many heater in room Filter blocked by dirt Clean filter ★ Instruction If problem still cannot be solved after above checking, please contact service center. 14 Flex Series for North America ★ The following circumstance doesn't belong to malfunction “Malfunction” Air conditioner doesn’t run Mist is blown from air conditioner Noise is heard from air conditioner Dust be blown for air conditioner Odor gives out from air conditioner Reason Start up unit immediately after turned off The overload protects switch makes it run after 3 minutes delay. When opening power Run for about 1 minute without other actions When cooling The high humidity air in room is cooled rapidly Slight click sound heard once begin running Sound of initialization for electric expand valve Hissing sound heard continuously when cooling The sound for gas refrigerant flowing in the unit Hissing sound heard when staring or stopping The sound for gas refrigerant stops flow Slight hissing sound heard when running or after running Sound for running of drainage system Creak sound heard when running or after running The grating sound caused by expands of panel and other parts for the change of temperature Started up after long time’s doesn’t runs Dust in indoor unit be blown out When running This is because when air conditioning, odors or cigarette smoke from the room that was sucked in is discharged again. ★ After-sales Service If there is any quality or other issues after purchasing air conditioner, please contact the local service center. 15 Flex Series for North America 6 Maintenance Method When the unit won’t be used for a long time, please cut off the main power supply of air conditioner. Warning! ◆ Do turn off the unit and cut off the main power supply when cleaning the air conditioner, otherwise electric shock or harm may happen. ◆ It is forbidden to wash air conditioner by water rinsing, otherwise electric shock may happen. 6.1 Cleaning Air Filter When the usage environment has lots of dust, air filter should be cleaned more frequently (about once 6 months). (1). Open air inlet grille Pull the 2 handles on air inlet grille at the same time with the direction showed by arrow in Fig. 18, pull it down slowly. (As per the reverse disassembly order when closing) (2). Disassemble air filter As shown in Fig. 19, pull the handle behind air inlet grille, raise it and disassemble. Then remove the 3 purifiers fixed on filter. purifier Fig. 18 Fig. 19 (3). Clean Use a cleaner or some water to wash filter; if the filter is too dirty ( like oil stain on it ), use some warm water ( lower than 45℃ ) with neutral detergent to clean it, then dry it in the shade. Note! Do not clean the filter by hot water which temp. is higher than 45 ℃ to prevent fading or deformation. Do not place the filter near fire; otherwise the filter may catch fire or lead to deformation. (4). Install air filter Fix the 3 purifiers on filter, install filter on the several bulges on top of air inlet grille, pull the handle behind air inlet grille toward inside to fix filter. As shown in Fig. 20. (5). Close air inlet grille (Refer to the 1st step) Maintenance Method 16 Flex Series for North America Fig. 20 Fig. 21 6.2 Clean Air Inlet Grille (1). Open air inlet grille (the same with the 1st step of Clean Air Filter) (2). Take out air filter (the same with the 2nd step of Clean Air Filter) (3). Take out air inlet grille Open air inlet grille for an angle of 45°, as shown in fig. 21, raise it. (4). Clean Clean it by soft brush, water and neutral cleaning, then dry it after cleaning. Note! Do not use water above 45℃ to wash the panel to prevent fading or deformation. (5). Install air inlet grille (refer to 3rd step) (6). Install air filter (refer to the 4th step of Clean Air Filter) (7). Close air inlet grille (refer to the 1st step) 6.3 Install and Change of Air Purifier (1). Open air inlet grille (the same the 1st step of Clean Air Filter) (2). Disassembly purifier As shown in fig 22, disassembly air filter, screw out fixing bolts fixed on purifier on filter, then purifier could be disassembly. (3). Take out the package sack of static fiber net filter, then install the filter in stand of purifier, and fix purifier on air filter. (4). Install air filter (the same with the 4th step of Clean Air Filter) Air filter Purifier filter Stand for purifier Fix bolt of purifier Fig.22 17 Flex Series for North America Function and usage period for air purifying ◆ Adsorb CO, CO2, benzene, aldehydes and odor of gasoline etc.. ◆ Adsorb poisonous material that is smaller than 1μm in air, as dust, pollen, bacteria, and virus. ◆ Usage period is 6 months to 1 year. If it is necessary to be changed, purchase new purifier in the nearest Impecca special engaged maintenance center. 6.4 Clean Outlet Vent and Surface Panel ◆ Clean the surface panel by soft dry cloth or wet cloth with neutral scourer. ◆ It is forbidden to clean surface panel by gasoline, benzene, diluents, cleansing powder etc.. ◆ If the guide louver is too dirty, it may be removed to be cleaned. (As narrated below) Disassembly and installation of guide louver (1). Disassemble guide louver Screw bolts in both ends of guide louver to loose. Note! Do not forcibly wipe guide louver when cleaning, otherwise painted surface layer would fall off. (2). Install guide louver Rotate guide louver slightly could install the protruding edge of both end into grooves on both end of guide louver, and then tighten bolts. 6.5 Maintenance before or after Seasonal Use Check before the seasonal use ◆ Check if there is blockage at inlet or outlet of air conditioner. ◆ Check if the earthing wire has been earthed reliably. ◆ Check if the air filter has been installed well. ◆ In order to start up the air conditioner smoothly after long time’s turned off, turn on the main power supply 8 hours before turning on the air conditioner. Maintenance after seasonal use ◆ Clean filter and body of air conditioner. ◆ Cut off the main power supply of air conditioner. ◆ The cooling or heating capacity and sound level are tested before leaving factory. ◆ If the parameter changes, refer to the data offered on nameplate. 6.6 Technical Support Before calling technical support, please see the troubleshooting guide above. You may also visit our website at www.impecca.com for answers to Frequently Asked Questions and to contact us. Email: [email protected] Phone: +1 866–954–4440 Web: www.impecca.com 18 Flex Series Outdoor Unit Owner's Manual Commercial Air Conditioners Model: ISMO-4221 Thank you for choosing our air conditioner, please read this Owner's manual carefully before operation and retain it for future reference. v. 1.1 Preface Impecca Flex System adopts the cutting-edge manufacturing technology and takes global acknowledged, environmental- friendly R410A as refrigerant, which is a green product in the 21 st century. Please carefully read this manual before installation and operation. Instructions before reading this manual: (1) This unit measures on the base of UL1995. (2) Flex System conforms to design standard: ARI 210240-2008. (3) For guaranteeing personal safety when operating this system, please strictly follow the instructions listed in the manual. (4) The total capacity of the indoor units which runs at the same time can not exceed that of the outdoor units; otherwise, the cooling (heating) effect of each indoor unit would be poor. Minimum number of connectible indoor units 2 Maximum number of connectible indoor units 5 Minimum capacity of connectible indoor units 18KBtu Maximum capacity of connectible indoor units 51KBtu (5) Switch the main power on 8 hours before starting the unit, helpful for a successful startup. (6) It is a normal phenomenon that the indoor unit fan will still run for 20~70 seconds after the indoor unit receives the “stop” signal so as to make full use of after-heat for the next operation. (7) When the running modes of the indoor and outdoor units conflict, it will be indicated on the display of the wired controller in five seconds and then the indoor unit will stop. In this case, they can back to the normal condition by harmonizing their running modes: the cooling mode is compatible with the dehumidifying mode and the fan mode can go with any other mode. If the supply power fails when the unit is running, then the indoor unit will send the “start” signal to the outdoor unit three minutes later after power recovery. (8) Cautions for the Debugging and Maintenance Personnel: During debugging and maintenance, prior to the startup of the compressor make sure the heating belt of the compressor has been energized for at least eight hours! Once the compressor is star ted, it must be guaranteed that it works continuously for at least 30 minutes, otherwise it would be damaged! User Notice This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons. DISPOSAL: Do not dispose this product as unsorted municipal waste. Collection of such waste separately for special treatment is necessary. Contents 1 Safety Precautions.................................................................................................... 1 2 Product Introduction................................................................................................. 3 2.1 Name of Main Parts............................................................................................................................. 3 2.2 Combinations for outdoor and indoor units .......................................................................................... 4 2.3 Rated working condition ...................................................................................................................... 5 2.4 The range of production working temperature...................................................................................... 5 3 Preparation before Installation .................................................................................. 6 3.1 Standard parts .................................................................................................................................... 6 3.2 Selecting installation site ..................................................................................................................... 6 3.3 Piping Connection ............................................................................................................................... 7 4 Installation Instruction.............................................................................................. 8 4.1 Outline and dimension of the outdoor unit ........................................................................................... 8 4.2 Installation of the Connection Pipe ....................................................................................................... 9 4.3 Air Purging and Refrigerant Charge..................................................................................................... 11 4.4 Electric Wiring................................................................................................................................... 12 5 Troubleshooting ..................................................................................................... 14 6 The conditions listed below are not classified into errors.......................................... 15 7 Troubleshooting ..................................................................................................... 17 8 Maintenance .......................................................................................................... 18 8.1 Outdoor heat exchanger.................................................................................................................... 18 8.2 Drain Pipe ......................................................................................................................................... 18 8.3 Notice before Seasonal Use ............................................................................................................... 18 8.4 Maintenance after Seasonal Use ........................................................................................................ 18 8.5 Parts Replacement ............................................................................................................................ 18 9 After-sales Service ................................................................................................. 19 Flex series 1 Safety Precautions This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user. This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property. NOTICE is used to address practices not related to personal injury. 1) Instructions for installation and use of this product are provided by the manufacturer and accompany each unit. The instruction of installation, maintenance and operating and safety instructions shall be included. 2) Installation must be performed in accordance with the requirements of NEC and CEC by authorized personnel only. 3) Before installation, please check if the power supply is in accordance with the requirements specified on the nameplate. And also take care of the power safety. 4) Make sure the unit can be earthed properly and soundly after plugging into the socket so as to avoid electric shock. Please do not connect the ground wire to gas pipe, water pipe, lightning rod or telephone line. 5) Be sure to use the exclusive accessory and part to prevent the water leakage, electric shock and fire accidents. 6) If refrigerant leakage happens during installation, please ventilate immediately. Poisonous gas will emerge if the refrigerant gas meets fire. 7) Wire size of power cord should be large enough. The damaged power cord and connection wire should be replaced by exclusive cable. 8) After connecting the power cord, please fix the electric box cover properly in order to avoid accident. 9) Never fail to comply with the nitrogen charge requirements. Charge nitrogen when welding pipes. 10) Never short-circuit or cancel the pressure switch to prevent unit damage. 11) Please firstly connect the wired controller before energization, otherwise wired controller can not be used. 12) Before using the unit, please check if the piping and wiring are correct to avoid water leakage, refrigerant leakage, electric shock, or fire etc. 13) Do not insert fingers or objects into air outlet/inlet grille. 14) Open the door and window and keep good ventilation in the room to avoid oxygen deficit when the gas/oil supplied heating equipment is used. 15) Never start up or shut off the air conditioner by means of directly plug or unplug the power cord. 16) Turn off the unit after it runs at least five minutes; otherwise it will influence oil return of the compressor. 17) Do not allow children operate this unit. 18) Do not operate this unit with wet hands. 19) Turn off the unit or cut off the power supply before cleaning the unit, otherwise electric shock or injury may happen. 20) Never spray or flush water towards unit, otherwise malfunction or electric shock may happen. 21) Do not expose the unit to the moist or corrosive circumstances. 22) Electrify the unit 8 hours before operation. Please switch on for 8 hours before operation. Do not cut off the power when 24 hours short-time halting (to protect the compressor). 23) Volatile liquid, such as diluent or gas will damage the unit appearance. Only use soft cloth with a little neutral detergent to clean the outer casing of unit. 24) Under cooling mode, please don't set the room temperature too low and keep the temperature difference between indoor and outdoor unit within 41℉ 25) If anything abnormal happens (such as burning smell), please power off the unit and cut off the main power supply, and then immediately contact Impecca appointed service center. If abnormality keeps going, the unit might be damaged and lead to electric shock or fire. 26) User is not allowed to repair the unit. Fault service may cause electric shock or fire accidents. Please contact Impecca appointed service center for help. 1 Flex Series Impecca is not responsible of personal injury or equipment damage caused by improper insta llation and commission, unnecessary service and incapable of following the rules and instructions listed in this manual. Flex Series 2 Product Introduction Impecca Flex Series adopts inverter compressor technology. According to change displacement of compressor, stepless capacity regulation within range of 15%~120% can be realized. Various product lineup is provided with capacity range from 30KBtu to 42KBtu, which can be widely used in boarding house and working area and especially applicable to the place with variable load change. Impecca commercial air conditioner is absolutely your best choice. 2.1 Name of Main Parts ① ② ③ ⑤ ④ NO. Name ① Motor ② Fan ③ Electric Box ④ Gas valve assembly Fig1 2 ⑤ Liquid valve assembly Flex Series 2.2 Combinations for outdoor and indoor units Wall Mounted Indoor Unit Wall Mounted Indoor Unit Cassettle Type Indoor Unit Floor/ Ceiling Indoor Unit Fig 2 See Fig.2 for Combinations for Outdoor and Indoor Units. For the Flex Series air conditioning syst em, one outdoor unit is able to drive up to five indoor units which can be cassette type, duct type, wall-mounted or floor ceiling type. The outdoor unit will run as long as any one indoor unit receives the running command, and all indoor units stop once the outdoor unit is turned off. Table 1 Energy Level and Capacity Code of the Indoor Capacity Code Indoor unit Model Outdoor unit 09 ISMI-W092 12 ISMI-W122 Wall Unit 18 ISMI-W182 24 ISMI-W242 ISMO-4221 18 ISMI-FC18 Floor/Ceiling Type ISMI-FC24 24 ISMI-C15 15 Cassettle type 24 ISMI-C24 2.3 Rated working condition Table 2 Rating cooling Rating Heating Indoor side state Dry buib temp.℉ Wet buib temp.℉ 80.06 66.92 69.98 60.08 NOTICE Outdoor side state Dry buib temp.℉ Wet buib temp.℉ 95 75.02 43.00 47 1) The following listed cooling /heating capacity and noise is tested before outgoing. 2) The parameters below are tested under rated working condition. If there is any change to them, please refer to the nameplate. 3) The parameters of heating capacity of indoor unit for heat pump excluded that of auxiliary electric heating power. 4) The performance parameters below are tested according to standard ANSI/AHRI 1230-2010. 3 Flex Series 2.4 The range of production working temperature Table 3 Cooling Working range Heating Working range Outdoor temperature 0~118℉ Outdoor temperature -4~86℉ 3 Preparation before Installation 3.1 Standard parts (Please use only Impecca supplied parts) Number Table 4 Parts of Outdoor Unit picture name 1 Owner's manual 2 Tube connector subassy Quantity Remark 1 8 3.2 Selecting installation site 1) Install the unit at a place where is adequate to withstand the weight of the unit and make sure the unit would not shake or fall off. 2) Never expose the unit under direct sunshine and rainfall. Install the unit at a place where is against dust, typhoon and earthquake. 3) Try to keep the unit away from combustible, inflammable and corrosive gas or exhaust gas. 4) Leave some space for heat exchanging and servicing so as to guarantee unit normal operation. 5) Keep the indoor and outdoor units close to each other as much units close to each other as much the pipe length and bends. 6) Never allow children to approach to the unit and take measures to prevent children touching the unit. When the outdoor unit is totally surrounded by walls, the installation space of the unit should be as required in Fig.3. 19 2/3 19 2/3 19 2/3 39 3/8 78 3/4 19 2/3 78 3/4 unit:inch Fig 3 4 Flex Series 3.3 Piping Connection The maximum pipe length is shown in the following table. When the distance between units (piping length) is out of the range listed below, normal run of the unit can not be guaranteed. Table 5 Connecting Pipe (inch) Max. Height Difference between Indoor Max. Pipe length(ft) Model Unit and Outdoor Unit (ft) Liquid Gas When the outdoor unit is above, maximum height difference between ISMO-4221 Ф1/4 Ф3/8 246.1 indoor and outdoor units is up to 49.2ft; When the indoor unit is above, maximum height difference between indoor and outdoor units is up to 49.2ft; NOTICE 1) Use water-proof insulating pipe. 2) Wall thickness of pipe: 0.019-0.039 inch; bearing pressure: 3.0MPa 3) The longer the connection pipe is, the more cooling and heating capacity will decrease. 4 Installation Instruction 4.1 Outline and dimension of the outdoor unit Unit:inch Fig 4 Outline dimension and Mounting holes 14 1/4 42 1/2 17 1/3 43 3/7 40 15 3/4 24 5/6 Unit:inch 5 Flex Series 4.2 Installation of the Connection Pipe Connecting piping for indoor unit and outdoor unit are in manifold mode. (As shown below). Fig. 5 4.2.1 Piping between the Indoor and Outdoor Units (1) If the liquid and gas stop valves which have the sign of A , B, C, D or E have not been connected to the indoor units, please turn off the screw cap with the spanner airproof. (2) Refer to Fig.6 for the moments of torque for tightening screws. (3) Let the flare end of the copper pipe point at the screw and then tighten the screw by hand. (4) After that, tighten the screw by the torque wrench unit it clatters (as shown in Fig.6). (5) The bending degree of the pipe can not be too small; otherwise it will crack. And please use a pipe tube bender to bend the pipe. (6) Wrap the exposed refrigerant pipe and the joints by sponge and then tighten them with the plastic tape. P ip e F la re N u t Pipe diameter Φ1/4 inch Φ3/8 inch Φ1/2 inch Φ5/8 inch Thickness of copper tube ≥0.0315 inch ≥0.0315 inch ≥0.0315 inch ≥0.0394 inch Tightening torque 11~22 ft·lbf 26~29 ft·lbf 33~37 ft·lbf 44~48 ft·lbf Spanner Fig6 1) During the connection of the indoor unit and the refrigerant pipe, never pull any joints of the indoor unit by force; otherwise the capillary pipe or other pipe may crack, which then would result in leakage. 2) The refrigerant pipe should be supported by brackets, that is, don’t let the unit withstand the weight of it. 3) If the piping connection size of outdoor unit does not match the piping connection size of indoor unit, use the piping connection dimension of indoor unit. And use different-diameter joints which is installing on the place of the piping connection to connect the indoor unit. 4) For the Flex Series, each pipe should be labeled to tell which system it belongs to avoid mistaken inaccurate piping. 4.2.2 Allowable pipe length and drop height among indoor and outdoor units If the total refrigerant pipe length (liquid pipe) is smaller than that listed in the table below, no additional refrigerant will be charged. Table 6 131.2 ft Total Liquid Pipe Lenght (a+b+c+d+e) 6 Flex Series Allowable Length and Height Fall of the Refrigerant Pipe Table 7 Allowable Value Fitting Pipe Total length (actual length) of fitting pipe 246.1ft Length of farthest fitting pipe (ft) 82ft LX(X=1,2,3,4,5) 49.2ft H1 49.2ft H3 24.6ft H2 Outdoor unit at upper Outdoor unit at lower Height difference between indoor units (m) Outdoor unit Indoor unit Equivalent length of the farthest fitting pipe Lx L1 L2 a b Height difference between indoor units H2 Height difference between indoor unit and outdoor unit H1 Height difference between outdoor unit and indoor unit L1 +L2 +…+L M(M ≤5) Indoor unit L3 L4 L5 c d e Fig 7 4.2.3 Installation of the Protection Layer of the Refrigerant Pipe (1)The refrigerant pipe should be insulated by the insulating material and plastic tape in order to prevent condensation and water leakage. (2)The joints of the indoor unit should be wrapped with the insulating material and no gap is allowed on the joint of the indoor unit, as shown in Fig.8. Thermal insulating layer is required to be wrapped at this part. Thermal insulating pipe No gap Fig 8 7 Flex Series After the pipe is protected well enough, never bend it to form a small angle; otherwise it would crack or break. (3)Wrap the Pipe with Tape: a. Bundle the refrigerant pipe and electric wire together with tape, and separate them from the drain pipe to prevent the condensate water overflowing. b. Wrap the pipe from the bottom of the outdoor unit to the top of the pipe where it enters the wall. During the wrapping, the later circle should cover half of the former one. c. Fix the wrapped pipe on the wall with clamps. 1) Do not wrap the pipe too tightly; otherwise the insulation effect would be weakened. Additionally, make sure the drain hose is separated from the pipe. 2) After that, fill the hole on the wall with sealing material to prevent wind and rain coming into the room. 4.2.4 Support and protection for pipeline Support should be made for hanging connection pipe. Distance between each support can not be over 1m. 4.3 Air Purging and Refrigerant Charge 4.3.1 Air purging (1) The refrigerant has been charged into the outdoor unit before shipment, while additional refrigerant still need be charged into the refrigerant pipe during the field installation. (2) Check if the liquid valve and the gas valve of the outdoor unit are closed fully. (3) As shown in the following figure (Fig.9), expel the gas ins ide the indoor unit and refrigerant pipe out by the vacuum pump. Manometer Manometer "HI"Knob "LO"Knob liquid valve Vacuuming pump Connection hose Gas valve Fig 9 (4) When the compressor is not running, charge the R410A refrigerant into the refrigerant pipe from the liquid valve of the outdoor unit (do not do it from the gas valve). 4.3.2 Additional refrigerant charging (1) Refrigerant Charge in the Outdoor Unit before Shipment NOTICE 1) Outdoor unit has been charged refrigerant before delivery. The refrigerant charge is not included those charged additionally in the indoor unit and the refrigerant pipe. 2) The amount of the additional refrigerant charge is dependent on the diameter and length of the liquid refrigerant pipe which is decided by the actual yield installation requirement. 3) Record the additional refrigerant charge for future maintenance. 8 Flex Series (2) Calculation of the Additional Refrigerant Charge Additional Refrigerant Charge= (ΣLength of Liquid Pipeφ0.375×54+ΣLength of Liquid Pipeφ0.25×22)-880 The biggest additional refrigerant charge value is 800g. It means that if the calculated value exceed 800g, the additional refrigerant charge takes 800g, while the calculated value less than 800g, the additional refrigerant charge takes the calculated value. 4.4 Electric Wiring 4.4.1 Wiring precautions (1) The installation must be done in accordance with the national wiring regulations. (2) Only the power cord with the rated voltage and exclusive circuit for the air conditioning can be used. (3) Do not pull the power cord by force. (4) The electric installation should be carried out by the technician as instructed by the local laws, regulations and also this manual. (5) The diameter of the power cord should be large enough and once it is damaged it must be replaced by the dedicated one. (6) The earthing should be reliable and the earth wire should be connected to the dedicated device of the building by the technician. Bes ides, the air switch coupled with the leakage current protection switch must be equipped, which is of enough capacity and of both magnetic and thermal tripping functions in case of the short circuit and overload. Table 8 Power Supply Capacity of the air Switch(A) Recommended Cord(pieces× sectional area) 208/230V~60Hz 32 3×0.0062 sq in OUTDOOR UNIT XT L1 L2 N(1) 2 3 PE L1 L2 POWER N(1) 2 N(1) 2 3 N(1) 2 3 INDOOR UNIT A N(1) 2 3 N(1) 2 INDOOR UNIT B N(1) 2 3 PE PE XT5 XT4 XT3 XT2 XT1 3 INDOOR UNIT C N(1) 2 3 PE PE 3 N(1) 2 3 INDOOR UNIT D N(1) 2 PE 3 INDOOR UNIT E Fig 11 4.4.2 Earthing Requirements (1) The air conditioner is classified into the Class I appliances, so its earthing must be reliable. (2) The yellow-green line of the air conditioner is the earth line and can not be used for other purpose, cut off or fixed by the tapping screw; otherwise it would cause the hazard of electric shock. (3) The reliable earth terminal should be provided and the earth wire can not be connected to any of the following places. ①Running water pipe;; ②Coal gas pipe; ③Sewage pipe; ④Other places where the professional personnel think unreliable. 9 Flex Series 4.4.3 Electrical Cable Connection 1) The mistake connecting line will result in malfunction. After the electrical wiring working, ensure the wire between the connection place and the fixed place has a certain freedom degree. 2) The connection piping and connection line of each indoor unit should connect well according to the instruction. 3) The electric installation should be carried out by the technician as instructed by the local laws, regulations and also this manual. 4) The installation location should be dry, and can't be expose in direct sunlight or strong breeze. 5) Have to install a breaker in the circuit that can shut off the main power supply of the system. Besides, the air switch coupled with the leakage current protection switch must be equipped. 4.4.4 Wiring of the Power Cord (1). Open the side plate. (2). Connect the power cord to the terminals “L1”, “L2” and also the earthing screw, and then connect the wiring terminals “N(1),2,3” of the indoor unit to those of the outdoor unit correspondingly. Please use the green bonding screw to connect the earthing cord. The location is showing in the figure 12. (3). Fix the power cord with wire clips. (4). Let the power cord go through the rubber ring. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similarly qualified person in order to avoid a hazard. Tighten the green bonding screw here Figure 12 10 Flex Series 5 Troubleshooting 1) In the event of abnormal conditions (like, stinky smell), please shut off the main power supply immediately and then contact the Impecca appointed service center; otherwise the continuous abnormal running would damage the air conditioning unit and also would cause electric shock or fire hazard etc. 2) Do not repair the air conditioning personally but instead contact the professionally skilled personnel at the Impecca appointed service center, as the incorrect repair would cause electric shock or fire hazard etc. Check before Contacting Service Center. Check Items Has the unit been fixed firmly? Have you done the gas leakage test? Is the unit get proper thermal insulation? Does the unit drain well? Is the voltage in accordance with the rated voltage specified on the nameplate? Is the electric wiring and piping connection installed correctly and securely? Has the unit been earthed securely? Is the power cord specified? Has the inlet and outlet been blocked? NOTICE! Table 9 Conditions Might Happen The unit may drop, shake or emit noise. It may cause insufficient cooling/heating capacity. It may cause condensation and dripping. It may cause condensation and dripping. It may cause malfunction or damage the part. Check It may cause malfunction or damage the part. It may cause electrical leakage. It may cause malfunction or damage the part. It may cause insufficient cooling/heating capacity. If the air conditioner still runs abnormally after the above check and handling, please contact the maintenance serviceman at the local appointed service center and also give a description of the error occurred as well as the model of the unit. 11 Flex Series 6 The conditions listed below are not classified into errors. The unit does not run The unit blows out mist The unit generates noise The unit blows out dust. The unit emits odors. Table 10 Conditions When restart the unit soon after it is stopped. Causes The overload protection switch of the unit let the startup delayed for three minutes. The unit will stand by for approximate one As soon as power is on. minute. When the cooling operation starts. The hi-humidity air indoor is cooled quickly. The unit “clatters” as soon as it It is the sound generated during the initialization of the electronic expansion valve. starts running. The unit “swishes ” during the It is the sound when the refrigerant gas runs inside the unit. cooling operation. The unit “swishes ” when it is It is the sound when the refrigerant gas stops running. started or stopped. The unit “swishes” when it is in It is the sound when the draining system is operating. and after the running. It is the sound of frication generated by the skin The unit “squeaks” when it is in plate etc which swells due to the temperature and after the running. change. When the unit restarts after it is not The dust inside the unit is blown out again. used for a long time. When the unit is running. The odors absorbed in are blown out again. NOTICE! If problem can not be solved after checking the above items, please contact Impecca service center and show phenomena and models. Following circumstance are not malfunction Table 11 Malfunction Reason Unit doesn’t run When unit is started Overload protection switch makes it run after 3 minutes immediately after it is just delay turned off When power is turned on Standby operating for about 1 minute Mist comes from the Under cooling Indoor high humidity air is cooled rapidly unit Noise is emitted Slight cracking sound is heard It is noise when electronic expansion valve initialization when just turned on That's sound for gas refrigerant flowing in unit The unit blows out duct The unit emits odor There is consecutive sound when cooling There is sound when unit starts or stops There is slight and consecutive sound when unit is running or after running Cracking sound is heard when unit is operating and after operating When unit runs after no operation for a long period Operating Indoor unit still runs after switch off After every indoor unit receive "stop" signal, fan will keep Indoor fan motor will keep running 20-70s so as to take good use of excess cooling and heating and prepare for That's sound for gas refrigerant stops to flow That's sound for operation of drainage system That’s sound caused by expansion of panel and other parts due to temperature change Dust in indoor unit is blew out The room odor absorbed by the unit is blew out again 12 Flex Series Mode conflict running next operation COOL or HEAT mode can not be operated When the indoor operating mode conflicts with that of outdoor unit, indoor fault indicator will flash and conflict will be shown on the wired controller after 5 minutes. Indoor unit stops to run and meanwhile change outdoor operating mode as the same as that of indoor unit, then the unit will go back to normal. COOL mode doesn't conflict with DRY mode. FAN mode doesn't conflict with any mode. 13 Flex Series 7 Troubleshooting The error code will be displayed on the wired controller and the main board of the outdoor unit The meaning of each error, as shown in table 13. Table 12 The indicator display Name of malfunction Yellow light Red light Green light Compressor runs Flash once Defrost Flash twice Anti-freezing protection Flash 3 times IPM protection Flash 4 times AC over-current protection Flash 5 times Over-burden protection Flash 6 times Compressor exhaust high temperature protection Flash 7 times Compressor overload protection Flash 8 times Power protection Flash 9 times EEPROM reads and write protection Flash 11 times Low PN voltage protection Flash 12 times Over voltage protection for PN Flash 13 times PFC protection Flash 14 times PFC module temperature protection Flash 15 times Low pressure protection Flash 17 times High pressure protection Flash 18 times Limit/decline frequency(electric current) Flash 1 times Frequency limit(exhaust) Flash 2 times Frequency limit(Over-burden) Flash 3 times Outdoor ambient sensor malfunction Flash 6 times Outdoor tube sensor malfunction Flash 5 times Exhaust sensor malfunction Flash 7 times Attain the temperature of switch on Flash 8 times Frequency limit(power) Flash 13 times Outdoor fan malfunction Flash 14 times Frequency limit(PFC module temperature) Flash 15 times PFC module sensor malfunction Flash 16 times Liquid pipe temperature sensor malfunction of A Flash 17 times Gas pipe temperature sensor malfunction of A Flash 18 times Liquid pipe temperature sensor malfunction of B Flash 19 times Gas pipe temperature sensor malfunction of B Flash 20 times Liquid pipe temperature sensor malfunction of C Flash 21 times Gas pipe temperature sensor malfunction of C Flash 22 times Liquid pipe temperature sensor malfunction of D Flash 23 times Gas pipe temperature sensor malfunction of D Flash 24 times Liquid pipe temperature sensor malfunction of E Flash 25 times Gas pipe temperature sensor malfunction of E Flash 26 times Exit of the condenser tube sensor malfunction Flash 27 times Flash n times(n=indoor Correspondence is normal unit number) Often bright Communication failure between indoor unit and (indoor unit all outdoor unit Communication failure) 14 Flex Series 8 Maintenance Regular check, Maintenance and care should be performed by professional personnel, which will prolong the unit life span. 8.1 Outdoor heat exchanger Outdoor heat exchanger is required to be cleaned once every two months. Use vacuum cleaner with nylon brush to clean up dust and sundries on the surface of heat exchanger. Blow away dust by compressed air if it is available. Never use water to wash the heat exchanger. 8.2 Drain Pipe Regularly check if the drain pipe is clogged in order to drain condensate smoothly. 8.3 Notice before Seasonal Use (1) Check if the inlet/outlet of the indoor/outdoor unit is clogged. (2) Check if the ground wire is earthed reliably. (3) Check if battery of remote wireless controller has been replaced. (4) Check if the filter screen has been set soundly. (5) After long period of shutdown, open the main power switch 8 hours before re-operating the unit so as to preheat the compressor crankcase. (6) Check if the outdoor unit is installed firmly. If there is something abnormal, please contact the Impecca appointed service center. 8.4 Maintenance after Seasonal Use (1) Cut off main power supply of the unit. (2) Clean filter screen and indoor and outdoor units. (3) Clean the dust and sundries on the indoor and outdoor units. (4) In the event of rusting, use the anti-rust paint to stop spreading of rust. 8.5 Parts Replacement Purchase parts from Impecca appointed service center or dealer if necessary. NOTICE! During airtight and leakage test, never mix oxygen, ethyne and other dangerous gas into refrigeration circuit. In case of hazard, it's better to use nitrogen or refrigerant to accomplish such test. 15 9 CUSTOMER SUPPORT Before contacting customer support, please see the troubleshooting guide above. Visit our website to contact us, find answers to Frequently Asked Questions, and for other resources which may include an updated version of this user's guide. WWW.IMPECCA.COM If you wish to contact us by phone, please be sure to have your model number and serial number ready and call us between 9:00am and 6:00pm ET, at +1 866-954-4440. Keep tabs on Impecca's newest innovations & enter contests via our social network feeds: www.facebook.com/Impecca/ www.instagram.com/impecca/ Wired Controller IS-TT850 User's Manual Thank you for choosing Impecca Air Conditioners. Please read this owner’s manual carefully before operation and retain it for future reference. User Notice Please carefully read this manual before installation and use of this product ƹ (QVXUHthere is separate SRZHUVXSSO\IRUHDFKLQGRRUXQLW ƹ Never install wired controller in a wet place or under direct sunlight. ƹ Shielded twisted pair line must be substituted as signal line for wired controller if the unit is installed in the place where there is electromagnetic interference. ƹ ƹ ƹ Make sure communication line is connected into correct port to avoid communication malfunction. Never knock, throw or frequently disassemble the wired controller. Never operate the wired controller with wet hand. Contents 1 Display Section................................................................................................ 1 1.1 Controller's LCD ........................................................................................ 1 1.2 Instruction to LCD ....................................................................................... 2 2 Buttons ............................................................................................................ 3 2.1 Layout of Buttons ....................................................................................... 3 2.2 Functions of Buttons ................................................................................... 3 3 Operation Instructions ..................................................................................... 4 3.1 On/Off ......................................................................................................... 4 3.2 Mode Setting .............................................................................................. 4 3.3 Temperature Setting ................................................................................... 4 3.4 Fan Setting ................................................................................................. 5 3.5 Timer Setting .............................................................................................. 5 3.6 Swing Setting ............................................................................................. 7 3.7 Sleep Setting .............................................................................................. 8 3.8 Turbo Setting .............................................................................................. 9 3.9 E-heater Setting ....................................................................................... 10 3.10 Blow Setting ........................................................................................... 11 3.11 Other Functions ...................................................................................... 12 4 Installation and Dismantlement ..................................................................... 12 4.1 Connection of the Signal Line of the Wired Controller ............................. 12 4.2 Installation of the Wired Controller ........................................................... 12 4.3 Dismantlement of the Wired Controller .................................................... 14 5 Errors Display ................................................................................................ 14 Wired Controller IS-TT850 1 Display Section Fig1.1.1 Diagram of wired controller 1.1 LCD Display of Wired Controller Fig.1.1.2 LCD display 1 Wired Controller IS-TT850 1.2 Instruction to LCD Display Table 1.1 No. Symbols Description 1 Swing function 2 Air exchange function (this function is yet unavailable for this unit). 3 Sleep function (Only sleep 1). 4 Each kind of running mode of indoor unit (auto mode) 5 Cooling mode 6 Dry mode 7 Fan mode 8 Heating mode 9 Defrosting function for the outdoor unit. 10 Gate-control function (this function is yet unavailable for this unit). 11 Lock function. 12 SHIELD 13 Turbo 14 MEMORY 15 16 Turbo function state Memory function (The indoor unit resumes the original setting state after power failure and then power recovery). It blinks under on state of the unit without operation of any button. SAVE 17 Energy-saving function (this function is yet unavailable for this unit). Ambient/setting temperature value 18 E-HEATER 19 BLOW 20 21 Shield functions (Button operation, temperature setting, On/Off operation, Mode setting are disabled by the remote monitoring system.) Electric auxiliary heating function. Blow function. Timing value. QUIET Quiet function (two types: quiet and auto quiet) (this function is yet unavailable for this unit). 2 Wired Controller IS-TT850 2 Buttons 2.1 Layout of Buttons 2.2 Functions of Buttons Table 2.1 No. Name 1 Enter/Cancel 2 Ÿ 6 ź 3 Fan 4 Mode 5 Function 7 Timer Timer setting. 8 On/Off Turn on/off the indoor unit. 4+2 Mode + Ÿ 3+6 )DQź 4+6 2+6 Mode ź Ÿź Function Function selection and cancellation. ķ Running temperature setting of the indoor unit, range:61°F-86° F(16°C-30°C). ĸ Timer setting, range:0.5(30 minutes) - 24 (hours). Setting of the low/middle/high/auto fan speed. Setting of the Cooling/Heating/Fan/Dry/Auto mode of the indoor unit. Switchover among the functions of Turbo/Save/E-heater/Blow etc.. With the A/C powered off, press these two buttons together for 5 seconds to toggle the Memory function. With Memory on, the unit will return the the previous setting after resuming from a power failure. With Memory toggled off, it will stay off With the A/C powered off, press these two buttons together for 5 seconds to determine if your unit is capable of just cooling or both cooling and heating, indicated by the symbols shown. With the A/C powered off, press these two buttons together for 5 seconds to toggle between Fahrenheit and Celsius. Press these two buttons together for 5 seconds to toggle the lock function. 3 Wired Controller IS-TT850 3 Operation Instructions 3.1 On/Off Press On/Off button to toggle your A/C's power. Note: The state shown in Fig.3.1.1 indicates the “Off” state of the unit after power has been restored to the unit. The screen shown in Fig.3.1.2 indicates the “On” state of the unit after power on. Fig.3.1.1 “Off” State Fig.3.1.2 “On” State 3.2 Mode Setting Under ON state of the unit, press the Mode to switch the operation modes as the following sequence: Auto–Cooling–Dry–Fan–Heating. 3.3 Temperature Setting 3UHVV ŸRU ź WR LQFUHDVHGHFUHDVH WKH SUHVHW WHPSHUDWXUH ,I SUHVVLQJ HLWKHU RI WKHP continuously, the temperature will be increased or decreased by 1° every half a second,as shown in Fig.3.3.1. In the Cooling, Dry, Fan or Heating mode, the temperature setting range is 61°F-86° F(16°C-30°C). In the Auto mode, the setting temperature not manually adjustable. Fig.3.3.1 Fig.3.4.1 4 Wired Controller IS-TT850 3.4 Fan Setting While the unit is powered on, press Fan and then fan speed of the indoor unit will change circularly as shown in Fig.3.4.1. Low Middle High (Fig. 3.4.1) 3.5 Timer Settings While the unit is powered on, pressing the Timer button allows you to set the delay until the unit turns off. While the unit is powered off, pressing the Timer button allows you to set the dealy until the unit turns on. • 7LPHURQVHWWLQJ details With the unit turned off, and no timer already programmed, press the Timer button. The display will show "0.5" with "Hour on" blinking. PressŸorźbutton to adjust delay until unit turns on and press Timer or Enter/Cancel to confirm. • Timer off setting details: With the unit turned on, and no timer already programmed, press the Timer button. The display will show "0.5" with "Hour off" blinking. • Timer off setting details: With the unit turned on, and no timer already programmed, press the Timer button. The display will show "0.5" with "Hour off" blinkingSUHVVŸRUźEXWWRQWRDGMXVWdelay until unit turns on and press Timer or Enter/Cancel to confirm. &DQFHOWLPHU After setting of timer, if Timer button is pressed, LCD won’t display xx. Hour so that timer setting is Timer off setting under the “On” state of the unit is shown as Fig.3.5.1. canceled. Fig.3.5.1 Timer off Setting under the “On” State of the Unit 5 Wired Controller IS-TT850 Timer on setting under the “Off” state of the unit is shown as Fig.3.5.2. Fig.3.5.2 Timer on Setting under the “Off” State of the Unit 7LPHUUDQJHKU(YHU\SUHVVRIŸRUźZLOOPDNHWKHVHWWLPHLQFUHDVHGRUGHFUHDVHGE\ 0.5hr. If either of them is pressed continuously, the set time will increase/ decrease by 0.5hr every 0.5s. 6 Wired Controller IS-TT850 3.6 Swing Setting Swing On: Press Function under on state of the unit to activate the swing function. In this case, ZLOOEOLQN$IWHUWKDWSUHVV(QWHU&DQFHOWRPDNHDFRQ¿UPDWLRQ Swing Off: When the Swing function is on, press Function to enter the Swing setting interface,with blinking. After that, press Enter/Cancel to cancel this function. Swing setting is shown as Fig.3.6.1. Fig.3.6.1 Swing Setting Notes: ķ Sleep, Turbo or Blow setting is the same as the Swing setting. ĸ After the setting has been done, it has to press the key “Enter/Cancel” to back to the setting VWDWXVRUTXLWDXWRPDWLFDOO\¿YHVHFRQGVODWHU 7 Wired Controller IS-TT850 3.7 Sleep Setting Sleep on: Press Function under the On state of the unit till the unit enters the Sleep setting VWDWH$IWHUWKDWSUHVV(QWHU&DQFHOWRFRQ¿UPWKLVVHWWLQJ Sleep off: When the Sleep function is activated, press Function to enter the Sleep setting status. After that, press Enter/Cancel to cancel this function. In the Cooling or Dry mode, the temperature will increase by 1°C after the unit runs under Sleep1 for 1hr and 1°C after another 1hr.After that, the unit will run at this temperature. In the Heating mode, the temperature will decrease by 1°C after the unit runs under Sleep 1 for 1hr and 1°C after another 1hr. After that, the unit will run at this temperature. Sleep setting is shown as Fig.3.7.1. Fig.3.7.1. Sleep Setting 8 Wired Controller IS-TT850 3.8 Turbo Setting Turbo function: The unit at the high fan speed can realize quick cooling or heating so that the room temperature can quickly approach the setting value. In the Cooling or Heating mode, press Function till the unit enters the Turbo setting status and WKHQSUHVV(QWHU&DQFHOWRFRQ¿UPWKHVHWWLQJ When the Turbo function is activated, press Function to enter the Turbo setting status and then press Enter/Cancel to cancel this function. Turbo function setting is as shown in Fig.3.8.1. Fig.3.8.1 Turbo Setting 9 Wired Controller IS-TT850 3.9 E-heater Setting E-heater (auxiliary electric heating function): In the Heating mode, E-heater is allowed to be WXUQHGRQIRULPSURYHPHQWRIHI¿FLHQF\ Once the wired controller or the remote controller enters the Heating mode, this function will be turned on automatically. Press Function in the Heating mode to enter the E-heater setting interface and then press Enter/Cancel to cancel this function. Press Function to enter the E-heater setting status, if the E-heater function is not activated, and then press Enter/Cancel to activate it. The setting of this function is shown as Fig.3.9.1 below: Fig.3.9.1 E-heater Setting 10 Wired Controller IS-TT850 3.10 Blow Setting Blow function: After the unit is turned off, the water in evaporator of indoor unit will be automatically evaporated to avoid mildew. In the Cooling or Dry mode, press Function till the unit enters the Blow setting status and then press Enter/Cancel to active this function. When the Blow function is activated, press Function to the Blow setting status and then press Enter/Cancel to cancel this function. Blow function setting is as shown in Fig.3.10.1 Fig.3.10.1 Blow Setting Notes: ķ When the Blow function is activated, if turning off the unit by pressing On/Off or by the remote controller, the indoor fan will run at the low fan speed for 2 min, with “BLOW” displayed on the LCD. While, if the Blow function is deactivated, the indoor fan will be turned off directly. ĸ Blow function is unavailable in the Fan or Heating mode. 11 Wired Controller IS-TT850 3.11 Other Functions a. Lock 8SRQVWDUWXSRIWKHXQLWZLWKRXWPDOIXQFWLRQRUXQGHUWKH³2II´VWDWHRIWKHXQLWSUHVVŸDQGźat the same time for 5s till the wired controller enters the Lock function. In this case, LCD displays . After that, repress these two buttons at the same time for 5s to quit this function. Under the Lock state, any other button press won’t get any response. b. Memory 0HPRU\VZLWFKRYHU8QGHUWKH³2II´VWDWHRIWKHXQLWSUHVV0RGHDQGŸDWWKHVDPHWLPHIRU 5s to switch memory states between memory on and memory off. When this function is activated, Memory will be displayed. If this function is not set, the unit will be under the “Off” state after power failure and then power recovery. Memory recovery: If this function has been set for the wired controller, the wired controller after power failure will resume its original running state upon power recovery. Memory contents: On/ Off,Mode, set temperature, set fan speed and Lock function. 4 Installation and Dismantlement 4.1 Connection of the Signal Line of the Wired Controller Ɣ2SHQWKHFRYHURIWKHHOHFWULFFRQWUROER[RIWKHLQGRRUXQLW Ɣ/HWWKHVLQJOHOLQHRIWKHZLUHGFRQWUROOHUWKURXJKWKHUXEEHUULQJ Ɣ&RQQHFWWKHVLJQDOOLQHRIWKHZLUHGFRQWUROWRWKHSLQVRFNHWRIWKHLQGRRUXQLW3&% Ɣ7LJKWHQWKHVLJQDOZLUHZLWKWLHV Ɣ7KHFRPPXQLFDWLRQGLVWDQFHEHWZHHQWKHPDLQERDUGDQGWKHZLUHGFRQWUROOHUFDQEHXSWR 20 meters ( the standard distance is 8 meters) 4.2 Installation of the Wired Controller PVC Pipe 1 2 3 4 5 Fig.4.1 Accessories for the Installation of the Wired Controller Table 4.1 No. 1 2 3 4 5 Name Socket box embedded in the wall* Back-plate of the Wired Controller Screw M4X25* Front Panel of the Wired Controller Screw ST 2.9X6* *Not included 12 Wired Controller IS-TT850 3 2 1 6 7 8 9 4 5 10 Fig.4.2 Fig.4.2 shows the installation steps of the wired controller, but there are some issues that need your attention. 1) Prior to the installation, please firstly cut off the power supply of the wire buried in the installation hole, that is, no operation is allowed with electricity during the whole installation. 2) Pull out the four-core twisted pair line from the installation holes and then let it go through the rectangular hole behind the back-plate of the wired controller. 6WLFNWKHVROHSODWHRIWKHZLUHGFRQWUROOHUWRWKHZDOORYHUWKHLQVWDOODWLRQKROHDQGWKHQ¿[LW with screws M4X25. 4) Insert the four-core twisted pair line into the slot of the wired controller and then buckle the front panel and the back-plate of the wired controller together. )LQDOO\¿[WKHIURQWSDQHODQGWKHVROHSODWHRIWKHZLUHGFRQWUROOHUWLJKWO\E\VFUHZV67; CAUTION! Please pay special attention to the followings during the connection to avoid the malfunction of the air conditioning unit due to electromagnetic interference. ķ Separate the signal and communication lines of the wired controller from the power cord 13 Wired Controller IS-TT850 and connection lines between the indoor and outdoor unit, with a minimum interval of 20cm, otherwise the communication of the unit will probably work abnormally. ĸ I f the air conditioning unit is installed where is vulnerable to electromagnetic interference,then the signal and communication lines of the wired controller must be the shielding twisted pair lines. 4.3 Dismantlement of the Wired Controller 1 2 3 4 5 Errors Display If there is an error occurring during the operation of the system, the error code will be displayed on the LCD, as show in Fig.5.1. If multi errors occur at the same time, their codes will be displayed circularly. Note: In event of any error, please turn off the unit and contact the professionally skilled personnel. Fig.5.1 14 Wired Controller IS-TT850 Table 5.1 Meaning of Each Error Error Return air temperature sensor open/ short circuited evaporator temperature sensor open/ short circuited Indoor unit liquid valve temperature sensor open/short circuited Indoor gas valve temperature sensor open/ short circuited IPM temperature sensor open/short circuited Outdoor ambient temperature sensor open/ short circuited Outdoor unit condenser mid-tube temperature sensor open/short circuited Discharge temperature sensor open/ short circuited Error Code Error Error Code F1 Drive board communication error P6 F2 Compressor overheating protection H3 b5 Indoor and outdoor units unmatched LP b7 Communication line misconnected or expansion valve error dn P7 5XQQLQJPRGHFRQÀLFW E7 F3 Pump-down Fo F4 Jumper error C5 F5 Forced defrosting H1 Indoor and outdoor communication error E6 Compressor startup failure Lc DC bus under-voltage protection PL High discharge temperature protection E4 DC bus over-voltage protection PH Overload protection E8 Compressor phase current sensing circuit error U1 Whole unit over-current protection E5 Compressor demagnetization protection HE Over phase current protection P5 PFC protection Hc Compressor desynchronizing H7 IPM Temperature Protection P8 IPM Current protection H5 Compressor phase loss/reversal protection Frequency restricted/reduced with whole unit current protection Frequency restricted/reduced with IPM current protection Frequency restricted/reduced with high discharge temperature Frequency restricted/reduced with antifreezing protection Frequency restricted/reduced with overload protection Frequency restricted/reduced with IPM temperature protection Over-power protection L9 System charge shortage or blockage protection F0 Capacitor charging error PU High pressure protection E1 Low pressure protection E3 Compressor stalling LE Over-speeding LF Drive board temperature sensor error PF Indoor unit full water error E9 AC contactor protection P9 Anti-freezing protection E2 Temperature drift protection PE AC input voltage abnormal PP Sensor connection protection Pd Whole unit current sensing circuit error U5 DC bus voltage drop error U3 4-way valve reversing error U7 Outdoor fan 1 error protection L3 Motor stalling H6 Outdoor fan 2 error protection LA PG motor zero-crossing protection U8 15 Ld F8 En F9 FH F6 EU Technical Support Before calling technical support, please see the troubleshooting guide above. You may also visit our website at www.impecca.com for answers to Frequently Asked Questions and to contact us. Email: [email protected] Phone: +1 866–954–4440 Web: www.impecca.com
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project