LG | LUU188HV | LUU188HV Submittal | LG LUU188HV LUU188HV Submittal

Job Name/Location:
Tag #:
Date:
For:
PO No.:
Architect:
GC:
Engr:
Mech:
File
Resubmit
Approval
Other
Rep:
(Company)
(Project Manager)
LV180HV4
Single Zone Vertical Air Handler Unit
Outdoor Unit (ODU) - LUU188HV Indoor Unit (IDU) - LVN180HV4
Operating Range:
Outdoor Unit:
Performance:
Cooling:
Cooling (Min‐Rated‐Max, Btu/h)
SEER/EER
SEER ‐ Seasonal Energy Efficiency Rating
8,000 ~ 18,000 ~ 24,000
19.0/13.33
EER ‐ Energy Efficiency Rating
Heating:
Heating (Min‐Rated‐Max, Btu/h)
HSPF
9,000 ~ 20,000 ~ 23,000
9.5
HSPF ‐ Heating Seasonal Performance Factor
Cooling Nominal Test Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
Electrical:
208-230 / 60 / 1
Outdoor Unit:
30
MOP (A)
20
MCA (A)
15.1
Cooling Rated Amps (A)
13.5
Compressor (A)
Fan Motor (A)
1.6
MOP ‐ Maximum Overcurrent Protection
MCA ‐ Minimum Circuit Ampacity
Cooling Power Input (Min-Rated-Max, kW)
Heating Power Input (Min-Rated-Max,kW)
0.65 ~ 1.35 ~ 2.70
0.65 ~ 1.60 ~ 2.10
Piping:
3/8
5/8
0.43
Liquid Line (in, OD)
Vapor Line (in, OD)
Additional Refrigerant (oz/ft)
Min/Max Pipe Length (ft)²
6.6/164
24.6
Pipe Length (no add'l Refrigerant, ft)
98.4
Max Elevation (ft)
Features:
•ESP control
•Hot start
•Optional Wi-Fi
•Auto restart
•Group control
•Timer (on/off)
Included Accessories:
Indoor Unit:
57-77
59-81
Cooling (°F WB)
Heating (°F DB)
Unit Data:
Refrigerant Type/Control
Heating Nominal Test Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
Power Supply (V¹/Hz/Ø)
Total Power Input:
5 - 118
-4 - 64
Cooling (°F DB)
Heating (°F WB)
•Sleep mode
•Built in dry contact
•Inverter (variable speed fan)
•Simple Controller with Mode (White) ‐ PQRCVCL0QW
Optional Accessories:
Wi-Fi Module ‐ PCRCUDT3
LG MultiSITE™ CRC1 Controller ‐ PREMTBVC0
Wireless Remote Controller - PQWRHQ0FDB
Wall Mounted Temperature Sensor - PQRSTA0
Base Pan Heater for ODU - PQSH1200
Low Ambient Wind Baffle (cooling operation to -4°) ‐ ZLABGP04A¹⁰
Electric Heater 3kW - ANEH033B1¹¹
Downflow Conversion Kit - PNDFJ0
Refrigerant Charge (lbs)
ODU Sound Pressure Max (Cool/Heat) ±3 dB(A)³
IDU Sound Pressure (H/M/L) ±3 dB(A)³
R410A/EEV
4.85
48/52
42/42/41
ODU Net Weight (lbs)
ODU Shipping Weight (lbs)
IDU Net Weight (lbs)
IDU Shipping Weight (lbs)
129
141
129
140
Fan:
ODU/IDU Fan Type
Propeller/Sirocco
Fan Speeds (Fan/Cooling/Heating)
3/3/3
Fan Quantity (ODU + IDU)
1+1
Motor/Drive
Brushless Digitally Controlled / Direct
ODU Air Circulation (CFM)
2048
IDU Air Circulation H/M/L (CFM)
640 / 580 / 480
IDU External Static Pressure (ESP) (in-wg)
0.3
Minimum ESP/Fan Setting Value⁴
0.1/63
Maximum ESP/Fan Setting Value⁴
0.5/88
Dehumidification Rate (pts/hr)
2
Notes:
1. Acceptable operating voltage: 187V‐253V.
2. Piping lengths are equivalent.
3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. Fan setting value correlates to High speed air flow.
5. All power/communication cable to be minimum 18 American wire gage (AWG), 4‐
conductor, stranded, shielded or unshielded wire and must comply with applicable local and
national code. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
6. Power wiring cable size must comply with the applicable local and na onal code.
7. The indoor unit comes with a dry helium charge.
8. This data is rated 0 above sea level, with 25 of refrigerant line and a 0 level
difference between outdoor and indoor units.
9. Must follow installa on instruc ons in the applicable LG installa on manual.
10. If the optional low ambient wind baffle (ZLABGP04A) is used, one wind baffle is required
for each ODU fan.
11. Electric heater accessory available in 3kW, 5kW, 8kW, and 10kW capacities. Refer to the
engineering manual for details.
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
SB_SZ_VAHU_LV180HV4_2018_02_16_135624
Page 1 of 4
Job Name/Location:
LUU188HV
Single Zone Vertical Air Handler Unit
Tag #:
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
SB_SZ_VAHU_LV180HV4_2018_02_16_135624
Page 2 of 4
Job Name/Location:
LUU188HV
Single Zone Vertical Air Handler Unit
Tag #:
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
SB_SZ_VAHU_LV180HV4_2018_02_16_135624
Page 3 of 4
Job Name/Location:
LVN180HV4
Single Zone Vertical Air Handler Unit
Tag #:
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
SB_SZ_VAHU_LV180HV4_2018_02_16_135624
Page 4 of 4
Download PDF