LG | LS090HEV1 | LS090HEV1 Submittal | LG LS090HEV1 LS090HEV1 Submittal

LG LS090HEV1 LS090HEV1 Submittal
Job Name/Location:
Tag #:
Date:
For:
PO No.:
Architect:
GC:
Engr:
Mech:
File
Resubmit
Approval
Other
Rep:
(Company)
(Project Manager)
LS090HEV1
Mega 220V Single Zone Inverter
Outdoor Unit (ODU) ‐ LSU090HEV1 Indoor Unit (IDU) ‐ LSN090HEV1
Performance:
Cooling:
Operating Range:
Outdoor Unit:
Capacity (Min/Rated/Max) (Btu/h)
SEER
EER
3,070~8,500~9,500
19.0
12.5
SEER ‐ Seasonal Energy Efficiency Ratio EER ‐ Energy Efficiency Ratio
Heating:
Capacity (Min/Rated/Max) (Btu/h)
HSPF
3,070~9,000~10,500
9.0
HSPF ‐ Heating Seasonal Performance Factor
Cooling Nominal Test Conditions:
Indoor: 80°F DB/67°F WB
Outdoor: 95°F DB/75°F WB
Heating Nominal Test Conditions:
Indoor: 70°F DB/60°F WB
Outdoor: 47°F DB/43°F WB
Electrical:
Power Supply (V¹/Hz/Ø)
208‐230/60/1
Outdoor Unit:
MOP (A)
15
MCA (A)
Cooling Rated Amps (A)
Heating Rated Amps (A)
10
7.5
7.5
Compressor (A)
7.0
0.5
Fan Motor (A)
MOP ‐ Maximum Overcurrent Protection MCA ‐ Minimum Circuit Ampacity
Total Power Input:
Cooling Power Input (kW)
0.68
Heating Power Input (kW)
0.78
Piping:
14‐118
14‐65
Indoor Unit:
Cooling (°F WB)
Heating (°F DB)
53‐75
60‐86
Unit Data:
Refrigerant Type
Refrigerant Control
Refrigerant Charge (lbs)
ODU Sound Pressure (±3 dB(A))³
IDU Sound Pressure ±3 (H/M/L/Sleep) dB(A)³
R410A
EEV
1.87
47
39/33/25/19
ODU Net Unit Weight (lbs)
ODU Shipping Weight (lbs)
62
67
IDU Net Unit Weight (lbs)
IDU Shipping Weight (lbs)
17
20
Heat Exchanger Coating
GoldFin™
Fan:
ODU Type
IDU Type
Fan Speeds (Fan/Cooling/Heating)
208‐230/60/1
Quantity (ODU + IDU)
Propeller
Cross Flow
4/4/4
1+1
Motor/Drive
Brushless Digitally Controlled/Direct
ODU Max Air Flow Rate (CFM)
953
IDU Air Flow Rate H/M/L (CFM)
276/226/177
Dehumidification (pts/hr)
Liquid Line (in, OD)
Vapor Line (in, OD)
1/4
3/8
Additional Refrigerant (oz/ft)
Max Pipe Length (Min/Max) (ft)²
Piping Length (no add'l refrigerant, ft)
Max Elevation (ft)
0.22
9.8/49.2
24.6
22.9
Controls Features:
•24‐Hour on/off mer
•2‐Way (up/down) auto
swing
•Auto changeover
•Auto restart
•Condensate sensor
connection
Cooling (°F DB)
Heating (°F WB)
2.12
Notes:
1.Acceptable opera ng voltage: 187V‐253V.
2.Piping lengths are equivalent.
3.Sound Pressure levels are tested in an anechoic chamber under ISO Standard 1996.
4.All power/communica on cable to be minimum 18 AWG, 4‐conductor, stranded, shielded
and must comply with applicable local and national code.
5.See Engineering Manual for sensible and latent capaci es.
6.Power wiring cable size must comply with the applicable local and na onal code.
7.The indoor unit comes with a dry helium charge.
8.This data is rated 0 above sea level, with 24.6 of refrigerant line and a 0 level difference
between outdoor and indoor units.
9.Must follow installa on instruc ons in the applicable LG installa on manual.
•Energy saving
•Inverter (variable speed
compressor)
•Jet cool/Jet heat
•Self‐cleaning indoor coil
•Sleep mode
•Ultra quiet opera on
For continual product development, LG reserves the right to change specifications without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com.
SB‐SZ‐Mega220‐LS090HEV1‐4‐15
Page 1 of 3
Job Name/Location:
Outdoor Unit (ODU) ‐ LSU090HEV1
Tag #:
Mega 220V Single Zone Inverter
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com.
SB‐SZ‐Mega220‐LS090HEV1‐4‐15
Page 2 of 3
Job Name/Location:
Indoor Unit (IDU) ‐ LSN090HEV1
Tag #:
Mega 220V Single Zone Inverter
Date:
PO No.:
For continual product development, LG reserves the right to change specifications without notice.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com.
SB‐SZ‐Mega220‐LS090HEV1‐4‐15
Page 3 of 3
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising