LG | LA120HSV5 | LA120HSV5 Submittal | LG LA120HSV5 LA120HSV5 Submittal

Tag #:
Job Name/Location:
Date:
For:
PO No.:
Architect:
GC:
Engr:
Mech:
Rep:
(Company) File
Approval
Resubmit
Other
(Project Manager)
LA120HSV5
Single Zone Art Cool™ Mirror Wall Mount
Outdoor Unit (ODU) - LSU120HSV5, Indoor Unit (IDU) - LAN120HSV5
Performance:
Cooling:
Operating Range:
Outdoor Unit:
Cooling Capacity
(Min~Rated~Max) (Btu/h)
SEER
EER
SEER - Seasonal Energy Efficiency Ratio
1,023 ~ 12,000 ~ 13,785
22.7
12.5
EER - Energy Efficiency Ratio
Heating:
Heating Capacity
(Min~Rated~Max) (Btu/h)
HSPF
Max. Heating @ Indoor 70°F DB
Outdoor 19°F DB / 17°F WB
Outdoor 6°F DB / 5°F WB
Outdoor -3°F DB / -4°F WB
HSPF - Heating Seasonal Performance Factor
Cooling Nominal Test Conditions:
Indoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
1,023 ~ 13,600 ~ 22,178
11.4
13,810 (102%)
11,930 (88%)
10,360 (76%)
Heating Nominal Test Conditions:
Indoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB
MOP (A)
MCA (A)
Cooling / Heating Rated Amps (A)
Compressor (A)
Fan Motor (A)
15
10
7.4 / 7.4
7
0.4
MCA - Minimum Circuit Ampacity
Total Power Input:
Cooling Power Input (kW)
Heating Power Input (kW)
0.96
1.04
Piping:
Liquid Line (in., O.D.)
Vapor Line (in., O.D.)
Additional Refrigerant (oz./ft.)
Min. / Max. Pipe Length (ft.)²
Piping Length (no add’l refrig., ft.)
Max. Elevation (ft.)
Controls Features:
• 24-Hour on/off timer
• 4-Way auto swing
• Auto changeover
• Auto restart
• Jet cool/Jet heat
• Built-in low ambient standard, down to
14°F (cooling mode)
Optional Accessories:
ø1/4
ø3/8
0.22
9.8 / 82
41
49.2
• Condensate Sensor
Connection
• Inverter (variable speed
compressor)
• IDU compatible with
Multi F ODUs
• Smart Diagnosis
• 3M Micro Filter
MultiSITE™ CRC1 - PREMTBVC0
MultiSITE CRC1+ - PREMTBVC1
MultiSITE Comm. Mgr. - PBACNBTR0A
PI-485 - PMNFP14A1
Dry Contact - PDRYCB300
LonWorks® Gateway - PLNWKB100
14 ~ 118
-4 ~ +65
Indoor Unit:
Cooling (°F WB)
Heating (°F DB)
53 ~ 75
60 ~ 86
Electrical:
Outdoor Unit:
MOP - Maximum Overcurrent Protection
Cooling (°F DB)
Heating (°F WB)
• Self-cleaning indoor
coil
• Sleep mode
• Cooling only function
• Built-in Wi-Fi via Smart
ThinQ™ app
• Built-in drain pan
heater (9/12k; optional
for 18k)
AC Smart IV BACnet® Gateway PBACNA000
ACP IV BACnet Gateway - PQNFB17C2
Drain Pan Heater for 18k - PQSH1201
Low Ambient Wind Baffle Kit (Cooling
to 0°F) - ZLABGP01A
Power Supply (V¹/Hz/Ø)
208-230/60/1
System Data:
Refrigerant Type
Refrigerant Control
Refrigerant Charge (lbs.)
ODU Sound Pressure
(Cooling / Heating) (±3 dB[A])³
IDU Sound Pressure
Cooling (H/M/L/Sleep) (±3 dB[A])³
Heating (H/M/L) (±3 dB[A])³
ODU Net / Shipping Weight (lbs.)
IDU Net / Shipping Weight (lbs.)
Heat Exchanger Coating
R410A
EEV
2.21
45 / 48
39 / 33 / 23 / 19
39 / 33 / 23
74.1 / 78.9
20.5 / 25.6
GoldFin™
Fan:
ODU Type
IDU Type
Fan Speeds (Fan/Cool/Heat)
Quantity (ODU + IDU)
Motor/Drive
ODU Max. Air Flow Rate (CFM)
IDU Air Flow
Cooling, Max/H/M/L (CFM)
Heating, Max/H/M/L (CFM)
Dehumidification (pts./hr.)
Propeller
Cross Flow
6/6/6
1+1
Brushless Digitally Controlled/Direct
1,165
459 / 338 / 317 / 194
459 / 338 / 317 / 229
2.7
Notes:
1. Acceptable operating voltage: 187V-253V.
2. Piping lengths are equivalent.
3. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
4. All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied
and is to be minimum four-conductor, 18 AWG, stranded, shielded or unshielded (if shielded, it must be
grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes.
5. See Engineering Manual for sensible and latent capacities.
6. Power wiring cable size must comply with the applicable local and national code.
7. The indoor unit comes with a dry helium charge.
8. This data is rated 0 ft. above sea level, with 24.6 ft. of refrigerant line and a 0 ft. level difference between
outdoor and indoor units.
9. Must follow installation instructions in the applicable LG installation manual.
10. Multi compatible 18k IDUs include socket adapters for refrigerant pipe connections with Multi F systems.
BACnet® is a registered trademark of ASHRAE. LonWorks® is a trademark of Echelon Corporation.
For a complete list of available accessories, contact your LG representative.
SB_SZ_Art_Cool_Mirror_LA120HSV5_2018_03_21_102037
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Page 1 of 3
Job Name/Location:
LA120HSV5
Single Zone Art Cool™ Mirror Wall Mount
Outdoor Unit (ODU) - LSU120HSV5, Indoor Unit (IDU) - LAN120HSV5
Tag No.:
Date:
PO No.:
SB_SZ_Art_Cool_Mirror_LA120HSV5_2018_03_21_102037
For continual product development, LG reserves the right to change specifications without notice.
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com
Page 2 of 3
Job Name/Location:
LA120HSV5
Tag No.:
Outdoor Unit (ODU) - LSU120HSV5, Indoor Unit (IDU) - LAN120HSV5
PO No.:
Single Zone Art Cool™ Mirror Wall Mount
Date:
SB_SZ_Art_Cool_Mirror_LA120HSV5_2018_03_21_102037
For continual product development, LG reserves the right to change specifications without notice.
Page 3 of 3
© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp. /www.lghvac.com