GE Zoneline® Heat Pump Unit with Corrosion Protection, 265 Volt
DIMENSIONS AND INSTALLATION INFORMATION (IN INCHES)
ELECTRICAL WIRING
All wiring, including installation of receptacle, must
be made in accordance with local electrical codes
and ­regulations.
Room
Cabinet
MAXIMUM CORD EXTENSION
A
NOTE: Aluminum wiring may pose special problems – consult a
qualified electrician.
RETROFIT KITS:
RAK40 – Deflector Kit to adapt chassis for use with
existing (non-GE) exterior louvered grilles.
DUCTED APPLICATIONS
AZ45 and AZ65 Series can be used with ductwork to heat or cool more
than one room. RAK6053 Duct Adaptor is applied to the top of case
over the air discharge. RAK601B Duct Extension is applied to right or
left of adaptor. Locally fabricated ductwork may be added to extend to
maximum recommended straight distance of 15 feet in one direction.
ELECTRICAL CONNECTION
265 volt units are provided with a junction box and require direct
connection or permanent direction per NEC. See Architects and
Engineers Design Data Manual for ­electrical connection information
including use of sub-base for direct connected units. Installation must
­comply with local electrical codes and regulations.
Power connection kits are required on all Zoneline chassis.
Outside
Zoneline RAC Wall Installation
WALL CASE DIMENSIONS
GRILLE OPTIONS
Stamped Aluminum Grille – RAG60
Exterior Architectural Louvers Durable Polycarbonate:
RAG61 (Beige)
RAG63 (Dark Brown)
RAG62 (Maple)
Extruded Aluminum Architectural Grille – RAG67
RAB71A = 16
RAB77A = 16
SIDE
VIEW
C
21
58
B
RAB71B WALL SLEEVE
Heavy-gauge galvanized steel,
with insulation.
A – 42", B – 13-3/4", C – 16"
Also available in 16" and 24"
depths
RAB77B WALL SLEEVE
Molded SMC fiberglassreinforced polyester compound.
A – 42-1/8", B– 13-7/8",
C – 16-1/4"
WALL OPENING
DIMENSIONS
Add 1/4" to A and C dimensions
for all cut-outs.
RAB71B 16-1/4" Min. H x
42-1/4" Min. W
RAB77B 16-1/2" Min. H x
42-3/8" Min. W
265 VOLT SUB-BASE CONNECTED UNITS
SUB-BASE
POWER
CONNECTION
KIT
ELECTRIC
HEATER
WATTS
RAK204E15
RAK204E20
RAK204E30
RAK515D
RAK520D
RAK530D
2,460
3,470
4,870
For more information, please visit our website at zoneline.com or call 888.231.2548.
ELECTRIC MIN. CIRCUIT
HEAT AMPS PROTECTION
(AMPS)
9.1
12.8
18.1
15
20
30
Specification Revised 7/16
AZ65H15EAC
GE Zoneline® Heat Pump Unit with Corrosion Protection, 265 Volt
FEATURES AND BENEFITS
Cooling capacity - 14,500 BTU
Energy efficiency - 10.6 EER
Dehumidification - 4.8 pints/hour
Reverse heat cycle - 13,500 BTU
Heat pump efficiency - 3.3 COP
Indoor fan CFM (high/low) - 449/290
Fresh air vent CFM (fully open high fan) - 44
Quiet operation - Baked-on mastic sound barrier,
cross flow blower and two DC fan motors create less
noise to ensure comfort
Corrosion resistant - Extends life of the unit in sea
coast areas/corrosive environments
Heat & Freeze Sentinels - Keeps the room from
overheating or freezing
Boost heat option - Provides supplemental resistance
heat in heat pump mode
Electronic temperature limiting - Prevents expensive
over-cooling or over-heating of the room
Electronic touch controls with LED display
R-410A refrigerant
SMC base pan
Specification Revised 7/16