Klimaire | KSIO018-H221-OC | Specifications | Klimaire KSIO012-H223-OC Specifications

KSIO Outdoor Unit
Klimaire Model No.
KSIO012-H223-O
KSIO018-H221-O
KSIO024-H218-OC
V- Ph-Hz
230-1-60
230-1-60
230-1-60
Max. fuse
A
15
20
25
Minimum circuit ampacity
A
8
13
15
1
1
1
r/min
850/580
750/500
850
cfm
1295
1471
2060
dB(A)
55
60,5
61
Capillary
Capillary
Capillary + EXV
Power supply
Ourdoor fan motor
Qty
Speed
Outdoor air flow
Outdoor noise level
Throttle type
Outdoor unit
Refrigerant type/Quantity
Dimension (W×D×H)
in
Packing (W×D×H)
in
35" x 14" x 25"-3/8
38" x 15"-5/8 x 29"-11/16
41" x 15"-5/8 x 36"
Net/ Gross weight
lb
87 /92.4
104.5 / 112.2
159 /168
R410A
R410A
R410A
oz
56,53
61,83
89,6
psig
340
340
340
Liquid side/ Gas side
in
1/4" / 1/2"
3/8" / 5/8"
3/8" / 5/8"
Max. pipe length
ft
35
98
160
Max. difference in level
ft
33
65
80
Cooling
ºF
0~50
5~122
5~122
Heating
ºF
5~75
5~75
5~75
Type
Charged volume
Design pressure
Refrigerant piping
Ambient temperature
30"-1/8 x 11"-1/8 x 23"-1/4 33"-1/4 x 13"-3/16 x 27"-13/32 35"-3/16 x 12"-3/16 x 33"-7/8
Remarks:1.The above design and specifications are subject to change without prior notice for product improvement.
2.The values given in the table for the noise level reflect the levels in anechoic chamber.