Split System Submittal Data
System: 26XHW72R
Indoor/Outdoor: XHWX2672R/CH2672R
Grille: PNR-XH2442
Ceiling Recessed Heat Pump
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
Power
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Approval:
Date:
Construction:
Unit #:
Drawing #:
General Data (at 230V)
V/PH/Hz
230/208/1/60
(A)
15-30 Indoor-Outdoor
(A)
15-30 Indoor-Outdoor
DC Rotary Inverter
1
12.9-17.5
(A)
Propeller
18-7/64-1
DC Motor
8 - 800
1 - 90
1765
13.8
(RPM)
(W)
(High)
(A)
(sq.ft.)
(in.)
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifed
1-15.9
7.26
3/8”
Refrigerant
Lbs. - R410a (outdoor unit)
Control
Connection
Line Length, Max (ft.)
Lift Difference, Max (ft.)
Line Size
Line Size
Dimensions
Indoor Unit
Outdoor Unit
Weight
Net
Shipping
Shipping Volume
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
(RPM, High)
No. Poles
(W)
No. Motors
(HI/Med/Lo)
CFM
Indoor Sound Rating
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
(Hi) (dB-A)
(A)
Turbo
17-7/16-1
3 & Auto
6 - 466
1 - 40
710/530/450
38
0.7
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifed
2 - 14.9
(sq.ft.)
3.69
(in.)
9/32”
(in.)
1-17/64
R410A
4.19
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge)
3/8”
(in. O.D. Suction)
5/8”
(in.)
(Uncrated)
(Crated)
(Uncrated)
(Crated)
(lbs.)
(lbs.)
(cu.ft.)
HxWxD
13-5/16 x 33-55/64 x 33-55/64
11-9/64 x 32-7/8 x 33-9/32
30-23/32 x 37 x 3-3/8
34-31/32 x 39-31/32 x 16-3/32
Indoor
49
57
Outdoor
128
148
Indoor
7.1
Outdoor
13.0
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity
(BTU/H)
24,800 (9,500-24,800)
Sensible Capacity
(BTU/H)
14,810
Latent Capacity
(BTU/H)
9,990
SEER
14.1
Dehumidification
(Pints/H)
8.1
(A)
15.6/17.3
Amps
(W)
2,920/2,920
Power Inputs
Outdoor Sound Rating
(dB-A)
49
Heating
Total Capacity
HSPF
(BTU/H) 29,800 (8,000-29,800)
10.5
Dimensions
Heating
Amps
Max. Amps
Power Inputs
Back-up Strip Heater
Outdoor Sounds Rating
(A)
(A)
(W)
(KW)
(dB-A)
Features
Dimensional
Data for 26XH72R
Options
14.8/16.4 Refrigerant Line Set
14.8/16.4 Fresh Air Intake
2,790/2,790 Airduct Extension
0.00/0.00 Condensate Drain Pump
49 Wireless Remote Controller
Non-Removeable Locking Remo-con Bracket
Microprocessor Operating Range
Remote Controller
LCD Wired Type, Temp. Sensor Built In
IC Thermostat Cooling
Temperature Control
72 Hr. ON/OFF
Maximum
Timer
Minimum
Built-In
Night Setback
(Horizontal)
Manual
Air Louver
(Vertical)
Automatic
Built-In Heating
Power Failure Automatic Restart
Dimensional Data for
Heating/Cooling Automatic Changeover
Built-In
Maximum
Indoor unit : XH2672R
Self-Diagnosis
Built-In
Minimum
Air Filter
Washable, Anti-Mold
Available
Available
Knock-out
Standard
Available
Available
Indoor
Controlsunit : XH2672R
Indoor Air Intake Temp.
Outdoor Air Intake Temp.
95F DB/71F WB
67F DB/57F WB
Indoor Air Intake Temp.
26XH72R
80F DB/67F WB
-DB/-WB
109F DB
0F DB
Outdoor Air Intake Temp.
75F DB/65F WB
5F DB
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com