INSTALLATION INSTRUCTIONS
Ventilating Fan
Model No. FV-01WS2 FV-04WS2
Contents
GENERAL SAFETY INFORMATION --------==================- 2-3
DESCRIPTION -------=-=====e=eceeeceeeaoeneoeanananecenneenne 4
UNPACKING ---------=====ccccc00eneeenaooooneene nacen m eee 4
SUPPLIED ACCESSORIES --------=-====eeeecoceenanaconeneeeo- 4
DIMENSIONS ------""00000 00m eeeeeeeenna nc esse seen nn nee 5
WIRING DIAGRAM -------<<<<<<<<<<<<<<<<00eeeeee eee e eee neess 5
INSTALLATION I (Wall thickness is 4.5"- 6") --------------- 6-8
INSTALLATION II (Wall thickness is 6"-10") ----------------- 9
MAINTENANCE (CLEANING) --------========eeeeecconneaneo—- 10
SWITCH INDICATION ----------========ereceeeeeeneceeeeeeee 11
PRACTICAL GUIDE TO INSTALLATION »=====================-- 11
SPECIFICATIONS +++ rennen rk AREA RER RER RER RAR EEE 11
PRODUCT SERVICE ---------<-<---<-<--<"<----"----- BACK COVER
READ AND SAVE THESE INSTRUCTIONS
Thank you very much for having purchased our product.
Please read these instructions carefully before attempting to install, operate or service
the Panasonic product. Failure to comply with instructions could result in personal injury
or property damage. Please explain to users how to operate and maintain the
product after installation, and this booklet should be presented to users.
Please retain this booklet for future reference.
GENERAL SAFETY INFORMATION
For Your Safety
To reduce the risk of injury, loss of life, electric shock, fire, malfunction, and damage to
equipment or property, always observe the following safety precautions.
Explanation of symbol word panels
The following symbol word panels are used to classify and describe the level of hazard, injury, and
property damage caused when the denotation is disregarded and improper use is performed.
A VV A R N | N G nur 2 potential hazard that could result in serious
A CAUTI O N Denotes a hazard that could result in minor injury.
The following symbols are used to classify and describe the type of instructions to be observed.
This symbol is used to alert users to a specific operating procedure that must not be
performed.
This symbol is used to alert users to a specific operating procedure that must be followed
in order to operate the unit safety.
This symbol is used to alert users to a specific operating procedure that must not be
performed.
This symbol is used to alert users to make sure of grounding when using the equipment
with the grounding terminal.
A WARNING
To reduce the risk of fire, electric shock or injury to persons, observe the following:
Use this unit only in the manner intended by the manufacturer. If you have any questions,
contact the manufacturer.
Before servicing or cleaning unit, switch power off at service panel and lock the service
disconnecting means to prevent power from being switched on accidentally. When the
service disconnecting means cannot be locked, securely fasten a prominent warning device,
such as a tag, to the service panel.
Installation work and electrical wiring must be done by qualified person(s) in accordance
with all applicable codes and standards, including fire-rated construction.
When cutting or drilling into wall, do not damage electrical wiring and other hidden utilities.
Ducted fans must always be vented to the outdoors.
Not to be installed over a tub or shower.
Do not use this fan with any solid-state speed control device.
OE OL
GENERAL SAFETY INFORMATION
A WARNING
O
Do not disassemble the unit for reconstruction. It may cause fire or electric shock.
When this product is no longer being operated, please remove the product to prevent the
possibility of falling.
@ This product must be properly grounded.
A CAUTION
SS SS IO
To reduce the risk of fire, electric shock or injury to persons, observe the following:
Do not install this ventilating fan in the window or ceiling.
Do not install this ventilating fan where the children can reach.
Do not install this ventilating fan where interior room temperature may exceed 104°F(40°C).
Make sure that the electric service supply voltage is AC 120V, 60Hz.
Follow all local electrical and safety codes, as well as the National Electrical Code (NEC) and
the Occupation Safety and Health Act (OSHA).
Always disconnect the power source before working on or near the fan, motor, or junction box.
Protect the supply wiring from sharp edges, oil, grease, hot surfaces, chemicals or other
objects.
Do not kink the supply wiring.
The wall must be subjected to static load more than five times the weight of the product.
Do notinstall the product with a method which is not approved
in the instruction.
(Cooking area)
Do not install above or
Not for use in cooking area. (Fig.A) \ <—— inside this area —»
N /
Condensation may form on the inner cover if the outdoor NN / / | \ \ DA
temperature is less than 23°F(-5°C) and the indoor temperature \ 6 45 7
is above 77°F(25C) with a 50%RH. SL >
Do not install the hood where it can be buried in snow. Cooking Floor
equipment y
Fig.A
DESCRIPTION
These ventilating fan models are listed by UL under UL file No. E78414.
These ventilating fan models use a propeller fan driven by a capacitor motor.
The motor is designed to have an extended service life with reduced energy consumption.
The motor incorporates a thermal-cutoff for safety.
The inner cover will act as a damper to prevent unintended air entry.
These ventilating fans are equipped with a filter which is replaceable.
UNPACKING
Unpack and carefully remove the unit from carton.
Refer to the supplied accessories list to verify that all parts are present.
SUPPLIED ACCESSORIES
Part name Appearance Quantity
Screw I
(M4X10) Em 2
Screw II
(ST4.2X20) QE 8
Installation | 2
instructions
Warranty
sheet
A CAUTION
The special-purpose or dedicated parts, such as mounting fixtures, must be used if such
parts are provided.
DIMENSIONS
Main unit Duct unit
1 2
— 4 (8)
< Y
О
_ L
Hood unit
| N J O f
—! 19 _ No. Part name No. Part name
/ Ш ® Frame @ Junction box
© Filter Duct
= J 3) Motor ©) Hood
@ Blade Duct collar
® Panel aD Hood base
(6) Switch
Unit: inches (mm)
Model A B C D E F G H |
FV-01WS2 6 3/4 33/4 33/4 23/16 61/8 55/16 | 47/16 51/8 41/2
(172) (95) (95) | (55) (156) | (135) | (112) | (130) | (115)
FV-04WS2 83/4 59/16 33/4 23/16 8 6 7/8 | 5 15/16 | 6 13/16 | 5 13/16
(222) (141) (95) (55) (203) (174) (151) | (173) (148)
Model J K L M N O Р Q
FV-01WS2 6 1/4 3 7/8 6 67/8 51/2 47/16 11/16 35/8
(159) (98) (152) | (174) (140) (113) (17) (92)
FV-04WS2 83/16 | 513/16 | 63/16 | 87/16 | 75/16 5 1/4 11/16 | 59/16
(208) | (148) | (157) | (215) | (186) | (134) (17) | (142)
WIRING DIAGRAM
FV-01WS2 FV-04WS2
4 O D
Fan body | Fan body
Red (0.5HF) . Junction box g Capacitor (1.1pF) -- Junction box ==
Capacitor White White iNeutral _ Switch Hi White ||| White ) Neutral pour supply
Motor White Switch © я 7 Power supply Ra (за) Г 7 | AC120V 60Hz
; Back >] Black |||) Black Live — AC120V 60Hz Ressior_Resior | Black Black tive >
(1 14 C Fuse in Motor) ! Capacitor Lo |
Impedanceprotected | __|Green | | Green [Earth ground, (114° Fuse in Motor) | [Green Green | Esti ground” 7
Ноя Thermally - protected/ | 5
\ A J
INSTALLATION I — Wall thickness is 4.5" - 6" (114Mmm-152mm)
Exterior sheathing
yin
NOTE: Unit: inches (mm) Stud
1. This ventilating fan can be installed with an
interior wall covering thickness of 1/2"-1 1/4"
(12.7mm-31.8mm). >8(203)
2. The figures below are applicable to both
the FV-01WS2 model and the FV-04WS2
model.
72-84,
1. Cut an interior and exterior hole matching the fan g gd
duct diameter. For the interior hole, maintain an Model | Abt! € Te
8" clearance between the outer hole diameter and ||rv-01wWs2 | (145) | (114) | (4) Sr A ©
walls or ceilings. For the exterior hole, the ideal 71/2 [65/16] 3/16
height would be between 72" (1829 mm) and 84" FV-04WS? | (190) | (160) | (4) Fig. 1
(2137 mm). (Fig 1)
A CAUTION vi
O The hole should be made in an area where
Hood unit
Duct unit
pipes, cables and telephone line are not run,
and there are not studs in the way.
2. Separate the product to main unit, duct unit and
hood unit. (Fig.2)
Fig.2
3. Unscrew two screws, lower the junction box into
the duct and pull it out from duct unit. (Fig.3)
Duct unit
4.Insert the duct unitinto wall and secure it to the Fig. 3
drywall or other wall covering by screwII
(ST4.2X20) in accessory. (Fig.4) Interior drywall
Before installation, adjust the direction of
theduct unitin accordance with UP mark.
Theupper edge should be kept horizontal.
A CAUTION os
(ST4.2X20)
Particularly in the extremely cold area, please
take thermal insulation around the duct unit,
to avoid condensation. Fig. 4
5.Pull flexible conduit or other supply wiring Flexible Conduit
through the junction box hole in the duct unit
and into the room 6-10”. (Fig.5)
Fig. 5
INSTALLATION I — Wall thickness is 4.5"~ 6" (114mm~152mm)
Flexible Conduit
6. Open knock-out hole and unscrew the screw
holding the junction box cover. After removing
junction box cover, secure conduit or stress
relief on the knock-out hole.(Fig.6) Knock-out
hole
Junction box cover Fig. 6
7. Refer to wiring diagram (page 5). Follow all the
local electrical safety codes as well as the National
Electrical Code (NEC). Using UL approved wire nuts,
connect house power wires to ventilating fan wires.
Insure the wires are attached so that the wire
connections within the Junction Box can be
re-inserted into the Duct Unit. (Fig. 7)
Earth ground
black to green Fig.7
8. Reattach the junction box cover to junction box by
using screw. (Fig. 8)
A CAUTION
The pin must insert
to the hole
Screw N А Junction box
Junction box
cover
O Mountjunction box cover carefully so
that lead wires are not pinched. Junction box
9. Reinstall junction box back into duct unit by
using screws . (Fig.9) ê ,
Screws /
Duct unit
Fig.9
10. Detach the panel from fan body by pushing Fan body
up and pulling outward the tab at the base
of the panel.(Fig.10)
. . Panel
11. Open the cover in the top right corner of the Fig. 10
fan body to allow the junction box pigtail and
plug to come through. Insert the plastic duct ; Plug connector
of the fan body into the metal duct unit and ‘
secure it with 2 screw I (M4X10) in accessory.
(Fig. 11)
A CAUTION
Mount fan body carefully so that lead Fanbody Duct unit SN
wires are not pinched. Fig.11
INSTALLATION I — Wall thickness is 4.5"~ 6" (114mm-~152mm)
12. Link up the plug connector and close the
cover. (Fig.12) Plug connector
A CAUTION
The connection of the plug connector should
be tight. After the plug connector is connected
and fixed, make sure it does not tilt.
13. Replace the panel by hanging the panel from
the mounting hinge on the top of the black
plastic frame and “swinging” the cover down
into place.
After replacing, move the lever left and right
to confirm the movement of the shutter.
(Fig.13)
A CAUTION
)
Lever
«финн»
Close Open
Fig. 13
Stop the fan while closing the shutter.
Open the shutter while running the fan.
14. Detach hood and hood base by loosening the
screw . (Fig. 14)
15. Insert duct collar into duct and adjust the
upper edge of hood base to horizontal.
Secure hood base by using screwII (ST4.2x20)
in accessory and seal the gap between the
wall and hood base by sealant. (Fig. 15)
Hood base Fig.1 5
16. Install hood on hood base and secure it by using
screw . (Fig. 16)
The rib of the hood should be matched firmly
with the claw of the hood base.
“Screw Fig.16
INSTALLATION II — Wall thickness is 6"~10" (152mm-~254mm)
NOTE:
1. This ventilating fan can be installed with an
interior wall covering a thickness of 1/2"-1 1/4"
(12.7-31.8mm).
1. Cut holes in the wall and remove the junction
box following the step 1-3 of installation 1 .(Page 6)
2. Slip duct unit into flexible duct (not supplied) and
secure it with duct tape. (Fig.17)
According to the thickness of the wall, decide the
length of the flexible duct. For 10” wall, it is
suggested the flexible duct length is 5” when itis in
extension.
3.Insert the duct into wall and secure it with 4
screw II(ST4.2X20) in accessory. (Fig.18)
Before installation, adjust the direction of
the duct unit in accordance with UP mark.
The upper edge should keep horizontal.
4.Finish indoor installation following step 5-13
of installation! . (Page 6 to 8)
5.Detach hood following step 14 of installation].
(Page 8)
Press buckle on hood base and detach duct
collar after loosening three buckles. (Fig.19).
6. Pull flexible duct to a suitable length through
the hood base. Keep the upper edge of hood
base horizontal and secure it by 4 screwlIl
(ST4.2X20) in accessory. Seal the gap between
the wall and hood base by sealant. (Fig. 20)
7. Join the flexible duct and duct collar with mastic
tape. (Fig.21)
8.Press duct collar and flexible duct until duct
collar fits into hood base completely.(Fig. 22)
A CAUTION
O
9. Follow steps 16 of installation! (page 8) to
complete the installation work.
Make sure the three buckles fix the duct
collar firmly.
Flexible duct
(Not supplied
FV-01WS2: 4inch size
FV-04WS2: 6inch size)
Duct tape
Fig.17
Interior
drywall
Fig.18
Loose the screw
Buckle
Hood base
№
X= =
ZE
f Te
Fig. 20
Flexible duct
Exterior wall
Mastic tape
Hood base
Duct
collar
ood base
Duct collar
Fasten by buckles
Fig.22
MAINTENANCE (CLEANING)
A WARNING
Disconnect power source before working on
unit. Maintenance must be done every year.
©
When removing the panel, beware of it in
case it may fall off and cause an injury.
A CAUTION
10
Never use gasoline, benzene, thinner or any
O other such chemicals for cleaning the
ventilating fan.
Do not immerse motor in water when
cleaning.
Do not soak resin parts in water over 140°F
(60°C).
After long time use, dust may fall down
when removing the panel and filter.
To maintain the performance of product,
please clean the filter every month and
replace it every year.
When cleaning the product,switch cap
can't be removed.
e
©
If the filter is damaged or the filter has not
been installed, insects may get into the unit.
. Close shutter and detach the panel by pushing up
the tab. (Fig.23)
. Remove dust and dirt inside the panel by using a
vacuum cleaner. Clean the surface of the panel with
non-abrasive kitchen detergent and wipe dry with
clean cloth. (Please do not immerse panel in water
while cleaning). (Fig.24)
. Squeeze the buckle of the filter and detach it.
Remove dirt from it by using a vacuum cleaner.
(Fig.25)
When replacing the filter, please purchase new
filter from our representative. (Model number
of filter is FV-FLO1WS1 for FV-01WS2 and
FV-FLO4WS1 for FV-04WS2.)
. Remove dust and dirt from fan body by using
a vacuum cleaner first, and then a cloth
dampened with kitchen detergent. Wipe any
dirt with clean cloth.(Fig.26)
. Replace the filter after finishing the cleaning.
(Fig.27)
. Follow step 13 of installationI (page 8) to replace
the panel.
Switch cap
(can't be removed)
O Buckle the filter firmly
(1) Fully insert to frame Fig.27
SWITCH INDICATION
FV-01WS2 Switch (Fig. 28)
"1"- Power ON (10 CFM)
"O"- Power OFF
FV-04WS2 Switch (Fig. 28)
"11"- Power ON high speed (40 CFM)
"O"- Power OFF
"| "- Power ON low speed(20 CFM)
O)
FV-01WS2
FV-04WS2
Switch Fig.28
Properly insulate the area around the fan to |
minimize building heat loss and gain. (Fig.29) Interior wall Exterior wall
Loose fill or batt insulation can be placed covering siding
directly over the duct in the wall. Fan body
Junction box
Hood
O
Duct
unit
Indoor Outdoor
|| Fig.29
. . Air volume ;
Duct Air Voltage |Frequency| Noise Power Speed я Weight
Model No. | diameter нач consumption . at 0.03" WG
(inches) direction (V) (Hz) (sones) (W) (r/min) (СЕМ) Ib.(kg)
FV-01WS2 4 Intake | 120 60 <0.3 3.0 2590 10 5.3 (2.4)
| 2520
FV-04WS2 6 Intake HL 120 60 1.2 8:5 40 6.8 (3.1)
Lo| 120 60 <0.3 5.5 1680 20
HVI Certified performance based on HVI Procedures 915, 916 and 920.
11
PRODUCT SERVICE
Warning Concerning Removal of Covers.
The unit should be serviced by qualified technicians only.
Your product is designed and manufactured to ensure a minimum of maintenance.
Should your unit require service or parts, call Panasonic Call Center at 1-866-292-7299 (USA)
or 1-800-669-5165 (Canada).
Panasonic Corporation of North America
Two Riverfront Plaza, Newark, NJ 07102
WWW. panasonic.com
Panasonic Canada Inc.
5770 Ambler Drive, Mississauga, Ontario L4W 2T3
WWW. panasonic.ca
© Panasonic corporation 2014
Printed in China T0214-0 01WS24010