LG ATUQ36LMLE3 Installation guide


Add to my manuals
21 Pages

advertisement

LG ATUQ36LMLE3 Installation guide | Manualzz
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
www.lg.com
P/NO : MFL67448512
Single A Air Conditioner Installation Manual
CONTENTS
Safety Precautions ..............................................................................................3
Installation of Outdoor Unit................................................................................6
Wiring Connection...............................................................................................8
Connecting Pipes ..............................................................................................11
Leakage test and Evacuation ...........................................................................14
Test running .......................................................................................................16
Function..............................................................................................................18
Self-diagnosis Function....................................................................................19
Installation Guide at the Seaside .....................................................................20
2 Air Conditioner
Safety Precautions
Safety Precautions
To prevent the injury of the user or other people and property damage, the following instructions
must be followed.
n Be sure to read before installing the air conditioner.
n Be sure to observe the cautions specified here as they include important items related to safety.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to properties only.
n The meanings of the symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
n Installation
Always perform grounding.
Donʼt use a Power cable, a
plug or a loose socket
which is damaged.
• Otherwise, it may cause electrical shock.
• Otherwise, it may cause a fire
or electrical shock.
• Otherwise, it may cause a fire,
electrical shock, explosion or injury.
Securely attach the electrical
part cover to the indoor unit
and the service panel to the
outdoor unit.
Be sure to install an earth
leakage breaker.
Do not keep or use flammable gases or combustibles
near the air conditioner.
• If the electrical part cover of the indoor
unit and the service panel of the outdoor unit are not attached securely, it
could result in a fire or electric shock
due to dust, water, etc.
For installation of the product, always contact the service center or a professional
installation agency.
• Failure to install an earth leak- • Otherwise, it may cause a fire
age breaker may result in
or the failure of product.
electric shocks or fire.
Ensure that an installation frame of the outdoor unit is not damaged due to use for a
long time.
• It may cause injury or an accident.
Do not disassemble or repair the product
randomly.
• It will cause a fire or electrical shock.
Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion.
• There is the risk of death, injury, fire or explosion.
Installation Manual 3
Safety Precautions
Do not install the product at a place that there
is concern of falling down.
• Otherwise, it may result in personal injury.
Use caution when unpacking and installing.
• Sharp edges may cause injury.
n Operation
Do not share the outlet with
other appliances.
• It will cause an electric shock
or a fire due to heat generation.
Unplug the unit if strange
sounds, smell, or smoke
comes from it.
• Otherwise, it may cause electrical shock or a fire.
Do not use the power cord
near the heating tools.
• Otherwise, it may cause a fire
and electrical shock.
Hold the plug by the head
when taking it out.
• It may cause electric shock
and damage.
Do not use the damaged
Power cable.
• Otherwise, it may cause a fire
or electrical shock.
Keep the flames away.
• Otherwise, it may cause a fire
or electrical shock.
Take the power plug out if
necessary, holding the head
of the plug and do not touch
it with wet hands.
• Otherwise, it may cause a fire. • Otherwise, it may cause a fire
or electrical shock.
Do not open the suction
inlet of the indoor/outdoor
unit during operation.
• Otherwise, it may electrical
shock and failure.
Never touch the metal parts
of the unit when removing
the filter.
• They are sharp and may
cause injury.
Do not place a heavy object on the power
cord.
• Otherwise, it may cause a fire or electrical
shock.
Take care so that children may not step on
the outdoor unit.
• Otherwise, children may be seriously injured
due to falling down.
4 Air Conditioner
Take care so that the power
cord may not be pulled during operation.
Do not allow water to run
into electrical parts.
• Otherwise, it may cause the
failure of machine or electrical
shock.
Do not step on the
indoor/outdoor unit and do
not put anything on it.
• It may cause an injury through
dropping of the unit or falling
down.
When the product is submerged into water,
always contact the service center.
• Otherwise, it may cause a fire or electrical
shock.
Safety Precautions
n Installation
Install the drain hose to ensure that drain
can be securely done.
• Otherwise, it may cause water leakage.
Always inspect gas leakage after the installation and repair of product.
• Otherwise, it may cause the failure of product.
Install the product so that the noise or hot
wind from the outdoor unit may not cause
any damage to the neighbors.
• Otherwise, it may cause dispute with the neighbors.
Keep level parallel in installing the product.
• Otherwise, it may cause vibration or water
leakage.
n Operation
Avoid excessive cooling and perform ventilation sometimes.
• Otherwise, it may do harm to your health.
Do not use an appliance for special purposes
such as preserving animals vegetables, precision machine, or art articles.
• Otherwise, it may damage your properties.
Use a soft cloth to clean. Do not use wax,
thinner, or a strong detergent.
• The appearance of the air conditioner may
deteriorate, change color, or develop surface
flaws.
Do not place obstacles around the flow inlet
or outlet.
• Otherwise, it may cause the failure of appliance or an accident.
Do not use the product for special purposes,
such as preserving foods, works of art, etc.
It is a consumer air conditioner, not a precision refrigeration system
• Otherwise, it may damage your properties.
Installation Manual 5
Installation of Outdoor Unit
Installation of Outdoor Unit
1. Installation Places
• If an awning is built over the unit to prevent direct
sunlight or rain exposure, make sure that heat
radiation from the condenser is not restricted.
• Ensure that the spaces indicated by arrows
around front, back and side of the unit.
• Do not place animals and plants in the path of
the warm air.
• Take the air conditioner weight into account and
select a place where noise and vibration are minimum.
• Select a place so that the warm air and noise
from the air conditioner do not disturb neighbors.
Su
nro
of
More than
300mm
More than
300mm
Fe
ob nce
sta or
cle
s
More than 600mm
More than 700mm
Unit : mm
2. Piping length and the elevation
FREE JOINT SINGLE OUTDOOR
Pipe Size
Model
Length A(m)
Elevation B(m)
Standard
Max.
Standard
Max.
Additional
Refrigerant
(g/m)
Capacity
Gas
Liquid
AUUQ36LH1
36kBtu/h Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
20
AUUQ42LH1
42kBtu/h Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
20
AUUQ48LH1
48kBtu/h Ø15.88(5/8) Ø9.52(3/8)
7.5
50
5
30
20
6 Air Conditioner
Installation of Outdoor Unit
If installed tube is shorter than 7.5 m, additional charging is not necessary.
Additional Refrigerant = (A -7.5) x Additional refrigerant (g)
Indoor unit
Outdoor unit
A
B
A
Outdoor unit
Indoor unit
B
CAUTION:
• Capacity is based on standard length and maximum allowance length is on the
basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
Night Silent Operation setting
1. Open the Side panel or Top Cover of outdoor unit.
2. Set the SW01N.
SW01N
3. Close the Side panel or Top Cover.
Installation Manual 7
Wiring Connection
Wiring Connection
Electrical Wiring
Perform the electrical wiring work according to the electrical wiring connection.
• All wiring must comply with local requirements.
• Select a power source that is capable of supplying the current required by the air conditioner.
• Use a recognized ELCB(Electric Leakage Circuit Breaker) between the power source and
the unit. A disconnection device to adequately
disconnect all supply lines must be fitted.
• Model of circuit breaker recommended by
authorized personnel only
Model
ELCB
Main
power source
Switch box
Outdoor
Indoor
Phase(Ø)
ELCB(A)
AUUQ36LH1
3
20
AUUQ42LH1
3
20
AUUQ48LH1
3
20
Connecting Cables between Indoor Unit and Outdoor Unit
Outdoor
unit
Indoor
unit
3
2
1
3
2
1
8 Air Conditioner
Wiring Connection
CAUTION
The power cord connected to the outdoor unit should be complied
withIEC 60245 or HD 22.4 S4 (This equipment shall be provided with a
cord set complying with the national regulation.
The connecting cable connected to the outdoor unit should be
complied with IEC 60245 or HD 22.4 S4 (This equipment shall be
provided with a cord set complying with the national regulation.)
10±3mm
35
m
±5
m
10±3mm
35
mm
±5
NORMAL
CROSS-SECTIONAL
AREA 0.75mm2
GN
/YL
20
GN
/YL
mm
20
Model
Phase(Ø)
Area(mm2)
AUUQ36LH1
AUUQ42LH1
AUUQ48LH1
3
2.5
mm
When the connection line between the indoor unit and
outdooor unit is over 40m, connect the telecommunication
line and power line separately.
If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.
u Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power wire
When none are available, follow the instructions below.
• Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
• When connecting wiring which is the same thickness, do as shown in the figure below.
• For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal block.
• Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small head
will strip the head and make proper tighterning impossible.
• Over-tightening the terminal screws may break them.
Installation Manual 9
Wiring Connection
Connecting the cable to Outdoor Unit
• Remove the side panel for wiring connection.
• Use the cord clamp to fix the cord.
• Earthing work
- Connect the cable of diameter more to the earthing terminal provided in the control
box and do earthing.
Connecting cable terminal
Power cord terminal
Cord clamp
* Make sure the rubber
bushes are properly used
in knock-out holes after
connecting main power.
CAUTION:
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
CAUTION:
• The Power cord connected to the unit should be selected according to the following
specifications.
10 Air Conditioner
Wiring Connection
Connecting Pipes
Preparation of Piping
Main cause of gas leakage is defect in flaring
work. Carry out correct flaring work in the following procedure.
Copper
tube
Slanted Uneven Rough
90
Cut the pipes and the cable.
• Use the accessory piping kit or the pipes
purchased locally.
• Measure the distance between the indoor
and the outdoor unit.
• Cut the pipes a little longer than measured
distance.
• Cut the cable 1.5m longer than the pipe
length.
Pipe
Reamer
Point down
Burrs removal
• Completely remove all burrs from the cut
cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in order to
avoid to let burrs drop in the tubing.
Flare nut
Copper tube
Putting nut on
• Remove flare nuts attached to indoor and
outdoor units, than put them on pipe/tube
having completed burr removal.
(Not possible to put them on after flaring work)
Handle
Flaring work
• Carry out flaring work using dedicated flaring tool for R-410A as shown below.
Bar
Bar
"A"
Yoke
Cone
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
"A"
mm
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8
1.9~2.1
Copper pipe
Clamp handle
Red arrow mark
Smooth all round
Inside is shining without scratches
Firmly hold copper tube in a bar(or die) as
indicated dimension in the table above.
= Improper flaring =
Check
• Compare the flared work with figure below.
• If flare is noted to be defective, cut off the
flared section and do flaring work again.
Even length
all round
Inclined Surface Cracked Uneven
damaged
thickness
Installation Manual 11
Wiring Connection
Connecting the pipes to the Outdoor unit
• Align the center of the piping and sufficiently
tighten the flare nut by hand.
• Finally, tighten the flare nut with torque wrench
until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
Outside diameter
mm
inch
Ø6.35
1/4
Ø9.52
3/8
Ø12.7
1/2
Ø15.88
5/8
Ø19.05
3/4
Torque
N.m
16±2
38±4
55±6
75±7
110±10
Torque
wrench
Contin
-uous
h When tighten the pipe, hold the haxagonal
body.
Preventing foreign objects from entering
• Plug the pipe through-holes with putty or insulation material(procured locally)to stop up all gaps.
CAUTION:
Insects or small animals entering the
outdoor unit may cause a short circuit
in the electrical box.
Drain hose
Connecting wire
Gas side piping
Liquid side piping
12 Air Conditioner
opening around
the pipings with
gum type sealer.
Wiring Connection
Forming the piping
Form the piping by wrapping the
connecting portion of the indoor
unit with insulation material and
secure it with two kinds of vinyl
tape.
• If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the ground. Secure the drain
hose appropriately.
Seal a small
opening around
the pipings with
gum type sealant.
sealer.
Plastic
band
Taping
Drain hose
Pipings
Plastic
band
In cases where the outdoor unit is
installed below the indoor unit perform the following.
Connecting
cable
Power supply
cord
1. Tape the piping, drain hose and connecting
cable from down to up.
2. Secure the tapped piping along the exterior wall using saddle or equivalent.
• Trap is required to prevent water from entering
into electrical parts.
In cases where the outdoor unit is
installed above the indoor unit perform the following.
Seal a small opening
around the pipings
with gum type sealant.
sealer.
1. Tape the piping and connecting cable from
down to up.
2. Secure the taped piping along the exterior
wall. Form a trap to prevent water entering
the room.
3. Fix the piping onto the wall by saddle or
equivalent.
Trap
Seal a small opening
aroundTrap
the pipings
with gum type sealer.
Trap
Installation Manual 13
Leakage test and Evacuation
Leakage test and Evacuation
Air and moisture remaining in the refrigerant system have undesirable effects as indicated below.
1. Pressure in the system rises.
2. Operating current rises.
3. Cooling(or heating) efficiency drops.
4. Moisture in the refrigerant circuit may freeze and block capillary tubing.
5. Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight, and vacuumed to remove incondensible gas and moisture in the system.
Preparation
• Check that each tube(both liquid and gas side tubes) between the indoor and outdoor units have been
properly connected and all wiring for the test run has been completed. Remove the service valve caps
from both the gas and the liquid side on the outdoor unit. Check that both the liquid and the gas side service valves on the outdoor unit are kept closed at this stage.
Leakage test
• Connect the manifold valve(with pressure gauges)
and dry nitrogen gas cylinder to this service port
with charge hoses.
CAUTION: Be sure to use a manifold valve for leakage test.
If it is not available, use a stop valve for
this purpose. The "Hi" knob of the manifold valve must always be kept close.
2. After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening
the charge hose connector at the nitrogen
cylinder. When the system pressure is
reduced to normal, disconnect the hose from
the cylinder.
Indoor unit
• Pressurize the system to no more than 3.0
Mpa with dry nitrogen gas and close the cylinder valve when the gauge reading reached 3.0
MPa Next, test for leaks with liquid soap.
CAUTION: To avoid nitrogen entering the refrigerant system in a liquid
state, the top of the cylinder must be higher than its bottom when you pressurize the
system. Usually, the cylinder is used in a
vertical standing position.
1. Do a leakage test of all joints of the
tubing(both Indoor unit and outdoor unit) and
both gas and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off
the soap with a clean cloth.
14 Air Conditioner
Outdoor unit
Manifold valve
Lo
Hi
Pressure
gauge
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
Leakage test and Evacuation
Evacuation
1. Connect the charge hose end described in the preceding steps to the vacuum pump to evacuate the
tubing and indoor unit.
Confirm the "Lo and Hi" knob of the manifold valve
is open. Then, run the vacuum pump.
The operation time for evacuation varies with tubing length and capacity of the pump. The following
table shows the time required for evacuation.
Indoor unit
Outdoor unit
Required time for evacuation when 30 gal/h
vacuum pump is used
If tubing length is longer
If tubing length is less
than 10 m(33 ft)
than 10 m(33 ft)
30 min. or more
60 min. or more
0.07 kPa or less
2. When the desired vacuum is reached, close the "Lo
and Hi" knob of the manifold valve and stop the
vacuum pump.
Manifold valve
Finishing the job
1. With a service valve wrench, turn the valve stem of
liquid side valve counter-clockwise to fully open the
valve.
2. Turn the valve stem of gas side valve counterclockwise to fully open the valve.
3. Loosen the charge hose connected to the gas side
service port slightly to release the pressure, then
remove the hose.
4. Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut securely
with an adjustable wrench. This process is very
important to prevent leakage from the system.
5. Replace the valve caps at both gas and liquid side
service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
Lo
Pressure
gauge
Hi
Open
Open
Vacuum pump
Installation Manual 15
Test running
Test running
1. PRECAUTIONS IN TEST RUNNING
• The initial power supply must provide at least 90% of the rated voltage.
Otherwise, the air conditioner should not be operated.
CAUTION
① For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out firstly, it leads to the
trouble of compressor. Then attention must be paid.
② Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
• The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
• To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
• After completing work, be sure to measure and record trial run properties, and store measured
data, etc.
• Measuring items are room temperature, outside temperature, suction temperature, blow out temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and noise,
operating pressure, piping temperature, compressive pressure.
• As to the structure and appearance, check following items.
□Is the circulation of air adequate?
□Is the draining smooth?
□Is the heat insulation complete
(refrigerant and drain piping)?
□Is there any leakage of refrigerant?
□Is the remote controller switch operated?
□Is there any faulty wiring?
□Are not terminal screws loosened?
M4......118N.cm{12kgf.cm} M5......196N.cm{20kgf.cm}
M6......245N.cm{25kgf.cm} M8......588N.cm{60kgf.cm}
2. Connection of power supply
1. Connect the power supply cord to the independent power supply.
• Circuit breaker is required.
2. Operate the unit for fifteen minutes or more.
3. Evaluation of the performance
1. Measure the temperature of the intake and discharge air.
2. Ensure the difference between the intake temperature and the discharge one is
more than 8°C (Cooling) or reversely (Heating).
16 Air Conditioner
Test running
CAUTION: After the confirmation of the above conditions, prepare the wiring
as follows:
1) Never fail to have an individual power specialized for the air conditioner.
As for the method of wiring, be guided by the circuit diagram pasted on
the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are
liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they
are all tightly fastened. (If they are loose, it could give rise to burn-out of
the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent
of the rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources
specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of fuse
breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
Installation Manual 17
Function
Function
Forced Cooling Operation
• Adding the refrigerant in winter.
Setting Procedure
1) Set the Dip Switch as follow after shutting the power source down.
2) Reset the power.
3) Red LED and Green LED of PCB lights during work.
(The indoor unit is operated by force.)
4) If operation is done, Red LED will be turned off.
If operation is not done normally, Red LED will blink.
5) Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine).
Then close the gas valve after Green LED on.
WARNING:
• When the green LED of PCB is on, compressor is going to be off because of low
pressure.
• You should return the Dip Switch to operate normally after finishing the operation.
• Improper Pump down will lead to product turn off along with LED (green &red) off
with in 20 minutes from the initial start.
Pump Down Dip S/W Setting
Power on
(Red LED On, Green LED Off)
Comp on
(Red LED On, Green LED On)
Pump Down Start
(Red LED On, Green LED Off)
Liquid Valve Closed
Pump Down Complete
(Red LED Off, Green LED On)
Gas Valve Closed
Power off
(Red LED Off, Green LED On)
18 Air Conditioner
Self-diagnosis Function
Self-diagnosis Function
Error Indicator (Outdoor)
2 Times
2 Times
Outdoor Error
Ex) Error 21 (DC Peack)
2 Times
LED01G
(RED)
1 Sec.
1 Sec.
1 Time
1 Sec.
1 Time
1 Time
LED02G
(GREEN)
2 Sec.
Error Code
2 Sec.
Description
LED 1
(Red)
LED 2
(Green)
Indoor
status
21
DC Peak(IPM Fault)
2times ◑
1time ◑
OFF
22
Max. CT(CT2)
2times ◑
2times ◑
OFF
23
DC Link Low Volt.
2times ◑
3times ◑
OFF
24
Pressure switch/Heater Sink.
2times ◑
4times ◑
OFF
26
DC Comp Position Error
2times ◑
6times ◑
OFF
27
PFC Fault Error
2times ◑
7times ◑
OFF
29
Comp Over Current
2times ◑
9times ◑
OFF
32
D-Pipe High(Inv.)
3times ◑
2times ◑
OFF
40
CT Sensor(Open/Short)
4times ◑
0
OFF
41
Inv. D-Pipe Th Error(Open/Short)
4times ◑
1time ◑
OFF
43
High Pressure Sensor(Open/Short)
4times ◑
3times ◑
OFF
44
Outdoor air Th Error(Open/Short)
4times ◑
4times ◑
OFF
45
Cond. Middle Pipe Th Error(Open/Short)
4times ◑
5times ◑
OFF
51
Capacity over
5times ◑
1times ◑
OFF
53
Communication Error(Indoor ÷ Outdoor)
5times ◑
3times ◑
OFF
60
EEPROM Error(Outdoor)
6times ◑
0
OFF
61
Cond. Middle Pipe High
6times ◑
1times ◑
OFF
62
Heatsink Error(High)
6times ◑
2times ◑
OFF
65
Heatsink Th Error(Open/Short)
6times ◑
5times ◑
OFF
67
BLDC motor fan lock(Outdoor)
6times ◑
7times ◑
OFF
If abnormal voltage is supplied, the protection circuits will turn off the product in order to prevent
the component damage. The product will automatically restart after 3 minutes.
Installation Manual 19
Installation Guide at the Seaside
Installation Guide at the Seaside
CAUTION:
1. Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are produced.
2. Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion
on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient performance.
3. If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise it
needs additional anticorrosion treatment on the heat exchanger.
Selecting the location(Outdoor Unit)
1) If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
Sea wind
Sea wind
2) In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
Windbreak
• It should be strong enough like concrete to prevent
the sea wind from the sea.
• The height and width should be more than 150% of
the outdoor unit.
Sea wind
• It should be keep more than 70 cm of space
between outdoor unit and the windbreak for easy
air flow.
3) Select a well-drained place.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water
20 Air Conditioner

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement