LG ABUW36GRLT0 Installation guide

Add to my manuals
27 Pages

advertisement

LG ABUW36GRLT0 Installation guide | Manualzz
ENGLISH
FRANÇAIS
INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
P/NO : MFL68061201
www.lg.com
2
TIPS FOR SAVING ENERGY
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
• Do not cool excessively indoors. This may be harmful to your health and may consume more electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them labeled on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
3
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
! WARNING
It can result in serious injury or death when the directions are ignored
! CAUTION
It can result in minor injury or product damage when the directions are ignored
! WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation work must be performed in accordance with the National Electric Code by qualified and authorized personnel only.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Always perform grounding. Otherwise, it may cause electrical shock.
• Don’t use a damaged power cable. Otherwise, it may cause a fire or electrical shock.
• For installation of the product, always contact the service center or a professional installation
agency. Otherwise, it may cause a fire, electrical shock, explosion or injury.
• Securely attach the electrical part cover to the indoor unit and the service panel to the outdoor
unit. If the electrical part cover of the indoor unit and the service panel of the outdoor unit are
not attached securely, it could result in a fire or electric shock due to dust, water, etc.
• Always install an earth leakage circuit breaker and a dedicated switching board. No installation
may cause a fire and electrical shock.
• Do not keep or use flammable gases or combustibles near the air conditioner. Otherwise, it
may cause a fire or the failure of product.
• Ensure that an installation frame of the outdoor unit is not damaged due to use for a long
time. It may cause injury or an accident.
• Do not disassemble or repair the product randomly. It will cause a fire or electrical shock.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air or Oxygen and do not use Flammable gases. Otherwise, it may cause fire or explosion. There is the risk of death, injury, fire or explosion.
• Do not install the product at a place that there is concern of falling down. Otherwise, it may
result in personal injury.
• Use caution when unpacking and installing. Sharp edges may cause injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box cover are removed or opened. Otherwise, it may cause fire, electric shock, explosion
or death.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
Operation
• Do not share the outlet with other appliances. It will cause an electric shock or a fire due to
heat generation.
• Do not use the damaged power cable. Otherwise, it may cause a fire or electrical shock.
• Do not modify or extend the power cable randomly. Otherwise, it may cause a fire or electrical shock.
• Take care so that the power cable may not be pulled during operation. Otherwise, it may
cause a fire or electrical shock.
• Turn off the unit if strange sounds, smell, or smoke comes from it. Otherwise, it may cause
electrical shock or a fire.
• Keep the flames away. Otherwise, it may cause a fire.
• Do not use the power cable near the heating tools. Otherwise, it may cause a fire and electrical shock.
• Do not open the suction inlet of the indoor/outdoor unit during operation. Otherwise, it may
electrical shock and failure.
• Do not allow water to run into electrical parts. Otherwise, it may cause the failure of machine
or electrical shock.
• Do not touch the power cable with wet hands. It may cause electric shock and damage.
• Never touch the metal parts of the unit when removing the filter. They are sharp and may
cause injury.
• Do not step on the indoor/outdoor unit and do not put anything on it. It may cause an injury
through dropping of the unit or falling down.
• Do not place a heavy object on the power cable. Otherwise, it may cause a fire or electrical
shock.
• When the product is submerged into water, always contact the service center. Otherwise, it
may cause a fire or electrical shock.
• Take care so that children may not step on the outdoor unit. Otherwise, children may be seriously injured due to falling down.
IMPORTANT SAFETY INSTRUCTIONS
• Install the drain hose to ensure that drain can be securely done. Otherwise, it may cause
water leakage.
• Install the product so that the noise or hot wind from the outdoor unit may not cause any
damage to the neighbors. Otherwise, it may cause dispute with the neighbors.
• Always inspect gas leakage after the installation and repair of product. Otherwise, it may
cause the failure of product.
• Keep level parallel in installing the product. Otherwise, it may cause vibration or water leakage.
Operation
• Avoid excessive cooling and perform ventilation sometimes. Otherwise, it may do harm to
your health.
• Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent. The appearance of
the air conditioner may deteriorate, change color, or develop surface flaws.
• Do not use an appliance for special purposes such as preserving animals vegetables, precision machine, or art articles. Otherwise, it may damage your properties.
• Do not place obstacles around the flow inlet or outlet. Otherwise, it may cause the failure of
appliance or an accident.
ENGLISH
! CAUTION
Installation
5
6
TABLE OF CONTENTS
ENGLISH
TABLE OF CONTENTS
2 TIPS FOR SAVING ENER-
19 LEAKAGE TEST AND
GY
3 IMPORTANT SAFETY
INSTRUCTIONS
7 INSTALLATION OF OUTDOOR UNIT
10
Night Silent Operation setting
11 WIRING CONNECTION
11
Electrical Wiring
12
Connecting Cables between Indoor Unit
and Outdoor Unit
14
Connecting the cable to Outdoor Unit
15 CONNECTING PIPES
15
Preparation of Piping
16
Connecting the pipes to the Outdoor
unit
18
Forming the Piping
EVACUATION
19
Preparation
19
Leakage test
20
Evacuation
21 TEST RUNNING
23 FUNCTION
23
Forced Cooling Operation
24 SELF-DIAGNOSIS FUNCTION
24
Error Indicator (Outdoor)
26 INSTALLATION GUIDE AT
THE SEASIDE
INSTALLATION OF OUTDOOR UNIT
7
ENGLISH
INSTALLATION OF OUTDOOR UNIT
Installation Places
- If an awning is built over the unit to prevent direct sunlight or rain exposure, make sure that
heat radiation from the condenser is not restricted.
- Ensure that the spaces indicated by arrows around front, back and side of the unit.
- Do not place animals and plants in the path of the warm air.
- Take the air conditioner weight into account and select a place where noise and vibration are
minimum.
- Select a place so that the warm air and noise from the air conditioner do not disturb neighbors.
Unit : mm
Su
nro
of
More than
300 mm
More than
300
mm
300mm
Fe
ob nce o
sta r
cle
s
More than 600 mm
More than 700 mm
Piping length and the elevation
Free Joint Single Outdoor
Standard
Max.
Standard
Max.
Additional
Refrigerant
(g/m)
Ø 12.7(1/2) Ø 6.35(1/4)
Ø 12.7(1/2) Ø 6.35(1/4)
7.5
7.5
30
50
5
5
15
30
20
20
24 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
28 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
34 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
46 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
54 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
Pipe Size
MODEL
Gas
AUUQ18GHT0
AUUW18GHT0
AUUQ24GHT0
AUUW24GHT0
AUUQ30GHT0
AUUW30GHT0
AUUQ36GHT0
AUUW36GHT0
AUUQ48GHT0
AUUW48GHT0
AUUQ54GHT0
AUUW54GHT0
AUUQ60GHT0
AUUW60GHT0
Length A (m)
Elevation B (m)
CAPACITY
18 kBtu/h
18 kBtu/h
Liquid
8
INSTALLATION OF OUTDOOR UNIT
ENGLISH
Ceiling Cassette
Pipe Size
MODEL
CAPACITY
ATUQ18GPLT0
ATUW18GPLT0
ATUQ24GNLT0
ATUW24GNLT0
ATUQ30GNLT0
ATUW30GNLT0
ATUQ36GMLT0
ATUW36GMLT0
ATUQ48GMLT0
ATUW48GMLT0
18 kBtu/h
18 kBtu/h
Gas
Liquid
Length A (m)
Elevation B (m)
Additional
Refrigerant (g/m)
Standard
Max.
Standard
Max.
Ø 12.7(1/2) Ø 6.35(1/4)
Ø 12.7(1/2) Ø 6.35(1/4)
7.5
7.5
30
50
5
5
15
30
20
20
24 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
28 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
34 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
46 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
ATUQ54GMLT0
ATUW54GMLT0
54 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
ATUQ60GMLT0
ATUW60GMLT0
7.5
50
5
30
40
Ceiling Suspended Air conditioner
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant (g/m)
MODEL
CAPACITY
Standard
Max.
Standard
Max.
AVUQ18GJLT0
AVUW18GJLT0
18 kBtu/h
18 kBtu/h
Ø 12.7(1/2) Ø 6.35(1/4)
Ø 12.7(1/2) Ø 6.35(1/4)
7.5
7.5
30
50
5
5
15
30
20
20
AVUQ24GKLT0
AVUW24GKLT0
24 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
AVUQ30GKLT0
AVUW30GKLT0
28 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
AVUQ36GLLT0
AVUW36GLLT0
34 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
AVUQ48GLLT0
AVUW48GLLT0
46 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
AVUQ54GLLT0
AVUW54GLLT0
AVUQ60GLLT0
AVUW60GLLT0
54 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
Gas
Liquid
INSTALLATION OF OUTDOOR UNIT
9
ENGLISH
Ceiling Concealed Duct Air conditioner
Pipe Size
Length A (m)
Elevation B (m)
Additional
Refrigerant (g/m)
MODEL
CAPACITY
Standard
Max.
Standard
Max.
ABUQ18GHLT0
ABUW18GHLT0
18 kBtu/h
18 kBtu/h
Ø 12.7(1/2) Ø 6.35(1/4)
Ø 12.7(1/2) Ø 6.35(1/4)
7.5
7.5
30
50
5
5
15
30
20
20
ABUQ24GGLT0
ABUW24GGLT0
24 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
ABUQ30GGLT0
ABUW30GGLT0
28 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
ABUQ36GRLT0
ABUW36GRLT0
34 kBtu/h Ø 15.88(5/8) Ø 9.52(3/8)
7.5
50
5
30
40
46 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
54 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
53 kBtu/h Ø 19.05(3/4) Ø 9.52(3/8)
7.5
50
5
30
40
Gas
ABUQ48GRLT0
ABUW48GRLT0
ABUQ48LRLT0
ABUW48LRLT0
ABUQ54GRLT0
ABUW54GRLT0
ABUQ60GRLT0
ABUW60GRLT0
ABUQ54LRLT0
ABUW54LRLT0
ABUQ53GRLT0
Liquid
If installed tube is shorter than 7.5 m, additional charging is not necessary.
Additional Refrigerant = (A -7.5) x Additional refrigerant (g)
Indoor unit
Outdoor unit
A
B
A
Outdoor unit
Indoor unit
B
! CAUTION
• Capacity is based on standard length and maximum allowance length is on the basis of
reliability.
• Improper refrigerant charge may result in abnormal cycle.
10 INSTALLATION OF OUTDOOR UNIT
- Open the Side panel or Top Cover of outdoor unit.
- Set the SW01N.
6
AUUQ18GHT0/AUUW18GHT0
(ATUQ18GPLT0/ATUW18GPLT0)
(AVUQ18GJLT0/AVUW18GJLT0)
(ABUQ18GHLT0/ABUW18GHLT0)
AUUQ24GHT0/AUUW24GHT0
(ATUQ24GNLT0/ATUW24GNLT0)
(AVUQ24GKLT0/AVUW24GKLT0)
(ABUQ24GGLT0/ABUW24GGLT0)
AUUQ30GHT0/AUUW30GHT0
(ATUQ30GNLT0/ATUW30GNLT0)
(AVUQ30GKLT0/AVUW30GKLT0)
(ABUQ30GGLT0/ABUW30GGLT0)
AUUQ36GHT0/AUUW36GHT0
(ATUQ36GMLT0/ATUW36GMLT0)
(AVUQ36GLLT0/AVUW36GLLT0)
(ABUQ36GRLT0/ABUW36GRLT0)
AUUQ48GHT0/AUUW48GHT0 ABUW48LRLT0/ABUQ48LRLT0
(ATUQ48GMLT0/ATUW48GMLT0) ABUW54LRLT0/ABUQ54LRLT0
(AVUQ48GLLT0/AVUW48GLLT0)
(ABUQ48GRLT0/ABUW48GRLT0)
AUUQ54GHT0/AUUW54GHT0
(ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
SW_DIP
SW01N
SW01N
- Close the Side panel or Top Cover.
DIP_SW
ENGLISH
Night Silent Operation setting
6
AUUQ18GHT0/AUUW18GHT0
AUUQ30GHT0/AUUW30GHT0
AUUQ48GHT0/AUUW48GHT0
(ATUQ18GPLT0/ATUW18GPLT0) (ATUQ30GNLT0/ATUW30GNLT0) (ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ18GJLT0/AVUW18GJLT0) (AVUQ30GKLT0/AVUW30GKLT0) (AVUQ48GLLT0/AVUW48GLLT0)
(AUNQ18GHLT0/ABUW18GHLT0) (ABUQ30GGLT0/ABUW30GGLT0) (ABUQ48GRLT0/ABUW48GRLT0)
AUUQ24GHT0/AUUW24GHT0
AUUQ36GHT0/AUUW36GHT0
AUUQ54GHT0/AUUW54GHT0
(ATUQ24GNLT0/ATUW24GNLT0) (ATUQ36GMLT0/ATUW36GMLT0) (ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ24GKLT0/AVUW24GKLT0) (AVUQ36GLLT0/AVUW36GLLT0) (AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ24GGLT0/ABUW24GGLT0) (ABUQ36GRLT0/ABUW36GRLT0) (ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
ABUW48LRLT0/ABUQ48LRLT0
ABUW54LRLT0/ABUQ54LRLT0
WIRING CONNECTION
ENGLISH
WIRING CONNECTION
Electrical Wiring
Perform the electrical wiring work according
to the electrical wiring connection.
- All wiring must comply with local requirements.
- Select a power source that is capable of supplying the current required by the air conditioner.
- Use a recognized ELCB(Electric Leakage
Circuit Breaker) between the power source
and the unit. A disconnection device to adequately disconnect all supply lines must be
fitted.
- Model of circuit breaker recommended by
authorized personnel only
Model
AUUQ18GHT0/AUUW18GHT0
(ATUQ18GPLT0/ATUW18GPLT0)
(AVUQ18GJLT0/AVUW18GJLT0)
(ABUQ18GHLT0/ABUW18GHLT0)
AUUQ24GHT0/AUUW24GHT0
(ATUQ24GNLT0/ATUW24GNLT0)
(AVUQ24GKLT0/AVUW24GKLT0)
(ABUQ24GGLT0/ABUW24GGLT0)
AUUQ30GHT0/AUUW30GHT0
(ATUQ30GNLT0/ATUW30GNLT0)
(AVUQ30GKLT0/AVUW30GKLT0)
(ABUQ30GGLT0/ABUW30GGLT0)
AUUQ36GHT0/AUUW36GHT0
(ATUQ36GMLT0/ATUW36GMLT0)
(AVUQ36GLLT0/AVUW36GLLT0)
(ABUQ36GRLT0/ABUW36GRLT0)
AUUQ48GHT0/AUUW48GHT0
(ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ48GLLT0/AVUW48GLLT0)
(ABUQ48GRLT0/ABUW48GRLT0)
AUUQ54GHT0/AUUW54GHT0
(ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
ABUQ48LRLT0/ABUW48LRLT0/
ABUQ54LRLT0/ABUW54LRLT0
11
ELCB
Main
power source
Switch box
Outdoor
Indoor
Phase(ø)
ELCB
1
25 A
1
25 A
1
30 A
1
30 A
1
40 A
1
40 A
1
40 A
1
40 A
3
20 A
12 WIRING CONNECTION
ENGLISH
Connecting Cables between Indoor Unit and Outdoor Unit
Outdoor
unit
Indoor
unit
3
2
1
3
2
1
! CAUTION
The power cable connected to the outdoor unit should be complied with IEC 60245 or HD 22.4 S4
(This equipment shall be provided with a cable set complying with the national regulation.
10±3 mm
±5
GN
/Y
L
20
m
m
For the 1-Phase
10±3 mm
mm
±5
35
GN
/Y
Model
Phase(Ø)
Area(mm2)
AUUQ18GHT0/AUUW18GHT0(ATUQ18GPLT0/ATUW18GPLT0)
(AVUQ18GJLT0/AVUW18GJLT0)(ABUQ18GHLT0/ABUW18GHLT0)
AUUQ24GHT0/AUUW24GHT0(ATUQ24GNLT0/ATUW24GNLT0)
(AVUQ24GKLT0/AVUW24GKLT0)(ABUQ24GGLT0/ABUW24GGLT0)
AUUQ30GHT0/AUUW30GHT0(ATUQ30GNLT0/ATUW30GNLT0)
(AVUQ30GKLT0/AVUW30GKLT0)(ABUQ30GGLT0/ABUW30GGLT0)
AUUQ36GHT0/AUUW36GHT0(ATUQ36GMLT0/ATUW36GMLT0)
(AVUQ36GLLT0/AVUW36GLLT0)(ABUQ36GRLT0/ABUW36GRLT0)
1
2.5
AUUQ48GHT0/AUUW48GHT0(ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ48GLLT0/AVUW48GLLT0)(ABUQ48GRLT0/ABUW48GRLT0)
AUUQ54GHT0/AUUW54GHT0(ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ54GLLT0/AVUW54GLLT0)(ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
1
6
ABUQ48LRLT0/ABUW48LRLT0/ABUQ54LRLT0/ABUW54LRLT0
3
2.5
mm
35
L
20
mm
For the 3-Phase
The connecting cable connected to the outdoor unit should be complied with IEC 60245 or
HD 22.4 S4 (This equipment shall be provided with a cable set complying with the national
regulation.)
10±3 mm
±5
mm
NORMAL
CROSS-SECTIONAL
AREA 0.75 mm2
35
GN
When the connection line between the indoor unit and outdooor unit is over 40 m, connect the telecommunication line
and power line separately.
/Y
L
20
m
m
If the supply cable is damaged, it must be replaced by a special cable or assembly availible
from the manufacturer of its service agent.
WIRING CONNECTION 13
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power wire
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
Connect same thickness
wiring to both sides.
It is forbidden to connect
two to one side.
It is forbidden to
connect wiring of
different thicknesses.
- For wiring, use the designated power wire and connect firmly, then secure to prevent outside
pressure being exerted on the terminal block.
- Use an appropriate screwdriver for tightening the terinal screws. A screwdriver with a small
head will strip the head and make proper tighterning impossible.
- Over-tightening the terminal screws may break them.
ENGLISH
Precautions when laying power wiring
14 WIRING CONNECTION
ENGLISH
Connecting the cable to Outdoor Unit
Remove the side panel for wiring connection.
Use the cord clamp to fix the cable.
Earthing work
- Connect the cable of diameter more to the earthing terminal provided in the control box and do
earthing.
Connecting cable terminal
Power cable terminal
Cord clamp
Cord clamp
* Make sure the rubber bushes are properly
used in knock-out holes after connecting
main power.
! CAUTION
• The circuit diagram is not subject to change without notice.
• Be sure to connect wires according to the wiring diagram.
• Connect the wires firmly, so that not to be pulled out easily.
• Connect the wires according to color codes by referring the wiring diagram.
• The Power cable connected to the unit should be selected according to the following
specifications.
CONNECTING PIPES 15
ENGLISH
CONNECTING PIPES
Preparation of Piping
Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following
procedure.
Cut the pipes and the cable
- Use the piping kit accessory or the pipes purchased locally.
- Measure the distance between the indoor
and the outdoor unit.
- Cut the pipes a little longer than measured
distance.
- Cut the cable 1.5 m longer than the pipe
length.
Copper
tube
Pipe
Burrs removal
- Completely remove all burrs from the cut
cross section of pipe/tube.
- Put the end of the copper tube/pipe in a
downward direction as you remove burrs in
order to avoid dropping burrs into the tubing.
Reamer
Point down
Putting nut on
- Remove flare nuts attached to indoor and
outdoor unit, then put them on pipe/tube
having completed burr removal.
(not possible to put them on after flaring
work)
Flaring work
- Carry out flaring work using flaring tool as
shown below.
Outside diameter
mm
inch
Ø 6.35
1/4
Ø 9.52
3/8
Ø 12.7
1/2
Ø 15.88
5/8
Ø 19.05
3/4
A
mm
1.1~1.3
1.5~1.7
1.6~1.8
1.6~1.8
1.9~2.1
Firmly hold copper pipe in a bar in the
dimension shown in the table below.
Slanted Uneven Rough
90
Flare nut
Copper tube
Handle
Bar
"A"
Bar
Yoke
Cone
Copper pipe
Clamp handle
Red arrow mark
Smooth all round
Inside is shining without scratches.
Check
- Compare the flared work with figure below.
- If flare is noted to be defective, cut off the
flared section and do flaring work again.
= Improper flaring =
Even length
all round
Inclined Surface Cracked Uneven
damaged
thickness
16 CONNECTING PIPES
ENGLISH
Connecting the pipes to the Outdoor unit
Align the center of the piping and sufficiently
tighten the flare nut by hand.
Finally, tighten the flare nut with torque
wrench until the wrench clicks.
- When tightening the flare nut with torque
wrench, ensure the direction for tightening
follows the arrow on the wrench.
Outside diameter
mm
inch
Ø 6.35
1/4
Ø 9.52
3/8
Ø 12.7
1/2
Ø 15.88
5/8
Ø 19.05
3/4
Continuous
Torque
wrench
Torque
N·m
16±2
38±4
55±6
75±7
110±10
h When tighten the pipe, hold the haxagonal body.
<Figure 1>
Backward
Sideways
Forward
Downward
CONNECTING PIPES 17
Knock-out
When connecting in a downward direction,
knock out the knock-out hole of the base pan.
(refer to figure 2)
Base pan
<Figure 3>
Liquid side piping
Gas side piping
Connecting wire
Drain hose
Connection pipe
Putty or insulating material
(produced locally)
Preventing foreign objects from entering
(Figure3)
- Plug the pipe through-holes with putty or
insulation material(procured locally)to stop up
all gaps,as shown in the figure 3.
! CAUTION
Insects or small animals entering the outdoor unit may cause a short circuit in the
electrical box.
ENGLISH
<Figure 2>
18 CONNECTING PIPES
ENGLISH
Forming the Piping
Form the piping by wrapping the connecting
portion of the indoor unit with insulation material and secure it with two kinds of vinyl tape.
- If you want to connect an additional drain
hose, the end of the drain outlet should be
routed above the ground. Secure the drain
hose appropriately.
In cases where the outdoor unit is installed
below the indoor unit perform the following.
1 Tape the piping, drain hose and connecting
cable from down to up.
2 Secure the tapped piping along the exterior
wall using saddle or equivalent.
Seal a small
opening around
the pipings with
gum type sealer.
sealant.
In cases where the Outdoor unit is installed
above the Indoor unit perform the following.
1 Tape the piping and connecting cable from
down to up.
2 Secure the taped piping along the exterior
wall. Form a trap to prevent water entering
the room.
3 Fix the piping onto the wall by saddle or
equivalent.
Seal a small opening
around the pipings
with gum type sealer.
sealant.
Trap
Trap
Taping
Drain hose
Plastic
band
Pipings
Connecting
cable
Power supply
cable
• Trap is required to prevent water from entering
into electrical parts.
Seal a small opening
around the pipings
with gum type sealer.
Trap
LEAKAGE TEST AND EVACUATION 19
ENGLISH
LEAKAGE TEST AND EVACUATION
Air and moisture remaining in the refrigerant
system have undesirable effects as indicated
below.
- Pressure in the system rises.
- Operating current rises.
- Cooling(or heating) efficiency drops.
- Moisture in the refrigerant circuit may freeze
and block capillary tubing.
- Water may lead to corrosion of parts in the
refrigeration system.
Therefore, the indoor/outdoor unit and connecting tube must be checked for leak tight,
and vacuumed to remove incondensible gas
and moisture in the system.
Preparation
Check that each tube(both liquid and gas side
tubes) between the indoor and outdoor units
have been properly connected and all wiring
for the test run has been completed. Remove
the service valve caps from both the gas and
the liquid side on the outdoor unit. Check that
both the liquid and the gas side service valves
on the outdoor unit are kept closed at this
stage.
! CAUTION
To avoid nitrogen entering the refrigerant
system in a liquid state, the top of the
cylinder must be higher than its bottom
when you pressurize the system. Usually,
the cylinder is used in a vertical standing
position.
- Do a leakage test of all joints of the
tubing(both indoor and outdoor) and both gas
and liquid side service valves.
Bubbles indicate a leak. Be sure to wipe off
the soap with a clean cloth.
- After the system is found to be free of leaks,
relieve the nitrogen pressure by loosening
the charge hose connector at the nitrogen
cylinder. When the system pressure is
reduced to normal, disconnect the hose from
the cylinder.
Indoor unit
Outdoor unit
Leakage test
Connect the manifold valve(with pressure
gauges) and dry nitrogen gas cylinder to this
service port with charge hoses.
Manifold valve
! CAUTION
Be sure to use a manifold valve for leakage
test. If it is not available, use a stop valve for
this purpose. The "Hi" knob of the manifold
valve must always be kept close.
- Pressurize the system to no more than
3.8 Mpa with dry nitrogen gas and close
the cylinder valve when the gauge reading reached 3.8 MPa Next, test for leaks
with liquid soap.
Lo
Hi
Pressure
gauge
Charge hose
Nitrogen gas
cylinder(in vertical
standing position)
20 LEAKAGE TEST AND EVACUATION
ENGLISH
Evacuation
- Connect the charge hose end described in
the preceding steps to the vacuum pump to
evacuate the tubing and indoor unit.
Confirm the "Lo and Hi" knob of the manifold
valve is open. Then, run the vacuum pump.
The operation time for evacuation varies with
tubing length and capacity of the pump. The
following table shows the time required for
evacuation.
- Replace the valve caps at both gas and liquid
side service valves and fasten them tight.
This completes air purging with a vacuum pump.
The air conditioner is now ready to test run.
Indoor unit
Outdoor unit
Required time for evacuation when 30 gal/h
vacuum pump is used
If tubing length is
less than 10 m(33 ft)
If tubing length is
longer than 10 m(33
ft)
30 min. or more
60 min. or more
Gas pipe
0.07 kPa or less
- When the desired vacuum is reached, close
the "Lo and Hi" knob of the manifold valve
and stop the vacuum pump.
Manifold valve
Lo
Pressure
gauge
Hi
Finishing the Job
Open
- With a service valve wrench, turn the valve
stem of liquid side valve counter-clockwise to
fully open the valve.
- Turn the valve stem of gas side valve counterclockwise to fully open the valve.
- Loosen the charge hose connected to the gas
side service port slightly to release the pressure,
then remove the hose.
- Replace the flare nut and its bonnet on the gas
side service port and fasten the flare nut securely with an adjustable wrench. This process is
very important to prevent leakage from the system.
Vacuum pump
Open
TEST RUNNING 21
ENGLISH
TEST RUNNING
Precautions In Test Running
- The initial power supply must provide at least 90 % of the rated voltage.
Otherwise, the air conditioner should not be operated.
! CAUTION
For test run, carry out the cooling operation firstly even during heating season. If heating operation
is carried out firstly, it leads to the trouble of compressor. Then attention must be paid.
Carry out the test run more than 5 minutes without fail.
(Test run will be cancelled 18 minutes later automatically)
- The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time.
- To cancel the test run, press any button.
CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE
- After completing work, be sure to measure and record trial run properties, and store measured
data, etc.
- Measuring items are room temperature, outside temperature, suction temperature, blow out
temperature, wind velocity, wind volume, voltage, current, presence of abnormal vibration and
noise, operating pressure, piping temperature, compressive pressure.
- As to the structure and appearance, check following items.
□Is the circulation of air adequate?
□Is the draining smooth?
□Is the heat insulation complete
(refrigerant and drain piping)?
□Is there any leakage of refrigerant?
□Is the remote controller switch operated?
□Is there any faulty wiring?
□Are not terminal screws loosened?
M4......118 N·cm {12 kgf·cm}
M5......196 N·cm {20 kgf·cm}
M6......245 N·cm {25 kgf·cm}
M8......588 N·cm {60 kgf·cm}
Connection of power supply
• Connect the power supply cable to the independent power supply.
- Circuit breaker is required.
• Operate the unit for fifteen minutes or more.
Evaluation of the performance
- Measure the temperature of the intake and
discharge air.
- Ensure the difference between the intake
temperature and the discharge one is more
than 8 °C (Cooling) or reversely (Heating).
Thermometer
22 TEST RUNNING
ENGLISH
! CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1 Never fail to have an individual power specialized for the air conditioner. As for the
method of wiring, be guided by the circuit diagram pasted on the inside of control box
cover.
2 Provide a circuit breaker switch between power source and the unit.
3 The screw which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of transportation.
Check them and make sure that they are all tightly fastened. (If they are loose, it could
give rise to burn-out of the wires.)
4 Specification of power source
5 Confirm that electrical capacity is sufficient.
6 Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7 Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8 Never fail to equip a leakage breaker where it is wet or moist.
9 The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point there of fuse breaking, disturbance to the normal function of a overload protection device.
- Proper starting power is not given to the compressor.
FUNCTION 23
ENGLISH
FUNCTION
Forced Cooling Operation
Adding the refrigerant in winter.
Setting Procedure
- Set the Dip Switch as follow after shutting the power source down.
6
AUUQ18GHT0/AUUW18GHT0
AUUQ30GHT0/AUUW30GHT0
AUUQ48GHT0/AUUW48GHT0
(ATUQ18GPLT0/ATUW18GPLT0) (ATUQ30GNLT0/ATUW30GNLT0) (ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ18GJLT0/AVUW18GJLT0) (AVUQ30GKLT0/AVUW30GKLT0) (AVUQ48GLLT0/AVUW48GLLT0)
(ABUQ18GHLT0/ABUW18GHLT0) (ABUQ30GGLT0/ABUW30GGLT0) (ABUQ48GRLT0/ABUW48GRLT0)
AUUQ24GHT0/AUUW24GHT0
AUUQ36GHT0/AUUW36GHT0
AUUQ54GHT0/AUUW54GHT0
(ATUQ24GNLT0/ATUW24GNLT0) (ATUQ36GMLT0/ATUW36GMLT0) (ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ24GKLT0/AVUW24GKLT0) (AVUQ36GLLT0/AVUW36GLLT0) (AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ24GGLT0/ABUW24GGLT0) (ABUQ36GRLT0/ABUW36GRLT0) (ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
ABUW48LRLT0/ABUQ48LRLT0
ABUW54LRLT0/ABUQ54LRLT0
- Reset the power.
- Red LED and Green LED of PCB lights during work. (The indoor unit is operated by force.)
- If operation is done, Red LED will be turned off.
If operation is not done normally, Red LED will blink.
- Close the Liquid valve only after green LED turned off (7 minutes from the start of the machine).
Then close the gas valve after Green LED on.
! WARNING
• When the green LED of PCB is on, compressor is going to be off because of low
pressure.
• You should return the Dip Switch to operate normally after finishing the operation.
• Improper Pump down will lead to product
turn off along with LED (green &red) off
with in 20 minutes from the initial start.
Pump Down Dip S/W Setting
Power on
(Red LED On, Green LED Off)
Comp on
(Red LED On, Green LED On)
Pump Down Start
(Red LED On, Green LED Off)
Liquid Valve
Closed
Pump Down Complete
(Red LED Off, Green LED On)
Gas Valve
Closed
Power off
(Red LED Off, Green LED On)
24 SELF-DIAGNOSIS FUNCTION
ENGLISH
SELF-DIAGNOSIS FUNCTION
Error Indicator (Outdoor)
2 Times
2 Times
Outdoor Error
Ex) Error 21 (DC Peack)
2 Times
LED01G
(RED)
1 Sec.
1 Sec.
1 Time
1 Sec.
1 Time
1 Time
LED02G
(GREEN)
2 Sec.
2 Sec.
AUUQ18GHT0/AUUW18GHT0
AUUQ30GHT0/AUUW30GHT0
AUUQ48GHT0/AUUW48GHT0
(ATUQ18GPLT0/ATUW18GPLT0) (ATUQ30GNLT0/ATUW30GNLT0) (ATUQ48GMLT0/ATUW48GMLT0)
(AVUQ18GJLT0/AVUW18GJLT0) (AVUQ30GKLT0/AVUW30GKLT0) (AVUQ48GLLT0/AVUW48GLLT0)
(ABUQ18GHLT0/ABUW18GHLT0) (ABUQ30GGLT0/ABUW30GGLT0) (ABUQ48GRLT0/ABUW48GRLT0)
AUUQ24GHT0/AUUW24GHT0
AUUQ36GHT0/AUUW36GHT0
AUUQ54GHT0/AUUW54GHT0
(ATUQ24GNLT0/ATUW24GNLT0) (ATUQ36GMLT0/ATUW36GMLT0) (ATUQ54GMLT0/ATUW54GMLT0)
(AVUQ24GKLT0/AVUW24GKLT0) (AVUQ36GLLT0/AVUW36GLLT0) (AVUQ54GLLT0/AVUW54GLLT0)
(ABUQ24GGLT0/ABUW24GGLT0) (ABUQ36GRLT0/ABUW36GRLT0) (ABUQ54GRLT0/ABUW54GRLT0)
AUUQ60GHT0/AUUW60GHT0
(ATUQ60GMLT0/ATUW60GMLT0)
(AVUQ60GLLT0/AVUW60GLLT0)
(ABUQ60GRLT0/ABUW60GRLT0)
ABUQ53GRLT0
ABUW48LRLT0/ABUQ48LRLT0
ABUW54LRLT0/ABUQ54LRLT0
INSTALLATION GUIDE AT THE SEASIDE 25
Description
LED 1
(Red)
LED 2
(Green)
Indoor
status
21
DC Peak(IPM Fault)
2times ◑
1time ◑
OFF
22
Max. CT(CT2)
2times ◑
2times ◑
OFF
23
DC Link Low Volt.
2times ◑
3times ◑
OFF
24
Pressure switch/Heater Sink.
2times ◑
4times ◑
OFF
26
DC Comp Position Error
2times ◑
6times ◑
OFF
27
PFC Fault Error
2times ◑
7times ◑
OFF
29
Comp Over Current
2times ◑
9times ◑
OFF
32
D-Pipe High(Inv.)
3times ◑
2times ◑
OFF
40
CT Sensor(Open/Short)
4times ◑
0
OFF
41
Inv. D-Pipe Th Error(Open/Short)
4times ◑
1time ◑
OFF
43
High Pressure Sensor(Open/Short)
4times ◑
3times ◑
OFF
44
Outdoor air Th Error(Open/Short)
4times ◑
4times ◑
OFF
45
Cond. Middle Pipe Th Error(Open/Short)
4times ◑
5times ◑
OFF
46
Suction Pipe Th Error(Open/Short)
4times ◑
6times ◑
OFF
48
Cond. Out-Pipe Th Error(Open/Short)
4times ◑
8time ◑
OFF
51
Capacity over
5times ◑
1times ◑
OFF
53
Communication Error(Indoor ÷ Outdoor)
5times ◑
3times ◑
OFF
60
EEPROM Error(Outdoor)
6times ◑
0
OFF
61
Cond. Middle Pipe High
6times ◑
1times ◑
OFF
62
Heatsink Error(High)
6times ◑
2times ◑
OFF
65
Heatsink Th Error(Open/Short)
6times ◑
5times ◑
OFF
67
BLDC motor fan lock(Outdoor)
6times ◑
7times ◑
OFF
If abnormal voltage is supplied, the protection circuits will turn off the product in order to prevent
the component damage. The product will automatically restart after 3 minutes.
ENGLISH
Error Code
26 INSTALLATION GUIDE AT THE SEASIDE
ENGLISH
INSTALLATION GUIDE AT THE SEASIDE
! CAUTION
• Air conditioners should not be installed
in areas where corrosive gases, such as
acid or alkaline gas, are produced.
• Do not install the product where it could
be exposed to sea wind (salty wind)
directly. It can result corrosion on the
product. Corrosion, particularly on the
condenser and evaporator fins, could
cause product malfunction or inefficient
performance.
• If outdoor unit is installed close to the
seaside, it should avoid direct exposure
to the sea wind. Otherwise it needs
additional anticorrosion treatment on the
heat exchanger.
Selecting the location(Outdoor Unit)
If the outdoor unit is to be installed close to
the seaside, direct exposure to the sea wind
should be avoided. Install the outdoor unit on
the opposite side of the sea wind direction.
Sea wind
Sea wind
In case, to install the outdoor unit on the
seaside, set up a windbreak not to be
exposed to the sea wind.
Windbreak
Sea wind
- It should be strong enough like concrete to
prevent the sea wind from the sea.
- The height and width should be more than
150 % of the outdoor unit.
- It should be keep more than 70 cm of space
between outdoor unit and the windbreak for
easy air flow.
Select a well-drained place.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on
the heat exchanger by using water.
‫العربية‬
‫‪٢٧‬‬

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement