INSTALLATION MANUAL
AIR CONDITIONER
• Please read this installation manual completely before installing the product.
• Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
• Please retain this installation manual for future reference after reading it
thoroughly.
TYPE : MULTI TYPE CEILING CASSETTE
P/NO : MFL65779702
www.lg.com
2
TIPS FOR SAVING ENERGY
ENGLISH
TIPS FOR SAVING ENERGY
Here are some tips that will help you minimize the power consumption when you use the air
conditioner. You can use your air conditioner more efficiently by referring to the instructions
below:
• Do not cool excessively indoors. This may be harmful for your health and may consume more
electricity.
• Block sunlight with blinds or curtains while you are operating the air conditioner.
• Keep doors or windows closed tightly while you are operating the air conditioner.
• Adjust the direction of the air flow vertically or horizontally to circulate indoor air.
• Speed up the fan to cool or warm indoor air quickly, in a short period of time.
• Open windows regularly for ventilation as the indoor air quality may deteriorate if the air conditioner is used for many hours.
• Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the
air flow or weaken the cooling / dehumidifying functions.
For your records
Staple your receipt to this page in case you need it to prove the date of purchase or for warranty
purposes. Write the model number and the serial number here:
Model number :
Serial number :
You can find them on a label on the side of each unit.
Dealer’s name :
Date of purchase :
IMPORTANT SAFETY INSTRUCTIONS
3
READ ALL INSTRUCTIONS BEFORE USING THE APPLIANCE.
Always comply with the following precautions to avoid dangerous situations and ensure peak
performance of your product
! WARNING
It can result in serious injury or death when the directions are ignored
! CAUTION
It can result in minor injury or product damage when the directions are ignored
! WARNING
• Installation or repairs made by unqualified persons can result in hazards to you and others.
• Installation MUST conform with local building codes or, in the absence of local codes, with
the Nation Electrical Code NFPA 70/ANSI C1-1003 or current edition and Canadian Electrical
Code Part1 CSA C.22.1.
• The information contained in the manual is intended for use by a qualified service technician
familiar with safety procedures and equipped with the proper tools and test instruments.
• Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death.
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a window is left open.
- Moisture may condense and wet or damage furniture.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
ENGLISH
IMPORTANT SAFETY INSTRUCTIONS
4
IMPORTANT SAFETY INSTRUCTIONS
ENGLISH
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,
and personal injury.
• Do not use the aluminum pipe.
- It will cause gas leakage.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress
air or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
Operation
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
! CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator
fins, could cause product malfunction or inefficient operation.
TABLE OF CONTENTS
5
ENGLISH
TABLE OF CONTENTS
2 TIPS FOR SAVING
17 INSTALLATION
ENERGY
INSTRUCTIONS
17
Installer Setting -How to enter installer
setting mode
17
Installer Setting - Installer Setting Code
Table
18
Installer Setting - Setting Address of
Central Control
7 INSTALLATION
18
Installer Setting - Checking Address of
Central Control
7
Selection of the best location
18
Dip Switch Setting of Indoor unit PCB
8
Ceiling dimension and hanging bolt
location
11
Installation of Decoration Panel
12
Drain Piping
14
Wiring Connection
15
Remote Control Preparation
16
Test Running
3 IMPORTANT SAFETY
INSTRUCTIONS
6 INTRODUCTION
6
Features
6
INTRODUCTION
ENGLISH
INTRODUCTION
Features
Filter
Air Outlet
Air Inlet
Remote
Controller
Name
Quantity
Clamp metal
2 EA
Drain hose
1 EA
Insulation for
fitting
1 set
Shape
for gas pipe
Washer for
hanging bracket
8 EA
Clamp
(Tie Wrap)
4 EA
Bolt
4 EA
for liquid pipe
Screws for fixing panels are attached to decoration panel.
Other
• Paper pattern for
installation
• Owner's manual
• Installation manual
INSTALLATION
7
ENGLISH
INSTALLATION
Read completely, then follow step by step.
Selection of the best location
Ceiling Board
500 or
more
Above 2500
4000 or less
500 or
more
1000
or more
Ceiling
Ceiling Board
300 or less
300 or more
There should not be any heat source or steam near the unit.
There should not be any obstacles to the air circulation.
A place where air circulation in the room will be good.
A place where drainage can be easily obtained.
A place where noise prevention is taken into consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
The indoor unit must have the maintenance space.
Unit:mm
Floor
! CAUTION
In case that the unit is installed near the sea, the installation parts may be corroded by salt.
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
* Please use an annexed sheet or the corrugated cardboard on the bottom of packing
as installation sheet.
Or
Annexed sheet
Packing corrugated
cardboard on the
bottom
* When using the bottom sheet, please use it
after separating the installation sheet from
packing of the product floor by using a knife
etc as a picture below.
8
INSTALLATION
The dimensions of the paper model for installation are the same as those of the ceiling opening
dimensions.
Ceiling
Ceiling board
Level gauge
TQ/TR Chassis
TM/TN/TP Chassis
585~660(Ceiling opening)
875(Ceiling opening)
875(Ceiling opening)
840
Unit size
840
Unit size
671
517
585~660
(Ceiling opening)
570
319
570
684(Hanging bolt)
787
(Hanging bolt)
517
523
ENGLISH
Ceiling dimension and hanging bolt location
461
Unit:mm
Unit:mm
! CAUTION
• This air-conditioner uses a drain pump.
• Install the unit horizontally using a level gauge.
• During the installation, care should be taken not to damage electric wires.
Select and mark the position for fixing bolts and piping hole.
Decide the position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose.
Drill the hole for anchor bolt on the wall.
INSTALLATION
ENGLISH
Air conditioner
Take enough
distance
Cooking table
!
9
Use the
ventilation
fan for smoke
-collecting
hood with
sufficient
capacity.
NOTE
• Avoid the following installation location.
1 Such places as restaurants and kitchen where considerable amount of oil steam and
flour is generated. These may cause heat exchange efficiency reduction, or water
drops, drain pump mal-function. In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a
place where it may not suck oily steam.
2 Avoid installng air conditioner in such places where cooking oil or iron powder is generated.
3 Avoid places where inflammable gas is generated.
4 Avoid place where noxious gas is generated.
5 Avoid places near high frequency generators.
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
Flat washer for M10
(accessory)
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
10
90mm
ENGLISH
Ceiling
Keep the length of the bolt
from the bracket to 40mm
False
ceiling board
Air Conditioner body
False ceiling board
Keep the length of *( ) mm between
the air conditioner bottom surface
and the ceiling surface
Paper pattern
for installation
Adjust the same height
* The following parts are local purchasing.
① Hanging Bolt - W 3/8 or M10
② Nut
- W 3/8 or M10
③ Spring Washer - M10
④ Plate Washer - M10
! CAUTION
Tighten the nut and bolt to prevent the unit from falling.
*( ) → TQ/TR : 31~34mm
TP : 15mm
Set screw of
paper pattern (4 pieces)
Open the ceiling board
along the outer edge of the
paper pattern
11
The decoration panel has its
installation direction.
Before installing the decoration panel,
always remove the paper template.
1 Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body.
(Tighten by amount 10mm in length.)
The fixing screws (hexagon M5 screw) are included the indoor unit box.
2 Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille
cord.)
3 Hook the decoration panel key hole (
) on the screws fixed in step above, and slide the
panel so that the screws reach the key hole edge.
4 Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5 Connect the louver motor connector and display connector.
6 After tightening these screws, install the air inlet grille (including the air filter).
Air conditioner unit
Decorative panel
fixing screws
(hexagon M6 screws)
Temporary fitting
at 2 poles
(Tightening about 10mm)
Piping side
Control box cover
Cover
Plasma filter
Louver motor
Key holes
Decorative panel
fixing screws
(Hexagon M6 screw)
Decorative panel
Push
Ratch
pull
Inlet Grille
ENGLISH
Installation of Decoration Panel
12 INSTALLATION
ENGLISH
Correct method
Wrong method
Air conditioner
unit
Cool air leakage
(no good)
Ceiling
board
Decoration panel
Air conditioner
unit
Ceiling
board
Decoration panel
Fit the insulator (this part) and
be careful for cool air leakage
! CAUTION
Install certainly the decoration panel.
Cool air leakage causes sweating. ‘ Water drops fall.
Drain Piping
Drain test
• Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down
slope to prevent reversal flow.
• During drain piping connection, be careful
not to exert extra force on the drain port on
the indoor unit.
• The outside diameter of the drain connection on the indoor unit is 32mm.
- Piping material: Polyvinyl chloride pipe VP25 and pipe fittings
• Be sure to install heat insulation on the drain
piping.
- Heat insulation material: Polyethylene
foam with thickness more than 8 mm.
Pipe clamp
Upward
routing
not allowed
Indoor unit
Maintenance
drain port
The air conditioner uses a drain pump to drain
water.
Use the following procedure to test the drain
pump operation:
• Connect the main drain pipe to the exterior
and leave it provisionally until the test
comes to an end.
• Feed water to the flexible drain hose and
check the piping for leakage.
• Be sure to check the drain pump for normal
operating and noise when electrical wiring is
complete.
• When the test is complete, connect the flexible drain hose to the drain port on the indoor unit.
Feed water
Drain Pump
1/50~1/100
MAX 700mm
Drain pan
Flexible drain hose
(accessory)
Main
drain pipe
Drain
port
Glue the joint
Drain hose connection
Use the clip (accessory)
INSTALLATION 13
The supplied flexible drain hose should not
be curved, neither screwed.
The curved or screwed hose may cause a
leakage of water.
Flexible drain hose
1/50~1/100
MAX 700mm
! CAUTION
After the confirmation of the above conditions, prepare the wiring as follows:
1 Never fail to have an individual power specialized for the air conditioner. As for the
method of wiring, be guided by the circuit diagram posted on the inside of control box
cover.
2 Provide a circuit breaker switch between power source and the unit.
3 The screws which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of transportation.
Check them and make sure that they are all tightly fastened. (If they are loose, it could
give rise to burn-out of the wires.)
4 Specification of power source
5 Confirm that electrical capacity is sufficient.
6 Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate.
7 Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.)
8 Never fail to equip a leakage breaker where it is wet or moist.
9 The following troubles would be caused by voltage drop-down.
- Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance
by the normal function of an overload protection device.
- Proper starting power is not given to the compressor.
ENGLISH
! CAUTION
14 INSTALLATION
ENGLISH
Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit
connection.
Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of
indoor unit respectively.
1(L)
Terminal Block of Indoor Unit
2(N)
3
4
Connected to outdoor unit
5
TO AIR
FRESH
KIT
OPTION
Precautions when laying power wiring
Use round pressure terminals for connections to the power terminal block.
Round pressure terminal
Power wire
When none are available, follow the instructions below.
- Do not connect wiring of different thicknesses to the power terminal block. (Slack in the power
wiring may cause abnormal heat.)
- When connecting wiring which is the same thickness, do as shown in the figure below.
! WARNING
Make sure that the screws of the terminal are free from looseness.
INSTALLATION 15
HOW TO MOUNT ONTO A WALL
1 Remove the battery cover from the remote controller.
- Slide the cover according to the arrow direction.
2 Insert the two batteries.
- Be sure that the (+) and (-) directions are correct.
- Be sure that both batteries are new.
3 Re-attach the cover.
- Slide it back into position.
- Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and performance.
- Romove the batteries from the remote controller if the air conditioner is not going to be used for
some long time.
ENGLISH
Remote Control Preparation
16 INSTALLATION
ENGLISH
Test running
[Ceiling Cassette Type]
PRECAUTIONS IN TEST RUN
The initial power supply must provide at least
90% of the rated voltage.
Otherwise, the air conditioner should not be
operated.
! CAUTION
• For test run, carry out the cooling operation firstly even during heating season. If heating operation is carried out
firstly, it leads to the trouble of compressor. Then attention must be paid.
Test operation
- During the TEST OPERATION, the unit operates in cooling mode at high speed fan,
regardless of room temperature and resets
in 18 minutes. During test operation, if
remote controller signal is received, the unit
operates as remote controller sets. If you
want to use this operation, Press and hold
the ON/OFF button for 3~5 seconds, then
the buzzer sound 1 'beep'. If you want to
stop the operation, re-press the button.
(
)
Forced Operation
Button
( ) : Heat pump only
Connection of power supply
- Connect the power supply cord to the independent power supply.
Circuit breaker is required.
Evaluation of the performance
- Measure the pressure of the gas side service
valve.
- Measure the air temperature from inlet and
outlet of air conditiioner.
- Ensure the difference between the inlet and
outlet temperature is more than 8°C.
- For reference; the gas side pressure at optimum condition is shown on table (cooling).
Outside
Refrige
ambient
rant
TEMP.
The pressure of the gas
side service valve
35°C(95°F)
4~5 kg/cm2G
(56.8~71.0 P.S.I.G.)
R410A 35°C(95°F)
8.5~9.5 kg/cm2G
(120~135 P.S.I.G.)
R22
!
NOTE
• If the actual pressure is higher than
shown, the system is most likely overcharged, and charge should be removed. If the actual pressure are lower
than shown, the system is most likely
undercharged, and charge should be
added.
INSTALLATION 17
Installer Setting -How to enter installer setting mode
! CAUTION
Installer setting mode is to set the detail function of the remote controller.
If the installer setting mode is not set correctly, it can cause problems to the product, user
injury or property damage. This must be set by an certificated installer, and any installation
or change that is carried out by a non-certificated person should be responsible for the
results. In this case, free service cannot be provided.
1. With the JET COOL button pressed, press the RESET button.
2. By using the TEMPERATURE SETTING button, set function code and setting value. (Please
refer the Installer Setting Code Table.)
3. Press the ON/OFF button toward the indoor unit 1 time.
4. Reset the remote controller to use the general operation mode.
Installer Setting - Installer Setting Code Table
Installer Setting Code Table
No.
Function
Function Code
Setting Value
Remote Controller LCD
1 : Standard
1
Ceiling Height
Selection
2 : Low
1
3 : High
4 : Super High
0 : Set to Master
2
Group Control
2
1 : Set to Slave
2 : Check Master/Slave
Ceiling Height Selection & Group Control
Indoor unit connected to wired remote controller operate as wired remote controller setting.
Please refer to the wired remote controller accessory manual for more details.
ENGLISH
INSTALLATION INSTRUCTIONS
18 INSTALLATION INSTRUCTIONS
ENGLISH
Installer Setting - Setting Address of Central Control
1. With the MODE button pressed, press the RESET button.
2. By using the temperature setting button, set the indoor unit address.
• Setting range : 00 ~ FF
3. After setting the address, press the ON/OFF button toward the indoor unit 1 time.
4. The indoor unit will display the set address to complete the address setting.
• The address display time and method can differ by the indoor uint type.
5. Reset the remote controller to use the general operation mode.
Installer Setting - Checking Address of Central Control
1. With the PLASMA button pressed, press the RESET button.
2. Press the ON/OFF button toward the indoor unit 1 time, and the indoor unit will display the set
address in the display window.
• The address display time and method can differ by the indoor unit type.
3. Reset the remote controller to use the general operation mode.
Dip Switch Setting of Indoor unit PCB
ON
1
2 3
4
5 6
7 8
Indoor PCB
Function
SW3 Group Control
SW4
!
Dry Contact
Mode
Description
Setting Off
Setting On
Default
Selection of Master or Slave
Master
Slave
Off
Wired/Wireless remote
controller
Selection of Manual or Auto
operation Mode
Auto
Off
Selection of Dry
Contact Mode
NOTE
Please refer to the wired remote controller accessory manual for more details about ‘Group
Control’ & ‘Dry Contact Mode’.