LG | ARNU18GTLA2.ANWAIDN | Owner's Manual | LG ARNU18GTLA2.ANWAIDN Owner's Manual

LG ARNU18GTLA2.ANWAIDN Owner's Manual
ENGLISH
BAHASA INDONESIA
INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring
standards by authorized personnel only.
Please retain this installation manual for future reference after reading it
thoroughly.
CEILING CASSETTE - 2WAY
Original instruction
ARNU18GTLA2
ARNU24GTLA2
I.15.LG23.01504.0416
P/NO : MFL69446302
www.lg.com
Ceiling Cassette - 2Way Type Indoor Unit Installation Manual
TABLE OF CONTENTS
Installation Requirements
Required Parts
Required Tools
Installation Parts ...................3
Safety Precautions.................4
Installation
Selection of the best
location...................................6
Ceiling dimension and hanging bolt location......................7
Wiring Connection.................8
Installation of Decoration
Panel......................................9
Drain Piping.........................10
❏ Installation guide map
❏ Four type "A" screws & plastic anchors
❏ Connecting cable
❏ Level gauge
❏ Screw driver
❏ Electric drill
❏ Hole core drill
❏ Horizontal meter
❏ Pipes: Gas side
Liquid side
(Refer to Product
Data)
❏ Insulation materials
❏ Additional drain pipe
❏ Flaring tool set
❏ Specified torque wrenches
(different depending on model No.)
❏ Spanner.......Half union
❏ Hexagonal wrench
❏ Gas-leak detector
❏ Vacuum pump
❏ Gauge manifold
DIP Switch Setting ..............12
Group Control Setting .........13
2
Indoor Unit
❏ Owner's manual
❏ Thermometer
Installation Parts
ENGLISH
Installation Parts
Anti-bacteria filter
Air Intake
Air Outlet
Wired Remote Controller(Accessory)
Installation Tool
Name
Quantity
Drain hose Clamp metal
1 EA
2 EA
Washer for
hanging bracket
8 set
Clamp
(Tie Wrap)
4 EA
Shape
Insulation for
fitting
1 EA
for gas pipe
(Other)
• Paper pattern for
installation
• Owner's manual
• Installation manual
for liquid pipe
• Screws for fixing panels are attached to decoration panel.
Installation Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be
followed.
■ Be sure to read before installing the air conditioner.
■ Be sure to observe the cautions specified here as they include important items related to safety.
■ Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is classified by the following indications.
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage to properties only.
■ Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
■ Installation
Do not use a defective or underrated circuit breaker. Use
this appliance on a dedicated
circuit.
• There is risk of fire or electric
shock.
Install the panel and the
cover of control box securely.
• There is risk of fire or electric
shock.
Do not modify or extend the
power cable.
• There is risk of fire or electric
shock.
4
Indoor Unit
For electrical work, contact
the dealer, seller, a qualified
electrician, or an Authorized
Service Center.
• Do not disassemble or repair
the product. There is risk of fire
or electric shock.
Always install a dedicated
circuit and breaker.
• Improper wiring or installation
may cause fire or electric
shock.
Do not let the air conditioner
run for a long time when the
humidity is very high and a
door or a window is left open.
• Moisture may condense and
wet or damage furniture.
Always ground the product.
• There is risk of fire or electric
shock.
Use the correctly rated
breaker or fuse.
• There is risk of fire or electric
shock.
Be cautious when unpacking
and installing the product.
• Sharp edges could cause injury. Be especially careful of the
case edges and the fins on the
condenser and evaporator.
Safety Precautions
• There is risk of fire, electric
shock, explosion, or injury.
Do not install the product on
a defective installation stand.
Be sure the installation area
does not deteriorate with age.
• It may cause injury, accident, or • If the base collapses, the air
damage to the product.
conditioner could fall with it,
causing property damage,
product failure, and personal injury.
Use a vacuum pump or inert (nitrogen) gas
when doing leakage test or air purge. Do not
compress air or oxygen, and do not use flammable gases. Otherwise, it may cause fire or
explosion.
Do not turn on the breaker or power under
condition that front panel, cabinet, top cover,
control box cover are removed or opened.
• There is the risk of death, injury, fire or explosion. • Otherwise, it may cause fire, electric shock, explosion or death.
■ Operation
Do not store or use flammable gas or combustibles near the product.
• There is risk of fire or failure of product.
CAUTION
■ Installation
Always check for gas (refrigerant) leakage after installation or repair of product.
• Low refrigerant levels may
cause failure of product.
Install the drain hose to ensure that water is drained
away properly.
Keep level even when installing the product.
• A bad connection may cause
water leakage.
• To avoid vibration or water
leakage.
Use two or more people to lift and transport the product.
• Avoid personal injury.
Installation Manual 5
ENGLISH
For installation, always contact the dealer or an Authorized Service Center.
Installation
Installation
Read completely, then follow step by step.
Selection of the best location
20±3
Above 1 800
3 000 or less
500 or
more
1 000
or more
Ceiling
Ceiling Board
Ceiling Board
500 or
more
300 or less
200 or more
• There should not be any heat source or steam near the unit.
• There should not be any obstacles to the air circulation.
• A place where air circulation in the room will be good.
• A place where drainage can be easily obtained.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, or other obstacles.
• The indoor unit must have the maintenance space.
Unit:mm
Floor
CAUTION : In case that the unit is installed near the sea, the installation parts
may be corroded by salt. The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
6
Indoor Unit
Installation
ENGLISH
Ceiling dimension and hanging bolt location
• The dimensions of the paper model for installation are the same as those of the ceiling
opening dimensions.
1 010 (Ceiling opening)
Ceiling
877 (Hanging bolt)
830
• Select and mark the position for fixing bolts
and piping hole.
• Decide the position for fixing bolts slightly
tilted to the drain direction after considering
the direction of drain hose.
• Drill the hole for anchor bolt on the wall.
59
60
482(Hanging bolt)
CAUTION :
• This air-conditioner uses a drain
pump.
• Install the unit horizontally using a
level gauge.
• During the installation, care should
be taken not to damage electric
wires.
600 (Ceiling opening)
550
Level gauge
unit: mm
Ceiling board
NOTICE
• Avoid the following installation location.
1. Such places as restaurants and kitchen where considerable amount of oil steam and flour is
generated.
These may cause heat exchange efficiency reduction, or water drops, drain pump mal-function.
In these cases, take the following actions;
• Make sure that ventilation fan is enough to cover all noxious gases from this place.
• Ensure enough distance from the cooking room to install the air conditioner in such a place
where it may not suck oily steam.
2. Avoid installng air conditioner in such
places where cooking oil or iron
Air conditioner
powder is generated.
3. Avoid places where inflammable gas
Take enough
is generated.
distance
Use the ventilation fan
4. Avoid places where noxious gas is
for smoke-collecting
hood with sufficient
generated.
capacity.
Cooking table
5. Avoid places near high frequency
generators.
Installation Manual 7
Installation
Ceiling
Nut
(W3/8 or M10)
Flat washer for M10
(accessory)
Ceiling board
Flat washer for M10
(accessory)
Nut
(W3/8 or M10)
Adjust the
same height
• The following parts are local purchasing.
① Hanging Bolt - W 3/8 or M10
② Nut
- W 3/8 or M10
③ Spring Washer - M10
④ Plate Washer - M10
90 mm
Keep the length of the bolt
from the bracket to 40 mm
Hanging bolt
(W3/8 or M10)
Air Conditioner body
Paper pattern
for installation
Ceiling board
Set screw of
paper pattern (4 pieces)
Open the ceiling board
along the outer edge of the
paper pattern
CAUTION : Tighten the nut and bolt
to prevent the unit from falling.
Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit
connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of
indoor unit respectively.
Outdoor unit Indoor unit
Terminal Block Indoor
1(L)
2(N)
3
4
Central controller
Outdoor unit
SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V
INDOOR POWER INPUT
WARNING : Make sure that the screws of the terminal are free from looseness.
CAUTION : The Power cord connected to the unit should be selected according
to the following specifications.
8
Indoor Unit
Installation
The decoration panel has its installation direction.
Before installing the decoration panel, always remove the paper template.
1. Temporarily fix two decoration panel fixing screws (hexagon M5 screw) on the unit body.
(Tighten by amount 10 mm in length.) The fixing screws (hexagon M5 screw) are included the indoor unit box.
2. Remove the air inlet grille from the decoration panel. (Remove the hook for the air inlet grille cord.)
3. Hook the decoration panel key hole (
) on the screws fixed in step above, and slide
the panel so that the screws reach the key hole edge.
4. Retighten completely two temporarily fixed screws and other two screws. (Total 4 screws)
5. Connect the louver motor connector and display connector.
6. After tightening these screws, install the air inlet grille (including the air filter).
Air conditioner unit
Decorative panel
fixing screws
(hexagon M6 screws)
Temporary fitting
at 2 poles
(Tightening about 10 mm)
Piping side
Control box cover
Cover
Plasma filter
Louver motor
Key holes
Decorative panel
fixing screws
(Hexagon M6 screw)
Decorative panel
Push
Ratch
pull
Inlet Grille
CAUTION : Install
certainly the decoration panel.
Cool air leakage
causes sweating.
⇨ Water drops
fall.
Good example
Bad example
Air conditioner
unit
Cool air leakage
(no good)
Ceiling
board
Decoration panel
Air conditioner
unit
Ceiling
board
Decoration panel
Fit the insulator (this part) and
be careful for cool air leakage
Installation Manual 9
ENGLISH
Installation of Decoration Panel
Installation
Drain Piping
• Drain piping must have down-slope (1/50 to
1/100): be sure not to provide up-and-down slope
to prevent reversal flow.
• During drain piping connection, be careful not to
exert extra force on the drain port on the indoor
unit.
• The outside diameter of the drain connection on
the indoor unit is 32 mm.
Upward
routing
not allowed
Pipe clamp
Indoor unit
Maintenance
drain port
Piping material: Polyvinyl chloride pipe VP-25
and pipe fittings
1/50~1/100
• Be sure to install heat insulation on the drain piping.
MAX 700 mm
Heat insulation material: Polyethylene foam
with thickness more than 8 mm.
Drain test
The air conditioner uses a drain pump to drain water.
Use the following procedure to test the drain pump operation:
Feed water
Flexible drain hose
(accessory)
Main
drain pipe
Drain Pump
Drain
port
Glue the joint
Drain hose connection
Use the clip (accessory)
Drain pan
• Connect the main drain pipe to the exterior and leave it provisionally until the
test comes to an end.
• Feed water to the flexible drain hose
and check the piping for leakage.
• Be sure to check the drain pump for normal operating and noise when electrical
wiring is complete.
• When the test is complete, connect the
flexible drain hose to the drain port on
the indoor unit.
Flexible drain hose
Hanger
Max 300 mm distance
1~15 m
Hanger Bracket
1/50~1/100 slope
Metal
Flexible drain hose
clamp
Flexible drain hose
Insulation
10
Indoor Unit
Max 700 mm
CAUTION : The supplied flexible
drain hose should not be curved,
neither screwed. The curved or
screwed hose may cause a leakage
of water.
Installation
1) Never fail to have separate power specially for the air conditioner. As for the
method of wiring, follow the circuit diagram pasted on the inside of control
box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screw which fasten the wiring in the casing of electrical fittings are liable
to come loose from vibrations to which the unit is subjected during the
course of transportation. Check them and make sure that they are all tightly
fastened. (If they are loose, it could give rise to burn-out of the wires.)
4) Confirm the Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 % of the rated
voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Do not install the leakage breaker in a place which is wet or moist.
Water or moist may cause short circuit.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device.
• Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)
Installation Manual 11
ENGLISH
CAUTION:
After the confirmation of the above conditions, prepare the wiring as follows:
Installation
DIP Switch Setting
SW1
SW2
Function
Communication
Cycle
SW3
Group Control
SW4
Dry Contact
Mode
SW5
SW6
SW7
SW8
Description
N/A (Default)
N/A (Default)
Setting Off
-
Selection of Master or
Slave
Master
Wired/Wireless remote
Selection of Dry Concontroller
tact
selection of Manual or Auto
Mode
operation Mode
Fan continuous
Continuous operation
Installation
operation
Removal
Heater linkage
N/A
-
Slave
Off
Auto
Off
-
Off
-
Off
Ventilator linkage
Selection of Ventilator
linkage
Vane selection
(Console)
Selection of up/down
Up side Vane
Up side + Down side Vane
side Vane
Only
Region selection
Etc.
Selection tropical
region
Spare
Linkage Removal
General model
CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
12
Setting On Default
Off
Off
Indoor Unit
-
Working
Tropical
model
-
Off
Off
Installation
ENGLISH
Group Control Setting
1. Group Control 1
■ Wired remote controller 1 + Standard Indoor Units
LGAP Network System
or
Master
Slave
Slave
Slave
GND
Signal
12 V
Only connect serial signal and
GND lines between indoor units.
Display Error Message
Master
■ Dip Switch in PCB (Cassette and Duct Type indoor units)
➀ Master Setting
- No. 3 Off
➁ Slave Setting
- No. 3 On
Indoor Unit DIP Switch
1. It is possible to 16 indoor units(Max.) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
- In case of Central controller and Group controller at the same time, it is possible to connect standard 2series indoor units or later since Feb. 2009.
- In case of Central controller setting, the Central controller can control indoor units after setting only
the address of master indoor unit.
- Slave indoor unit will be operated like master indoor unit.
- Slave indoor unit can not be individually controlled by Central controller.
- Some remote controller can’t perform with Dry Contact and Central controller at the same time.
So contact us further information about it.
Installation Manual 13
Installation
5. In case of any error occurs at indoor unit, display on the wired remote controller.
Exception of the error indoor unit, an individual indoor unit control possibility.
6. In case of Group Control, it is possible to use following functions.
- Selection of operation options (operation/stop/mode/set temperature)
- Control of flow rate (High/Middle/Low)
- It is not possible at some functions.
❈ Master/Slave setting of indoor units be set possible using a PCB Dip Switch.
❈ It is possible to connect indoor units since Feb. 2009.
In the other cases, please contact LGE.
❈ It can be the cause of malfuctions when there is no setting of master and slave.
2. Group Control 2
■ Wired remote controllers + Standard Indoor Units
LGAP Network System
or
Master
Master
Slave
Slave
Donʼt connect serial 12V line
Display Error Message
Master
Master
❈ It is possible to control N indoor units by wired remote controller M units. (M + N ≤ 17 Units)
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
Other than those, it is same with the Group Control 1.
14
Indoor Unit
GND
Signal
12 V
Installation
ENGLISH
3. Group Control 3
■ Mixture connection with indoor units and Fresh Air Intake Unit
LGAP Network System
or
FAU
Master
FAU
Slave
Master
GND
Signal
12 V
Slave
N
M
Display Error Message
Display Error Message
Master
Master
❈ In case of connecting with standard indoor unit and Fresh Intake Unit, separate Fresh Air Intake
Unit with standard units. (Because setting temperature are different.)
❈ Other than those, it is same with Group Control 1.
FAU
FAU
Standard
Standard
FAU
FAU
Standard
Standard
* FAU : Fresh Air Intake Unit
Standard: Standard Indoor Unit
Installation Manual 15
Installation
4. 2 Remote Control
■ Wired remote controller 2 + Indoor unit 1
LGAP Network System
or
Master
GND
Signal
12 V
Display Error Message
Master
Slave
1. It is possible to connect two wired remote controllers with one indoor unit.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired
remote controller.
6. There isnʼt limits of indoor unit function.
❈ Maximum 2wired remote controllers can be connected with 1 indoor unit.
16
Indoor Unit
Installation
ENGLISH
5. Accessories for group control setting
It is possible to set group control by using below accessories.
Indoor unit 2 EA +Wired remote controller 1 EA
Indoor unit 1 EA +Wired remote controller 2 EA
❈ PZCWRCG3 cable used for connection
❈ PZCWRC2 cable used for connection
Slave
Master
PZCWRC2
PZCWRCG3
Master
Master
Slave
• Apply totally enclosed noncombustible conduit in case of local building code Requiring
plenum cable usage.
Installation Manual 17
18
Indoor Unit
PT.LG Electronics Indonesia
Gandaria 8 Office Tower Lt. 29 BC & 31 ABCD
Jl.Sultan Iskandar Muda, Kebayoran Lama Utara - Kebayoran Lama,
Jakarta Selatan - DKI Jakarta Raya, Indonesia