LG ARNU24GCFA4 Installation manual


Add to my manuals
19 Pages

advertisement

LG ARNU24GCFA4 Installation manual | Manualzz
ENGLISH
BAHASA INDONESIA
INSTALLATION MANUAL
AIR
CONDITIONER
Please read this installation manual completely before installing the product.
Installation work must be performed in accordance with the national wiring standards
by authorized personnel only.
Please retain this installation manual for future reference after reading it thoroughly.
Floor Standing - Concealed Floor Standing
Original instruction
ARNU07GCEA4 ARNU09GCEA4 ARNU12GCEA4 ARNU15GCEA4
ARNU07GCEU4 ARNU09GCEU4 ARNU12GCEU4 ARNU15GCEU4
ARNU18GCFA4 ARNU24GCFA4 ARNU18GCFU4 ARNU24GCFU4
www.lg.com
P/NO : MFL69440024
Copyright © 2018 LG Electronics Inc. All Rights Reserved.
Table of Contents
TABLE OF CONTENTS
3
FEATURES
4
SAFETY PRECAUTIONS
7
INSTALLATION
7
Selection of the best location
9
How to connect wirings
9
Wiring Connection
10
Drain piping work
12
DIP Switch Setting
13
Group Control Setting
18
Model Designation
18
Airborne Noise Emission
18
Limiting concentration
2
Indoor Unit
Features
ENGLISH
Features
[CEA/CFA Type]
Control panel
Air Outlet
Remote Controller
Control panel
Air Filter
Air Inlet
[CEU/CFU Type]
Air Inlet
Air filter
(At Air Inlet)
Installation Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be
followed.
n Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
WARNING
This symbol indicates the possibility of death or serious injury.
CAUTION
This symbol indicates the possibility of injury or damage to properties only.
n Meanings of symbols used in this manual are as shown below.
Be sure not to do.
Be sure to follow the instruction.
WARNING
Installation
• Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
- There is risk of fire or electric shock.
• For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized Service Center.
- Do not disassemble or repair the product. There is risk of fire or electric shock.
• Always ground the product.
- There is risk of fire or electric shock.
• Install the panel and the cover of control box securely.
- There is risk of fire or electric shock.
• Always install a dedicated circuit and breaker.
- Improper wiring or installation may cause fire or electric shock.
• Use the correctly rated breaker or fuse.
- There is risk of fire or electric shock.
• Do not modify or extend the power cable.
- There is risk of fire or electric shock.
• Do not install, remove, or re-install the unit by yourself (customer).
- There is risk of fire, electric shock, explosion, or injury.
• Be cautious when unpacking and installing the product.
- Sharp edges could cause injury. Be especially careful of the case edges and the fins on the
condenser and evaporator.
• For installation, always contact the dealer or an Authorized Service Center.
- There is risk of fire, electric shock, explosion, or injury.
• Do not install the product on a defective installation stand.
- It may cause injury, accident, or damage to the product.
• Be sure the installation area does not deteriorate with age.
- If the base collapses, the air conditioner could fall with it, causing property damage, product failure,
and personal injury.
• Do not turn on the breaker or power under condition that front panel, cabinet, top cover, control box
cover are removed or opened.
- Otherwise, it may cause fire, electric shock, explosion or death.
• Use a vacuum pump or Inert (nitrogen) gas when doing leakage test or air purge. Do not compress air
or Oxygen and Do not use Flammable gases. Otherwise, it may cause fire or explosion.
- There is the risk of death, injury, fire or explosion.
4
Indoor Unit
Safety Precautions
Installation Manual 5
ENGLISH
Operation
• Do not let the air conditioner run for a long time when the humidity is very high and a door or a
window is left open.
- Moisture may condense and wet or damage furniture.
• Take care to ensure that power cable could not be pulled out or damaged during operation.
- There is risk of fire or electric shock.
• Do not plug or unplug the power supply plug during operation.
- There is risk of fire or electric shock.
• Do not touch(operate) the product with wet hands.
- There is risk of fire or electrical shock.
• Do not place a heater or other appliances near the power cable.
- There is risk of fire and electric shock.
• Do not place anything on the power cable.
- There is risk of fire or electric shock.
• Do not allow water to run into electric parts.
- It may cause There is risk of fire, failure of the product, or electric shock.
• Do not store or use flammable gas or combustibles near the product.
- There is risk of fire or failure of product.
• Do not use the product in a tightly closed space for a long time.
- Oxygen deficiency could occur.
• When flammable gas leaks, turn off the gas and open a window for ventilation before turn the product
on.
- Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
• If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the
power supply cable.
- There is risk of electric shock or fire.
• Stop operation and close the window in storm or hurricane.
If possible, remove the product from the window before the hurricane arrives.
- There is risk of property damage, failure of product, or electric shock.
• Do not open the inlet grill of the product during operation.
(Do not touch the electrostatic filter, if the unit is so equipped.)
- There is risk of physical injury, electric shock, or product failure.
• When the product is soaked (flooded or submerged), contact an Authorized Service Center.
- There is risk of fire or electric shock.
• Be cautious that water could not enter the product.
- There is risk of fire, electric shock, or product damage.
• Ventilate the product from time to time when operating it together with a stove, etc.
- There is risk of fire or electric shock.
• Turn the main power off when cleaning or maintaining the product.
- There is risk of electric shock.
• When the product is not be used for a long time, disconnect the power supply plug or turn off the
breaker.
- There is risk of product damage or failure, or unintended operation.
• Take care to ensure that nobody could step on or fall onto the outdoor unit.
- This could result in personal injury and product damage.
Safety Precautions
CAUTION
Installation
• Always check for gas (refrigerant) leakage after installation or repair of product.
- Low refrigerant levels may cause failure of product.
• Install the drain hose to ensure that water is drained away properly.
- A bad connection may cause water leakage.
• Keep level even when installing the product.
- To avoid vibration or water leakage.
• Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
- It may cause a problem for your neighbors.
• Use two or more people to lift and transport the product.
- Avoid personal injury.
• Do not install the product where it will be exposed to sea wind (salt spray) directly.
- It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
could cause product malfunction or inefficient operation.
• In order to avoid a hazard due to inadvertent resetting of the thermal cut-out, this appliance must not
be supplied through an external switching device, such as a timer, or connected to a circuit that is
regularly switched on and off by the utility.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly
qualified persons in order to avoid a hazrd.
• This equipment shall be provided with a supply conductor complying with the national regulation.
Operation
• Do not expose the skin directly to cool air for long periods of time. (Don't sit in the draft.)
- This could harm to your health.
• Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a
consumer air conditioner, not a precision refrigeration system.
- There is risk of damage or loss of property.
• Do not block the inlet or outlet of air flow.
- It may cause product failure.
• Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
- There is risk of fire, electric shock, or damage to the plastic parts of the product.
• Do not touch the metal parts of the product when removing the air filter. They are very sharp!
- There is risk of personal injury.
• Do not step on or put anyting on the product. (outdoor units)
- There is risk of personal injury and failure of product.
• Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
- A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or
damage.
• Do not insert hands or other objects through the air inlet or outlet while the product is operated.
- There are sharp and moving parts that could cause personal injury.
• Do not drink the water drained from the product.
- It is not sanitary and could cause serious health issues.
• Use a firm stool or ladder when cleaning or maintaining the product.
- Be careful and avoid personal injury.
• Replace the all batteries in the remote control with new ones of the same type. Do not mix old and
new batteries or different types of batteries.
- There is risk of fire or explosion.
• Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
- They may burn or explode.
• If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not use
the remote if the batteries have leaked.
- The chemicals in batteries could cause burns or other health hazards.
• If you eat the liquid from the batteries, brush your teeth and see doctor. Do not use the remote if the
batteries have leaked.
- The chemicals in batteries could cause burns or other health hazards.
6
Indoor Unit
Installation
ENGLISH
Installation
Selection of the best location
Indoor unit
Install the air conditioner in the location that
satisfies the following conditions.
• The place shall easily bear a load exceeding four
times the indoor unit’s weight.
• Sufficient space should be available to inspect
the unit as in the figure shown on the right.
• The place where the unit is installed shall be
leveled.
• The place shall be suitable for easy connection of
the indoor unit with the outdoor unit.
• The place where the unit is installed should not
be affected by electrical noise.
• The place where air circulation in the room will be
good .
• There should not be any heat source or steam
near the unit
20 or
more
(Unit: mm)
A
788
1066
Front side
100 or
more
175 or
more
100 or
more
1000 or
more
Air inlet
direction
Base
Window
654
Select an installation site where the following
conditions are satisfied and that meets your
customer's approval.
• Where the floor is strong enough to bear the
indoor unit weight.
• Where the floor is not significantly inclined.
• Where nothing blocks the air passage.
• Where condensate can be properly drained.
• Where sufficient clearance for installation and
maintenance can be ensured.
• Where there is no possibility of flammable gas
leakage.
• Where optimum air distribution can be ensured.
• Where piping between indoor and outdoor units
is possible within the allowable limit (Refer to the
installation manual of the outdoor unit.)
• Keep the indoor and outdoor unit, power cable
and transmission wiring, at least 1m from TVs
and radios, to prevent distorted pictures and
static.(Depending on the type and source of the
electrical waves, static may be heard even when
more than 1 m away.)
Air flow
direction
80 or more
Service space
Type
CEU Type
CFU Type
Window
Ma
inte
nan
ce
are
a
Ao
rm
ore
Bo
rm
ore
[IMPORTANT]
Leave sufficient clearance for air
inlet and maintenance.
B
1080
1358
Installation Manual 7
Installation
Bolt pitch
• Positioning of holes for fastening to the wall
A
A
858
1136
1. Use the installationmount for installation. Check
whether the wall is strong enough to bear the
weight of the unit or not. if there is a risk,
reinforce the wall before installing the unit.
2. The unit requires a minimum 100 mm clearance
on the underside for air intake. Also, ensure the
unit is level when installed so that drainage
flows smoothly. If inclined, water can leak.
3. By a state of the wall, operating sound may
become bigger.
270
Capacity(Btu/h)
CE
CF
198
(Unit:mm)
(Unit:mm)
(1)
How to open/close front panel
(2)
• How to open/close the front panel
(1) Open the lid of control panel(Both left and right)
(2) Remove screws(Both left and right)
(3) Lift the front panel of the unit
• To close, perform the procedure in opposite
order.
8
Indoor Unit
(2)
(3)
(1)
Installation
ENGLISH
How to connect wirings
Remove the electric parts Box cover and connect the wiring
Power Supply wiring
ground wiring
(Field wiring)
Transmission wiring
(Field wiring)
Wiring Connection
Connect the wires to the terminals on the control board individually according to the outdoor unit
connection.
• Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of
indoor unit respectively.
Terminal Block Indoor
Terminal Block Indoor
N(L2)
3(A)
4(B)
Outdoor unit Indoor unit
Central controller
Outdoor unit
SODU SODU IDU IDU INTERNET DRY1 DRY2 GND 12V
GN/YL
L(L1)
INDOOR POWER INPUT
WARNING : Make sure that the screws of the terminal are free from looseness.
CAUTION : The Power cord connected to the unit should be selected according
to the following specifications.
Installation Manual 9
Installation
HEAT INSULATION
1. Use the heat insulation material for the refrigerant
piping which has an excellent heat-resistance
(over 120°C).
2. Precautions in high humidity circumstance:
This air conditioner has been tested according to
the "ISO Conditions with Mist" and confirmed that
there is not any default. However, if it is operated
for a long time in high humid atmosphere (dew
point temperature: more than 23°C), water drops
are liable to fall. In this case, add heat insulation
material according to the following procedure:
• Heat insulation material to be prepared... EPDM
(Ethylene Propylene Diene Methylene)-over
120°C the heat-resistance temperature.
• Add the insulation over 10mm thickness at high
humidity environment.
After inspecting pipe joints for gas leakage, be sure
to insulate wit the accessory joint insulation for
fitting while referrig to the figure. (Fasten both ends
with clamps)
Fastening band
(accessory)
Refrigerant piping
Indoor unit
Thermal insulator
(accessory)
Insulation for fitting
(accessory)
(For liquid piped)
Insulation for fitting
(accessory)
(For gas piped)
liquid pipe
Clamp
(accessory)
Drain piping work
• Drain piping must have downward (1/50 to 1/100): be sure not to provide up-and-down slope to
prevent reverse flow.
• During drain piping connection, be careful not to exert extra force on the drain port on the indoor unit.
• The outside diameter of the drain connection on the inddor unit is 21mm.
Piping material: Polyvinyl chloride pipe 25mm and pipe fittings
• Be sure to install heat insulation on the drain piping
Heat insulation material: Polyethylene foam with thickness more than 10 mm.
• If converging multiple dranin pipes, install according to the procedure shown below.
Slope downwards at a gradient
of at least 1/100
• After piping work is finished check drainage flows smothly.
• Be sure to insulate all indoor units.
10
Indoor Unit
Installation
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have an individual power specialized for the air conditioner. As
for the method of wiring, be guided by the circuit diagram posted on the inside
of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable
to come loose from vibrations to which the unit is subjected during the course
of transportation. Check them and make sure that they are all tightly fastened.
(If they are loose, it could give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is maintained at more than 90 percent of the
rated voltage marked on the name plate.
7) Confirm that the cable thickness is as specified in the power sources
specification. (Particularly note the relation between cable length and
thickness.)
8) Never fail to equip a leakage breaker where it is wet or moist.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point, fuse breaking,
disturbance by the normal function of an overload protection device.
• Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)
Installation Manual 11
ENGLISH
CAUTION:
Installation
DIP Switch Setting
1. Indoor Unit
SW1
SW2
Function
Description
Communication N/A (Default)
Cycle
N/A (Default)
SW3
Group Control
Selection of Master or
Slave
SW4
Dry Contact
Mode
Selection of Dry
Contact Mode
SW5
Installation
SW6
Fan continuous
operation
Heater linkage N/A
Ventilator
linkage
SW7
SW8
Selection of Ventilator
linkage
Vane selection Selection of up/down
(Console)
side Vane
Region
selection
Etc.
Selection tropical
region
Spare
Setting Off
Master
Wired/Wireless remote
controller selection of
Manual or Auto
operation Mode
Continuous operation
Removal
-
Setting On Default
Off
Off
Slave
Off
Auto
Off
-
Off
-
Off
Linkage Removal
Working
Up side + Down side Vane
Up side Vane
Only
General model
-
Tropical
model
-
Off
Off
CAUTION
For Multi V Models, DIP switch 1, 2, 6, 8 must be set OFF.
2. Outdoor Unit
In case that the products meet specific conditions, “Auto addressing” function can start automatically
with the improved speed by turning the DIP switch #3 of the outdoor unit and resetting the power.
※ Specific conditions:
- All names of the indoor units are ARNU****4.
- The serial number of Multi V super IV (outdoor units) is after October 2013.
DIP switch
7 segment
Outdoor Unit PCB
12
Indoor Unit
Outdoor Unit DIP Switch
Installation
ENGLISH
Group Control Setting
1. Group Control 1
n Wired remote controller 1 + Standard Indoor Units
LGAP Network System
or
Master
Slave
Display Error Message
°C / °F (5 s)
Slave
Slave
GND
Signal
12 V
Only connect serial signal and GND lines
between indoor units.
Master
TIME (3 s)
n DIP Switch in PCB
¿ Master Setting
- No. 3 Off
¡ Slave Setting
- No. 3 On
Indoor Unit DIP Switch
Some products have no DIP switch on PCB. It is possible to set indoor units to Master or Slave by
using the wireless remote controller instead of DIP switch.
For the details of the setting, please refer to the manual of the wireless remote controller.
1. It is possible to 16 indoor units(Max.) by one wired remote controller.
Set only one indoor unit to Master, set the others to Slave.
2. It is possible to connect with every type of indoor units.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
- The Master indoor unit is possible to recognize Dry Contact and Central Controller only.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired remote
controller.
It is possible to control the other indoor units except the error units.
Installation Manual 13
Installation
h It is possible to connect indoor units since Feb. 2009.
h It can be the cause of malfuctions when there is no setting of master and slave.
h In case of Group Control, it is possible to use following functions.
- Selection of operation, stop or mode
- Temperature setting and room temperature check
- Current time change
- Control of flow rate (High/Middle/Low)
- Reservation settings
It is not possible to use some functions.
2. Group Control 2
n Wired remote controllers + Standard Indoor Units
LGAP Network System
or
Master
Master
Slave
Slave
Donʼt connect serial 12V line
Display Error Message
°C / °F (5 s)
Master
Master
TIME (3 s)
h It is possible to control 16 indoor units(Max.) with the master wired remote control.
h Other than those, it is same with the Group Control 1.
14
Indoor Unit
GND
Signal
12 V
Installation
ENGLISH
3. Group Control 3
n Mixture connection with indoor units and Fresh Air Intake Unit
LGAP Network System
or
FAU
Master
Master
Master
FAU
Slave
Slave
N
M
Display Error Message
Display Error Message
°C / °F (5 s)
GND
Signal
12 V
Master
Master
TIME (3 s)
h In case of connecting with standard indoor unit and Fresh Air Intake Unit, separate Fresh Air
Intake Unit with standard units. (N, M ≤ 16) (Because setting temperature are different.)
h Other than those, it is same with Group Control 1.
FAU
FAU
Standard
Standard
FAU
FAU
Standard
Standard
* FAU : Fresh Air Intake Unit
Standard: Standard Indoor Unit
Installation Manual 15
Installation
4. 2 Remote Control
n Wired remote controller 2 + Indoor unit 1
LGAP Network System
or
Slave
Master
Slave
Slave
GND
Signal
12 V
Display Error Message
°C / °F (5 s)
TIME (3 s)
Master
Slave
1. It is possible to connect two wired remote controllers (Max.) with one indoor unit.
Set only one indoor unit to Master, set the others to Slave.
Set only one wired remote controller to Master, set the others to Slave.
2. Every types of indoor unit is possible to connect two remote controller.
3. It is possible to use wireless remote controller at the same time.
4. It is possible to connect with Dry Contact and Central controller at the same time.
5. In case that any error occurs at indoor unit, the error code is displayed on the wired
remote controller.
6. There isnʼt limits of indoor unit function.
16
Indoor Unit
Installation
Indoor unit 2 EA +Wired remote controller 1 EA
h PZCWRCG3 cable used for connection
Indoor unit 1 EA +Wired remote controller 2 EA
h PZCWRC2 cable used for connection
Slave
Master
PZCWRC2
PZCWRCG3
Master
Master
Slave
CAUTION
• Apply totally enclosed noncombustible conduit in case of local building code Requiring plenum
cable usage.
Installation Manual 17
ENGLISH
5. Accessories for group control setting
It is possible to set group control by using below accessories.
Installation
Model Designation
ARN
U
07
G
CE
A
4
Serial Number
Combinations of functions
A:Basic function
L: Neo Plasma(Wall Mounted)
C: Plasma(Ceiling Cassette)
G: Low Static
K: High Sensible Heat
U: Floor Standing without Case
SE/S8 - R: Mirror V: Silver B:Blue(ART COOL Type Panel Clolr)
SF
- E: Red V: Silver G:Gold 1: Kiss (Photo changeable)
Q: Console
Z: Fresh Air Intake Unit
Chassis Name
Electrical Ratings
3:1Ø, 208/230V, 60Hz
G:1Ø, 220 - 240V, 50Hz/1Ø, 220V, 60Hz
(Only 50Hz for Australia)
Total Cooling Capacity in Btu/h
EX) 5,000 Btu/h ➝ '05'
18,000 Btu/h ➝ '18'
Combination of Inverter Type and
Cooling Only or Heat Pump
N: AC Inverter and H/P
V: AC Inverter and C/O
U: DC Inverter and H/P and C/O
System with Indoor Unit using R410A
❈ LGETA:U Ex) URN
Airborne Noise Emission
The A-weighted sound pressure emitted by this product is below 70 dB.
** The noise level can vary depending on the site.
The figures quoted are emission level and are not necessarily safe working levels. Whilst there is a
correlation between the emission and exposure levels, this cannot be used reliably to determine
whether or not further precautions are required. Factor that influence the actual level of exposure of the
workforce include the characteristics of the work room and the other sources of noise, i.e. the number
of equipment and other adjacent processes and the length of time for which an operator exposed to the
noise. Also, the permissible exposure level can vary from country to country. This information, however,
will enable the user of the equipment to make a better evaluation of the hazard and risk.
Limiting concentration
Limiting concentration is the limit of Freon gas concentration where immediate measures can be
taken without hurting human body when refrigerant leaks in the air. The limiting concentration shall
be described in the unit of kg/m3 (Freon gas weight per unit air volume) for facilitating calculation
Limiting concentration: 0.44kg/m3 (R410A)
n Calculate refrigerant concentration
Total amount of replenished refrigerant in refrigerant facility (kg)
Refrigerant concentration =
Capacity of smallest room where indoor unit is installed (m3)
18
Indoor Unit
PT.LG Electronics Indonesia
Gandaria 8 Office Tower Lt. 29 BC & 31 ABCD
Jl.Sultan Iskandar Muda, Kebayoran Lama Utara - Kebayoran Lama,
Jakarta Selatan - DKI Jakarta Raya, Indonesia