Pentair IntelliPro VSF Pump Owner Manual
INTELLIPRO® VSF
VARIABLE SPEED AND FLOW PUMP
INSTALLATION AND
USER’S GUIDE
IMPORTANT SAFETY INSTRUCTIONS
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
i
CUSTOMER SERVICE / TECHNICAL SUPPORT
If you have questions about ordering Pentair Aquatic Systems replacement parts, and pool products, please contact:
Customer Service and Technical Support, USA
(8 A.M. to 4:30 P.M. — Eastern/Pacific Times)
Phone: (800) 831-7133
Fax: (800) 284-4151
Sanford, North Carolina (8 A.M. to 4:30 P.M. ET)
Phone: (919) 566-8000
Fax: (919) 566-8920
Web site
Visit www.pentairpool.com or www.staritepool.com for
information about Pentair products.*
Moorpark, California (8 A.M. to 4:30 P.M. PT)
Phone: (805) 553-5000 (Ext. 5591)
Fax: (805) 553-5515
TABLE OF CONTENTS
Important Pump Warning and
Safety Instructions ................................................ ii
Pump Overview ......................................................
Drive Assembly and Control Panel
External Control
Motor Features
Drive Features
1
1
1
1
1
Installation ..............................................................
Location
Piping
Electrical Requirements
Optional Keypad Relocation Kit
Fittings and Valves
Electrical Installation
Wiring, Grounding and Bonding
Connecting to an Automation System
2
2
2
2
2
2
3
3
4
Operating the Pump ..............................................
Priming the Pump
Using the Operator Control Panel
Stopping and Starting the Pump
Adjusting and Saving a Pump Speed/Flow
Operating the Pump at Preset Speeds
Pump Operating Modes
Program Types
Control Panel: Pump Menu Guide
5
5
6
7
7
7
7
7
8
Pump Settings .......................................................
Set Date and Time
Set AM/PM or 24-Hour Clock
Set Min/Max Speeds
Set Min/Max Flow Rates
Set Flow Limit for Speed Program
Set Maximum System Pressure
Set Pressure Limit for Speed Program
Pump Address
Set Screen Contrast
Set Control Panel Language
Set Temperature Unit
Password Protection
Setting Password
Set Ramping Rate
10
10
10
10
10
11
11
12
12
12
12
12
13
13
13
Setting Programs 1-8 ............................................
Pump Operating Modes
Set Programs 1-4 in Manual Mode
Set Programs 1-4 in Egg-Timer Mode
Set Programs 1-8 in Schedule Mode
14
14
14
14
15
External Control .................................................... 16
Features ................................................................. 17
Time Out
17
Quick Clean/Only High Speed Override Feature 17
Priming ..................................................................
Priming Features
Setting Priming Features
Disabling Priming with an Automation System
17
18
19
19
Thermal Mode ....................................................... 20
Maintenance ..........................................................
Pump Strainer Basket
Cleaning the Pump Strainer Basket
Winterizing
21
21
21
21
Servicing ...............................................................
Motor and Drive Care
Shaft Seal Replacement
Pump Disassembly
Pump Reassembly
Drive Assembly Removal and Installation
22
22
22
22
23
23
Troubleshooting .................................................... 25
Alerts and Warnings
25
Troubleshooting Chart
26
Replacement Parts ............................................... 28
Technical Data .......................................................
Pump Dimensions
Electrical Specifications
Pump Performance Curves
Operator Control Panel Quick Reference Guide
29
29
29
29
30
* Translated versions of this manual are available online at / La versión en español de este manual del producto, se puede encontrar en línea a /
La version française de ce manuel est disponible à : https://pentairpool.com/en/products/pumps/intellipro%20vsf#resources
P/N 356654 Rev. D 7/17/18
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
ii
IMPORTANT PUMP WARNING AND SAFETY INSTRUCTIONS
IMPORTANT NOTICE
This guide provides installation and operation instructions for this pump.
Consult Pentair with any questions regarding this equipment.
Attention Installer: This guide contains important information about the
installation, operation and safe use of this product. This information should
be given to the owner and/or operator of this equipment after installation
or left on or near the pump.
Attention User: This manual contains important information that will help
you in operating and maintaining this product. Please retain it for future
reference.
READ AND FOLLOW ALL INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This is the safety alert symbol. When you see this
symbol on your system or in this manual, look for
one of the following signal words and be alert to
the potential for personal injury.
Warns about hazards that can cause death,
serious personal injury, or major property damage
if ignored.
Warns about hazards that may cause death,
serious personal injury, or major property damage
if ignored.
Warns about hazards that may or can cause minor
personal injury or property damage
if ignored.
NOTE
Indicates special instructions not related to hazards.
When installing and using this electrical equipment, basic safety
precautions should always be followed, include the following:
Do not permit children to use this product.
RISK OF ELECTRICAL SHOCK. Connect only to
a branch circuit protected by a ground-fault circuitinterrupter (GFCI). Contact a qualified electrician if you cannot verify that
the circuit is protected by a GFCI.
This unit must be connected only to a supply circuit
that is protected by a ground-fault circuit-interrupter
(GFCI). Such a GFCI should be provided by the installer and should
be tested on a routine basis. To test the GFCI, push the test button.
The GFCI should interrupt power. Push the reset button. Power should
be restored. If the GFCI fails to operate in this manner, the GFCI is
defective. If the GFCI interrupts power to the pump without the test button
being pushed, a ground current is flowing, indicating the possibility of an
electric shock. Do not use this pump. Disconnect the pump and have the
problem corrected by a qualified service representative before using.
This pump is for use with permanent swimming
pools and may also be used with hot tubs and spas
if so marked. Do not use with storable pools. A permanently-installed pool
is constructed in or on the ground or in a building such that it cannot be
readily disassembled for storage. A storable pool is constructed so that
it is capable of being readily disassembled for storage and reassembled
to its original integrity.
SUCTION ENTRAPMENT HAZARD: STAY OFF
THE MAIN DRAIN AND AWAY FROM ALL SUCTION
OUTLETS!
F
Carefully read and follow all safety instructions in this manual and on
equipment. Keep safety labels in good condition; replace if missing
or damaged.
General Warnings
• Never open the inside of the drive motor enclosure. There is a
capacitor bank that holds a 230 VAC charge even when there is no
power to the unit.
• The pump is not submersible.
• The pump is capable of high flow rates; use caution when installing
and programming to limit pumps performance potential with old or
questionable equipment.
• Code requirements for electrical connection differ from country to
country, state to state, as well as local municipalities. Install equipment
in accordance with the National Electrical Code and all applicable
local codes and ordinances.
• Before servicing the pump; switch OFF power to the pump by
disconnecting the main circuit to the pump.
• This appliance is not intended for use by persons (including children) of
reduced physical, sensory or mental capabilities, or lack of experience
and knowledge, unless they have been given supervision or instruction
concerning the use of the appliance by a person responsible for their
safety.
FAILURE TO FOLLOW ALL INSTRUCTIONS AND
WARNINGS CAN RESULT IN SERIOUS BODILY
INJURY OR DEATH. THIS PUMP SHOULD BE INSTALLED AND
SERVICED ONLY BY A QUALIFIED POOL SERVICE PROFESSIONAL.
INSTALLERS, POOL OPERATORS AND OWNERS MUST READ
THESE WARNINGS AND ALL INSTRUCTIONS IN THE OWNER’S
MANUAL BEFORE USING THIS PUMP. THESE WARNINGS AND
THE OWNER’S MANUAL MUST BE LEFT WITH THE POOL OWNER.
THIS PUMP PRODUCES HIGH LEVELS OF SUCTION AND CREATES
A STRONG VACUUM AT THE MAIN DRAIN AT THE BOTTOM OF THE
BODY OF WATER. THIS SUCTION IS SO STRONG THAT IT CAN TRAP
ADULTS OR CHILDREN UNDER WATER IF THEY COME IN CLOSE
PROXIMITY TO A DRAIN OR A LOOSE OR BROKEN DRAIN COVER
OR GRATE.
THE USE OF UNAPPROVED COVERS OR ALLOWING USE OF
THE POOL OR SPA WHEN COVERS ARE MISSING, CRACKED OR
BROKEN CAN RESULT IN BODY OR LIMB ENTRAPMENT, HAIR
ENTANGLEMENT, BODY ENTRAPMENT, EVISCERATION AND/OR
DEATH.
The suction at a drain or outlet can cause:
Limb Entrapment: When a limb is sucked or inserted into an opening
resulting in a mechanical bind or swelling. This hazard is present when
a drain cover is missing, broken, loose, cracked or not properly secured.
Hair Entanglement: When the hair tangles or knots in the drain cover,
trapping the swimmer underwater. This hazard is present when the flow
rating of the cover is too small for the pump or pumps.
Body Entrapment: When a portion of the body is held against the drain
cover trapping the swimmer underwater. This hazard is present when the
drain cover is missing, broken or the cover flow rating is not high enough
for the pump or pumps.
Evisceration/Disembowelment: When a person sits on an open pool
(particularly a child wading pool) or spa outlet and suction is applied directly
to the intestines, causing severe intestinal damage. This hazard is present
when the drain cover is missing, loose, cracked, or not properly secured.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
iii
IMPORTANT PUMP WARNING AND SAFETY INSTRUCTIONS
Mechanical Entrapment: When jewelry, swimsuit, hair decorations, finger,
toe or knuckle is caught in an opening of an outlet or drain cover. This
hazard is present when the drain cover is missing, broken, loose, cracked,
or not properly secured.
NOTE: ALL SUCTION PLUMBING MUST BE INSTALLED IN
ACCORDANCE WITH THE LATEST NATIONAL AND LOCAL CODES,
STANDARDS AND GUIDELINES.
TO MINIMIZE THE RISK OF INJURY DUE TO
SUCTION ENTRAPMENT HAZARD:
• A properly installed and secured ANSI/ASME A112.19.8 approved
anti-entrapment suction cover must be used for each drain.
• Each suction cover must be installed at least three (3’) feet apart, as
measured from the nearest point to nearest point.
• Regularly inspect all covers for cracks, damage and advanced
weathering.
• If a cover becomes loose, cracked, damaged, broken or is missing,
replace with an appropriate certified cover.
• Replace drain covers as necessary. Drain covers deteriorate over
time due to exposure to sunlight and weather.
• Avoid getting hair, limbs or body in close proximity to any suction
cover, pool drain or outlet.
• Disable suction outlets or reconfigure into return inlets.
A clearly labeled emergency shut-off switch for the
pump must be in an easily accessible, obvious place.
Make sure users know where it is and how to use it in case of emergency.
The Virginia Graeme Baker (VGB) Pool and Spa Safety Act creates
new requirements for owners and operators of commercial swimming
pools and spas.
Commercial pools or spas constructed on or after December 19, 2008,
shall utilize:
(A) A multiple main drain system without isolation capability with suction
outlet covers that meet ASME/ANSI A112.19.8a Suction Fittings for
Use in Swimming Pools, Wading Pools, Spas, and Hot Tubs and either:
(i) A safety vacuum release system (SVRS) meeting ASME/ANSI
A112.19.17 Manufactured Safety Vacuum Release systems (SVRS)
for Residential and Commercial Swimming Pool, Spa, Hot Tub,
and Wading Pool Suction Systems and/or ASTM F2387 Standard
Specification for Manufactured Safety Vacuum Release Systems
(SVRS) for Swimming pools, Spas and Hot Tubs or
(ii) A properly designed and tested suction-limiting vent system or
(iii) An automatic pump shut-off system.
Commercial pools and spas constructed prior to December 19, 2008,
with a single submerged suction outlet shall use a suction outlet cover
that meets ASME/ANSI A112.19.8a and either:
(A) A SVRS meeting ASME/ANSI A112.19.17 and/or ASTM F2387, or
(B) A properly designed and tested suction-limiting vent system, or
(C) An automatic pump shut-off system, or
(D) Disabled submerged outlets, or
(E) Suction outlets shall be reconfigured into return inlets.
For Installation of Electrical Controls at Equipment Pad (ON/OFF
Switches, Timers and Automation Load Center)
Install all electrical controls at equipment pad, such as
on/off switches, timers, and control systems, etc. to
allow the operation (startup, shut-down, or servicing)
of any pump or filter so the user does not place any
portion of his/her body over or near the pump strainer
lid, filter lid or valve closures. This installation should
allow the user enough space to stand clear of the filter
and pump during system start-up, shut down or servicing of the system filter.
HAZARDOUS PRESSURE: STAND CLEAR OF
PUMP AND FILTER DURING START UP
Circulation systems operate under high pressure.
When any part of the circulating system (i.e.
locking ring, pump, filter, valves, etc.) is serviced,
air can enter the system and become pressurized.
Pressurized air can cause the pump housing cover, filter lid, and valves
to violently separate which can result in severe personal injury or death.
Filter tank lid and strainer cover must be properly secured to prevent
violent separation. Stand clear of all circulation system equipment when
turning on or starting up pump.
Before servicing equipment, make note of the filter pressure. Be sure
that all controls are set to ensure the system cannot inadvertently start
during service. Turn off all power to the pump. IMPORTANT: Place filter
manual air relief valve in the open position and wait for all pressure
in the system to be relieved.
Before starting the system, fully open the manual air relief valve and place
all system valves in the “open” position to allow water to flow freely from the
tank and back to the tank. Stand clear of all equipment and start the pump.
IMPORTANT: Do not close filter manual air relief valve until all
pressure has been discharged from the valve and a steady stream
of water appears. Observe filter pressure gauge and be sure it is not
higher than the pre-service condition.
General Installation Information
• All work must be performed by a qualified service professional, and
must conform to all national, state, and local codes.
• Install to provide drainage of compartment for electrical components.
• These instructions contain information for a variety of pump models
and therefore some instructions may not apply to a specific model. All
models are intended for use in swimming pool applications. The pump
will function correctly only if it is properly sized to the specific application
and properly installed.
Pumps improperly sized or installed or used in
applications other than for which the pump was
intended can result in severe personal injury or death. These risks
may include but not be limited to electric shock, fire, flooding, suction
entrapment or severe injury or property damage caused by a structural
failure of the pump or other system component.
The pump can produce high levels of suction within
the suction side of the plumbing system. These
high levels of suction can pose a risk if a person comes within the close
proximity of the suction openings. A person can be seriously injured
by this high level of vacuum or may become trapped and drown. It is
absolutely critical that the suction plumbing be installed in accordance
with the latest national and local codes for swimming pools.
Pumps and replacement motors that are single speed and
one (1) Total HP or greater cannot be sold, offered for sale, or
installed in a residential pool for filtration use in California, Title
20 CCR sections 1601-1609.
Warnings and safety instructions for Pentair Aquatic Systems pumps
and other related products are available at:
http://www.pentairpool.com/pool-owner/safety-warnings/ or call
(800) 831-7133 for additional free copies of these instructions.
Please refer to http://www.pentairpool.com/pool-owner/safetywarnings/ for warning and safety instructions related to the this
product.
INTELLIPRO VSF Variable Speed and Flow Pump Installation and User’s Guide
®
Warning Page P/N 352557 Rev. C 7/18
1
PUMP OVERVIEW
The IntelliPro® VSF Variable Speed and Flow Pump
can be programmed to run at a speed or a constant
flow rate over set time intervals for maximum operating
efficiency and energy conservation for a variety of
inground pools.
•
•
•
•
•
•
•
•
The pump can operate from 450 RPM to 3450 RPM
with four preset speeds of 750, 1500, 2350 and 3110
RPM, or the pump can be set to control its own speed
and maintain a constant flow rate.
The pump can adapt to applications between 20 and
140 GPM. Simply program the pump to the desired
flow rate, and the pump will automatically adjust to
operating conditions to maintain that specific flow rate.
Up to 8 customizable programs that can be set for
constant flow or speed in either Manual, Egg Timer
or Schedule modes.
Pump control panel alarm LED and error messages
warn the user of improper operation.
Programmable priming mode with automatic detection
of prime for easy start-up and automatic detection of
loss of prime.
Compatible with most cleaning systems, filters, and
jet action spas.
UL/CUL/NSF
WEF 6.6 THP 3.95
Drive Assembly and Control Panel
The IntelliPro VSF pump drive is designed to produce
maximum motor operational efficiency. The drive controls
the motor’s rotational speed by controlling the frequency
of the supplied current. It also protects the motor and
pump from operating outside of their intended operating
parameters.
The control panel can be mounted on the pump in four
different directions in order to provide the user the best
access. The control panel can also be mounted in a more
convenient location with the help of the keypad relocation
kit (P/N 356905Z).
Operator Control Panel Cover
Buttons and LED (Beneath)
External Control
Most Pentair automation systems and IntelliComm®
Communication Centers can remotely control the
IntelliFlo VSF pump. The pump’s communications
address and other functions are accessible from the
pump’s control panel.
•
•
RS-485 communication cable included
IntelliComm systems control one IntelliFlo pump using
the 4 External Control programs.
Refer to the automation system manual for further
details on how to connect and use the system with
your variable speed pump.
Motor Features
• High Efficiency Permanent Magnet Synchronous
•
•
•
•
•
•
Motor (PMSM)
Superior speed control
Operates at lower temperatures due to high
efficiency
Designed to withstand outdoor environment
Totally Enclosed Fan Cooled (TEFC) Motor
56 Square Flange
Low noise
Drive Features
• Active Power Factor Correction
• UL 60730 Compliant
• Rotatable Keypad
• Easy Overhead Wiring
• High Drive Operational Efficiency
• Sensorless Flow and Pressure Control
Technology
• Loss of Prime Detection
Communication port for connection
to automation systems or
communication centers via two-wire
RS-485 cable (not shown)
Strain Relief Port for
Incoming AC Power
Motor Stand
Variable Speed and Flow Drive Assembly
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
2
INSTALLATION
Only a qualified plumbing professional should install the IntelliPro® VSF Variable Speed and Flow Pump. Refer to
“Important Pump Warning And Safety Instructions” on pages ii - iii for additional installation and safety information.
Note: The IntelliPro VSF pump cannot be connected in series with other pumps.
Location
6 IN.
(15.2 CM)
MINIMUM
Note: Do not install this pump within an outer enclosure or
beneath the skirt of a hot tub or spa unless marked accordingly.
Note: Ensure that the pump is mechanically secured to
the equipment pad.
Be sure the pump location meets the following
requirements:
3 IN.
(7.6 CM)
MINIMUM
1. Install the pump as close to the pool or spa as possible.
To reduce friction loss and improve efficiency, use short,
direct suction piping returns.
2. Install a minimum of 5 feet (1.52 meters) from the inside
wall of the pool and spa. Canadian installations require
a minimum of 9.8 feet (3 meters) from pool water level.
3. Install the pump a minimum of 3 feet (.9 meters) from
the heater outlet.
Figure 1: Pump Rear and Overhead Clearance
MIN 5 X SUCTION PIPE DIAMETER
ELBOW
4. Do not install the pump more than 10 feet (3.1 meters)
above the water level.
5. Install the pump in a well ventilated location protected
from excessive moisture (i.e., rain gutter downspouts,
sprinklers, etc.)
6. Install the pump with a rear clearance of at least 3-inches
(76.2 mm) so that the motor can be removed easily for
maintenance and repair. See Figure 1.
Piping
1. For improved pool plumbing, it is recommended to use
a larger pipe size. When installing the inlet and outlet
fittings (male adaptors), use thread sealant.
2. Piping on the suction side of the pump should be the
same or larger than the return line diameter.
3. Plumbing on the suction side of the pump should be as
short as possible.
4. For most installations Pentair recommends installing
a valve on both the pump suction and return lines
so that the pump can be isolated during routine
maintenance. We also recommend a valve, elbow or
tee installed in the suction line should be no closer to
the front of the pump than five (5) times the suction
line pipe diameter. See Figure 2.
Example: A 2-inch pipe requires a 10-inch (254 mm)
straight run in front of the suction inlet of the pump).
This will help the pump prime faster and last longer.
Note: DO NOT install 90° elbows directly into the pump
inlet and outlet.
Electrical Requirements
•
Install all equipment in accordance with the National
Electrical Code and all applicable local codes and
ordinances.
•
A means for disconnection must be incorporated in the
fixed wiring in accordance with the wiring rules.
Figure 2: Recommended Piping
Optional Keypad Relocation Kit
In special cases when the user lacks easy or convenient
access to the IntelliPro VSF pump, a Keypad Relocation
Kit (P/N 356905Z) may be purchased from your local
pool equipment supplier. This kit allows the user to
remove the keypad from the top of the drive and mount
the keypad in a fixed location with better access.
For installation instructions refer to the Keypad
Relocation Kit Installation Instructions provided with
the kit.
Fittings and Valves
1. Do not install 90° elbows directly into pump inlet.
2. Flooded suction systems should have valves installed
on suction and discharge pipes for maintenance,
however, the suction valve should be no closer than
five times the suction pipe diameter as described
in this section.
3. Use a check valve in the discharge line when
using this pump for any application where there is
significant height to the plumbing after the pump.
4. Be sure to install check valves when plumbing in
parallel with another pump. This helps prevent
reverse rotation of the impeller and motor.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
3
Electrical Installation
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION. This pump must be installed by a licensed or certified electrician or
a qualified service professional in accordance with the National Electrical Code and all applicable local codes and ordinances.
Improper installation will create an electrical hazard which could result in death or serious injury to users, installers, or others due
to electrical shock, and may also cause damage to property.
Always disconnect power to the pump at the circuit breaker before servicing the pump. Failure to do so could result in death or
serious injury to service people, users or others due to electric shock.
Read all servicing instructions before working on the pump.
Note: ALWAYS reinstall the drive lid onto the field wiring compartment when leaving the pump unsupervised during
servicing. This will prevent foreign matter (i.e. rainwater, dust, etc.) from accumulating in the drive.
Note: When connecting the pump to an automation system, continuous power must be supplied to the pump
by connecting it directly to the circuit breaker. When using an automation system, be sure that no other lights or
appliances are on the same circuit.
Wiring
Grounding
1. Be sure all electrical breakers and switches are turned
off before wiring motor.
1. Permanently ground the drive using the green ground
screw, as shown below. Use the correct wire size and
type specified by National Electrical Code. Be sure
the ground wire is connected to an electrical service
ground.
STORED CHARGE - Wait at least sixty (60)
seconds before servicing.
2. Be sure that the supply voltage meets the requirements
listed on the motor nameplate. If these requirements
are not met, permanent damage may occur.
3. For wiring sizes and general guidelines for proper
electrical installation, please follow the specifications
defined in the National Electric Code and any local
codes as required.
4. Use strain relief and be sure all electrical connections
are clean and tight.
5. Cut the wires to the appropriate length so they do
not overlap or touch when connected.
6. Reinstall the keypad after wiring the pump by plugging
the cover back into the drive wiring connection and
re-seating the keypad in the desired orientation with
the four (4) corner screws.
Note: Ensure that the keypad cable is not pinched
between the drive and keypad during re-seating.
2. The pump should be permanently connected to either
a circuit breaker, 2-pole timer or 2-pole relay.
Note: If AC power is supplied by a GFCI circuit breaker,
the pump should be wired on its own independent
circuit unless the pump is operated in tandem
with a Pentair salt chlorine generator.
Bonding
1. Bond the motor to the structure in accordance with the
National Electrical Code. Use a solid copper bonding
conductor not smaller than 8 AWG. For Canadian
installations, a 6 AWG or larger solid copper bonding
conductor is required. Run a wire from the external
bonding screw or lug to the bonding structure.
2. Connect the wire from the accessible bonding lug on
the motor to all metal parts of the swimming pool, spa,
or hot tub structure and to all electrical equipment,
metal conduit, and metal piping within 5 feet (1.52
meters) of the inside walls of the swimming pool,
spa, or hot tub. Run a wire from the external bonding
screw or lug to the bonding structure.
Drive Wiring
Connection
1/2” NPT
Conduit Port
Ground Wire
Connection
(Green Screw)
Note: When the pump is started and stopped by removing
power with a relay or timer, a two-pole device should
be used to apply and remove power to both POWER
LINE TERMINALS.
Pentair offers 2-Pole 20 Amp GFCI breakers (P/N
PA220GF) which offer personnel protection while
meeting 2008 to current NEC Standards for Pool
Pumps.
Bonding Lug
Field Wiring Compartment
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
4
Connecting to an Automation System
All IntelliFlo and IntelliPro pumps, including the IntelliPro®
VSF Variable Speed and Flow Pump, are compatible with
Pentair Automation Systems.
An RS-485 communication cable is provided with the
pump and will be used to connect the pump to a Pentair
automation system.
Refer to the automation system manual for further
details on how to connect and use the system with
your variable speed pump.
An IntelliTouch® Control System with
firmware 1.170 or earlier will display
"VSF+SVRS" in the pump type/selection. While you will
choose this option, the IntelliPro VSF pump DOES NOT
incorporate SVRS entrapment protection.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
5
OPERATING THE PUMP
NOTE: When setting up the IntelliPro® VSF Variable Speed and Flow Pump, the user must set the pump’s internal clock and
establish an operation schedule by following the steps in this manual. Please refer to user’s guide sections: ‘Set Time’ (page 10)
and ‘Set Programs 1-8 in Schedule Mode’ (page 15) to schedule a time to run the pump.
This pump is shipped with Priming mode ENABLED. Unless the Priming settings are changed in the menu, be aware
that the pump will speed up to the maximum speed when the pump is powered on for the first time, and the
Start/Stop button is pressed. To change the maximum speed of the pump, refer to page 10.
Before turning the pump ON, be sure the following conditions are met:
1. Open filter air relief valve.
2. Open valves.
3. Pool return is completely open and clear of any blockages.
4. Water in the pump basket.
5. Stand clear of the filter or other pressurized vessels.
Priming the Pump
Prime the pump before starting the pump for the first
time. Remove the lid and fill the basket with water. The
pump basket must be filled with water before initial
start up or after servicing.
Follow the steps below to prime the pump for start up:
Lid
Locking
Ring
Volute
1. Press Start/Stop to stop the pump. Disconnect the
pump main power supply and communication cable.
2. Close all valves in suction and discharge pipes.
Relieve all pressure from the system.
3. Remove the pump lid and locking ring.
Top View
4. Fill the pump strainer pot with water.
5. Reassemble the pump lid and locking ring onto the
strainer basket. The pump is now ready to prime.
6. Open all valves in suction and discharge pipes.
7. Open the filter air relief valve and stand clear of the
filter.
8. Connect power to the pump. Be sure green power
light is on.
9. Press Start/Stop to start the pump. The pump will
enter into priming mode (if enabled) and speed
up to the maximum speed set in the pump menu
settings.
10. When water comes out of the filter air relief valve,
close the valve. The system should now be free of
air and recirculating water to and from the pool
11. Do not allow your pump to run longer than 30
minutes time without developing full flow. If the
pump does not prime, check your priming settings
on the control panel or see the “Troubleshooting”
section on pages 25-27.
Priming Features
The default priming setting is ENABLED.
The pump also allows you to set the following from
the operator control panel:
• Priming speed
• Priming range (1-10)
• Priming delay
Set up instructions on page 19.
Do not add chemicals to the system directly
in front of pump suction. Adding undiluted
chemicals may damage the pump and will void the warranty.
This is a variable speed pump. Typically
the lower speeds are used for filtration and
heating. The higher speeds can be used for spa jets, water
features, and priming.
DO NOT run the pump dry. If the pump is run dry, the mechanical seal will be damaged and the pump will start
leaking. If this occurs, the damaged seal must be replaced. ALWAYS maintain proper water level in your pool
(half way up skimmer opening). If the water level falls below the skimmer opening, the pump will draw air through the skimmer, losing
the prime and causing the pump to run dry, resulting in a damaged seal. Continued operation in this manner could cause a loss of
pressure, resulting in damage to the pump case, impeller and seal and may cause property and personal injury.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
6
Using the Operator Control Panel
Use the operator control panel to start and stop the IntelliPro®
VSF Variable Speed and Flow Pump, set, and change programs,
and access pump features and settings.
Key Lockout Icon
Controls and LEDs on Keypad
13
Button 1: Press to select Program 1 (750 RPM). LED on
indicates Program 1 is active.
Button 2: Press to select Program 2 (1500 RPM). LED on
indicates Program 2 is active.
Button 3: Press to select Program 3 (2350 RPM). LED on
indicates Program 3 is active.
Button 4: Press to select Program 4 (3110 RPM). LED on
indicates Program 4 is active.
Back: Goes one step back in menu; exits without saving
current setting.
Save: Saves current menu item setting. When a parameter
has been adjusted the "Save?" icon will be displayed.
Menu: Accesses the menu items when and if the pump is
stopped.
Select: Press to select the currently displayed option on the
screen.
Arrow buttons:
• Up arrow: Move one level up in the menu or increase
a digit when editing a setting.
• Down arrow: Move one level down in the menu or
decrease a digit when editing a setting.
• Left arrow: Move cursor left one digit when editing a
setting.
• Right arrow: Move cursor right one digit when editing
a setting.
Quick Clean: Pump increases to a higher RPM (for
vacuuming, cleaning, adding chemicals, etc.). LED light is
on when active.
Time Out: Allow the pump to remain in a stopped state for
a set period of time before resuming normal operation. LED
is on when active.
Start/Stop button: To start or stop the pump. When LED is
on, the pump is running or in a mode to start automatically.
Reset button: Reset alarm or alert.
14
LEDs:
1
2
3
4
5
6
7
8
9
10
11
12
12:15p
750 RPM
T 0.00 150 WATTS
Running Speed 1
1
1
2
4
3
4
3
2
5
Back
6
Save
7
Menu
Select
8
Time
Out
Quick
Clean
Control Panel #1-8
Active Cursors
12:15p
Line 1
Current Time
Line 2
750 RPM
Line 3
T 0.00 150 WATTS
Current Power Usage
Line 4
Running Speed 1 Save?
"Save?" Icon
15
1
2
3
Back
Current Speed/Flow
Countdown Time
4
Current Running
Feature
Save
On: Green light when pump is powered on.
Warning: On if warning condition is present. See
“Alerts and Warnings” on page 25.
15
Alarm: Red LED on if alarm condition occurs. See
“Alerts and Warnings” on page 25.
Control Panel LCD Screen:
• Line 1: Key icon indicates password protection mode is
active. If password protect is not enabled, no key icon is
displayed. Also shows current time of day. Active cursors
display when arrow key input is available.
• Line 2: Displays current pump speed/flow (RPM/GPM).
• Line 3: Countdown time and watts
• Line 4: Current pump status and current feature. "Save?"
will display on this line when a parameter adjustment
can be saved.
Select
Menu
14
9
10
Quick
Clean
Time
Out
13
12
11
Control Panel #9-15
Note: Always close the keypad cover after using
the keypad.
Note: Using screwdrivers or pens to program the
pump will damage the keypad overlay. Use your
fingers only when programming the pump.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
7
Stopping and Starting the Pump
Pump Operating Modes
Starting the Pump
The IntelliPro® VSF Variable Speed and Flow Pump can
be programmed in three different modes:
1. Be sure the pump is powered on and the green
power LED is on.
2. Select one of the program buttons, then press the
Start/Stop button (LED on) to start the pump. The
pump will go into priming mode if priming feature
is enabled.
Programs 1-4 can be programmed in all three modes.
Programs 5-8 can only be programmed in Schedule
mode since there are no buttons on the control panel
for Programs 5-8. The default setting for Programs 5-8
is “Disabled”.
Program 1-4
Stopping the Pump
1. Press Start/Stop to stop the pump.
When servicing equipment (filters, heaters, chlorinators
etc.), disconnect the communication cable, and switch
OFF circuit breaker to remove power from the pump.
Note: The pump can automatically restart if the communication cable is connected.
Set Type
Schedule
Set Type
Set Start Time
Set Stop Time
Egg Timer
Set Type
Set Duration
Disabled
Schedule
Program 5-8
Default: Disabled
Set Type
Set Start Time
Set Stop Time
Adjusting and Saving a Pump Speed/Flow
1. While the pump is running, press the Up or Down
arrow to adjust to desired speed or flow setting.
2. Press and hold down a Program button (1-4) for
three (3) seconds to save speed/flow to the button
or press Save to save the speed/flow.
Manual
Set Speed
Set Flow
Set Speed
Set Flow
Set Speed
Set Flow
Set Speed
Set Flow
Program Menu Tree Options
Manual
The pump is programmed with four default speeds of 750,
1500, 2350 and 3110 RPM. Program buttons 1-4 are for
each of the preset speeds as shown below.
Assigns a speed or flow to one of the four Program
buttons on the control panel. This mode can only be
used for programs 1-4. Programs 1 and 2 are Manual
by default.
To operate in Manual mode, press one of the four
program buttons and then press the Start/Stop button.
The pump will run the assigned speed or flow assigned
to that program button.
1. Be sure the pump is powered on and the green
power LED is on.
Egg Timer
Operating the Pump at Preset Speeds
2. Press the Program button (1- 4) corresponding to
the desired preset speed and release quickly. The
LED above the button will turn on.
3. Press Start/Stop. The pump will quickly change to
the selected preset speed.
LED lit
1
2
3
4
Programs 1-4 can be programmed to run at a certain
speed or flow and for a duration of time once a program
button is pressed.
Programs 3 and 4 are Egg Timers by default. If you
desire a different method of operation, programs 3 and
4 can be changed to Manual mode in the control menu.
To operate in Egg Timer mode, press a program button
and then press Start/Stop. The pump will run that
setting for the set amount of time and then turn off.
Schedule
Programs 1-8 start and stop at a specific time during a 24
hour period. Speeds or flows programmed in Schedule
mode will override any manually selected speed or flow
once the next Schedule command commences.
Program Types
This pump can run saved programs at either constant
speeds or constant flow rates. This gives the user the
ability to precisely assign the output from the pump
so that no energy is wasted and the job is completed
accurately.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
8
Operator Control Panel: Pump Menu Guide
MENU
SETTINGS
Press MENU button to access menus
Date and Time
Date
(pages 10-13)
Time
Hour Format
Months (1-12)
Days (1-31)
Years (2010-2100 Plus)
Hours (24hr Mode: 0-23) (12hr Mode: 1-12 AM & PM)
Minutes (0-60)
AM/PM - Default: AM/PM
24 Hour
Min/Max
Set Min Speed (450-1700 RPM) - Default: 450 RPM
Set Max Speed (1900-3450 RPM) - Default: 3450 RPM
Set Min Flow (20-70 GPM) - Default: 20 GPM
Set Max Flow (80-140 GPM) - Default: 140 GPM
Flow Limit Speed (Disabled / Enabled) - Default: Disabled
Max Pressure (1-50 PSI) - Default: 30 PSI
Pressure Limit Speed (Disabled / Enabled) - Default: Disabled
Device
Pump Address (1-16) - Default: 1
Contrast Level (1-5) - Default: 3
English - Default: English
Language
Português
Deutsch
Italiano
Nederlands
Español
Français
Temperature Unit
Fahrenheit - Default: F°
Celsius C°
Flow Unit
GPM - Default: GPM
LPM
M3 / H
Pressure Unit
PSI - Default: PSI
BAR
Password
Disabled - Default: Disabled
Enabled
Password Timeout (1 min. to 6 hrs.) - Default: 1 hour
Set Password (0000 - 9999) - Default: 1234
Fast - Default: Fast
Ramping
Ramp Up
Medium
Slow
Fast - Default: Fast
Ramp Down
Medium
Slow
Firmware Version
Alarm Log (1-10)
PROGRAM 1-8
Program 1-4
(pages 14-15)
Program 5-8
Manual
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM) - Default Program 1-2: Manual
Schedule
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Start Time
Stop Time
Egg Timer
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM) - Default Program 3-4: Egg Timer
Duration
Disabled
Schedule
Default: Disabled
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Start Time
Stop Time
MENU TREE
CONTINUES TO
NEXT PAGE
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
9
Operator Control Panel: Pump Menu Guide (cont.)
MENU TREE
CONTINUED FROM
PREVIOUS PAGE
EXT CONTROL
Program 1
Enabled - Default
(page 16)
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 750 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
Program 2
Enabled - Default
Program 3
Enabled - Default
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 1500 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 2350 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
Program 4
Enabled - Default
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 3110 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
FEATURES
(page 17)
Time Out
Quick Clean
PRIMING
Disabled/Enabled
(pages 17-19)
Priming Speed
Max Priming Duration
Priming Range
THERMAL MODE
(page 20)
Time Out Duration (1 min. to 10 hrs.) Default: 3 hours
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Quick Clean Duration (1 min. to 10 hrs.) Default: 10 minutes
Disabled / Enabled - Default: Enabled
Set Speed (2400-3450 RPM) Default: 3450 RPM
(1 min. to 30 min.) Default: 11 minutes
(1 - 10) Default: 5
Priming Delay
(1 sec. to 10 min.) Default: 20 seconds
Loss of Prime
Enabled / Disabled - Default: Enabled
Disabled/Enabled
Disabled / Enabled - Default: Enabled
Set Type
Set Speed/Flow
Pump Temperature
Speed - Default: Speed
Flow
Set Speed (450-3450 RPM) Default 1000 RPM
Set Flow (20-140 GPM) Default: 40 GPM
40° F - 50° F (4.4° C through 10° C) Default: 40° F (4.4° C)
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
10
MENU
SETTINGS
Pump Menu: Settings
Set Date and Time
The time controls all scheduled times, functions, and
programmed cycles and stores the correct time for up
to 96 hours after power is turned off. Reset if the power
is off longer than 96 hours.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Date and
Time”. Press Select.
5. Press Select again and use Up or Down arrows to
set the date.
6. Press Save to save user input and return to "Date
and Time."
7. Use the Up or Down arrows to scroll to “Time”. Press
Select.
8. Use the Up or Down arrows to scroll to edit the time.
Note: To set AM/PM or a 24 hour clock see the next
section "Set AM/PM or 24 Hour Clock."
9. Press Save to save. To cancel any changes, press
Back to exit without saving.
10. Press Back to exit.
Set AM/PM or 24-Hour Clock
To change the time from a 12 hour clock (AM/PM) to a
24 hour clock:
1. Press Menu.
2. Press Select to select “Settings”.
3. Use the Up or Down arrows to scroll to “Date and
Time". Press Select.
4. Use the Up or Down arrows to scroll to "AM/PM".
Press Select.
5. Use the Up or Down arrows to scroll to choose
between 24 hr. and AM/PM.
6. Press Save to save. To cancel any edits, press Back
to exit without saving.
7. Press Back to exit.
Set Minimum Speed (RPM)
The minimum pump speed can be set from 450 RPM
to 1700 RPM. The default setting is 450 RPM.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Min Spd”.
6. Press Select to change the setting. The cursor will
appear in the first number column (ones).
7. Press the Up or Down arrows to edit the minimum
speed setting from 450 to 1700 RPM.
8. Press Save to save. To cancel, press Back to exit
edit mode without saving.
9. Press Back to exit.
Set Maximum Speed (RPM)
The maximum speed can be set from 1900 RPM to
3450 RPM (default is 3450). Use this setting to set the
maximum running speed of the IntelliPro® VSF Variable
Speed and Flow Pump.
Note: Maximum and minimum speed settings, and the
associated alarms, remain active when in Flow mode.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Max Spd”.
6. Press Select to change. The cursor will appear in
the first number column (ones).
7. Press Up or Down arrows to edit the maximum speed
setting from 1900 to 3450 RPM.
8. Press Save to save. Press Back to exit. To cancel,
press the Back to exit without saving.
Note: Maximum Speed will limit Priming Speed, except
in one case. If the Maximum Speed is set below the
lowest available Priming Speed (2400 RPM) then
the pump will exceed the Maximum Speed while the
priming feature is running. This prevents the pump from
having trouble priming if the Maximum Speed is set
this low. If this is a problem, priming can be disabled in
the Priming Menu (see “Priming” section on page 17).
Set Minimum Flow Rate (GPM)
The minimum programmed flow rate can be set from 20
GPM to 70 GPM.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”
and press Select.
5. Use the Up or Down arrows to scroll to “Set Minimum
Flow”.
6. Press Select to change the setting. The cursor will
appear in the first number column (ones).
7. Press the Up or Down arrows to edit the minimum
flow rate setting from 20 to 70 GPM.
8. Press Save to save. To cancel, press Back to exit
edit mode without saving.
9. Press Back to exit.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
11
Set Maximum System Pressure
MENU
SETTINGS
Pump Menu: Settings
Set Maximum Flow Rate (GPM)
The maximum programmed flow rate can be set from 80
GPM to 140 GPM.
Note: Maximum and minimum speed settings, and the
associated alarms, remain active when in Flow mode.
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
5. Use the Up or Down arrows to scroll to “Set Maximum
Flow”.
6. Press Select to change the setting. The cursor will
appear in the first number column (ones).
7. Press the Up or Down arrows to edit the maximum
flow rate setting from 80 to 140 GPM.
8. Press Save to save. To cancel, press Back to exit
edit mode without saving.
9. Press Back to exit.
Set Flow Limit for Speed Program
The flow limit in constant speed program type is disabled
by default. This setting allows the user to ensure that
the drive does not exceed the flow rate output that is set
when they are operating in a constant speed mode. The
system may change during a run at a constant speed
that would increase the flow rate, it this feature is enabled
then the pump will automatically limit itself to keep below
the previously set Maximum Flow Rate.
The maximum pressure can be set using the drive, so that
the pump does not exceed a set system pressure level
when it is asked to do a high power job, or if the system
changes during normal operation. This gives the user a
better way than Maximum Speed to limit the output of
their pump. If the system is less restrictive, then the pump
is still capable of the higher flow rates than it would have
been if the user had used a speed limit, but the pressure
is still limited where the user needed it to be limited.
The pressure is the total system head, so it is a product
of the suction pressure and the discharge pressure. The
calculated value is equivalent to Total Dynamic Head
(TDH). This value may not correspond with the filter's
pressure reading, because it is the TDH across the pump
and not the local pressure of the filter.
When the pump is running a Flow Program, it will always
attempt to reach the set flow no matter what the system
setup is. If the system pressure changes during the run
(such as from filter dirt loading, or manually changing a
valve position), the drive adjusts motor RPM to maintain
a consistent flow rate.
In some cases the newly requested motor speed will
increase the discharge pressure in order to maintain the
requested flow rate. While maintaining the flow rate, the
drive will remain within the pressure and speed limits set
within the Min/Max menu. If the pump meets one of the
limits, it will continue to run at the limit and the warning
light will illuminate. The limit warning will be displayed on
the bottom of the drives' keypad screen indicating that
the requested flow rate is not being achieved and which
limit that the drive is running into.
When the pump is running a Speed Program, the drive
is not monitoring the flow or pressure limits by default.
These features need to be Enabled in the Min/Max menu.
1. Check that the green power LED is on.
To Set Maximum System Pressure:
2. Press Menu.
1. Check that the green power LED is on.
3. Press Select to select “Settings”.
2. Press Menu.
4. Use the Up or Down arrows to scroll to “Min/Max”
and press Select.
3. Press Select to select “Settings”.
5. Use the Up or Down arrows to scroll to “Flow Limit
(Speed)”.
4. Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
6. Press Select to move the cursor over the "Disabled".
5. Use the Up or Down arrows to scroll to “Set Maximum
Pressure”.
7. Press and the Up or Down arrows to change it to
"Enabled".
6. Press Select to change the setting. The cursor will
appear in the first number column (ones).
8. Press Save to save. To cancel, press Back to exit
edit mode without saving.
7. Press the Up or Down arrows to edit the maximum
flow rate setting from 1 to 50 PSI.
9. Press Back to exit.
8. Press Save to save. To cancel, press Back to exit
edit mode without saving.
9. Press Back to exit.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
12
Set Screen Contrast
MENU
SETTINGS
Pump Menu: Settings
Set Pressure Limit for Speed Program
While Pressure Limit is active whenever the pump is
operating a Flow type of program, the pressure limit is
disabled by default when running the pump in a constant
speed mode. Enabling this feature will make sure that the
drive is monitoring the system pressure when operating
in constant speed mode also.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Check that the green power LED is on.
Press Menu.
Press Select to select “Settings”.
Use the Up or Down arrows to scroll to “Min/Max”.
Press Select.
Use the Up or Down arrows to scroll to “Press Limit
(Speed)”.
Press Select to move the cursor over the "Disabled".
Press and the Up or Down arrows to change it to
"Enabled".
Press Save to save. To cancel, press Back to exit
edit mode without saving.
Press Back to exit.
Pump Address
Use this setting if your pump is connected via the RS-485
COM port to a Pentair automation system.
The default pump address is #1 and only needs to be
changed when there is more than one pump on an
automation system. Change the address to allow the
automation system to send a command to the correct
pump. The pump address can be set from 1-16.
Refer to the automation system manual for further
details on how to connect and use an automation
system with your variable speed pump.
1. Be sure the green power LED is on and the pump
is stopped.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrows to scroll to “Device”.
Press Select.
5. Use the Up or Down arrows to scroll to “Pump
Address”. Press Select.
6. Press Up or Down arrows to change the address
number from 1-16.
7. Press Save to save. To cancel any changes, press
Back to exit without saving.
8. Press Back to exit.
The default contrast setting for the LCD screen is 3.
Screen contrast levels can be adjusted from 1 to 5
units for low or high lighting conditions.
Note: Changes to the contrast setting do not update
instantaneously. Changes to this setting must be saved
before the contrast level changes.
1.
2.
3.
4.
5.
6.
7.
8.
Check that the green power LED is on.
Press Menu.
Press Select to select “Settings”.
Use the Up or Down arrow to scroll to “Device”.
Press Select.
Use the Up or Down arrow to scroll to “Contrast
Level."
Press Select. Screen will show current contrast
setting number. Use Up or Down to change
number.
Press Save to save. To cancel any changes, press
Back to exit without saving.
Press the Back button to exit.
Set Control Panel Language
To access the language menu:
1. Check that the green power LED is on.
2. Press Menu and press Select to select “Settings”.
3. Use the Up or Down arrows and scroll to “Device”.
Press Select.
4. Use the Up or Down arrows to scroll to “Select
Language". Press Select.
5. Use the Up or Down arrows to choose the desired
language.
6. Press Save to select the control panel language. To
cancel any changes, press Back to exit without saving.
7. Press Back to exit.
Set Temperature Unit
The default setting is Fahrenheit (°F). The pump can be
set to either Celsius (°C) or Fahrenheit (°F).
1.
2.
3.
4.
5.
6.
7.
8.
Check that the green power LED is on.
Press Menu.
Press Select to select “Settings”.
Use the Up or Down arrows to scroll to “Device”
menu item. Press Select.
Use Up or Down arrows to scroll to "Temperature
Units". Press Select.
Use Up or Down arrows to choose Celsius (°C) or
Fahrenheit (°F).
Press Save to save. To cancel any changes, press
Back to exit without saving.
Press Back to exit.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
13
MENU
SETTINGS
Pump Menu: Settings
Password Protection
The default setting for password protection is disabled.
When this feature is enabled, the pump display will prompt
for the password before allowing access to the control
panel and buttons.
The entered password is any combination of four (4)
digits.
•
•
•
•
•
The pump can always be stopped by pressing Start/
Stop, even when password protection is enabled.
If the pump is stopped, the pump cannot be turned
back on with Start/Stop while running in manual mode.
Pressing Start/Stop when the pump is off will return it
back to the Running Cycles Mode and run at the next
scheduled run time. If the present time is within the
scheduled run time, the pump will run the scheduled
speed.
All functions including
Password
Protection
programming are
Enabled
disabled in Password
Protection Mode.
Screen will read “Enter
12:15p
Password” if any button
other than the Start/
Stop button is pressed
Key icon displayed
150 Watts
in the upper left side
Running Speed 1
of the screen when
Password Protection
is on.
750 RPM
•
Setting Password
1. Check that the green power LED is on.
2. Press Menu. Press Select to select “Settings”.
3. Use the Up or Down arrow to scroll to “Device”.
Press Select.
4. Press Up or Down arrow to scroll to “Password”.
Press Select.
5.
The default setting is “Disabled”. Press Up or Down
arrow to change the setting to “Enabled”. Press Save
to save.
9. Press the Left or Right arrows to move cursor and
press the Up or Down arrow to change the password
number to desired setting.
10. Press Save to save. To cancel any changes, press
Back to exit without saving.
Entering Password
1. Press any button (besides the program buttons) to
prompt the screen for a password.
2. To enter password, use the Left and Right arrows to
move the cursor and the Up and Down arrow button
to scroll through the digit then press Save to confirm.
Set Ramping Rate
The rate that the drive changes the motor speed
can be reduced for smoother operation. This setting
increases or decreases how quickly the pump can
ramp up or down between two speeds. Rates can be
set and adjusted for ramping up and ramping down
individually.
If the Start/Stop button is ever pressed, the motor will
immediately stop and will not follow the programmed
ramping rate. The default setting is Fast, which is the
traditional IntelliPro ramping rate. Medium will take
twice as long to change speeds, and Slow will take
three times as long.
To Set Ramping Rate:
1. Check that the green power LED is on.
2. Press Menu.
3. Press Select to select “Settings”.
4. Use the Up or Down arrow to scroll to “Device”.
Press Select.
5. Use the Up or Down arrow to scroll to “Ramping”.
Press Select.
6. Use the Up or Down arrow to scroll to "Ramp Up".
Press Select and use the Up or Down arrow to
choose between "Fast", Medium or "Slow". Press
Save.
7. Use the Up or Down arrow to scroll to "Ramp
Down". Press Select and use the Up or Down
arrow to choose between "Fast", Medium or
"Slow". Press Save.
6. Press the Down arrow. “Password Timeout” will be
displayed. The factory default time is 1 hour. This
means the IntelliPro® VSF Variable Speed and Flow
Pump will go into Password Protection mode 1 hour
after the last control panel key is pressed.
7. Press Select to enter edit mode. Use the Up or Down
arrow to edit the time setting from 1 minute to 6 hours
and press Save to save setting.
8. Press the Down arrow and then press Select on
“Set Password” to change the setting.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
14
Set Programs in Manual Mode
(Programs 1-4 Only)
MENU
PROGRAM 1-8
Pump Menu: Programs 1-8
1. Press Menu.
Pump Operating Modes
2. Use Up or Down arrows to scroll to “Program 1-8”,
then press Select.
This pump can be programmed in three different
modes:
3. Use Up or Down arrows to find the program (1-4)
you wish to edit, then press Select.
Programs 1-4 can be programmed in all three modes.
Programs 5-8 can only be programmed in Schedule
mode since there are no buttons on the control panel
for Programs 5-8. The default setting for Programs 5-8
is “Disabled”.
4. "Operation Mode" will display. Press Select and
use the Up or Down arrow to scroll to "Manual".
Press Save.
Program 1-4
Manual
Set Type
Schedule
Set Type
Set Start Time
Set Stop Time
Egg Timer
Set Type
Set Duration
Program 5-8
Disabled
Schedule
Default: Disabled
Set Type
Set Start Time
Set Stop Time
Set Speed
Set Flow
Set Speed
Set Flow
Set Speed
Set Flow
Set Speed
Set Flow
Program Menu Tree Options
Manual
Assigns a speed or flow to one of the four Program
buttons on the control panel. This mode can only be
used for programs 1-4. Programs 1 and 2 are Manual
by default.
To operate in Manual mode, press one of the four
program buttons and then press the Start/Stop
button. The pump will run the assigned speed or flow
assigned to that program button.
Egg Timer
Programs 1-4 can be programmed to run at a certain
speed or flow and for a duration of time once a
program button is pressed.
Programs 3 and 4 are Egg Timers by default. If you
desire a different method of operation, programs 3
and 4 can be changed to Manual mode in the control
menu.
To operate in Egg Timer mode, press a program button
and then press Start/Stop. The pump will run that
setting for the set amount of time and then turn off.
Schedule
Programs 1-8 start and stop at a specific time during
a 24 hour period. Speeds or flows programmed in
Schedule mode will override any manually selected
speed or flow once the next Schedule command
commences.
5. Use the Up or Down arrow to scroll to "Set Type".
Press Select and use the Up or Down arrow to
choose between "Speed" or "Flow". Press Save.
6. Use the Up or Down arrow to scroll to "Set Speed/
Flow". Press Select and use the Up or Down
arrow to adjust the speed or flow settings.
7. Press Save to save the new speed or flow setting.
Set Programs in Egg-Timer Mode
(Programs 1-4 Only)
1. Press Menu.
2. Use Up or Down arrows to scroll to “Program 1-8”,
then press Select.
3. Use Up or Down arrows to find the program (1-4)
you wish to edit, then press Select.
4. "Operation Mode" will display. Press Select and
use the Up or Down arrow to scroll to "Egg Timer".
Press Save.
5. Use the Up or Down arrow to scroll to "Set Type".
Press Select and use the Up or Down arrow to
choose between "Speed" or "Flow". Press Save.
6. Use the Up or Down arrow to scroll to "Set Speed/
Flow". Press Select and use the Up or Down
arrow to adjust the speed or flow settings. Press
Save.
7. Now press the Down arrow ("Egg Timer Duration"
will display) and press Select to change. Use the
Up or Down arrows to adjust the time.
8. Press Save to save the new time setting.
12:15p
Manual
Operation Mode
Manual Mode
Menu Screen
12:15p
Egg Timer
Operation Mode
Egg Timer
Menu Screen
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
15
MENU
PROGRAM 1-8
Pump Menu: Programs 1-8
Set Programs 1-8 in Schedule Mode
Programming Schedule for Constant Run
In Schedule mode, Programs 1-8 can be programmed
to run a certain speed or flow at a certain time of day. To
run a scheduled speed or flow, press Start/Stop. The
screen will display “Running Schedules” when it is ready
to run a scheduled speed/flow. If Start/Stop is pressed
while a scheduled speed/flow is running, the pump will
stop running the scheduled speed/flow. The pump will not
continue to run the scheduled speed/flow until the Start/
Stop button is pressed again.
Two programs cannot be programmed with the same
start and stop times. To run a program without stopping,
set the Start time one minute after the stop time.
Example: A single program will run non-stop if
programmed with a Start Time of 8:00 AM and a Stop
time of 7:59 AM.
12:15p
1. Press Menu.
Schedule
2. Use Up or Down arrows to scroll to “Program 1-8”,
then press Select.
Operation Mode
12:15p
750 RPM
T 1:05 150 Watts
Running Speed 1
3. Use Up or Down arrows and press Select for the
speed you wish to set and schedule.
4. "Operation Mode" will display. Press Select and
use the Up or Down arrow to scroll to "Schedule".
Press Save.
5. Use the Up or Down arrow to scroll to "Set Type".
Press Select and use the Up or Down arrow to
choose between "Speed" or "Flow". Press Save.
6. Use the Up or Down arrow to scroll to "Set Speed/
Flow". Press Select and use the Up or Down
arrow to adjust the speed or flow settings.
7. Press Save to save the new speed or flow setting.
8. Press the Down arrow again, “Start Time” will
display. Press Select - the cursor will highlight the
minute column.
9. Use the Up or Down arrow to change the time
and the Left or Right arrow to move cursor from
minutes to hours.
10. Press Save to save the new start time setting.
11. Press Down arrow - “Stop Time” will display. Press
Select. Repeat Steps 8-9 to set stop time.
12. Press Save to save the new stop time setting.
Note: The pump will not run the scheduled speeds or flows
until the Start/Stop button is pressed (LED on) to place the
pump in Schedule mode.
Scheduled Program Priority
When operating the pump in Schedule mode it is important
to keep each program within its own individual run time. If
program run times overlap the pump will prioritize programs
as explained below:
Schedule priorities are in descending order as follows:
Highest Flow » Lowest Flow » Highest Speed » Lowest
Speed
•
When two speed OR two flow program schedules
overlap, the pump will run the higher RPM Speed or
GPM Flow regardless of program in use.
•
When both a speed AND flow program schedule
overlap the pump will run the flow program first.
•
A manual or egg timer command takes precedent
over a running schedule. The manual or egg timer
command will operate until completed, unless the
next schedule program takes place or another
command is given.
13. Press Start/Stop.
The IntelliPro® VSF Variable Speed and Flow Pump will
prime and begin to run the programmed schedule at the
specified start time.
When running in Schedule or Egg Timer mode, the
countdown time (T 00:01) showing the hours and
minutes remaining is displayed.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
16
MENU
EXT CONTROL
Pump Menu: External
Control
External Control
This function is for programming speeds or flows that
will run when the IntelliComm® Communication Center
sends it a command. For example, Terminal 3 and 4 in the
IntelliComm system will correspond to External Control
Program #1. (5 and 6 to Ext Ctrl #2).
The Stop Delay feature allows the user to program the
pump to run a Program after the External Control has
been deactivated. This feature can be used to provide a
cooling down period for the pump after a trigger signal
from an installed heater has been deactivated. Each
individual Program can have a Stop Delay of 1 to 10
minutes programmed.
Use the External Control feature to program the
IntelliComm system power center.
External Control can also be used for disabling the pump
by choosing "Pump Off" when selecting an operation
mode. If this program is triggered via external control
the pump will stop running for as long as the program is
active. This feature could be useful for demand response
systems using an IntelliComm to communicate with the
pump.
6. Use the Up or Down arrow to scroll to "Set
Type". Press Select.
7. Use the Up or Down arrow to choose between
"Speed" or "Flow". Press Save.
8. Use the Up or Down arrow to scroll to "Set
Speed/Flow". Press Select and use the Up or
Down arrow to adjust the speed or flow settings.
Press Save.
9. If you do not wish to program a Stop Delay,
continue to step 11. If you do wish to program a
Stop delay press Up or Down arrow to scroll to
“Stop Delay”. Press Select.
10. Use the Up or Down arrows to change the Stop
Delay setting. Stop Delay can be set from 0
minutes (disabled) to 10 minutes.
11. Press Save to save the settings.
12. Press Back to return to set Program 2.
13. Use Up or Down arrow to scroll to “Program 2”.
14. Repeat Steps 4 through 11 to set Program 2, 3,
and 4.
To access the External Control menu:
1. Check that the green power LED is on.
2. Press the Menu button.
3. Use Up or Down arrow to scroll to “Ext. Ctrl.”.
Press Select.
4. “Program 1” will display. Press Select to enter
the Program 1 menu.
5. "Operation Mode" will display. Press Select and
use the Up or Down arrows to choose between
"Enabled" or "Pump Off". Press Save.
Note: The program you are attempting to edit
must be enabled in order to proceed further into
the menu.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
17
MENU
FEATURES
Pump Menu: Features
Time Out
The Time Out feature keeps the IntelliPro® VSF Variable
Speed and Flow Pump from running it’s programmed
speeds or flows for a set duration adjustable in the
menu. The Time Out feature is displayed in hours and
minutes (Hrs:Mins).
Once Time Out is finished, the pump will return to its
previous mode of operation, the Start/Stop LED will be
lit and ready to turn on at the next scheduled run time.
To access the Time Out menu:
1. Check that the green power LED is on.
2. Press Menu.
3. Use Up or Down arrows to scroll to “Features”,
then press Select.
4. Press Select to choose “Timeout”.
5. "Timeout Duration" will display. Press Select to
highlight the minutes column.
6. Press the Left arrow to move cursor to the hours
column. Time out can be set from 1 minute to 10
hours.
7. Press Save to save the setting.
Note: To cancel any changes, press Back to exit
without saving.
8. Press Back to exit the menu.
Quick Clean
This feature can be used to increase the pump speed
or flow for the purposes of vacuuming, cleaning, adding
chemicals, after a storm for extra skimming capability.
Press the Quick Clean button (LED on) and then
Start/Stop to start. When the Quick Clean cycle is over,
the pump will resume regular schedules and return to
“Schedule” mode.
To access the Quick Clean menu:
1. Check that the green power LED is on and the
pump is stopped.
2. Press Menu.
3. Use Up or Down arrows to scroll to “Features”,
then press Select.
4. Press the Down arrow and press Select for “Quick
Clean”.
5. Press Select to choose “Set Type”. Use the Up or
Down arrow to choose between "Speed" or "Flow".
Press Save.
6. Use the Up or Down arrow to scroll to "Set Speed/
Flow". Press Select and use the Up or Down arrow
to adjust the speed or flow settings. Press Save.
7. Press Save to save the speed or flow setting.
8. Press the Down arrow and press Select for “Time
Duration”.
9. The cursor will highlight the minutes column. Use
Up or Down arrows to change the time from 1
minute to 10 hours.
10. Press Save to save the time.
11. Press Back to exit the menu.
MENU
PRIMING
Pump Menu: Priming
The default setting for Priming is ENABLED. This setting
allows the pump to automatically detect if it is primed for
startup.
The priming feature increases the pump speed to
1800 RPM and pauses for three (3) seconds. If there is
sufficient water flow in the pump basket, the pump will
go out of priming mode and run its commanded speed.
If the water flow is not sufficient, the pump speed will
increase to the “Priming Speed” setting and remain for
the priming delay time (default 20 seconds). If there is
sufficient water flow in the pump basket at this time, it
will exit priming mode and transition to the commanded
speed.
If there is still insufficient flow in the pump basket, as
determined by the Priming Range setting, the pump will
try to prime at the “Priming Speed” for the amount of
time set in the “Maximum Priming Time” menu. Once the
pump achieves prime, it will resume normal operation
after the preset priming delay.
Note: It is possible to set “Maximum Speed” too low
for the pump to properly prime. Maximum Speed
will limit Priming Speed, except in one case. If the
Maximum Speed is set below the lowest available
Priming Speed (2400 RPM) then the pump will
exceed the Maximum Speed while the priming
feature is running. This prevents the pump from
having trouble priming if the Maximum Speed is set
this low. If this is a problem, priming can be disabled
in the Priming Menu.
12:15p
1800 RPM
T 00:01 460 WATTS
Priming
Display during priming
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
18
MENU
PRIMING
Pump Menu: Priming
Priming Features
Disabled/Enabled
Priming Speed
Default: ENABLED
Allows IntelliPro® VSF Variable Speed and Flow Pump to automatically detect if pump
if is primed for startup. The pump will speed up to 1800 RPM and pause for three (3)
seconds - if there is enough water in the basket, the pump will go out of priming mode
and run the commanded speed.
Default: 3450 RPM
The priming speed can be set between 2400 RPM and 3450 RPM. If the pump is on
an equipment pad that is close to the water level, it will not need to run at 3450 RPM
to successfully prime. The setting can be lowered to prevent running at a higher speed
than necessary.
Day to day factors (i.e. local ambient pressure, water/air temperatures, amount of
water retained from last system run) can effect priming performance. Because of the
frequently changing nature of these factors the priming speed should be set high
enough to accommodate environmental and mechanical changes to ensure that the
pump can successfully prime. Finding the most effective and efficient speed for your
specific needs may take careful testing and evaluation of priming performance.
Max Priming Duration
Default: 11 minutes
The maximum priming time can be set from 1 - 30 minutes. This setting is the amount
of time the pump will try to prime before it gives a priming error. If this occurs, fill the
pump basket with water and restart the pump.
Priming Range
Default: 5
Priming range can be set from 1-10. The smaller the range, the more water the pump
has to be moving to detect that it is primed. At larger ranges, the pump will detect that
it is fully primed while moving less water. If the range is set too high, then the pump
may exit Priming mode before it has fully primed. The range will automatically adjust
with the priming set speed because the flow rates of the pump will be lower at lower
speeds.
Priming Delay
Default: 20 seconds
Priming delay can be set from 1 second to 10 minutes.
When a pump ramps to full priming speed in an attempt to establish a prime, priming
delay allows the pump to operate at that speed for an additional set period of time prior
to continuing on to the requested or scheduled program.
Loss of Prime
Default: Enabled
This feature allows the pump to recognize unanticipated low-flow or no-flow situations
while running a program.
For example, the pump will pause for one (1) minute after detecting that it has lost
its prime unexpectedly. After this pause the pump will attempt to prime, and if prime
is successful it will continue programmed operation. If priming is not successful the
pump will continue attempting to prime, per normal priming operation, until a prime is
achieved or priming error occurs and is displayed.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
19
MENU
14. Press the Down arrow to scroll to “Loss of Prime”.
Setting Priming Features
15. The factory default is “Enabled“. To disable, press
Select to edit and use the Down arrow to scroll to
"Disabled". Press Save.
1. Press Menu.
16. Press Back to exit the priming menu.
PRIMING
Pump Menu: Priming
2. Use Down arrow to scroll to “Priming” and press
Select.
3. The factory default is set to priming “Enabled“. To
disable, scroll to "Disabled" and press Select.
Note: All priming features are only accessible if
priming is “Enabled”.
4. Press Save if you have changed the setting - this
will save the selection.
5. Press the Down arrow to scroll to "Set Speed".
Press Select to edit.
6. Use the Up or Down arrows to change the speed
settings. Press Save.
7. Press the Down to scroll to “Max Priming Duration”.
Press Select to edit.
8. Use the Up or Down arrows to change the time
from 1 minute to 30 minutes. Press Save.
9. Press the Down arrow to scroll to “Priming Range”.
Press Select to edit.
10. Use the Up or Down arrows to change from 1 to
10. Increasing the number allows the drive to detect
prime with less water flow.
11. Press Save.
12. Press the Down arrow to scroll to “Priming Delay”.
Press Select to edit.
13. Use the Up or Down arrows to change from 1
second to 10 minutes. Press Save.
Increasing the time causes the pump to
stay in the priming mode longer.
Disabling Priming with an Automation
System
When the IntelliPro® VSF Variable Speed and Flow
Pump is connected to an automation control system,
(IntelliTouch®, EasyTouch® or SunTouch® Control
Systems), the priming feature on the pump cannot be
disabled by the external automation control system
only. It must also be disabled on the pump itself.
If priming is enabled on start up, the pump responds
to its internal settings before responding to commands
from an automation control system.
If the pump is connected to an automation control
system and priming is not desired, disable the priming
feature on both the pump and the automation control
system.
To disable priming with an automation system:
1. Disable the priming feature on the automation control
system at the load center or using an IntelliTouch or
EasyTouch system remote. (Refer to the automation
control system user’s guide for additional information).
2. Temporarily disconnect the RS-485 communication
cable.
3. Open the lid to the control panel to disable priming
on the pump. Press Menu, use the Arrow buttons to
scroll and select “Priming”, then select “Disabled”
(the factory default is set to “Enabled”). Press Back
to exit the menu.
4. Once priming is disabled, reinstall the RS-485
communication cable.
P
1. Disable priming on automation control system.
2. Disconnect the RS-485 communication cable.
3. Disable priming on pump.
4. Reinstall the RS-485 communication cable.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
20
MENU
THERMAL MODE
Pump Menu: Thermal Mode
The sensor for Thermal Mode is in the drive, on top of
the motor. This feature allows you to set a speed (4503450 RPM) or flow (20-140 GPM) that runs when the
IntelliPro® VSF Variable Speed and Flow Pump goes
into Thermal Mode. The temperature level that you wish
Thermal Mode to start can also be set.
IMPORTANT NOTE: This feature is for protection of the
pump. Do not depend on the Thermal Mode feature for
freeze protection of the pool. Certain situations could
cause the pump to sense a different temperature than
actual air temperature.
Your automation systems air temperature sensor should
be used to sense actual temperature. For example, if
the pump is located indoors, the temperature of the
room does not indicate the outdoor temperature. The
pump does not sense the water temperature.
To access the Thermal Mode menu:
1. Check that the green power LED is on.
2. Press Menu.
3. Use the Down arrow to scroll to “Thermal Mode”
and press Select.
4. The factory default for Thermal Mode is
“Enabled“. To disable Thermal Mode, press
Select to highlight “Enabled”.
To Set Thermal Mode Speed/Flow and Pump
Temperature:
Note: Thermal Mode features are only accessible if
Thermal Mode is “Enabled”.
1. Use the Up or Down arrows to scroll to "Set
Type". Press Select.
2. Use the Up or Down arrow to choose between
"Speed" or "Flow". Press Save.
3. Use the Up or Down arrow to scroll to "Set
Speed/Flow". Press Select.
4. Use the Up or Down arrow to adjust the speed or
flow settings. Press Save.
5. Press the Down arrow. "Temperature" will
display. (This value will determine at what
temperature the pump will activate Thermal
Mode, default is 40° F/4.4° C).
6. Press Select to edit. Use the Up or Down arrow
to adjust the settings.
7. Press Save to save the temperature setting.
Note: To cancel any changes, press Back to exit
without saving.
8. Press Back to exit.
5. Press the Up arrow - “Disabled” is displayed.
ThermMode
6. Press Save to save.
ThermMode
12:15p
40 °F
12:15p
Pump Temperature
1000 RPM
Set Speed
Setting the Thermal Mode Pump Temperature
Setting the Thermal Mode Pump Speed
THERMAL MODE
Disabled/Enabled
Set Type
Set Speed/Flow
Pump Temperature
Disabled / Enabled - Default: Enabled
Speed
Flow
Set Speed (450-3450 RPM) Default 1000 RPM
Set Flow (20-140 GPM) Default: 40 GPM
40° F - 50° F (4.4° C through 10° C) Default: 40° F (4.4° C)
Thermal Mode Menu Options
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
21
MAINTENANCE
DO NOT open the strainer pot if IntelliPro® VSF Variable Speed and Flow Pump fails to prime or if pump has been operating without
water in the strainer pot. Pumps operated in these circumstances may experience a build up of vapor pressure and may contain
scalding hot water. Opening the pump may cause serious personal injury. In order to avoid the possibility of personal injury, be sure
the suction and discharge valves are open and strainer pot temperature is cool to touch, then open with extreme caution.
To prevent damage to the pump and for proper operation of the system, clean pump strainer and skimmer baskets regularly.
Pump Strainer Basket
Winterizing
The strainer basket (or ‘strainer pot’), is located in front of
the pump housing. The strainer basket must be kept clean
and free of debris. Inspect basket through the lid on the
top of the housing. Be sure to visually inspect the strainer
basket at least once a week. Dirty strainer baskets reduce
filter and heater efficiency and put abnormal stress on
the pump motor.
To protect the pump electronics from freeze damage,
the pump will switch on to generate internal heat as the
temperature drops below freezing if Thermal Mode is
enabled. The Thermal Mode feature on the pump is not
intended to protect the system plumbing from freezing.
Cleaning the Pump Strainer Basket
1. Press Start/Stop button on the pump and turn
off the pump at the circuit breaker. Disconnect
communication cable from pump.
2. Relieve pressure in the system.
3. Turn the lid and locking ring counter-clockwise and
remove from the pump.
4. Remove debris and rinse out the basket. Replace
the basket if it is cracked.
5. Put the basket back into the housing. Be sure to align
the notch in the bottom of the basket with the rib in
the bottom of the volute.
6. Fill the pump pot and volute up to the inlet port with
water.
7. Clean the lid and locking ring, O-ring, and sealing
surface of the pump pot.
Note: It is important to keep the lid O-ring clean and
well lubricated.
8. Reinstall the lid by placing the locking ring and lid on
the pot. Be sure the lid O-ring is properly placed.
Seat the locking ring and lid on the pump then
turn clockwise until the locking ring handles are
perpendicular to the inlet.
9. Turn the power “ON” at the circuit breaker. Reconnect
communication cable from pump.
10. Open the manual air relief valve on the top of the
filter. Stand clear of the filter.
11. Wait until all pressure is relieved. Start the pump.
12. Bleed air from the filter until a steady stream of
water comes out of the filter air relief valve. Close
the manual air relief valve.
THIS SYSTEM OPERATES UNDER HIGH PRESSURE.
When any part of the circulating system (e.g., Lock Ring,
Pump, Filter, Valves, etc.) is serviced, air can enter the
system and become pressurized. Pressurized air can
cause the lid to separate which can result in serious
injury, death, or property damage.
To avoid this potential hazard, follow above instructions.
•
In mild climate areas, when temporary freezing
conditions may occur, run your filtering equipment
all night to prevent freezing.
• You are responsible for determining when freezing
conditions may occur. If freezing conditions are
expected, take the following steps to reduce the risk
of freeze damage. Freeze damage is not covered
under warranty.
To prevent freeze damage, follow the procedures below:
1. Shut off electrical power for the pump at the circuit
breaker.
2. Drain the water out of the pump housing by removing
the two thumb-twist drain plugs from the housing.
Store the plugs in the pump basket.
3. Cover the motor to protect it from severe rain, snow
and ice.
Note: The motor may be covered during a storm, winter
storage, etc., but never when operating or expecting
operation. Never wrap motor with plastic or other air
tight materials during winter storage.
Locking Ring
Lid
Strainer Basket
O-Ring
Volute
Drain
Plugs
Strainer Pot Assembly
INTELLIPRO VSF Variable Speed and Flow Pump Installation and User’s Guide
®
22
SERVICING
Always disconnect power to the IntelliPro® VSF Variable Speed and Flow Pump at the circuit breaker and disconnect the communication
cable before servicing the pump. Failure to do so could result in death or serious injury to service people, users or others due to electric
shock. Read all servicing instructions before working on the pump.
DO NOT open the strainer pot if pump fails to prime or if pump has been operating without water in the strainer pot. Pumps operated in
these circumstances may experience a build up of vapor pressure and may contain scalding hot water. Opening the pump may cause
serious personal injury. In order to avoid the possibility of personal injury, be sure the suction and discharge valves are open and strainer pot temperature is
cool to touch, then open with extreme caution.
Be sure not to scratch or mar the polished shaft seal faces; seal will leak if faces are damaged. The polished and lapped faces of the
seal could be damaged if not handled with care.
Motor and Drive Care
Protect from heat
1. Shade the motor from the sun.
2. Any enclosure must be well ventilated to prevent
overheating.
3. Provide ample cross ventilation.
4. Provide a minimum clearance of 3-inches behind the
motor fan for proper circulation.
Protect against dirt
1. Protect from any foreign matter.
2. Do not store (or spill) chemicals on or near the motor.
3. Avoid sweeping or stirring up dust near the motor
while it is operating.
4. If a motor has been damaged by dirt it may void the
motor warranty.
Protect against moisture
1. Protect from continuous splashing or continuous
sprayed water.
2. Protect from extreme weather such as flooding.
3. If motor internals have become wet - let it dry before
operating. Do not allow the pump to operate if it has
been flooded.
4. If a motor has been damaged by water it may void
the motor warranty.
5. Be sure to close the keypad cover after every use.
To remove and repair the motor subassembly, follow the steps
below:
1.
Turn off the pump circuit breakers at the main panel.
2.
Release all pressure by opening all vents before starting.
Be sure gate valves and return piping are closed.
3.
Drain the pump by removing the drain plugs on the bottom
of the pump body and trap body.
4.
Be sure there is no pressure in the trap body. Remove the
cover (unscrew by turning the handle ring).
5.
Remove the clamp holding the pump halves together. The
motor and seal plate assembly can now be pulled away
from the pump body.
6.
Remove the five screws and washers holding the diffuser
to the seal plate. Remove the diffuser.
7.
Hold the impeller securely in place by hand. Remove the
impeller lock screw located at the center of the impeller.
Using a deep well 3/4 in socket wrench with racket, loosen
the left-handed screw thread in a clockwise direction.
Remove the impeller screw o-ring. Inspect the o-ring for
damage, cracks, etc. Replace if damaged.
The pump impeller may have sharp edges that could
potentially cut or scratch the user's hands. Pentair
recommends that safety gloves be worn when holding the impeller during
disassembly and reassembly.
8.
Use the 1/4 in Allen head wrench to hold the motor shaft.
The motor shaft has a hex on the end which is accessible
through the center of the fan.
Note: Sometimes the impeller becomes tight on the shaft
after years of service. It may be necessary to hold the Allen
wrench with a wrench or pliers as the torque may be too
high to hold by hand.
9.
While holding the motor shaft, unscrew the impeller by hand.
Turn the impeller counter clockwise when facing it to loosen.
Note: If the impeller is too tight, use leather gloves to help
loosen.
Shaft Seal Replacement
The Shaft Seal consists primarily of two parts, a rotating
ceramic seal housed in the impeller and a stationary
spring seal in the sealplate. The pump requires little or
no service other than reasonable care, however, a shaft
seal may occasionally become damaged and must
be replaced.
Note: The polished and lapped faces of the seal could
be damaged if not handled with care.
Pump Disassembly
Required Tools:
• 1/2 in open end wrench
• 1/4 in socket with ratchet or wrench
• 9/16 in open end wrench
• No. 2 Phillips screwdriver
• 3/4 in deep well socket with ratchet
• 1/4 in Allen head wrench
10. Pull the rotating member of the seal off the impeller sleeve.
Clean the sleeve.
11. Remove the four screws holding the seal plate to the motor.
12. Place the seal plate face down on flat surface and tap out
the ceramic seat.
13. Clean the seal cavity in the seal plate and clean the motor
shaft.
- Pump illustrated parts view on the next page -
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
23
Pump Reassembly/Installing New Seal
1. Clean the ceramic seat of dirt, grease, dust, etc.
Wet the outer edge of the rubber cup on the ceramic
seat with water. Press the ceramic seal into the seal
plate firmly and squarely with finger pressure. See
seal image below.
2. Place ceramic seat face up on bench and reclean
the cavity if seat does not lock properly.
3. If the seat still does not lock properly, place a
cardboard washer over the polished face and use
a piece of 3/4” standard pipe for pressing purposes.
10. Reconnect the RS-485 communication cable to the
pump.
11. Fill the pump with water.
12. Reinstall the pump lid and plastic clamp. See “Pump
Strainer Basket” on page 23 for details.
13. Turn on the pump circuit breakers at the main panel.
14. Prime the pump. See “Priming the Pump,” on page
5 for more information.
Drive Assembly Removal and Installation
4. Remount seal plate on the motor. Tighten the bolts
to 60-80 inch-lbs. (69-92kg/cm) torque.
To avoid dangerous or fatal electrical shock
hazard, switch OFF power to motor before working
on pump or motor.
To avoid electrical hazard, do not remove the four
tamper proof screws from the motor assembly.
5. Apply a small amount of liquid detergent to the
inside diameter of rotating half of seal.
6. Slide the rotating seal member, polished face last,
over impeller sleeve until the rubber drive ring
contacts the shoulder.
Note: Be sure not to nick or scratch the polished
seal face. The seal will leak if the face is damaged.
7. Screw the impeller onto the shaft (clockwise); this
will automatically lock the seal in the seal plate.
Note: On models with an impeller screw: Install the
impeller gasket and lock screw (left-hand thread turn counter-clockwise). Torque lock screw to 50-55
inch-lbs. (57.6-63 kg/cm).
8. Mount the diffuser on the seal plate. Tighten screws
to 10-14 inch-lbs. (11.2-16.1 kg/cm) torque.
9. Assemble the motor and seal plate to the volute.
Be sure the clamp is properly seated.
Note: Clamp knob can be located in any position
around volute; if it is moved after assembly, tighten
knob while tapping around clamp to assist sealing.
Do not move clamp while pump is full of water.
KEYPAD COVER
To remove the drive and control panel from the motor
assembly:
1. Be sure all electrical breakers and switches are turned
off before removing the control panel.
2. Disconnect the RS-485 communication cable
from the pump.
3. Remove the four (4) Phillips head screws from the
outer corners of the keypad.
4. Unplug the keypad from the drive and set it to the
side in a safe place.
5. Remove the three (3) Phillips head screws, located
inside the drive, that anchor the drive to the motor.
6. Lift up the drive assembly and remove it from the
motor adapter located on top of the motor assembly.
HEYCO PLUG FOR
KEYPAD RELOCATION CABLE
KEYPAD TO
DRIVE SCREWS
CAPTIVE (4X)
MECHANICAL
SEAL
DRIVE TO MOTOR
SCREWS (3X)
BAND CLAMP
KNOB
IMPELLER
SCREW
DRIVE
Note: Be careful not to remove the gasket between
the drive and motor, it is critical in keeping moisture
out of the drive and motor. Replace the gasket if
damaged. Do not reassemble with a damaged or
missing gasket.
LOCKING RING/LID
LID O-RING
MOTOR
MOTOR TO SEALPLATE
BOLT (4X)
STRAINER BASKET
DRAIN PLUG (2X)
SEAL PLATE
DRAIN PLUG O-RING (2X)
IMPELLER
DIFFUSER
DIFFUSER SCREWS (5X)
DIFFUSER O-RING
BAND CLAMP
VOLUTE
SCREW, VOLUTE TO BASE
SEAL PLATE O-RING
Press Seal into plate firmly
PUMP BASE/
MOTOR SUPPORT
Pump Illustrated Parts View
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
24
Drive Assembly Removal and
Installation, (continued)
Before installing this product, read and follow
all warning notices and instructions on page
ii - iii.
To install the drive assembly onto the motor
assembly:
Keypad Assembly
Keypad Screws
(4x)
Drive to Motor
Screws (3x)
1. Be sure all electrical breakers and switches are
turned off before installing the drive.
2. Be sure that the gasket between the drive and
motor is in place. It is critical in keeping moisture
out of the drive and motor. Replace the gasket if
damaged. Do not reassemble with a damaged
or missing gasket.
3. Verify that the three (3) orange motor post caps
are in position before placing the drive on the
motor assembly.
4. Align the drive assembly with the motor adapter
and seat the drive on the motor assembly.
5. Secure and tighten the drive assembly with the
three (3) Phillips head screws.
6. Plug the keypad back into the drive.
7. Place the keypad in the desired orientation on
the drive and reattach the four (4) screws in the
corners of the drive.
Note: Ensure that the keypad cable is not being
pinched between the drive and keypad.
Drive Gasket
Orange Motor
Post Caps (3x)
Adapter
Connector
Drive Assembly and Removal
FIRE and BURN HAZARD - The pump motor
may run at a high temperatures. To reduce the
risk of fire, do not allow leaves, debris, or foreign matter to collect
around the pump motor. To avoid burns when handling the motor, shut
off the motor and allow it to cool for 20 minutes before servicing. The
pump provides an automatic internal cutoff switch to protect the motor
from heat damage during operation.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
25
TROUBLESHOOTING
Always disconnect power to the IntelliPro® VSF Variable Speed and Flow Pump at the circuit breaker and disconnect the
communication cable before servicing the pump. Failure to do so could result in death or serious injury to serviceman, pool users
or others due to electric shock. DO NOT attempt to adjust or service without consulting your dealer or a qualified pool technician.
Read the entire Installation & User’s Guide before attempting to use, service, or adjust the pool filtering system or heater.
Alerts and Warnings
The IntelliPro® VSF Variable Speed and Flow Pump displays all alarms and warnings on the control panel display.
When an alarm or warning condition exists, the corresponding light will be lit on the display.
In the event of an alarm: The alarm light " " will illuminate and all control panel buttons will be disabled until the
alarm is cleared. Pressing the Reset button will clear the alarm once the fault condition has been resolved.
In the event of a warning: The warning light " " will illuminate, but the pump will continue to run. The speed, flow
or pressure limit that is causing the warning must be adjusted in order to correct the warning.
Note: The pump will not start if the impeller is rotating.
Power Out/OFF
The incoming supply voltage is less than required. The drive faults to protect itself from over current. The drive
contains capacitors that keep it powered up long enough to save the current run parameters. If power is restored
during this process, approximately 20 seconds, the drive will not restart until completed.
Priming Failure
If the pump is not defined as primed within the “Max Priming Duration” it will stop and generate a “Priming Alarm”
for 10 minutes, then attempt to prime again. The “Max Priming Duration” is set by the user on the priming menu
as discussed on page 19. If the pump cannot prime within five attempts it will generate a permanent alarm that
must be manually reset.
Overheat
If the drive temperature gets above 54.4° C (130° F) the pump will slowly reduce speed until the over temperature
condition clears.
Thermal Mode
When active, the motor will run at the preset RPM until the drive internal temperature increases above the
minimum. The pump’s internal thermal protection is disabled when connected to an automation system.
Thermal protection is provided by selecting YES at the ON WITH FREEZE portion of the circuit function menu
in the IntelliTouch® Control System. To re-enable the internal thermal protection, the power to the drive must
be cycled off then back on. Important: See explanation of Thermal Mode on page 20.
Over Current
Indicated that the drive is overloaded or the motor has an electrical problem. The drive will restart 20 seconds
after the over current condition clears.
Over Voltage
Indicates excessive supply voltage or an external water source is causing the pump and motor to rotate thereby
generating an excessive voltage on the drives internal DC buss. The drive will restart 20 seconds after the over
voltage condition clears.
Internal Error
Indicates that the self-monitoring motor control software has encountered an error. Clear the alarm and restart the
pump. If this alarm persists, contact Pentair Technical Service at 1-800-831-7133.
Speed Limit (Warning)
The pump has detected that it has met the maximum allowed speed set in the Min/Max menu. The pump will
continue to run, but it will not achieve the desired speed.
Pressure Limit (Warning)
The pump has detected that it has met the maximum system pressure set in the Min/Max menu. The pump will
continue to run, but it is not achieving the desired flow rate or speed because of the pressure limit. The feature
is enabled by default while running a program at a constant flow rate, but must be enabled manually if the user
wants the drive to monitor maximum pressure while running a constant speed program.
Flow Limit (Warning)
The pump has detected that it has met the maximum flow rate set in the Min/Max menu. The pump will continue
to run, but it is not achieving the desired speed because it is running at the maximum flow rate. The Maximum
Flow can be set in the Max/Min menu. This feature must be enabled in the Min/Max menu to be active while
running a speed program.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
26
Troubleshooting Chart
Problem
Possible Cause
Corrective Action
Pump failure.
Pump will not prime - Air leak in suction.
PRIME ERROR may be displayed.
Check suction piping and valve glands on any
suction gate valves. Secure lid on pump strainer pot
and be sure lid gasket is in place. Check water level
to be sure skimmer is not drawing air.
Pump will not prime - Not enough water.
Be sure the suction lines, pump, strainer, and pump
volute are full of water.
Pump does not come out of priming mode.
Adjust priming range to a higher setting
(default setting is 5).
Pump completes priming mode too early, and/or
there is still a large amount of air in the housing
Adjust priming range to a lower setting
(default setting is 5).
Pump stainer basket is clogged.
Clean pump strainer pot.
Pump strainer gasket is defective.
Replace gasket.
Air pockets or leaks in suction line.
PRIMING FAILURE may be displayed.
Check suction piping and valve glands on any
suction gate valves.
(For alert display
messages, refer to Alerts
and Warnings on page 25).
Reduced capacity and/
or head.
(For alert display
Clogged impeller.
messages, refer to Alerts
PRIMING FAILURE may be displayed.
and Warnings on page 25).
Turn off electrical power to the pump.
Remove the (6) bolts that holds the housing (strainer
pot/volute) to seal plate. Slide the motor and seal
plate away from the volute.
Clean debris from impeller. If debris cannot be
removed, complete the following steps:
1. Remove diffuser and o-ring.
2. Remove reverse-thread impeller screw and o-ring.
3. Remove, clean and reinstall impeller.
4. Reinstall reverse-thread impeller screw and o-ring.
Reinstall diffuser, and o-ring.
Reinstall motor and seal plate into volute.
Reinstall seal plate nuts and volute and tighten
securely.
Inadequate circulation.
(For alert display
messages, refer to Alerts
and Warning on page 25).
Electrical problem.
Pump strainer pot clogged.
PRIMING FAILURE may be displayed.
Clean suction trap.
Filter or pump basket dirty.
Check trap basket; if plugged, turn pump off and
clean basket.
Clean pump strainer pot.
Check and clean pool filter.
Suction/discharge piping is too small.
Increase piping size.
Speed is set too slow for proper filtration cycle.
Increase filtration run time.
Could appear as a “Low Voltage” alarm.
Check voltage at motor terminals and at panel while
pump is running. If low, see wiring instructions or
consult power company.
(For alert display
messages, refer to Alerts
and Warning on page 25).
Check for loose connections.
Could appear as “Over Heat” alert.
Check line voltage; if less than 90% or more than
110% of rated voltage consult a licensed electrician.
Increase ventilation.
Reduce ambient temperature.
Tighten any loose wiring connections.
Motor runs too hot. Turn power to motor off.
Check for proper voltage.
Check for proper impeller or impeller rubbing.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
27
Problem
Possible Cause
Corrective Action
Control panel LCD screen Loose drive wiring connection.
displays sporadically or
flickers on/off.
Check the connection between the drive and keypad.
See image on page 3. The drive wiring connection
should be tight.
Mechanical troubles and
noise.
The pump motor is running but with loud noise.
If suction and discharge piping are not adequately
supported, pump assembly will be strained. Do not
mount pump on a wooden platform! Securely mount
on concrete platform for quietest performance.
Foreign matter (gravel, metal, etc.) in
pump impeller.
Disassemble pump, clean impeller, follow pump service instructions for reassembly.
Cavitation.
Improve suction conditions.
Increase pipe size.
Decrease number of fittings.
Increase discharge pressure.
Pump does not respond
to IntelliTouch,
EasyTouch,
SunTouch, IntelliComm
system commands.
Speaking noise, especially evident at pump startup or slow down.
Inspect motor slinger and motor shaft seal behind
the slinger (NOT the pump’s mechanical seal). Apply
lubrication to the motor shaft rubber seals.
Improper automation setup.
1. Be sure that the communication cable is
connected at both ends.
2. Check that the pump local address matches with
the address used in the IntelliTouch control system.
3. Check that the pump has been assigned a circuit
name on the IntelliTouch control system.
4. Ensure that the pump display says
“DISPLAY NOT ACTIVE”.
Communication network inoperative.
A defective device on the network can inhibit the
proper operation of other network device. Devices
should be disconnected sequentially until the
network starts working.
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
28
REPLACEMENT PARTS
1
6
2
7
3
11
8
12
13
14
4
15
9
16
17
18
19
20
21
22
10
23
24
5
25
31
26
29
27
30
28
IntelliPro® VSF Variable Speed and Flow Pump Replacement Parts
Item
No.
Part
No.
Description
1
353141Z
DRIVE KIT W/ KEYPAD (Includes Item #2, 7 and 8)
2
355685
DRIVE HARDWARE KIT (Includes Drive Screws, Drive Gasket and Screw Caps)
3
17307-0110S TANK BODY ASSEMBLY (Includes Trap Cover
and Item #21-24)
4
17307-0111S TRAP COVER ASSEMBLY (Includes Trap Cover
and Item #21)
5
42001-0402 2” SLIP UNION HALF KIT (Includes Item #25-27)
6
356905Z
KEYPAD RELOCATION KIT (Includes Keypad Relocation Cable and Blank Drive Cover)
7
358527Z
KEYPAD ASSEMBLY KIT
8
356657Z
DRIVE KIT
9
350306S
MOTOR 3.2KW FERRITE BLK
10
U30-74SS
3/8-16 X 1” HEX HEAD SS (Qty. 4)
11
C103-194P
SEAL PLATE
12 17351-0101S SHAFT SEAL, EPDM BLACK
13 C105-238PLA IMPELLER ASSEMBLY
14
37007-6080 IMPELLER SCREW
15
C1-271P
DIFFUSER
16
U43-21SS #8 EXT TOOTH WASHER (Qty. 5)
Item
No.
Part
No.
17
U30-922SS
18
U9-374
19
C19-37a
20
WC-36-22
21
35505-1440
22
C8-58P
23
U78-920P
24
U9-359
25
U11-200PS
26
U11-196PS
27
U9-362
28
U30-918
29
C35-11
30
C4-78P
31
U9-228A
*
350122
Description
DIFFUSER SCREW
DIFFUSER O-RING
V-CLAMP
CLAMP, KNOB
TRAP O-RING, 6.90 O.D. 6.35 I.D.
TRAP BASKET
DRAIN PLUG (Qty. 2)
DRAIN PLUG O-RING (Qty. 2)
UNION COLLAR (Qty. 2)
2” SLIP ADAPTER (Qty. 2)
O-RING, #2-231 (Qty. 2)
BASE SCREW, 5/16-14 X 1 IN LG HI-LO HEX
(Qty. 2)
MOTOR PAD
MOTOR BASE
TRAP COVER ASSEMBLY O-RING
50 FT. COMMUNICATION CABLE
Note: (*) Items not shown
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
29
TECHNICAL DATA
Pump Dimensions
664
26.1
291
11.4
95
3.7
362
14.2
274
10.8
435
17.1
249
9.8
371
14.6
114
4.5
177
7.0
Electrical Specifications
Circuit Protection: Two-pole 20 AMP device at the Electrical Panel.
Input: 230 VAC, 50/60 Hz, 3200 Watts Maximum, 1 phase
WEF 6.6 THP 3.95
Pump Performance Curves
Total Dynamic Head in Feet of Water
100
MAX SPEED - 3450 RPM
90
80
OPERATING RANGE FOR
FLOW CONTROL
SPEED 4 - 3110 RPM
70
60
50
SPEED 3 - 2350 RPM
40
30
20
SPEED 2 - 1500 RPM
10
0
SPEED 1 - 750 RPM
0
20
40
60
80
100
120
140
160
180
Volumetric Flow Rate in U.S. GPM
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
30
Operator Control Panel: Pump Menu Quick Reference Guide
MENU
SETTINGS
Press MENU button to access menus
Date and Time
Date
(pages 10-13)
Time
Hour Format
Months (1-12)
Days (1-31)
Years (2010-2100 Plus)
Hours (24hr Mode: 0-23) (12hr Mode: 1-12 AM & PM)
Minutes (0-60)
AM/PM - Default: AM/PM
24 Hour
Min/Max
Set Min Speed (450-1700 RPM) - Default: 450 RPM
Set Max Speed (1900-3450 RPM) - Default: 3450 RPM
Set Min Flow (20-70 GPM) - Default: 20 GPM
Set Max Flow (80-140 GPM) - Default: 140 GPM
Flow Limit Speed (Disabled / Enabled) - Default: Disabled
Max Pressure (1-50 PSI) - Default: 30 PSI
Pressure Limit Speed (Disabled / Enabled) - Default: Disabled
Device
Pump Address (1-16) - Default: 1
Contrast Level (1-5) - Default: 3
English - Default: English
Language
Português
Deutsch
Italiano
Nederlands
Español
Français
Temperature Unit
Fahrenheit - Default: F°
Celsius C°
Flow Unit
GPM - Default: GPM
LPM
M3 / H
Pressure Unit
PSI - Default: PSI
BAR
Password
Disabled - Default: Disabled
Enabled
Password Timeout (1 min. to 6 hrs.) - Default: 1 hour
Set Password (0000 - 9999) - Default: 1234
Fast - Default: Fast
Ramping
Ramp Up
Medium
Slow
Fast - Default: Fast
Ramp Down
Medium
Slow
Firmware Version
Alarm Log (1-10)
PROGRAM 1-8
Program 1-4
(pages 14-15)
Program 5-8
Manual
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM) - Default Program 1-2: Manual
Schedule
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Start Time
Stop Time
Egg Timer
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM) - Default Program 3-4: Egg Timer
Duration
Disabled
Schedule
Default: Disabled
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Start Time
Stop Time
MENU TREE
CONTINUES TO
NEXT PAGE
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
31
Operator Control Panel: Pump Menu Quick Reference Guide (cont.)
MENU TREE
CONTINUED FROM
PREVIOUS PAGE
EXT CONTROL
Program 1
Enabled - Default
(page 16)
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 750 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
Program 2
Enabled - Default
Program 3
Enabled - Default
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 1500 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 2350 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
Program 4
Enabled - Default
Type (Speed / Flow) Default: Speed
Set Speed or Flow - Default: 3110 RPM
Stop Delay (0 min. to 10 min.) Default: 0 Minutes
Pump Off
FEATURES
(page 17)
Time Out
Quick Clean
PRIMING
Disabled/Enabled
(pages 17-19)
Priming Speed
Max Priming Duration
Priming Range
THERMAL MODE
(page 20)
Time Out Duration (1 min. to 10 hrs.) Default: 3 hours
Type (Speed / Flow)
Set Speed or Flow (450-3450 RPM or 20-140 GPM)
Quick Clean Duration (1 min. to 10 hrs.) Default: 10 minutes
Disabled / Enabled - Default: Enabled
Set Speed (2400-3450 RPM) Default: 3450 RPM
(1 min. to 30 min.) Default: 11 minutes
(1 - 10) Default: 5
Priming Delay
(1 sec. to 10 min.) Default: 20 seconds
Loss of Prime
Enabled / Disabled - Default: Enabled
Disabled/Enabled
Disabled / Enabled - Default: Enabled
Set Type
Set Speed/Flow
Pump Temperature
Speed - Default: Speed
Flow
Set Speed (450-3450 RPM) Default 1000 RPM
Set Flow (20-140 GPM) Default: 40 GPM
40° F - 50° F (4.4° C through 10° C) Default: 40° F (4.4° C)
INTELLIPRO® VSF Variable Speed and Flow Pump Installation and User’s Guide
*356653*
LIT. PKG. P/N 356653
1620 HAWKINS AVE., SANFORD, NC 27330 • (919) 566-8000
10951 WEST LOS ANGELES AVE., MOORPARK, CA 93021 • (805) 553-5000
WWW.PENTAIRPOOL.COM
All Pentair trademarks and logos are owned by Pentair or one of its global affiliates. Sta-Rite®, IntelliPro®, IntelliComm®, EasyTouch®, IntelliTouch®,
SunTouch® and EcoSelect™ are trademarks and/or registered trademarks of Pentair Water Pool and Spa, Inc. and/or its affiliated companies in the
United States and/or other countries. Unless expressly noted, names and brands of third parties that may be used in this document are not used
to indicate an affiliation or endorsement between the owners of these names and brands and Pentair Water Pool and Spa, Inc. Those names and
brands may be the trademarks or registered trademarks of those third parties. Because we are continuously improving our products and services,
Pentair reserves the right to change specifications without prior notice. Pentair is an equal opportunity employer.
© 2018 Pentair Water Pool and Spa, Inc. All rights reserved. This document is subject to change without notice.
*356654*
P/N 356654 REV. D 7/17/18
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement