Bulletin E-71
Vane Operated Flow Switch
Specifications - Installation and Operating Instructions
3-11/32
[84.93]
2-23/32
[69.06]
1-5/8 [41.28]
CLEARANCE FOR
COVER REMOVAL
EXPLOSION-PROOF HOUSING
WITH 3/4 FEMALE NPT
CONDUIT CONNECTION
6-3/4
[171.45]
8
[203.20]
U.L. AND C.S.A. TYPE
INCLUDES 16 GA.
LEADS, 6 [152.4] LONG.
ATEX VERSION
INCLUDES TERMINAL
BLOCK
4-11/16
[119.06]
1 [25.40]
SWITCH BODY, SAE 72 BRASS
OR 316 STAINLESS STEEL
1-1/2 MALE NPT
PROCESS CONNECTION
MAGNET KEEPER,
430 STAINLESS STEEL
VANE BLOCK,
316 STAINLESS STEEL
FIVE LAYER VANE,
316 STAINLESS STEEL,
DESIGNED FOR 1-1/2˝ TO 8˝ PIPES.
USABLE IN LARGER PIPE SIZES.
Rugged and reliable the Flotect® V4 flow switch operates automatically to
protect equipment and pipeline systems against damage from reduction or loss of
flow. The V4 is time tested being installed in thousands of pipelines and processing
plants around the world. A unique magnetically actuated switching design gives
superior performance. There are no bellows, springs, or seals to fail. Instead, a freeswinging vane attracts a magnet within the solid metal switch body, actuating a snap
switch by means of a simple lever arm.
FEATURES
• Leak proof body machined from bar stock
• Choice of custom vane calibrated for your application, Model V4, or field
adjustable multilayer vane, Model V4-2-U (see set point chart on page 4)
• Weatherproof, designed to meet NEMA 4
• Explosion-proof (listing included in specifications)
• Installs directly and easily into pipeline with a thredolet, tee, or flange (see
application drawings on page 4)
• Can be used in pipes 1-1/2˝ and up
• Electrical assembly can be easily replaced without removing the unit from
installation so that the process does not have to be shut down
• High pressure rating of 1000 psig (69 bar) with the brass body and 2000 psig (138
bar) with the 316 SS body
APPLICATIONS
• Protects pumps, motors and other equipment against low or no flow
• Controls sequential operation of pumps
• Automatically starts auxiliary pumps and engines
• Stops liquid cooled engines, machines and processing when coolant
flow is interrupted
• Shuts down burner when air flow through heating coil fails
• Controls dampers according to flow
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 U.S.A.
SPECIFICATIONS
Service: Gases or liquids compatible with wetted materials.
Wetted Materials: Vane: 316 SS; Body: Brass or 316 SS standard; Magnet
Keeper: 430 SS standard, 316 SS optional; Options: Other materials also
available, consult factory (e.g. PVC, Hastelloy, Nickel, Monel, Titanium).
Temperature Limit: -4 to 275°F (-20 to 135°C) standard, MT high temperature
option 400°F (205°C) [MT option not UL, CSA, ATEX or IECEx] ATEX and IECEx
options, ambient temperature -4 to 163°F (-20 to 73°C); Process temperature -4
to 163°F (-20 to 73°C).
Pressure Limit: Brass body 1000 psig (69 bar), 316 SS body 2000 psig (138
bar), optional 5000 psig (345 bar) available with 316 SS body and SPDT switch
only.
Enclosure Rating: Weatherproof and Explosion-proof. Listed with UL and CSA
for Class I, Groups C and D; Class II, Groups E, F, and G.
ATEX
0518
II 2 G Ex db IIB T6 Gb -20°C≤Tamb≤73°C.
-20°C≤Process Temp≤73°C.
EC-Type Certificate No.: KEMA 03 ATEX 2383.
ATEX Standards: EN60079-0: 2012 + A11: 2013; EN60079-1: 2014.
IECEx Certified: For Ex db IIB T6 Gb -20°C≤Tamb≤73°C. -20°C≤Process
Temp≤73°C.
IECEx Certificate of Conformity: IECEX DEK 11.0071.
IECEx Standards: IEC 60079-0: 2011; IEC 60079-1: 2014.
Zone I. Also FM approved.
Switch Type: SPDT snap switch standard, DPDT snap switch optional.
Electrical Rating: UL, FM, ATEX and IECEx models 10A @ 125/250 VAC (V~).
CSA models: 5A @ 125/250 VAC (V~); 5A res., 3A ind. @ 30 VDC (V ). MV
option: 1A @125 VAC (V~); 1A res., .5A ind. @ 30 VDC (V ). MT option: 5A @
125/250 VAC (V~). [MT and MV option not UL, CSA, FM, ATEX or IECEx].
Electrical Connections: UL and CSA models: 16 AWG, 6˝ (152 mm) long. ATEX
or IECEx unit: Terminal block.
Conduit Connection: 3/4˝ female NPT or M25 x 1.5 with -BSPT option.
Process Connection: 1-1/2˝ male NPT or 1-1/2˝ male BSPT.
Mounting Orientation: Within 5° of vertical for proper operation. Units for
horizontal installation (vertical pipe with up flow) available.
Set Point Adjustment: For universal vane: five vane combinations.
Weight: 4 lb 8 oz (1.9 kg).
Notes:
• Check all ratings given in the instructions and on the product to make sure that the
product is suitable for your application. Do not exceed electrical ratings, pressure
ratings, or temperature ratings of the product.
• Disconnect power supply before beginning installation to prevent possible
equipment damage or electrical shock.
MAINTENANCE
Inspect and clean wetted parts at regular intervals. The cover should be in place at
all times to protect the internal components from dirt, dust, and weather, and to
maintain hazardous location ratings. Disconnect device from the supply circuit
before opening to prevent ignition of hazardous atmosphere. Repairs to be
conducted by Dwyer Instruments, Inc. Units in need of repair should be returned to
the factory prepaid.
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyermail.com
Example
Construction
Construction
Options
Magnet Keeper
Material Options
Vane Material
Options
Body Material
Options
V4
V4
SS
SS
2
D
U
3
1
2
3
1
1
2
3
4
5
Other
Options
Flange*
Flange Size
6
1
2
3
4
5
6
7
C
AT
BSPT
IEC
EPOXY
FSV
FTR
HP
HV
MT
MV
NACE
NB
NH
SW
TBC
TRD
TRI
V
F
F
Flange Material
2
2
2.5
3
4
Flange Rating
Bushing*
Bushing Size
B
Bushing Type
1
2
4
Bushing Material
Tee*
Tee Size
Tee with Bushing*
Tee Size
Tee Material
and Type
*Options that do not have ATEX or IECEx.
T
TB
1
2
3
S
C
S
M
B
H
H
F
1
1
3
6
9
B
C
S
4
B0
B1
B2
C
CP
S
P
V4-SS-316-C-F2S1
Brass Body, SPDT Switch
316 SS Body
Type 2 Body Style
DPDT Switch
Universal Vane (Omit for a custom vane)
430 SS (Standard)
Nickel 200
316 SS
316 SS (Standard)
Carpenter 20
Hastelloy B
Hastelloy C
Monel
Brass (Standard)
Carpenter 20
CPVC*
Hastelloy B
Hastelloy C
316 SS (Must also use SS construction selection)
Monel
ATEX
1-1/2˝ Female BSPT Process Connection, M25 x 1.5 Conduit Connection
IECEx
Epoxy Coated Housing
Full Swing Vane
Flow Test Report
High Pressure*, 5000 psi (345 bar) (Only with SS body)
Hinged Vane
High Temperature* (See specifications for rating)
Gold Contact Snap Switch* (See specifications for rating)
NACE Heat Treated Body*
Neoprene Boot*
No Electrical Housing*
Socket Weld Connection*
Terminal Block Wire Connections*
Time Delay Relay* (On flow decrease)
Time Delay Relay* (On flow increase)
Vertical Up Flow Applications
Flange Process Connection
2˝
2-1/2˝
3˝
4˝
Carbon Steel
316 SS
Monel
Hastelloy B
Hastelloy C
150#
300#
600#
900#
Bushing Process Connection
2˝
2-1/2˝
4˝
Hex
Flush
Brass
Carbon Steel
316 SS
304 SS
Tee Process Connection
1-1/2˝
Tee with Bushing Process Connection (Both same material)
2˝
3˝
Brass 125 #
Brass 150 #
Brass 250 #
Carbon Steel 2000 #(Only with 2˝ and 3˝)
CPVC SCH 80
316 SS 150 #
PVC SCH 80
Attention: Units without the “AT” suffix are not Directive 2014/34/EU (ATEX) compliant. These units are not intended for use in potentially
hazardous atmospheres in the EU. These units may be CE marked for other Directives of the EU.
ADJUSTMENT OF MULTI-LAYER VANE
Remove only those layers which are too long. Leave the smaller layers to
reinforce the vane. The longest vane fits 6˝ (150 mm) or larger pipe, the
second longest vane fits 4˝ (100mm) pipe, etc. Actuation-Deactuation rates
are shown in the charts on the next page. To remove vane layers, proceed as
follows:
3-11/32
[84.93]
2-23/32
[69.06]
1-5/8 [41.28]
CLEARANCE FOR
COVER REMOVAL
1
2
3
A
a. Remove the two screws and lockwashers holding the layers together. Do
not lose these special corrosion resistant type 316 stainless steel screws and
lockwashers.
5
B
C
F G
7
7
D
9
10
10
8
8
c. Resecure the vane with the original two screws and lockwashers.
6
6
PROCESS CONNECTION
1-1/2 MALE NPT
9
1
[25.40]
b. Remove the unwanted layers.
4
3
4
E
INSTALLATION
1. Remove packing material from switch body-cap and remove tape from magnet
keeper. Adjust vane length if necessary on multi-layer vanes only (see flow
rate charts on next page). Install switch in thredolet previously welded to line.
In some cases, it may be necessary to install the switch in a flange or tee (see
installation drawings on next page). Note: extreme care must be exercised in
welding the fitting to the line so that it is plumb and level.
d. With a hammer, lightly peen the ends of the screws so that they can't back
out.
e. If you lose the screws or lockwashers, don't replace with other parts which
may corrode and break. That will void the warrantee and might cause severe
damage to equipment located downstream of the switch.
2.
3.
Note: Custom vane units have been calibrated at factory to meet
requirements. Do not change.
The arrow on the side of the switch must point in the direction of flow.
Wiring: UL and CSA units only: thread connecting wires through conduit and
connect. Wire in accordance with local electrical codes.
Black - Common
Blue - N.O.
Red - N.C.
Standard V4V4
STANDARD
5. For units supplied with both internal ground and external bonding terminals, the
ground screw inside the housing must be used to ground the control. The external
bonding screw is for supplementary bonding when allowed or required by local
code. When external bonding conductor is required, conductor must be wrapped a
minimum of 180° about the external bonding screw. See below.
LOCKWASHER
CLAMP
ATEX and IECEx Installation Instructions:
Cable Connection
The cable entry device shall be certified in type of explosion protection
flameproof enclosure “d”, suitable for conditions of use and correctly installed.
Cable entry may exceed 70°C. Conductors and cable gland rated ≥95°C shall
be used.
4.
Note: The switch is deactivated and contacts are in normal condition when
there is no flow in the line.
Make sure conduit or cable are properly sealed. Electrical components must
be kept free of moisture, including condensation, at all times. CAUTION: To
prevent ignition of hazardous atmosphere, disconnect the device from the
supply circuit before opening. Keep assembly tightly closed when in operation.
Note: ATEX and IECEX units only: The temperature class is determined by
the maximum ambient and or process temperature. Units are intended to be
used in ambient of -20°C≤Tamb≤73°C. Units may be used in process
temperatures up to 133°C providing the enclosure and switch body
temperature do not exceed 73°C. The standard Temperature Class is T6
Process Temp ≤73°C.
CONDUCTOR
SCREW
Note: Double pole, double throw switches have dual black, blue and red
leads. These are connected in the same manner as single pole, double throw
switches, as described above.
Conduit Connection
An Ex d certified sealing device such as a conduit seal with setting compound
shall be provided immediately to the entrance of the valve housing. Cable
entry may exceed 70°C. Conductors and cable gland rated ≥95°C shall be
used.
ATEX/IECEx
unit
CENELEC V4
FRONT VIEW DETAIL
TERMINAL CONNECTIONS SPDT
Dim
A
B
C
D
E
F
G
V4 in(mm)
8-3/16 (207.96)
6 (152.40)
4-11/16 (119.06)
1 (25.40)
1-5/16 (33.34)
7/8 (22.23)
11/16 (17.46)
V4-2 in(mm)
8 (203.20)
6-3/4 (171.45)
3-15/16 (100.01)
1-3/4 (44.45)
9/16 (14.30)
11/16 (17.63)
1/2 (12.70)
Ref # Standard V4
1
N/A
2
N/A
3
Explosion-proof housing with 3/4˝
female NPT conduit connection.
4
16 AWG, 6˝ (152 mm) long.
5
Internal
6
Magnet arm and switch assembly.
7
Switch body of SAE 72 Brass or
316 SS.
8
Five layer vane, 316 Stainless
Steel, Designed for 1/2˝ to 8˝
pipes. Usable in larger pipe sizes.
9
Magnet keeper of 430 Stainless
Steel.
10
Vane block of 316 Stainless Steel.
SIDE VIEW DETAIL
TERMINAL CONNECTIONS DPDT
ATEX/IECEx unit
Cover lock.
External ground.
Explosion-proof housing with 3/4˝
female NPT conduit connection.
Terminal Block
Internal ground.
Magnet arm and switch assembly.
Switch body of SAE 72 Brass or
316 Stainless Steel.
Five layer vane, 316 Stainless
Steel, Designed for 1/2˝ to 8˝ pipes.
Usable in larger pipe sizes.
Magnet keeper of 430 Stainless
Steel.
Vane block of 316 Stainless Steel.
V4 Universal Vane Flow Charts
Values shown in both charts are nominal. If normal flows exceed actuation rates by less than 10%, custom vanes are recommended.
Figures are based on standard vertical installation in a 1-1/2" thredolet in a horizontal run of pipe.
VANE
LAYERS
1
APPROXIMATE ACTUATION/DEACTUATION FLOW RATES FOR COLD WATER.
UPPER FIGURES IN GPM. LOWER FIGURES IN LPM
1.5˝ PIPE
2˝ PIPE 3˝ PIPE
45-22
7-3
15-8
26.67-11.67 56.7-30 167-83.3
4˝ PIPE
6˝ PIPE
8˝ PIPE
160-115
80-60
27-19
11-7
41.7-26.7 102-71.7 300-233 600-433
1,2,&3
17-12
65-45
1,2,3,&4
1,2,3,4,&5
20˝ PIPE
12˝ PIPE
450-250
1700-950
900-500
1200-650 1450-800 1800-1000
650-350
2467-1317 3400-1900 4550-2467 5483-3033 6817-3783
230-150
867-567
310-200
1167-750
14˝ PIPE
16˝ PIPE
1200-600 1400-800 2000-1000 2400-1200
900-450
210-120 375-175 600-300
95-40
367-150 800-450 1417-667 2267-1133 3400-1700 4550-2267 5300-3033 7567-3783 9083-4550
130-90 230-150
50-35
23-14
7-4
26.7-15 86.7-53.3 190-132 500-333 867-567
1&2
18˝ PIPE
10˝ PIPE
120-90
60-45
233-167 450-333
80-65
40-30
152-113 300-250
300-180
1133-683
135-100
517-383
1000-600 1200-700
600-350
750-450
450-275
1700-1033 2267-1317 2750-2083 3783-2267 4550-2650
200-140
750-533
850-550
700-450
430-280
550-360
1633-1067 2083-1367 2650-1700 3217-2083
290-200
1100-750
360-250
1367-950
575-400
460-325
1733-1233 2183-1517
Actuation rates are based on cold water at a specific gravity of 1.0. For fluids of different specific gravity, actuation rates may be approximated by
dividing the rate shown by the square root of the specific gravity.
VANE
LAYERS
1
1&2
1,2,&3
1,2,3,&4
APPROXIMATE ACTUATION/DEACTUATION FLOW RATES FOR AIR.
UPPER FIGURES IN SCFM. LOWER FIGURES IN LPS
1.5˝ PIPE 2˝ PIPE 3˝ PIPE 4˝ PIPE 6˝ PIPE 8˝ PIPE
32-17
15-8
65-32
30-20
23-13
10-6
10˝ PIPE
12˝ PIPE
14˝ PIPE
16˝ PIPE
18˝ PIPE
20˝ PIPE
210-105 400-200 950-475 1550-850 2400-1300 3450-1900 4700-2600 6400-3500 8000-4400 10000-5500
100-50 190-90 450-220 730-400 1100-600 1600-900 2200-1200 3000-1700 3800-2100 4700-2600
120-70
60-30
60-48
30-20
1,2,3,4,&5
195-140 550-375 1100-700 1850-1200 2700-1750 3400-2200 4800-3100 6000-3900 7400-4800
1300-800 1600-1000 2300-1500 2800-1800 3500-2300
90-70
260-180 520-330 870-570
135-100 375-265 725-500
60-50
180-130 340-240
65-50
30-20
260-200 500-400
120-90 240-190
130-100 310-250
150-120
60-50
1200-850
570-400
1850-1300 2600-1800 3350-2350 4300-3000 5300-3700
870-610
1200-800 1600-1100 2000-1400 2500-1700
650-525
310-250
1000-800
470-380
875-700
410-330
1250-1000 1900-1500 2500-2000 3100-2500 3900-3100
1200-900 1500-1200 1800-1500
590-470
900-710
1600-1250 2200-1750 2800-2250 3550-2850
1040-830 1300-1100 1700-1300
760-590
Actuation rates are based on air at standard conditions. For gases at other pressures, temperatures, or specific gravities, consult factory for
equivalent flow approximations.
APPLICATION DRAWINGS FOR FLOTECT® AUTOMATIC FLOW SWITCHES
Standard Installation
1-1/2˝ X 1-1/2˝ X 1-1/2˝
Tee Installation
Flange Installation
©Copyright 2018 Dwyer Instruments, Inc.
2˝ X 2˝ X 2˝
Tee Installation
Printed in U.S.A. 3/18
W.E. ANDERSON DIV., DWYER INSTRUMENTS, INC.
P.O. BOX 358 • MICHIGAN CITY, INDIANA 46360 U.S.A.
2-1/2˝ Thredolet Installation
Phone: 219/879-8000
Fax: 219/872-9057
FR# 82-440629-00 Rev. 7
www.dwyer-inst.com
e-mail: info@dwyermail.com