Dwyer | Series FIV & FIP | Instruction manual | Dwyer Series FIV & FIP Instruction Manual

Dwyer Series FIV & FIP Instruction Manual
Bulletin G-65
Series FIP Pulse Input Flow Meter
Specifications – Installation and Operating Instructions
• Pulse, Open Collector, NPN, PNP, TTL, Switch, or Square Wave Inputs
• Full Six Digit Display for Total, 4_ Digit + Extra Zero for Rate
• Display in Engineering Units; Rate per Second, Minute, or Hour
• K-Factor, Internal, or External Calibration
• Scale Without a Calibrator or Calibrate with a Signal Source
• 11-Point Linearization for Non-Linear Inputs
• Low-Flow Cutoff
• NEMA 4X, IP65 Front Panel
• 12 or 24 VDC Field Selectable Sensor Supply Standard
• 115 VAC or 230 VAC Power Options
• Quick Preset Change Feature for Batch Control
• 2 Relays +/or 4-20 mA Output Options
DWYER INSTRUMENTS, INC. Phone: 219/879-8000
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: info@dwyer-inst.com
Series FIP Frequency/Pulse Meter
Instruction Manual
Table of Contents
INTRODUCTION------------------------------------------------------------- 5
Features--------------------------------------------------------------------------------- 5
Ordering Information--------------------------------------------------------------- 7
Specifications------------------------------------------------------------------------- 9
Basic Rate Meter ------------------------------------------------------------------ 9
Rate/Totalizer/Batch Controller Features--------------------------------- 12
Options ----------------------------------------------------------------------------- 13
Display Functions and Messages ------------------------------------------- 16
SETUP AND PROGRAMMING----------------------------------------- 18
Overview------------------------------------------------------------------------------ 18
Jumpers and Switch Configuration ---------------------------------------- 19
Overview --------------------------------------------------------------------------- 19
Jumper Arrays & Switch Function ------------------------------------------ 19
Connections ------------------------------------------------------------------------- 21
Overview --------------------------------------------------------------------------- 21
Wiring Instructions -------------------------------------------------------------- 21
AC Power and Signal Connector ------------------------------------------- 22
Power Connections ------------------------------------------------------------- 23
Signal Connections ------------------------------------------------------------- 24
Acknowledgement, Reset Total Connections --------------------------- 26
Optional Relays and 4-20 mA Output Terminals ----------------------- 27
Isolated 4-20 mA Output Option Connections -------------------------- 28
Programming ----------------------------------------------------------------------- 29
Overview --------------------------------------------------------------------------- 29
General Programming Description ----------------------------------------- 29
ENTER and ACK Functionality ------------------------------------------ 29
Five Basic Digit/Display Setting Instructions------------------------- 30
Basic Meter Programming ---------------------------------------------------- 32
Overview ----------------------------------------------------------------------- 32
Quit Menu Scroll, Diagnostic, and Calibration----------------------- 32
Minimum Input Span (Error Message) --------------------------------- 32
Select Input Signal ---------------------------------------------------------- 33
Select K-Factor, Calibration, or Scaling Method-------------------- 34
Set Rate and Total Decimal Point -------------------------------------- 35
Scale or Calibrate the Meter---------------------------------------------- 36
Scale Using K-Factor (FActor)---------------------------------------- 36
Scale Using Internal Calibration (I-CAL) -------------------------- 36
Calibration Error (error) ------------------------------------------------- 37
Calibrate Using External Calibration (E-CAL) ------------------- 39
Gate Function (Gate)------------------------------------------------------------ 40
2
Series FIP Frequency/Pulse Meter
Instruction Manual
Programming the Gate (Gate) -------------------------------------------- 40
Contact De-Bounce Filter (FILter) ------------------------------------------ 42
Gate and Filter Settings---------------------------------------------------- 42
Rate Meter Setup---------------------------------------------------------------- 43
Overview ----------------------------------------------------------------------- 43
Set Display to Rate (dSPy r) ---------------------------------------------- 43
Low-Flow Cutoff Programming (Cutoff) ------------------------------- 44
Totalizer Programming--------------------------------------------------------- 45
Overview ----------------------------------------------------------------------- 45
Set Display for Total (dSPy t) --------------------------------------------- 45
Set Rate Time Base (t baSE) --------------------------------------------- 46
Set Totalizer Conversion Factor (tot CF) ------------------------------ 46
Set Totalizer Decimal Point ----------------------------------------------- 48
Set Alternating Total/Rate Display-------------------------------------- 49
Parameter Combinations Resulting in error1 Message ----------- 49
Set Point Setup and Programming ----------------------------------------- 50
Overview ----------------------------------------------------------------------- 50
Set Relays for Manual or Automatic Reset--------------------------- 51
Set Relays for Fail-Safe Operation ------------------------------------- 51
Assigning Set Points to Rate or Total (setup) ------------------------ 52
Rate or Total, Latching or Non-Latching Relays (Setup) ------ 53
Programming Internal Total Reset and Delay (DELAy)------- 56
Programming Alarm Points and Presets (SEtPtS) ------------------ 57
Overview ------------------------------------------------------------------- 57
Set and Reset Points for Rate Alarms ----------------------------- 57
Preset Values for Total Set Points ---------------------------------- 57
Preset Offset Values for Total Set Points (OFFSET) ----------- 57
Programming Alarm and Preset Values (SEtPtS) --------------- 58
Isolated 4-20 mA Output Programming (output) ------------------------ 61
4-20 mA Output Programming Confirmation--------------------- 61
Lockout and Display Selection Programming --------------------------- 62
Overview ----------------------------------------------------------------------- 62
Lockout ------------------------------------------------------------------------- 62
Display Selection (dSPLAy) ----------------------------------------------- 63
Include or Exclude Menu Titles from Menu Scroll -------------- 65
Alternating Display------------------------------------------------------- 66
OPERATION---------------------------------------------------------------- 67
Overview------------------------------------------------------------------------------ 67
Two Types of Display: Rate and Total ------------------------------------- 68
Basic Meter Operation----------------------------------------------------------- 69
Overview --------------------------------------------------------------------------- 69
ENTER and ACK Button Operation ---------------------------------------- 69
3
Series FIP Frequency/Pulse Meter
Instruction Manual
Display Peak & Reset Peak Operation (DSPy P & Rset P) ----------- 70
Rate Meter Operation ------------------------------------------------------------ 71
Overview --------------------------------------------------------------------------- 71
Display Rate (dSPy r) ----------------------------------------------------------- 71
Low-Flow Cutoff (CutoFF) ----------------------------------------------------- 71
Totalizer Operation --------------------------------------------------------------- 72
Overview --------------------------------------------------------------------------- 72
Display Total (dSPy t) ----------------------------------------------------------- 72
Total Conversion Factor (tot CF) and Time Base (t bASE)----------- 72
Applications Using Conversion Factor and Time Base ----------- 73
Totalizer Reset ------------------------------------------------------------------- 74
Resetting Total Using the ENTER Button ---------------------------- 74
Resetting Total via External Contact Closure ----------------------- 74
Resetting Total Automatically via User Selectable Preset ------- 74
Relays Operation ------------------------------------------------------------------ 75
Overview --------------------------------------------------------------------------- 75
Relays Auto Initialization ------------------------------------------------------ 75
Fail-Safe Operation ------------------------------------------------------------- 75
Front Panel LEDs --------------------------------------------------------------- 76
Latching and Non-Latching Relay Operation---------------------------- 76
Acknowledging Relays--------------------------------------------------------- 79
Delay on Release (delay) ------------------------------------------------------ 79
Priority Batch Programming or Quick Presets -------------------------- 79
Switching Inductive Loads ---------------------------------------------------- 80
Switching AC and DC Loads --------------------------------------------- 80
Switching Low Voltage DC Loads -------------------------------------- 80
Lockout and Display Selection Operation ------------------------------- 81
Overview --------------------------------------------------------------------------- 81
Low Voltage Detector ------------------------------------------------------------ 81
Diagnostic (dIA9) Feature ------------------------------------------------------ 81
Overview --------------------------------------------------------------------------- 81
Operation -------------------------------------------------------------------------- 81
Reset Meter to Factory Defaults --------------------------------------------- 81
OPTIONS CARD REMOVAL & INSTALLATION ------------------ 82
PROGRAMMED PARAMETER SETTINGS------------------------- 84
MOUNTING DIMENSIONS ---------------------------------------------- 87
4
Series FIP Frequency/Pulse Meter
Instruction Manual
List of Figures
Figure 1.
Input Signal Selection & Lockout ...................................19
Figure 2.
Relay Acknowledge Enable & Fail-Safe Jumper...........20
Figure 3.
AC Power & Signal Connector Diagram ........................22
Figure 4.
Input Power Connections ................................................23
Figure 5.
Flowmeter Powered by Internal Power Supply.............24
Figure 6.
Flowmeter Powered by External Supply........................24
Figure 7.
Self-Powered Magnetic Pickup Flowmeter....................25
Figure 8.
Open Collector Transistor Output ..................................25
Figure 9.
Switch Contact Closure ...................................................26
Figure 10. External Control Connections.........................................26
Figure 11. Connectors Location - Rear View of Meter....................27
Figure 12. Output Loop Powered by Meter ......................................28
Figure 13. Output Loop Powered from External Supply ................28
Figure 14. K-Factor Scaling Flowchart .............................................31
Figure 15. Input Signal Selection & Lockout ...................................33
Figure 16. Functions Locked Out with Lockout Jumper................62
Figure 17. Menu Titles Excluded with Dsplay Menu ........................64
Figure 18. Meter Displaying Process/Rate .......................................68
Figure 19. Meter Displaying Total......................................................68
Figure 20. AC and DC Loads Protection ..........................................80
Figure 21. Low Voltage DC Loads Protection..................................80
Figure 22. Front Cover Removal........................................................82
Figure 23. Options Card Installation .................................................83
Figure 24. Mounting Dimensions ......................................................87
Figure 25. Panel Cutout Dimensions ................................................87
introduction
This instrument is a frequency/pulse input meter with flow rate, totalizer,
and batch control capabilities housed in a 1/8 DIN high-impact plastic
enclosure with a NEMA 4X front. It accepts pulse (±125 mV to ±12 V),
square wave (0-5 V, 0-12 V, or 0-24 V), open collector (NPN or PNP),
TTL, or switch contact closure signals; and displays these signals in
engineering units on a 0.56" high 4_ digit LED display. The meter also
provides one isolated 12 VDC or 24 VDC power supply to drive either
the input or output loops. Options include up to 2 relays for alarms or
batch controlling as well as an isolated 4-20 mA transmitter output.
Features
Dwyer Instruments, Inc. is committed to improving its products and this
model contains several features of interest:
5
Series FIP Frequency/Pulse Meter
Instruction Manual
• Relay Fail-Safe Jumper Easily Accessible on Display Board
• Programmable Set Points for Latching and Non-latching Operation
• Any Set Point Programmable for Rate or Total
• Quit Main Menu Scroll, Diagnostic, and Calibration with ACK Button
• Programmable Gate Function for Slow Pulse Rates
• Programmable Contact De-Bounce Filter for Noisy Contacts
• Diagnostic Menu for Troubleshooting Programmed Parameters
6
Series FIP Frequency/Pulse Meter
Instruction Manual
Ordering Information
115 VAC
Model
FIP-2100
FIP-2110
FIP-2111
230 VAC
Model
FIP-2200
FIP-2210
FIP-2211
7
Options
Installed
No Options
2 Relays
2 Relays +
4-20 mA Out
Series FIP Frequency/Pulse Meter
Instruction Manual
Safety Notice
!
CAUTION: Read complete
instructions prior to installation and
operation of the meter.
!
!
WARNING: Risk of electric
shock.
Observe all safety regulations. Electrical wiring should be
performed in accordance with all applicable national, state
and local codes to prevent damage to the meter and ensure
personnel safety.
Do not use this meter to directly drive heavy equipment such
as pumps, motors, valves, etc.
It is recommended to use this meter in a fail-safe system that
accommodates the possibility of meter failure or power
failure.
WARNING
Hazardous voltages exist within enclosure. Installation and service
should be performed only by trained service personnel.
AVERTISSEMENT
Les pièces à l'intérieur du boîtier portent des tensions
dangereuses. Seules des personnes qualifiées et bien entrainées
devraient entreprondre l'ótalonnage et la maintenance.
Disclaimer
The information contained in this document is subject to change without
notice. Dwyer Instruments, Inc. makes no representations or warranties
with respect to the contents hereof, and specifically disclaims any
implied warranties of merchantability or fitness for a particular purpose.
8
Series FIP Frequency/Pulse Meter
Instruction Manual
Specifications
Except where noted all specifications apply to operation at +25°C.
Basic Rate Meter
INPUTS
Field selectable: Pulse or square wave 0-5 V, 0-12 V, or
0-24 V @ 30 kHz; TTL; open collector 4.7 k pull-up to
12 V @ 30 kHz; NPN or PNP transistor, switch contact
4.7 k pull-up to 12 V @ 40 Hz.
LOW VOLTAGE
MAG PICKUP
(Isolated)
Sensitivity: 125 mVp-p
Hysteresis: 30 mV
MINIMUM INPUT
FREQUENCY
0.0101 Hz
Minimum frequency is dependent on high gate setting.
MAXIMUM INPUT
FREQUENCY
30,000 Hz
INPUT
IMPEDANCE
Pulse input: Greater than 300 k @ 1 kHz.
Open collector/switch input: 4.7 k pull-up to 12 V.
DISPLAY
Six digit, 0.56" (14.2 mm) red seven-segment LED
Rate: -19999(0) to 29,999(0) with selectable extra zero
Total: 0 to 999,999; automatic lead zero blanking
DECIMAL POINT
Rate: 2.9999, 29.999, 299.99, 2999.9, or extra zero
may be turned on 299990
Total: 9.99999, 99.9999, 999.999, 9999.99, 99999.9
Rate and total decimal points are independent of each
other.
CALIBRATION
May be calibrated using K-factor, internal calibration, or
by applying an external calibration signal.
K-FACTOR
Field programmable K-factor converts input pulses to
rate in engineering units. May be programmed from
0.00001 to 999,999 pulses/unit.
MULTI-POINT
LINEARIZATION
2 to 11 points
Meter may be calibrated or scaled using up to 11 points.
CALIBRATION
RANGE
Input 1 signal may be set anywhere in the range of the
meter; input 2 signal may be set anywhere above or
below input 1 setting. An Error message will appear if
input 1 and input 2 signals are too close together.
Minimum input span between any two inputs is 3 Hz.
9
Series FIP Frequency/Pulse Meter
Instruction Manual
FILTER
Programmable contact de-bounce filter: 40 to 950 Hz
maximum input frequency allowed (Low speed filter).
TIME BASE
Seconds, minutes, or hours
GATE
Low gate: 1-98 seconds
High gate: 2-99.9 seconds
OUTPUT
POWER
Isolated power supply field selectable, 12 VDC @
50 mA for sensor or 24 VDC ± 5% @ 20 mA for output
transmitter, regulated. Maximum loop resistance is
1200 (AC powered units only).
ACCURACY
±0.1% FS
ALARM POINTS
Four, any combination of high or low alarms
ALARM POINT
DEADBAND
0-100% FS, user selectable
ALARM STATUS
INDICATION
Front panel LED
PEAK HOLD
(MAX DISPLAY)
Captures the peak rate and displays it via the front
panel ENTER button (Dspy p)
PEAK HOLD
INDICATION
Front panel flashing R LED
LOCKOUT
Jumper JP2 restricts modification of calibration values.
NON-VOLATILE
MEMORY
All programming and totalizer values are stored in nonvolatile memory for a minimum of ten years if power is
lost.
POWER OPTIONS
115 or 230 VAC ±10%, 50/60 Hz, 12 VA
ISOLATION
1500 VAC
ENVIRONMENTAL Operational ambient temperature range: 0 to +60°C
Storage temperature range: -40 to +85°C
Relative humidity: 0 to 90% non-condensing
ENCLOSURE
1/8 DIN, high impact plastic, UL 94V-0
FRONT PANEL
Type 4X, NEMA 4X, IP65; panel gasket provided. Some
applications require the use of silicone RTV to ensure a
Type 4X seal
MOUNTING
1/8 DIN panel cutout required.
Two panel mounting brackets provided.
10
Series FIP Frequency/Pulse Meter
Instruction Manual
OVERALL
DIMENSIONS
2.30 x 4.25 x 5.30 in (58 x 108 x 135 mm)
WEIGHT
19.7 oz (559 g) (including options)
CONNECTIONS
Removable screw terminal blocks, accept 12 to 22
AWG wire
WARRANTY
1 years parts & labor
11
Series FIP Frequency/Pulse Meter
Instruction Manual
Rate/Totalizer/Batch Controller Features
RATE DISPLAY
INDICATION
LED labeled R on right illuminates when meter is
displaying rate input.
LOW-FLOW
CUTOFF
Any input below the low-flow cutoff value will result
in a display of zero. May be set from 1 count to
100% F.S., user selectable. To disable low-flow
cutoff, program cutoff value to zero.
In multi-point calibration/scaling, the total is based
on the rate display; so, inputs below the low-flow
cutoff value will not affect the totalizer.
In K-factor scaling, the totalizer ignores the low-flow
cutoff; the totalizer counts every incoming pulse
regardless of the rate display.
ALTERNATING
DISPLAY
Display may be programmed to alternate between
rate and total every 10 seconds.
TOTAL DISPLAY
0 to 999,999; automatic lead zero blanking
TOTAL DECIMAL
POINT
May be set in any of the following positions:
9.99999, 99.9999, 999.999, 9999.99, or 99999.9
Total and rate decimal points are independent.
TOTAL
CONVERSION
FACTOR
Programmable from 0.00001 to 59999.
This is a multiplier applied to the rate display to
obtain the total in any engineering units.
TOTALIZER
In multi-point calibration/scaling, the meter
calculates the total based on rate display and field
programmable total conversion factor to display total
in engineering units. Time base must be selected
according to time units in which rate is displayed.
In K-factor scaling, the meter calculates the total
based on the input pulses, K-factor value, and total
conversion factor.
TOTALIZER
ROLLOVER
Totalizer rolls over when display exceeds 999,999.
Relay status reflects the display.
TOTALIZER
PRESETS
Up to four, user selectable under setup menu Setup.
Any set point can be assigned to total and may be
programmed anywhere in the range of the meter.
PRESET OFFSET
Relays assigned to total can be programmed to trip
at any point below the next relay’s preset value.
12
Series FIP Frequency/Pulse Meter
Instruction Manual
PROGRAMMABLE
DELAY ON
RELEASE
If the meter is programmed to reset total to zero
automatically when the highest preset is reached,
then a delay will occur before the total relays reset.
This delay can be programmed anywhere between 1
and 999 seconds.
PRIORITY BATCH
PROGRAMMING
This feature allows the user to quickly change preset
values without going into the main menu by holding
the ENTER button for more than 3 seconds.
TOTAL RESET
Via front panel ENTER button, external contact
closure, or automatically via user selectable preset.
TOTAL RESET
LOCKOUT
Meter may be programmed so total cannot be reset
from the front panel.
Options
Relays
RATING
2 SPDT (Form C); rated 2 A @ 30 VDC or 2 A @
1
250 VAC resistive load; /14 HP @ 125/250 VAC for
inductive loads
ASSIGNED TO
RATE OR TOTAL
Any relay may be assigned to rate or total.
ELECTRICAL
NOISE
SUPPRESSION
A suppressor (RC network) to prolong the life of the
relays should be connected to each relay contact
switching inductive loads. The suppressor provides
a degree of protection against electrical noise
caused by inductive loads. Recommended
suppressor value, 0.01 F/470 , 250 VAC. See
page 80.
DEADBAND
0-100% FS, user selectable
HIGH OR LOW
ALARM
User may program any alarm for a high or low trip
point.
RELAY
OPERATION
Latching or non-latching, field selectable
FAIL-SAFE
OPERATION
Relay coils are energized in non-alarm condition. In
case of power failure, relays will go to alarm state.
Fail-safe operation may be disabled, by removing
jumper JP6 located on the Display Board.
AUTO
INITIALIZATION
When power is applied to the meter, relays assigned
to total will reflect the state of the accumulated total
value in memory. Relays assigned to rate will reflect
the state of the input to the meter.
13
Series FIP Frequency/Pulse Meter
Instruction Manual
RELAYS RESET
User select via JP3 jumper array and SetuP menu
Total relays reset
When total is reset to zero, if set up for external total
reset
After delay has elapsed, if set up for internal total
reset
Manual any time, if set up for external total reset (via
user supplied external contact closure at terminals
AK and CM or front panel ACK button)
Manual reset resets all manually resettable relays.
Rate relays reset
Automatic reset only
Manual reset only, at any time
Automatic plus manual reset at any time
Manual reset only after alarm condition has been
corrected
Automatic reset: Relays will automatically reset
when the input passes the reset point.
Manual reset: Performed via user supplied external
contact closure at terminals AK and CM or front
panel ACK button. Manual reset resets all manually
resettable relays.
14
Series FIP Frequency/Pulse Meter
Instruction Manual
Isolated 4-20 mA Transmitter Output
CALIBRATION
RANGE
The transmitter output can be calibrated so that a
4 mA output is produced for any rate measured by
the meter. The 20 mA output may correspond to any
rate that is at least 501 counts greater or smaller
than the rate corresponding to 4 mA. (Ex. 4 mA = 0,
20 mA = 501) If the span between 4 and 20 mA is
less than 501 counts, an error message will appear.
NO EQUIPMENT
NEEDED
The 4-20 mA output from the meter is calibrated
without the use of a calibrator.
OUTPUT LOOP
POWER
24 VDC ± 5% @ 20 mA, regulated
Maximum loop resistance is 1200 . Output loop is
isolated from input.
ACCURACY
± 0.1% FS ± 0.004 mA
ISOLATION
500 VDC or peak AC, input-to-output or input/outputto-24 VDC supply
EXTERNAL
LOOP-POWER
SUPPLY
35 VDC max
OUTPUT LOOP
RESISTANCE
Power supply
24 VDC
35 VDC (external)
15
Minimum
Maximum
10 600 600 1000 Series FIP Frequency/Pulse Meter
Instruction Manual
Display Functions and Messages
The meter displays various functions and messages during operation
and programming. The following table shows the various displayed
functions and messages with their description.
Display
Parameter
Description/Comments
Indicates an input voltage below
specifications during power up.
Indicates the input signal is below the
negative range of the meter.
Indicates number of calibration points
selected (2 to 11 points can be selected).
Indicates the input signal exceeds the fullscale range of the meter.
Calibrates meter using a calibrated signal
source.
Sets meter to display zero below
programmed cutoff point.
Sets the decimal position for total and rate
18888L
Low Voltage
-19999
Underrange
2 PtS
2 Points
29999
Overrange
CALIb
External Calibration
CutoFF
Low-Flow Cutoff
DECpt
Decimal Point
Delay
Delay
DIA9
Diagnostic
DspLAy
Display
Dspy 1
Display 1
Sets delay on release between 1 and 999
seconds for internal total reset.
Displays parameter settings one at a time for
diagnostic purposes. Setting cannot be
changed under this function.
Sets menu title scroll, selections are activated
with lockout jumper installed.
Value displayed at input 1.
Dspy 2
Display 2
Value displayed at input 2.
DSPy P
Display Peak
Displays the highest rate value captured.
DSPy r
Display Rate
Sets rate as default display.
DSPy t
Display Total
Sets total as default display.
E rSt
External Total Reset
E-CAL
External Calibration
Error
Error
Indicates total does not reset to zero when
preset value is reached.
Sets meter to be calibrated using a calibrated
signal source.
Indicates calibration was not successful.
Error1
Error 1
FActor
K-factor Scaling
FILtEr
Filter
Gate
Gate
Indicates a combination of parameters that
exceeds the totalizer capabilities.
Programs unit to convert input pulse to rate in
engineering units.
Sets filter value from 2 to 50. Maximum
frequency is 950 to 40 Hz respectively.
Sets low and high gate values to allow rate
display of slow pulse rates.
16
Series FIP Frequency/Pulse Meter
Display
Instruction Manual
Parameter
Description/Comments
Sets time base to display rate in units per
hour.
Sets high gate value from 2.0 to 99.9
Hour
Hour
HI
High Gate
HI SPd
High Speed Filter
I or e
Internal or External
I rSt
Internal Total Reset
I-CAL
Internal Calibration
Inpt 1
Input 1
Sets meter to high speed filter. Maximum
frequency is 30,000 Hz.
Sets operation of total reset; internal or
external.
Indicates total will reset to zero when highest
preset value is reached.
Sets meter for internal calibration to scale
meter without applying an input signal.
Sets Input 1 value.
Inpt 2
Input 2
Sets Input 2 value.
LatCk
Latch
LO
Low Gate
Sets rate set points for latching or nonlatching relay operation.
Sets low gate value from 1.0 to 98.9
LO SPd
Low Speed Filter
min
Minute
No PtS
Number of Points
OFFSET
Preset Offset
outPut
Output
PtS
Multi-Point
Calibration
R or t
Rate or Total
Rate
Rate
Rset P
Reset Peak
RSEt t
Reset Total
SCALE
Scale
SeC
Second
SEt 1
Set Point 1
Scales meter using internal calibration for
desired display (signal source not required).
Sets time base to display rate in units per
second.
Sets operation and value for set point 1.
SEt 2
Set Point 2
Sets operation and value for set point 2.
SEt 3
Set Point 3
Sets operation and value for set point 3.
SEt 4
Set Point 4
Sets operation and value for set point 4.
Sets meter for low speed filter. Maximum
frequency is 950 Hz.
Sets time base to display rate in units per
minute.
Sets meter for 2 to 11 calibration points.
Sets preset offset value (relay n trips at a
point below relay n+1 preset value).
Sets the optional 4-20 mA output values.
Selects internal or external, multi-point
calibration. Power up meter with ENTER
button pressed.
Assigns relay set points to rate or total.
Sets rate decimal point, or it Indicates set
point was assigned to rate.
Erases peak value from memory and
captures a new peak reading.
Resets the totalizer to zero.
17
Series FIP Frequency/Pulse Meter
Display
Instruction Manual
Parameter
Description/Comments
SetPtS
Set Points
Sets alarm set /reset points and total presets.
Setup
Setup
t bASE
Time Base
Tot CF
Totalizer Conversion
Factor
Sets operation of set points for rate or total,
latching or non-latching, etc.
Sets meter with correct time unit factor
(seconds, minutes, or hours).
Sets multiplier factor to display total in any
engineering unit.
TotAL
Total
y or n
Yes or No
Sets total decimal point, or it indicates set
point was assigned to total.
Sets selection or de-selection of various
functions.
SETUP AND PROGRAMMING
Overview
Setting up and programming the meter involves three basic steps:
1. Jumper Configuration (Page 19)
a. Input selection and lockout jumpers
b. Relay acknowledge enable
c. Fail-safe operation of relays
2. Connections (Page 20)
a. Power
b. Input signal
c. Acknowledgement and reset total
d. Relays
e. 4-20 mA output
3. Programming (Page 29)
a. Basic meter
b. Rate meter
c. Totalizer
d. Batch controller
e. Relays
f. 4-20 mA output
g. Lockout and display selection
Programmed Parameter Settings
To simplify programming, write down the desired programming settings
prior to attempting to program the meter. The Programmed Parameter
Settings form located on page 84 provides a convenient method to
record the user settings; it also provides the factory settings for most of
the programmable parameters.
18
Series FIP Frequency/Pulse Meter
Instruction Manual
Jumpers and Switch Configuration
Overview
Before programming the meter, it is necessary to configure three jumper arrays
and switch S1. The jumper arrays and switch S1 are used for setting the type of
input signal; excitation voltage, enable relay acknowledgement (ACK), and
setting relay fail-safe operation. Removing the lockout jumper enables the
programming functions.
Jumper Arrays & Switch Function
Function
Label
Input Signal
Excitation
Lockout
Relay ACK Enable
Fail-Safe
JP5, JP7, S1
JP1
JP2
JP3
JP6
Location
Diagram
Main Board
Figure 1
Display Board
Display Board
Figure 2
Figure 2
P+
P-
S-
S+
CM
R
1
3
JP5
JP7
3
3
2
1
AK
1
2
4.7k Internal
Resistor
3
2
1
EXCITATION
LOCKOUT
JP5
JP1
JP2
B A
JP7
S1
INPUT
SELECTION
2
MAIN PCB
+5V +12V
Signal
Figure 1.
Function
±125 mV to ±12 V
Pulse Input
0-5 V Pulse Input
0-24 V Pulse Input
NPN Input
PNP Input
12 VDC (P+, P-)
Excitation
24 VDC (P+, P-)
Excitation
Lockout
Input Signal Selection & Lockout
JP5
(1-2)
JP5
(2-3)
JP7
(1-2)
JP7
(2-3)
Switch
S1
Off
On
Off
On
B
On
Off
Off
Off
Off
On
On
On
Off
Off
Off
On
On
On
On
Off
A
A
A
A
JP1
JP2
On
Off
On
19
Series FIP Frequency/Pulse Meter
Instruction Manual
ACK ENABLE 1
JUMPERS 2
FAIL-SAFE
JUMPER
JP6
JP3
SOLDER
PADS
Figure 2.
Relay Acknowledge Enable & Fail-Safe Jumper
Relay Acknowledge Enable (Display Board)
Jumper JP3 Position
Function
1
Enable relay 1 manual reset
2
Enable relay 2 manual reset
Fail-Safe Operation of Relays (Display Board)
Jumper
Function
JP6 Position
On
Apply fail-safe function to the relays
Off
Disable fail-safe function to the relays
20
Series FIP Frequency/Pulse Meter
Instruction Manual
Connections
Overview
The following connections are made to removable screw terminal
connectors supplied with each meter:
• Power
• Input Signal
• Acknowledgement and Reset Total
• Relays
• 4-20 mA Output
Disconnect power to the meter prior to performing the
following procedures.
Wiring Instructions
Refer to Figure 3 for connectors’ location.
1. All field connections to be made with insulated copper wire, either
solid or stranded. Tighten all screw terminals to 4.5 in-lb (0.5 Nm).
Strip length = _ in (7 mm). DO NOT pre-treat wire with solder.
2. Terminals L, L on Main Board connector and terminals 1-6 on
J2, Options Board: Use AWG #12-18 wire, 600 volt, 60°C.
Connect only one wire to each terminal.
3. Terminals AK, R, CM, S+, S-, P-, P+ on Main Board and
terminals +, - on Options Board: Use AWG #12-22 wire, 150 volt,
60°C. If using AWG #20 or smaller wire, up to two wires may be
connected to each terminal. If using AWG #18 or larger wire, only
one wire may be connected to each terminal.
Terminals Designation
Terminal
Description
Terminal
Description
L, L
AC input power
R
P+, P-
12 or 24 VDC
output power
Input signal
Common (return)
for AK and R
AK
External total
reset
External relay
acknowledge
4-20 mA output
Relays 1-4
S+, SCM
+, 1-6
21
Series FIP Frequency/Pulse Meter
Instruction Manual
AC Power and Signal Connector
AC
PWR
INPUT
SELECTION
EXCITATION
L
L
P+
P-
S-
S+
CM
R
JP5
A
3
2
1
JP1
JP2
B
JP7
S1
LOCKOUT
3
2
1
AK
MAIN PCB
Figure 3.
AC Power & Signal Connector Diagram
22
Series FIP Frequency/Pulse Meter
Instruction Manual
Power Connections
Disconnect power to the meter before making any connections.
Connecting 230 VAC to meters designed for 115 VAC will result in
damage to the instrument as well as endanger personnel.
!
Do not connect power or earth ground to any unused or CM terminals.
Connect power to terminals L and L on Main Board screw terminal
connector, located at the rear of the instrument.
Notice:
•
Primary voltages must not be accessible to the user.
•
Primary wires must be installed in accordance to the applicable
standards.
•
Keep the primary wires separated from signal cables.
PWR
L
L
S-
S+
CM
R
MAIN PCB
Figure 4.
Input Power Connections
23
AK
Series FIP Frequency/Pulse Meter
Instruction Manual
Signal Connections
Signal connections are made to the connector on the Main Board. This
connector also includes connections for power, acknowledgement, reset
total, and common. Refer to Figure 3 for location.
Flowmeter
(Pulse output)
PWR
MAIN PCB
L
L
Figure 5.
P+
P-
S-
S+
CM
R
AK
Flowmeter Powered by Internal Power Supply
-
+
External
Power
Supply
Flowmeter
(Pulse output)
PWR
MAIN PCB
L
Figure 6.
L
P+
P-
S-
S+
CM
R
AK
Flowmeter Powered by External Supply
24
Series FIP Frequency/Pulse Meter
Instruction Manual
Flowmeter
(Magnetic Pickup)
PWR
MAIN PCB
L
L
Figure 7.
P+
P-
S-
S+
CM
R
AK
Self-Powered Magnetic Pickup Flowmeter
V+
Output
SENSOR
SENSOR
NPN
PNP
Com
MAIN PCB
L
L
P+
Figure 8.
P-
S-
S+
CM
R
Open Collector Transistor Output
25
AK
Series FIP Frequency/Pulse Meter
Instruction Manual
SWITCH CONTACT
PWR
L
L
P+
P-
S-
S+
CM
R
MAIN PCB
1
4.7k Internal
Resistor
2
1
Signal
Figure 9.
AK
3
2
JP5
+5V +12V
3
JP7
Switch Contact Closure
Acknowledgement, Reset Total Connections
Acknowledgement and reset total terminals provide a convenient
method to remotely access the following functions:
Terminal
Function
AK
Acknowledges or resets relays, exit
menu scroll, diagnostic and calibration.
R
Resets total to zero.
RESET
TOTAL
ACK
MAIN PCB
L
L
P+
P-
S-
S+
CM
R
Figure 10. External Control Connections
26
AK
Series FIP Frequency/Pulse Meter
Instruction Manual
Optional Relays and 4-20 mA Output Terminals
Depending on the model number, the Options Board may contain 2
relays and an isolated 4-20 mA output transmitter. Relay connections
are made to removable screw terminal connectors located at J2 and J3
on the Options Board. Connections for the isolated 4-20 mA output
option are made to J1 on the Options Board.
Function
Screw Terminal
Connector
Pin Number
J1
J1
J2
J2
J2
J2
J2
J2
1
2
1
2
3
4
5
6
Transmitter +
Transmitter Relay 1 Common
Relay 1 NC
Relay 1 NO
Relay 2 Common
Relay 2 NC
Relay 2 NO
6
5
4
3
2
1
J2
AK R CM S+ S- P- P+ L
- +
J1
L
Figure 11. Connectors Location - Rear View of Meter
27
Series FIP Frequency/Pulse Meter
Instruction Manual
Isolated 4-20 mA Output Option Connections
The meter can be equipped with an isolated 4-20 mA output signal
option that can be programmed to produce a 4-20 mA output for virtually
any rate display with at least a 501 count span.
The following diagrams illustrate the 4-20 mA output signal being
powered from the meter’s internal power supply and by an external
power supply.
- +
Meter,
J1
- Recorder,
+
AK R CM S+ S- P- P+ L
Controller,
etc
L
Figure 12. Output Loop Powered by Meter
+
- +
J1
-
Loop
Power
Supply
Meter,
Recorder,
Controller,
+
etc
-
AK R CM S+ S- P- P+ L
L
Figure 13. Output Loop Powered from External Supply
If the output loop is powered by an external supply, the loop
power supply must be turned on before the meter is turned
on. Otherwise, the output loop signal may be incorrect.
28
Series FIP Frequency/Pulse Meter
Instruction Manual
Programming
Overview
The meter is programmed using the ENTER button, three jumper
arrays, and switch S1. The ENTER button is used to calibrate the meter,
program various totalizer functions, and to set alarm trip and reset
points. The jumper arrays are used for programming the input signal,
lockout, relay acknowledge enable, and relay fail-safe operation. This
section of the manual deals with programming the following aspects of
the meter:
•
Basic Meter Programming
•
Rate Meter Setup
•
Totalizer Programming
•
Set Point Setup and Programming
•
Isolated 4-20 mA Output Programming (output)
•
Lockout and Display Selection Programming
General Programming Description
All programming is performed using the ENTER button. To set up a
function there are sequential steps that have to be performed. As each
step progresses, either a single digit or the entire display will flash. The
flashing digit, or flashing display, will be looking for acknowledgement if
it is the desired digit or display. Pressing the ENTER button will accept
the value. If the flashing display or digit is not the one desired, wait and
the value will change.
Each digit will flash for 3 seconds before it starts to change, when it is
accepted the next digit will flash for 3 seconds. This procedure will
continue until the ENTER button is pressed while the desired option is
flashing. As the programming progresses there will be times when a
decision has to be made, an example is yes or no ( y or n ).
ENTER and ACK Functionality
The ENTER button is used to program the meter for various functions.
The ACK button is used to acknowledge the relays during operation and
to quit main menu scroll during programming, diagnostic menu, and
calibration.
29
Series FIP Frequency/Pulse Meter
1.
2.
3.
4.
Instruction Manual
Five Basic Digit/Display Setting Instructions
If flashing display is OK, press ENTER to accept it, before display
stops flashing.
If flashing display is not OK, (or if ENTER was not pressed in time
to accept it), wait for the first digit to flash.
If a flashing digit is OK, press ENTER to accept it, before it starts to
scroll.
If a flashing digit is not OK, (or if ENTER was not pressed in time to
accept it) wait for digit to scroll, and press ENTER when OK.
5. Digits will scroll until ENTER is pressed. When a digit is accepted
by pressing ENTER, next digit flashes.
The display will scroll through the following main menu functions in the
order shown:
Display
Dspy r or
Dspy t
Type of Function
Rset t
Resets total to zero.
Dspy p
Displays and hold peak reading.
FActor, CALIb or
SCale
Calibrates meter after setting it for K-factor,
external or internal calibration.
Cutoff
Sets low-flow cutoff point.
T base
Sets time base.
Tot Cf
Sets totalizer conversion factor.
dECpt
Sets rate and total decimal point.
Setup
Sets set points for rate or total, latching or nonlatching relays.
SetPtS
Sets alarms set/reset points and batch presets.
output
Sets 4-20 mA output values, if option is
installed.
Dsplay
Includes or excludes menu titles from scroll.
Displays rate or display total.
Displays parameter settings one at a time for
diagnostic purposes.
To quit main menu scroll, diagnostic menu, calibration, or scaling press
ACK while displaying menu item or while display is flashing input n or
display n, where n is the input or display number.
dIA9
30
Series FIP Frequency/Pulse Meter
Instruction Manual
Press
ENTER
Press ENTER
when FActor
appears
999.999
appears; select
decimal point
Press ENTER
Is
YES
flashing display
OK?
Press ENTER
NO
Wait for digitNO
to flash
Wait for digit
to scroll
NO
K-factor
Scaling
Complete!
Is flashing
digit OK?
YES
Press ENTER
when OK
Press ENTER
Is
entire display
flashing?
NO
YES
Figure 14. K-Factor Scaling Flowchart
31
Series FIP Frequency/Pulse Meter
Instruction Manual
Basic Meter Programming
Overview
The meter is programmed using the ENTER button, three jumper
arrays, and switch S1. The ENTER button is used to calibrate the meter,
program various totalizer functions, and to set alarm trip and reset
points. The jumper arrays are used for programming the input signal,
lockout, relay acknowledge enable, and relay fail-safe operation.
There are three steps for programming the basic meter functions:
1. Select Input Signal
2. Select K-Factor, Calibration, or Scaling Method
3. Program K-Factor, Calibrate or Scale the Meter
To disable the relays’ fail-safe operation it is necessary to remove the
snap-off cover from the enclosure and remove the fail-safe jumper JP6
on the Display Board, see Figure 2 on page 20.
Note
To simplify programming, write down the desired programming
settings prior to attempting to program the meter. The
Programmed Parameter Settings form located on page 84
provides a convenient method to record the user settings; it
also provides the factory settings for most of the
programmable parameters.
Quit Menu Scroll, Diagnostic, and Calibration
To quit main menu scroll, diagnostic menu, calibration, or scaling
press ACK while displaying menu item or while display is flashing
input n or display n, where n is the input or display number.
Minimum Input Span (Error Message)
The calibration input signals must be within the range of the meter
and input 2 must be greater than input 1. However, the display for
input 2 does not have to be greater than the desired display for
input 1.
If input 1 signal and input 2 signal are within 3 Hz, an Error message
will appear and the display will return to the current input to be
calibrated. To terminate calibration process press ACK button.
32
Series FIP Frequency/Pulse Meter
Instruction Manual
Select Input Signal
The meter can be programmed to accept all the common pulse inputs
and contact closure signals using jumper JP5, JP7, and S1 switch
located on the Main Board, at the rear of the instrument. Jumper JP1
sets the excitation voltage to 12 VDC or 24 VDC.
P+
P-
S-
S+
CM
R
JP7
1
3
JP5
2
3
3
2
1
AK
1
4.7k Internal
Resistor
3
2
1
EXCITATION
LOCKOUT
JP5
JP1
JP2
B A
JP7
S1
INPUT
SELECTION
2
MAIN PCB
+5V +12V
Signal
Figure 15. Input Signal Selection & Lockout
Function
±125 mV to ±12 V
Pulse Input
0-5 V Pulse Input
0-24 V Pulse Input
NPN Input
PNP Input
12 VDC (P+, P-)
Excitation
24 VDC (P+, P-)
Excitation
Lockout
JP5
(1-2)
JP5
(2-3)
JP7
(1-2)
JP7
(2-3)
Switch
S1
Off
On
Off
On
B
On
Off
Off
Off
Off
On
On
On
Off
Off
Off
On
On
On
On
Off
A
A
A
A
JP1
JP2
On
Off
On
The meter can also be programmed to restrict personnel from making
changes to the meter’s programming by installing a jumper over JP2
pins on Main Board. For a complete description of the Lockout and
Display Selection Programming features, see page 62.
33
Series FIP Frequency/Pulse Meter
Instruction Manual
Select K-Factor, Calibration, or Scaling Method
The meter may be scaled using the K-factor function, calibrated using
an external signal source such as a calibrator, or scaled using the
internal source with the I-CAL (internal calibration) feature. With I-CAL,
a frequency input signal can be scaled for any display range without
applying a signal.
To select Calibration Method, apply power with ENTER button pressed.
1. When display stops flashing, release ENTER button. Display
alternates between PtS and FActor.
2. To select multi-point calibration/scaling, press ENTER when PtS is
displayed.
3. To calibrate meter with an external source, such as a calibrator,
press ENTER when E-CAL appears.
4. To scale meter with internal source, press ENTER when I-CAL
appears.
After the calibration method has been selected, the meter returns to
reading mode. To perform K-factor scaling, calibration, or scaling follow
the corresponding procedure on pages 36-39.
34
Series FIP Frequency/Pulse Meter
Instruction Manual
Set Rate and Total Decimal Point
The totalizer decimal point may be set independently of the rate decimal
point. For instance, it is possible to have a rate decimal point set at
2999.9 and a totalizer decimal point set at 999.999.
Set decimal point
dECPt
Press ENTER when the dECPt (decimal
point) function appears. The display moves
to the total and rate decimal point
functions. If ENTER is not pressed within 3
seconds the display moves on to the next
function to be programmed.
Set totalizer decimal point
Total
Press ENTER when the totAL (totalizer
decimal point) function appears.
Select the desired decimal point location by pressing
ENTER when the decimal point is in the desired
location. If no decimal point is required press ENTER
when the decimal point is not shown. The display
moves to the rate decimal point function.
Set rate decimal point
Press ENTER when the rAtE (rate decimal
point) function appears.
The decimal point will begin to scroll, and a zero will
be displayed for the sixth digit. Select decimal point
location or extra zero by pressing ENTER when
decimal point is in the required location or extra zero
is displayed. If no decimal point is required, press
ENTER when the decimal point is not shown.
35
99999.9
final
9999.99
rAtE
299.99
final
2999.9
Series FIP Frequency/Pulse Meter
Instruction Manual
Scale or Calibrate the Meter
The meter may be scaled using the K-factor function, calibrated using
an external signal source such as a calibrator, or scaled using the
internal source with the I-CAL (internal calibration) feature. With I-CAL,
a frequency input signal can be scaled for any display range without
applying a signal.
Scale Using K-Factor (FActor)
Set K-factor
FActor
Press ENTER when the FActor (K-factor)
function appears. The display moves to
setting the K-factor decimal point.
Select the desired decimal point location by pressing
ENTER when the decimal point is in the desired
location. If no decimal point is required press ENTER
when the decimal point is not shown. The display
moves to setting the K-factor value.
Set K-factor value
The entire display will flash for three seconds. For
instructions, see Five Basic Digit/Display Setting
Instructions, page 30.
99999.9
final
9999.99
001.000
final
1000.00
Scale Using Internal Calibration (I-CAL)
Note
To simplify programming, write down the desired programming
settings prior to attempting to program the meter. The
Programmed Parameter Settings form located on page 84
provides a convenient method to record the user settings; it
also provides the factory settings for most of the
programmable parameters.
Press ENTER, then press it again when
the SCale (scale) function appears.
SCale
Select the number of calibration points
If ENTER is not pressed when no. pts is displayed,
the number of points will default to whatever was
selected previously. To program the number of
calibration points, press ENTER while no. pts is
flashing. When desired number of points is
displayed, press ENTER.
No. pts
36
then
2
...
11
Series FIP Frequency/Pulse Meter
Instruction Manual
Set the first calibration point
INPT 1 (input 1) flashes indicating that the
meter is ready to be programmed for the
input corresponding to the first calibration
point. Press ENTER.
Set the input for the first calibration point
The entire display will flash for three seconds. For
instructions, see Five Basic Digit/Display Setting
Instructions, page 30.
Set display for the first calibration point
Dspy 1 (display 1) flashes indicating that
the meter is ready to be programmed for
the display corresponding to the first
calibration point. Press ENTER.
Program the display for Dspy 1 (display 1) as
described above when the input for the first
calibration point was programmed.
Inpt 1
00000.0
final input 1
00020.0
Dspy 1
00000
final display 1
00020
Calibration Error (error)
A meter display of Error during calibration indicates that the calibration
process was not successful. The meter should be recalibrated.
The Error message will appear if input 1 signal and input 2 signal are
too close together. Refer to Minimum Input Span (Error Message),
page 32.
The Error message will appear if input 1 signal is inadvertently also
applied for input 2 calibration, or ENTER is pressed before applying
input 2.
37
Series FIP Frequency/Pulse Meter
Instruction Manual
Set the second calibration point
INPT 2 (input 2) flashes indicating that the
meter is ready to be programmed for the
input corresponding to the second
calibration point. Press ENTER.
Set the input for the second calibration point
Program the display for INPT 2 (input 2) as
described above when the input for the first
calibration point was programmed.
Set display for the second calibration
point
Dspy 2 (display 2) flashes indicating that
the meter is ready to be programmed for
the display corresponding to the second
calibration point. Press ENTER.
Program the display for Dspy 2 (display 2) as
described above when the input for the first
calibration point was programmed.
Inpt 2
10000.0
then
20000.0
Dspy 2
10000
final display 2
20000
Set the display for the remaining calibration points, if selected.
Decimal point is set up under decimal point menu (dECPt).
38
Series FIP Frequency/Pulse Meter
Instruction Manual
Calibrate Using External Calibration (E-CAL)
Note
To simplify programming, write down the desired programming
settings prior to attempting to program the meter. The
Programmed Parameter Settings form located on page 84
provides a convenient method to record the user settings; it
also provides the factory settings for most of the
programmable parameters.
Press ENTER, then press it again when the
CalIb (calibrate) function appears.
CalIb
Select the number of calibration points
If ENTER is not pressed when no. pts is displayed,
the number of points will default to whatever was
selected previously. To program the number of
calibration points, press ENTER while no. pts is
flashing. When desired number of points is
displayed, press ENTER.
No. pts
Apply the signal for the first calibration
point
INPT 1 (input 1) flashes indicating that the
meter is ready to accept a signal for the first
calibration point. Apply the desired signal
and press ENTER.
Set the display for the first calibration point
The entire display will flash for three seconds.
Program display value per Five Basic Digit/Display
Setting Instructions, page 30.
Apply signal for the second calibration
point
INPT 2 (input 2) flashes indicating that the
meter is ready to accept a signal for the
second calibration point. Apply the desired
signal and press ENTER.
Set the display for the second calibration point
Program the display as described above when the
display for the first calibration point was
programmed.
then
2
…
11
Inpt 1
00000
final display 1
00020
Inpt 2
10000
final display 2
20000
Set the display for the remaining calibration points, if selected.
39
Series FIP Frequency/Pulse Meter
Instruction Manual
Gate Function (Gate)
The gate function is used for displaying slow pulse rates. In the previous version
of this meter, the minimum rate that could be displayed was 0.33 pulse/sec.
Using the programmable gate, the meter is able to display pulse rates as slow as
1 pulse every 99 seconds (0.0101 pulse/sec). The gate function can also be used
to obtain a steady display reading with a fluctuating input signal.
The gate function (Gate) has been added to t bASE menu. After time base is
selected, Gate will appear. If there is no need to change gate setting, let it time
out without pressing ENTER. There are two settings for the Gate, low gate (LO)
and high gate (HI).
Low Gate (LO)
For most applications, low gate setting should be left at 1.0 second. Increase low
gate setting to obtain a steadier rate display. The rate display will update in
accordance with the low gate setting, for example if low gate is set at 10.0, the
display will update every 10 seconds; changes in rate between updates will not
be reflected until next display update.
High Gate (HI)
Set the high gate value to correspond to the highest expected pulse width (lowest
pulse rate). For instance if the meter must display a rate when there is 1 pulse
coming into the meter every 10 seconds, set the high gate to 11.0 seconds.
When the signal is removed from the meter, the display will show the last reading
for 11 seconds; then it will read zero.
Programming the Gate (Gate)
Press ENTER, then press it again when
the t bASE (time base) function appears.
Select appropriate time base, after time
base has been selected Gate appears.
Press ENTER to set gate values.
t bASE
then
SEC
then
GatE
Low gate function and setting will be
displayed. Press ENTER to accept low
gate value. Display will show high gate
function and setting, change value as
required.
After gate values have been
programmed, the meter moves on to the
next function to be programmed.
LO
then
00001.0
then
HI
then
00003.0
40
Series FIP Frequency/Pulse Meter
Instruction Manual
41
Series FIP Frequency/Pulse Meter
Instruction Manual
Contact De-Bounce Filter (FILter)
The filter function (FILter) can be used for applications where the meter is set up
to count pulses generated by switch contacts. The filter value can be set
anywhere between 2 and 50, the higher the value, the greater the filtering.
To access this feature, power up the meter with ACK button pressed. When
display comes on release ACK button, display will alternate between HI SPd
(high speed) and LO SPd (low speed), press ENTER when LO SPd is displayed
to enable filter function. The filter function (FILter) appears at the end of the main
menu scroll with low speed filter selected. Program the filter value, so that there
are no extra counts when contact closure is completed.
Gate and Filter Settings
Contact De-Bounce Filter
Filter
Setting
2
4
10
25
50
N/A
*
**
NOTE:
Slow Pulse Rate
Speed
Setting
Max Freq Low
High
Min Pulse
Min Freq*
Gate**
Gate
Rate (p/s)
Hz
Hz
LO
950
1
3.1
1/3
0.3333
LO
450
1
10.1
1/10
0.1000
LO
200
1
30.1
1/30
0.0333
LO
75
1
60.1
1/60
0.0167
LO
40
1
90.1
1/90
0.0111
HI
30,000
1
99.1
1/99
0.0101
Minimum frequency is dependent on high gate setting.
Low gate setting can be used to stabilize display reading with
fluctuating signal.
(Input frequency) x (Low gate) must be < 65,000. Otherwise,
display goes overrange.
42
Series FIP Frequency/Pulse Meter
Instruction Manual
Rate Meter Setup
Overview
The meter can be used to display flow rate. In addition to the scaling
and calibration procedures described above, the only setup required for
this type of application is setting the meter to display rate, and
programming the low-flow cutoff if required.
Set Display to Rate (dSPy r)
The user may select either rate or total to be set as the default
displayed reading. When displaying rate, the rate LED indicator will be
illuminated.
To change the display from reading total
to rate
Press ENTER to begin scrolling through the
functions.
ENTER
When dspy r (display rate) appears,
press ENTER.
ACK
dSPY r
ENTER
ACK
ENTER
ACK
The meter now displays rate and the green
R LED on the right side is illuminated.
43
Series FIP Frequency/Pulse Meter
Instruction Manual
Low-Flow Cutoff Programming (Cutoff)
The low-flow cutoff feature allows the meter to be programmed so that
any input below the cutoff point is always displayed as zero on the rate
display.
In multi-point calibration/scaling, the total is based on the rate display;
so, inputs below the low-flow cutoff value will not affect the totalizer.
In K-factor scaling, the totalizer ignores the low-flow cutoff; the totalizer
counts every incoming pulse regardless of the rate display.
To set the low-flow cutoff point Cutoff
Press ENTER, then press it again when
Cutoff (low-flow cutoff) appears.
Cutoff
The entire display will flash for three seconds.
Program low-flow cutoff value per Five Basic
Digit/Display Setting Instructions, page 30.
NOTE: To disable low-flow cutoff, reprogram the
value to zero.
-19.999
then
01.000
then
01.500
final
01.520
44
Series FIP Frequency/Pulse Meter
Instruction Manual
Totalizer Programming
Overview
The meter can also be used to display total flow. There are five
functions to be programmed to allow the meter to act as a flow totalizer:
1. Set display to total
2. Set rate time base
3. Set totalizer conversion factor
4. Set totalizer decimal point
5. Set alternating display (if needed)
Set Display for Total (dSPy t)
The user may select either rate or total to be set as the default
displayed reading. When displaying rate, the green rate LED indicator
will be illuminated.
To change the display from reading rate
to total
The meter is now displaying rate, as
indicated by the green LED illuminated on
the right side of the display. Press ENTER
to begin scrolling through the functions.
When dspy t (display total)
appears, press ENTER.
50.25
ENTER
ACK
dSPY t
ENTER
ACK
The meter now displays total.
45657
ENTER
45
ACK
Series FIP Frequency/Pulse Meter
Instruction Manual
Set Rate Time Base (t baSE)
To act as a totalizer, the meter must be programmed with the same time
base as the flowmeter. The time base is the time units in which the rate
is displayed. For example, if the rate is in gallons per hour then the time
base must be set to kour.
To set the time base t base
T base
Press ENTER, then press it again when the
t basE (time base) function appears.
The different units of time will scroll: minute, hour,
second. Press ENTER when the required unit is
displayed.
The display moves to setting the gate function. If
ENTER is not pressed within 3 seconds, the display
moves to the next function to be programmed. Refer
to page 40.
min
or
Hour
or
seC
Set Totalizer Conversion Factor (tot CF)
The totalizer conversion factor is a number that is multiplied by the rate
to compute the total. For example, if the rate display is gallons per hour
and total is desired in barrels, (1 gallon = .02381 barrels) a total
conversion factor of .02381 should be used. If the rate display is gallons
per hour and total is desired in gallons, a factor of 1 should be used.
The factor has a selectable decimal point. Because the decimal point is
mathematically significant, values such as 1.0000, 1.0, and 1 produce
identical results. However, values such as 1.1111, 1.1, and 1 produce
different results. The decimal point should be set so as to produce the
best resolution for the application. The maximum value for the totalizer
conversion factor depends upon the decimal point selection.
Number of Decimal Places
0
1
2
3
4
5
Maximum Conversion Factor
59999
5999.9
599.99
59.999
5.9999
0.59999
46
Series FIP Frequency/Pulse Meter
Instruction Manual
Set totalizer conversion factor
Press ENTER, then press ENTER again
when the Tot Cf (totalizer conversion factor)
function appears.
Set the totalizer conversion factor decimal point
Immediately after tot Cf is selected, the display will
show six numbers. After three seconds, the decimal
point will begin to scroll. Select the desired decimal
point location by pressing ENTER when the decimal
point is in the desired location. If no decimal point is
required press ENTER when the decimal point is not
shown.
Set the total conversion factor value
Once the decimal point has been selected, the entire
display will flash for three seconds. For instructions,
see Five Basic Digit/Display Setting Instructions,
page 30.
Tot Cf
99999.9
then
999999
final
9.99999
0.01000
then
0.02000
final
0.02381
47
Series FIP Frequency/Pulse Meter
Instruction Manual
Set Totalizer Decimal Point
The totalizer decimal point may be set independently of the rate decimal
point. For instance, it is possible to have a rate decimal point set at
2999.9 and a totalizer decimal point set at 999.999. Rate decimal point
setting instructions are also explained below, ignore if the rate decimal
point has been set up already.
Set decimal point
Press ENTER when the dECPt (decimal
point) function appears. The display moves
to the total and rate decimal point
functions. If ENTER is not pressed within 3
seconds the display moves on to the next
function to be programmed.
Set totalizer decimal point
Press ENTER when the totAL (totalizer
decimal point) function appears.
dECPt
Select the desired decimal point location by pressing
ENTER when the decimal point is in the desired
location. If no decimal point is required press ENTER
when the decimal point is not shown. The display
moves to the rate decimal point function.
Set rate decimal point
Press ENTER when the rAtE (rate decimal
point) function appears.
99999.9
The decimal point will begin to scroll, and a zero will
be displayed for the sixth digit. Select decimal point
location or extra zero by pressing ENTER when
decimal point is in the required location or extra zero
is displayed. If no decimal point is required, press
ENTER when the decimal point is not shown.
48
Total
final
9999.99
rAtE
299.99
final
2999.9
Series FIP Frequency/Pulse Meter
Instruction Manual
Set Alternating Total/Rate Display
The display may be programmed to automatically toggle between rate
and total every ten seconds. The alternating display is set up by
selecting n (no) for both, dSPy r (display rate) and dSPy t (display total)
on the dSPLAy (display) menu.
Set alternating total/rate display
Press ENTER, then press it again when
dsplay (display) function appears.
Dsplay
Press ENTER when DSPY r (display rate)
appears
DSPY r
Y or n (yes or no) will flash alternately. Press ENTER
when n (no) appears.
Press ENTER when DSPY t (display total)
appears
Y or n
DSPY t
Y or n (yes or no) will flash alternately. Press ENTER
Y or n
when n appears.
NOTE: Selections made through the display menu can be made with
or without the lockout jumper installed, but only become active when
the lockout jumper is installed.
This completes the calibration and
setup of the Basic Meter and
Totalizer
Parameter Combinations Resulting in error1 Message
Certain extreme combinations of parameter selections may exceed the
totalizer range of the meter. If this occurs, the meter will momentarily
display Error 1 immediately after a programming operation. Steps to
correct this situation are:
Increase the number of decimal places in rate or totalizer conversion
factor, or
Decrease the number of decimal places in total.
49
Series FIP Frequency/Pulse Meter
Instruction Manual
Set Point Setup and Programming
Overview
The meter is available with 4 alarm points and corresponding front panel
status LEDs as a standard feature. The front panel LEDs are useful for
alarm applications that require visual notification only. For applications
that require relay contacts, such as driving external alarm devices or
batch controlling, the meter can be equipped with either two or four
relays. Any of these relays may be assigned to rate or total.
Programming the relays involves four steps:
1. Setting the relay manual reset (ACK enable) jumpers:
These jumpers (JP3) are located on the Display Board and
determine if a relay can be reset manually.
2. Setting the fail-safe jumper (JP6):
Fail-safe mode (default): In the alarm condition, the normally closed
(NC) contacts are connected to the common (C) contacts of the
relays. The fail-safe operation can be disabled, by removing jumper
JP6 located on the Display Board.
3. Setting set point functions using setup (SETUP) menu:
a. Selecting set points for rate or total.
b. Selecting latching or non-latching relay action for rate set points.
c. Selecting preset offset for total set points.
d. Selecting internal or external (I or E) total reset for batch control
applications.
e. Programming delay on release between 1 and 999 seconds if
internal total reset (I) has been selected.
f. Selecting pump alternation control feature for non-latching
relays.
4. Programming set, reset, preset, offset, and delay values using the
set points (SEtPtS) menu:
a. Set and reset points for alarms (set points) assigned to rate (thus
determining high or low alarm status and deadband).
b. Preset values for set points assigned to total.
c. Preset offset values for set points assigned to total with offset
selected.
50
Series FIP Frequency/Pulse Meter
Instruction Manual
Set Relays for Manual or Automatic Reset
Jumper array JP3 located on the Display Board is used to program the
relays so they can be reset manually. This jumper array, in combination
with SETUP functions of latching or non-latching for rate and internal or
external total reset, provide multiple relay reset modes:
Relays Assigned to Total
Type of reset
JP3 Jumper
SETuP Menu
Position
Automatic after delay elapses
N/A
Internal ( I )
Automatic when total resets to
On
External ( E )
zero + manual reset at any time
Relays Assigned to Rate
JP3 Jumper
Type of reset
Position
Automatic only after passing the
Off
reset point
Automatic + manual at any time
On
Manual only at any time
On
Manual only after passing the
Off
reset point
SETuP Menu
Non-latching
Non-latching
Latching
Latching
Set Relays for Fail-Safe Operation
In the fail-safe mode, the relay coils are energized and the Normally
Open (NO) contacts are connected to the Common (C) contacts under
normal operation. During an alarm condition the relay coils are
de-energized and the Normally Closed (NC) contacts are connected to
the Common (C) contacts. During a power failure the relay contacts
reflect an alarm condition.
Removing jumper JP6 disables the fail-safe operation. Jumper JP6 is
located on the Display Board, see Figure 2 on page 20. If fail-safe
mode is disabled, the operation of the relay contacts is opposite to
the one described in the previous paragraph.
51
Series FIP Frequency/Pulse Meter
Instruction Manual
Assigning Set Points to Rate or Total (setup)
The optional relays can be assigned to respond to the rate or the
accumulated total using the setup function. Rate relays may be set for
latching or non-latching operation. Total relays may be programmed for
manual or automatic reset after a programmable delay on release of
between 1 and 999 seconds has elapsed. Delay on release is available
when internal total reset is selected. The internal total reset function is
applied to the highest programmed preset value.
The Setup menu is used to program the following:
1. Selecting a set point for rate or total
Any set point can be set up so it responds to the rate or total display.
2. Latching or non-latching relay action for rate set points
Any rate set point can be set up so it functions as a latching or nonlatching relay. In latching mode, the relay must be reset via the front
panel ACK button or an external switch wired across terminals AK and
CM at connector on the Main Board.
3. Internal or external total reset effect on total relays
If internal total reset is selected, the total resets to zero when the
highest preset value is reached. All relays assigned to total will
automatically reset after the delay on release elapses, allowing a new
batch to begin.
If external total reset is selected, relays must be reset manually. total
relays also reset when total is reset to zero.
4. Preset offset for total set points
Relays assigned to total can be programmed to trip at any point below
the next relay’s preset value. If preset offset mode is selected the
corresponding relay will always trip at a programmed offset value before
the next relay trips. When an offset value is being programmed, the
corresponding status LED flashes.
Example: Set point 1 and 2 are set up for total, with offset selected
(under set point 2). If the preset offset is set at 10, (during Set points
programming for set point 1), then relay 1 will trip 10 counts before
relay 2.
52
Series FIP Frequency/Pulse Meter
Instruction Manual
5.
Program delay on release between 1 and 999 seconds if internal
total reset has been selected.
If internal total reset is selected, the total is automatically reset to zero
when the highest preset is reached, then a delay will occur before all
total relays reset automatically. The delay can be programmed
anywhere between 1 and 999 seconds. Once the delay has started, the
ACK button becomes inoperative for all total relays until the delay has
elapsed.
Rate or Total, Latching or Non-Latching Relays (Setup)
To simplify programming, write down the desired
programming settings prior to attempting to program the
meter. The Programmed Parameter Settings form
located on page 84 provides a convenient method to
record the user settings; it also provides the factory
settings for most of the programmable parameters.
Press ENTER, then press ENTER again
Setup
when the Setup (setup) function appears
Note
To set up set points
SEt 1 (set point 1) will be displayed. Press ENTER to
program set point 1 or wait and the display will move
to the next set point. When SEt 4 (set point 4) is
shown, the meter will exit the Setup (setup) menu and
move to the next programming menu.
SEt 1
then
SEt 2
then
SEt 3
then
SEt 4
then
I or E
If ENTER is pressed while SEt 1 (set point
1) is shown, the display will then show r or
t (rate or total) flashing alternately.
Select the desired one by pressing
ENTER when it is flashing.
53
SEt 1
then
R or t
Series FIP Frequency/Pulse Meter
Instruction Manual
Select rate
After selecting r for rate, the display will show LatCH
(latching). Press ENTER to program this function. If
ENTER is not pressed within 3 seconds, this function
will remain programmed as it was before, and the
next set point will be displayed.
R or t
then
LatCk
then
SEt 2
If ENTER is pressed while the display reads
LatCH,then Y or n (yes or no) will flash
alternately. To program this set point for
latching relay, press ENTER when Y is
flashing. To program this set point for nonlatching relay, press ENTER when n is
flashing. After making the selection, setup of
this set point is complete and the next set
point will be displayed. After set point 4 is
shown the meter will exit the Setup menu.
R or t
then
LAtCH
then
y or n
then
SEt 2
Select total
After selecting t for total, the display will show Set 2
(set point 2), press ENTER to set up set point 2 or
wait and the display will move to the next set point.
R or t
then
SET 2
Programming the second set point
The only potential difference between the way set point 2 is
programmed from the way set point 1 was programmed is if set point 1
was assigned to total. If set point 1 was assigned to total, and set point
2 is also assigned to total, then the user may select offset mode after
setting set point 2 for total. The offset value will be programmed during
set point 1 (SEtPtS) programming and it corresponds to the value at
which relay 1 trips before relay 2 trips. This feature is useful for some
batch control applications.
If ENTER is pressed while Set 2 (set point
2) is shown, the display will then show r
or t (rate or total) flashing alternately.
Select the desired one by pressing
ENTER when it is flashing.
54
SEt 2
then
r or t
Series FIP Frequency/Pulse Meter
Instruction Manual
Select rate
After selecting r for rate, the display will show LatCH
(latching). Press ENTER to program this function. If
ENTER is not pressed within 3 seconds, this function
will remain programmed as it was before, and the
next set point will be displayed.
R or t
then
LatCk
then
SEt 3
If ENTER is pressed while the display reads
LatCH,then Y or n (yes or no) will flash
alternately. To program this set point for
latching relay, press ENTER when Y is
flashing. To program this set point for nonlatching relay, press ENTER when n is
flashing. After making the selection, setup of
this set point is complete and the next set
point will be displayed. After set point 4 is
shown the meter will exit the Setup menu.
R or t
then
LatCk
then
Y or n
then
SEt 3
Select total when the first set point was assigned
to rate
After selecting t for total, the display will show Set 3
(set point 3), press ENTER to set up set point 3 or
wait and the display will move to the next set point.
Select total when the first set point was assigned
to total
After selecting t for total for second set point, the
display will show OFFSEt (preset offset) press
ENTER to set up this function. If ENTER is not
pressed within 3 seconds, this function will remain
programmed as it was before, and the next set point
will be displayed.
If ENTER is pressed while the display
reads OFFSET,then Y or N (yes or no) will
flash alternately. To program this set point
for preset offset, press ENTER when Y is
flashing. To program this set point without
preset offset, press ENTER when n is
flashing. After making the selection, setup
of set point 2 is complete and the next set
55
R or t
then
Set 3
R or t
then
OFFSET
then
SEt 3
OFFSET
then
Y or n
then
Series FIP Frequency/Pulse Meter
Instruction Manual
point will be displayed. Press ENTER to set
SEt 3
up that set point, if not, wait until desired
set point is displayed or wait for the meter
to exit the Setup menu completely.
Setup of the remaining set points
The remaining set points, set point 3 and set point 4 are set up in the
same fashion as set point 2. They can be set up as rate or total set
points.
Programming Internal Total Reset and Delay (DELAy)
Select internal total reset and delay
I or e
After the last set point is set up or displayed, I or E
appears, press ENTER. while I (internal) is flashing.
Delay (delay) will be displayed for 3 seconds, press
Delay
ENTER to program delay. For instructions, see Five
then
Basic Digit/Display Setting Instructions, page 30.
This completes the Delay (delay) programming.
000010
final delay
000600
This completes the set points setup. The display now moves to the
next programming menu (SEtPtS) to program the alarm set/reset and
preset values. To exit main programming menu and return to reading
press the ACK button.
56
Series FIP Frequency/Pulse Meter
Instruction Manual
Programming Alarm Points and Presets (SEtPtS)
Overview
The set points (SEtPtS) menu is used to program the following
functions:
1. Set and reset points for alarms assigned to rate, thus determining
high or low alarm status and deadband.
2. Preset values for set points assigned to total.
3. Preset offset values for set points assigned to total with OFFSET
selected
Set and Reset Points for Rate Alarms
The meter can be programmed so any alarm point that is assigned to
rate can be set for a high or low alarm. In addition, any rate alarm point
can be programmed for 0-100% deadband. A rate alarm is programmed
for a high alarm, by programming the set point at a higher value than
the reset point. Conversely, a rate alarm is programmed for a low alarm,
by programming the set point at a lower value than the reset point.
Example: To program an alarm for a high alarm at 500, with 100 counts
of deadband program set and reset points as follows:
Set point:
500
Reset point: 400
Preset Values for Total Set Points
When a set point is assigned to total, a preset value at which the relay
will trip must be programmed. Unlike set points assigned to rate, which
require a set and reset point, set points assigned to total require only a
preset value. When the preset value is reached, the relay transfers. The
relay can be programmed to reset automatically or manually.
Preset Offset Values for Total Set Points (OFFSET)
A preset offset value can be assigned when two adjacent set points are
assigned to total and the second one has been assigned to OFFSET
during Setup above. The first relay of a pair will trip at a programmed
preset offset value below the second relay’s preset value.
Example: If the preset offset value is set at 10 then the first relay will trip
at 10 counts before the second relay trips.
In the above example the relay pair combination could be 1 & 2, 2 & 3,
or 3 & 4.
57
Series FIP Frequency/Pulse Meter
Instruction Manual
Programming Alarm and Preset Values (SEtPtS)
Alarm, preset, and preset offset values are programmed under the
SEtPtS menu, one at a time, starting with set point 1. The set points are
programmed according to whether they were assigned to rate or total
during the setup program. For set points assigned to rate, it is necessary
to program both a set and reset points. For set points assigned to total,
either a reset value or preset offset value needs to be programmed.
The 4 discrete LEDs labeled 1-4, on the display indicate which set point
is being programmed.
For set points assigned to rate, there are two LEDs labeled S and R that
indicate whether a set or reset point is being programmed.
When programming set points assigned to total, only one of the 4
discrete LEDs on the display will be illuminated at a time. A flashing
LED indicates that a preset offset value is being programmed, a steadyon LED indicates that a preset value is being programmed.
Note
To simplify programming, write down the desired
programming settings prior to attempting to program the
meter. The Programmed Parameter Settings form
located on page 84 provides a convenient method to
record the user settings; it also provides the factory
settings for most of the programmable parameters.
Press ENTER, then press ENTER again
SEtPtS
when the SEtPtS (set points) function
appears. The display will scroll through the
set points, press ENTER when the desired
set point is displayed to program that set
point.
If ENTER is pressed while SEt 1
SEt 1
(set point 1) is shown, the display will then
then
show a flashing number. Follow
instructions below to program set points
070.00
assigned to rate and set points (presets)
assigned to total.
Set points assigned to rate
For set points assigned to rate during the Setup function, the alarm #
(1,2,3, or 4) and the S (set point) LED will be illuminated. This
indicates that the set point for alarm # (1, 2, 3, or 4) is being
programmed.
58
Series FIP Frequency/Pulse Meter
Instruction Manual
Set the display for alarm # (1,2,3, or 4) set point
The entire display will flash for three seconds.
Program set point per Five Basic Digit/Display
Setting Instructions, page 30.
070.00
then
120.00
final
125.00
Set the display for alarm # (1,2,3, or 4) reset point
As soon as the set point for alarm # (1,2,3, or 4) has been
programmed, the meter displays the reset point for alarm # (1,2,3, or
4). This is indicated by the alarm # (1, 2, 3, or 4) LED and R (reset
point) LED being illuminated. The reset point is programmed in the
same fashion as the set point above.
Press ENTER, then press ENTER again
when the SetPtS (set points) function
appears.
SEtPtS
Preset values for set points assigned to total without Offset
For set points that have been assigned to total without Offset during
the Setup function, the preset # (1,2,3, or 4) will be illuminated. This
indicates that the value for preset # (1, 2, 3, or 4) is being
programmed.
Set the display for preset # (1,2,3, or 4)
070.00
The entire display will flash for three seconds.
then
Program preset values per Five Basic Digit/Display
Setting Instructions, page 30.
120.00
final
125.00
Press ENTER, then press ENTER again
when the SetPtS (set points) function
appears.
SEtPtS
Preset values for set points assigned to total with Offset
If a set point was assigned to total with Offset during the Setup
function, it means that this set point and the one before it function as
59
Series FIP Frequency/Pulse Meter
Instruction Manual
a pair. That is, the first relay will always trip a specified number of
counts before the second relay. This is called the preset offset value
and it is programmed as the first preset in a pair of set points set up
for Offset. The second value in a pair of set points set up for Offset
represents the actual preset value.
Set the display for preset offset and preset values
070.00
The entire display will flash for three seconds.
then
Program presets per Five Basic Digit/Display
Setting Instructions, page 30.
170.00
then
120.00
final
125.00
60
Series FIP Frequency/Pulse Meter
Instruction Manual
Isolated 4-20 mA Output Programming (output)
Programming the 4-20 mA transmitter output option for the meter does
not require the use of a calibrator. The transmitter output can be
calibrated so that a 4 mA output is produced for any rate measured by
the meter. The 20 mA output may correspond to any rate that is at least
501 counts greater or smaller than the rate corresponding to 4 mA. (Ex.
4 mA = 0, 20 mA = 501) If the span between 4 and 20 mA is less than
501 counts, an error message will appear and the previously
programmed values will be retained in memory until a new set of values
is accepted.
Press ENTER, then press ENTER again
output
when the Output menu appears
Set the display for value at which 4 mA is
produced
The green LED labeled “4” will be on indicating the
meter is ready to accept the value at which 4 mA is
produced.
The entire display will flash for three seconds.
Program display value corresponding to 4 mA output
per Five Basic Digit/Display Setting Instructions,
page 30.
Set the display for value at which 20 mA is
produced
The green LED labeled “20” will now be on indicating
the meter is ready to accept the value at which 20
mA is produced. Program this value in the same
fashion as it was done above.
00000
final
00032
10000
final
01450
4-20 mA Output Programming Confirmation
The values that have been programmed to produce the 4 and 20 mA
outputs can be quickly checked to make sure they are the desired
values. To do this, access the outPut routine by pressing ENTER, and
then pressing ENTER again when outPut appears. Note display values
when “4” and “20” LEDs are on and press ENTER before the display
stops flashing.
61
Series FIP Frequency/Pulse Meter
Instruction Manual
Lockout and Display Selection Programming
Overview
The meter provides the user with the ability to restrict modification of
programming values and to exclude menu titles from appearing during
the menu scroll. Restricting modification of the programming values is
accomplished by installing the lockout jumper (JP2). Excluding menu
titles from the menu scroll is performed with the dSPLAy menu.
Lockout
The lockout jumper is used to restrict modification of calibration and
programming values. It is labeled JP2, and it is located at the rear of the
Main Board. When ENTER is pressed with the lockout jumper in place,
SCale, CalIb, Cutoff, Tbase, Tot Cf, and dECPt do not appear during the
menu scroll, and thus cannot be modified.
FILtEr
SetPtS menu title always
appears. Ability to change
values may be restricted.
outPut menu title appears
only if 4-20 mA output
option is installed.
Figure 16. Functions Locked Out with Lockout Jumper
Notes:
1.
2.
The other function the lockout jumper performs is activating
selections made through the dSPLAy menu. That is, selections
made through the dSPLAy menu only become active when the
lockout jumper is installed.
With the lockout jumper in place, the SEtPtS menu still appears. To
program it so the set points, reset points or presets can only be
viewed and not changed, it is necessary to set the SEtPtS menu in
the dSPLAy menu to n. To be able to change these values, set
SEtPtS menu in the dSPLAy menu to y.
62
Series FIP Frequency/Pulse Meter
Instruction Manual
Display Selection (dSPLAy)
The display (dSPLAy) menu is used to remove menu titles from
appearing during the menu scroll. This feature is useful for eliminating
unused menu titles from the menu scroll, making it impossible to
perform certain functions, and making the display automatically toggle
between rate and total.
For instance, the user may want to eliminate certain unused menu titles
from the scroll that do not relate to a particular application such as those
relating to flow totalization. The dSPLAy menu could be used to
eliminate the rSEt t (reset total) and the dSPy t (display total) and thus
streamline the menu.
A supervisor may want to make it impossible for an operator to perform
certain functions, but still allow himself to do them without having to
remember passwords or remove a hard-to-get-at jumper. For instance,
a supervisor could program the meter with the batch presets he wants
and disable the SEtPtS menu, thus making it impossible for a user to
change the batch presets by using the dSPLAy menu. When the
supervisor wants to change the batch presets, he can re-activate the
SEtPtS menu and make his changes. Or a supervisor may want to make
it impossible for an operator to reset the total via the front panel, but still
allow himself to do it easily. This can be accomplished by removing the
rSEt t (reset total) menu title from the menu scroll, thus making it
impossible to reset the total via the front panel and then re-activating it
when he wants to reset the total.
The user may want to make the display automatically toggle between
rate and total. This can be accomplished by setting the dspy r (display
rate) and dspy t (display total) menus to n (no), as described below.
With the lockout jumper in place, the menu titles dspy r, dspy t, rset t,
dspy p, setpts, dsplay, and, output can still be accessed. The 4-20 mA
output calibration points can be viewed, but cannot be modified.
63
Series FIP Frequency/Pulse Meter
Instruction Manual
SetPtS menu title always appears.
Ability to change values may be restricted.
Figure 17. Menu Titles Excluded with Dsplay Menu
Notes:
1. The user may program which of these routine titles are active
during operation and which ones are not. See below for
instructions.
2. Selections made through the display menu can be made with or
without the lockout jumper installed, but only become active when
the lockout jumper is installed.
3. With the lockout jumper in place, the SEtPtS menu still appears. To
program it so the set points, reset points or presets can only be
viewed and not changed, it is necessary to set the SEtPtS menu in
the dSPLAy menu to n. To be able to change these values, set
SEtPtS menu in the dSPLAy menu to y.
64
Series FIP Frequency/Pulse Meter
Instruction Manual
Include or Exclude Menu Titles from Menu Scroll
Press ENTER, then press ENTER again
Dsplay
when the Dsplay (display) function appears.
The meter will now scroll through the
various menu titles that can be included or
excluded . To program a menu title, press
ENTER when it appears.
Set menu scroll to include/exclude display rate
Dspy r
Dspy r (display rate) will appear for 3 seconds. Press
ENTER to set. Otherwise wait and meter moves on to
next menu title.
Y or N (yes or no) will flash alternately. To include
Y or n
Dspy r in menu scroll, press ENTER when y is
displayed. To exclude it, press ENTER when n is
displayed.
Set menu scroll to include/exclude
Dspy t
display total
Dspy t (display total) will appear for 3 seconds. Press
ENTER to set. Otherwise wait and meter moves on to
next menu title.
Y or N (yes or no) will flash alternately. To include
y or n
Dspy r in menu scroll, press ENTER when y is
displayed. To exclude it, press ENTER when n is
displayed.
Set menu scroll to include/exclude reset total
Rset t
Rset t (reset total) will appear for 3 seconds. Press
ENTER to set. Otherwise wait and meter moves on to
next menu title.
Y or N (yes or no) will flash alternately. To include
y or n
Dspy r in menu scroll, press ENTER when y is
displayed. to exclude it, press ENTER when n is
displayed.
Set menu to include/exclude display peak
Dspy p
dspy p (display peak) will appear for 3 seconds. Press
ENTER to set it. Otherwise wait and meter moves on
to next menu title.
Y or N (yes or no) will flash alternately. To include Dspy r in
menu scroll, press ENTER when y is displayed. To exclude
it, press ENTER when n is displayed.
65
y or n
Series FIP Frequency/Pulse Meter
Instruction Manual
Set menu scroll to include/exclude set points
SEtPtS
SEtPtS
SEtPtS (set points) will appear for 3 seconds. Press
ENTER to set. Otherwise wait and meter moves on to
next menu title.
Y or N (yes or no) will flash alternately. To include
Y or n
SEtPtS in menu scroll, press ENTER when y is
displayed. To exclude it, press ENTER when n is
displayed.
Notes:
1. Select n for both dSPy r and dSPy t to program the display to toggle
between rate and total every 10 seconds.
2. Selecting y for SEtPtS will allow an operator to view and change
set/reset points and presets even with the lockout jumper in place.
3. Selecting n for SEtPtS will still allow an operator to view set/reset
points and presets, but will not allow making changes.
4. The total can be reset with an external push-button even if rSEt t is
set to n.
Alternating Display
The display may be programmed to automatically toggle between rate
and total every ten seconds. The alternating display is set up by
selecting n (no) for both, dSPy r (display rate) and dSPy t (display total)
on the dSPLAy (display) menu.
Note: Selections made through the display menu can be made with or
without the lockout jumper installed, but only become active when the
lockout jumper is installed.
The Lockout jumper must be installed to see the alternating display or
any other display selection made.
66
Series FIP Frequency/Pulse Meter
Instruction Manual
OPERATION
Overview
This instrument is a frequency/pulse input meter with flow rate, totalizer,
and batch control capabilities housed in a 1/8 DIN high-impact plastic
enclosure with a NEMA 4X front. It accepts pulse (±125 mV to ±12 V),
square wave (0-5 V, 0-12 V, or 0-24 V), open collector (NPN or PNP),
TTL, or switch contact closure signals; and displays these signals in
engineering units on a 0.56" high 4_ digit LED display. The meter also
provides one isolated 12 VDC or 24 VDC power supply to drive either
the input or output loops. Options include up to 2 relays for alarms or
batch controlling as well as an isolated 4-20 mA transmitter output.
The front panel of the meter consists of six 0.56" high seven-segment
LEDs as well as nine programming/operational LEDs. The
programming/operational LEDs provide the following indication:
LED
During Programming:
During Operation:
1
2
3
4
S
R
4
20
R
Alarm 1
Alarm 2
Alarm 3
Alarm 4
Set point Indicator
Reset point Indicator
4 mA Output Indicator
20 mA Output Indicator
Rate Indicator
Alarm 1
Alarm 2
Alarm 3
Alarm 4
None
None
None
None
Rate
The four alarm status LEDs indicate alarm condition only and do not
represent relay status when set points are set up for non-latching relay
mode. For instance, if alarm 1 is programmed for a high alarm at 500
with manual reset of the relays and the operator resets the relays when
the display reads 650, the #1 LED will stay on until the display falls
below 500.
Set points set up for latching relay mode will reflect the status of the
LEDs, regardless of the status of the alarm condition. For instance,
when a latching relay is acknowledged the corresponding status LED
will extinguish.
67
Series FIP Frequency/Pulse Meter
Instruction Manual
Two Types of Display: Rate and Total
The meter has the capability to display both rate and total. The operator
may toggle back and forth between flow rate and total automatically or
manually. When the meter is displaying rate, an LED labeled R on the
right side of the front panel, illuminates to indicate this. There is no loss
of data while performing any of the programming or calibration
operations; the meter continues working in the background even when
values are being reprogrammed.
751.2
ENTER
ACK
Figure 18. Meter Displaying Process/Rate
ENTER
ACK
Figure 19. Meter Displaying Total
68
Series FIP Frequency/Pulse Meter
Instruction Manual
Basic Meter Operation
Overview
In its most basic form, the meter provides a digital display in engineering
units of any frequency input signal. As a standard feature, the AC
powered meters provide the power to drive either the input or the
4-20 mA output transmitter option.
ENTER and ACK Button Operation
In addition to programming the meter, the ENTER button is also used to
operate the meter.
The ACK button is used to acknowledge the relays during operation and
to quit main menu scroll during programming, diagnostic menu, and
calibration.
The ENTER button performs the following operations with lockout
jumper installed:
Definition
Function Displayed
DSPy r
Display Rate
Sets the rate as the default display
DSPy t
Display Total
Sets the total as the default display
RSEt t
Reset Total
Resets the totalizer to zero.
DSPy P
Display Peak
Rset P
Reset Peak
Dsplay
Display
Selection
Diagnostic
Displays the highest rate value
captured
Erases peak value from memory
and captures a new reading
Activates or de-activates display
functions
Displays parameter settings one at
a time for diagnostic purposes.
DIA9
69
Series FIP Frequency/Pulse Meter
Instruction Manual
Display Peak & Reset Peak Operation (DSPy P & Rset P)
The meter captures the highest rate reading and displays it through the
dspy p (display peak) function. The peak value may be reset using the
rset p (reset peak) function.
Display Peak (Hold) Reading
Press ENTER, then press ENTER
again when the DSPy P (display
peak) menu-title appears.
DSPy P
Meter displays peak reading
The meter is now displaying the peak
reading as indicated by the flashing
green R LED on the right side.
ENTER
Reset Peak Reading
Press ENTER, then press ENTER
again when the Rset P (reset peak)
menu-title appears.
Meter returns to displaying current
value
The meter is now displaying the
current value. The flashing green R
LED on the right side has stopped
flashing.
ACK
Rset P
751.2
ENTER
ACK
Note:
While in the DSPy P (display peak) mode, the meter continues
capturing new peaks; but it does not respond to signals below the
last peak value captured; it remains “locked” on the peak display
reading. For instance, if while the meter is displaying a peak of 100,
the input increases to 150, the new peak of 150 will be displayed. If
the input falls down to 125 before the peak display is reset, the
meter will continue displaying 150 as the peak reading.
70
Series FIP Frequency/Pulse Meter
Instruction Manual
Rate Meter Operation
Overview
The meter can also be used to display flow rate and is available with a
low-flow cutoff feature. Totalizer functions can be excluded from the
menu scroll through the dsplay function, if the user is not interested in
total display.
Display Rate (dSPy r)
The user may toggle between a display of rate or total at any time.
When displaying rate, the rate LED indicator will be illuminated. To
change the display to rate:
To change the display from reading
total to rate
Press ENTER to begin scrolling
through the functions.
ENTER
When dspy r (display rate)
appears, press ENTER.
ACK
dSPY r
ENTER
ACK
ENTER
ACK
The meter now displays rate and the
green R LED on the right side is
illuminated.
Low-Flow Cutoff (CutoFF)
The low-flow cutoff feature allows the meter to be programmed so that
any input below the cutoff point is always displayed as zero on the rate
display.
In multi-point calibration/scaling, the total is based on the rate display;
so, inputs below the low-flow cutoff value will not affect the totalizer.
In K-factor scaling, the totalizer ignores the low-flow cutoff; the totalizer
counts every incoming pulse regardless of the rate display.
71
Series FIP Frequency/Pulse Meter
Instruction Manual
Totalizer Operation
Overview
The total is displayed on a six-digit display that is capable of reading to
999,999. When the total exceeds 999,999, the display rolls over and
begins counting from zero again without loosing counts. The total can
be reset at any time via the front panel, via an external switch closure,
or when the meter reaches the highest preset value.
In multi-point calibration/scaling, the meter calculates the total based on
rate display and field programmable total conversion factor to display
total in engineering units. Time base must be selected according to time
units in which rate is displayed.
In K-factor scaling, the meter calculates the total based on the input
pulses, K-factor value, and total conversion factor.
Display Total (dSPy t)
The user may toggle between a display of rate or total at any time.
When displaying rate, the rate LED indicator will be illuminated.
To change the display from reading rate
to total
The meter is now displaying rate, as
indicated by the green "R" LED illuminated
on the right side of the display. Press
ENTER to begin scrolling through the
functions.
When dspy t (display total)
appears, press ENTER.
50.25
ENTER
ACK
dSPY t
ENTER
The meter now displays total.
ACK
45657
ENTER
ACK
Total Conversion Factor (tot CF) and Time Base (t bASE)
The total conversion factor is a number that is multiplied by the rate to
compute the total. Time base is available in seconds, minutes, and
hours.
72
Series FIP Frequency/Pulse Meter
Instruction Manual
Applications Using Conversion Factor and Time Base
The following tables illustrate the effect various total conversion factors
and time bases have on the operation of the meter:
Application 1
Rate
Time
Base
60
GPM
min
Total
Conv.
Factor
1 gal
Total after
one
second
1 gal
Total after
one minute
60 gal
Total
after one
hour
360 gal
Total
after one
day
8640 gal
In the above application, a total conversion factor of 1 with a rate of 60
GPM results in a total of 60 gallons after 1 minute.
Application 2
Rate
Time
Base
Total
Conv.
Factor
Total after
one
second
Total after
one
minute
60
GPM
min
0.2
0.2 can
12 cans
Total
after one
hour
720 cans
Total
after one
day
17280
cans
In the above application, 5-gallon paint cans are being filled and the
user wants to keep track of the number of cans that have been filled, not
the total gallons of paint that has been dispensed.
73
Series FIP Frequency/Pulse Meter
Instruction Manual
Totalizer Reset
The totalizer may be reset in any of three ways:
1. Via the front panel ENTER button
2. External contact closure
3. Automatically via highest preset value
Resetting Total Using the ENTER Button
Press ENTER, then press ENTER
again when the RSEt t (reset total)
function appears. After ENTER is
pressed, the total display resets to zero.
87652.0
then
RSEt t
then
0.0
Note: It is possible to exclude the reset total function from the menu
scroll. See Display Selection (dSPLAy), page 63 for details.
Resetting Total via External Contact Closure
The total may be reset at any time by closing a normally open pushbutton switch that is wired across terminals R and CM located on the
Main Board connector. See Figure 10 on page 26 for details. Note that
this switch is still functional even if reset total function has been
removed from the menu scroll.
Resetting Total Automatically via User Selectable Preset
The meter can also be programmed so the total automatically resets
when the total reaches a user selectable preset value.
74
Series FIP Frequency/Pulse Meter
Instruction Manual
Relays Operation
Overview
The relay capabilities of the meter expand its usefulness beyond simple
indication to provide users with alarm and control functions. These
capabilities include front panel alarm status LEDs as well as either 2
optional relays. There are four basic ways the relays can be used:
1. High or Low Alarms
2. Simple On/Off Control with 100% Adjustable Deadband
3. Automatic Batch Control
4. Manual Batch Control
Relays Auto Initialization
When power is applied to the meter, the front panel LEDs and alarm
relays will reflect the state of the input to the meter. For instance, when
meter is powered up, the following table indicates how the alarm LEDs
and relays will react based on the various set and reset points:
Alarm
Reset
Power-up
Relay &
HI or LO Set point
#
point
reading
LED
1
HI
1000
500
499
Off
2
LO
700
900
500
On
3
LO
250
400
500
Off
4
HI
450
200
500
On
Fail-Safe Operation
The following table indicates how the relays behave based on Jumper
JP6 being installed or not installed:
Jumper JP6 on Fail-safe
Relay coils
Power failure
Display Board
energized in
On
Enabled
Non-alarm state
Relays go to
alarm state
Off
Disabled
Alarm state
Relays go to
non-alarm state
75
Series FIP Frequency/Pulse Meter
Instruction Manual
Front Panel LEDs
The LEDs on the front panel provide status for the following:
LED
Status
LED
Status
1
Alarm 1
S
Set point Indicator
2
Alarm 2
R
Reset point Indicator
3
Alarm 3
4
4 mA indicator
4
Alarm 4
20
20 mA indicator
R
Rate indicator
The meter is supplied with four alarm points that include front panel
LEDs to indicate alarm conditions. This standard feature is particularly
useful for alarm applications that require visual-only indication. The front
panel LEDs are controlled by the set and reset points programmed by
the user. When the display passes a set point for a particular alarm, that
alarm’s LED will light up. When the meter passes back through that
alarm’s reset point the LED will go off. The front panel LEDs respond
differently for latching and non-latching relays.
For non-latching relays, the LED is always off during normal condition
and always on during alarm condition, regardless of the state of the
relay.
For latching relays, the alarm LEDs reflect the status of the relays,
regardless of the alarm condition. The following tables illustrate how the
alarm LEDs function in relation to the relays and the acknowledge
button:
Latching and Non-Latching Relay Operation
Rate relays can be set up for latching or non-latching operation.
Relay key legend for following tables
Key
Relay condition
On
Tripped
Off
Reset
Ack
Acknowledged
The On and Off keys do not refer to the status of the relay’s coil, which
depends on the fail-safe mode selected.
76
Series FIP Frequency/Pulse Meter
Instruction Manual
Non-Latching Relay
Automatic reset only JP3(1-4 off)
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack (No effect)
On
On
Normal
Off
Off
In this application, the meter is set up for automatic reset and nonlatching relay. Acknowledging the alarm while it is still present has no
effect on either the LED or the relay. When the alarm finally goes away,
the relay automatically resets and the LED also goes off.
Non-Latching Relay
Automatic + manual reset at any time JP3(1-4 on)
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Normal
Off
Off
In this application, the meter is set up for automatic and manual reset at
any time and non-latching relay. The LED and the relay automatically
reset when the meter returned to the normal condition.
Automatic + manual reset at any time JP3(1-4 on)
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack
On
Off
Normal
Off
Off
In this application, the meter is also set up for automatic and manual
reset at any time. But this time, an operator acknowledges the alarm
manually while it still exists. This causes the relay to reset, but the LED
stays on until the meter returns to the normal condition.
Remember, for non-latching relays, the LED is always off during normal
condition and always on during alarm condition, regardless of the state
of the relay.
77
Series FIP Frequency/Pulse Meter
Instruction Manual
Latching Relay
Manual reset only after signal passes reset point JP3(1-4 off)
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack (No effect)
On
On
Normal
On
On
Ack
Off
Off
In this application, the meter is set up for manual reset only after the
signal passes the reset point of the latching relay. Acknowledging the
alarm while it is still present has no effect on either the LED or the relay.
When the alarm is acknowledged after it returns to the normal state, the
LED and the relay go off. Notice that the LED remained on, even after
the meter returned to the normal condition. This is because, for latching
relays, the alarm LEDs reflect the status of the relays, regardless of the
alarm condition.
Manual reset only after signal passes reset point JP3(1-4 off)
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Normal
On
On
Ack
Off
Off
In this application, the meter is set up for manual reset only after the
signal passes the reset point of the latching relay. When the alarm is
acknowledged after it returns to the normal state, the LED and the relay
go off.
Manual reset any time JP3(1-4 on)
Condition
LED
Relay
Normal
Off
Off
Alarm
On
On
Ack
Off
Off
In this application, the meter is set up for Manual reset at any time.
Acknowledging the alarm even if the alarm condition is still present
resets the relay and turns off the LED.
78
Series FIP Frequency/Pulse Meter
Instruction Manual
Acknowledging Relays
There are two ways to acknowledge relays programmed for manual
reset: via the front panel ACK button and remotely via a switch wired
across AK and CM terminals on the Main Board. When the ACK button
or a switch wired across the AK and CM terminals is closed, all relays
programmed for manual reset will reset.
The total display is not affected by this action and therefore pressing the
ACK button or closing the acknowledge switch will not reset the total.
Delay on Release (delay)
The meter can be programmed so that when the highest preset value is
reached the total automatically resets to zero (Automatic Batch Control).
A delay on release can be programmed to reset the total relays after the
delay has elapsed. The delay can be programmed between 1 and 999
seconds.
Example: Under the setup menu, relay 1 and 2 are assigned to total,
OFFSET is not selected, internal total reset (I) is selected and a delay of
60 second is programmed. Under SEtPtS menu, the preset values are
programmed as follows:
Set 1 (preset 1): 1000
Set 2 (preset 2): 2000
When the total reaches 1000, relay 1 transfers. The total keeps
increasing until it reaches 2000; at that moment, relay 2 transfers, the
total resets to zero automatically, delay on released starts. Then 60
seconds later relays 1 and 2 reset automatically and are ready to start a
new batch.
Priority Batch Programming or Quick Presets
For some batch control applications it may be necessary to change the
presets frequently. The meter has a Quick Preset change feature that
allows all presets to be changed without entering the programming
routine.
To change presets without entering the programming routine press and
hold the ENTER button for more than 3 seconds. The meter will go
immediately to the first preset; the user can now program all presets.
After the last preset has been programmed the meter returns to reading
the rate or total.
It is recommended to disable the process while changing presets.
79
Series FIP Frequency/Pulse Meter
Instruction Manual
Switching Inductive Loads
The meter has the ability to suppress electrical noise generated by
switching inductive loads. However installing resistor-capacitor (RC)
networks improves performance and prolongs the life of the meter’s
relay contacts. This suppression can be obtained with RC networks
assembled by the user or purchased as complete assemblies. Refer to
the following circuits for RC network assembly and installation:
Switching AC and DC Loads
Figure 20. AC and DC Loads Protection
Choose R and C as follows
R: 0.5 to 1 for each volt across the contacts
C: 0.5 to 1 F for each amp through closed contacts
Notes:
1.
2.
3.
Use capacitors rated for 240 VAC.
RC networks may affect load release time of solenoid loads, check to
confirm proper operation.
Install the RC network at the meter's relay screw terminals. An RC network
may also be installed across the load. Experiment for best results.
Switching Low Voltage DC Loads
Use a diode with a reverse
breakdown voltage two to
three times the circuit
voltage and forward current
at least as large as the load
current.
Figure 21. Low Voltage DC Loads Protection
80
Series FIP Frequency/Pulse Meter
Instruction Manual
Lockout and Display Selection Operation
Overview
The meter provides the user with the ability to restrict modification of
programming values and to exclude menu titles from appearing during
the menu scroll. Restricting modification of the programming values is
accomplished by installing the lockout jumper JP2. Excluding menu
titles from the menu scroll is performed with the display menu.
Low Voltage Detector
The meter has a circuit, which monitors the line voltage. To protect
against data loss the meter will shut down, after saving the total, when
the voltage falls below specifications.
At power up the display normally flashes a test display of 188888 for a
few seconds. If the line voltage is below specifications the meter will
flash 18888L until the problem is corrected.
Diagnostic (dIA9) Feature
Overview
The diagnostic menu in the meter provides an easy way to view and
write down the parameter settings. The information gathered through
the diagnostic menu will be helpful to determine if a wrong setting is
causing the operation of the meter to be undesirable.
Operation
When the diagnostic menu is entered, the function and programmed
parameters setting will be displayed one at a time. Press ENTER to step
through the functions and settings. If ENTER is not pressed within 10
seconds, the display will move to the next function or setting. To exit the
diagnostic menu press the ACK button at any time.
Reset Meter to Factory Defaults
1.
2.
3.
4.
Remove the snap-off front cover, see page 82.
Using a pair of needle-nose pliers, short out the solder pads located
on the top and bottom of the Main Board, to the right of the ACK
button below JP6 (see Figure 2 on page 20), until the display
shows “reset”.
Press the ENTER button. The meter starts scrolling the menus.
Press the ACK button, at any time, to exit the menu scroll.
81
Series FIP Frequency/Pulse Meter
Instruction Manual
OPTIONS CARD REMOVAL & INSTALLATION
Meter options are installed at the factory. It is NOT necessary to remove
the circuit boards from the case to disable the relays’ fail-safe operation.
The fail-safe jumper is located on the Display Board, see Figure 2 on
page 20. Refer to the following instructions and illustrations to remove
the snap-off cover and the circuit boards from the case.
Disconnect power prior to performing the following
operations.
To remove the front cover from the case:
The meter's snap-off cover is held in place by 6 latches that snap into
notches on the snap-off cover. To remove the snap-off cover from the
meter, grasp it firmly on its top and bottom edges and pull it forward.
The latch plate remains around the meter's case.
To remove the circuit boards from the case:
1. Unscrew the retaining screws holding the circuit boards to the case.
2. Remove the screw terminal connectors at the rear of the meter.
3. Push the boards through the case by applying pressure to the
circuit boards at the rear of the meter. Apply pressure evenly to
both boards.
4. Do not apply pressure to the vertical Display Board.
Latch
Latch
Plate
Retaining Screws
and Washers
Snap-off
Cover
Notch
Figure 22. Front Cover Removal
82
Series FIP Frequency/Pulse Meter
5.
6.
Instruction Manual
Jumper J2 on Options Board must NOT be installed on meters that
have the fail-safe jumper JP6 on the Display Board.
To avoid electric shock, re-install the circuit boards in the case prior
to applying power.
All programming and calibrating can be performed
with the circuit boards installed in the case.
To re-install the meter in its case:
1. Fold the Options Board over the Main Board, grasp both boards so
the Main Board is on the bottom and the two Boards are separated
by about an inch.
2. Insert the two boards together into the case. Be sure both the top
and bottom boards engage the rails, which hold them in place.
3. Do not press on the Display Board when seating the assembly in
the case.
4. Install washers and retaining screws in 4 corners of meter and
install front cover.
Input Configuration
Jumpers
Screw Terminals (Rear)
Relays
Transformer
Ribbon Cable
J2
Display Board
Not Installed
Options Board
Figure 23. Options Card Installation
83
Series FIP Frequency/Pulse Meter
Instruction Manual
PROGRAMMED PARAMETER SETTINGS
The following table shows the factory setting for most of the
programmable parameters on the meter. Next to the factory setting,
record the new setting for the particular application.
Model: ______________ S/N: _______________
Date: _________
Parameter
Display
Factory
Setting
Input range
0-30,000 Hz
Type of
signal
0-12V square
wave pulse
Calibration
mode
FActor
1.000
Filter
HI Spd
High speed filter
Total dec.
point
999999
Rate decimal
point
29999
Cutoff value
CutOFF
-199.99
Time base
SEC
Second
Low gate
LO
1.0
High gate
HI
3.0
Total conv.
factor
tot CF
1.000
Set point
setup
Set 1
Total
Set 2
Total
Set 3
Rate
latCH
Non-latching
Latching
relay
84
User
Setting
Series FIP Frequency/Pulse Meter
Parameter
Instruction Manual
Display
Factory
Setting
Set 4
Rate
latCH
Non-latching
Total reset
mode
e rst
External
total reset
Set point
Set 1
1000
Set 2
4000
Set 3
7000
(Reset 3)
6000
Set 4
9000
(Reset 4)
8000
(4 mA)
00000
(20 mA)
10000
dSPy r
Yes
dSPy t
Yes
rSEt t
Yes
dspy p
Yes
setpts
No
Latching
relay
4-20 mA out
Display
selection
85
User
Setting
Series FIP Frequency/Pulse Meter
Instruction Manual
User Set point Setup and Programming Table
Parameter
Set point 1
Display
User Setting
SET 1
latCH
Set point 2
SET 2
latCH
OFFSEt
Set point 3
SET 3
latCH
OFFSEt
Set point 4
SET 4
latCH
OFFSEt
Total reset
mode
I or E
Delay on
release
delay
Set point 1
Set 1
Reset point 1
(Reset 1)
Set point 2
Set 2
Reset point 2
(Reset 2)
Set point 3
Set 3
Reset point 3
(Reset 3)
Set point 4
Set 4
Reset point 4
(Reset 4)
86
Series FIP Frequency/Pulse Meter
Instruction Manual
MOUNTING DIMENSIONS
Panel Thickness
0.125" - 0.250" (3.2 - 6.4 mm)
4.25" (108 mm)
2.30"
(59 mm)
4.30" (109 mm)
Installed
6" (152 mm) Clearance
4.83" (123 mm)
Required for Installation
0.575" (14.6 mm)
Figure 24. Mounting Dimensions
A
3.622" (92 mm)
Square Corners to 0.060"
(1.5 mm) Max Radius
1.772"
B
(45 mm)
Panel Cutout
to DIN 43700
Tolerances:
A: +0.032 (+0.8 mm)
-0.000 (-0.0 mm)
B: +0.024 (+0.6 mm)
-0.000 (-0.0 mm)
Figure 25. Panel Cutout Dimensions
Notes:
1. Panel cutout required: 1.772" x 3.622" (45 mm x 92 mm) 1/8 DIN
2. Panel thickness: 0.125" - 0.250" (3.2 mm - 6.4 mm)
3. Clearance: Allow 6" (152 mm) behind the panel
87
Series FIP Frequency/Pulse Meter
Instruction Manual
NOTES
MAINTENANCE
Upon final installation of the Series FIP Pulse Input Flow Indicator, no routine maintenance is
required. A periodic check of the system calibration is recommended. The Series FIP is not field
serviceable and should be returned if repair is needed (field repair should not be attempted and
may void warranty). Be sure to include a brief description of the problem plus any relevant
application notes. Contact customer service to receive a return goods authorization number
before shipping.
©Copyright 2006 Dwyer Instruments, Inc.
Printed in U.S.A. 11/06
DWYER INSTRUMENTS, INC. Phone: 219/879-8000
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A