Dwyer Series SSS-1000 User manual

Dwyer Series SSS-1000 User manual
SSS-1000:SSS-1000
8/13/09
11:08 AM
Page 1
Bulletin SSS-1000
Series SSS-1000 Lightweight Averaging Flow Sensor
Specifications - Installation and Operating Instructions
PUSH-ON
CONNECTIONS
FOR 3/8 OD
POLY TUBING
[9.53 OD]
3-1/2
[88.90]
FOAM GASKET
1/4 THK
[6.35 THK]
2-3/4
[69.85]
1-1/4
[57.15]
A
DIMENSIONS
Length (A)
3-5/32˝ (80.17 mm)
5-13/32˝ (137.32 mm)
7-21/32˝ (195.47 mm)
9-29/32˝ (252.62 mm)
Model
SSS-1002
SSS-1003
SSS-1004
SSS-1005
The Series SSS-1000 Lightweight Averaging Flow
Sensor from Dwyer Instruments, Inc. is ideal for sensing
differential pressure in the inlet section of variable air volume
terminal units and fan terminal units. They can also be used
to sense differential pressure at other locations in the main,
or branch duct systems.
The “H” port senses total pressure and the “L” port senses
static pressure. The difference between these signals is the
SPECIFICATIONS
Service: Air and compatible gases.
Wetted Materials: ABS/Polycarbonate (UL94-5V).
Temperature Limits: Operating: 40 to 120°F (4 to 49°C);
Storage: -40 to 140°F (-40 to 60°C).
Connection: 1/4˝ (6 mm) I.D. tubing for 3/8˝ (10 mm) O.D.
tubing.
Mounting Orientation: Integral flange with gasket.
Weight: 1 oz (28 g).
differential, or velocity pressure.
CONNECTION CURVE
Models offer up to four sensing points and lengths of 35/32˝ to 9-29/32˝ (8.02 to 25.26 cm) to accommodate box
.80
size diameters of 4˝ to 16˝ (10.16 to 40.64 cm).
.70
INSTALLATION
tubing. First check that there are no sharp bends in the tubing at any connection. Bends and creases may leak over
time as the tubing ages.
ΔP INCHES H2O
The Series SSS-1000 utilizes 1/4˝ I.D. tubing for 3/8˝ O.D.
.60
.50
.40
.30
Connect the “H” Port to the high input on the differential
.20
pressure gage, transmitter, or switch.
.10
Connect the “L” Port to the low input on the differential
0
pressure gage, transmitter, or switch.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
1000
2000
3000
VELOCITY - FEET PER MINUTE
SSS-1002
SSS-1003
SSS-1004 &
SSS-1005
Phone: 219/879-8000
Fax: 219/872-9057
www.dwyer-inst.com
e-mail: [email protected]
SSS-1000:SSS-1000
8/13/09
11:08 AM
Page 2
Bulletin SSS-1000
MOUNTING
MAINTENANCE
1. Install the unit horizontally to assure accurate velocity
Sensing orifices must be kept free of dust accumulation or
readings.
debris.
2. Determine the duct’s flow direction and install the Series
The Series SSS-1000 Lightweight Averaging Flow Sensors
SSS-1000 based on the unit’s flow arrow imprint.
are not field repairable. If you wish to return a unit contact
customer service to receive a return goods authorization
3. Cut a 7/8˝ hole in the ducting to accept the unit.
number before shipping.
4. Attach using two self-tapping screws inserted in the 3/16˝
mounting holes.
MOUNTING DETAILS
1-3/8˝
[35]
1-3/8˝
[35]
7/8˝ [22] DIA
CLEARANCE HOLE
(2) 3/16 DIA HOLE FOR
SELF TAPPING SCREWS
©Copyright 2009 Dwyer Instruments, Inc.
DWYER INSTRUMENTS, INC.
P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.
Printed in U.S.A. 7/09
Phone: 219/879-8000
Fax: 219/872-9057
FR# R1-443361-00 Rev. 3
www.dwyer-inst.com
e-mail: [email protected]