ADTRAN | TOTAL ACCESS 4303 | Job Aid | Adtran TOTAL ACCESS 4303 Job Aid

Adtran TOTAL ACCESS 4303 Job Aid
Quick Start
Technical Support (800) 726-8663
61200335L1-13B
October 2001
Copyright © 2001 ADTRAN All rights reserved
TOTAL ACCESS® 4303 DC POWER SUPPLY
CLEI: SLPOCD0C_ _
fa
FACEPLATE LEDS
INSTALLATION INFORMATION
• Insert the module into either slot PS-A or PS-B (hot insertion
permissible).
POWER LED
Description
Off
Both –48V fuses blown, power not supplied to
the shelf, or incorrect polarity on the voltage
supplied to the shelf.
• When power is supplied to the shelf, verify that the Power LED is
green.
Green
Power supplied is the correct voltage and
polarity; backplane and hot insertion voltages
correct.
• If power is supplied to the shelf and the Power LED does not
illuminate, remove power and verify polarity.
Red
–48V input present; no backplane voltage and
no hot insertion voltage.
Amber
–48V input and hot insertion voltage present;
no backplane voltage.
TEMP LED
Description
Off
Normal
SPECIFICATIONS
Red
Over-temperature condition
Input voltage
–42 to –54 VDC
Operating temperature
0oC to 50oC
Storage temperature
–40oC to 70oC
Over-temperature Indication
90oC + 10oC
Relative humidity
0% to 95% noncondensing
–48V short circuit protection
Fused (1 amp)
Backplane voltage short
circuit protection
Self-mending
Compliance
FCC Part 15, UL 60950,
NEBS Level 3
Warranty
10 years
DC SUPPLY
1200335L1
POWER
TEMP
• To verify one or both -48V supply voltages, use the SCU terminal
menus (see SCU Quick Start, 61200334L1-13A) and navigate
the following path:
System Status/System Alarms/–48V Bus.
.
FUNCTIONALITY
The Total Access 4303 DC Power Supply furnishes the voltages
necessary for proper backplane operation. The DC Power Supply
also provides the voltages that enable hot insertion of the option
cards and SCUs. The DC Power Supply does not, however, provide the voltages necessary to power individual option cards or the
SCUs as each card has its own DC-DC supply.
In addition, the DC Power Supply in slot PS-A provides alarm relay
output functionality. If only one DC Power Supply is used, place
the DC Power Supply in PS-A to provide alarm relay facilities. The
DC Power Supply, as well as all Total Access 4303 option modules and SCUs, has protection against the wrong voltage polarity
being applied to the shelf.
Quick Start
Technical Support (800) 726-8663
61200335L1-13B
October 2001
Copyright © 2001 ADTRAN All rights reserved
TOTAL ACCESS® 4303 DC POWER SUPPLY
CRI - A
VIS. ALARM
OUTPUTS
CRI - V
MAJ - V
AUD. ALARM OUTPUTS
MAJ - A
MIN - A
+
P50
_
A - IN
NO COM NC NO COM NC NO COM NC
NO COM NC NO COM NC NO COM NC
s
+
P52
_
s
EXT STA CLK
P51 _
+
ADMIN
s
+
P53
_
s
MIN - V
A - OUT
B - IN
B - OUT
TX 1
TX 3
ADTRAN 1999
© COPYRIGHT
5200330-1B
TX 2
TX 4
TA 4303
Backplane
RX 2
RX 4
NTWK MGMT
-48 VDC PRI
T
R
S
T
-48 VDC SEC
RX 1
RX 3
A MISC B
ACO
R
S
A
B
RMT
A
B
AU X 1
AU X 2
A
A
B
B
AU X 1
AU X 2
NO COM NC
NO COM NC
-48 VDC RET
10-15A Fuse
E - NET B
E - NET A
Minimum
10 AWG wire
-48 VDC RET
Minimum 12 AWG wire
Minimum 12 AWG wire
Minimum 12 AWG wire
Minimum 12 AWG wire
Chassis
Ground
10-15A Fuse
(-)
(+)
Primary 48V Supply
(-)
Chassis
Ground
(+)
Secondary 48V Supply
Note: Only one of the above supplies is necessary for proper operation.
Chassis
Ground