ESAB | U6 | Instruction manual | ESAB U6 User manual

ESAB U6 User manual
Aristo®
U6
Instruction manual
0459 287 501 US 20170331
Valid for: from program version 2.14P
TABLE OF CONTENTS
1
INTRODUCTION ............................................................................................
4
1.1
Do this first................................................................................................
4
1.2
The control panel's working method ......................................................
4
1.3
Control panel ............................................................................................
5
1.4
Symbols in the display ............................................................................
6
1.5
Update of software ...................................................................................
6
MENUS ..........................................................................................................
7
2.1
The main menu and the measurements menu ......................................
7
2.2
The selection menu ..................................................................................
7
MIG/MAG WELDING .....................................................................................
8
3.1
Settings .....................................................................................................
8
3.2
Explanation of functions..........................................................................
10
TIG WELDING................................................................................................
15
4.1
Overview ...................................................................................................
15
4.2
Settings .....................................................................................................
15
4.3
Explanation of functions..........................................................................
16
MMA WELDING .............................................................................................
21
5.1
Settings .....................................................................................................
21
ARC-AIR GOUGING ......................................................................................
23
6.1
Settings .....................................................................................................
23
GENERAL FUNCTIONS ................................................................................
24
7.1
Remote control unit..................................................................................
24
7.2
Settings .....................................................................................................
24
MEMORY MANAGEMENT ............................................................................
25
8.1
Store welding data....................................................................................
25
8.2
Recall welding data ..................................................................................
26
8.3
Delete welding data ..................................................................................
27
9
LOCK CODE ..................................................................................................
28
10
FAULT CODES ..............................................................................................
29
10.1
General ......................................................................................................
29
10.2
List of fault codes.....................................................................................
29
10.3
Fault code descriptions ...........................................................................
30
ORDERING SPARE PARTS ..........................................................................
35
DIAGRAM .............................................................................................................
36
WIRE AND GAS DIMENSIONS............................................................................
37
MENU STRUCTURE.............................................................................................
39
2
3
4
5
6
7
8
11
0459 287 501
© ESAB AB 2017
TABLE OF CONTENTS
ORDERING NUMBERS ........................................................................................
46
Rights reserved to alter specifications without notice.
0459 287 501
© ESAB AB 2017
1 INTRODUCTION
1
INTRODUCTION
This manual describes the operation of the U6 control panel.
For general information on operation, see the wire feed unit and power source operating
instructions.
1.1
Do this first
This menu appears on the display the first time you start the power unit.
When delivered, the control panel and display are set to English. There are 14 languages
stored in the control panel: to change to the one you want, do as follows.
Press
Press
to reach the first selection menu.
to reach the configuration menu.
Press
(the soft button on the right beneath the display) until the correct language is
shown in the display.
1.2
The control panel's working method
The control panel can be said to comprise two units: the primary memory and the welding
data memory.
0459 287 501
-4-
© ESAB AB 2017
1 INTRODUCTION
In the primary memory, a complete set of welding data settings are created, which can be
stored in the welding data memory.
When welding, the process is always controlled by the content of the primary memory. For
this reason, it is also possible to recall welding data settings from the welding data memory
to the primary memory.
Note, the primary memory always contains the most recently set of welding data settings.
These can be recalled from the welding data memory or individually altered settings. In other
words, the primary memory is never empty or “reset”.
1.3
Control panel
1.
2.
3.
4.
5.
Display
Knob for setting the voltage
Knob for setting the wire feed speed and
current
Soft pushbuttons (function keys), see
further explanation below
MENU button
Soft pushbuttons
The functions of these buttons (i.e. what each one does) change, depending on the
sub-menu shown in the display. The particular function for each button is shown by the text,
in the bottom line of the display, corresponding to the buttons. (A white dot beside the text
indicates that the button is active.)
When the text in this manual advises you to press a button of this type
is that you should press the function key beneath the relevant display text.
, the intention
MENU pushbutton
This pushbutton brings you to the selection menu (see item <>), if you are in the main menu.
If you are in some other menu, it moves you back up one menu.
0459 287 501
-5-
© ESAB AB 2017
1 INTRODUCTION
1.4
Symbols in the display
Back to the main menu.
Move the cursor down to a new setting parameter.
Change the function in the selected line.
Increase the value.
Decrease the value.
1.5
Update of software
If this warning is shown in the display, it means that the power source doesn’t support this
function.
Contact an authorized ESAB service engineer to obtain updated software.
0459 287 501
-6-
© ESAB AB 2017
2 MENUS
2
MENUS
The control panel uses several different menus: the main menu, the measurements menu,
the selection menu, the process menu, the settings menu, the configuration menu and the
memory menu. A startup display is also shown on startup, with information on the type of
panel and the software version in use.
2.1
The main menu and the measurements menu
The main menu always appears immediately after
startup, showing the current set values. If you are in
the main menu when you start to weld, the menu
changes automatically to show the measured values
(the measurements menu). The measured values
remain on the display even after welding stops.
Other menus can be accessed without losing the measured values.
The set values are only displayed, instead of the measured values, when a knob is turned,
or the welding method changed.
2.2
The selection menu
Use the selection menu to select the next menu level
you want to go to: process, settings, configuration, or
memory.
The process menu
The settings menu
Use this menu to
change the welding
process, material
type, etc.
Use this menu to set
welding parameters,
such as gas preflow,
hot start time, crater
fill time, etc.
The configuration
menu
The memory menu
Use this menu to
change the language,
measurements units,
etc.
Use this menu to
store, recall and/or
erase various stored
welding data settings.
There are ten storage
positions for welding
data.
0459 287 501
-7-
© ESAB AB 2017
3 MIG/MAG WELDING
3
MIG/MAG WELDING
The arc in MIG/MAG welding melts a filler wire (the electrode), which is continuously fed into
the weld, with the molten zone being protected by a shielding gas.
Pulsing the current affects the transfer of molten droplets from the wire , to produce a stable,
spatter-free arc even at low welding data.
3.1
Settings
MIG/MAG welding without pulsing
Settings
Setting range
In steps of
Default setting
2/4-stroke 1)
2-stroke or 4-stroke
-
2-stroke
Crater filling
OFF or ON
-
OFF
Crater fill time
0-5s
0.1 s
1.0 s
Hot start
OFF or ON
-
OFF
Hot start time
0.0 - 10.0 s
0.1 s
1.5 s
Creep start
OFF or ON
-
ON
Gas purging 1)
-
-
-
Cold wire feed
-
-
-
QSet
OFF or ON
-
OFF
Synergy
OFF or ON
-
ON 2)
Display of amperage
estimate
OFF or ON
-
OFF
Inductance
0 - 100
1
70
Gas pre-flow
0.1 - 25 s
0.1 s
0.1 s
Burnback time 3)
0 - 0.35 s
0.01 s
0.08 s
SCT
SYN, OFF, ON
-
SYN
Start parameter R
8.0 - 60.0
0.25
-
Gas post-flow
0.1 - 20 s
1s
1s
Spot welding
OFF or ON
-
OFF
Spot welding time
0.1 - 25 s
0.1 s
0.1 s
Voltage
8 - 60
0.25 (displayed to one synergy deviation ±0
decimal)
Wire feed speed
0.8 - 25.0 m/min
0.33 ft./min (0.1 m)
Trigger data
OFF, ON or ARC OFF -
OFF
Dimensions
METRIC or INCH
-
METRIC
Panel enable
OFF or ON
-
ON
Automatic save
OFF or ON
-
OFF
AVC feeder
OFF or ON
-
OFF
Limits
OFF or ON
-
OFF
Lock code
OFF or ON
-
OFF
5 m/min
1)
These functions cannot be changed while welding is in progress.
2)
The synergy line on delivery: solid wire (ER70S), shielding gas CO2 with wire 0.8 mm.
0459 287 501
-8-
© ESAB AB 2017
3 MIG/MAG WELDING
3)
The burnback time setting is only available when SCT is OFF. This will be the case if SCT
setting = OFF, or SCT setting = SYN and the chosen synergic line has SCT set to OFF.
MIG/MAG welding with pulsing
Settings
Setting range
In steps of
Default setting
2/4-stroke 1)
2-stroke or 4-stroke
-
2-stroke
Crater filling
OFF or ON
-
OFF
Crater fill time
0-5s
0.1 s
1.0 s
Hot start
OFF or ON
-
OFF
Hot start time
0.0 - 10.0 s
0.1 s
1.5 s
Creep start
OFF or ON
-
ON
Gas purging 1)
-
-
-
Cold wire feed
-
-
-
Display of amperage
estimate
OFF or ON
-
OFF
Gas pre-flow
0.1 - 25 s
0.1 s
0.1 s
Burnback time 2)
0 - 0.35 s
0.01 s
0.08 s
SCT 3)
SYN, OFF, ON
-
SYN
Gas post-flow
0 - 20 s
1s
1s
Spot welding
OFF or ON
-
OFF
Spot welding time
0.1 - 25 s
0.1 s
0.1 s
Voltage
8 - 60
0.25 (displayed to one synergy deviation ±0
decimal)
Wire feed speed
0.8 - 25.0 m/min
0.33 ft./min (0.1 m)
Trigger data
OFF, ON or ARC OFF -
DISABLE
Dimensions
METRIC or INCH
-
METRIC
Panel enable
OFF or ON
-
ON
Automatic save
OFF or ON
-
OFF
AVC feeder
OFF or ON
-
OFF
Limits
OFF or ON
-
OFF
Lock code
OFF or ON
-
OFF
Pinch-off / final pulse
0 - 100 %
1%
5 m/min
2)
1)
These functions cannot be changed while welding is in progress.
2)
Only possible to set if SCT is off
3)
The burnback time setting is only available when SCT is OFF. This will be the case if SCT
setting = OFF, or SCT setting = SYN and the chosen synergic line has SCT set to OFF.
0459 287 501
-9-
© ESAB AB 2017
3 MIG/MAG WELDING
3.2
Explanation of functions
2-stroke
2-stroke operation of the welding torch switch button
A = Gas pre-flow B = Hot start
C = Welding
D = Crater fill
E = Gas post-flow
In the 2-stroke control mode, pressing the welding torch trigger switch starts the gas preflow
(if used) (1) and strikes the arc. Releasing the trigger switch (2), starts crater filling (if in
operation), extinguishes the arc and starts the gas postflow (if in operation).
TIP: If the welding torch trigger switch is pressed again during the crater fill time, welding can
be continued for as long as required (shown by the dotted line) using the crater fill data.
Crater filling can also be interrupted by quickly pressing and releasing the trigger switch while
crater filling is in progress.
- Activating 2-stroke from the main menu.
4-stroke
Function when using 4-stroke control of the welding torch
A = Gas pre-flow B = Hot start
C = Welding
D = Crater fill
E = Gas post-flow
In the 4-stroke control mode, pressing the welding torch trigger switch starts the gas preflow
(1). Releasing the trigger switch (2) starts the welding process. At the end of welding, the
welder presses the trigger switch again (3), which starts crater filling (if in operation) and
reduces the welding data to a lower value. Releasing the trigger switch again (4)
extinguishes the arc and starts the gas postflow (if used).
0459 287 501
- 10 -
© ESAB AB 2017
3 MIG/MAG WELDING
TIP: Crater filling stops, when the trigger switch is released. Keeping the button pressed
continues the welding at the lower data of the crater filling function (dotted line).
- Activating 4-stroke from the main menu.
Crater filling
Crater filling helps to avoid pores, thermal cracking, and crater formation in the workpiece at
the end of the weld.
- Setting the crater filling time from the settings menu.
Hot start
The hot start function increases the welding current for an adjustable time at the start of
welding, which reduces the risk of poor fusion at the start of the weld.
- Setting of hot start time performed in the settings menu.
Creep start
The creep start function reduces the initial feed speed of the wire to 50% of the set speed,
until the wire contacts the workpiece.
- Activating creep start from the main menu.
Gas purging
The gas purging function is used when measuring the gas flow rate, or to purge the gas
hoses of any air or moisture before starting to weld. It continues for as long as the button is
kept pressed down, and prevents a voltage from being applied and the wire feed from
starting.
- Activating gas purging from the main menu.
Cold wire feed (Wire inching)
Cold wire feed is used to feed out wire without energizing the arc. The wire is fed out for as
long as the button is kept pressed in.
- Activating cold wire feed from the main menu.
QSet™
QSet™ is used to make it easier to set the welding parameters.
•
•
Turning the knob clockwise increases (+) the arc length.
Turning the knob counterclockwise reduces (-) the arc length.
SHORT ARC
Initially, when starting to weld with a wire type/gas type, QSet™ automatically sets all of the
necessary welding parameters. Once this is done, QSet™ stores all the data to produce a
good weld. The voltage then automatically conforms to changes in the wire feed speed.
SPRAY ARC
When approaching the spray arc area, the value for QSet™ must be increased. Disengage
the QSet™ function when welding with pure spray arc. All the settings are inherited from
QSet™, with the exception of the voltage, which must be set.
Recommendation: First, make a weld (6 seconds) with QSet™ on a test piece, to obtain all
the correct data.
0459 287 501
- 11 -
© ESAB AB 2017
3 MIG/MAG WELDING
NOTE!
The QSet function and the synergy function
cannot be activated at the same time.
- Activating QSet from the process menu.
Synergy
Every combination of wire type, wire diameter, and gas mixture requires a unique relationship
between the wire feed speed and voltage (arc length) to ensure a stable arc. The voltage
(arc length) is automatically controlled in accordance with the preprogrammed synergy line
that has been selected by the welder, which makes it much easier to quickly find the optimum
welding parameters. The relationship between the wire feed speed and the other parameters
is referred to as the synergy characteristic or synergy line.
Synergy ON: the main menu shows the set wire feed,
as well as positive and negative deviations from the
synergy line's voltage.
Positive deviations are displayed with a bar above SYN,
negative ones are displayed below.
Synergy OFF: the main menu shows the set value for voltage and wire feed.
- Activating synergy from the process menu.
Synergy line package
The synergy line package supplied with the machine is called “Standard synergic lines”.
It is also possible to order other synergy line packages, but these must be installed by an
authorized ESAB service engineer.
0459 287 501
- 12 -
© ESAB AB 2017
3 MIG/MAG WELDING
Display of amperage estimate
Given the chosen synergic line an amperage estimate is calculated using the current wire
feed speed. The setting is adjusted in the main menu, using soft key AMP.
The amperage estimate is displayed as a reference when the welder does not know what
wire feed speed to set. Depending on joint type and the stick out (contact tip to work piece
distance) that is used, there will be some deviation between amperage estimate and the
actual measured amperage. Large deviation might mean that stick out should be adjusted
for optimal weld results.
The amperage estimate is presented in the main menu when the wire feed speed or the
voltage is adjusted. The row showing wire feed speed in the display is replaced with
amperage estimate. During and after welding the welding current measure values are
displayed on the same row.
Inductance
Higher inductance produces a more flowing weld and less spatter. Lower inductance
produces a harsher sound and a stable, concentrated arc.
- Setting the inductance from the settings menu.
Gas pre-flow
The gas preflow time is the time during which the shielding gas flows before the arc is struck.
- Setting the gas preflow time from the settings menu.
Burnback time
The burnback time is a delay between when the wire feed unit starts to brake the wire until
the power unit shuts off the welding current. Too short of a burnback time leaves a long piece
of filler wire projecting after welding has stopped, with the resulting risk of the wire freezing
into the solidifying weld pool. On the other hand, too long of a burnback time reduces the
stickout to such an extent that there is a risk of the arc striking from the welding torch contact
tip when welding is started the next time.
- Setting the burnback time from the settings menu. The burnback time setting is only
available when SCT is OFF. This will be the case if SCT setting = 1, or SCT setting = 0 and
the chosen synergic line has SCT set to OFF.
SCT
SCT is a function that gives small repeated short circuits at the end of the welding until the
wire feeding has totally stopped and the contact with the workpiece has been broken.
The following settings exist: SYN = The value (ON/OFF) is determined by the synergy line
(default option).
0459 287 501
- 13 -
© ESAB AB 2017
3 MIG/MAG WELDING
OFF = SCT is OFF
ON = SCT is ON
Start parameter R
Start parameter R enables fine-tuning of the electric arc during the start moment when
welding. The parameter can be set from 8.0 to 60.0, in steps of 0.25. Synergy must be OFF
for this parameter to be available (which means that the chosen method is Short Arc).
Gas post-flow
The gas postflow function controls the time during which shielding gas continues to flow after
the arc has been extinguished.
- Setting the gas postflow time from the settings menu.
Changing trigger data
Using this function, it is possible to toggle between different pre-set welding data alternatives
by double-clicking on the welding blowpipe's trigger.
Toggling takes place between the memory positions 1, 2 and 3, see the “MEMORY
MANAGEMENT”. If there is no data in memory position 2, toggling takes place between
positions 1 and 3 instead.
ON - Toggling between memory positions can take place before, after, or during welding.
ARC OFF - Toggling between memory positions can only take place before or after welding.
- Activating trigger data toggling from the configuration menu.
AVC feeder
When this function is activated, it is possible to use an Arc Voltage Controlled or Off-The-Arc
feeder, where the arc voltage from the power source is used to power the feed unit.
- Activating AVC feeder from the process menu.
Spot welding
Select Spot welding when you want to “spot-weld” thin sheet metal.
- Activation and setting of Spot welding is performed in the settings menu.
Voltage
A higher voltage gives a longer arc, with a hotter and wider weld pool.
Irrespective of which menu is displayed, the set value for the voltage can always be
changed. The value is displayed in the main menu or selection menu.
Wire feed speed
The wire feed speed is the speed at which the filler wire is supplied, measured in m/min.
Irrespective of which menu is displayed, the set value for the wire feed speed can always be
changed. The value is displayed in the main menu or selection menu.
Pinch-off / final pulse
Pinch-off pulse is applied to ensure that a ball is not formed on the wire when welding stops.
Applies to MIG/MAG welding with short/spray arc and short pulsing. When pulsing,
completion is synchronized with a pulse, finishing pulse, which can be set between 0% and
100%.
0459 287 501
- 14 -
© ESAB AB 2017
4 TIG WELDING
4
TIG WELDING
4.1
Overview
TIG welding uses a non-melting tungsten electrode from which the arc is struck that melts
the workpiece. The molten weld pool and the tungsten electrode are protected by a shielding
gas.
Pulsing is used, to give better control of the weld pool and solidification. The pulse frequency
is sufficiently low to allow some of the weld pool to start to solidify between each pulse.
Pulsing has four controllable parameters: pulse duration, background current time, pulse
current, and background current.
4.2
Settings
TIG welding without pulsing
Settings
Setting range
In steps of
Default setting
2/4-stroke 1)
2-stroke or 4-stroke
-
2-stroke
HF / Liftarc
HF or Liftarc
-
HF
Live TIG-start 2)
-
-
-
Gas purging 1)
-
-
-
Gas pre-flow
0-5s
0,1 s
0,5 s
“Slope up” time
0-5s
0,1 s
0,0 s
”Slope down” time
0 - 10 s
0,1 s
2,0 s
Gas post-flow
0 - 25 s
0,1 s
5,0 s
Current 2)
4 - 500 A
1A
100 A
Trigger data
OFF, ON or ARC OFF -
DISABLE
Dimensions
METRIC or INCH
-
METRIC
Panel enable
OFF or ON
-
ON
Automatic save
OFF or ON
-
OFF
Limits
OFF or ON
-
OFF
Lock code
OFF or ON
-
OFF
Min. current
0 - 99%
1%
0%
VRD
-
-
-
1)
These functions cannot be changed while welding is in progress.
2)
Live TIG-start/Maximal current depends on the machine type is used.
TIG welding with pulsing
Settings
Setting range
In steps of
Default setting
2/4-stroke 1)
2-stroke or 4-stroke
-
2-stroke
HF or Liftarc
-
HF
0-5s
0,1 s
0,5 s
Gas pre-flow
0-5s
0,1 s
0,5 s
“Slope up” time
0-5s
0,1 s
0,0 s
”Slope down” time
0-5s
0,1 s
2,0 s
HF / Liftarc
Gas purging
0459 287 501
1)
- 15 -
© ESAB AB 2017
4 TIG WELDING
Settings
Setting range
In steps of
Default setting
Gas post-flow
0 - 25 s
0,1 s
5,0 s
Pulse duration
0.001 - 0.1 s
0.001 s
0,100 s
0.1 - 5 s
0.1 s
0.001 - 0.1 s
0.001 s
0.1 -1 s
0.1 s
4 - 500 A
1A
100 A
Background current 2) 4 - 500 A
1A
25 A
Background duration
Pulse current 2)
0,200 s
Trigger data
OFF, ON or ARC OFF -
DISABLE
Dimensions
METRIC or INCH
-
METRIC
Panel enable
OFF or ON
-
ON
Automatic save
OFF or ON
-
OFF
Limits
OFF or ON
-
OFF
Lock code
OFF or ON
-
OFF
Min. current
0 - 99%
1%
0%
1)
These functions cannot be changed while welding is in progress.
2)
The maximum current depends on the machine type used.
4.3
Explanation of functions
2-Stroke
2-stroke operation of the welding torch switch button.
A = Gas pre-flow
B = Slope up
C = Slope down
D = Gas post-flow
In the 2-stroke control mode, pressing the welding torch switch button starts the gas preflow
(if used) and strikes the arc (1). The current rises to the set value (as controlled by the “slope
up” function, if in operation). Releasing the switch button (2) reduces the current (or starts
“slope down” if in operation) and extinguishes the arc. Gas postflow follows, if it is in
operation.
- Activating 2-stroke from the main menu.
0459 287 501
- 16 -
© ESAB AB 2017
4 TIG WELDING
4-Stroke
4-stroke operation of the welding torch switch button.
A = Gas pre-flow
B = Slope up
C = Slope down
D = Gas post-flow
4-stroke operation of the welding torch switch button.
In the 4-stroke control mode, pressing the switch button starts the gas preflow (if used) (1).
At the end of the gas preflow time, the current rises to the pilot level (a few ampere), and the
arc is struck. Releasing the switch button (2) increases the current to the set value (with
“slope up”, if in use). At the end of welding, the welder presses the switch button again (3),
which reduces the current to the pilot level again (with “slope down”, if in use). Releasing the
switch button again (4) extinguishes the arc and starts the gas postflow (if used).
- Activating 4-stroke from the main menu.
HF
The HF function strikes the arc, by a spark produced when the tungsten electrode is brought
to within a given distance from the workpiece.
- Activating HF from the process menu.
LiftArc
The LiftArc function strikes the arc when the electrode is brought into contact with the
workpiece and then lifted away from it.
Striking the arc with the LiftArc™ function:
1.
2.
3.
The electrode is touched on to the workpiece.
The trigger switch is pressed, and a low current starts to flow.
The welder lifts the electrode from the workpiece: the arc strikes, and the current
rises automatically to the set value.
0459 287 501
- 17 -
© ESAB AB 2017
4 TIG WELDING
”Live TIG-start”
With “Live TIG start”, the arc strikes when the tungsten electrode is brought into contact with
the workpiece and then lifted away from it.
- Activating “Live TIG-start” from the process menu.
Gas purging
Gas purging is used when measuring the gas flow or to flush any air or moisture from the gas
hoses before welding starts. Gas purging takes place for as long as the button is held
depressed and takes place without voltage or wire feed starting.
- Gas purging from the main menu.
Gas pre-flow
This controls the time during which the shielding gas flows before the arc is struck.
- Setting the gas preflow time from the settings menu.
Slope up
The slope up function means that, when the TIG arc strikes, the current rises slowly to the
set value. This provides a gentler heating of the electrode, and gives the welder a chance to
position the electrode properly before the set welding current is reached.
- The setting of slope up time performed in the settings menu.
Slope down
The slope down function in TIG welding is used to avoid the formation of crate cracking at
the end of welding. It reduces the current slowly over an adjustable period of time.
- The setting of slope down time performed in the settings menu.
Gas post-flow
This controls the time during which the shielding gas flows after the arc is extinguished.
- Setting the gas postflow time from the settings menu.
Pulse duration
This is the length of time during which the pulse current is on during a pulse cycle.
- Setting the pulse duration time from the settings menu.
Background time
This is the length of time during which the background current flows. Together with the pulse
duration time, it gives the total pulse cycle time.
- Setting the background time from the settings menu.
Background current
This is the lower current value of the two currents used in pulsed current welding.
0459 287 501
- 18 -
© ESAB AB 2017
4 TIG WELDING
- Setting the background current from the settings menu.
Pulse current
This is the higher current value of the two currents used in pulsed current welding.
Irrespective of which menu is displayed, the set value for the pulse current can always be
changed. The value is displayed in the main menu, the selection menu or the settings menu.
TIG welding with pulsing.
A = Current
B = Time
C = Background time
D = Background
E = Pulse time
F = Pulse current
Current
Higher currents produce wider and deeper penetration into the workpiece.
Irrespective of which menu is displayed, the set value for the current can always be changed.
The value is displayed in the main menu or selection menu.
Change of trigger data
Using this function, it is possible to toggle between different pre-set welding data alternatives
by double-clicking on the welding blowpipe's trigger.
Toggling takes place between the memory positions 1, 2 and 3, see the “MEMORY
MANAGEMENT” chapter. If there is no data in memory position 2, toggling takes place
between positions 1 and 3 instead.
ON - Toggling between memory positions can take place before, after, or during welding.
ARC OFF - Toggling between memory positions can only take place before or after welding.
- Activating trigger data toggling from the configuration menu.
Min current (Remote min)
Used to set the minimum current for the remote control. If the max current is 100 A and the
min current is to be 50 A, set the min current to 50%. If the max. current is 100 A and the
min. current is 90 A, set the min. current to 90%.
- Activating min current from the settings menu.
0459 287 501
- 19 -
© ESAB AB 2017
4 TIG WELDING
VRD (Voltage Reduction Device)
The VRD function ensures that the open-circuit voltage does not exceed 35 V when welding
is not being carried out. This is indicated when the VRD icon is visible displayed, see
picture.
The VRD function is blocked when the system senses that welding has started.
If the VRD function is activated and the open-circuit voltage exceeds the 35 V limit, this is
indicated by an error message (16) appearing in the display and welding cannot be started
while the error message is displayed.
The VRD icon
NOTE!
The VRD function works for power sources where it is implemented.
0459 287 501
- 20 -
© ESAB AB 2017
5 MMA WELDING
5
MMA WELDING
MMA welding is welding with the use of coated electrodes. Striking the arc melts the
electrode and the coating, and the coating then forms a protective slag.
5.1
Settings
Settings
Setting range
In steps of
Default setting
ON or OFF
-
OFF
Hot start time
1 - 30
1
10
Arc force
0 - 10
0,5
3
Current 2)
16 - 500 A
1A
164 A
Dimensions
METRIC or INCH
-
METRIC
Panel enable
OFF or ON
-
ON
Automatic save
OFF or ON
-
OFF
Limits
OFF or ON
-
OFF
Lock code
OFF or ON
Min. current
0 - 99%
1%
0%
VRD
-
-
-
Hot start
1)These
2)The
1)
OFF
functions cannot be changed while welding is in progress.
maximum current depends on the machine type used.
The synergy line on delivery: rutile electrode 4.0 mm.
Hot start
The hot start function increases the welding current for an adjustable time at the start of
welding. This reduces the risk of defects arising from poor fusion at the start of the weld.
Setting the hot start time from the settings menu.
Arc force
The arc force function controls how the current changes when the arc length changes. A
lower value gives a calmer arc with less spatter.
Setting the arc force from the settings menu.
Current
Higher currents produce wider and deeper penetration into the workpiece.
Irrespective of which menu is displayed, the set value for the current can always be changed.
The value is displayed in the main menu or selection menu.
Min current (Remote min)
Used to set the minimum current for the remote control. If the max current is 100 A and the
min current is to be 50 A, set the min current to 50%.
If the max. current is 100 A and the min. current is 90 A, set the min. current to 90%.
- Activating min current from the settings menu.
0459 287 501
- 21 -
© ESAB AB 2017
5 MMA WELDING
VRD (Voltage Reduction Device)
The VRD function ensures that the open-circuit voltage does not exceed 35 V when welding
is not being carried out. This is indicated when the VRD icon is visible displayed, see
picture.
The VRD function is blocked when the system senses that welding has started.
If the VRD function is activated and the open-circuit voltage exceeds the 35 V limit, this is
indicated by an error message (16) appearing in the display and welding cannot be started
while the error message is displayed.
The VRD icon
NOTE!
The VRD function works for power sources where it is implemented.
0459 287 501
- 22 -
© ESAB AB 2017
6 ARC-AIR GOUGING
6
ARC-AIR GOUGING
Arc-air gouging involves the use of a special electrode consisting of a carbon bar with a
copper case. An arc is formed between the carbon bar and the workpiece, air is supplied to
blow away the melted material, and a seam is formed.
6.1
Settings
Settings
Setting range
In steps of
Default setting
Electrode diameter
4.0-8.0 mm
1.0 mm
4.0 mm
Voltage
8.0-60.0 V
0.25 V (Displayed to
one decimal.)
37.0 V
Electrode diameter
Larger electrode diameters produce wider and deeper penetration into the workpiece.
Voltage
Higher voltages produce wider and deeper penetration into the workpiece.
0459 287 501
- 23 -
© ESAB AB 2017
7 GENERAL FUNCTIONS
7
GENERAL FUNCTIONS
7.1
Remote control unit
Machines with integral control panels should have program version 1.21 or higher, in order
for the remote control to function correctly.
Control panel's behavior on connection of the remote control unit
•
•
•
The menu in the display freezes, indicating that the remote control unit is connected.
Measurement and set values are updated, but only displayed in those menus in which
the values can be shown.
If a fault code symbol is displayed, it cannot be removed until the remote control has
been disconnected.
With 10-program remote control units, it is possible to toggle between memory
positions 1, 2, 3, 4, 5, 6, 7, 8, 9 and 10. If memory position 2 is empty, the values from
position 1 are retained. For further information, see the “MEMORY MANAGEMENT”
chapter.
7.2
Settings
Panel enable
When a remote control unit is connected it is possible to set the current or voltage and wire
feed speed by using the control panel or the remote control unit.
NOTE!
This function must be activated before the remote control unit is connected.
- Activating panel enable from the configuration menu.
Auto save
If a welding data setting is recalled from the welding data memory, and the settings are
adjusted, the changed settings will be saved automatically when a new welding data set is
recalled from the memory.
- Activating auto save from the configuration menu.
Limits
This function facilitates the assurance of a good welding quality by setting the max. and min.
values for wire feed / current or voltage. The limits can be saved in the first 5 memory
positions of the welding data memory.
- Activating limits from the configuration menu.
Lock code
By using this function, the settings menu can be locked, it is then only possible to select the
main menu, the memory menu and the measurements menu, see the “LOCK CODE”
chapter.
- Activating lock code from the configuration menu.
0459 287 501
- 24 -
© ESAB AB 2017
8 MEMORY MANAGEMENT
8
MEMORY MANAGEMENT
Various welding data sets created in the primary memory can be stored in the memory menu.
Up to 10 different welding data sets can be stored.
8.1
Store welding data
Place a welding data set in the primary memory.
Press
settings.
to access the “selection menu” and then
to access the relevant
Check that the welding data settings are correct.
Press
to access the memory menu.
Press
until you come to the memory position in which you want to store the welding
data setting, e.g. position 2.
Press
a welding data setting is now stored in memory position 2. The other memory
positions are empty.
0459 287 501
- 25 -
© ESAB AB 2017
8 MEMORY MANAGEMENT
8.2
Recall welding data
NOTE!
An error message (error 44) may appear when welding data is recalled if the U6
panel has detected a mismatch between method data read from memory and
current data. This can occur if welding data is recalled when connected to a
power source that has a different software version than the power source that
was used to save the weld data.
Press
settings.
Press
to access the selection menu and then
to access the relevant
to access the memory menu.
Choose which memory position you want to recall, e.g. position 2. Press
come to position 2.
Press
until you
to recall memory position 2. The following question appears:
Press “YES”, if you want to recall welding data from memory position 2 and change the
settings that are currently in the primary memory. (If you change your mind, press “NO”).
This icon
0459 287 501
in the main menu shows which memory position is recalled.
- 26 -
© ESAB AB 2017
8 MEMORY MANAGEMENT
8.3
Press
settings.
Press
Delete welding data
to access the selection menu and then
to access the relevant
to access the memory menu.
Choose which memory position you want to delete, e.g. position 2. Press
come to position 2.
Press
until you
to delete memory position 2. The following question appears:
Press “YES”, if you want to delete welding data from memory position 2, (if you change your
mind, press “NO”). Memory position 2 is now empty.
0459 287 501
- 27 -
© ESAB AB 2017
9 LOCK CODE
9
Press
LOCK CODE
to access the lock code menu.
Press
until the first digit of the PIN code is selected.
Press
, to store the first digit of the code. Repeat the procedure for the remaining digits.
Press
to unlock the control panel.
0459 287 501
- 28 -
© ESAB AB 2017
10 FAULT CODES
10
FAULT CODES
10.1
General
Fault codes are used to indicate that a fault has occurred in the equipment. They are shown
in the display in the form of a symbol as follows:
Fault codes are updated every three seconds. The upper numeral in the
symbol is the number of the particular fault code. The lower figure indicates
where the fault is.
The above symbol shows that the control panel (0) has lost contact with the power unit.
If several faults have been detected, only the code for the latest fault to occur will be
displayed.
Press any of the function keys to clear the symbol from the display.
Symbols may be steady or flashing, depending on the type of fault.
Flashing symbols are highlighted with “o” in the list of fault codes.
10.2
List of fault codes
0 = control panel
3 = wire feed unit
1 = cooling unit
4 = remote control
2 = power source
Fault
code
Description
0
1
2
3
4
1
Memory error, EPROM
x
x
x
x
x
2
Memory error, RAM
x
x
x
x
3
Memory error, external RAM
x
x
4
5 V power supply
x
5
Intermediate DC voltage outside
limits
6
High temperature
8
Power supply 1*
9
x
x
x
x
x
x
x
x
Power supply 2*
x
x
x
10
Power supply 3*
x
11
Wire feed servo
12
Communication error (warning)
x
x
14
Communication error (bus off)
x
x
15
Messages lost
x
16
High open-circuit voltage
17
Lost contact with the wire feed unit
o
18
Lost contact with the power unit
o
19
Incorrect settings values in external
RAM
x
20
Memory allocation error
x
0459 287 501
x
x
x
x
x
x
x
x
x
- 29 -
© ESAB AB 2017
10 FAULT CODES
Fault
code
Description
0
1
2
3
22
Transmitter buffer overflow
x
x
23
Receiver buffer overflow
x
x
26
Watchdog
x
x
x
27
Out of wire
x
x
o
28
Stack overflow
x
x
x
29
No cooling water flow
o
30
Regulator time error level exceeded x
x
31
No reply from the display unit
32
No gas flow
40
Incompatible units
x
43
The connected power source does
not have the latest software
x
44
Memory management error
x
45
Corresponding dip/spray line
missing
x
x
4
x
o
Unit
Power supply 1*
Power supply 2*
Power supply 3*
Cooling unit
+24V
Control panel
+3V
Power unit
+15V
-15V
+24V
Wire feed unit
+15V
+20 V
Wire feed unit L
+15V
60V
Remote control
+12V
+10V
10.3
Fault code descriptions
Below are described the event codes for which the user can take corrective action. If any
other code is shown, contact a service technician.
Fault code
Description
1
Program memory error (EPROM)
There is a fault in the program memory.
This fault does not disable any functions.
Action: Restart the machine. If the fault persists, contact a service
technician.
2
Microprocessor RAM error
The microprocessor is unable to read/write from/to a certain memory position
in its internal memory.
This fault does not disable any functions.
Action:Restart the machine. If the fault persists, contact a service
technician.
0459 287 501
- 30 -
© ESAB AB 2017
10 FAULT CODES
Fault code
Description
3
External RAM error
The microprocessor is unable to read/write from/to a certain memory position
in its external memory.
This fault does not disable any functions.
Action: Restart the machine. If the fault persists, contact a service
technician.
4
5V power supply low
The power supply voltage is too low.
The current welding process is stopped, and cannot be restarted.
Action: Turn off the power supply to reset the unit. If the fault persists,
contact a service technician.
5
Intermediate DC voltage outside limits
The voltage is too low or too high. Too high a voltage can be due to severe
transients on the mains power supply or to a weak power supply (high
inductance of the supply or loss of a phase).
The power unit is stopped, and cannot be restarted.
Action: Turn off the power supply to reset the unit. If the fault persists,
contact a service technician.
6
High temperature
The thermal overload cutout has operated.
The current welding process is stopped, and cannot be restarted until the
cutout has reset.
Action: Check that the cooling air inlets or outlets are not obstructed or
clogged with dirt. Check the duty cycle being used to make sure that the
equipment is not overloaded.
8
+24 V power supply (cooling unit)
The voltage is too low or too high.
Action: Contact a service technician.
8
Low battery voltage +3 V (in the control panel)
The voltage of the memory backup battery is too low. If the battery is not
replaced, the contents of the welding data memory in the control panel will
be lost.
This fault does not disable any functions.
Action: Contact a service technician to replace the battery.
8
+15 V power supply (wire feed unit and power unit)
The voltage is too low or too high.
Action: Contact a service technician.
8
+13V power supply (remote control unit)
The voltage is too low or too high.
Action: Contact a service technician.
9
-15 V power supply (power unit)
The voltage is too low or too high.
Action: Contact a service technician.
0459 287 501
- 31 -
© ESAB AB 2017
10 FAULT CODES
Fault code
Description
9
+20V, +60V power supply (wire feed unit)
The voltage is too low or too high.
Action: Contact a service technician.
9
+10V power supply (remote control unit)
The voltage is too low or too high.
Action: Contact a service technician.
10
+24V power supply
The voltage is too low or too high.
Action: Contact a service technician.
11
Wire feed speed
The wire feed speed differs from the set value.
Wire feed stops if this fault occurs.
Action: Contact a service technician.
12
Communication error (warning)
The load on the system CAN bus is temporarily too high.
The power unit or wire feed unit may have lost contact with the control panel.
Action: Check the equipment to ensure that only one wire feed unit or
remote control unit is connected. If the fault persists, contact a service
technician.
14
Communication error
The system's CAN bus has temporarily ceased to work due to excessive
load.
The current welding process is stopped.
Action: Check the equipment to ensure that only one wire feed unit or
remote control unit is connected. Turn off the power supply to reset the unit.
If the fault persists, contact a service technician.
15
Messages lost
The microprocessor is unable to process incoming messages sufficiently
quickly, with the result that information has been lost.
Action: Turn off the power supply to reset the unit. If the fault persists,
contact a service technician.
16
High open-circuit voltage
The open-circuit voltage has been too high.
Action: Turn off the power supply to reset the unit. If the fault persists,
contact a service technician.
17
Lost contact
The control panel has lost contact with the wire feed unit.
The current welding process is stopped.
Action: Check the cables. If the fault persists, contact a service technician.
18
Lost contact
The control panel has lost contact with the power unit.
The current welding process is stopped.
Action: Check the cables. If the fault persists, contact a service technician.
0459 287 501
- 32 -
© ESAB AB 2017
10 FAULT CODES
Fault code
Description
19
Incorrect settings values in external RAM
This fault will be detected if the information in the battery-backed memory
has become corrupted.
Action: The fault will correct itself, but the data stored in the current memory
position will be lost.
20
Memory allocation error
The microprocessor is unable to reserve sufficient memory space.
This fault will generate fault code 26.
Action: Contact a service technician.
22
Transmitter buffer overflow
The control panel is unable to transmit information to the other units at a
sufficiently high speed.
Action: Turn off the power supply to reset the unit.
23
Receiver buffer overflow
The control panel is unable to process information from the other units at a
sufficiently high speed.
Action: Turn off the power supply to reset the unit.
26
Watchdog
Something has prevented the processor from performing its normal program
duties.
The program restarts automatically. The current welding process is stopped.
This fault does not disable any functions.
Action: If the fault recurs, contact a service technician.
27
Out of wire (wire feed unit)
The wire feed unit is not feeding any wire. The current welding process will
be stopped, and cannot be restarted.
Error code from external source.
Action: Load new wire.
Check manual for connected units.
28
Stack overflow
Program execution is not working.
Action: Turn off the power supply to reset the unit. If the fault persists,
contact a service technician.
29
No cooling water flow
The flow monitor switch has tripped.
The current welding process is stopped, and cannot be restarted.
Action: Check the cooling water circuit and the pump.
30
Regulator time error level exceeded
Too long of a regulator time has occurred (only in MIG/MAG).
31
No reply from the display unit
The microprocessor is not in contact with the display board.
Action: Contact a service technician.
0459 287 501
- 33 -
© ESAB AB 2017
10 FAULT CODES
Fault code
Description
32
No gas flow
Gas flow is less than 1.59 gal/min (6 L/min). Welding cannot be started.
Action: Check the gas valve, hoses, and connectors.
40
Incompatible units
Incorrect wire feed unit is connected. Start is prevented
Action: Connect the correct wire feed unit.
43
The connected power source does not have the latest software
U6 panel is connected to a power source that does not support regulator
type 17.
Action: Update power source software.
44
Memory management error
U6 panel has detected a mismatch between method data read from memory
and current data. Applicable to MIG/MAG welding in synergy mode.
Action: Edit settings and store new values. Old values are obsolete.
45
Corresponding dip/spray line missing
The U6 panel has detected that the dip/spray line corresponding to the
chosen synergy line for pulse welding is not available. Applicable only when
using synergy group 99 with user-defined synergy lines.
Action: Download the missing synergy line using ESAT and restart.
0459 287 501
- 34 -
© ESAB AB 2017
11 ORDERING SPARE PARTS
11
ORDERING SPARE PARTS
CAUTION!
All warranty undertakings from the supplier cease to apply if the customer
attempts any work to rectify any faults in the product during the warranty period.
Spare parts and wear parts can be ordered through your nearest ESAB dealer, see the back
cover of this document. When ordering, please state product type, serial number, designation
and spare part number in accordance with the spare parts list. This facilitates dispatch and
ensures correct delivery.
0459 287 501
- 35 -
© ESAB AB 2017
DIAGRAM
DIAGRAM
0459 287 501
- 36 -
© ESAB AB 2017
WIRE AND GAS DIMENSIONS
WIRE AND GAS DIMENSIONS
MIG/MAG synergy welding
Wire type
Shielding gas
Wire diameter
Low-alloy or non-alloy solid wire (Fe ER70S)
CO2
0.8 1.0 1.2
Ar + 8% CO2
0.8 1.0 1.2
Ar + 18% CO2
0.8 1.0 1.2
Ar + 2% CO2
0.8 1.0 1.2
Ar + 2% O2
0.8 1.0 1.2
AR + 30 % HE
+1% O2
1.0
Stainless solid wire (Ss ER316LSi)
Stainless duplex wire (Duplex ER2209)
Magnesium-alloyed aluminium wire (AlMg ER5356) Ar
1.0 1.2 1.6
Silicon-alloyed aluminium wire (AlSi ER4043)
Ar
0.9 1.0 1.2 1.6
Metal powder-filled cored wire (Fe E70 MCW)
Ar + 18% CO2
1.2 1.4 1.6
Rutile flux-filled cored wire (Fe E70 RFCW)
Ar + 18% CO2
1.2 1.4 1.6
Basic flux-filled cored wire (Fe E70 BFCW)
Ar + 18% CO2
1.2 1.4 1.6
Silicon bronze (ERCuSi-A)
Ar
1.0 1.2
Ar + 1% O2
1.0 1.2
Copper and aluminium wire (ERCuAl-A1)
Ar
1.0 1.2
Stainless solid wire (Ss ER307Si)
Ar + 2% O2
1.0 1.2
Ar + 2% CO2
0.8 1.0 1.2
Pulsed MIG/MAG synergy welding
Wire type
Shielding gas
Wire diameter
Low-alloy or non-alloy solid wire (Fe ER70S)
Ar + 8% CO2
0.8 1.0 1.2
Ar + 18% CO2
0.8 1.0 1.2
Ar + 2% CO2
0.8 1.0 1.2
Ar + 2% O2
0.8 1.0 1.2
Stainless solid wire (Ss ER308LSi)
Ar + 2% CO2
0.9 1.0 1.2
Stainless solid wire (Ss ER309LSi)
Ar + 2% CO2
1.0 1.2
Stainless solid wire (Ss ER307Si)
Ar + 2% O2
1.0 1.2
Ar + 2% CO2
1.0 1.2
Stainless solid wire (Ss 309 MoL)
Ar + 2% CO2
1.0 1.2
Stainless duplex wire (Duplex ER2209)
Ar + 30% He + 1% O2 1.0 1.2
Magnesium-alloyed aluminium wire
(AlMg ER5356)
Ar
1.0 1.2 1.6
Magnesium-alloyed al wire (AlMg ER5356)
Ar + 30% He
1.2
Magnesium-alloyed al wire (AlMg ER5183)
Ar
1.6
Stainless solid wire (Ss ER316LSi)
0459 287 501
- 37 -
© ESAB AB 2017
WIRE AND GAS DIMENSIONS
Wire type
Shielding gas
Wire diameter
Silicon-alloyed aluminium wire (AlSi ER4043)
Ar
0.9 1.0 1.2 1.6
Silicon-alloyed al wire (AlSi ER4043)
Ar + 30% He
0.9 1.0 1.2
Silicon-alloyed al wire (AlSi ER4047)
Ar
1.2 1.6
Silicon bronze (ERCuSi-A)
Ar
1.0 1.2
Ar + 1% CO2
1.0 1.2
Aluminium solid wire (Al99,5 ER1100)
Ar
1.2
Copper and aluminium wire (ERCuAl-A1)
Ar
1.0 1.2
Metal powder-filled cored wire (Fe E70 MCW)
Ar + 18% CO2
1.2 1.4 1.6
MMA welding
Electrode type
Electrode diameter
Basic
1.6 2.0 2.5 3.2 4.0 4.5 5.0 5.6 6.0 7.0
Rutile
1.6 2.0 2.5 3.2 4.0 4.5 5.0 5.6 6.0 7.0
Cellulose
2.0 2.5 3.2 4.0 4.5 5.0 5.6 6.0
Air arc gouging
Electrode type: 4.0 5.0 6.0 8.0
The text on the display panel is available in the following languages: Swedish, Danish,
Norwegian, Finnish, English, German, Dutch, French, Spanish (Castilian), Italian,
Portuguese, Polish, Czech, Hungarian, Turkish and US English.
0459 287 501
- 38 -
© ESAB AB 2017
MENU STRUCTURE
MENU STRUCTURE
0459 287 501
- 39 -
© ESAB AB 2017
MENU STRUCTURE
0459 287 501
- 40 -
© ESAB AB 2017
MENU STRUCTURE
0459 287 501
- 41 -
© ESAB AB 2017
MENU STRUCTURE
0459 287 501
- 42 -
© ESAB AB 2017
MENU STRUCTURE
0459 287 501
- 43 -
© ESAB AB 2017
MENU STRUCTURE
0459 287 501
- 44 -
© ESAB AB 2017
MENU STRUCTURE
0459 287 501
- 45 -
© ESAB AB 2017
ORDERING NUMBERS
ORDERING NUMBERS
Ordering no.
Denomination
0458 535 890
Aristo™ U6
0458 818 990
Spare parts list M2, MA4, MA6, U6
Instruction manuals and the spare parts list are available on the Internet at www.esab.com
0459 287 501
- 46 -
© ESAB AB 2017
ORDERING NUMBERS
0459 287 501
- 47 -
© ESAB AB 2017
ESAB subsidiaries and representative offices
Europe
AUSTRIA
ESAB Ges.m.b.H
Vienna-Liesing
Tel: +43 1 888 25 11
Fax: +43 1 888 25 11 85
BELGIUM
S.A. ESAB N.V.
Heist-op-den-Berg
Tel: +32 15 25 79 30
Fax: +32 15 25 79 44
BULGARIA
ESAB Kft Representative Office
Sofia
Tel: +359 2 974 42 88
Fax: +359 2 974 42 88
THE CZECH REPUBLIC
ESAB VAMBERK s.r.o.
Vamberk
Tel: +420 2 819 40 885
Fax: +420 2 819 40 120
DENMARK
Aktieselskabet ESAB
Herlev
Tel: +45 36 30 01 11
Fax: +45 36 30 40 03
FINLAND
ESAB Oy
Helsinki
Tel: +358 9 547 761
Fax: +358 9 547 77 71
GREAT BRITAIN
ESAB Group (UK) Ltd
Waltham Cross
Tel: +44 1992 76 85 15
Fax: +44 1992 71 58 03
THE NETHERLANDS
ESAB Nederland B.V.
Amersfoort
Tel: +31 33 422 35 55
Fax: +31 33 422 35 44
NORWAY
AS ESAB
Larvik
Tel: +47 33 12 10 00
Fax: +47 33 11 52 03
POLAND
ESAB Sp.zo.o.
Katowice
Tel: +48 32 351 11 00
Fax: +48 32 351 11 20
PORTUGAL
ESAB Lda
Lisbon
Tel: +351 8 310 960
Fax: +351 1 859 1277
ROMANIA
ESAB Romania Trading SRL
Bucharest
Tel: +40 316 900 600
Fax: +40 316 900 601
RUSSIA
LLC ESAB
Moscow
Tel: +7 (495) 663 20 08
Fax: +7 (495) 663 20 09
SLOVAKIA
ESAB Slovakia s.r.o.
Bratislava
Tel: +421 7 44 88 24 26
Fax: +421 7 44 88 87 41
North and South America
ARGENTINA
CONARCO
Buenos Aires
Tel: +54 11 4 753 4039
Fax: +54 11 4 753 6313
BRAZIL
ESAB S.A.
Contagem-MG
Tel: +55 31 2191 4333
Fax: +55 31 2191 4440
MEXICO
ESAB Mexico S.A.
Monterrey
Tel: +52 8 350 5959
Fax: +52 8 350 7554
SOUTH AFRICA
ESAB Africa Welding & Cutting
Ltd
Durbanvill 7570 - Cape Town
Tel: +27 (0)21 975 8924
USA
ESAB Welding & Cutting
Products
Florence, SC
Tel: +1 843 669 4411
Fax: +1 843 664 5748
Asia/Pacific
AUSTRALIA
ESAB South Pacific
Archerfield BC QLD 4108
Tel: +61 1300 372 228
Fax: +61 7 3711 2328
CHINA
Shanghai ESAB A/P
Shanghai
Tel: +86 21 2326 3000
Fax: +86 21 6566 6622
FRANCE
ESAB France S.A.
Cergy Pontoise
Tel: +33 1 30 75 55 00
Fax: +33 1 30 75 55 24
SWEDEN
ESAB Sverige AB
Gothenburg
Tel: +46 31 50 95 00
Fax: +46 31 50 92 22
GERMANY
ESAB Welding & Cutting GmbH
Langenfeld
Tel: +49 2173 3945-0
Fax: +49 2173 3945-218
ESAB International AB
Gothenburg
Tel: +46 31 50 90 00
Fax: +46 31 50 93 60
INDONESIA
P.T. ESABindo Pratama
Jakarta
Tel: +62 21 460 0188
Fax: +62 21 461 2929
SWITZERLAND
ESAB Europe GmbH
Baar
Tel: +41 1 741 25 25
Fax: +41 1 740 30 55
JAPAN
ESAB Japan
Tokyo
Tel: +81 45 670 7073
Fax: +81 45 670 7001
UKRAINE
ESAB Ukraine LLC
Kiev
Tel: +38 (044) 501 23 24
Fax: +38 (044) 575 21 88
MALAYSIA
ESAB (Malaysia) Snd Bhd
USJ
Tel: +603 8023 7835
Fax: +603 8023 0225
INDIA
ESAB India Ltd
Calcutta
Tel: +91 33 478 45 17
Fax: +91 33 468 18 80
SINGAPORE
ESAB Asia/Pacific Pte Ltd
Singapore
Tel: +65 6861 43 22
Fax: +65 6861 31 95
www.esab.com
Africa
EGYPT
ESAB Egypt
Dokki-Cairo
Tel: +20 2 390 96 69
Fax: +20 2 393 32 13
ESAB Automation Ltd
Andover
Tel: +44 1264 33 22 33
Fax: +44 1264 33 20 74
ITALY
ESAB Saldatura S.p.A.
Bareggio (Mi)
Tel: +39 02 97 96 8.1
Fax: +39 02 97 96 87 01
UNITED ARAB EMIRATES
ESAB Middle East FZE
Dubai
Tel: +971 4 887 21 11
Fax: +971 4 887 22 63
CANADA
ESAB Group Canada Inc.
Missisauga, Ontario
Tel: +1 905 670 0220
Fax: +1 905 670 4879
SPAIN
ESAB Ibérica S.A.
San Fernando de Henares
(MADRID)
Tel: +34 91 878 3600
Fax: +34 91 802 3461
HUNGARY
ESAB Kft
Budapest
Tel: +36 1 20 44 182
Fax: +36 1 20 44 186
SOUTH KOREA
ESAB SeAH Corporation
Kyungnam
Tel: +82 55 269 8170
Fax: +82 55 289 8864
Distributors
For addresses and phone
numbers to our distributors in
other countries, please visit our
home page
www.esab.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising