Application Report
SLUA758 – October 2015
UCD3138 – Responding to Multiple PMBus Slave
Addresses
High Voltage Power Solution
Jack Tan, Ian Bower
ABSTRACT
The use of digital power controllers is becoming mainstream in isolated power supplies for
achieving higher system integration, enabling advanced control methods, and
implementing real-time metrology and communication. The Power Management Bus
(PMBus) is a commonly used protocol which supports communication between power
converters, host processors and other related peripherals in a digital power-management
ecosystem. The UCD3138 family of digital controllers feature a flexible and powerful
PMBus interface integrated in the device for this purpose. While the controller is designed
to respond to a single PMBus address, some applications have a need for the controller to
support more than one PMBus address. This application note provides a firmware solution
to make a single UCD3138 device support multiple PMBus addressees. The document
covers the high-level approach and provides a suggested firmware structure, along with
the detailed firmware code changes list. This approach also works on other devices in the
UCD3138 family of products such as UCD3138A, UCD3138064, UCD3138128 and so
on.
1
2
3
4
5
Contents
Introduction .................................................................................................................................. 4
Overview of the Approach ........................................................................................................... 5
2.1 Handling Write Sequence ....................................................................................................... 5
2.2 Handling Read Sequence ....................................................................................................... 5
PMBus Low-Level Firmware Structure ....................................................................................... 6
3.1 PMBus Idle State Structure..................................................................................................... 6
3.2 PMBus Command ack State Structure.................................................................................... 7
3.3 PMBus Wait for Handler ......................................................................................................... 8
3.4 PMBus Read Handler Structure .............................................................................................. 9
3.5 PMBus Read Block Handler ................................................................................................. 10
3.6 PMBus Write Block Handler .................................................................................................. 10
3.7 PMBus Wait for EOM Handler .............................................................................................. 11
Changes to the Existing Code to Make it Respond to Multiple Slave Addresses .................. 12
4.1 Implement Other 3 State Machines in the Existing Code ...................................................... 12
4.2 Implement the Address You Would Like to Respond ............................................................ 12
4.3 Define a New Variable to Store the PMBus Address and PMBus Status Registers............... 12
4.4 Changes to Initialization PMBus ........................................................................................... 12
4.5 Changes to pmbus_handler.c. .............................................................................................. 13
Test Result .................................................................................................................................. 20
5.1 Multiple Addresses Shown in Device GUI ............................................................................. 20
1
SLUA758
6
7
2
5.2 PMBus Master can get the Different Value in Different Address as There are Multiple Devices
in Slave................................................................................................................................. 21
Summary ..................................................................................................................................... 21
Reference .................................................................................................................................... 21
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
Figure 1.
Figure 2.
Figure 3.
Figure 4.
Figure 5.
Figure 6.
Figure 7.
Figure 8.
Figure 9.
Figure 10.
Figure 11.
Figure 12.
Figures
Use Single UCD3138 to Replace 2 or More Devices ...................................................... 4
Standard PMBus Write Sequence................................................................................... 5
Standard PMBus Read Sequence ................................................................................... 5
Idle State Handler Structure ............................................................................................ 7
Command ack State Structure ........................................................................................ 7
Wait for State Handler Structure ..................................................................................... 8
Read Handler Structure ................................................................................................... 9
Read Block Handler Structure ...................................................................................... 10
Write Block Handler Structure ...................................................................................... 11
End of Message Handler Structure............................................................................... 12
Multiple Slave Addresses .............................................................................................. 20
Slaver Sends its own Address to Master ..................................................................... 21
UCD3138 – Responding to Multiple PMBus Slave Addresses
3
SLUA758
1
Introduction
The Power Management Bus (PMBus) is an open standard protocol that defines a means of
communicating with power conversion and other devices.
In some power supply applications, there are 2 or more digital controllers or MCUs. One of them
is used to control the power converter, and others are added for monitoring or housekeeping. All
the digital controllers are able to communicate with host via PMBus or I2C, and each of devices
has its own slave address.
The UCD3138 has powerful peripherals, and it can do both monitoring and controlling of the
power converter. Please see Figure 1, here is the example of using a single UCD3xxx to replace
2 or more digital controllers. In order to be compatible with original PMBus or I2C host, UCD3xxx
should be able to respond at least more than 2 slave addresses.
Digital
Controller 0#
PMBUS_CLK
PMBUS_CLK
PMBUS_DAT
PMBUS_DAT
PMBUS_CLK
PMBUS_CLK
Digital
Controller 1#
PMBUS_DAT
PMBUS_DAT
PMBUS_CLK
PMBUS_CLK
UCD3xxx
PMBUS_DAT
PMBUS_DAT
PMBUS_CLK
PMBUS_CLK
Digital Controller
(N – 1)
Figure 1.
PMBUS_DAT
PMBUS_DAT
Use Single UCD3138 to Replace 2 or More Devices
The current PMBus solution only supports response to a single address. This application note
describes how to use the UCD3138 to respond to multiple addresses and introduce the PMBus
firmware structure. This solution can be also applicable to UCD30xx and UCD3138 refresh
silicon.
4
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
2
Overview of the Approach
As previously described, a single UCD3138 should respond to multiple addresses, and the
addresses may not sequential, so the PMBus hardware could not meet this requirement. Here
we propose using manual acknowledge to each PMBus address and manual acknowledge to
command. Manual acknowledge to address means that firmware were used to ack valid PMBus
address and command instead of using hardware to do automatic ack.
2.1
Handling Write Sequence
For most standard write sequences, there is only one address, and others are data. Code is
implemented to identify the valid PMBus address when the address ready bit was set. So it is
easy to implement in firmware.
Figure 2.
2.2
Standard PMBus Write Sequence
Handling Read Sequence
There is a little bit more difficulty for reading PMBus command sequence than write sequence,
since the command is in the middle of PMBus address write and PMBus address read. In the
UCD3xxx family, the polling method is recommended since it is simple and leaves more time
available for interrupt. Suppose that using automatic ack to command, and further suppose that
the background loop is not fast enough, there is a possibility that the PMBus handler is executed
after both command and address are ready. That makes it hard to identify which is command
and which one is address. In order to handle the read sequence, manual acknowledge to
command is used. That means only the slaver got the command, then master can send out the
slave address plus read.
Figure 3.
Standard PMBus Read Sequence
UCD3138 – Responding to Multiple PMBus Slave Addresses
5
SLUA758
3
PMBus Low-Level Firmware Structure
The PMBus Low-Level firmware was targeted to handle data from or to host. It will depend on
PMBus status Register, then change state machine and how to process data. The firmware,
supported multi-address responds, does contain 7 states. Each state has different responsibility.
3.1
•
Idle state – When does the STOP condition occur, or some fault which causes PMBus
hardware reset, the firmware will be returned to this state. This is beginning of PMBus
handle data. And the valid address is acked in this state.
•
Command ack state - If the address + write is valid in idle state, then the state will change
to this one, and the valid command will be acked.
•
Wait for state - This state is from the original idle state, due to the manual ack to slave
address, this handler has a tiny difference with the original idle state code.
•
Read state - If the wait for state find there is address + read, this state will be the next
subroutine in PMBus state machine. The data will be transferred from UCD to host in this
state.
•
Read Block state – This state is similar with read state. But the condition of entering into
this state is that the host request more data than the read handler can operate, it just
continues to send data to host.
•
Write block state – If the write number of bytes is more than wait for state can handle, this
state is executed, and it continues to handle the write data from host.
•
Wait for EOM state – This sate handler is the continuous state for read sequence. The
firmware should wait for the host sends the stop condition before resetting the state to idle
state.
PMBus Idle State Structure
In this state, just check if there is a valid address ready or not.
•
•
6
If the slave address ready bit was set
–
If it is the valid address, ACK it and change the state to command ack handler.
–
If there is an invalid address ready, NACK it and stay in idle state handler.
Otherwise, do nothing, just keep staying in this sate
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
Active
Active Address
Address
Pmbus_address_ready
Pmbus_address_ready
Data
Data ready
ready == 00
Check the
Address
ACK it
Changes
Changes state_machine
state_machine
to
to cmd_ack_handler
cmd_ack_handler
Inactive
Inactive Address
Address
NACK it
START
Other
Other
Things
Things
Do Nothing
Figure 4.
3.2
Idle State Handler Structure
PMBus Command ack State Structure
In this state:
•
If nothing happened, still stay in this handler
•
If there is a data ready, ack to the command and change the state to wait handler
•
If the stop condition happened, that must be a quick command, then go back to idle state
directly
•
If none of the previous 3 conditions, goes back to idle state
Stay in this
Handler
Nothing
Nothing
Happens
Happens
Data
Data
Ready
Ready
ACK this Command, go to
PMBus Wait Handler
Changes
Changes
state_machine
state_machine to
to
wait_handler
wait_handler
START
EOM
EOM
Quick Command, go Back to
Idle Handler
Other
Other
Things
Things
Go Back to Idle
State Handler
Figure 5.
Command ack State Structure
UCD3138 – Responding to Multiple PMBus Slave Addresses
7
SLUA758
3.3
PMBus Wait for Handler
This state is from the original idle state, due to the manual ack to slave address, this handler has
a tiny difference with the original idle state code:
•
If nothing happened, just stay in this handler
•
If the PEC and stop condition bit were set, that must be write byte or word. Process it
directly and goes back to idle state.
•
If only the data ready bit is set, and the byte counter is 4, that means the buffer is full and it
needs to transfer multiple times. That must be a write block, change the state machine to
write block state.
•
If the slave address bit is set, that must be a read sequence.
•
–
If there is a valid address, ack to this address and it goes to PMBus read handler
–
Otherwise, NACK to this address and it goes back to idle state
If none of the previous things happen, reset firmware and it goes back to idle directly.
Stay in this
Handler
Nothing
Nothing
Happens
Happens
Write_byte/
word
EOM,
EOM, PEC_valid
PEC_valid
START
Other
Other
Things
Things
Data_ready,
Data_ready,
byte_count
byte_count == 44
Write_block
Slave_address_ready,
Slave_address_ready,
data_ready
data_ready == 00
Read Command
Go Back to
Idle State
Handler
Figure 6.
8
After
After Writing,
Writing, Changes
Changes
state_machine
state_machine to
to
idle_handler
idle_handler
Changes
Changes
state_machine
state_machine to
to
write_block
write_block
ACK
pmbus_active_
address
Changes
Changes
state_machine
state_machine to
to
read_handler
read_handler
Force Back
to Idle
Changes
Changes
state_machine
state_machine to
to
idle_handler
idle_handler
Wait for State Handler Structure
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
3.4
PMBus Read Handler Structure
In this state:
•
If nothing happened, just stay in this state.
•
If Data request bit was set and the number of bytes of this command is less than 5, then
transmit the data to master directly, and change the state to wait of end of message state.
•
If Data request bit was set and the number of bytes of this command is larger than 5,
transmit the first 4 bytes and change the state to read block state for continuing transfer.
•
If none of the previous things happened, then it goes back to idle state
No
No Flags
Flags
Stay in this
Handler
Data_request,
Data_request, and
and
only
1–4
Bytes
only 1–4 Bytes
Transmit to
Master
Changes
Changes
state_machine
state_machine for
for
Waiting
Waiting of
of EOM
EOM
START
Data_request,
Data_request, and
and
More
More Than
Than 44 Bytes
Bytes
Transmit 4
Bytes to Master
Other
Other
Things
Things
Changes
Changes
state_machine
state_machine to
to
read_block
read_block
Go Back to Idle
State Handler
Figure 7.
Read Handler Structure
UCD3138 – Responding to Multiple PMBus Slave Addresses
9
SLUA758
3.5
PMBus Read Block Handler
The read block handler is very similar to the read handler, it continues to transfer the data to
master.
Data_request and
Only 1–4 Bytes Data
Transmit Data
to Host
Change State Machine
to Waiting for EOM
START
Data_request and
More Than 4 Bytes Data
Transmit Data
to Host
Waiting
Waiting for
for Send
Send Next
Next Data
Data
No
No Flag
Flag
Others
Others
Return
Force Back to
Idle With NACK
Change
Change State
State Machine
Machine to
to Idle
Idle
Figure 8.
3.6
Read Block Handler Structure
PMBus Write Block Handler
If there are more than 4 bytes for write sequence, the state will enter into this handler:
•
No flag was set, just stay in this handler.
•
If EOM, Data ready and PEC valid bit are set, that means write block is finished, process
this command and it goes back to idle.
•
If EOM was set, process this command and go back to idle.
•
If data ready was set, RD_BYTE_COUND is 4, and NO EOM, that means the receive data
from master is still required.
•
10
–
If the total number of bytes is less than the max buffer size, stay in this state and
continuing to receive data
–
Otherwise, stop to receive the data and force the sate machine back to idle
If none of the previous things occurred, then force the state machine back to idle state.
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
Change State
Machine to Idle
Change
Change State
State
Machine
Machine to
to Idle
Idle
Write Block
Finished
Process
CMD
Process This CMD
PMBus Data Buffer Overflow
EOM
Force Back
to Idle, NACK
EOM, Data_ready
PEC_Valid
pmbus_number_of_bytes ≥ PMBUS_BUFFER_SIZE
START
Data_ready
RD_Byte_Count = 4
Block Data
not
Finished
pmbus_number_of_bytes < PMBUS_BUFFER_SIZE
Waiting for
Other Data
No
No Flag
Flag
Others
Others
Return
Force Back to
Idle With NACK
Figure 9.
3.7
Change
Change State
State
Machine
Machine to
to Idle
Idle
Write Block Handler Structure
PMBus Wait for EOM Handler
This state handler is the continuous state for read sequence:
•
If the stop condition bit is set, then goes back to idle state
•
If nothing happened, stay in this state
•
If other things, such as clock low time out, goes back to idle state
UCD3138 – Responding to Multiple PMBus Slave Addresses
11
SLUA758
Return;
No
No Flag
Flag
Goes Back to
Idle State
EOM
EOM
START
Others
Others
Goes Back to
Idle State
Figure 10. End of Message Handler Structure
4
Changes to the Existing Code to Make it Respond to Multiple Slave
Addresses
4.1
Implement Other 3 State Machines in the Existing Code
•
•
•
4.2
4
5
6
Implement the Address You Would Like to Respond
•
•
•
•
4.3
#define PMBUS_STATE_WAIT
#define PMBUS_STATE_CMD_ACK
#define PMBUS_STATE_READ
#define PMBUS_ADDRESS1
#define PMBUS_ADDRESS2
#define PMBUS_ADDRESS3
#define PMBUS_ADDRESS4
0x01
0x22
0x59
0x7b
Define a New Variable to Store the PMBus Address and PMBus Status Registers
EXTERN Uint32 pmbus_active_address;
EXTERN union PMBST_REG pmbst_shadow;
4.4
Changes to Initialization PMBus
UCD should be able to manually acknowledge to multiple addresses, the initialization code
should be changed from auto acknowledge address to manual acknowledge address. And
considering the PMBus read sequence, UCD should be also configured as manual acknowledge
to command.
PMBusRegs.PMBCTRL2.all = PMBCTRL2_HALF0_PEC_ENA + pmbus_address
+ PMBCTRL2_HALF0_SLAVE_ADDRESS_MASK_DISABLE
+ PMBCTRL2_ALL_RX_BYTE_ACK_CNT
+ PMBCTRL2_ALL_MAN_SLAVE_ACK
12
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
+ PMBCTRL2_ALL_MAN_CMD; // for Manual slave address ack
4.5
Changes to pmbus_handler.c.
As previously described, the manual acknowledge address and command will be used in this
part. So the related PMBus handler part also should be modified.
a. Implement 3 subroutines at PMBus low-level routine.
else if (pmbus_state == PMBUS_STATE_CMD_ACK)
{
pmbus_cmd_ack_handler();
return ;
}
else if (pmbus_state == PMBUS_STATE_WAIT)
{
pmbus_wait_handler();
return ;
}
else if (pmbus_state == PMBUS_STATE_READ)
{
pmbus_read_handler();
return ;
}
else
{
pmbus_state = PMBUS_STATE_IDLE;
pmbus_idle_handler();
return ;
}
b. For pmbus_idle_handler, the main job is to check the valid PMBus address if there is an
address ready.
void pmbus_idle_handler(void)
{
pmbst_shadow.all=PMBusRegs.PMBST.all;
if( (pmbst_shadow.bit.SLAVE_ADDR_READY == 1) && (pmbst_shadow.bit.DATA_READY == 0) )
{
pmbus_active_address = (PMBusRegs.PMBRXBUF.byte.BYTE0 & 0x7F);
if((pmbus_active_address == PMBUS_ADDRESS1)
|| (pmbus_active_address == PMBUS_ADDRESS2)
||(pmbus_active_address == PMBUS_ADDRESS3)
||(pmbus_active_address == PMBUS_ADDRESS4))
{
UCD3138 – Responding to Multiple PMBus Slave Addresses
13
SLUA758
PMBusRegs.PMBACK.bit.ACK=1;
pmbus_state= PMBUS_STATE_CMD_ACK;
}
else
{
}
14
}
return;
PMBusRegs.PMBACK.bit.ACK=0;
pmbus_state = PMBUS_STATE_IDLE;
}
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
c. Add void pmbus_cmd_ack_handler(void) function to acknowledge command manually.
void pmbus_cmd_ack_handler(void)
{
pmbst_shadow.all=PMBusRegs.PMBST.all;
if( (pmbst_shadow.all & (PMBST_HALF0_CHECK_BITS +
PMBST_BYTE0_RD_BYTE_COUNT)) == 0) //if there is nothing happen
{
return;
}
if(pmbst_shadow.bit.DATA_READY==1)
{
pmbus_buffer[0] = PMBusRegs.PMBRXBUF.byte.BYTE0;// copy command
}
PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack them
pmbus_state = PMBUS_STATE_WAIT ;
else if (pmbst_shadow.all & (PMBST_HALF0_CHECK_BITS+
PMBST_BYTE0_RD_BYTE_COUNT) == PMBST_BYTE0_EOM) //quick command
{
pmbus_state= PMBUS_STATE_IDLE ;
}
else
{
}
return ;
pmbus_state= PMBUS_STATE_IDLE ;
}
d. In pmbus_wait_handler() is from the original pmbus_idle_handler()
i. Use pmbst_shadow.all to replace int32 pmbus_status = PMBusRegs.PMBST.all
pmbst_shadow.all=PMBusRegs.PMBST.all;
pmbus_status_half_word_0_value = pmbst_shadow.all & 0xFFFF ;
ii. Write command changes
if((pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS )) ==
(PMBST_BYTE0_EOM + PMBST_BYTE0_DATA_READY +
PMBST_BYTE0_PEC_VALID))
//end of message, good data ready, pec valid, must be 2 to 4 bytes
{
//copy all 4 over just to make sure
pmbus_buffer[1] = PMBusRegs.PMBRXBUF.byte.BYTE0;
UCD3138 – Responding to Multiple PMBus Slave Addresses
15
SLUA758
pmbus_buffer[2] = PMBusRegs.PMBRXBUF.byte.BYTE1;
pmbus_buffer[3] = PMBusRegs.PMBRXBUF.byte.BYTE2;
pmbus_buffer[4] = PMBusRegs.PMBRXBUF.byte.BYTE3;
pmbus_number_of_bytes = ( (pmbus_status_half_word_0_value &
PMBST_BYTE0_RD_BYTE_COUNT) + 1 );
pmbus_write_message();
//PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack them
pmbus_state = PMBUS_STATE_IDLE;
return;
}
iii. Write block request changes
else if((pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS +
PMBST_BYTE0_RD_BYTE_COUNT)) ==
(4 //4 is read byte count
+ PMBST_BYTE0_DATA_READY))
//no end of message, good data ready, 4 bytes of data - must be a send block
{
//copy data into buffer, set up to receive more.
pmbus_buffer[1] = PMBusRegs.PMBRXBUF.byte.BYTE0;
pmbus_buffer[2] = PMBusRegs.PMBRXBUF.byte.BYTE1;
pmbus_buffer[3] = PMBusRegs.PMBRXBUF.byte.BYTE2;
pmbus_buffer[4] = PMBusRegs.PMBRXBUF.byte.BYTE3;
pmbus_number_of_bytes = 5 ; //start counting bytes.
PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack first 4 bytes;
pmbus_state = PMBUS_STATE_WRITE_BLOCK;
}
iv. Delete read request and add ack to valid address to this function
else if( (pmbst_shadow.bit.SLAVE_ADDR_READY == 1) && (pmbst_shadow.bit.DATA_READY==0) ) //ack
pmbus address
{
pmbus_active_address = (PMBusRegs.PMBRXBUF.byte.BYTE0 & 0x7F);
if(
{
(pmbus_active_address == PMBUS_ADDRESS1)
||(pmbus_active_address == PMBUS_ADDRESS2)
||(pmbus_active_address == PMBUS_ADDRESS3)
||(pmbus_active_address == PMBUS_ADDRESS4) )
PMBusRegs.PMBACK.bit.ACK=1;
pmbus_state = PMBUS_STATE_READ;
return;
}
else
{
16
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
}
PMBusRegs.PMBACK.bit.ACK=0;
pmbus_state = PMBUS_STATE_IDLE;
return;
e. Add new void pmbus_read_handler(void), in addition, please also set the manual
command bit in PMBCTRL2 while writing to the register for sending data to host.
void pmbus_read_handler(void)
{
int32 i; //loop counter
union
{
Uint32 pmbus_transmit_load;
Uint8 pmbus_transmit_bytes[4];
}
u;
pmbst_shadow.all=PMBusRegs.PMBST.all;
pmbus_status_half_word_0_value = pmbst_shadow.all & 0xFFFF ; //assign to temporary value
pmbus_status_half_word_0_value_ored = pmbus_status_half_word_0_value_ored |
pmbus_status_half_word_0_value;
if((pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS +
PMBST_BYTE0_RD_BYTE_COUNT)) == 0)
{//if no activity on PMBus, do nothing
}
return ;
else if ( (pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS +
PMBST_BYTE0_RD_BYTE_COUNT)) ==
PMBST_BYTE0_DATA_REQUEST)//
{
pmbus_read_message();
if(pmbus_number_of_bytes == 0) //0 shows it is not a valid command, so
{
PMBusRegs.PMBACK.byte.BYTE0 = 1; //nack them
pmbus_state= PMBUS_STATE_IDLE ;
return;
}
else if(pmbus_number_of_bytes < 5) //here if it all fits in one rxbuf
UCD3138 – Responding to Multiple PMBus Slave Addresses
17
SLUA758
{
//
PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack command;
PMBusRegs.PMBCTRL2.byte.BYTE2 = PMBCTRL2_BYTE2_TX_PEC +
pmbus_number_of_bytes + PMBCTRL2_BYTE2_MAN_CMD +
PMBCTRL2_BYTE2_RX_BYTE_ACK_CNT;
//transmit with pec, desired number of bytes.
for(i = 0;i < pmbus_number_of_bytes;i++)
{
u.pmbus_transmit_bytes[3-i] = pmbus_buffer[i]; //big
endian stuff - great fun
}
PMBusRegs.PMBTXBUF.all = u.pmbus_transmit_load; //this
sends message
PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack command;
pmbus_state= PMBUS_STATE_READ_WAIT_FOR_EOM;
//pmbus_state = PMBUS_STATE_ACK;
return ;
}
else //here if we have to do multiple rxbuf loads - do first one, set up for more
{
PMBusRegs.PMBCTRL2.byte.BYTE2 = 4 +
PMBCTRL2_BYTE2_RX_BYTE_ACK_CNT + PMBCTRL2_BYTE2_MAN_CMD;
for(i = 0;i < 4;i++)
{
u.pmbus_transmit_bytes[3-i] = pmbus_buffer[i]; //big
endian stuff - great fun
}
PMBusRegs.PMBTXBUF.all = u.pmbus_transmit_load; //this
sends message
PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack command;
pmbus_buffer_position = 4;
}
pmbus_state = PMBUS_STATE_READ_BLOCK;
return ;
}
18
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
}
f. Changes to void pmbus_read_wait_for_eom_handler(void):
else if( (pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS+
PMBST_BYTE0_RD_BYTE_COUNT )) == PMBST_BYTE0_EOM)
{//if eom, done
pmbus_state = PMBUS_STATE_IDLE;
//PMBusRegs.PMBACK.byte.BYTE0 = 1; //ack them
return ;
}
else //some other error, still go back to idle.
{
//PMBusRegs.PMBACK.byte.BYTE0 = 0; //NACK
pmbus_state = PMBUS_STATE_IDLE;
return;
}
g. Changes to void pmbus_write_block_handler(void):
Delete the ack since we have manual ack after receiving address in pmbus_idle_handler
else if((pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS )) ==
(PMBST_BYTE0_EOM + PMBST_BYTE0_DATA_READY +
PMBST_BYTE0_PEC_VALID))
//end of message, good data ready, pec valid, must be 2 to 4 bytes
{
//copy all 4 over just to make sure
pmbus_buffer[pmbus_number_of_bytes] = PmbusRegs.PMBRXBUF.byte.BYTE0;
pmbus_buffer[pmbus_number_of_bytes + 1] = PmbusRegs.PMBRXBUF.byte.BYTE1;
pmbus_buffer[pmbus_number_of_bytes + 2] = PmbusRegs.PMBRXBUF.byte.BYTE2;
pmbus_buffer[pmbus_number_of_bytes + 3] = PmbusRegs.PMBRXBUF.byte.BYTE3;
pmbus_number_of_bytes = pmbus_number_of_bytes +
(pmbus_status_half_word_0_value & PMBST_BYTE0_RD_BYTE_COUNT);
pmbus_write_message();
//PmbusRegs.PMBACK.byte.BYTE0 = 1; //ack these 4 bytes;
pmbus_state = PMBUS_STATE_IDLE;
return;
}
else if((pmbus_status_half_word_0_value & (PMBST_HALF0_CHECK_BITS )) ==
(PMBST_BYTE0_EOM + PMBST_BYTE0_PEC_VALID))
//end of message, no new data ready, pec valid; was exact multiple of 4 bytes, already
acked last time
{
pmbus_write_message();
UCD3138 – Responding to Multiple PMBus Slave Addresses
19
SLUA758
//PmbusRegs.PMBACK.byte.BYTE0 = 1; //ack the message;
pmbus_state = PMBUS_STATE_IDLE;
return;
}
else //here if something has happened on bus, not covered by anything above
{
//PmbusRegs.PMBACK.byte.BYTE0 = 1; //nack them
pmbus_state = PMBUS_STATE_IDLE;
return;
}
5
Test Result
5.1
Multiple Addresses Shown in Device GUI
The device GUI shows there are multiple slavers on the PMBus interface, but it is actually a
single device.
Figure 11. Multiple Slave Addresses
20
UCD3138 – Responding to Multiple PMBus Slave Addresses
SLUA758
5.2
PMBus Master can get the Different Value in Different Address as There are
Multiple Devices in Slave
Figure 12. Slaver Sends its own Address to Master
6
Summary
This application note describes a firmware solution to let UCD3138 respond to multiple PMBus
addresses. The method involves firmware to ack address and command manually. From the test
result, UCD3xxx families can fully support this feature.
7
Reference
1.
PMBus – Power System Management Protocol Specification, System Management
Interface Forum, Inc. February, 2010
2.
UCD3138 Highly Integrated Digital Controller for Isolated Power (SLUSAP2C), Texas
Instruments, 2013
3.
UCD3138 ARM and Digital System Programmer’s Manual (SLUU994), Texas
Instruments, July 2012
4.
UCD3138 Monitoring and Communications Programmer’s Manual (SLUU996), Texas
Instruments, April, 2013
UCD3138 – Responding to Multiple PMBus Slave Addresses
21
IMPORTANT NOTICE
Texas Instruments Incorporated and its subsidiaries (TI) reserve the right to make corrections, enhancements, improvements and other
changes to its semiconductor products and services per JESD46, latest issue, and to discontinue any product or service per JESD48, latest
issue. Buyers should obtain the latest relevant information before placing orders and should verify that such information is current and
complete. All semiconductor products (also referred to herein as “components”) are sold subject to TI’s terms and conditions of sale
supplied at the time of order acknowledgment.
TI warrants performance of its components to the specifications applicable at the time of sale, in accordance with the warranty in TI’s terms
and conditions of sale of semiconductor products. Testing and other quality control techniques are used to the extent TI deems necessary
to support this warranty. Except where mandated by applicable law, testing of all parameters of each component is not necessarily
performed.
TI assumes no liability for applications assistance or the design of Buyers’ products. Buyers are responsible for their products and
applications using TI components. To minimize the risks associated with Buyers’ products and applications, Buyers should provide
adequate design and operating safeguards.
TI does not warrant or represent that any license, either express or implied, is granted under any patent right, copyright, mask work right, or
other intellectual property right relating to any combination, machine, or process in which TI components or services are used. Information
published by TI regarding third-party products or services does not constitute a license to use such products or services or a warranty or
endorsement thereof. Use of such information may require a license from a third party under the patents or other intellectual property of the
third party, or a license from TI under the patents or other intellectual property of TI.
Reproduction of significant portions of TI information in TI data books or data sheets is permissible only if reproduction is without alteration
and is accompanied by all associated warranties, conditions, limitations, and notices. TI is not responsible or liable for such altered
documentation. Information of third parties may be subject to additional restrictions.
Resale of TI components or services with statements different from or beyond the parameters stated by TI for that component or service
voids all express and any implied warranties for the associated TI component or service and is an unfair and deceptive business practice.
TI is not responsible or liable for any such statements.
Buyer acknowledges and agrees that it is solely responsible for compliance with all legal, regulatory and safety-related requirements
concerning its products, and any use of TI components in its applications, notwithstanding any applications-related information or support
that may be provided by TI. Buyer represents and agrees that it has all the necessary expertise to create and implement safeguards which
anticipate dangerous consequences of failures, monitor failures and their consequences, lessen the likelihood of failures that might cause
harm and take appropriate remedial actions. Buyer will fully indemnify TI and its representatives against any damages arising out of the use
of any TI components in safety-critical applications.
In some cases, TI components may be promoted specifically to facilitate safety-related applications. With such components, TI’s goal is to
help enable customers to design and create their own end-product solutions that meet applicable functional safety standards and
requirements. Nonetheless, such components are subject to these terms.
No TI components are authorized for use in FDA Class III (or similar life-critical medical equipment) unless authorized officers of the parties
have executed a special agreement specifically governing such use.
Only those TI components which TI has specifically designated as military grade or “enhanced plastic” are designed and intended for use in
military/aerospace applications or environments. Buyer acknowledges and agrees that any military or aerospace use of TI components
which have not been so designated is solely at the Buyer's risk, and that Buyer is solely responsible for compliance with all legal and
regulatory requirements in connection with such use.
TI has specifically designated certain components as meeting ISO/TS16949 requirements, mainly for automotive use. In any case of use of
non-designated products, TI will not be responsible for any failure to meet ISO/TS16949.
Products
Applications
Audio
www.ti.com/audio
Automotive and Transportation
www.ti.com/automotive
Amplifiers
amplifier.ti.com
Communications and Telecom
www.ti.com/communications
Data Converters
dataconverter.ti.com
Computers and Peripherals
www.ti.com/computers
DLP® Products
www.dlp.com
Consumer Electronics
www.ti.com/consumer-apps
DSP
dsp.ti.com
Energy and Lighting
www.ti.com/energy
Clocks and Timers
www.ti.com/clocks
Industrial
www.ti.com/industrial
Interface
interface.ti.com
Medical
www.ti.com/medical
Logic
logic.ti.com
Security
www.ti.com/security
Power Mgmt
power.ti.com
Space, Avionics and Defense
www.ti.com/space-avionics-defense
Microcontrollers
microcontroller.ti.com
Video and Imaging
www.ti.com/video
RFID
www.ti-rfid.com
OMAP Applications Processors
www.ti.com/omap
TI E2E Community
e2e.ti.com
Wireless Connectivity
www.ti.com/wirelessconnectivity
Mailing Address: Texas Instruments, Post Office Box 655303, Dallas, Texas 75265
Copyright © 2015, Texas Instruments Incorporated