START HERE
3
Using This Quick Start Manual
Connecting the RTD
Use this Quick Start Manual to set up your controller
and begin operation. Information is provided on how to:
¥
Connect ac power
1.
¥
Connect the RTD
¥
Set basic options for operation
For complete information on all setup options, see the
OperatorÕs Manual.
TB2
VERSION #1
Locate the TB2 connector on the rear of the
meter.
2.
4
+E
Attach the RTD wires, referring to the appropriate
diagram below and tighten down lockdown
screws.
3.
Tug gently on the wires to verify the connections.
4.
Replace the panel at the back of the meter.
1
+R
2
5
TB2
VERSION #2
3
6
4
7
+S -S
1
5
8
-R
3
2
6
4
7
+E1 +S1
In addition to the meter and the related parts, you will
need the following items to set up your meter:
¥
ac power, as listed on meterÕs ID/Power Label
¥
RTD
¥
1
+E
1
Ú8Ó flat blade screwdriver
5
PANEL THICKNESS
6,4 (.25) MAX
0,8 (.03) MIN
Mount the Meter
1.
Cut a panel opening
using the dimensions
shown here.
2.
3
2
6
Remove the panel at the back of the meter.
2.
Locate the TB1 connector.
3.
Insert the correct wire in each terminal and tighten
the lockdown screws. Tug gently on the wires to
verify connections.
VERSION #2
TB2
5
6
1
2
7
+E1 +S1
-S1 -E1
5
TB2
VERSION #2
3
6
1
4
7
+S
-S
2
5
8
-R
3
6
7
+E1 +S1
1
4
2
3
4
5
TB2
7
8
9
10 11 12
NEUTRAL
LINE
5
6
7
8
EARTH
GROUND
AC POWER
7
8
9
10 11 12
5
6
7
TB2 PINS 1 THRU 4
NOT AVAILABLE FOR
SINGLE RTD MODEL
8
RTD
RTD
The message STRD quickly
flashes, indicating that the
selection has been stored in
memory. Then the next
menu function displays.
Go back to the
previous menu
function.
Press RESET once.
Exit the meter
Configuration
Menu.
¥
Press RESET twice. The
reinitializes (displays RST,
then RTD). When the
temperature displays, the
meter is back in run mode.
1.
Apply ac power to the meter. The meter initializes,
flashing RST then RTD on the front panel. Then
the temperature should appear.
¥
Optionally, you can press
MENU to move through all
the menu functions until the
meter reinitializes.
2.
Verify that a temperature is displayed. If not:
¥
Remove ac power
¥
Verify the TB1 power connections
¥
Check your power source
¥
Apply ac power again
To Set the RTD Type:
1.
2.
Press MENU until the meter
displays:
8
To:
Take This Action
Display the
Configuration
Menu.
Press the MENU button.
The first function on the
menu, INPT, displays.
Select the
sub-menu
(a function you
want to perform).
1. Press MENU until the
function you want is shown.
2. Press 䊳/DEV.
The information you can change
begins to flash.
3.
Main ac Power Connections
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
RESET
Press 䊱/MAX until the RTD
for your installation is shown.
¥ RTD.2 is for a 2-wire RTD
¥ RTD.3 is for a 3-wire RTD
¥ RTD.4 is for a 4-wire RTD
4.
Press MENU to select the RTD shown. The
meter displays:
3-Wire RTD Input Connection
SETPTS
FUSE
SETPTS
Press 䊳/DEV. The meter
displays:
To configure the meter, use the buttons on the front
panel.
-S1 -E1
6
1. Press 䊳/MAX. to display
the option you want.
2. Press MENU to select it.
Turn on the Meter
Configure the Meter
4
TB1
3
8
+R
2
RTD
4-Wire RTD Input Connection
RTD
TB2
VERSION #1
1
VERSION #1
4
-R
RTD
+E
1.
TB1
-S
6
4
2-Wire RTD Input Connection
Warning: Do not connect ac power to your meter
until you have completed all input and output
connections. Failure to do so may result in injury!
3
5
8
3
92,00 + 0,81/Ð0,00
(3.622 + .032/Ð.000)
Connect ac Power
2
7
2
45,00 + 0,61/-0,00
(1.772 + .024/Ð.000)
Position the meter in
NOTE: Dimensions in Millimeters (Inches)
the opening, making
sure the front bezel is flush with the panel.
1
1
4
+S
1,5
R(.06)
4 PLCS
RTD
Select a value
for that submenu
function.
-S1 -E1
TB2
VERSION #2
+R
Take This Action
8
Before You Begin
TB2
VERSION #1
To:
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
RESET
12504ML-98A_CN1000-RTD_OMG.qxd
8/13/99
11:29 AM
Page 2
5
WARRANTY/DISCLAIMER
OMEGA Engineering, Inc. warrants this unit to be free of defects in materials
and workmanship for a period of 13 months from date of purchase. OMEGA
Warranty adds an additional one (1) month grace period to the normal one (1)
year product warranty to cover handling and shipping time. This ensures that
OMEGAÕs customers receive maximum coverage on each product.
If the unit should malfunction, it must be returned to the factory for evaluation.
OMEGAÕs Customer Service Department will issue an Authorized Return (AR)
number immediately upon phone or written request. Upon examination by
OMEGA, if the unit is found to be defective it will be repaired or replaced at no
charge. Omega's WARRANTY does not apply to defects resulting from any
action of the purchaser, including but not limited to mishandling, improper
interfacing, operation outside of design limits, improper repair, or unauthorized
modification. This WARRANTY is VOID if the unit shows evidence of having
been tampered with or shows evidence of being damaged as a result of
excessive corrosion; or current, heat, moisture or vibration; improper
specification; misapplication; misuse or other operating conditions outside of
OMEGAÕs control. Components which wear are not warranted, including but
not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various
products. However, OMEGA neither assumes responsibility for any
omissions or errors nor assumes liability for any damages that result
from the use if its products in accordance with information provided by
OMEGA, either verbal or written. OMEGA warrants only that the parts
manufactured by it will be as specified and free of defects. OMEGA
MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY
KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY
OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE
ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies
of purchaser set forth herein are exclusive and the total liability of
OMEGA with respect to this order, whether based on contract,
warranty, negligence, indemnification, strict liability or otherwise, shall
not exceed the purchase price of the component upon which liability is
based. In no event shall OMEGA be liable for consequential, incidental
or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor
shall it be used: (1) as a ÒBasic ComponentÓ under 10 CFR 21 (NRC), used in
or with any nuclear installation or activity; or (2) in medical applications or
used on humans. Should any Product(s) be used in or with any nuclear
installation or activity, medical application, used on humans, or misused in any
way, OMEGA assumes no responsibility as set forth in our basic WARRANTY
/ DISCLAIMER language, and additionally, purchaser will indemnify OMEGA
and hold OMEGA harmless from any liability or damage whatsoever arising
out of the use of the Product(s) in such a manner.
RETURN REQUESTS / INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service
Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA,
PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUMBER
FROM OMEGAÕS CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID
PROCESSING DELAYS). The assigned AR number should then be marked on
the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper
packaging to prevent breakage in transit.
FOR WARRANTY RETURNS,
please have the following information
available BEFORE
contacting OMEGA:
1. P.O. number under which the
product was PURCHASED,
2. Model and serial number of the
product under warranty, and
3. Repair instructions and/or specific
problems relative to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current repair
charges. Have the following
information available BEFORE
contacting OMEGA:
1. P.O. number to cover the COST of
the repair,
2. Model and serial number of product,
and
3. Repair instructions and/or specific
problems relative to the product.
OMEGAÕs policy is to make running changes, not model changes, whenever an
improvement is possible. This affords our customers the latest in technology and
engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 1999 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced, translated, or
reduced to any electronic medium or machine-readable form, in whole or in
part, without prior written consent of OMEGA ENGINEERING, INC.
PATENT NOTICE: The ÒMeter Case Bezel DesignÓ is a trademark of
NEWPORT Electronics, Inc., registered in the U.S. USED UNDER LICENSE.
This product is covered by one or more of the following patents: U.S. Pat. No.
Des. 336,895; 5,274,577 / CANADA 2052599; 2052600 / ITALY 1249456;
1250938 / FRANCE BREVET No. 91 12756 / SPAIN 2039150; 2048066 /
UK PATENT No. GB2 249 837; GB2 248 954 / GERMANY DE 41 34398 C2.
OTHER INTERNATIONAL PATENTS PENDING.
MQS1609/0899
12504ML-98 Rev. A
6
QUICK START
RoHS 2 Compliant
To Set the Decimal Point Position:
Begin Operation
1.
Reinitialize the meter (press
RESET twice or press MENU
until RST flashes on the display).
If it's not already shown, press
MENU until the meter shows:
SETPTS
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
2.
Press 䊳/DEV. The meter
displays:
SETPTS
3.
䊱 /MAX
䊳/DEV
MENU
RESET
䊱 /MAX
䊳/DEV
MENU
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
If it's not already shown, press
MENU until the meter shows:
䊱 /MAX
䊳/DEV
MENU
3.
3.
Press 䊱/MAX to display the
setting you want. Choices are
F and C.
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
TEMPERATURE CONTROLLER WITH
TIME PROPORTIONAL CONTROL
RESET
OMEGAnet¨ On-Line Service
http://www.omega.com
Press 䊳/DEV until the digit(s) you want to
change flashes on the display.
䊱/MAX
USA:
ISO 9001 Certified
to change the value.
¥
Press
¥
Press SETPTS to store the value shown. The
current value for setpoint 2 is shown:
Canada:
RESET
Press 䊳/DEV. The meter
displays:
SETPTS
MENU
To change the setpoint 1 value:
SETPTS
2.
䊳/DEV
RESET
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
䊱 /MAX
䊳/DEV
MENU
When setpoint 2 appears, you can change it using
the procedure above or press SETPTS to return
to RUN mode.
This device is marked with the international caution symbol. It is important
to read the Setup Guide before installing or commissioning this device as
it contains important information relating to safety and EMC.
SETPTS
䊱 /MAX
䊳/DEV
MENU
RESET
SETPTS
䊱 /MAX
䊳/DEV
MENU
RESET
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI
regulations that apply. OMEGA is constantly pursuing certification of its products to
the European New Approach Directives. OMEGA will add the mark to every
appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA
Engineering, Inc. accepts no liability for any errors it contains, and reserves the right
to alter specifications without notice.
TRADEMARK NOTICE:
omega.com™, and
are trademarks of OMEGA Engineering, Inc.
FAX: (514) 856-6886
For immediate technical or application assistance:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA¨
Customer Service: 1-800-622-2378 / 1-800-622-BEST¨
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN¨
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
Mexico
TEL: (001)800-826-6342
En Espa–ol: (001) 203-359-7803
e-mail: info@omega.com.mx
Benelux:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
Tel: +31 (0)20 6418405
FAX: +31 (0)20 6434643
Toll Free in Benelux: 0800 0993344
e-mail: nl@omega.com
RudŽ arm‡dy 1868, 733 01 Karvin‡ 8
Tel: +420 (0)69 6311899
FAX: +420 (0)69 6311114
e-mail: czech@omega.com
9, rue Denis Papin, 78190 Trappes
Tel: +33 (0)130 621 400
FAX: +33 (0)130 699 120
Toll Free in France: 0800406342
e-mail: france@omega.com
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
Tel: +49 (0)7056 9398-0
FAX: +49 (0)7056 9398-29
Toll Free in Germany: 0800 TC-OMEGASM
e-mail: germany@omega.com
One Omega Drive,
River Bend Technology Centre
Northbank, Irlam
Manchester M44 5EX United Kingdom
Tel: +44 (0)161 777 6611
FAX: +44 (0)161 777 6622
Toll Free in United Kingdom: 0800 488 488
e-mail: sales@omega.co.uk
®
,
FAX: (001) 203-359-7807
Servicing Europe:
France:
RESET
Press MENU to select the temperature meter
shown.
The
meter
displays:
FAX: (203) 359-7700
RESET
WARNING: These products are not designed for use in, and should not be used
for, patient connected applications.
4.
One Omega Drive, P.O. Box 4047
Stamford, CT 06907-0047
Tel: (203) 359-1660
e-mail: info@omega.com
976 Bergar
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928
e-mail: info@omega.ca
USA and Canada:
Czech Republic:
SETPTS
Internet e-mail
info@omega.com
Servicing North America:
To Select the Temperature Unit
(Fahrenheit or Celsius):
SETPTS
䊱 /MAX
RESET
¥
1.
CN1000-RTD
You can change setpoint 1 or press SETPTS
again to show the current value for setpoint 2.
2.
䊳/DEV
RESET
RESET
Press MENU to select the decimal point position
shown. The meter displays:
䊱 /MAX
MENU
While in RUN mode, press SETPTS. The unit
displays setpoint 1:
SETPTS
SETPTS
䊳/DEV
Changing Setpoint Values:
1.
Press 䊱/MAX to move the
decimal point to the desired
location. Choices are: FFFF.
or FFF.F.
SETPTS
4.
䊱 /MAX
When the temperature appears,
the meter is up and running.