Omega | DP26-RTD | Owner Manual | Omega DP26-RTD Owner Manual

Omega DP26-RTD Owner Manual
TM
User’s Guide
Shop online at
omega.com
e-mail: info@omega.com
For latest product manuals:
www.omegamanual.info
DP26-RTD
Differential Temperature
Meter with RTD
omega.com info@omega.com
U.S.A.
Headquarters:
Servicing North America:
Omega Engineering, Inc.
Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660
Fax: (203) 359-7700
e-mail: info@omega.com
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves
the right to alter specifications without notice.
PREFACE
Manual Objectives
This manual shows you how to set up and use the Differential RTD Meter.
Standard Procedures:
*
Checking voltage jumpers, or changing voltage power
*
Mounting the panel
*
Selecting the input type
*
Selecting a decimal point position
*
Selecting reading configuration (Fahrenheit or Celsius)
*
Setting setpoint configuration
*
Setting setpoint deadbands
*
Entering temperature offset
*
Accessing the deviation mode
*
Selecting meter display
Optional Procedures:
*
Enabling/disabling analog output
*
Selecting analog output as current or voltage
*
Selecting analog output or proportional control
*
Routing analog output
*
Selecting proportional band
*
Using manual reset (offsetting setpoint errors)
*
Scaling analog output
For first-time users: Refer to the QuickStart Manual for basic operation and
set-up instructions.
i
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by these labels:
•
•
•
•
NOTE
WARNING
CAUTION
IMPORTANT
NOTE: provides you with information that is important to successfully setup
and use the Programmable Digital Meter.
CAUTION or WARNING: tells you about the risk of electric shock.
CAUTION, WARNING or IMPORTANT: tells you of circumstances or
practices that can effect the meter's functionality and must refer to
accompanying documents.
TIP: Provides you helpful hints.
iii
Table of Contents
Section
Page
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.1 UNPACKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.2 SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
2. ABOUT THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.1 DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.2 STANDARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
2.3 AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
2.4 FRONT OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2.5 FRONT-PANEL BUTTON LOCK OUT . . . . . . . . . . . . . . . . . . . . . . . . .8
2.5.1 Push Button Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.5.2 Jumper Lock Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2.6 BACK OF THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
2.7 DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3. GETTING STARTED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.1 RATING/PRODUCT LABEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.2 MAIN BOARD POWER JUMPERS . . . . . . . . . . . . . . . . . . . . . . . . . .12
3.3 MOUNTING THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3.4 CONNECTING SENSOR INPUT . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3.5 CONNECTING MAIN POWER . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
3.6 CONNECTING ANALOG AND RELAY OUTPUT CONNECTIONS . .19
4. CONFIGURING THE METER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
4.1 SELECTING THE INPUT TYPE (INPT) . . . . . . . . . . . . . . . . . . . . . .20
4.2 SELECTING DECIMAL POINT POSITION (DEC.P) . . . . . . . . . . . . .20
4.3 SELECTING READING CONFIGURATION ("RD.CF") . . . . . . . . . . .21
4.4 SETTING SETPOINT 1 CONFIGURATION (S1.CF) . . . . . . . . . . . . .22
4.5 SETTING SETPOINT 2 CONFIGURATION (S2.CF) . . . . . . . . . . . . .23
4.6 SETTING SETPOINT 1 DEADBAND (S1.DB) . . . . . . . . . . . . . . . . . .24
4.7 SETTING SETPOINT 2 DEADBAND (S2.DB) . . . . . . . . . . . . . . . . . .25
iv
Section
Page
4.8 SELECTING OUTPUT CONFIGURATION (OT.CF) . . . . . . . . . . . . . .26
4.8.1 Enabling or Disabling The Analog Output . . . . . . . . . . . . . . . . .26
4.8.2 Selecting Analog Output as Current or Voltage . . . . . . . . . . . .27
4.8.3 Selecting Analog Output or Proportional Control . . . . . . . . . . .27
4.9 ROUTING ANALOG OUTPUT (OUT) . . . . . . . . . . . . . . . . . . . . . . . .29
4.10 SELECTING PROPORTIONAL BAND (P.BND) . . . . . . . . . . . . . . . .29
4.11 USING MANUAL RESET (M.RST) . . . . . . . . . . . . . . . . . . . . . . . . .31
4.12 SCALING THE ANALOG OUTPUT (OT.S.O) . . . . . . . . . . . . . . . . .32
4.13 RTD TEMPERATURE OFFSET ERROR CORRECTION . . . . . . . .36
5. ACCESSING THE DEVIATION MODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
6. SELECTING METER DISPLAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
7. TUNING THE PROPORTIONAL CONTROLLER . . . . . . . . . . . . . . . . . . . . . . .41
8. DISPLAY MESSAGES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
9. MENU CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
10. FRONT PANEL DISPLAYS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
11. SETPOINT CONFIGURATION DISPLAYS
12. SPECIFICATIONS
. . . . . . . . . . . . . . . . . . . . . . . . . .48
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
13. FACTORY PRESET VALUES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
14. APPROVALS
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
v
List of Figures
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
Figure
2-1. Front-Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
2-3. Connector Label (AC-Powered and DC-Powered Detail) . . . . . . . . . . .9
3-1. Main Board Power Jumpers (W1, W2, W3) . . . . . . . . . . . . . . . . . . . .12
3-2. Main Board Jumper Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3-3. Upper Option Board Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
3-4. Meter - Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3-5. Panel Cut-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
3-6. 2-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3-7. 3-Wire RTD Input Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3-8. 4-Wire RTD Input connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
3-9. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . . . . . .17
3-10. Main Power Connections - DC Powered Unit . . . . . . . . . . . . . . . . . .18
3-11. Relay Output Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
3-12. Analog Output Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
3-13. Isolated Analog Output Connections. . . . . . . . . . . . . . . . . . . . . . . . .19
4-1 Proportional Band . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
12-1. Meter Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
List of Tables
Table
Table A-1. Sections of the Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ii
Table 2-1. Accessories and Add-Ons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Table 2-2. Connector Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Table 3-1. S3 Jumper Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Table 3-2. Main Power Connections - AC Powered Unit . . . . . . . . . . . . . . . . . . . .18
Table 6-1. Truth Table for Display Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Table 8-1. Display Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Table 9-1. Configuration Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Table 10-1. Front Panel Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Table 10-2 Run Mode Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
Table 11-1. Setpoint Configuration Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Table 13-1. Factory Preset Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
vi
SECTION 1. INTRODUCTION
1.1 UNPACKING
Remove the Packing List and verify that all equipment has been received. If there are
any questions about the shipment, use the phone numbers listed on the back cover to
contact the Customer Service Department nearest you.
Upon receipt of shipment, inspect the container and equipment for any signs of
damage. Take particular note of any evidence of rough handling in transit. Immediately
report any damage to the shipping agent.
The carrier will not honor any claims unless all shipping material is saved
for their examination. After examining and removing contents, save
packing material and carton in the event reshipment is necessary.
Verify that you receive the following items in the shipping box:
QTY
DESCRIPTION
1
Meter with all applicable connectors attached.
1
Owner's Manual
1
Set Mounting brackets
1
QuickStart Manual
If you ordered any of the available options (except the "BL" Blank Lens
option), they will be shipped in a separate container to avoid any damage
to your indicator/controller.
1
SECTION 1.2 SAFETY CONSIDERATIONS
This device is marked with the international caution symbol. It is important to
read this manual before installing or commissioning this device as it contains
important information relating to Safety and EMC (Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment for
measurement, control and laboratory. Installation of this instrument should be
done by qualified personnel. In order to ensure safe operation, the following
instructions should be followed.
This instrument has no power-on switch. An external switch or circuit-breaker
shall be included in the building installation as a disconnecting device. It shall be
marked to indicate this function, and it shall be in close proximity to the equipment
within easy reach of the operator. The switch or circuit-breaker shall not interrupt
the Protective Conductor (Earth wire), and it shall meet the relevant requirements
of IEC 947–1 and IEC 947-3 (International Electrotechnical Commission). The
switch shall not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn from
the main supply in case of a fault in the equipment, an overcurrent protection
device shall be installed.
•
Do not exceed voltage rating on the label located on the top of the instrument
housing.
• Always disconnect power before changing signal and power connections.
• Do not use this instrument on a work bench without its case for safety
reasons.
• Do not operate this instrument in flammable or explosive atmospheres.
• Do not expose this instrument to rain or moisture.
• Unit mounting should allow for adequate ventilation to ensure instrument does
not exceed operating temperature rating.
• Use electrical wires with adequate size to handle mechanical strain and power
requirements. Install without exposing bare wire outside the connector to
minimize electrical shock hazards.
EMC Considerations
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wires close to the instrument if EMC problems
persist.
Note ☞
Failure to follow all instructions and warnings may result in injury!
2
SECTION 2. ABOUT THE METER
2.1 DESCRIPTION
The Differential RTD meter is a value packed indicator/controller. Four full digits
accurately display your temperature. Select from DIN (Alpha = .00385) or NIST (Alpha
= .00392); 2,3, or 4 wire RTD. Your meter may be a basic indicator or it may include
analog output or dual relay output. Analog or dual relay output must be ordered at time
of purchase. Analog output is fully scalable and may be configured as a proportional
controller, or to follow your display. Dual 5 amp, form C relays control critical
processes. Front panel peak detection and memory is also standard. A mechanical
lockout has been included to guard against unauthorized changes.
2.2 STANDARD FEATURES
The following is a list of features:
*
*
*
*
*
*
*
4-digit, 14 segment LED Display
NEMA 4/Type 4 Front Bezel
±0.5° C accuracy
Automatic Decimal Adjustment
Non-volatile memory
115 or 230 V ac 50/60 Hz power supply or
10-32 Vdc or 26-56 Vdc
T1, T2, T1-T2 display
The following is a list of optional features
*
*
*
*
*
*
Dual 5 amps, form C relay outputs
Scalable analog output
Analog out Proportional control
Easy setup for proportional control
Front-panel deviation correction
Easy RTD error offset calibration
3
2.3 AVAILABLE ACCESSORIES
Table 2.1 Accessories and Add-ons
Add-On Options
FS
SPC4
SPC18
Special Calibration/Configuration
NEMA-4 Splash Proof Cover
NEMA-4 Splash Proof Cover, NEW
Accessories
TP1A
RP18
RP28
RP38
Trimplate panel adaptor.
Adapts DIN1A/DIN2A cases to larger panel cutouts
19-In. Rack Panel for one (1) 1/8 DIN instrument
19-In. Rack Panel for two (2) 1/8 DIN instrument
19-In. Rack Panel for three (3) 1/8 DIN instrument
4
2.4 FRONT OF THE METER
Figure 5-1 shows the location of each part of the front of the meter.
••••
T1
1
SETPTS
/T1/T2/
-
T2
/DEV
C
F
2
MENU
RESET
Figure 2-1 Front Panel
Digital LED Display: -1.9.9.9. or 9.9.9.9. 4-digit, 14 segment, 13.8 mm
(0.54") high LED display with programmable decimal point.
These meter display windows light when appropriate:
1
2
C
F
T1
T2
T1-T2
-
Setpoint 1 status
Setpoint 2 status
°C unit indicator
°F unit indicator
T1 on display
T2 on display
T1-T2 on display
5 Pushbuttons for programming the meter.
5
2.4 FRONT OF THE METER (Continued)
METER BUTTONS
SETPTS Button
In the run mode, press this button to sequentially recall the previous setpoint settings.
After using the /T1/T2 and /DEV buttons to alter these settings as desired, press
the SETPTS button to store these new values.
Unless you press the SETPTS, /T1/T2 or /DEV button within 20 seconds to
store your input, the meter will scroll to setpoint 2 the return to the run mode.
If the dual relay option is not installed or if the “L.3=1” on the “LK.CF” menu, pressing
the SETPTS button will display the meter's firmware version.
/T1/T2 Button
In the run mode, pressing the /T1/T2 button will scroll to show T1, T2, and T1-T2.
During the configuration mode or Setpoint modes, use the /T1/T2 button to
change the values of the flashing digit shown on the display and/or toggle between
menu choices, such as "R.1=F" or "R.1=C". When configuring your setpoint values,
press the /T1/T2 button to increment the flashing digit from 0 to 9 by 1's.
/DEV Button
In the run mode press the /DEV button to display the deviation of reading from
Setpoint 1.
In the configuration or setpoint modes, press the /DEV button to scroll to the next
digit.
6
2.4 FRONT OF THE METER (Continued)
MENU Button
In the run mode, press the MENU button to terminate the current measuring process
and enter you into the configuration mode.
In the configuration mode, press the MENU button to store changes in the non-volatile
memory and then advance you to the next menu item.
To lock the MENU button, install S3E jumper. Refer to Table 3-1 for more information
about the S3 jumpers.
RESET Button
In the run mode, press the RESET button to:
*
reset the latched setpoints. The display will show "SP.RS" (Setpoint Reset).
*
perform tuning for Proportional Control if the meter is setup to serve as a
proportional controller (0.3=P refer to Section 4.8.3 and Section 7) the meter will
show “TUNE”.
Also in the run mode, if you hard reset or power off/on the meter, it shows "RST"
followed by "D.RTD".
In the configuration mode, press the RESET button once to review the previous menu.
Pressing the RESET button twice results in a hard reset and returns you to the run
mode.
In the setpoint mode, press RESET button to go back to the run mode. THe meter will
show “RUN”.
7
2.5 FRONT PANEL LOCKOUT
2.5.1 PUSH BUTTON LOCKOUT
To lock the RESET, MENU and SETPTS buttons, verify that the S3-A jumper is
installed and the S3-E jumper is not installed, then follow these steps:
In the run mode1.
Press and hold down the RESET button. The meter shows “SP.RS”. Do not
release the RESET button.
2.
Press the MENU button and hold RESET button down (3-5 seconds) until the
meter shows “LOCK”.
3.
Release both buttons.
To unlock the RESET, MENU and SETPTS buttons, follow these steps:
1.
Press and hold down the RESET button. The meter shows “LOCK”. Do not
release the RESET button.
2.
Press the MENU button and hold RESET button down (3-5 seconds) until the
meter shows “UN.LK”.
3.
Release both buttons.
2.5.2 JUMPER LOCKOUT
To lock all front panel buttons, remove the S3-A jumper (refer to Figure 3-2).
To lock the MENU button only, verify that the S3-B jumper is removed, then install
the S3-A and S3-E jumpers, (refer to Table 3-1).
8
2.6 BACK OF THE METER
Figure 2-2 shows the connector label mounted at the top of the meter housing. Table
2-2 gives a brief description of each connector at the back of the meter.
POWER & INPUT CONNECTIONS
(DIFFERENTIAL RTD)
RTD2
+E2
+S2
+E1
-S2
+S1
-E2
-S1
-E1
RTD1
Figure 2-2 Connector label (ac Powered and dc Powered detail)
9
2.6 BACK OF THE METER (Continued)
Table 2-2 Connector Description
Connector
TB1-1
TB1-2
TB1-3
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
TB5-1
TB5-2
TB5-3
Description
Setpoint 1: Normally open (N.O.1) connection
Setpoint 1: Normally closed (N.C.1) connection
Setpoint 1: Common (COM1) connection
Setpoint 2: Normally open (N.O.2) connection
Setpoint 2: Normally closed (N.C.2) connection
Setpoint 2: Common (COM2) connection
ac line connection (no connections on dc-powered units)
ac neutral connection (+ Input on dc-powered units)
ac Earth ground (-dc-power return on dc-powered units)
Analog 1 voltage output
Analog 2 current output
Analog 3 return
+E2:
Positive excitation for input #2
+S2:
Positive signal input for input #2
-S2:
Negative signal input for input #2
-E2:
Negative excitation for input #2
+E1:
Positive excitation for input #1
+S1:
Positive signal input for input #1
-S1:
Negative signal input for input #1
-E1:
Negative excitation for input #1
Isolated Analog Voltage Output
Isolated Analog Current Output
Isolated Analog Output Return
10
2.7 DISASSEMBLY
You may need to open up the meter for one of the following reasons:
•
To check or change the 115 or 230 Vac power jumpers.
•
To install or remove jumpers on the main board.
Disconnect the power supply before proceeding.
To remove and access the main board, follow these steps:
•
Disconnect the main power from the meter.
•
Remove the back case cover.
•
Lift the back of the main board upwards and let it slide out of the
case.
11
SECTION 3. GETTING STARTED
Caution: The meter has no power-on switch, so it will be in operation as
soon you apply power.
If you power off/on the meter, or perform a hard reset (press the RESET button twice),
the meter shows "RST", followed by "D.RTD".
3.1 RATING/PRODUCT LABEL
This label is located on top of the meter housing (Refer to Figure 3-3).
3.2 MAIN BOARD POWER JUMPERS
Important: If you want to change the Factory preset jumpers, do the
following steps; otherwise go to section 3.3.
Warning: Disconnect the power from the unit before proceeding. This
device must only be reconfigured by a specially trained electrician with
corresponding qualifications. Failure to follow all instructions and warnings
may result in injury!
To check voltage jumpers, or to change from 115 V to 230 V ac:
1.
Remove the main board from the case. Refer to Section 2.7.
2.
Locate the solder jumpers W1, W2, and W3 (located near the edge of the
main board alongside the transformer - refer to Figure 3-1).
3.
If your power requirement is 115 V ac, solder jumpers W1 and W3 should
be wired, but jumper W2 should not. If your power requirement is 230 V ac,
solder jumper W2 should be wired, but jumpers W1 and W3 should not.
Figure 3-1 shows the location of solder jumpers W1 through W3 on the main board.
Figure 3.1 Main Board Power Jumpers
12
3.2 MAIN BOARD POWER JUMPERS (Continued)
Figure 3-2 shows the main board jumpers.
Figure 3.2 Main Board Jumper Positions
Attach cable
to P1.
TB5
P1
Figure 3.3 Upper Option Board Installation
13
3.2 MAIN BOARD POWER JUMPERS (Continued)
S2 jumpers are for sensor break indications:
*
*
*
*
S2A jumper is not used
S2B jumper is for positive sensor break on input 1 (i.e. heating)
S2C jumper is for positive sensor break on input 2 (i.e. heating)
S2D is not used
S3 jumpers are used for the following (refer to Table 3-1):
*
*
*
*
To enable or disable the front panel push-buttons
To allow for an extremely low resistance load for analog output
To disable the MENU button
To perform calibration procedure
Test pins TP1 - TP11 are for testing purposes. Do not use as reading errors may
result.
Table 3-1 S3 Jumper Functions
Jumper
S3-A
S3-B
S3-C
S3-D
S3-E
Description
Install to enable front panel push-buttons.
Remove to disable all front panel push-buttons
Removed. Install for factory calibration only.
Normally removed. Install for analog voltage output when load is less than
1 Kohm impedance. Care should be taken when installing this jumper.
Removed. Not used.
If installed without S3-B, the MENU button locks out.
While in run mode, if you press the MENU button, the display shows
“LOCK".
14
3.3 MOUNTING THE METER
RE
A
(R R C
EM OV
OV ER
ED
CONNECTOR
)
PANEL
CUT-OUT
"NEW" STYLE
MOUNTING
BRACKET
LABEL
PRODUCT
LABEL
CASE
"OLDER" STYLE
MOUNTING
BRACKET 2 PCS
GASKET
FRONT BEZEL
Figure 3-3 Meter - Exploded View
1. Cut a hole in your panel, as
shown in Figure 3-3. For
specific dimensions refer to
Figure 3-4.
2. Insert the meter into the hole.
Be sure the front bezel gasket
is flush to the panel.
3. Slide on mounting bracket to
secure.
4. Proceed to Section 3.4 to
connect your sensor input
and main power.
PANEL THICKNESS
6,4 (.25) MAX
0,8 (.03) MIN
1,5
R(.06)
4 PLCS
45,00 + 0,61/-0,00
(1.772 + .024/–.000)
92,00 + 0,81/–0,00
(3.622 + .032/–.000)
NOTE: Dimensions in Millimeters (Inches)
Figure 3-4 Panel Cut-Out
15
3.4 CONNECTING SENSOR INPUT
Figure 3-5 through 3-7 illustrate how to connect you power sensors.
+E2 +S2
1
-S2 -E2
2
3
5
6
+E1 +S1
4
7
8
-S1 -E1
RTD
Channel 2
RTD
Channel 1
Figure 3-5 2-Wire RTD Input Connection
-S2 -E2
+E2 +S2
1
2
3
5
6
+E1 +S1
4
7
RTD
Channel 2
8
-S1 -E1
RTD
Channel 1
Figure 3-6 3-Wire RTD Input Connection
-S2 -E2
+E2 +S2
1
2
5
+E1 +S1
3
6
4
7
RTD
Channel 2
8
-S1 -E1
RTD
Channel 1
Figure 3-7 4-Wire RTD Input Connection
Note: Install rear plastic cover after RTD connection.
16
3.5 CONNECTING MAIN POWER
Connect the ac main power connections as shown in Figure 3-8.
Warning: Do not connect AC power to your device until you have
completed all input and output connections. This device must only be
installed by a specially trained electrician with corresponding qualifications.
Failure to follow all instructions and warnings may result in injury!
Figure 3-8 Main Power Connections (ac powered unit)
Table 3-2 shows the wire color and respective terminal connections for both USA and
Europe.
Table 3-2 Main Power Connections (ac powered unit)
WIRE COLORS
TB1
AC POWER
EUROPE
USA
7
~ ac Line
Brown
Black
8
~ ac Neutral
Blue
White
9
~ ac Earth
Green/Yellow
Green
17
3.5 CONNECTING MAIN POWER (Continued)
Connect the dc main power connections as shown in Figure 3-9..
Figure 3-9 Main Power Connections (dc powered unit)
3.6 ANALOG AND RELAY OUTPUT CONNECTIONS
If you have purchased a meter with analog or dual relay or isolated analog output,
refer to the following figures for output connections.
Figure 3-10 Relay Output Connections
18
3.6 ANALOG AND RELAY OUTPUT CONNECTIONS (continued)
Figure 3-11 Analog Output Connections
Figure 3-12 Isolated Analog Output Connections
19
Table 10-1 Front-Panel Displays (continued)
MENU
/DEV
/T1/T2/
DESCRIPTION
P.BND
Scroll right one digit
Changes the value
of the flashing digit
Proportional Band
select from 0000
through 9999
M.RST
Scroll right one digit
Changes the value
of the flashing digit
Manual Reset
select from 0000
through 9999
T1.OF
Shows prior value
entered.
Scroll right one digit
Changes the value
of the flashing digit
RTD Temperature
Offset Channel 1
T2.OF
Shows prior value
entered.
Scroll right one digit
Changes the value
of the flashing digit
RTD Temperature
Offset Channel 2
Table 10-2 Run Mode Display
DISPLAY
/DEV
/T1/T2/
Run
Mode
RESET
DESCRIPTION
LATCHED RESET
Press RESET button
to reset your
setpoints.
47
SECTION 11. SETPOINT CONFIGURATION DISPLAYS
Table 11-1 Setpoints Configuration Displays
MENU
SP 1
Setpoint 1
SP 2
Setpoint 2
/DEV
/T1/T2/
DESCRIPTION
Press to scroll
to the next
digitto the right
Press to change
the value of the
flashing digit
SETPOINT 1
Scroll right
one digit
Press to change
the value of the
flashing digit
SETPOINT 2
48
Select from -1999
through 9999
Select from -1999
through 9999
SECTION 12. SPECIFICATIONS
SIGNAL INPUT
RTD types:
DIN (0.00385) type 2,3, or 4 wire
NIST (0.00392) type 2,3, or 4 wire
Lead Resistance for Specified Accuracy:
2 Wire Up to 55 milliohm/lead
3 Wire Up to 10 ohms/lead balanced
4 Wire Up to 20 ohms/total unbalanced
Isolation:
Dielectric strength to 2500V transient per 3mm
spacing based on EN 61010 for 260Vrms or dc
working voltage
Noise Rejection:
Normal Mode Rejection (NMR) = 60dB
Common Mode Rejection (CMR) = 120dB
Protection:
240 V rms max for voltage input ranges
200 mA for current input ranges
Standard Display:
4-digit, 14-segment LED, 13.8 mm (0.54”)
Symbol:
( -1.9.9.9. ~ 9.9.9.9.)
ANALOG TO DIGITAL
Technique:
Dual slope
Internal resolution:
15 bits
Read rate:
3/seconds for each channel
Polarity:
Automatic
ACCURACY AT 25°C
Accuracy:
±0.50°C after 30 minute warm-up
Temperature Stability:
0.04°C/°C
Step response:
1 second to 99% of the final value
49
INPUT POWER INFORMATION:
~ AC units
115/230 V~(AC) ±10%, 50/60 Hz
7 W max, power consumption (Non-Isolated Analog
Output)
8 W max, power consumption (Isolated Analog Output)
DC units
10-32 Vdc
6 W max, power consumption (Non-Isolated Analog
Output)
7 W max, power consumption (Isolated Analog Output)
External Fuse Required:
IEC 127-2/III
Power
Fuse
115 V
125 mA @ 250 (T)
230 V
63 mA @ 250 (T)
UL 248-14 (Listed Fuse)
Power
Fuse
115 V
175 mA @ 250 V Slow-Blow
230 V
80 mA @ 250 V Slow-Blow
ENVIRONMENT
Operating temperature:
0 to 50°C (32° to 122°F)
Storage temperature:
-40° to 85°C (-40° to 185°F)
Relative humidity:
90% at 40°C (non-condensing)
MECHANICAL
Panel cutout:
1/8 DIN 3.62 x 1.78" (92 x 45 mm)
Weight:
1.27 lb (574 g)
Case material:
Polycarbonate, 94 V-O UL rated
50
ANALOG OUTPUT (if applicable)
Signal type:
Current or voltage
Signal level:
Current: 10 V max compliance at 20 mA output
Voltage: 20 mA max for 0-10 V output
Function:
May be assigned to a display range or proportional
control output with setpoint #1 when used as a
control output.
Linearity:
0.2%
Load Regulation:
1.1%
Line Regulation:
Step Response Time:
0.02% /V ac
2 - 3 seconds to 99% of the final value
ALARM OUTPUTS (if applicable)
2 Form "C" on/off relays. Configurable for latched and unlatched by software.
Max current:
5 AMPS, resistive load.
Max voltage:
250 V ac or 30 V dc
ISOLATED ANALOG OUTPUT (TB5, if applicable)
Same as non-isolated analog output except isolated to 1000 Vdc.
Signal Type:
Current or voltage
Signal Level:
Current: 10 V max compliance at 20 mA output
Voltage: 20 mA max for 0-10 V output
Function:
May be assigned to a display range or proportional
control output with setpoint #1 when used as a
control output.
Linearity:
0.2%
Step Response Time:
2 - 3 seconds to 99% of the final value
Only one analog output is available on each unit and it must be factory installed.
51
48,0 (1.89)
96,0 (3.78)
FRONT BEZEL
20,3 (.80)
151,4 (5.96)
RETAINER
CASE
REAR COVER
TOP VIEW
SIDE VIEW
PANEL THICKNESS
6,4 (.25) MAX
0,8 (.03) MIN
1,5
R(.06)
4 PLCS
45,00 + 0,61/-0,00
(1.772 + .024/–.000)
92,00 + 0,81/–0,00
(3.622 + .032/–.000)
NOTE: Dimensions in Millimeters (Inches)
Figure 12-1 Meter Dimensions
52
SECTION 13. FACTORY PRESET VALUES
Table 13-1 Factory Preset Values
MENU ITEM
INPT
DEC.P
RD.CF
S1.CF
S2.CF
S1.DB
S2.DB
OT.CF
OUT
OT.S.O
T1.OF
T2.OF
SP1
SP2
FACTORY PRESET VALUES
Input Type: 385.3 (3 wire DIN RTD)
Decimal Point Position: FFF.F
Reading Configuration:
R.1=F (Fahrenheit)
Setpoint 1 Configuration:
S.1=A (Setpoint is active above)
S.2=U (Setpoint is unlatched)
S.3=0 (Setpoint 1 is assigned to T1-T2)
Setpoint 2 Configuration:
S.1=A (Setpoint is active above)
S.2=U (Setpoint is unlatched)
S.3=0 (Setpoint 2 is assigned to T1-T2)
Setpoint 1 Deadband: .0003
Setpoint 2 Deadband: .0003
Output Configuration:
O.1=E (Analog output is enabled)
O.2=C (Analog output is current)
O.3=A (Analog output follows the display value)
Analog Output Routing: T1 - T2
Output Scale and Offset:
0-1000 = 4-20 mA dc
RTD for T1: 000.0
RTD for T2: 000.0
Setpoint 1 Value: 000.0
Setpoint 2 Value: 000.0
53
APPROVALS INFORMATION
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Power to Input/Output:
• Power to Input/Output:
2300 Vac (3250 Vdc)
500 Vac (720 Vdc)
(Low Voltage dc Power Option*)
• Power to Relays Output:
2300 Vac (3250 Vdc)
• Relay 1 to Relay 2:
2300 Vac (3250 Vdc)
• Isolated Analog to Inputs:
1000 Vac (1420 Vdc)
• Analog to Inputs:
No Isolation
Measurement Category I
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50 Vac/dc. This
unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power:
2500 V
• Input Power:
500 V
(Low Voltage dc Power Option*)
• Isolated Analog:
500 V
• Input/Output Signals:
500 V
Note: *Units configured for external low power dc voltage, 10-32 Vdc (Basic Insulation)
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement,
control and laboratory.
• EMC Emissions Table 4, Class B of EN61326
• EMC Immunity** Table 1 of EN61326
Note: **I/O signal and control lines require shielded cables and these cables
must be located on conductive cable trays or in conduits. Furthermore,
the length of these cables should not exceed 30 meters
Refer to the EMC and Safety installation considerations (Guidelines) of this manual for
additional information.
54
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 61 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal five (5) year product warranty to cover handling and shipping time. This
ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for
any damages that result from the use of its products in accordance with information provided
by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR NON-WARRANTY REPAIRS, consult
FOR WARRANTY RETURNS, please have the
OMEGA for current repair charges. Have
following information available BEFORE contacting
the following information available BEFORE
OMEGA:
contacting OMEGA:
1. Purchase Order number under which the product
1. Purchase Order number to cover the COST
was PURCHASED,
of the repair,
2. Model and serial number of the product under
2. Model and serial number of the product, and
warranty, and
3. Repair instructions and/or specific problems
3. Repair instructions and/or specific problems
relative to the product.
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2017 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
TEMPERATURE
M
U Thermocouple, RTD & Thermistor Probes, Connectors,
Panels & Assemblies
M
U Wire: Thermocouple, RTD & Thermistor
M
U Calibrators & Ice Point References
M
U Recorders, Controllers & Process Monitors
M
U Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
M
U Transducers & Strain Gages
M
U Load Cells & Pressure Gages
M
U Displacement Transducers
M
U Instrumentation & Accessories
FLOW/LEVEL
M
U Rotameters, Gas Mass Flowmeters & Flow Computers
M
U Air Velocity Indicators
M
U Turbine/Paddlewheel Systems
M
U Totalizers & Batch Controllers
pH/CONDUCTIVITY
M
U pH Electrodes, Testers & Accessories
M
U Benchtop/Laboratory Meters
M
U Controllers, Calibrators, Simulators & Pumps
M
U Industrial pH & Conductivity Equipment
DATA ACQUISITION
M
U Communications-Based Acquisition Systems
M
U Data Logging Systems
M
U Wireless Sensors, Transmitters, & Receivers
M
U Signal Conditioners
M
U Data Acquisition Software
HEATERS
M
U Heating Cable
M
U Cartridge & Strip Heaters
M
U Immersion & Band Heaters
M
U Flexible Heaters
M
U Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
M
U Metering & Control Instrumentation
M
U Refractometers
M
U Pumps & Tubing
M
U Air, Soil & Water Monitors
M
U Industrial Water & Wastewater Treatment
M
U pH, Conductivity & Dissolved Oxygen Instruments
M1865/0917
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising