Omega | iLD24 Big Display SP Series | Owner Manual | Omega iLD24 Big Display SP Series Owner Manual

Omega iLD24 Big Display SP Series Owner Manual
FLOW CHART d
d
a
d
Below is a flowchart showing how to navigate through all
top level menus by pressing the d and a buttons.
d
a
a
d
_____Underline denotes factory default setup
a
a
a
a
a
a
a
SPECIFICATION
Accuracy:
0.03% rdg.
Resolution:
10 / 1 µV process
Linearization Points:
10 points
Temperature Stability:
50 ppm/°C process
Display:
4-digit, 7-segment LED,
57.2 mm (2.25") with red, green
and amber programmable colors.
Input Types:
Analog Voltage and Current
Voltage:
0 to 100 mV, 0 to 1 V (+100 mV),
0 to 10 Vdc
Input Impedance:
10 MΩ for 100 mV
1 MΩ for 1 or 10 Vdc
Current:
0 to 20 mA (5 Ω load)
Options: Communication
RS-232 / RS-485 or
Excitation 5Vdc @40mA,
10Vdc @60mA
Power Supply:
100-240 Vac ±10%, 50/60 Hz, 22.5 W
Operating Temperature: 0 to 40°C
Storage Temperature: -20 to 60°C
Relative Humidity: 0 to 85%
Protection:
NEMA-4x (IP65)
Dimensions:
289 L x 137 W x 73 D mm
(11.75” L x 5.375” W x 2.875” D)
Panel Cutout:
279.4 L x 116.8 W mm
(11.00” L x 4.60” W)
Weight:
1,360 g (3 lbs)
Approvals:
per EN61010-1
WARRANTY/DISCLAIMER
†
Where:
CALC/VALUE = Calculated input based on
the transducer specification
[Without Known Loads (DSBL)]
ACT/VALUE = Actual signal being received
[Known Loads (ENBL)]
READING CONFIGURATION SETUP
(operation example)
DISPLAY COLOR SETUP (examples)
Below is a flowchart showing how to navigate through the
submenus of the Reading Configuration menu item by
pressing the front buttons.
d
d
b
b
b
a
a
b
d
b
d
a
Display colors change sequences:
d
d
b
GREEN |
RED
|
AMBER
•-➤----------------•-----------------------•--------------------------------➤
0
AL2.H=200
AL1.H=400
d
•••
•••
d
d
Example 1:
Output 1 & Output 2: SSR
Alarm setup: Absolute, Above, Alarm 2 HI Value
"ALR.H" =200, Alarm 1 HI Value "ALR.H"=400
Color Display setup: Normal Color "N.CLR"=Green, Alarm 1
Color "1.CLR"=Amber, Alarm 2 Color "2.CLR"=Red
bc
b
d
b
d
d
d
bc
Example 2:
Output 1: Relay, Set Point 1 = 200,
Output 2: Relay, Set Point 2 = 200
Alarm 1 setup: Deviation, Band, "ALR.H" = 20
Alarm 2 setup: Deviation, Hi/Low, "ALR.H = 10", "ALR.L = 5"
Color Display setup: "N.CLR"=Green, "1.CLR"=Amber,
"2.CLR"=Red
Display colors change sequences:
d
•
•
bc
•
d
•
bc
d
d
•
d
•
•
d
AMBER | RED | GREEN | GREEN | RED | AMBER
•-➤--------•----------•--------------•--------------•----------•------------➤
0
180
195
200
210
220
bc
•
bc
d
OMEGA ENGINEERING, INC. warrants this unit to be free of defects
in materials and workmanship for a period of 61 months from
date of purchase. OMEGA’s WARRANTY adds an additional one (1)
month grace period to the normal five (5) year product warranty
to cover handling and shipping time. This ensures that OMEGA’s
customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized
Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it
will be repaired or replaced at no charge. OMEGA’s WARRANTY does
not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation
outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having
been tampered with or shows evidence of having been damaged as a
result of excessive corrosion; or current, heat, moisture or vibration;
improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear
is not warranted, include but are not limited to contact points, fuses,
and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any
damages that result from the use if its products in accordance
with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by
the company will be as specified and free of defects. OMEGA
MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF
ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT
THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING
ANY WARRANTY OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set
forth herein are exclusive, and the total liability of OMEGA
with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise,
shall not exceed the purchase price of the component upon
which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used,
nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC),
used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with
any nuclear installation or activity, medical application, used on humans,
or misused in any way, OMEGA assumes no responsibility as set forth
in our basic WARRANTY/DISCLAIMER language, and, additionally,
purchaser will indemnify OMEGA and hold OMEGA harmless from any
liability or damage whatsoever arising out of the use of the Product(s)
in such a manner.
iLD24 Big Display
Universal Strain &
Process Monitor
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA
Customer Service Department.
BEFORE RETURNING ANY
PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN
AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER
SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the
outside of the return package and on any correspondence.
FOR WARRANTY RETURNS,
please have the following
information available BEFORE
contacting OMEGA:
1. Purchase Order number
under which the product
was PURCHASED,
2. Model and serial number of the
product under warranty, and
3. Repair instructions and/or
specific problems relative
to the product.
FOR NON-WARRANTY REPAIRS,
consult OMEGA for current repair
charges. Have the following
information available BEFORE
contacting OMEGA:
1. Purchase Order number to cover
the COST of the repair or
calibration,
2. Model and serial number of the
product, and
3. Repair instructions and/or specific
problems relative to the product.
OMEGA’s policy is to make running changes, not model changes,
whenever an improvement is possible. This affords our customers
the latest in technology and engineering.
OMEGA is a trademark of OMEGA ENGINEERING, INC.
© Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved.
This document may not be copied, photocopied, reproduced,
translated, or reduced to any electronic medium or machine-readable
form, in whole or in part, without the prior written consent of OMEGA
ENGINEERING, INC.
MQS3718/0818
omega.com info@omega.com
Servicing North America:
U.S.A.
Omega Engineering, Inc.
Headquarters: Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660
Fax: (203) 359-7700
e-mail: info@omega.com
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but
OMEGA accepts no liability for any errors it contains, and reserves the right to
alter specifications without notice.
This Quick Start Reference provides information
on setting up your instrument for basic operation.
The latest complete Communication and Operational
Manual as well as free Software and ActiveX Controls
are available at www.omega.com or on the CD-ROM
enclosed with your shipment.
SAFETY CONSIDERATION
This device is marked with the international
Caution symbol.
The instrument is a panel mount device protected in
accordance with EN61010-1:2001. Remember that the unit
has no power-on switch. Building installation should include
a switch or circuit-breaker that must be compliant to IEC
947-1 and 947-3.
SAFETY:
• Do not exceed voltage rating on the label located on
the back of the instrument housing.
• Always disconnect power before changing signal and
power connections.
• Do not use this instrument on a work bench without
its case for safety reasons.
• Do not operate this instrument in flammable or
explosive atmospheres.
EMC:
• Whenever EMC is an issue, always use shielded cables.
• Never run signal and power wires in the same conduit.
• Use signal wire connections with twisted-pair cables.
• Install Ferrite Bead(s) on signal wire close to the
instrument if EMC problems persist.
MOUNTING
Mounting Big Display Through Panel:
1. Using the panel cutout diagram shown above, cut an
opening in the panel.
2. Remove six screws at the back of Big Display to remove
back cover.
3. Insert the unit into the opening from the front of the panel,
so the gasket seals between the bezel and the front of the
panel.
4. Align back cover to Big Display and reinstall screws.
Mounting Big Display on Bail:
1. Mark the location of mounting screws on the flat surface.
2. Be sure to leave enough room around the bail to allow for
removal and rotation of the display.
3. The display can be rotated for the best viewing angle.
Disassembly Instruction:
Warning: Disconnect all ac power from the unit
before proceeding.
1. Remove all wiring connections from the rear of the
instrument, by unscrewing the power and input connectors.
2. Remove six screws at the back of the display and back
cover.
3. Remove the Big Display from the panel.
4. To remove the Big Display from the bail, unscrew the
two knobs at each end of the mounting brackets.
CONFIGURATION
DISPLAY ABBREVIATIONS
MENU Mode:
Flashing display in MENU Mode means you can make your
selection by pressing b button. If the flashing display is not
a four digit value, pressing c button will always direct the
instrument one step backward of the top menu item. The
second push on the c button will reset the instrument
except after the setpoint and the alarms, that will go to the
RUN Mode without resetting the instrument. The a button
will always sequence the instrument thru the menu items.
SP1
Set Point 1 Value
CNFG Configuration Menu
INPt
Input Type (range)
The d button has two functions:
1. To save a selected flashing display
2. To direct the instrument to the next submenu level
RUN Mode:
b causes the display to flash the PEAK with the
corresponding value. Press again to go back to RUN
Mode.
c causes the display to flash VALLEY with the
corresponding value. Press again to go back to RUN
Mode.
d causes flashing PEAK or VALLEY to reset corresponding
values. Pressing d twice will cause the display to flash
STBY and put the instrument into standby, which disables
all outputs and alarms. Press d one more time to go
back to RUN Mode.
Button Functions in Configuration Mode
WIRING
•
a
Wire the instrument according to the Input Wiring
Connections described in your Operator’s Manual.
•
MENU
Warning: Do not connect ac power to your
device until you have completed all input and
output connections. This device must only be
installed by a specially trained electrician with
corresponding qualifications. Failure to follow
all instructions and warnings may result in injury!
•
•
b
PK/GRS
(UP)
•
•
•
•
AC
PWR
DC
PWR
TB1
TB2
1 2 3
LN
REMOTE
PROGRAMMER
TB3
1 2 1 2 3 4 5
+ -
COMMUNICATION
PJ3
1 3 5
2 4 6
OUTPUTS
INPUTS
TB4
TB5
TB9
1 2 3
1 2 3 4 5 6
1 2 3 4 5 6 7 8
123456
•
c
TARE
(DOWN)
•
Connect the main power connections as shown in the figure below.
•
•
POWER
d
•
ENTER
•
•
To enter the Menu, the user must first press a
button.
Use this button to advance/navigate to the next
menu item. The user can navigate through all the
top level menus by pressing a.
While a parameter is being modified, press a to
escape without saving the parameter.
Press the up b button to scroll through “flashing”
selections. When a numerical value is displayed
press this key to increase value of a parameter that
is currently being modified.
Holding the b button down for approximately
3 seconds will speed up the rate at which the
setpoint value is incremented.
In the Run Mode pressing b causes the display to
flash the PEAK or GROSS value – press again to
return to the Run Mode.
Press the down c button to go back to a previous
Top Level Menu item.
Press this button twice to reset the controller to the
Run Mode.
When a numerical value is flashing (except setpoint
value) press c to scroll digits from left to right
allowing the user to select the desired digit to
modify.
When a setpoint value is displayed press c to
decrease value of a setpoint that is currently being
modified. Holding the c button down for
approximately 3 seconds will speed up the rate at
which the setpoint value is decremented.
In the Run Mode pressing c causes the display to
flash TARE value to tare your reading (zeroing).
Press the enter d button to access the submenus
from a Top Level Menu item.
Press d to store a submenu selection or after
entering a value — the display will flash a STRD
message to confirm your selection.
To reset flashing PEAK or GROSS press d.
In the Run Mode, press d twice to enable
Standby Mode with flashing STBY.
Reset: Except for Alarms, modifying any settings of
the menu configuration will reset the meter prior to
resuming Run Mode.
0 - 1.0
0 - 20
Rtio
bUtN
GROS
RdG
dEC
LOAd
DSbL
0002..
..0010
0001..
..0128
IN 1
IN 2
....
IN 10
ALR1
_dEV
UNLt
N.o.
ActV
bELo
bANd
ALR.L
ALR.2
SP.dN
Id
FULL
COMM
C.PAR
PRtY
EVEN
dAtA
8.bit
1.bit
bus.F
_LF_
StNd
485_
CMd_
SEPR
_cR_
stAt
PEAk
UNit
tR.tM
COLR
1.CLR
REd
GRN
dSbL
ERRO
SP2
Set Point 2 Value
INPt
Input Type (Range)
0 - 0.1 100 mV Input
Voltage
0 - 10 10 V Input Voltage
1 V Input Voltage
20 mA Input Current
Ratiometric Operation RESO Display Resolution
Button Peak/Gross
PEAk Peak Value
Gross Value
Reading Configuration
Decimal Point
F.FFF Decimal Point
..FFFF Position
Input Load
EnbL Scaling with Known
Loads (Actual Value)
Scaling without Known L.PNt Linearization Points
Loads (Calculated Value)
Number of Linearization FLtR
Filter Constant
Points
Filter Constant Value IN.Rd Input/Reading Scale
and Offset Menu
Input 1
Rd 1
Reading 1
Input 2
Rd 2
Reading 2
......
....
......
Input 10
Rd 10 Reading 10
Alarm 1 Menu
AbSo Absolute Mode
Deviation Mode
LtcH
Latched Mode
Unlatched Mode
Ct.CL Contact Closure
Normally Open
N.c.
Normally Closed
Active Type
AboV Active Above
Active Below
Hi.Lo Above High/Below
Low
Above or Below Band A.P.oN AlarmEnable/Disable
at Power On
Alarm Low Value
ALR.H Alarm High Value
Alarm 2 Menu
Set Point Deviation
ID Code Menu
CH.Id Change ID Code
Full ID
SP.Id Set Point ID
Communication Option* NONE Communication is
Not Installed
Communication
bAUd Baud Rate
Parameters
Parity
odd_ Odd
Even
_No_ No
Data Bit
7.bit
7 Data Bit
8 Data Bit
StOP Stop Bit
1 Data Bit
2.bit
2 Stop Bit
Bus Format
M.bus Modbus Protocol
Line Feed
ECHO Echo
Communication
232C RS-232
Standard
RS-485
ModE Data Flow Mode
Command Mode
CoNt Continuous Mode
Data Separation
SPCE Space
Character
Carriage Return
dAt.F Data Format
Alarm Status
RdNG Transmit Reading
Value
Transmit Peak Value GROS Transmit Gross Value
Units of Measurement AddR Multipoint Address
Transmit Color Selection
Display Color Selection N.CLR Normal Color Display
Alarm 1 Color Display 2.CLR Alarm2 Color Display
Display Color is Red AMbR Display Color is Amber
Display Color is Green
Disable
ENbL Enable
Error
+ OL
Input (+) Overload
* For abbreviations of Communication Option see Communication Manual.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising