Omega | iLD24-UTP, iLD44-UTP Series Monitor | Owner Manual | Omega iLD24-UTP, iLD44-UTP Series Monitor Owner Manual

Omega iLD24-UTP, iLD44-UTP Series Monitor Owner Manual
User’s Guide
Shop online at
omega.com
e-mail: info@omega.com
For latest product manuals:
www.omegamanual.info
ILD24-UTP, ILD44-UTP BIG DISPLAY
Universal Temperature & Process
Monitor Manual
omega.com info@omega.com
U.S.A.
Headquarters:
Servicing North America:
Omega Engineering, Inc.
Toll-Free: 1-800-826-6342 (USA & Canada only)
Customer Service: 1-800-622-2378 (USA & Canada only)
Engineering Service: 1-800-872-9436 (USA & Canada only)
Tel: (203) 359-1660
Fax: (203) 359-7700
e-mail: info@omega.com
For Other Locations Visit omega.com/worldwide
The information contained in this document is believed to be correct, but OMEGA accepts no liability for any errors it contains, and reserves
the right to alter specifications without notice.
TABLE OF CONTENTS
Part 1: Introduction............................................................................................2
1.1
Description .................................................................................2
1.2
Safety Considerations ...............................................................3
1.3
Before You Begin .......................................................................4
Part 2: Setup.......................................................................................................5
2.1
Mounting .....................................................................................5
2.2
Rear Panel Connections............................................................7
2.3
Electrical Installation .................................................................8
2.3.1 Power Connections........................................................8
2.3.2 Thermocouple - Input Connection................................9
2.3.3 Two / Three / Four Wire RTD-Hookups .......................10
2.3.4 Process Current - Wiring Hookup...............................11
2.3.5 Process Voltage - Wiring Hookup ...............................11
2.3.6 Communication Output - Wiring Hookup...................12
Part 3: Operation: Configuration Mode .........................................................13
3.1
Introduction ..............................................................................13
Turning your Instrument On for the First Time
Buttons Functions in Configuration Mode
3.2
Menu Configuration ................................................................14
3.2.1 ID Number .....................................................................15
3.2.2 Setpoints .......................................................................16
3.2.3 Configuration Menu ....................................................17
3.2.4 Input Type Menu ...........................................................17
Input Type (Thermocouple) ........................................18
Input Type (RTD)...........................................................19
Input Type (Process) ...................................................20
3.2.5 Reading Configuration Menu .....................................20
3.2.6 Alarm 1 Menu ...............................................................24
3.2.7 Alarm 2 Menu................................................................28
3.2.8 Reading Adjust Menu...................................................29
3.2.9 Setpoint Deviation Menu / Field Calibration ..............30
3.2.10 ID Code Menu ...............................................................31
3.2.11 Communication (Options) Menu.................................33
3.2.12 Display Color Selection Menu.....................................39
Part 4: Specifications ......................................................................................42
Part 5: Factory Preset Values .........................................................................45
APPROVAL INFORMATION .............................................................................46
i
LIST OF FIGURES:
Figure 2.1
Figure 2.2
Figure 2.3
Figure 2.4
Figure 2.5
Figure 2.6
Figure 2.7
Figure 2.8
Figure 2.9
Figure 2.10
Figure 3.1
Figure 3.2
Figure 3.3
Figure 3.4
Figure 3.5
Figure 3.6
Figure 3.7
Figure 3.8
Figure 3.9
Figure 3.10
Figure 3.11
Mounting ...............................................................................................5
Rear Panel Power Connector Labels..................................................7
Rear Panel Input Connector Labels....................................................7
Main Power Connections.....................................................................8
Inside Cover Rear View........................................................................8
Thermocouple Wiring Hookup ............................................................9
Two/Three/Four-wire RTD
a) RTD-1000 ohm and 500 ohm Wiring Hookup ............................10
b) RTD-100 ohm Wiring Hookup .....................................................10
Process Current Wiring Hookup
(Internal and External Excitation)......................................................11
Process Voltage Wiring Hookup
a) Without Sensor Excitation ..........................................................11
b) With Sensor Excitation ................................................................11
Communication Output:
a) RS-232 Output – Wiring Hookup ................................................12
b) RS-485 Output – Wiring Hookup ................................................12
Flow Chart for ID and Setpoints........................................................14
Flow Chart for Configuration Menu ..................................................17
Flow Chart for Input Type Menu........................................................17
Flow Chart for Reading Configuration .............................................20
Flow Chart for Alarm 1 .......................................................................24
Flow Chart for Alarm 2 .......................................................................28
Flow Chart for Reading Adjust Menu ...............................................29
Flow Chart for Setpoint Deviation Menu / Field Calibration ...........30
Flow Chart for ID Code.......................................................................31
Flow Chart for Communication Option ............................................33
Flow Chart for Display Color Selection ............................................39
LIST OF TABLES:
Table 2.1
Table 2.2
Table 2.3
Table 3.1
Table 3.2
Table 4.1
Table 5.1
Front Panel Annunciators....................................................................6
Rear Panel Connector ..........................................................................7
TC Wire Color Chart .............................................................................9
Button Function in Configuration Mode...........................................13
Conversion Table................................................................................23
Input Properties ..................................................................................44
Factory Preset Values ........................................................................45
ii
NOTES, WARNINGS and CAUTIONS
Information that is especially important to note is identified by following labels:
• NOTE
• WARNING or CAUTION
• IMPORTANT
• TIP
NOTE: Provides you with information that is important to successfully
setup and use the Programmable Digital Meter.
CAUTION or WARNING: Tells you about the risk of electrical shock.
CAUTION, WARNING or IMPORTANT: Tells you of circumstances or
practices that can effect the instrument’s functionality and must refer
to accompanying documents.
TIP: Provides you helpful hints.
1
PART 1
INTRODUCTION
1.1 Description
This device can be purchased as monitor (read process value only) or as
a controller.
•
The iLD Big Display monitor offers unparalleled flexibility in process
measurement. Each unit allows the user to select the input type, from
10 thermocouple types (J, K, T, E, R, S, B, C, N and J DIN), Pt RTDs (100,
500 or 1000 Ω, with either 385 or 392 curve), DC voltage, or DC current.
The voltage/current inputs are fully scalable to virtually all engineering units,
with selectable decimal point, perfect for use with pressure, flow or other
process input.
•
The iLD Big Display device features a large, three color programmable
display with capability to change a color every time the Alarm is triggered.
Options include programmable RS-232 or RS-485 serial communication and
excitation. Universal power supply accepts 100 to 240 Vac.
2
1.2 Safety Considerations
This device is marked with the international caution symbol. It is important
to read this manual before installing or commissioning this device as it
contains important information relating to Safety and EMC
(Electromagnetic Compatibility).
This instrument is a panel mount device protected in accordance with
EN 61010-1:2001, electrical safety requirements for electrical equipment
for measurement, control and laboratory. Installation of this instrument
should be done by qualified personnel. In order to ensure safe operation,
the following instructions should be followed.
This instrument has no power-on switch. An external switch or circuitbreaker shall be included in the building installation as a disconnecting
device. It shall be marked to indicate this function, and it shall be in close
proximity to the equipment within easy reach of the operator. The switch or
circuit-breaker shall meet the relevant requirements of IEC 947–1 and
IEC 947-3 (International Electrotechnical Commission). The switch shall
not be incorporated in the main supply cord.
Furthermore, to provide protection against excessive energy being drawn
from the main supply in case of a fault in the equipment, an overcurrent
protection device shall be installed.
•
•
•
•
•
•
•
Do not exceed voltage rating on the label located on the top of the
instrument housing.
Always disconnect power before changing signal and power
connections.
Do not use this instrument on a work bench without its case for safety
reasons.
Do not operate this instrument in flammable or explosive atmospheres.
Do not expose this instrument to rain or moisture.
Unit mounting should allow for adequate ventilation to ensure
instrument does not exceed operating temperature rating.
Use electrical wires with adequate size to handle mechanical strain
and power requirements. Install without exposing bare wire outside the
connector to minimize electrical shock hazards.
EMC Considerations
•
•
•
•
Whenever EMC is an issue, always use shielded cables.
Never run signal and power wires in the same conduit.
Use signal wire connections with twisted-pair cables.
Install Ferrite Bead(s) on signal wires close to the instrument if EMC
problems persist.
Failure to follow all instructions and warnings may result in injury!
3
1.3 Before You Begin
Inspecting Your Shipment:
Remove the packing slip and verify that you have received everything
listed. Inspect the container and equipment for signs of damage as soon
as you receive the shipment. Note any evidence of rough handling in
transit. Immediately report any damage to the shipping agent. The carrier
will not honor damage claims unless all shipping material is saved for
inspection. After examining and removing the contents, save the packing
material and carton in the event reshipment is necessary.
Customer Service:
If you need assistance, please call the nearest Customer Service
Department, listed in this manual.
Manuals, Software:
The latest Operation and Communication Manual as well as free
configuration software and ActiveX controls are available from the
website listed in this manual or on the CD-ROM enclosed with your
shipment.
For first-time users: Refer to the QuickStart Manual for basic operation
and set-up instructions.
If you have the Serial Communications/Ethernet Option you can easily
configure the controller on your computer or on-line.
To Disable Outputs:
Standby Mode is useful during setup of the instrument or when
maintenance of the system is necessary. When the instrument is in
standby, it remains in the ready condition but all outputs are disabled.
This allows the system to remain powered and ready to go.
When the instrument is in "RUN" Mode, push d twice to disable all
outputs and alarms. It is now in "STANDBY" Mode. Push d once more
to resume "RUN" Mode.
PUSH d TWICE to disable the system during an EMERGENCY.
To Reset the Meter:
When the controller is in the "MENU" Mode, push c once to direct
controller one step backward of the top menu item.
Push c twice to reset controller, prior to resuming "Run" Mode except
after "Alarms", that will go to the "Run" Mode without resetting the
controller.
4
PART 2
SETUP
2.1 Mounting
Figure 2.1 Mounting
5
Mounting iLD Big Display Through Panel:
1. Using the panel cutout diagram shown in your Quick Start manual, cut
an opening in the panel.
2. Remove six (or eight) screws at the back of iLD Big Display to remove
back cover.
3. Insert the unit into the opening from the front of the panel so the gasket
seals between the bezel and the front of the panel.
4. Pass all wiring through customer drilled holes in back cover and
connect wiring to terminal blocks.
5. Align back cover to iLD Big Display and reinstall screws.
Mounting iLD Big Display on Bail:
1. Remove six (or eight) screws at the back of iLD Big Display to remove
back cover.
2. Pass all wiring through customer drilled holes in back cover and
connect wiring to terminal blocks.
3. Align back cover to iLD Big Display and reinstall screws.
4. Mark the location of mounting screws on the flat surface.
5. Be sure to leave enough room around the bail to allow for removal and
rotation of the display.
6. The display can be rotated for the best viewing angle.
Table 2.1 Front Panel Annunciators
1
2
°C
°F
a
b
c
d
Output 1/Setpoint 1/ Alarm 1 indicator
Output 2/Setpoint 2/ Alarm 2 indicator
°C unit indicator
°F unit indicator
Changes display to Configuration Mode
and advances through menu items*
Used in Program Mode and Peak Recall*
Used in Program Mode and Valley Recall*
Accesses submenus in Configuration Mode
and stores selected values*
* See Part 3 Operation: Configuration Mode
6
2.2 Rear Panel Connections
The rear panel connections are shown in Figures 2.2 and 2.3.
1
2
3
Figure 2.2 Rear Panel Power Connections
Figure 2.3 Rear Panel Input Connections
Table 2.2 Rear Panel Connector
POWER
INPUT
OPTION
AC Power Connector: All models
Input Connector: TB7 & TB8 for TC models
TB9 for PR (Process) & RTD models
Based on one of the following models:
RS-232C or RS-485
7
2.3 Electrical Installation
2.3.1 Power Connections
Caution: Do not connect power to your device until you have completed all
input and output connections. Failure to do so may result in injury!
Connect the main power connections as shown in Figure 2.4.
1
2
3
Figure 2.4 Main Power Connections
DC REMOTE
AC
PWR PWR PROGRAMMER
TB1 TB2
1 2 3
LN
TB3
COMMUNICATION
PJ3
1 2 1 2 3 4 5
+ -
1 3 5
2 4 6
OUTPUTS
T/C INPUT
TB5
TB7 TB8
1 2 3 4 5 6
+ -
TB4
1 2 3
1 2 3 4 5 6 RTN Rx Tx
OUTPUT2 OUTPUT1
TB5A
TB5B TB5C
1 2
3 4 5 6
OUTPUT2
OUTPUT1
iLD24 OUTPUTS
Figure 2.5 Inside Cover Rear View
8
INPUTS
TB9
1 2 3 4 5 6 7 8
2.3.2 Thermocouple
The figure below shows the wiring hookup for any thermocouple type. For
example, for Type K hookup, connect the yellow wire to the TB7 terminal and the
red wire to the TB8 terminal.
When configuring your controller, select Thermocouple and Thermocouple
Type in the Input Type menu (see Part 3).
Figure 2.6 Thermocouple Wiring Hookup
Table 2.3 TC Wire Color Chart
TYPE
J
K
T
E
N
R
S
B
Input Connector
Jacket (external insulation)
Terminal 8 (-) Terminal 7 (+)
Extension
Grade
Red
White
dark-Brown
Black
Red
Yellow
dark-Brown
Yellow
Red
Blue
dark-Brown
Blue
Red
Purple
dark-Brown
Purple
Red
Orange
dark-Brown
Brown
Red
Black
Green
Red
Black
Green
Red
Gray
Black
9
2.3.3 Two/Three/Four-Wire RTD
The figures below show the input connections and input connector jumpers
(shown in bold lines) required to hookup a 2-, 3- or 4-wire RTD.
Figure 2.7
a) RTD-1000 ohm and 500 ohm
Wiring Hookup
b) RTD-100 ohm Wiring Hookup
The two-wire connection is simplest method, but does not compensate for
lead-wire temperature change and often requires calibration to cancel lead-wire
resistance offset.
The three-wire connection works best with RTD leads closely equal in
resistance. The device measures the RTD, plus upper and lower lead drop
voltage and the subtracts twice the measured drop in the lower supply current
lead producing excellent lead-resistance cancellation for balanced
measurements.
The four-wire RTD hookup is applicable to unbalanced lead resistance and
enables the device to measure and subtract the lead voltage, which produces
the best lead-resistance cancellation.
When configuring your controller, select RTD type and RTD value in the
Input Type menu (see Part 3).
If the input wires of the meter get disconnected or broken, it will display
+OPN “Input (+) Open” message except in case of 500/1000 Ω 2-wire
RTD. In this case the display shows -OPN “Input (-) Open” message. For
safety purpose you may want to set up your alarm to be triggered when
input is open. See Alarm 1 & 2 chapters for details.
10
2.3.4 Process Current
The figure below shows the wiring hookup for Process Current 0 – 20 mA.
Figure 2.8 Process Current Wiring Hookup
(Internal and External Excitation)
When configuring your instrument, select Process Type in the Input Type Menu (see Part 3).
2.3.5 Process Voltage
The figure below shows the wiring hookup for Process Voltage 0 – 100 mV,
0 – 1 V, 0 – 10 V.
Figure 2.9
a) Process Voltage Wiring Hookup b) Process Voltage Wiring Hookup
with Sensor Excitation
without Sensor Excitation
RL - Voltage limiting resistor, which allows conversion of the 24 Vdc internal excitation voltage to
the appropriate process input value. For instance: if the potentiometer value is equal to 10 kΩ, the
minimum RL is 14 kΩ for 10 V process input.
When configuring your instrument, select Process Type in the Input Type Menu (see Part 3).
11
2.3.6 Communication Output
This device may have a programmable communication output. The RS-232 and
RS-485 Output Connection are shown below.
1
1
Figure 2.10
a) RS-232 Output Wiring Hookup b) RS-485 Output Wiring Hookup
12
PART 3
OPERATION: Configuration Mode
3.1 Introduction
The instrument has two different modes of operation. The first, Run Mode, is
used to display values for the Process Variable, and to display or clear Peak
and Valley values. The other mode, Menu Configuration Mode, is used to
navigate through the menu options and configure the controller. Part 3 of this
manual will explain the Menu Configuration Mode. For your instrument to
operate properly, the user must first "program" or configure the menu options.
Turning your Controller On for the First Time
The device becomes active as soon as it is connected to a power source. It
has no On or Off switch. The device at first momentarily shows the software
version number, followed by reset RST, and then proceeds to the Run Mode.
Table 3.1 Button Function in Configuration Mode
• To enter the Menu, the user must first press a button.
• Use this button to advance/navigate to the next menu item. The user can
a
navigate through all the top level menus by pressing a.
MENU
• While a parameter is being modified, press a to escape without saving
the parameter.
• Press the up b button to scroll through “flashing” selections. When a
numerical value is displayed press this key to increase value of a
parameter that is currently being modified.
b
• Holding the b button down for approximately 3 seconds will speed up the
(UP)
rate at which the set point value increments.
• In the Run Mode press b causes the display to flash the PEAK value –
press again to return to the Run Mode.
• Press the down c button to go back to a previous Top Level Menu item.
• Press this button twice to reset the controller to the Run Mode.
• When a numerical value is flashing (except set point value) press c to
scroll digits from left to right allowing the user to select the desired digit to
modify.
c
• When a setpoint value is displayed press c to decrease value of a
(DOWN)
setpoint that is currently being modified. Holding the c button down for
approximately 3 seconds will speed up the rate at which the setpoint
value is decremented.
• In the Run Mode press c causes the display to flash the VALLEY value –
press again to return to the Run Mode.
• Press the enter d button to access the submenus from a Top Level
Menu item.
• Press d to store a submenu selection or after entering a value — the
d
ENTER
display will flash a STRD message to confirm your selection.
• To reset flashing Peak or Valley press d.
• In the Run Mode, press d twice to enable Standby Mode with
flashing STBY.
Reset: Except for Alarms, modifying any settings of the menu configuration
will reset the instrument prior to resuming Run Mode.
13
3.2 Menu Configuration
It is recommended that you put the controller in the Standby Mode for
any configuration change other than Setpoints & Alarms.
Figure 3.1 Flow Chart for ID and Setpoints
14
3.2.1 ID Number
SEE ID MENU SELECTION IN CONFIGURATION SECTION FOR
ENABLE/DISABLE OR CHANGE ID CODE.
If ID Code is Disabled or set as Default (0000) the menu will skip ID step
to Setpoint Menu.
If ID Code is set to Full Security Level and user attempts to enter the
Main Menu, they will be prompted for an ID Code.
If ID Code is set to Setpoint/ID Security Level and user attempts to enter
the Configuration Menu, they will be prompted for an ID Code.
ENTERING YOUR NON-DEFAULT FULL SECURITY ID NUMBER.
Press a
1) Display shows ID.
Press d
2) Display advances to ____.
Press b & c 3) Press b to increase digit 0-9. Press c to activate next digit
(flashing). Continue to use b and c to enter your 4-digit ID
code.
Press d
4) If the correct ID code is entered, the menu will advance to the
Setpoint 1 Menu, otherwise an error message ERRo will be
displayed and the instrument will return to the Run Mode.
To change ID Code, see ID Menu in the Configuration section.
ENTERING YOUR NON-DEFAULT SETPOINT/ID SECURITY ID NUMBER.
Press
Press
Press
Press
Press
Press
a
a
a
d
b&c
d
5) Display shows SP1 Setpoint 1 Menu.
6) Display shows SP2 Setpoint 2 Menu.
7) Display shows ID ID Code Menu.
8) Display advances to ____.
9) Use b and c to change your ID Code.
10) If correct ID Code is entered, the display will advance to the
INPT Input Menu, otherwise the error message ERRo will be
displayed and the controller will return to the Run Mode.
To prevent unauthorized tampering with the setup parameters, the
instrument provides protection by requiring the user to enter the ID Code
before allowing access to subsequent menus. If the ID Code entered
does not match the ID Code stored, the controller responds with an error
message and access to subsequent menus will be denied.
Use numbers that are easy for you to remember. If the ID Code is
forgotten or lost, call customer service with your serial number to access
and reset the default to 0000.
15
3.2.2 Set Points
SETPOINT 1:
Press a
1) Press a, if necessary until SP1 prompt appears.
Press d
2) Display shows previous value of “Setpoint 1”.
Press b & c 3) Press b and c to increase or decrease Setpoint 1
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up the
rate at which the Setpoint value increments or decrements.
Press b & c 4) Continue to use b and c to enter your 4-digit Setpoint 1 value.
Press d
5) Display shows STRD stored message momentarily and then
advances to SP2 only, if a change was made, otherwise press
a to advance to SP2 Setpoint 2 Menu.
SETPOINT 2:
Press d
6) Display shows previous value of “Setpoint 2”.
Press b & c 7) Press b and c to increase or decrease Setpoint 2
respectively.
Holding b & c buttons down for approximately 3 seconds will speed up
the rate at which the setpoint value increments or decrements.
Press d
8) Display shows STRD stored message momentarily and then
advances to CNFG only, if a change was made, otherwise press
a to advance to CNFG Configuration Menu.
16
3.2.3 Configuration Menu
Figure 3.2 Flow Chart for Configuration Menu
Enter Configuration Menu:
Press a
Press d
Press a
1) Press a, if necessary, until CNFG prompt appear.
2) Display advances to INPT Input Menu.
3) Pressing and releasing a to scroll through all available
menus of Configuration section.
3.2.4 Input Type Menu
Figure 3.3 Flow Chart for Input Type Menu
17
Input Type (Thermocouple)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is T.ç, press a to skip to
step 6 (T.ç stops flashing).
THERMOCOUPLE SUBMENU:
Press b
Press d
Press d
Press b
Press d
4) Scroll through the available selection to T.ç (flashing).
5) Display shows STRD stored message momentarily and then
T.ç (not flashing).
6) Display flashes previous thermocouple type selection. i.e. J
(see below for types).
7) Scroll through the available thermocouple types to the
selection of your choice.
8) Display shows STRD stored message momentarily and then
advances to the RDG Reading Configuration Menu.
Use the Input Type (Thermocouple) (RTD) or (Process) and verify your
Electrical Installation (see section 2.3).
Thermocouple Types: J, K, T, E, N, DIN J, R, S, B, C
Display:
J K T E N DNJ R S B C
18
Input Type (RTD)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is RTD, press a to skip to
step 6 (RTD stops flashing).
RTD SUBMENU:
Press b
Press d
Press d
Press b
Press d
4) Scroll through the available selection to RTD (flashing).
5) Display shows STRD stored message momentarily and then
RTD (not flashing).
6) Display flashes previous RTD type selection i.e. 392.2
(see below for RTD types selection).
7) Scroll through the available RTD types to the selection of
your choice.
8) Display shows STRD stored message momentarily and then
advances to RTD RTD value.
RTD Types: 392
385
Two, Three or Four-wire
Display:
392.2, 392.3, 392.4, 385.2, 385.3, 385.4
Last digit indicates: 2-, 3- or 4-wire input.
RTD VALUE SUBMENU:
Press d
Press b
Press d
9) Display flashes previous RTD value selection i.e. 100_
(see below for RTD value selection).
10) Scroll through the available RTD values to the selection of
your choice.
11) Display shows STRD stored message momentarily and then
advances to RDG Reading Configuration Menu.
RTD Values: 100 ohm
Display:
100_
500 ohm
500_
1000 ohm
1000
19
Input Type (Process)
ENTER INPUT TYPE MENU:
Press a
Press d
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display flashes T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is PROC, press a to skip to
step 6 (PROC stops flashing).
PROCESS SUBMENU:
Press b
Press d
Press d
Press b
Press d
4) Scroll through the available selection to PROC (flashing).
5) Display shows STRD stored message momentarily and then
PROC (not flashing).
6) Display flashes previous Process type selection. i.e. 0-10
(see below for Process types selection).
7) Scroll through the available Process types to the selection of
your choice.
8) Display shows STRD stored message and then advances to
RDG Reading Configuration Menu.
Process Types: 100 mV 1 V
Display:
0-0.1 0-1.0
10 V
0-10
0 – 20 mA
0-20
For 4-20 mA Input select 0-20 mA then adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under INPUT/READING submenu. The
factory preset value is 4-20 mA.
3.2.5 Reading Configuration
Figure 3.4 Flow Chart for Reading Configuration Menu
20
ENTER READING CONFIGURATION MENU:
Press a
Press d
Press a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Display advances to RDG Reading Configuration Menu.
4) Display advances to DEC Decimal Point.
DECIMAL POINT SUBMENU:
Press d
Press b
Press d
5) Display flashes previous selection for Decimal location.
6) Scroll though the available selections and choose Decimal
location: FFFF or FFF.F (also FF.FF and F.FFF — if PROC
Process type was selected in the Input Type Menu).
7) Display shows STRD stored message momentarily and then
advances to TEMP Temperature Unit.
Decimal Point for Process Input Type is passive.
TEMPERATURE UNIT SUBMENU:
Press d
Press b
Press d
8) Display flashes previous Temperature Unit selection.
9) Scroll though the available selections to the Temperature Unit
of your choice: °F or °C.
10) Display shows STRD stored message momentarily and then
advances to FLTR Filter Constant.
FILTER CONSTANT SUBMENU:
Press d
Press b
Press d
11) Display flashes previous selection for Filter Constant.
12) Scroll though the available selections:
0001, 0002, 0004, 0008, 0016, 0032, 0064, 0128
13) Display shows STRD stored message momentarily only, if
change was made, otherwise press a to advance to the next
menu.
If Process was selected in the Input Type Menu the display will
advance to IN.RD Input/Reading Submenu, otherwise the
display advances to the ALR1 Alarm 1 Menu.
The Filter Constant Submenu allows the user to specify the
number of readings stored in the Digital Averaging Filter.
For PID control select filter value 0001-0004. A filter value of 2 is
approximately equal to 1 second RC low pass time constant.
21
Reading Configuration (If Process was selected)
INPUT/READING (SCALE AND OFFSET) SUBMENU:
Input Voltage or Current can be converted or scaled into values appropriate for
the process or signal being measured. So, a reading may be displayed, for
example, in units of weight or velocity instead of in amperes or volts.
The instrument determines Scale and Offset values based on two user-provided
input values entered with the corresponding readings. Note that “In1” Input 1 and
“In2” Input 2 are represented and entered as a product of the input
voltage/current and the conversion number from the Table 3.1.
The following instructions include details for a specific scenario in which a
4-20 mA input (in the 20 mA Process Mode) is to be represented as a
measurement of 0-100 percent.
14) Press d at the IN.RD prompt. Display shows IN1 Input 1
submenu.
Press d
15) Display shows Input 1 value with 1st digit flashing.
Press b & c 16) Use b and c buttons to enter IN1 value.
The IN1 value = min. input value * conversion number.
Press d
Disregard the position of the decimal point, such that 2000
counts may actually appear as “200.0”, “20.00”, or “2.000”.
Example: 4 mA as 4(mA) x 500 = 2000.
Press d
17) Display advances to RD1 Reading 1 Submenu.
Press b & c 18) Use b and c buttons to enter RD1 value.
This value represents IN1 in terms of some meaningful
engineering units. To show the 4 mA as zero percent enter RD1
value = 0000.
Example: RD1 value = 0000.
Press d
19) Display IN!2 Input 2 Submenu.
Press d
20) Display shows Input 2 value with 1st digit flashing.
The IN!2 value = max. input value * conversion number.
Example: 20(mA) x 500 = 10000 (9999).
Press b & c 21) Use b and c buttons to enter IN!2 value.
Press d
22) Display advances to RD!2 Reading 2 Submenu.
Press b & c 23) Use b and c buttons to enter RD!2 value.
Example: RD!2 value = 0100.
Press d
24) Display flashes STRD stored message momentarily and
then advances to ALR1 only, if change was made, otherwise
press d to advance to ALR1 Alarm 1 Menu.
22
Conversion number is a coefficient of conversion between input values
and real full display range (10000 counts, shown as 9999). See Table 3.2
below for proper conversion number.
Table 3.2 Conversion Table
RANGE
100 mV
1V
10 V
0 -20 mA
Example
0-1V
In 1
Rd 1
Inp 2
Rd 2
CONVERSION NUMBER
10000 / (100 x 1) = 100
10000 / (1000 x 1) = 10
10000 / (1000 x 10) = 1
10000 / (20 x 1) = 500
=
=
=
=
=
=
0 - 100.0
0
0
9999
100.0
23
3.2.6 Alarm 1
Figure 3.5 Flow Chart for Alarm 1
ENTER ALARM 1 MENU:
Press a
Press d
Press a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to ALR1 Alarm 1
Menu.
4) Display advances to Alarm 1 ENBL Enable or DSBL Disable
Submenu and flashes the previous selection.
24
ALARM 1 ENABLE/DISABLE SUBMENU:
Press b
Press d
5) Scroll though the available selection until ENBL displays to
use Alarm 1.
6) Display shows STRD stored message momentarily and then
advances to ABSo only if it was changed, otherwise press a to
advance to ABSo Alarm 1 Absolute/Deviation Submenu.
If DSBL Alarm 1 Disabled was selected, all submenus of Alarm
1 Menu will be skipped and meter advances to ALR2 Alarm 2
Menu. If ENBL Alarm 1 Enabled was selected, Output 1 would
be automatically Disabled, and reassigned as Alarm 1.
ALARM 1 ABSOLUTE/DEVIATION SUBMENU:
Press d
Press d
7) Display flashes previous selection. Press b to ABSo
Absolute or _DEV Deviation.
8) Display shows STRD stored message momentarily and then
advances to LTçH only if it was changed, otherwise press a to
advance to LTçH Alarm 1 Latch/Unlatch Submenu.
Absolute Mode allows Alarm 1 to function independently from Setpoint 1. If the
process being monitored does not change often, then "Absolute" Mode is
recommended.
Deviation Mode allows changes to Setpoint 1 to be made automatically to
Alarm 1. Deviation mode is typically the ideal mode if the process temperature
changes often. In Deviation Mode, set Alarm 1 a certain number of degrees or
counts away from Setpoint 1 — this relation remains fixed even if Setpoint 1 is
changed.
ALARM 1 LATCH/UNLATCH SUBMENU:
Press d
Press d
9) Display flashes previous selection. Press b to LTçH
Latched or UNLT Unlatched.
10) Display shows STRD stored message momentarily and then
advances to CT.CL only, if it was changed, otherwise press a to
advance to CT.CL Contact Closure Submenu.
Latched Mode: Relay remains "latched" until reset. To reset already latched
alarm, select Alarm Latch and press Max twice (i.e. Unlatch and then back to
Latch) or from a Run Mode, push d twice to put the controller in Standby Mode
and then push d one more time to return to the Run Mode.
Unlatched Mode: Relay remains latched only as long as the alarm condition is
true.
25
ACTIVE SUBMENU:
Press d
Press d
11) Display flashes previous selection. Press b to scroll through
the available selections: ABoV Above, BELo Below, HI.Lo
HI/Low and BAND Band. (Band is active if _DEV Deviation was
selected).
12) Display shows STRD stored message momentarily and then
advances to A.P.oN only if it was changed, otherwise press a to
advance to A.P.oN Alarm Enable/Disable at Power On Submenu.
Above: Alarm 1 condition triggered when the process variable is greater than the
Alarm Hi Value (Low value ignored).
Below: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value (Hi value ignored).
Hi/Low: Alarm 1 condition triggered when the process variable is less than the
Alarm Low Value or above the Hi Value.
Band: Alarm 1 condition triggered when the process variable is above or below
the "band" set around Setpoint 1. Band equals Hi Value (Low Value ignored). A
"band" is set around the Setpoint by the instrument only in the "Deviation" Mode.
26
ALARM ENABLE/DISABLE AT POWER ON:
Press d
Press d
15) Display flashes previous selection. Press b to ENBL enable
or DSBL disable.
16) Display shows STRD stored message. momentarily and then
advances to ALR.L only if it was changed, otherwise press a to
advance to the ALR.L Alarm 1 Low Value Submenu.
If the alarm is enabled at Power On, the alarm will be active right after
reset. If the alarm is disabled at Power On, the alarm will become
enabled when the process value enters the non alarm area. The alarm is
not active while the process value is approaching Setpoint 1.
ALARM 1 LOW VALUE SUBMENU:
17) Display flashes 1st digit of previous value. Use b and c to
enter new value.
Press b & c 18) Use b and c to enter Alarm 1 Low Value.
Press d
19) Display shows STRD storage message momentarily and
then advances to ALR.H only, if it was changed, otherwise press
a to advance to ALR.H Alarm 1 Hi Value Submenu.
Press d
ALARM 1 HI VALUE SUBMENU:
20) Display flashes 1st digit of previous value. Use b and c to
enter new value.
Press b & c 21) Use b and c to enter Alarm1 Hi Value.
Press d
22) Display shows STRD stored message momentarily and then
advances to the next menu only, if it was changed, otherwise
press a to advance to the next menu.
Press d
27
3.2.7 Alarm 2
Figure 3.6 Flow Chart for Alarm 2
ENTER ALARM 2 MENU:
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to ALR2 Alarm 2
Menu.
Press d
4) Display advances to Alarm 2 ENBL Enable or DSBL Disable
Submenu.
ALARM 2 ENABLE/DISABLE SUBMENU:
Press a
Press d
Press a
Press d
Press d
5) Display flashes previous selection. Press b until ENBL
displays to use Alarm 2.
6) Display shows STRD stored message momentarily and then
advances to ABSo only if it was changed, otherwise press a to
advance to ABSo Absolute/Deviation Submenu.
If DSBL Alarm 2 Disabled was selected, all submenus of Alarm 2
will be skipped and meter advances to R.ADJ Cold Junction
(C.J.) Reading Adjust Menu.
The remaining Alarm 2 menu items are identical to Alarm 1
Menu. Modifying Alarm Settings will not reset the instrument.
28
3.2.8 Reading Adjust Menu
For Temperature
Reading only,
not Process
Figure 3.7 Flow Chart for Reading Adjust Menu
ENTER READING ADJUST MENU:
Press a
Press d
Press a
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to R.ADJ
Reading Adjust Menu.
READING ADJUST VALUE SUBMENU:
Press d
4) Display flashes 1st digit of previous Reading Adjust value.
Press b & c 5) Press b and c buttons to enter a new Reading Adjust value
(-1999 to 9999).
Press d
6) Display shows STRD stored message momentarily and then
advances to SP.DV Setpoint Deviation Menu.
Reading Offset Adjust allows the user to fine tune a minor error of the transducer,
however some applications may require a large offset adjust. (Displayed Process
Value = Measured Process Value ±R.ADJ). Reading Adjust value is adjustable
between -1999 to 9999.
29
3.2.9 Setpoint Deviation Menu /
Field Calibration
ENTER SETPOINT DEVIATION MENU:
Press a
1) Press a, if necessary,
until CNFG prompt appears.
Press d
2) Display advances to
INPT Input Menu.
Press a
3) Press a, if necessary,
until Display advances to
SP.DV Setpoint Deviation
Menu.
Figure 3.8 Flow Chart for
Setpoint Deviation Menu /
Field Calibration
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:
Press d
4) Display advances to Setpoint Deviation ENBL Enable or
DSBL . Disable Submenu and flashes the previous selection.
Press b
5) Scroll through the available selections: ENBL or DSBL .
Press d
6) Display shows STRD stored message momentarily and then
advances to the next menu item.
Setpoint Deviation menu, if “enabled”, allows changes to Setpoint 1 to be made
automatically to Setpoint 2. This mode is very helpful if the Process temperature
changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees or
counts away from SP1 - this relation remains fixed when SP1 is changed. For
instance: Setting SP1=200 and SP2=20 and enabling SP.DV means that the absolute
value of SP2=220. Moving SP1 to 300, the absolute value of SP2 becomes 320.
THERMOCOUPLE FIELD CALIBRATION SUBMENU:
CAUTION: Do not perform the following steps until you fully
understand this entire section.
RTD and Process are perfectly calibrated. This section is applicable to
Thermocouple (TC) calibration only.
Be sure that the TC being used to calibrate the meter is of the type
selected in the TC submenu. Place the TC in an ice-bath (or other
0°C / 32°F environment). In ambient temperature conditions: connect the
TC to the meter, apply power to the meter.
CAUTION: Do not proceed with TC calibration unless the above conditions
have been in effect for at least one hour.
Press a
7) Display shows CAL .
Press d
8) Display shows flashing 0000.
Press a *
9) Display will still show flashing 0000.
Press d *
10) Display shows OUT1 (meaning Calibration is complete)
* If you accidently engage the flashing 0000 (CAL° alert) simply re-press
the last button you pressed, to avoid unintentionally mis-calibrating your meter.
30
3.2.10 ID CODE
Figure 3.9 Flow Chart for ID Code
ENTER ID CODE MENU:
Press a
Press d
Press a
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to ID ID Code
Menu.
ENTERING OR CHANGING YOUR (NON-DEFAULT) ID CODE:
Press d
4) Display advances to ____ with 1st under score flashing.
Press b & c 5) Press b and c to enter your 4-digit “ID Code” number.
Press d
6) Display advances to CH.ID Change ID Code Submenu.
If entered “ID Code” is incorrect display shows ERRo Error
message momentarily and then skips to the Run Mode.
Press d
7) Display flashes the first digit of previous entered “ID Code”
number.
Press b & c 8) Press b and c buttons to enter your new “ID Code” number.
Press d
9) Display shows STRD stored message momentarily and then
advances to the FULL Full Security Submenu.
31
ENTERING OR CHANGING YOUR (DEFAULT) ID CODE:
Enter ID menu (Repeat steps from 1 to 3).
Press d
Press d
10) Display advances to CH.ID Change ID Code Submenu.
11) Display shows 0000 message with flashing 1st digit.
If you want to change your default “ID Code” you can do it now,
otherwise press a and menu will skip to FULL Full Security
Submenu.
Press b & c 12) Press b and c buttons to enter your new “ID Code”
number.
Press d
13) Display shows STRD stored message momentarily and then
advances to the FULL Full Security Submenu.
FULL SECURITY LEVEL SUBMENU:
Press d
Press b
Press d
14) Display flashes ENBL Enable or DSBL Disable.
15) Scroll through the available selections: “Enable” or “Disable”.
16) Display shows STRD stored message momentarily and then
advances to SP.ID Setpoint/ID Submenu.
If "Full" Security Level is "Enabled" and the user attempts to
enter the Main Menu, they will be prompted for an ID Code. The
ID Code should be correct to enter the instrument Menu item.
SETPOINT/ID SECURITY LEVEL SUBMENU:
This Security Level can be functional only if FULL Security
Level is Disabled.
Press d
Press b
Press d
17) Display flashes ENBL Enable or DSBL Disable.
18) Scroll through the available selections: “Enable” or “Disable”.
19) Display shows STRD stored message momentarily and then
advances to COMM Communication Submenu.
If "Setpoint/ID" Security Level is "Enabled" and the user
attempts to advance into the CNFG Configuration Menu, he will
be prompted for ID Code number. The ID Code should be
correct to proceed into the Configuration Menu, otherwise
display will show an Error and skip to the Run Mode.
If “Full” and “Setpoint/ID” Security Levels are "Disabled", the
ID code will be “Disabled” and user will not be asked for ID
Code to enter the Menu items (“ID” Submenu will not show up in
“ID/Setpoint” Menu).
32
3.2.11 COMMUNICATION OPTION
Purchasing the controller with Serial Communications permits an instrument to be
configured or monitored from an IBM PC compatible computer using software
available from the website or on the CD-ROM enclosed with your shipment.
For complete instructions on the use of the Communications Option, refer to the
Serial Communications Reference Manual.
Figure 3.10 Flow Chart for Communication Option
33
ENTER COMMUNICATION OPTION MENU:
Press a
Press d
Press a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to COMM
Communication Options Menu.
4) Display advances to C.PAR Communication Parameters
Submenu.
If Communication Option is not installed, the display shows NONE
and skips to the Color Display Menu.
COMMUNICATION PARAMETERS SUBMENU:
Allows the user to adjust Serial Communications Settings of the instrument.
When connecting an instrument to a computer or other device, the
Communications Parameters must match. Generally the default settings
(as shown in Section 5) should be utilized.
Press d
5) Display advances to BAUD Baud Submenu.
BAUD SUBMENU:
Press d
Press b
Press d
6) Display flashes previous selection for BAUD value.
7) Scroll through the available selections: 300_, 600_, 1200,
2400, 4800, 9600, 19.2K.
8) Display shows STRD stored message momentarily and then
advances to PRTY only, if it was changed, otherwise press a to
advance to PRTY Parity Submenu.
PARITY SUBMENU:
Press d
Press b
Press d
9) Display flashes previous selection for “Parity”.
10) Scroll through the available selections: NO, ODD, EVEN.
11) Display shows STRD stored message momentarily and then
advances to DATA only, if it was changed, otherwise press a to
advance to DATA Data Bit Submenu.
DATA BIT SUBMENU:
Press d
Press b
Press d
12) Display flashes previous selection for “Data Bit”.
13) Scroll through the available selections: 7-BIT, 8-BIT.
14) Display shows STRD stored message and then advances to
STOP only, if it was changed, otherwise press a to advance to
STOP Stop Bit Submenu.
34
STOP BIT SUBMENU:
Press d
Press b
Press d
15) Display flashes previous selection for “Stop Bit”.
16) Scroll through the available selections: 1-BIT, 2-BIT.
17) Display shows STRD stored message momentarily and then
advances to BUS.F only, if it was changed, otherwise press a to
advance to BUS.F Bus Format Submenu.
BUS FORMAT SUBMENU:
Determines Communications Standards and Command/Data Formats for
transferring information into and out of the controller via the Serial
Communications Bus. Bus Format submenus essentially determine how and
when data can be accessed via the Serial Communications of the device.
Press d
18) Display advances to M.BUS Modbus Submenu.
MODBUS PROTOCOL SUBMENU:
Press d
Press b
Press d
19) Display flashes previous selection for M.BUS.
20) Scroll through the available selections: NO, YES.
21) Display shows STRD stored message momentarily and then
advances to _LF_ only, if it was changed, otherwise press a to
advance to _LF_ Line Feed submenu.
To select iSeries Protocol, set Modbus submenu to “No”.
To select Modbus Protocol, set Modbus submenu to “Yes”.
If Modbus Protocol was selected, the following Communications
Parameters must be set as: No Parity, 8-bit Data Bit, 1-Stop Bit. Do not
attempt to change these parameters.
LINE FEED SUBMENU:
Determines if data sent from the instrument will have a Line Feed appended to
the end - useful for viewing or logging results on separate lines when displayed
on communications software at a computer.
Press d
Press b
Press d
22) Display flashes previous selection for “Line Feed”.
23) Scroll through the available selections: NO, YES.
24) Display shows STRD stored message momentarily and then
advances to ECHO only, if it was changed, otherwise press a to
advance to ECHO Echo Submenu.
ECHO SUBMENU:
When valid commands are sent to the instrument, this determines whether the
command will be echoed to the Serial Bus. Use of echo is recommended in most
situations, especially to help verify that data was received and recognized by the
controller.
35
Press d
Press b
Press d
25) Display flashes previous selection for “Echo”.
26) Scroll through the available selections: NO, YES.
27) Display flashes STRD stored message momentarily and then
advances to STND only if it was changed, otherwise press a to
advance to STND Communication Standard Submenu.
COMMUNICATION INTERFACE STANDARD SUBMENU:
Determines whether device should be connected to an RS-232C serial port
(as is commonly used on IBM PC-compatible computers) or via an RS-485 bus
connected through appropriate RS-232/485 converter. When used in RS-485
Mode, the device must be accessed with an appropriate Address Value as
selected in the Address Submenu described later.
Press d
Press b
Press d
28) Display flashes previous selection for “Standard”.
29) Scroll through the available selections: 232C, 485.
30) Display shows STRD stored message momentarily and then
advances to MoDE only, if it was changed, otherwise press a to
advance to MoDE Data Flow Mode Submenu.
DATA FLOW MODE SUBMENU:
Determines whether the instrument will wait for commands and data requests
from the Serial Bus or whether the instrument will send data automatically and
continuously to the Serial Bus. Devices configured for the RS-485
Communications Standard operate properly only under Command Mode.
Press d
Press b
Press d
31) Display flashes previous selection for “Mode”.
32) Scroll through the available selections: CMD_
_ “Command”,
CoNT “Continuous”.
33) Display shows STRD stored message momentarily and then
advances to SEPR only, if it was changed, otherwise press a to
advance to SEPR Data Separation Submenu.
DATA SEPARATION CHARACTER SUBMENU:
Determines whether data sent from the device in Continuous Data Flow Mode
will be separated by spaces or by Carriage Returns.
Press d
Press b
Press d
34) Display flashes previous selection for “Separation” Submenu.
35) Scroll through the available selections: SPCE “Space” or
_çR_ “Carriage Return”.
36) Display shows STRD stored message momentarily and then
advances to DAT.F only, if it was changed, otherwise press a to
advance to DAT.F Data Format Submenu.
36
DATA FORMAT SUBMENU:
Preformatted data can be sent automatically or upon request from the controller.
Use the Data Format Submenus to determine what data will be sent in this
preformatted data string. Refer to the iSeries Communications Manual for more
information about the data format. At least one of the following suboptions must
be enabled and hence output data to the Serial Bus.
This menu is applicable for Continuous Mode of RS-232 communication.
Press d
37) Display advances to STAT Alarm Status Submenu.
ALARM STATUS SUBMENU:
Includes Alarm Status bytes in the data string.
Press d
Press b
Press d
38) Display flashes previous selection for “Status” (alarm status).
39) Scroll through the available selections: NO, YES.
40) Display shows STRD stored message momentarily and then
advances to RDNG only, if it was changed, otherwise press a to
advance to RDNG Reading Submenu.
MAIN READING SUBMENU:
Includes Main Reading in the data string.
Press d
Press b
Press d
41) Display flashes previous selection for “Reading”.
42) Scroll through the available selections: NO, YES.
43) Display shows STRD stored message momentarily and then
advances to PEAK only, if it was changed, otherwise press a to
advance to PEAK Peak Submenu.
PEAK VALUE SUBMENU:
Includes Peak Value in the data string.
Press d
Press b
Press d
44) Display flashes previous selection for PEAK Submenu.
45) Scroll through the available selections: NO, YES.
46) Display shows STRD stored message momentarily and then
advances to VALY only, it was changed, otherwise press a to
advance to VALY Valley Submenu.
VALLEY VALUE SUBMENU:
Includes Valley Value in the data string.
Press d
Press b
Press d
47) Display flashes previous selection for “Valley”.
48) Scroll through the available selections: NO, YES.
49) Display shows STRD stored message momentarily and then
advances to UNIT only, if it was changed, otherwise press a to
advance to UNIT Temperature Unit Submenu.
37
TEMPERATURE UNIT SUBMENU:
Includes a byte in the data string to indicate whether reading is in Celsius or
Fahrenheit.
Press d
Press b
Press d
50) Display flashes previous selection for UNIT.
51) Scroll through the available selections: NO, YES.
52) Display shows STRD stored message momentarily and then
advances to ADDR only, if it was changed, otherwise press a to
advance to ADDR Address Setup Submenu.
ADDRESS SETUP SUBMENU:
This menu is applicable to the RS-485 Option only.
Press d
53) Display advances to “Address Value” (0000 to 0199) Submenu.
ADDRESS VALUE SUBMENU:
Press d
54) Display flashes 1st digit of previously stored Address Value.
Press b & c 55) Press b and c to enter new “Address Value”.
Press d
56) Display shows STRD stored message momentarily and then
advances to TR.TM only, if it was changed, otherwise press a to
advance to TR.TM Transmit Time Interval Submenu.
TRANSMIT TIME INTERVAL SUBMENU:
This menu is applicable if “Continuous” Mode was selected in the “Data
Flow Mode” Submenu and the device is configured as an RS-232C
Standard device. Also, one or more options under the Data Format
Submenu must be enabled.
Press d
57) Display advances to “Transmit Time Value” Submenu.
TRANSMIT TIME INTERVAL VALUE SUBMENU:
Determines the interval at which data will be emitted to the RS-232 Serial Bus
when the instrument is in Continuous Data Flow Mode.
58) Display flashes 1st digit of previous “Transmit Time Value” in
seconds.
Press b & c 59) Press b and c to enter new “Transmit Time Value”, e.g.
0030 will send the data every 30 seconds in Continuous Mode.
Press d
60) Display shows STRD stored message momentarily and then
advances to COLR only, if it was changed, otherwise press a to
advance to COLR Color Display Selection Menu.
Press d
For more details, refer to the Communication Manual available at the
website listed in the cover page of this manual or on the CD-ROM
enclosed with your shipment.
38
3.2.12 DISPLAY COLOR SELECTION
This submenu allows the user to select the color of the display.
Figure 3.11 Flow Chart for Display Color Selection
ENTER DISPLAY COLOR SELECTION MENU:
Press a
Press d
Press a
Press d
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to COLR
Display Color Selection Menu.
4) Display advances to N.CLR Normal Color Submenu.
NORMAL COLOR DISPLAY SUBMENU:
Press d
Press b
Press d
5) Display flashes the previous selection for “Normal Color”.
6) Scroll through the available selections: GRN, RED or AMBR.
7) Display shows STRD stored message momentarily and then
advances to 1.CLR only, if it was changed, otherwise press a to
advance to 1.CLR Alarm 1 Display Color Submenu.
The menu below allows the user to change the color of display when alarm is
triggered.
ALARM 1 DISPLAY COLOR SUBMENU:
Press d
Press b
Press d
8) Display flashes previous selection for “Alarm 1 Color
Display”.
9) Scroll through the available selections: GRN, RED or AMBR.
10) Display shows STRD stored message momentarily and then
advances to 2.CLR only, if it was changed, otherwise press a to
advance to 2.CLR Alarm 2 Display Color Submenu.
39
ALARM 2 DISPLAY COLOR SUBMENU:
Press d
Press b
Press d
11) Display flashes previous selection for “Alarm 2 Color Display”.
12) Scroll through the available selections: GRN, RED or AMBR.
13) Display shows STRD stored message momentarily and then
momentarily shows the software version number, followed by
RST Reset, and then proceeds to the Run Mode.
IN ORDER TO DISPLAY ONE COLOR, SET THE SAME DISPLAY
COLOR ON ALL THREE SUBMENUS ABOVE.
If user wants the Display to change color every time when both Alarm 1
and Alarm 2 are triggered, the Alarm values should be set in such a way
that Alarm 1 value is always on the top of Alarm 2 value, otherwise value
of Alarm 1 will overwrite value of Alarm 2 and Display Color would not
change when Alarm 2 is triggered.
Example 1:
Alarm Setup: Absolute, Above, Alarm 2 HI Value “ALR.H” = 200, Alarm 1
HI Value “ALR.H” = 400
"Color Display" Setup: Normal Color “N.CLR” = Green, Alarm 1 Color
“1.CLR” = Amber, Alarm 2 Color “2.CLR” = Red
Display Colors change sequences:
GREEN
RED
AMBER
•--➤------------------------------•-----------------------------•------------------------------➤
0
AL2.H = 200
AL1.H = 400
Example 2:
Alarm Setup: Absolute, Below, Alarm 2 Low Value “ALR.L” = 300, Alarm 1
Low Value “ALR.L” = 100
Color Display Setup: "N.CLR" = Green, "1.CLR" = Amber, "2.CLR" = Red
Display Colors change sequences:
AMBER
RED
GREEN
• --------------•----------------------------------•------------------------------------------- •
0
AL1.L = 100
AL2.L = 300
40
Example 3:
Setpoint 1 = 300,
Setpoint 2 = 200
Alarm 1 & 2 Setup: Deviation, Band, “ALR.H” = 10
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display Colors change sequences:
RED
RED
RED
GREEN
RED
•➤---------------•------•------•--------------------------------•------•-------•----------------➤
0
190 200 210
290 300 310
Alarm 1 is designed to monitor the Process Value around the Setpoint 1.
Alarm 2 is designed to monitor the Process Value around the Setpoint 2.
If Analog Output Option board is installed (Alarm 1 is disabled), only
Alarm 2 is active and only two colors are available.
Example 4:
Setpoint 1 = 200
Setpoint 2 = 200
Alarm 1 Setup: Deviation, Band, “ALR.H” = 20
Alarm 2 Setup: Deviation, Hi/Low, “ALR.H” = 10, “ALR.L” = 5
Color Display Setup: “N.CLR” = Green, “1.CLR” = Amber, “2.CLR” = Red
Display colors change sequences:
AMBER
RED
GREEN GREEN
RED
AMBER
•--➤---------------•----------------•-------------•--------------•-------------•---------------------➤
0
180
195
200
210
220
Reset: The instrument automatically resets after the last menu of
the Configuration Mode has been entered. After the instrument
resets, it advances to the Run Mode.
41
PART 4
SPECIFICATIONS
Accuracy
±0.5°C temp; 0.03% reading process
Thermocouple Lead Resistance
100 ohm max
Resolution
1°/0.1°; 10 µV process
RTD Input (ITS 68)
100/500/1000 Ω Pt sensor, 2-, 3- or
4-wire; 0.00385 or 0.00392 curve
Temperature Stability
1) RTD: 0.04°C/°C
2) TC @ 25°C (77°F): 0.05°C/°C
- Cold Junction Compensation
3) Process: 50 ppm/°C
Voltage Input
0 to 100 mV, 0 to 1 V, 0 to 10 Vdc
Input Impedance
10 MΩ for 100 mV
1 MΩ for 1 or 10 Vdc
NMRR
60 dB
Current Input
0 to 20 mA (5 ohm load)
CMRR
120 dB
Configuration
Single-ended
A/D Conversion
Dual slope
Polarity
Unipolar
Reading Rate
3 samples per second
Step Response
0.7 sec for 99.9%
Digital Filter
Programmable
Decimal Selection
None, 0.1 for temperature
None, 0.1, 0.01 or 0.001 for process
Display
4-digit or 6-digit, 7-segment LED
57.2 mm (2.25") or 101.6mm (4.00”)
red, green and amber programmable
colors for process variable, set point
and temperature units
Setpoint Adjustment
-1999 to 9999 counts
Span Adjustment
0.001 to 9999 counts
Warm up to Rated Accuracy
60 min.
Offset Adjustment
-1999 to +9999
INPUT
Input Types
Thermocouple, RTD, Analog
Voltage, Analog Current
Thermocouple Type (ITS 90)
J, K, T, E, R, S, B, C, N, L
42
NETWORK AND COMMUNICATIONS
(Optional -C24, -C4EI)
GENERAL
Power
100-240 Vac +/-10%, 50/60 Hz
22.5 W
Ethernet: Standards Compliance
IEEE 802.3 10Base-T
Supported Protocols: TCP/IP, ARP,
HTTPGET
RS-232/RS-422/RS-485:
Programmable 300 to 19.2 K baud;
complete programmable setup
capability; program to transmit current
display, alarm status, Peak and Valley
value.
RS-485: Addressable from 0 to 199
Connection: Screw terminals
Fuse
4A, 250V, GFE, 5x20mm
Environmental Conditions
0 to 40°C (32 to 104°F),
90% RH non-condensing
Protection
NEMA-4x (IP65) front bezel
Dimensions and Panel Cutout
Refer to Quickstart Specifications.
ALARM 1 & 2 (programmable):
Weight
Refer to Quickstart Specifications.
Operation
High/low, above/below, band,
latch/unlatch, normally open/normally
closed and process/deviation; front
panel configurations
INSULATION
Power to Input/Output
2300 Vac per 1 minute test
(RS-232/485, Input or Output)
Between Inputs
500 Vac per 1 minute test
Approvals
See Approval Section
43
Table 4.1 Input Properties
TC
J
K
Input Type
Iron-Constantan
CHROMEGA ALOMEGA
TM
TM
T
Copper-Constantan
E
CHROMEGAConstantan
R
Pt/13%Rh-Pt
S
Pt/10%Rh-Pt
B
30%Rh-Pt/
6%Rh-Pt
C
N
5%Re-W/
26%Re-W
L
RTD
RTD
PROCESS
Nicrosil-Nisil
J
DIN
Pt, 0.00385, 100 Ω,
500 Ω, 1000 Ω
Pt, 0.00392, 100 Ω,
500 Ω, 1000 Ω
Voltage
PROCESS Current
Range
-210 to 760°C
-346 to 1400°F
-270 to -160°C
-160 to 1372°C
-454 to -256°F
-256 to 2502°F
-270 to -190°C
-190 to 400°C
-454 to -310°F
-310 to 752°F
-270 to -220°C
-220 to 1000°C
-454 to -364°F
-364 to 1832°F
-50 to 40°C
40 to 1788°C
-58 to 104°F
104 to 3250°F
-50 to 100°C
100 to 1768°C
-58 to 212°F
212 to 3214°F
200 to 640°C
640 to 1820°C
212 to 1184°F
1184 to 3308°F
0 to 2354°C
32 to 4253°F
-250 to -100°C
-100 to 1300°C
-418 to -148°F
-148 to 2372°F
-200 to 900°C
-328 to 1652°F
200 to 900°C
-328 to 1652°F
-200 to 850°C
-328 to 1562°F
0 to 100 mV, 0 to 1 V,
0 to 10 Vdc
0 to 20 mA, 4 to 20 mA
Accuracy*
0.4°C
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
1.0°C
0.5°C
1.8°F
0.9°F
1.0°C
0.5°C
1.8°F
0.9°F
1.0°C
0.5°C
1.8°F
0.9°F
0.4°C
0.7°F
1.0°C
0.4°C
1.8°F
0.7°F
0.4°C
0.7°F
0.4°C
0.7°F
0.4°C
0.7°F
0.03% rdg
0.03% rdg
0.03% rdg
PART 5
FACTORY PRESET VALUES
Table 5.1 Factory preset value
MENU ITEMS
Set Point 1 (SP1)
Set Point 2 (SP2)
Input:
Input Type (INPT)
Reading Configuration (RDG):
Decimal Point (DEC.P)
Temperature unit (TEMP)
Filter value (FLTR)
Alarm 1 & 2:
Alarm 1 (ALR1), Alarm 2 (ALR2)
Absolute/Deviation (ABSO/DEV)
Latch/Unlatch (LTCH/UNLT)
Active (ACTV)
Alarm At Power On (A.P.ON)
Alarm Low (ALR.L)
Alarm High (ALR.H)
ID:
ID Value
Full ID (FULL)
Set Point ID (ID.SP)
Communication Parameters:
Baud Rate (BAUD)
Parity (PRTY)
Data bit (DATA)
Stop Bit
Modbus Protocol (M.BUS)
Line Feed (LF)
Echo (ECHO)
Standard Interface (STND)
Command Mode (MODE)
Separation (SEPR)
Alarm Status (STAT)
Reading (RDNG)
Peak
Valley (VALY)
Units (UNIT)
Multipoint Address (ADDR)
Transmit Time (TR.TM)
Display Color (COLR):
Normal Color (N.CLR)
Alarm 1 Color (1.CLR)
Alarm 2 Color (2.CLR)
FACTORY PRESET VALUES
000.0
000.0
NOTES
TC, type K
FFF.F
°F
0004
Disable (DSBL)
Absolute (ABSO)
Unlatch (UNLT)
Above (ABOV)
Disable (DSBL)
-100.0
400.0
0000
Disable (DSBL)
Disable (DSBL)
9600
Odd
7 bit
1 bit
No
No
Yes
RS-232 (232C)
Command (CMD)
Space (SPCE)
No
Yes
No
No
No
0001
0016
Green (GRN)
Red (RED)
Amber (AMBR)
45
Alarm 1 only
PART 6
APPROVALS INFORMATION
This product conforms to the EMC directive 89/336/EEC amended by
93/68/EEC, and with the European Low Voltage Directive 72/23/EEC.
Electrical Safety EN61010-1:2001
Safety requirements for electrical equipment for measurement, control and
laboratory.
Double Insulation
Pollution Degree 2
Dielectric withstand Test per 1 min
• Power to Input/Output:
2300Vac (3250Vdc)
• Power to Relays/SSR Output:
2300Vac (3250Vdc)
• Ethernet to Inputs:
1500Vac (2120Vdc)
• Isolated RS232 to Inputs:
500Vac (720Vdc)
• Isolated Analog to Inputs:
500Vac (720Vdc)
• Analog/Pulse to Inputs:
No Isolation
Measurement Category I
Category I are measurements performed on circuits not directly connected to the
Mains Supply (power). Maximum Line-to-Neutral working voltage is 50Vac/dc.
This unit should not be used in Measurement Categories II, III, IV.
Transients Overvoltage Surge (1.2 / 50uS pulse)
• Input Power:
2500V
• Ethernet:
1500V
• Input/Output Signals:
500V
EMC EN61326:1997 + and A1:1998 + A2:2001
Immunity and Emissions requirements for electrical equipment for measurement,
control and laboratory.
• EMC Emissions Table 4, Class B of EN61326
• EMC Immunity** Table 1 of EN61326
Note: **I/O signal and control lines require shielded cables and these cables
must be located on conductive cable trays or in conduits.
Furthermore, the length of these cables should not exceed 30 meters
Refer to the EMC and Safety installation considerations (Guidelines) of this manual
for additional information.
46
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a
period of 61 months from date of purchase. OMEGA’s WARRANTY adds an additional one (1) month grace
period to the normal five (5-) year product warranty to cover handling and shipping time. This ensures
that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service
Department will issue an Authorized Return (AR) number immediately upon phone or written request.
Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no
charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser,
including but not limited to mishandling, improper interfacing, operation outside of design limits,
improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of
having been tampered with or shows evidence of having been damaged as a result of excessive corrosion;
or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating
conditions outside of OMEGA’s control. Components in which wear is not warranted, include but are not
limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However,
OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for
any damages that result from the use of its products in accordance with information provided
by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by the
company will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSOEVER, EXPRESSED OR IMPLIED, EXCEPT THAT OF
TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF
LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence,
indemnification, strict liability or otherwise, shall not exceed the purchase price of the
component upon which liability is based. In no event shall OMEGA be liable for
consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic
Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical
applications or used on humans. Should any Product(s) be used in or with any nuclear installation or
activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility
as set forth in our basic WARRANTY/DISCLAIMER language, and, additionally, purchaser will indemnify
OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the
Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE
RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR)
NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING
DELAYS). The assigned AR number should then be marked on the outside of the return package and on any
correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.
FOR NON-WARRANTY REPAIRS, consult
FOR WARRANTY RETURNS, please have the
OMEGA for current repair charges. Have
following information available BEFORE contacting
the following information available BEFORE
OMEGA:
contacting OMEGA:
1. Purchase Order number under which the product
1. Purchase Order number to cover the COST
was PURCHASED,
of the repair,
2. Model and serial number of the product under
2. Model and serial number of the product, and
warranty, and
3. Repair instructions and/or specific problems
3. Repair instructions and/or specific problems
relative to the product.
relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our
customers the latest in technology and engineering.
OMEGA is a trademark of OMEGA ENGINEERING, INC.
© Copyright 2018 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied,
reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior
written consent of OMEGA ENGINEERING, INC.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA…Of Course!
Shop online at omega.com
TEMPERATURE
M
U Thermocouple, RTD & Thermistor Probes, Connectors,
Panels & Assemblies
M
U Wire: Thermocouple, RTD & Thermistor
M
U Calibrators & Ice Point References
M
U Recorders, Controllers & Process Monitors
M
U Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
M
U Transducers & Strain Gages
M
U Load Cells & Pressure Gages
M
U Displacement Transducers
M
U Instrumentation & Accessories
FLOW/LEVEL
M
U Rotameters, Gas Mass Flowmeters & Flow Computers
M
U Air Velocity Indicators
M
U Turbine/Paddlewheel Systems
M
U Totalizers & Batch Controllers
pH/CONDUCTIVITY
M
U pH Electrodes, Testers & Accessories
M
U Benchtop/Laboratory Meters
M
U Controllers, Calibrators, Simulators & Pumps
M
U Industrial pH & Conductivity Equipment
DATA ACQUISITION
M
U Communications-Based Acquisition Systems
M
U Data Logging Systems
M
U Wireless Sensors, Transmitters, & Receivers
M
U Signal Conditioners
M
U Data Acquisition Software
HEATERS
M
U Heating Cable
M
U Cartridge & Strip Heaters
M
U Immersion & Band Heaters
M
U Flexible Heaters
M
U Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
M
U Metering & Control Instrumentation
M
U Refractometers
M
U Pumps & Tubing
M
U Air, Soil & Water Monitors
M
U Industrial Water & Wastewater Treatment
M
U pH, Conductivity & Dissolved Oxygen Instruments
M3716/0818
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising