Cooper Lighting 0-10V Preset Slide Dimmer Installation Instruction

Add to my manuals
2 Pages

advertisement

Cooper Lighting 0-10V Preset Slide Dimmer Installation Instruction | Manualzz
Fluorescent and LED Fixture Slide Dimmer
Single Pole (One location) or 3-Way (Multi-location)
Cat. No. WBSD-010M-C1
1200VA-120VAC, 60Hz, 1500VA-277VAC, 60Hz
10A LED, 120VAC/277VAC, 60Hz
10A Electronic Ballast, 120VAC/277VAC, 60 Hz
28mA Maximum Sink Current
For Use with LED fixtures using 0-10V dimmable power supply/drivers, Advance Transformer Mark 7® OSRAM Sylvania Quicktronic® Helios™ or equivalent dimmable ballasts.
DI-420-IP710-02A
INSTALLATION INSTRUCTIONS
WARNING:
CAUTIONS:
• T
O AVOID FIRE, SHOCK, OR DEATH; TURN OFF POWER AT CIRCUIT BREAKER OR FUSE AND TEST THAT POWER IS OFF BEFORE WIRING
OR SERVICING FIXTURE!
•
•
•
•
CAUTIONS:
•
To avoid overheating and possible damage to this device and other equipment, use only with the appropriate LED 0-10V dimmable power supplies/
drivers, Advance Transformer 120/277V Mark 7® 0-10V ballasts or OSRAM Sylvania Quicktronic® Helios™ electronic ballasts.
Tools needed to install your Dimmer
Note: No derating is required in this mult-device installation
as referenced in the following chart.
Slotted/Philips Screwdriver
Electrical Tape
Pliers
PencilCuttersRuler
Changing the color of your Dimmer
Your Dimmer includes three color options. The Dimmer
ships with the White frame attached. To change color of
frame, proceed as follows:
Volts
Single
Two
Gang
More than
2 Devices
WBSD-010M-C1
120
1200VA
1200VA
1200VA
WBSD-010M-C1
277
1500VA
1500VA
1500VA
Line up tabs and
press in side to attach
Note: Move slider on dimmer and slider on change kit
to bottom of the slide bar prior to engaging.
Installing Dimmer by itself or with other devices
If installing Dimmer in a single device application, proceed
with the INSTALLING YOUR DIMMER section. If installing
Dimmer in a multi-device application, proceed as follows:
MULTI-DEVICE APPLICATION:
NOTE: You only need to remove side sections if installing
with other dimmers or if it does not fit in wall box – not
when installing with mechanical switches.
When installing more than one dimmer in the same
location, the side sections of the mounting strap must be
removed. Use pliers to carefully bend side sections back
and forth until they break off.
Remove
all inner
side
sections
(most common):
NOTE: If the wiring in the wall box does not
resemble any of these configurations, consult an
electrician.
MAXIMUM BULB WATTAGE:
3
0-10VDC ballasts are rated in Volt-Amps (VA). The maximum
number of ballast per dimmer is based on the load VA rating.
The maximum bulb wattage is determined by the efficiency of
the ballast.
1
1
SP20-RD4 SWITCH RATINGS:
20 Amps for 120 and 277 VAC Ballast
0-10 VDC Sink Current Rating:
28 mA maximum sink current. Contact your ballast
manufacturer for the sink current rating of the ballast.
INSTALLING YOUR DIMMER
Step 1 WARNING: TO AVOID FIRE, SHOCK, OR
DEATH; TURN OFF POWER at circuit breaker or
fuse and test that power is off before wiring!
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
Step 4B
3-Way Wiring Application:
This wire is used in 3-way installations only.
For single pole installations, do not remove this
insulating label.
Violet
Neutral
Gray
Insert wires
straight then twist
clockwise
3-Way
1. Load (See note below)
2. Neutral
3. Ground
4. First Traveler – note color
5. Second Traveler – note color
6. Gray (-)
7. Violet (+)
IMPORTANT: For 3-way applications, note that one of the
screw terminals from the old switch being removed will usually
be a different color (Black) or labeled Common. Tag that wire
with electrical tape and identify as the common (Line or Load)
in both the dimmer wall box and the standard 3-way switch
wall box.The remaining two wires on the brass or lighter
screws screw terminatls of the old switch are the travelers.
Step 3
• Pull off pre-cut insulation from Dimmer leads.
• Make sure that the ends of the wires from the wall
box are straight (cut if necessary).
• Remove 5/8" (1.6 cm) of insulation from each wire
in the wall box (shown).
• For Single-Pole Application, go to Step 4A.
• For 3-Way Application, go to Step 4B.
Cut
(if necessary)
Black
Red
Black
Red
Electrical
Tape
5/8"
(1.6 cm)
Strip Gage
Electrical
Tape
Connect wires per WIRING DIAGRAM 1
(shown on page 2) as follows:
Connect wires per WIRING DIAGRAM 3
(shown on page 2) as follows:
Screw wire nuts on clockwise making sure no bare
conductors show below the wire connectors. Secure
each connector with electrical tape.
Screw wire nuts on clockwise making sure no bare
conductors show below the wire connectors. Secure
each connector with electrical tape.
NOTE: Ensure that low-voltage wiring (for Gray and
Violet connection of dimmer) is installed at wallbox
that will house the WBSD-010M-C1 dimmer.
NOTE: For additional switching capacity, use dimmers
in conjuction with an Eaton SP20-RD4 switchpack.
Preparing wires:
Strip 5/8"
(1.6 cm)
Gray
Insert wires
straight then twist
clockwise
Red
5
Single Pole
1. Load
2. Neutral
3. Ground
4. Line (Hot)
5. Gray (-)
6. Violet (+)
Neutral
Ground
Ground
4
Violet
Green
Green
4
Do not
remove
outer
side
sections
Bend back and
forth to remove side
section
2
NOTE: Ensure that low-voltage wiring (for Gray and
Violet connection of dimmer) is installed at wallbox
that will house the WBSD-010M-C1 dimmer.
OFF
Single-Pole Wiring Application:
Red
6
2
3
For applications using Eaton's SP20-RD4 switchpack
(Shown in Wiring Diagrams 2), the SP20-RD4 switch
ratings are as follows (refer to SP20-RD4 Instruction
Sheet for additional information):
Step 4A
7
6
5
NOTE: For additional switching capacity, use dimmers in
conjuction with an Eaton SP20-RD4 switchpack.
Push in side at tab
to release
NOTE: Use only one (1) dimmer in a 3- or 4-way circuit. The switch(es) will turn the light on at the brightness level selected at the dimmer.
Step 2 Identifying your wiring application
MAXIMUM LOAD PER DIMMER FOR MULTI-DEVICE
Cat. No.
To be installed and/or used in accordance with appropriate electrical codes and regulations.
If you are unsure about any part of these instructions, consult an electrician.
Lighting fixture and dimmer must be grounded.
Use this device only with copper or copper clad wire.
• Green dimmer Ground lead to Green or bare copper
wire in wall box.
• Black dimmer lead to Line Hot wall box wire.
• Red dimmer lead without insulating label to Load wall
box wire.
• Remaining Red dimmer lead should have Red
insulation label affixed.
NOTE: If insulating label is not affixed to Red lead, use
a small wire nut or electrical tape to cap off.
• V
iolet dimmer lead to (+) Violet connection on ballast.
• G
ray dimmer lead to (-) Gray connection on ballast.
• Proceed to Step 5.
NOTE: Dimmer can be installed on either the Load
or Line side.
NOTE: Ensure that low-voltage wiring (for Gray and
Violet connection of dimmer) is installed at wallbox
that will house the WBSD-010M-C1 dimmer.
NOTE: For additional switching capacity, use
dimmers in conjuction with an Eaton SP20-RD4
120/277V switchpack.
• Green dimmer Ground lead to Green or bare copper
wire in wall box.
• B
lack dimmer lead to tagged (common) wall box
wire identified in step 2.
• R
emove Red insulating label from Red lead.
• F
irst Traveler wall box wire identified in step 2 to
any red dimmer lead.
• S
econd Traveler wall box wire identified in step 2
to the remaining red dimmer lead.
• V
iolet dimmer lead to (+) Violet connection on
ballast.
• G
ray dimmer lead to (-) Gray connection on
ballast.
• Proceed to Step 5.
Step 5
Testing your Dimmer prior to mounting in
wall box:
• Restore power at circuit
breaker or fuse.
• Carefully holding Dimmer
as shown, move slider
control lever to highest
position. Lights should
turn ON to brightest level.
If lights do not turn ON,
depress push-button switch
once. Lights should turn
ON to brightest level.
If lights still do not
turn ON, refer to the
TROUBLESHOOTING
section.
OPERATION
NOTE: If using the dimmer in a 3-way application, the
lights will turn ON at brightness set on dimmer's slide
control lever. The lights can be controlled from either
the dimmer or the switch location.
ON/OFF:
Depress push-button switch to
ON position - Lights will turn ON.
Dimmer
Depress push-button switch to
OFF position - Lights will turn
OFF.
Hot (Black)
BRIGHTEN & DIM:
Move slider control lever Lights will BRIGHTEN or DIM.
Line
120/277VAC,
60Hz
Dimmer Mounting:
Black
Violet
Gray
Red
Red
To Lamps
Insulating
Label
Black
This dimmer features a Maximum
Trim adjustment to adjust the
maximum light level of the dimmer.
Yellow
Yellow/Orange
2. Rotate the dial clockwise to
reduce the maximum light level,
or counter-clockwise to increase
the maximum light level.
Yellow/Orange
Blue
Blue
Black
White/Blue
SP20-RD4
Blue
Red
White
Red
Black
Insulating
Label
Violet
Blue
Red
Black
Black
0-10 VDC
Ballast
Gray
Green
Ground
White/Blue
SP20-RD4
White
Red
Gray
Yellow/Orange
Blue
Blue
Black
Violet
White
• L
ights Flickering
- Lamp has a bad connection.
- Wires not secured firmly with wire connectors.
• Light does not turn ON
- Circuit breaker or fuse has tripped.
- Lamp is burned out.
- Lamp Neutral connection is not wired.
WBSD-010M-C1
Dimmer
Black
0-10 VDC
Ballast
Gray
White
Violet
Neutral (White)
Wiring Diagram 3: Two Location Control
Hot (Black)
WIRE CONNECTOR / # OF COND.
COMBINATION CHART
Line
120/277VAC,
60Hz
Red
Violet
Gray
Red
Black
To Lamps
Black Screw
(common)
1- #12 w/ 1 to 3 #14, #16 or #18
2- #12 w/ 1 or 2 #16 or #18
1- #14 w/ 1 to 4 #16 or #18
2- #14 w/ 1 to 3 #16 or #18
To Additional Ballasts
Gray
Violet
Dimmer
3-Way Switch
For non-standard wiring
applications, refer to Wire
Nut and Connector Size Chart
Restore power at circuit breaker or fuse.
Installation is complete.
White
Blue
Wiring Diagram 2 : Single Location Control with SP20-RD4 switchpacks
Hot (Black)
TROUBLESHOOTING
Restore Power:
Red
0-10 VDC
Ballast
Setting the Maximum Light Level
Black
Step 7
Primary
Side
Green
Ground
1. Locate the "Trim Adjustment" dial
on the top of the dimmer.
TURN OFF POWER AT CIRCUIT BREAKER
OR FUSE.
Installation may now be
completed by carefully
positioning all wires to
provide room in wall box for
dimmer. Mount dimmer into
box with mounting screws
supplied. Attach wallplate.
To Additional Ballasts
Gray
Violet
Neutral (White)
Trim
Adjustment
Dial
Step 6
Wiring Diagram 1 : Single Location Control
Black
Green
Ground
Green
Ground
Primary
Side
White
Red
0-10 VDC
Ballast
Blue
Yellow
Neutral (White)
For additional information, contact Eaton’s technical support line at
1-800-553-3879 or visit www.eaton.com/lighting
Copyright © 2018 Eaton Manufacturing Co., Inc. All rights Including Trade Dress Rights Reserved.
Third party trademarks are the property of their respective owners
For Technical Assistance Call: 1-800-553-3879 (U.S.A. Only) www.eaton.com/lighting
DI-420-IP710-02A
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
Eaton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Eaton is free of defects in materials and workmanship under normal and proper use for five years from the purchase date. Eaton’s only obligation is to correct such defects by repair or replacement, at its option. For details visit www.
eaton.com/lighting or call 1-800-553-3879. This warranty excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused, opened, abused, or altered in any manner, or is not used under normal operating conditions or not
in accordance with any labels or instructions. There are no other or implied warranties of any kind, including merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a particular purpose, is limited to five years.
Eaton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment, lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.