Installation & Operation Manual
4080 Graphical Controller
with optional Profiling
and Recording
PK510-1
0037-75515
March 2017
A
This page intentionally left blank.
B
This manual supplements the Concise Product
manual(s) supplied with each instrument at the time
of shipment. Information in this installation, wiring and
operation manual is subject to change without notice.
Copyright © March 2013, Chromalox, all rights reserved. No part of this publication may be reproduced,
transmitted, transcribed or stored in a retrieval system,
or translated into any language in any form by any
means without the written permission of Chromalox.
THE INTERNATIONAL HAZARD SYMBOL IS INSCRIBED ADJACENT TO THE REAR CONNECTION TERMINALS. IT IS IMPORTANT TO READ
THIS MANUAL BEFORE INSTALLING OR COMMISSIONING THE UNIT.
Copies of this manual are available in electronic format on the Chromalox web site (www.chromalox.com)
Printed versions are available from Chromalox or its
representatives.
Note: It is strongly recommended that applications incorporate a high or low limit protective device, which
will shut down the equipment at a preset process condition in order to prevent possible damage to property
or products.
THIS SYMBOL MEANS THE EQUIPMENT IS
PROTECTED THROUGHOUT BY DOUBLE INSULATION. Products covered by this manual are
suitable for Indoor use, Installation Category II,
Pollution category 2 environments.
This user guide covers all versions of the Chromalox
4080 controller.
Warranty and Returns Statement
Limitations
These products are sold by Chromalox under the warranties set forth in the following paragraphs. Such warranties are extended only with respect to a purchase
of these products, as new merchandise, directly from
Chromalox or from a Chromalox distributor, representative or reseller and are extended only to the first
buyer thereof who purchases them other than for the
purpose of resale.
Chromalox shall not be liable for any incidental damages, consequential damages, special damages, or any
other damages, costs or expenses excepting only the
cost or expense of repair or replacement as described
above. Products must be installed and maintained in
accordance with Chromalox instructions. There is no
warranty against damage to the product resulting from
corrosion. Users are responsible for the suitability of
the products to their application.
Warranty
For a valid warranty claim, the product must be returned carriage paid to the supplier within the warranty period. The product must be properly packaged
to avoid damage from Electrostatic Discharge or other
forms of harm during transit.
These products are warranted to be free from functional defects in material and workmanship at the time the
products leave Chromalox factory and to conform at
that time to the specifications set forth in the relevant
Chromalox manuals sheet or sheets, for such products
for a period of 18 months.
THERE ARE NO EXPRESSED OR IMPLIED
WARRANTIES, WHICH EXTEND BEYOND
THE WARRANTIES HEREIN AND ABOVE
SET FORTH. NO WARRANTY IS MADE OF
MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE WITH RESPECT
TO THE PRODUCTS.
i
Table of Contents
Contents
Page Number
Warranty and Returns Statement............................................................................................................................i
1
Introduction....................................................................................................................................................... 1
2
Installation......................................................................................................................................................... 1
Unpacking........................................................................................................................................................... 1
Installation........................................................................................................................................................... 1
Panel-Mounting.................................................................................................................................................. 2
Cleaning.............................................................................................................................................................. 2
3
Field Upgrade Options...................................................................................................................................... 3
Options Modules and Functions......................................................................................................................... 3
Preparing to Install or Remove Options Modules............................................................................................... 4
Removing/Replacing Option / Output Modules.................................................................................................. 4
Replacing the Instrument in its Housing............................................................................................................. 4
Auto Detection of Option Modules..................................................................................................................... 4
Replacement of Power Supply or Input Boards................................................................................................. 4
Data Recorder Board.......................................................................................................................................... 5
Profiler Enabling.................................................................................................................................................. 5
4
Electrical Installation........................................................................................................................................ 5
Installation Considerations................................................................................................................................. 5
AC Power Wiring - Neutral (for 100 to 240V AC versions).................................................................................. 5
Wire Isolation...................................................................................................................................................... 5
Use of Shielded Cable........................................................................................................................................ 6
Noise Suppression at Source............................................................................................................................. 6
Sensor Placement (Thermocouple or RTD)........................................................................................................ 6
Thermocouple Wire Identification Chart............................................................................................................. 7
Connections and Wiring..................................................................................................................................... 7
Power Connections............................................................................................................................................ 8
Universal Input Connections........................................................................................................................... 9
Option Slot 1 / Output 1 Connections.......................................................................................................... 10
Option Slot 2 / Output 2 Connections.......................................................................................................... 11
Option Slot 3 / Output 3 Connections.......................................................................................................... 12
Option Slot A Connections........................................................................................................................... 13
Option Slot B Connections........................................................................................................................... 14
5
Powering Up.................................................................................................................................................... 14
Powering Up Procedure.................................................................................................................................... 14
Front Panel Overview........................................................................................................................................ 14
Display.............................................................................................................................................................. 15
LED Functions................................................................................................................................................... 15
Keypad.............................................................................................................................................................. 15
6
Messages and Error Indications.................................................................................................................... 16
Start-up Errors.................................................................................................................................................. 16
Input Problems.................................................................................................................................................. 16
USB Data Transfer Problems............................................................................................................................ 16
Getting Help...................................................................................................................................................... 16
ii
Contents
Page Number
7
Configuration and Use................................................................................................................................... 17
Operation Mode................................................................................................................................................ 17
Base, Trend & Profile Operating Screens.......................................................................................................... 17
Adjusting the Local Setpoint(s)......................................................................................................................... 19
Adjusting the Setpoint Ramp Rate................................................................................................................... 19
Selecting Automatic or Manual Mode.............................................................................................................. 19
Control Enable or Disable................................................................................................................................. 20
Main Menu........................................................................................................................................................ 20
Entry into the Main Menu.............................................................................................................................. 20
Unlock Codes............................................................................................................................................... 20
Setup Wizard.................................................................................................................................................... 21
Manual entry to the Setup Wizard................................................................................................................ 21
Supervisor Mode............................................................................................................................................... 21
Entry into Supervisor Mode.......................................................................................................................... 21
Configuration Menu.......................................................................................................................................... 22
Entry into the Configuration Menu................................................................................................................ 22
Input Configuration Sub-Menu......................................................................................................................... 22
Control Configuration Sub-Menu...................................................................................................................... 23
Output Configuration Sub-Menu...................................................................................................................... 26
Alarm Configuration Sub-Menu........................................................................................................................ 26
Communications Configuration Sub-Menu...................................................................................................... 27
Recorder Configuration Sub-Menu................................................................................................................... 27
Clock Configuration Sub-Menu........................................................................................................................ 28
Display Configuration Sub-Menu...................................................................................................................... 28
Lock Code View................................................................................................................................................ 29
Lost Lock Codes........................................................................................................................................... 29
Resetting To Defaults........................................................................................................................................ 29
Automatic Tuning Menu.................................................................................................................................... 29
Profiler Setup Menu.......................................................................................................................................... 30
Profiler Control Menu........................................................................................................................................ 32
USB Menu......................................................................................................................................................... 33
Recorder Menu................................................................................................................................................. 34
Product Information Mode................................................................................................................................ 34
Service Information Mode................................................................................................................................. 35
8
The USB Interface........................................................................................................................................... 35
Using the USB Port........................................................................................................................................... 35
USB Memory Stick Folders & Files............................................................................................................... 35
9
The Data Recorder Option............................................................................................................................. 36
Introduction....................................................................................................................................................... 36
Changes To Operation Mode............................................................................................................................ 36
10 The Profiler Option.......................................................................................................................................... 36
Profile Components.......................................................................................................................................... 36
Profile Starting & Standard Segments.............................................................................................................. 37
Loops Segments............................................................................................................................................... 38
Profile Running / Holding vs. Hold Segments.................................................................................................. 39
The Auto-Hold Feature..................................................................................................................................... 39
Profile Cycles & Repeat Sequences................................................................................................................. 40
Power/Signal Lost Recovery Actions............................................................................................................... 40
Profile End Actions............................................................................................................................................ 41
Profile Abort Actions......................................................................................................................................... 41
iii
Contents
Page Number
11 Manually Tuning Controllers.......................................................................................................................... 42
Single Control Tuning (PID with Primary Output only)...................................................................................... 42
Dual Control Tuning (PID with Primary and Secondary Outputs)..................................................................... 43
PI Tuning (Valve, Damper & Speed Controllers)................................................................................................ 43
Fine Tuning........................................................................................................................................................ 45
12 Serial Communications.................................................................................................................................. 45
Supported Protocols......................................................................................................................................... 45
RS485 Configuration......................................................................................................................................... 45
Ethernet Configuration...................................................................................................................................... 45
Supported Modbus Functions.......................................................................................................................... 46
Function Descriptions....................................................................................................................................... 47
Exception Responses................................................................................................................................... 48
13 Modbus Parameters....................................................................................................................................... 49
Example Register Address Calculations....................................................................................................... 49
Universal Process Input Parameters................................................................................................................. 50
Option Slot A Parameters................................................................................................................................. 52
Option Slot B Parameters................................................................................................................................. 53
Option Slot 1 (Output 1) Parameters................................................................................................................ 54
Option Slot 2 (Output 2) Parameters................................................................................................................ 56
Option Slot 3 (Output 3) Parameters................................................................................................................ 60
Option Slot 4 (Output 4) Parameters................................................................................................................ 65
Setpoint Parameters......................................................................................................................................... 71
Control Parameters........................................................................................................................................... 73
Alarm parameters............................................................................................................................................. 75
Recorder & Clock Parameters.......................................................................................................................... 77
Display Parameters........................................................................................................................................... 80
Profiler Control & Status Parameters................................................................................................................ 84
Profile Setup Via Modbus................................................................................................................................. 86
Instrument Data.............................................................................................................................................. 102
14 Calibration..................................................................................................................................................... 103
Calibration Reminder...................................................................................................................................... 103
Equipment Required For Checking or Calibrating The Universal Input.......................................................... 103
Calibration Check........................................................................................................................................... 103
Recalibration Procedure................................................................................................................................. 103
15 Appendix 1 – Glossary of Terms Used........................................................................................................ 104
Active Setpoint................................................................................................................................................ 104
Actual Setpoint............................................................................................................................................... 104
Alarm Configuration........................................................................................................................................ 104
Alarm Operation.............................................................................................................................................. 107
Alarm Inhibit.................................................................................................................................................... 107
Alarm Types.................................................................................................................................................... 107
Alternative Setpoint........................................................................................................................................ 107
Auto Pre-Tune................................................................................................................................................. 107
Automatic Reset............................................................................................................................................. 107
Auxiliary Input................................................................................................................................................. 107
Auxiliary Input Lower Limit.............................................................................................................................. 107
Auxiliary Input Offset....................................................................................................................................... 107
Auxiliary Input Type......................................................................................................................................... 107
Auxiliary Input Upper Limit.............................................................................................................................. 108
iv
Contents
Page Number
Band Alarm Value............................................................................................................................................ 108
Bar Graphs...................................................................................................................................................... 108
Bias (Manual Reset)........................................................................................................................................ 108
Bumpless Transfer.......................................................................................................................................... 108
Cascade Control............................................................................................................................................. 108
Clock Configuration........................................................................................................................................ 109
Communications Write Enable....................................................................................................................... 109
Configuration Menu........................................................................................................................................ 109
Contactor........................................................................................................................................................ 109
Control Configuration...................................................................................................................................... 109
Control Deviation............................................................................................................................................ 109
Control Action................................................................................................................................................. 109
Control Enable/Disable................................................................................................................................... 109
Control Type.................................................................................................................................................... 109
Controller........................................................................................................................................................ 109
Controller Mode.............................................................................................................................................. 110
Correcting Variable......................................................................................................................................... 110
CPU .............................................................................................................................................................. 110
Current Proportioning Control........................................................................................................................ 110
Custom Display Mode.................................................................................................................................... 110
Cycle Time...................................................................................................................................................... 110
Data Recorder................................................................................................................................................. 110
Deadband....................................................................................................................................................... 110
Derivative Action............................................................................................................................................. 110
Deviation Alarm Value..................................................................................................................................... 110
Digital Input..................................................................................................................................................... 111
Direct Acting Control....................................................................................................................................... 111
Display Configuration...................................................................................................................................... 111
Display Languages.......................................................................................................................................... 111
Display Resolution.......................................................................................................................................... 111
Effective Setpoint............................................................................................................................................ 111
Engineering Units............................................................................................................................................ 111
Ethernet.......................................................................................................................................................... 111
Indicator.......................................................................................................................................................... 111
Input Configuration......................................................................................................................................... 111
Input Filter Time Constant.............................................................................................................................. 111
Input Range.................................................................................................................................................... 111
Input Span...................................................................................................................................................... 112
Integral Time Constant.................................................................................................................................... 112
Latching Relay................................................................................................................................................ 112
LED 1.............................................................................................................................................................. 112
Linear Input..................................................................................................................................................... 112
Linear Output.................................................................................................................................................. 112
Limit Controller................................................................................................................................................ 112
Local Setpoints............................................................................................................................................... 112
Lock Codes..................................................................................................................................................... 112
Logical Combination of Alarms....................................................................................................................... 112
Loop Alarm..................................................................................................................................................... 113
LSD .............................................................................................................................................................. 113
mADC............................................................................................................................................................. 113
Main Menu...................................................................................................................................................... 113
Manual Loop Alarm Time................................................................................................................................ 114
Manual Mode.................................................................................................................................................. 114
v
Contents
Page Number
Master & Slave Controllers............................................................................................................................ 114
Minimum Duration Of Change........................................................................................................................ 114
Modbus RTU................................................................................................................................................... 114
Modbus TCP................................................................................................................................................... 115
Modulating Valve............................................................................................................................................. 115
Multi-Point Scaling.......................................................................................................................................... 115
mVDC.............................................................................................................................................................. 115
On-Off Control................................................................................................................................................ 115
On-Off Differential (On-Off Hysteresis)............................................................................................................ 115
Operation Mode.............................................................................................................................................. 115
Output Configuration...................................................................................................................................... 116
Overlap/Deadband.......................................................................................................................................... 117
PD Control...................................................................................................................................................... 117
PI Control........................................................................................................................................................ 117
PID Control..................................................................................................................................................... 117
PLC .............................................................................................................................................................. 117
Pre-Tune.......................................................................................................................................................... 118
Power Output Limits....................................................................................................................................... 118
Primary Proportional Band.............................................................................................................................. 118
Process High Alarm n Value............................................................................................................................ 118
Process Input.................................................................................................................................................. 118
Process Low Alarm n Value............................................................................................................................ 118
Process Variable (PV)...................................................................................................................................... 118
Process Variable Offset................................................................................................................................... 118
Profile Control Menu....................................................................................................................................... 119
Profile Events.................................................................................................................................................. 119
Profile Header................................................................................................................................................. 119
Profile Segments............................................................................................................................................. 119
Profile Setup Menu......................................................................................................................................... 119
Profiler............................................................................................................................................................. 119
Profiler Mode.................................................................................................................................................. 119
Proportional Control........................................................................................................................................ 119
Rate .............................................................................................................................................................. 119
Rate Of Change Alarm.................................................................................................................................... 119
Recorder Configuration................................................................................................................................... 120
Recorder Option............................................................................................................................................. 120
Recorder Menu............................................................................................................................................... 120
Relay .............................................................................................................................................................. 120
Remote Setpoint (RSP)................................................................................................................................... 120
Retransmit Output.......................................................................................................................................... 120
Retransmit Output n Scale Maximum............................................................................................................. 120
Retransmit Output n Scale Minimum.............................................................................................................. 120
Reset To Defaults............................................................................................................................................ 121
Reverse Acting Control................................................................................................................................... 121
RS485............................................................................................................................................................. 121
RTD .............................................................................................................................................................. 121
Scale Range Upper Limit................................................................................................................................ 121
Scale Range Lower Limit................................................................................................................................ 121
Secondary Proportional Band......................................................................................................................... 122
Self-Tune......................................................................................................................................................... 122
Sensor Break Pre-Set Power.......................................................................................................................... 122
Serial Communications Configuration............................................................................................................ 122
Serial Communications Option....................................................................................................................... 122
vi
Contents
Page Number
Setpoint........................................................................................................................................................... 122
Setpoint Upper Limit....................................................................................................................................... 122
Setpoint Lower Limit....................................................................................................................................... 123
Setpoint Ramp Editing.................................................................................................................................... 123
Setpoint Ramp Rate....................................................................................................................................... 123
Setpoint Selection........................................................................................................................................... 123
Setup Wizard.................................................................................................................................................. 123
Solid State Relay (SSR)................................................................................................................................... 123
Solenoid Valve................................................................................................................................................ 123
Supervisor Mode............................................................................................................................................. 124
Thermocouple................................................................................................................................................. 124
Three Point Stepping Control......................................................................................................................... 124
Time Proportioning Control............................................................................................................................. 124
Trend Display.................................................................................................................................................. 124
Tuning............................................................................................................................................................. 124
Tuning Menu................................................................................................................................................... 124
Triac .............................................................................................................................................................. 125
USB Menu....................................................................................................................................................... 125
Valve Motor Drive Control (VMD).................................................................................................................... 125
VDC .............................................................................................................................................................. 125
VMD .............................................................................................................................................................. 125
16 PC SOFTWARE.............................................................................................................................................. 126
Using The Software........................................................................................................................................ 126
Instrument Configuration................................................................................................................................ 127
Profile Creation And Editing............................................................................................................................ 128
Changing the Start-up Splash Screen............................................................................................................ 130
Changing the Alternate Display Language..................................................................................................... 130
Instrument Simulation..................................................................................................................................... 130
Configuring The Connection........................................................................................................................... 130
Network Configuration For Modbus TCP Options.......................................................................................... 132
17 Appendix 2 - Specifications......................................................................................................................... 134
Universal Process Input.................................................................................................................................. 134
General Input Specifications....................................................................................................................... 134
Thermocouple Input.................................................................................................................................... 134
Resistance Temperature Detector (RTD) Input........................................................................................... 135
DC Linear Input........................................................................................................................................... 135
Auxiliary Inputs................................................................................................................................................ 136
Digital Inputs................................................................................................................................................... 136
Output Specifications..................................................................................................................................... 137
Communications............................................................................................................................................. 139
Display............................................................................................................................................................ 139
Control Loop................................................................................................................................................... 140
Data Recorder Option..................................................................................................................................... 140
Alarms............................................................................................................................................................. 140
Profiler Option................................................................................................................................................. 141
Conditions For Use......................................................................................................................................... 141
Standards....................................................................................................................................................... 142
Dimensions..................................................................................................................................................... 142
18 Appendix 3 - Product Coding....................................................................................................................... 143
vii
How to use this manual
This manual is structured to give easy access to the information required for all aspects of the installation and use
and of the Graphical Controller. The main sections are shown here, followed by a full table of contents.
Section 1:
Introduction - A brief description of the product and its features.
Section 2:
Installation - Unpacking, installing and panel mounting instructions.
Section 3:
Field Upgrade Options - Installation of the plug-in option modules.
Section 4:
Wiring Instructions - Guidance on good wiring practice, noise avoidance, wiring diagrams and
input/output connections.
Section 5:
Powering Up - Powering up procedure and descriptions of displays & switches.
Section 6:
Messages & Error Indications - Display Messages and fault indications.
Section 7:
Configuration & Use - Describes operating and configuration modes available. These include Operation
Mode; the Main and Configuration menus; the Easy Setup Wizard; Supervisor Mode; Automatic tuning;
Product and Service Information. Also available on some models are menus to setup the USB, Data Recorder and Profiler features.
Section 8:
The USB Interface Option – Describes uploading or downloading of instrument settings, profiles
or recorder logs to a USB memory stick.
Section 9:
The Data Recorder Option – Describes the Data recorder feature. This allows process data to
be stored in to memory for later download and analysis.
Section 10:
The Profiler Option – Describes the Profiler feature. A profile controls the value of the setpoint
over time; increasing, decreasing or holding its value as required.
Section 11:
Manually Tuning Controllers - Advice on manually adjusting the controller to the process
characteristics.
Sections 12:
Serial Communications - Details the physical layer and message formats used for the RS485
and Ethernet communications options.
Sections 13:
Modbus Parameters - Details the parameter addresses and data formats used for the Modbus
RTU and TCP communications protocols.
Section 14:
Calibration - Step-by-step instructions to calibrate the instrument. This section is intended for
use by suitably qualified personnel.
Appendix 1:
Glossary - Explanations of the terms used and product features.
Appendix 2:
PC Software – Using the software suite.
Appendix 3:
Specifications - Technical specifications for all products in the range.
Appendix 4:
Product Coding - Product model/ordering codes.
viii
1 Introduction
This product is a 1/4 DIN size (96 x 96mm front) microprocessor based graphical process controller, featuring
a 160 x 80 pixel, monochrome LCD with a dual color
(red/green) backlight. It can control process variables
from a variety of sources such as temperature, pressure, flow and level.
Inputs are user configurable for thermocouple and RTD
probes, as well as linear process signal types such as
mVDC, VDC or mADC. Multipoint scaling can compensate for non-linear signals. Output options include
relays, SSR drivers, triacs or linear mV/voltage modules. These can be used for process control, alarms
or retransmission of the process variable or setpoint
to external devices. Transmitter Power Supply options
can provide an unregulated 24V DC (22mA) auxiliary
output voltage, or a 0 to 10VDC stabilised excitation for
external signal transmitters.
The operating voltage is either 100-240V at 50/60 Hz or
24V-48V AC/DC depending on the model purchased.
Optional features include a USB interface, RS485 or
Ethernet communications, profile controlling and data
recording. Non-volatile memory protects against data
or configuration loss during power outages. If the unit
is left un-powered, a lithium battery powers the data
recorder’s real-time clock for a minimum of one year.
Alarm indication is standard on all instruments; up
to five alarms can be defined. Alarms may be set as
process high or low, deviation (active above or below
controller setpoint), band (active both above and below
setpoint), rate of input change, control loop or signal
break types. Alarm status can be indicated by lighting
an LED, changing the display backlight color or viewing
the alarm status screen. These alarms can be linked to
any suitable output.
The USB Interface option allows uploading or downloading instrument configuration settings to/from a
USB memory stick, for easy configuration of multiple
instruments or transfer to/from the PC configuration
software. If the Data Recorder of Profiler options are
fitted, recordings and profile information can also be
transferred via the memory stick.
The controller can be programmed for on-off, time
proportioning, or current proportioning control implementations, depending on the output modules fitted,
and feature manual or automatic tuning of the PID parameters. A secondary control output is available when
additional output modules are fitted. Optional analog
Remote Setpoint inputs can be included. Configuration
of the major settings is made easy by a Setup Wizard
that runs automatically at first ever power-up or whenever option modules have been changed. Access to
the full range of parameters is via a simple menu driven
front panel interface, or the PC based configuration
software.
The Data Recorder option allows the user to make recordings of the process over time. Recordings can be
transferred to a memory stick using the USB Port or
downloaded using one of the communications options.
The Profiler option allows the user to predefine up 255
segments, shared amongst up to 64 Setpoint Profiles.
These control the setpoint level over time, increasing,
decreasing or holding its value as required. When combined with the real-time clock of the Data Recorder option, the profiling capabilities are expanded to allow
automatic program start at a defined time and day.
2 Installation
Unpacking
Installation
1. Remove the product from its packing. Retain the
packing for future use, in case it is necessary to
transport the instrument to a different site or to return it to the supplier for repair/testing.
Installation should be only performed by technically competent personnel. It is the responsibility of the installing engineer to ensure that
the configuration is safe. Local Regulations
regarding electrical installation & safety must
be observed (e.g. US National Electrical Code
(NEC) or Canadian Electrical Code).
2. The instrument is supplied with a panel gasket and
push-fit fixing strap. Concise manual(s) are supplied
with the instrument, in one or more languages. Examine the delivered items for damage or defects. If
any are found, contact your supplier immediately.
1
Instruments may be mounted side-by-side in a multiple installation, but instrument to panel moisture and
dust sealing will be compromised. Allow a 20mm gap
above, below and behind the instrument for ventilation.
The cut-out width (for n instruments) is:
(96n - 4) mm or (3.78n - 0.16) inches
If panel sealing must be maintained, mount each instrument into an individual cut-out with 6mm or more
clearance between the edges of the holes.
Note: The mounting clamp tongues may engage the
ratchets either on the sides or the top/bottom faces of
the Instrument housing. When installing several Instruments side-by-side in one cut-out, use the ratchets on
the top/bottom faces.
Figure 1. Main dimensions
Ensure the inside of the panel remains within
the instrument operating temperature and that
there is adequate airflow to prevent overheating.
Do not remove the panel gasket, as this may
result in inadequate clamping and sealing of
the instrument to the panel.
Once the instrument is installed in its mounting panel,
it may be subsequently removed from its housing, if
necessary, as described in the Fitting and Removing
Option Modules section.
Figure 1. Main dimensions
Figure 1. Main dimensions
Panel-Mounting
Cleaning
The mounting panel must be rigid and may be up to
6.0mm (0.25 inches) thick. The cut-out size is:
Clean the front panel by washing with warm soapy
water and dry immediately If the USB option is fitted,
close the USB port cover before cleaning.
92mm x 92mm (+0.5mm / -0.0mm).
Gasket
Slide mounting clamp over
the instrument housing
Mounting Panel
towards rear face of
Clamp
mounting panel until the
tongues engage in ratchets
Ratchets
and instrument is clamped in
Instrument
Housing
position.
Hold instrument firmly in
position (apply pressure to
bezel only)
Figure 2. Panel-Mounting the instrument
2
3 Field Upgrade Options
Options Modules and Functions
Board Mounting Struts
Option 4 (Output 4) Module
The available plug-in modules, options and accessories are shown in below:
Option A Module
Option 3 (Output 3) Module
Note: Modules can be either pre-installed at the time of
manufacture, or retrofitted in the field.
Universal Input Board
Power Supply Board
Note: Field replacement of plug-in modules is easily
done via this Instruction manual. However, without having the ability to perform a full factory validation test
after the replacement, the warranty becomes voided.
Option B Module
Option 1 (Output 1) Module
(hidden below B)
Option 2 (Output 2) Module
Option C Module
Plastic pegs prevent fitting of older non-reinforced single relay modules (Board Identification Numbers 637/01 and 638/01). Fitting the
older relay modules reduces the isolation rating to Basic 240V Isolation and is therefore not
recommended. Remove this peg when fitting
Dual Relay Modules.
Figure 3. Rear view (uncased) & board positions
Note: All dual relay modules have reinforced isolation.
Table 1. Options and Accessories
PART
NUMBER
DESCRIPTION
BOARD
IDENTIFICATION NUMBER
OPTION SLOT
(Output) 1
0149-50043
Single Relay Output for option slot (Output) 1
716/01
0149-50044
Single SSR Driver Output for option slot (Output) 1
716/02
0149-50077
Triac Output for option slot (Output) 1
716/03
0149-50047
Linear mA / Voltage Output module for option slot (Output) 1
639/01
0149-50050
Single Relay Output for option slot (Output) 2 or 3
717/01
0149-50049
Dual Relay Output for option slot (Output) 2 or 3
644/01
0149-50051
Single SSR Driver Output for option slot (Output) 2 or 3
717/02
0149-50052
Dual SSR Driver Output for option slot (Output) 2 or 3
644/02
0149-50070
Triac module Output for slot (Output) 2 or 3
647/01
0149-50047
Linear mA / Voltage Output for option slot (Output) 2 or 3
640/01
0149-50053
24VDC Transmitter Power Supply for option slot (Output) 2 or 3
642/01
0149-50056
Digital Input for option slot A
641/02
0149-50057
Basic Auxiliary Input for option slot A
653/01
0149-50055
RS485 Serial Communications for option slot A
680/01
0149-50058
Ethernet Communications for option slot A
707/01
Full Auxiliary Input (inc digital input B) for option slot B
641/01
4-Relay Output for option slot (Output) 4
703/01
OPTION SLOT
(Output) 2 or 3
OPTION SLOT A
OPTION SLOT B
0149-50059
OPTION SLOT
(Output) 4
0149-50054
ACCESSORIES
0149-50063
Profiler Enable Key-code
0149-50061
Chromalox DIN Configuration Software & Lead
3
Preparing to Install or Remove Options
Modules
slots cut into the main boards, opposite each of the
connectors. Hold the Power and Input boards together and relocate them back on their mounting struts.
4. Remove or replace the Slot C and 4 modules as required.
Before removing the instrument from its housing, ensure that all power has been removed from the rear
terminals. Any repair or modification done on the controller is subject to the requirements of the jurisdiction.
The jurisdiction can be defined as plant safety or chief
engineer, city, county or state electrical inspector, etc.
Modules / boards should only be replaced by a trained
and qualified technician per the latest edition of the
NEC (National Electric Code).
5. Push the boards forward to ensure correct connection to the front Display/CPU board.
Check for correct orientation of the modules
and that all pins are located correctly.
Replacing the Instrument in its Housing
1. Remove the instrument from its housing by gripping
the edges of the front panel (there is a finger grip on
each edge) and pull the instrument forwards. This
will release the instrument from the rear connectors
in the housing and will give access to the boards.
Before replacing the instrument in its housing,
ensure that all power has been removed from
the rear terminals.
2. Take note of the orientation of the instrument for subsequent replacement into the housing. The positions
of the boards in the instrument are shown above.
With the required option modules correctly located
into their respective positions the instrument can be
replaced into its housing as follows:
Main Board Connectors
POWER SUPPLY
BOARD
Transformer Color
Code
1. Hold the Power Supply and Input boards together.
2. Align the boards with the guides in the housing.
Option Slot (Output) 3
Connector PL4B
3. Slowly and firmly, push the instrument in position.
Option Slot A
Connectors PL5, & PL6
100-240V (Yellow)
24-48V(Blue)
Option Slot (Output) 1
Connectors PL7 & PL8
Ensure that the instrument is correctly orientated. A mechanical stop will operate if an
attempt is made to insert the instrument in
the wrong orientation, this stop MUST NOT be
over-ridden.
PC Configurator
Socket SK1
Display Board
Connections
Option Slot (Output) 2
Connector PL4A
UNIVERSAL INPUT
BOARD
Auto Detection of Option Modules
Option Slot B
Connectors PL2A, PL2B &
PL2C
The instrument automatically detects which option
modules have been fitted into each slot.
The menus and screens change to reflect the options
compatible with the hardware fitted. The modules fitted can be viewed in the products information menu,
as detailed in the Product Information Mode section of
this manual.
Figure 4. Main board connectors
Removing/Replacing Option / Output
Modules
Replacement of Power Supply or Input
Boards
1. To remove or replace modules in Option Slots (Outputs) 1, 2, 3 & Option Slots A or B, it is necessary to
detach the Power Supply and Input boards from the
front panel by lifting first the upper and then lower
mounting struts.
It is recommended that users change these boards
only if unavoidable.
1. Remove the instrument from its housing as detailed
above.
2. Remove or fit the modules to the connectors on the
Power Supply and Input boards. The location of the
connectors is shown below. Plastic pegs prevent
fitting of older non-reinforced single relay modules –
Remove the peg to fit dual relay modules
2. Remove all option modules.
3. Replace the Power Supply or Input board as required. Carefully observe the transformer color and
the case labelling to check the supply voltage
when replacing the power supply board.
3. Assemble the Power Supply and Input boards together. Tongues on each option module locate into a
4. Reassemble the unit in its case.
4
Profiler Enabling
5. If the input board has to be replaced, a full recalibration must be carried out before the instrument is
used. Refer to the calibration section of this manual
for instructions.
If you purchased a controller with the Profiler option
installed, these features will be enabled during manufacture.
Controllers supplied without the Profiler option installed can be upgraded in the field by purchasing a
licence code number from your supplier. A unique code
must be purchased to enable profiling on each controller that requires it.
Replacement of boards must be carried out by
a trained technician.
If the Power Supply board does not match the labelling, users may apply incorrect voltage resulting in irreparable damage.
Entering the Profiler Enable Code
Hold down the
“splash screen”.
and
keys during the power-up
Using the
or
keys, enter the 16-character licence code in the displayed screen. Press
to move
on to the next character. Press
to move back to the
previous character.
Data Recorder Board
If installed, the Data Recorder memory and Real Time
Clock (RTC) components are located on a plug-in
daughter board attached to the front Display/CPU
board.
Press
after entering the final character.
To confirm if profiling is installed in your instrument,
check the Controller Feature Information in Product Information mode.
Servicing of the Data Recorder/RTC circuit and
replacement of the lithium battery should only
be carried out by a trained technician.
4 Electrical Instructions
4. A separate isolation transformer to feed only the
instrumentation should be considered. The transformer can isolate the instrument from noise found
on the AC power input.
Installation should be only performed by technically competent personnel. It is the responsibility of the installing engineer to ensure that
the configuration is safe. Local Regulations
regarding electrical installation & safety must
be observed (e.g. US National Electrical Code
(NEC) or Canadian Electrical Code).
AC Power Wiring - Neutral (for 100 to 240V
AC versions)
It is good practice to ensure that the AC neutral is at or
near ground (earth) potential. A proper neutral will help
ensure maximum performance from the instrument.
Installation Considerations
Wire Isolation
Ignition transformers, arc welders, motor drives, mechanical contact relays and solenoids are examples of
devices that generate electrical noise in typical industrial environments. The following guidelines MUST be
followed to minimise their effects.
Four voltage levels of input and output wiring may be
used with the unit:
1. Analog input or output (for example thermocouple,
RTD, VDC, mVDC or mADC)
2. Relays & Triac outputs
1. If the instrument is being installed in existing equipment, the wiring in the area should be checked to
ensure that good wiring practices have been followed.
3. SSR Driver outputs
4. AC power
2. Noise-generating devices such as those listed
should be mounted in a separate enclosure. If this
is not possible, separate them from the instrument,
by the largest distance possible.
The only wires that should run together are
those of the same category.
3. If possible, eliminate mechanical contact relays and
replace with solid-state relays. If a mechanical relay
being powered by an output of this instrument cannot be replaced, a solid-state relay can be used to
isolate the instrument.
If any wires need to run parallel with any other lines,
maintain a minimum space of 150mm between them.
If wires MUST cross each other, ensure they do so at
90 degrees to minimise interference.
5
Use of Shielded Cable
All analog signals must use shielded cable. This will
help eliminate electrical noise induction on the wires.
Connection lead length must be kept as short as possible keeping the wires protected by the shielding. The
shield should be grounded at one end only. The preferred grounding location is at the sensor, transmitter
or transducer.
Noise Suppression at Source
Usually when good wiring practices are followed, no
further noise protection is necessary. Sometimes in
severe electrical environments, the amount of noise is
so great that it has to be suppressed at source. Many
manufacturers of relays, contactors etc supply ‘surge
suppressors’ which mount on the noise source. For
those devices that do not have surge suppressors supplied, Resistance-Capacitance (RC) networks and/or
Metal Oxide Varistors (MOV) may be added.
Figure 6. Contact noise suppression
Figure 6.
Contact noise suppression
Sensor Placement (Thermocouple or RTD)
If the temperature probe is to be subjected to corrosive
or abrasive conditions, it must be protected by an appropriate thermowell. The probe must be positioned to
reflect true process temperature:
Inductive coils:- MOVs are recommended for transient
suppression in inductive coils, connected in parallel
and as close as possible to the coil. Additional protection may be provided by adding an RC network across
the MOV.
1. In a liquid media - the most agitated area
2. In air - the best circulated area
The placement of probes into pipe work some
distance from the heating vessel leads to transport delay, which results in poor control.
For a two wire RTD a wire link should be used in place
of the third wire. Two wire RTDs must only be used with
lead lengths less than 3 meters. Use of three wire RTDs
is strongly recommended.
Figure 5. Transient suppression with inductive coils
Contacts:- Arcing may occur across contacts when
they open and close. This results in electrical noise as
well as damage to the contacts. Connecting a properly
sized RC network can eliminate this arc.
For circuits up to 3 amps, a combination of a 47 ohm
resistor and 0.1 microfarad capacitor (1000 volts) is
recommended. For circuits from 3 to 5 amps, connect
two of these in parallel.
6
Thermocouple Wire Identification Chart
The table below shows the wire and sheath colors used
for most common thermocouple types. The format
used in this table is:
+ Wire
Sheath
- Wire
The different thermocouple types are identified by their
wires color, and where possible, the outer insulation as
well. There are several standards in use throughout the
world.
Table 2. Thermocouple Extension Wire Colors
Table 2. Thermocouple Extension Wire Colors
International
USA ANSI
British
IEC584-3
MC 96.1
BS1843
Type
Type J
J
+*
T
International
+* Black
IEC584-3
Black
T White
+
Brown
- K White
K
+
Green
-*N White
N
+
Pink
- B White
B
+
Grey
-R & S
White
R&S
+
-
C
(W5)
Orange
C (W5)
White
Note:
+
-
-
White
Brown
+Black
-
White
Brown
+ Green
-*
White
+ Pink
Green
-
White
+PinkGrey
-
White
USA ANSI
White
MC 96.1
Black
White
Red
Brown
Blue
Green
Red
Yellow
Pink
Red
Orange
Grey
Red
Orange Grey
+Grey
-
White
Orange
Red
+
Black
-
Red
Orange
White
* = Wire is magnetic
Red
British
Yellow
BS1843
Black
Red
Yellow
Black
Blue
Blue
Blue
Red
White
Blue
Yellow
Yellow
Blue
Red
Brown
Orange
Yellow
Red
Grey
Orange
Orange
Blue
Orange
Red
Black
Grey
Red
Grey
Blue
Green
White
White
Red
Blue
Green
White
Blue
Black
White
Blue
Blue
Brown
Blue
Orange
Red
Blue
French
NFC 42-324
German
DIN 43710
Black
Blue
French
Yellow
NFC
Black 42-324
Yellow
Black
Blue
Yellow
Red
Blue
Yellow
Orange
Purple
Black
Yellow
Blue
Blue
Yellow
Purple
Yellow
German
Red
DIN
43710
Black
Red
Blue
Blue
Red
Yellow
Brown
Red
Green
Blue
Red
Brown
Brown
Red
Green
Blue
Brown
Green
Green
Red
Orange
Grey
Grey
White
Blue
Green
Green
Yellow
Green
Yellow
Green
Green
Red
Green
Grey
Red
White
Red
Grey
White
White
White
White
*Wire is magnetic
Connections and Wiring
TO AVOID ELECTRICAL SHOCK, AC POWER
WIRING MUST NOT BE CONNECTED TO THE
SOURCE DISTRIBUTION PANEL UNTIL ALL WIRING PROCEDURES ARE COMPLETED. CHECK
THE INFORMATION LABEL ON THE CASE TO
DETERMINE THE CORRECT VOLTAGE BEFORE
CONNECTING TO A LIVE SUPPLY.
This symbol means the equipment is protected throughout by double insulation.
Note: The wiring diagram on the next page shows all
possible combinations to the main connections (numbered 1 to 24) in the centre of the case rear. The actual
connections required depend upon the features available on the model and the modules and options fitted.
All external circuits connected must provide
double insulation. Failure to comply with the
installation instructions may impact the protection provided by the unit.
7
Output 3 / Option Slot 3
Output 1 / Option Slot 1
Output 2 / Option Slot 2
Figure 7. Main Rear terminals
Note: The wiring diagram shows the additional connections (numbered 25 to 42) at the sides of the case
rear. These are required for Options Slots 4 (Output 4)
and C if fitted.
input, where the correct thermocouple or compensating cable and connectors must be used.
Power Connections
Output 4 / Option Slot 4
Power Connections - Mains Powered Instruments
Mains powered instruments operate from a 100 to 240V
(±10%) 50/60Hz supply. Power consumption is 24VA.
Connect the line voltage (live and neutral) as illustrated
via a two-pole IEC60947-1 & IEC60947-3 compliant
isolation switch / circuit breaker and a UL listed fuse
type: 250V AC 1Amp anti-surge. If the instrument has
relay outputs with contacts carrying mains voltage, it is
recommended that the relay contacts supply should be
switched and fused in a similar manner, but should be
separate from the instruments mains supply.
Figure
8. 8.Additional
Option
terminals
Figure
Additional Option
terminals
Note: Use single strand (1.2mm / AWG18 max size)
copper wire throughout, except for the thermocouple
8
Universal Input Connections
13
L
14
N
Universal Input Connections - Thermocouple (T/C)
Use only the correct thermocouple wire or compensating cable from the probe to the instrument terminals
avoiding joints in the cable if possible. Where joints are
made, special thermocouple connectors must be used.
Failure to use the correct wire type and connectors will
lead to inaccurate readings. Ensure correct polarity of
the wires by cross-referencing the colors with a thermocouple reference table.
Figure 9. Mains Power Connections
CHECK THE INFORMATION LABEL ON THE
CASE TO DETERMINE THE CORRECT VOLTAGE
BEFORE CONNECTING TO A LIVE SUPPLY.
This equipment is designed for installation
in an enclosure that provides adequate protection against electric shock. The isolation
switch should be located in close proximity to
the unit, in easy reach of the operator and appropriately marked.
14
+
Figure 10.
2
+
For three wire RTDs, connect the resistive leg and the
common legs of the RTD as illustrated. For a two wire
RTD a wire link should be used in place of the third wire
(shown by dotted line). Two wire RTDs should only be
used when the leads are less than 3 metres long. Avoid
cable joints.
24/48V AD/DC powered instruments will operate from
a 20 to 48V AC or 22 to 55V DC supply. AC power
consumption is 15VA max, DC power consumption is
12 watts max. Connection should be via a two-pole
IEC60947-1 & IEC60947-3 compliant isolation switch /
circuit breaker and a UL listed fuse type: 65v dc 1Aamp
anti-surge.
_
_
Figure 11. Thermocouple Input Connections
Universal Input Connections – PT100 /
NI120 (RTD) input
Power Connections - 24/48V AC/DC Powered Instruments
13
3
3
2
1
Figure 12.
24/48V AC/DC Power Connections
RTD
RTD Input Connections
Four wire RTDs can be used, provided that the fourth
wire is left unconnected. This wire should be cut short
or tied back so that it cannot contact any of the terminals on the rear of the instrument.
CHECK THE INFORMATION LABEL ON THE
CASE TO DETERMINE THE CORRECT VOLTAGE
BEFORE CONNECTING TO A LIVE SUPPLY.
This equipment is designed for installation
in an enclosure that provides adequate protection against electric shock. The isolation
switch should be located in close proximity to
the unit, in easy reach of the operator and appropriately marked.
9
Universal Input Connections - Linear Volt,
mV or mA input
19
Linear DC voltage, millivolt or milliamp input connections are made as illustrated. Carefully observe the polarity of the connections.
2
_
+
+
21
mV/V
+
Figure 15.FigureOption
SlotSlot
1 / 1Output
1 1––Single
SSR Driver Mod
15. Option
/ Output
Single SSR
_
1
Figure 13.
20
Driver Module
Option Slot 1 / Output 1 - Triac Output
Module
mA
3
_
If Option Slot 1 / Output 1 is fitted with a Triac output
module, make connections as shown. This output is
rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber
should be fitted across inductive loads to ensure reliable switch off the Triac.
DC Volt, mV & mA Input Connections
Option Slot 1 / Output 1 Connections.
NOTE: Option Slot 1 and Output 1 are interchangeable
terms for the same connection.
20
Option Slot 1 / Output 1 – Single Relay
Output Module
If Option slot 1 / Output 1 is fitted with a single relay
output module, make connections as illustrated. The
relay contacts are SPDT and rated at 2 amps resistive,
240 VAC.
19
N/C
20
COM
21
N/O
21
Figure
16.
Option
1 / Output
1 -Module
Triac Module
Figure
16. Option
SlotSlot
1 / Output
1 - Triac
Option Slot 1 / Output 1 - Linear Voltage
or mADC Output module
If Option Slot 1 / Output 1 is fitted with a DC linear output module, make connections as illustrated.
Option Slot 1 / Output 1 - Linear Voltage & mADC
Module
19
Figure 14. Figure
Option
Slot 1Slot
/ Output
1 –1 Single
Relay Module
14. Option
1 / Output
–
Single Relay Module
Option Slot 1 / Output 1 – Single SSR
Driver Output Module
20
21
If Option Slot 1 / Output 1 is fitted with a single SSR
driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal, load
impedance must be no less than 500 ohms. SSR driver
outputs are not isolated from the signal input or other
SSR driver outputs.
_
+
Option Slot 2 / Output 2 Connections.
NOTE: Option Slot 2 and Output 2 are interchangeable
terms for the same connection.
10
Option Slot 2 / Output 2 – Single Relay
Output Module
22
If Option Slot 2 / Output 2 is fitted with a single relay
output module, make connections as illustrated. The
relay contacts are SPDT, and rated at 2 amps resistive,
240 VAC.
22
N/C
23
COM
24
N/O
_
23
24
+
FigureOption
19. Option
/ Output22–– Single
Single SSR
Figure 19.
SlotSlot
2 /2Output
SSR Driver Mod
Driver Module
Option Slot 2 / Output 2 – Dual SSR Driver
Output Module
17. Option
2 / Output
– SingleRelay Module
Figure 17. Figure
Option
Slot 2Slot
/ Output
2 –2Single
If Option Slot 2 / Output 2 is fitted with a dual SSR
driver output module, make connections as illustrated.
The solid-state relay drivers are a 0-10V DC signal,
load impedance must be no less than 500 ohms. SSR
driver outputs are not isolated from the signal input or
other SSR driver outputs.
Relay Module
Option Slot 2 / Output 2 - Dual Relay
Output Module
If Option Slot 2 / Output 2 is fitted with a dual relay
output module, make connections as illustrated. This
module has two independent SPST relays, which share
a common connection terminal. The contacts are rated
at 2 amp resistive 240 VAC.
22
23
24
N/O OUTPUT 2B
COMMON
22
- OUTPUT 2A
23
- OUTPUT 2B
24
+ COMMON
20. Option
2 / Output
2 –Dual
Dual SSR
SSR Driver Modu
Figure 20.FigureOption
Slot Slot
2 / Output
2–
Driver Module
N/O OUTPUT 2A
Option Slot 2 / Output 2 - Triac Output
Figure
Slot
2 / Output
2 - Dual
Figure
18.18.Option
Option
Slot
2 / Output
2 -Relay
DualModule
Relay Module
Module
If Option Slot 2 / Output 2 is fitted with a Triac output
module, make connections as shown. This output is
rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber
should be fitted across inductive loads to ensure reliable switch off the Triac.
Option Slot 2 / Output 2 – Single SSR
Driver Output Module
If Option Slot 2 / Output 2 is fitted with a single SSR
driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal, load
impedance must be no less than 500 ohms. SSR driver
outputs are not isolated from the signal input or other
SSR driver outputs.
23
24
Figure
Option Slot
2 - Triac
Module
Figure
21. 21. Option
Slot2 /2Output
/ Output
2 - Triac
Module
11
Option Slot 2 / Output 2 - Linear Voltage
or mADC Output module
If Option Slot 2 / Output 2 is fitted with a DC linear output module, make connections as illustrated.
_
22
23
10
N/C
11
COM
12
N/O
FigureOption
24. Option
/ Output33–– Single
Single Relay
Figure 24.
SlotSlot
3 / 3Output
Relay Module
24
Module
+
Option
Slot 3 / Output 3 - Dual Relay
22. Option
2 / Output
- LinearVoltage
Voltage & mADC
Figure 22. Figure
Option
Slot 2Slot
/ Output
2 -2Linear
module
& mADC module
Output Module
igure 23.
If Option Slot 3 / Output 3 is fitted with a dual relay
output module, make connections as illustrated. This
module has two independent SPST relays, which share
a common connection terminal. The contacts are rated
at 2 amp resistive 240 VAC.
Option Slot 2 / Output 2 - Transmitter
Power Supply Module
If Option Slot 2 / Output 2 is fitted with a transmitter
power supply module, make connections as illustrated.
The output is an unregulated 24V DC, 22mA supply.
22
_
23
24
+
10
N/O OUTPUT 3B
11
COMMON
12
N/O OUTPUT 3A
Option Slot 3 / Output 3 - Dual Relay Module
FigureFigure
25. 25.Option
Slot 3 / Output 3 - Dual Relay Module
Figure 23.
Option
Slot 2 / 2Output
2 - Transmitter
Option
Slot 3 / Output 3 – Single SSR
Option
Slot
2 / Output
- Transmitter
Power Supply
Module
Power Supply Module
Driver Output Module
If Option Slot 3 / Output 3 is fitted with a single SSR
driver output module, make connections as illustrated.
The solid-state relay driver is a 0-10V DC signal, load
impedance must be no less than 500 ohms. SSR driver
outputs are not isolated from the signal input or other
SSR driver outputs.
Option Slot 3 / Output 3 Connections.
NOTE: Option Slot 3 and Output 3 are interchangeable
terms for the same connection.
Option Slot 3 / Output 3 – Single Relay
Output Module
10
If Option Slot 3 / Output 3 is fitted with a single relay
output module, make connections as illustrated. The
relay contacts are SPDT, and rated at 2 amps resistive,
240 VAC.
_
11
12
+
26. Option
3 / Output
– SingleSSR
SSR Driver Modu
Figure 26. Figure
Option
Slot 3Slot
/ Output
3 –3Single
Driver Module
12
Option Slot 3 / Output 3 – Dual SSR Driver
Output Module
Option Slot 3 / Output 3 - Transmitter
Power Supply Module
If Option Slot 3 / Output 3 is fitted with a dual SSR
driver output module, make connections as illustrated.
The solid-state relay drivers are a 0-10V DC signal,
load impedance must be no less than 500 ohms. SSR
driver outputs are not isolated from the signal input or
other SSR driver outputs.
If Option Slot 3 / Output 3 is fitted with a transmitter
power supply module, make connections as illustrated.
The output is an unregulated 24V DC, 22mA supply.
_
10
10
- OUTPUT 3A
11
11
- OUTPUT 3B
12
12
+ COMMON
Figure 30.
+
Figure 30.
Option
Slot 3 / Output
3 - Transmitter
Option
Slot
3 / Output
3 - Transmitter
Power Supply M
Power Supply Module
OptionSlot
Slot 3
– Dual
SSRSSR
DriverDriver Module
FigureFigure
27. 27.
Option
3 // Output
Output3 3
– Dual
Option Slot A Connections
Module
Option Slot A Connections – Basic Auxiliary Input Module
Option Slot 3 / Output 3 - Triac Output
Module
If option slot A is fitted with a basic auxiliary input module, connect as shown. Consider using the full auxiliary
input (Option Slot B) instead, as this has additional features and leaves option slot A free for other modules.
If Option Slot 3 / Output 3 is fitted with a Triac output
module, make connections as shown. This output is
rated at 0.01 to 1 amp @ 280V AC 50/60Hz. A snubber
should be fitted across inductive loads to ensure reliable switch off the Triac.
10
11
16
+
17
_
Figure
Option Slot
– Basic
Auxiliary
Input Module
Figure
31. 31.Option
SlotA A
– Basic
Auxiliary
Input Module
Figure
Option Slot
3 - Triac
Module
Figure
28. 28. Option
Slot3 /3Output
/ Output
3 - Triac
ModuleOption Slot A Connections - Digital Input
A Module
If a digital input module is fitted in option slot A, this
may be connected to either voltage free contacts (e.g.
switch or relay), or a TTL compatible voltage. Connections are shown below.
Option Slot 3 / Output 3 - Linear Voltage
or mADC Output module
If Option Slot 3 / Output 3 is fitted with a DC linear output module, make connections as illustrated.
10
_
11
12
16
+
17
_
FigureFigure
32. 32.Option
Digital
Input
A Module
Option Slot
Slot AA––Digital
Input
A Module
+
29. Option
3 / Output
- LinearVoltage
Voltage && mADC module
Figure 29.Figure
Option
Slot Slot
3 / Output
3 -3Linear
mADC module
13
Option Slot B Connections
Option Slot A Connections - Ethernet
Communications Module
Option Slot B Connections – Digital Input
B (Full Auxiliary Module)
If option slot A is fitted with the Ethernet communication module, a standard RJ45 connector is accessible
from the top of case. No rear connections are required.
If option slot B is fitted with the Full Auxiliary input
module (see below), a secondary digital input is also
provided. This may be connected to the voltage free
contacts of a switch or relay, or to a TTL compatible
voltage.
Option Slot A Connections - RS485 Serial
Communications Module
If option slot A is fitted with the RS485 serial communication module, connections are as illustrated. Carefully
observe the polarity of the A (Rx/Tx +ve) and B (Rx/Tx
-ve) connections.
16
Figure 33.
A
17
B
18
COM
9
+
8
_
OptionSlot
Slot B
Input
B Connections
FigureFigure
34. 34.Option
B ––Digital
Digital
Input
B Connections
RS485
Option Slot B Connections – Full Auxiliary
Input B Module
If option slot B is fitted with full auxiliary input feature,
input connections are as shown.
Figure 33. Option Slot A – RS485 Serial
Option Slot
A – RS485Module
Serial Communications Module 7
Communications
+
(or Pot Low)
6
_
(or Pot Wiper)
External computing devices connected to the
communications port should comply with the
standard, UL 60950.
5
(or Pot High)
FigureOption
35. Option
– Full
AuxiliaryInput
Input Connections
Figure 35.
SlotSlot
B –BFull
Auxiliary
Connections
5 Powering Up
the LED indicators are lit. At the first power up from
new, or if the option modules are changed, the Setup
Wizard will run, indicating that configuration is required
(refer to the Setup Wizard section of this manual). At all
other times, the instrument returns to Operation Mode
once the self-test procedure is complete.
Ensure safe wiring practices have been followed. When powering up for the first time,
disconnect the output connections.
The instrument must be powered from a supply according to the wiring label on the side of the unit. The
supply will be either 100 to 240V AC, or 24/48V AC/DC
powered. Check carefully the supply voltage and connections before applying power.
Front Panel Overview
The illustration below shows the instrument front panel.
A USB socket fitted to USB and Data Recorder versions, to the right of the keypad.
Powering Up Procedure
Clean the front panel by washing with warm soapy
water and dry immediately If the USB option is fitted,
close the USB port cover before cleaning.
At power up, a self-test procedure is automatically
started, during which a splash screen is displayed and
14
play Configuration section for more details). The top
line of the display has labels for the 4 LED indicators. If
desired, the backlight color can be changed to indicate
the presence of an active alarm.
LED Functions
There are four red LEDs that by default, indicate the
status of the primary and secondary control outputs,
automatic tuning and alarm status. The top line of the
graphical display has four labels for LED indicators.
The function of these LEDs and their display labels can
be changed using the PC configuration software. The
information in this manual assumes standard functions
for these LEDs.
Keypad
Each instrument has four keypad switches, which are
used to navigate through the user menus and adjust
the parameter values. In configuration screens, a context sensitive scrolling help text is displayed that guides
the user about the function of the keys.
Figure 36. Front panel and keys
Figure 36.
Front panel and keys
Display
The instrument has a 160 x 80 pixel monochrome
graphical display with dual color (red/green) backlight.
The main display typically shows the process variable
and setpoint values or a graphical trend during normal
operation. There are various bar graph, recorder status
and profile status information options (refer to the Dis-
Table 3. Keypad button functions
Table 3. Keypad button functions
Button
Function
Moves backwards to the previous parameter or screen in the current mode.
CAUTION: If editing a parameter, ensure that the current (highlighted) parameter value is correct before pressing the key as this action will update the instrument to the
value displayed.
In menus and configuration choice screens, this key moves to the next item on the list.
Editable values can be decreased by pressing this key. Holding the key down speeds up the change.
In Trend view this key moves the Cursor Line back through the stored data points
In menus and configuration choice screens, this key moves to the previous item on the list.
Editable values can be increased by pressing this key. Holding the key down speeds up the change.
In Trend view this key moves the Cursor Line forward through the stored data points
Moves forwards to the next parameter or screen in the current mode.
CAUTION: If editing a parameter, ensure that the current (highlighted) parameter value is correct before pressing the key as this action will update the instrument to the
value displayed.
Pressing the
key while holding down the
key causes the instrument to move up one menu
level. From Operation Mode and in most menus, this will result in entry to the Main Menu.
From sub-menus, it is necessary to carry out this sequence more than once to reach the main menu.
CAUTION: If editing a parameter, ensure that the current (highlighted) parameter value is correct before pressing the key as this action will update the instrument to the
value displayed.
15
6 Messages and Error Indicators
Start-up Errors
PV Over-range or Under-range Indication
The following displays are shown when an error detected during the power-up self-test.
If the measured process variable value is more than
5% above than the Scale Range Upper Limit, its value
is replace by the word “HIGH”.
Option Module Problems
If the measured process variable value is more than
5% below than the Scale Range Lower Limit, its value
is replace by the word “LOW”.
The “Option Slot n Error” display is shown when an error detected with the installed option modules - where
“n” is the slot number for the fault. Recall that Option
Slot n is the same as Output n.
Replace the module in slot “n”. If this does not solve
the problem, return the instrument for servicing.
Auxiliary Input Over-range or Under-range
Indication
Configuration Problem
If the auxiliary input (RSP) is more than 5% above than
the Auxiliary Input Upper Limit, its value is replace by
the word “HIGH”.
Warns if a problem has been detected with the instrument configuration. Check all settings are correct before proceeding. If the problem persists, return the instrument for servicing.
If the auxiliary input (RSP) is more than 5% below than
the Auxiliary Input Lower Limit, its value is replace by
the word “LOW”.
If you need to return your instrument for servicing,
check the Service Information screen (available from
the main menu) or contact your supplier.
Input Problems
Sensor Break Detection
Whenever a problem is detected with the process variable or auxiliary input connections, their displayed value is replaced with the word “OPEN”.
USB Data Transfer Problems
Data Transfer Failure message
This may be the result of a failed sensor, a broken connection or an input circuit fault.
In this condition, the Control Outputs go to the pre-set
power value (see Control Configuration).
If the instrument cannot successfully write to the USB
memory stick, the message “Data Transfer Failure” will
be displayed. Check that there is adequate disk space
on the memory stick, then retry.
Correct the signal/wiring problem to continue
normal operation.
If the instrument cannot successfully read data from
the USB memory stick, the message “Data Transfer
Failure” will also appear. Check that this operation
would not cause the maximum number of profiles and/
or segments to be exceeded, then retry.
Un-Calibrated Input Detection
The instrument is fully calibrated during manufacture.
If a fault occurs and the calibration data becomes corrupted, the process input display is replaced with the
word “ERROR”.
Getting Help
First Level Support
In this condition, the Control Outputs go to the pre-set
power value (see Control Configuration).
If the errors persist or other problems are encountered,
refer your supplier for first level support. This includes
help with configuration, tuning, servicing and replacement modules.
Re-calibrate the input before continuing normal operation. If the problem persists, return
the instrument for servicing.
Second Level Support
If your supplier is unable to assist or cannot be contacted, check the Service Information Page (in Configuration Mode) for details of whom to contact.
Third Level Support
If further assistance is required, contact the nearest company from those listed on the back page of this manual.
16
7 Configuration and Use
Operation Mode
Base, Trend & Profile Operating Screens
This is the mode used during normal operation of the
instrument. It can be accessed from the Main Menu,
and is the usual mode entered at power-up. The available displays are dependent upon the features and options fitted and the way in which it has been configured.
The Base screen is the usual screen displayed during
operation. It provides “at a glance” information about
the process. The Profile Operating screen shows similar information when using profiles. Trend View is a
graphical representation of recent process conditions.
Its scale adjusts automatically for the best resolution
for the visible data.
DURING NORMAL USE, THE USER MUST NOT
REMOVE THE CONTROLLER FROM ITS HOUSING OR HAVE UNRESTRICTED ACCESS TO THE
REAR TERMINALS, AS THIS WOULD PROVIDE
POTENTIAL CONTACT WITH HAZARDOUS LIVE
PARTS.
Note: Trend data is not retained at power down or if the
Sample Interval is changed.
Set all Configuration parameters as required
before starting normal operations. It is the responsibility of the installing engineer to ensure
that the configuration is safe for the intended
application.
Example Base Operating Screen
LED Indicators
LED Function Labels
Process Variable Value
Engineering Units
Actual Setpoint Value
Secondary Power,
Memory remaining or
-ve Deviation Bar Graph
Primary Power,
Memory remaining or
+ve Deviation Bar Graph
Example Trend View Screen
Trend Upper Scale Value
Active Alarm(s)
Cursor Line
Process Variable Trend
PV Value At Cursor Line
Setpoint Trend (dotted)
Trend Lower Scale Value
Time Markers
(10 samples per marker)
Sample Interval
(or Time At Cursor Line)
Example Profile Operating Screen
LED Indicators
LED Function Labels
Process Value & Setpoint
Engineering Units
Profile Name & Progress
Segment No. & Progress
Profile Status
Held,
17
Stopped
Table 4. Operation Mode Screens
Operation Mode:
After 2 minutes without key activity, the most screens revert to the Base Operating Screen. Screens marked
do not revert automatically. They remain displayed until the user navigates away.
Calibration Check Due
Warning
Shown if a Calibration Reminder is set and the due date has passed- if
the feature is enabled in Control Configuration. Recorder version only.
Shown at power up (and repeated once per day).
Press d to acknowledge and continue using the instrument.
Re-calibrate or disable the reminder to cancel the warning.
Base Operating Screen.
Displayed is:
LED Labels; PV value;
SP value & Bar Graph
LED Labels = LED indicator functions. Defaults are HEAT, COOL, TUNE
& ALARM - can be altered with configuration software
PV value = The current Process Variable value.
SP value = The current Setpoint value.
Bar Graph = Primary/Secondary Power; Deviation or Memory Use. see Bar Graph Format screen in Display Configuration.
Auto/Manual Control
Mode Selection
Allows switching between automatic and manual control modes.
Setpoint Value Display &
Adjustment
View and alter local (internal) setpoint(s) to any value between the Setpoint Upper and Lower Limits. Remote setpoints are read only.
Setpoint Ramp Rate
Setpoint Ramp Rate adjustment between 0.1 and 9999.0 Display Units
per hour. - only shown if enabled in Control Configuration.
Select Setpoint Source
Select if Local Setpoint 1 or the Alternate Setpoint is to be the active
setpoint. - only shown if enabled in Control Configuration.
Control Enable
Enables or disables control outputs. When disabled, the unit works normally except the Primary and Secondary Control Outputs are turned off
- only shown if enabled in Control Configuration.
Alarm Status
Shows the status (Active, Inactive or Unused) of the five alarms.
Event Status
Shows the status (Active or Inactive) of the five Events - Profiler version
only.
Profiler Operating Screen
LED Labels = LED indicator functions. Defaults are HEAT, COOL, TUNE
& ALARM - can be altered with configuration software
Displayed is:
LED Labels; PV value;
SP value; Bar Graph &
Status Indicator
– only shown if enabled in Control Configuration.
PV value = The current Process Variable value.
SP value = The current Setpoint value.
Bar Graph = The Profile Name & overall progress; the current Segment
Number and segment progress
Status Indicator =
4(Run), ;(Held), or g (Stopped).
- Profiler version only.
Operator Profile
Control
Allows the operator to control the defined profiles.
If a profile is running, the choices are: Do Nothing; Abort Profile (end
immediately); Jump to Next Segment; Hold Profile or Release Hold.
If no profile is running, the choices are: Do Nothing; Run Profile or End
Profile Control (returns to standard controller operation). - only shown if
enabled in the Profile Control Menu.
Profile Information
Shows the Profile Status (Running, Held, Aborted or Ended); Profile
Time Remaining, Cumulative Held Time; Cycles Completed and Profile
Sequences Completed - not shown when in Controller mode.
18
Segment Information
Shows the Current segment number and type (Ramp Up, Ramp Down,
Dwell, or End); Segment Time Remaining, Loops completed if loopback active- not shown when in Controller mode.
Start & Stop Data
Recording
Recorder Status
Information
Manually Stop or Start a new recording. – only shown if Recorder Log
Trigger is Operator Start/Stop.
The status of the data recorder. It shows if a recording is in progress;
the recording mode (FIFO or Record Until Memory Is Used); the memory usage for each recording sample; memory remaining (in bytes) and
the approximate* recording time remaining.
*If the status of alarms is recorded, extra samples are taken when these
alarms change state. Therefore recording time will reduce.
Trend View
An auto-scaling trend graph of the Process Variable; Process Variable
& Setpoint (doted line), or the Minimum and Maximum value of the Process Variable measured since the last sample. Any active alarm(s) are
indicated above the graph. 120 data points are visible. The user can
scroll the right hand cursor line back to examine up to 240 data points.
The sample interval is set in Display Configuration.
Recorder Memory
Full Warning
Custom Display
Screens
Indicates that the Data Recorder memory is full and that recording has
stopped – Only if Recording mode is Record Until Memory Full.
The user can copy up to 50 Configuration Menu parameters into Operation Mode using the PC software.
Note: In this mode these screens are not pass-code protected.
Note: The operator can freely use the screens in this mode, but it is possible to make the entire Operation Mode
“read only” from the Display Configuration sub-menu. This includes any custom screens.
Navigating in Operator Mode
Press
to move forward or
through the available screens.
Press
value.
to move backwards
When a displayed value can be adjusted, use
to change its value.
or
to adjust ramp rate to the required
Note: The SETPOINT ramp feature disables the pretune facility. The self-tune facility will calculate new
tuning terms only after the SETPOINT has completed
the ramp.
or
In Trend View, pressing
or
moves the Cursor
Line back through the last 240 data points.
Selecting Automatic or Manual Mode
Depending on the Control Configuration settings, an
Auto/Manual selection screen may be shown which allows operators to select between automatic or manual
control. Switching to or from manual mode is made via
Bumpless Transfer. In Manual mode the Setpoint display is replaced by a 0 to 100% power output level,
labelled “Man”.
Adjusting the Local Setpoint(s)
Setpoints can be adjusted within the limits set by the
Setpoint Upper and Lower Limit parameters in Control
Configuration. Operation Mode adjustment of Setpoint
is not possible if Read Only Operation Mode has been
selected in the Display Configuration settings.
Press
to select the Setpoint Value Display and Adjustment screen
Press
or
required value.
Press
to select the Manual Power screen
Press
or
quired value.
to adjust each Local Setpoint to the
to adjust required power to the re-
Note: In Manual mode a running profile will hold until
automatic control is reselected.
A Remote Setpoint value cannot be altered from the
key pad.
Adjusting the Setpoint Ramp Rate
The Setpoint Ramp Rate may be adjusted in the range
0.1 to 9999.0 (in display units per hour) and OFF. When
the Setpoint Ramp Rate is set to Off, setpoint changes
will step immediately to the new value.
Press
The Manual Mode power level can be adjusted
from 0 to 100% (-100 to +100% for dual control). It is not restricted by the Output Power
Limit parameters.
to select the Setpoint Ramp Rate screen
19
Control Enable or Disable
Mode and most other screens will cause the unit to enter the Main Menu. Each time this key press sequence
is made, the instrument moves to the next menu level
above. Sub-menu levels will require this sequence to
be pressed more than once in order to reach the Main
Menu.
Depending on the Control Configuration settings, a
Control Enable/Disable screen may be shown. Disabling control turns off all control outputs (Primary and
Secondary power output levels are set to zero).
Press
to select the Control Enable screen
Press
or
and disable.
Navigating the Main Menu
to change between control enable
Once in the Main Menu, press
required option
Press
to enter the chosen menu.
Unlock Codes
Main Menu
To prevent unauthorised entry, most modes require a
pass-code (1 to 9999) to gain entry. These modes are
indicated by the symbol against their names. The default unlock code for all modes is 10 and the current
codes can be viewed and changed from the Lock Code
View in Configuration Mode. For security, users should
to change the codes. If the Configuration Mode lock
code is lost, refer to the Lock code View section of this
manual.
This menu is used to access the various features and
configuration menus available in the instrument. The
available menus are dependent upon the features and
options fitted and the way in which it has been configured.
Entry into the Main Menu
and pressing
to select the
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
Use with care. The instrument is not able to
control the process when control is disabled.
The Output Power Lower Limit parameters are
also ignored.
Holding down
or
from Operation
Table 5: Main Menu Screens
Main Menu:
Operation Mode
Display of the process and setpoint values, selection/adjustment of
the Setpoints, auto/manual control, alarm/event status, trend view and
where available, data recorder and profile information.
Setup Wizard
Easy, step-by-step parameter setup for simple applications.
Supervisor Mode
If configured from the PC software, a sub-set of up to 50 Configuration
screens can be accessed.
Configuration Menu
Accesses the sub-menus for Input; Control; Outputs; Alarms; Communications; Recorder; Clock; Display; Lock Codes and Reset To Defaults
menus and functions.
Automatic Tuning
Selection of Pre-Tune, Self-Tune and Auto Pre-Tune.
Profile Setup Menu
Setting of Global Control Parameters for all profiles; plus Profile creation, editing and deletion.
Profile Control Menu
Selection of profiles. Running, holding or aborting the selected profile.
USB Menu
Uploading/downloading instrument configuration, profile information
and data recordings.
Recorder Menu
Manually starting, stopping and deleting recordings.
Product Information
Instrument information, including features and options installed.
Service Information
Contact information for service/support etc.
20
Setup Wizard
Table 6. Setup Wizard Screens
An easy Setup Wizard runs automatically at first ever
power-up or if whenever a Reset To Defaults is carried out. Users can follow the Wizard screens to setup
parameters required for typical applications (screens
marked w in the following Screen Sequence lists are
also included in the Setup Wizard).
Setup Wizard:
Setup Wizard
Unlocking
- major screens w
from Configuration Menu (those
marked w)
A partial Wizard also runs whenever option modules
have been changed. The partial wizard, only shows parameters affected by the changes made. The Wizard
can also be run manually from the Main Menu. Once
completed, the Setup Wizard exits to Operation Mode.
Setup Wizard
Completed
Experts or users with more complex applications can
select the parameters they wish to set-up from the
Configuration Menus instead of using the Wizard.
Entry into Supervisor Mode
from to enter the Main
or
Press
to enter the Setup Wizard.
Adjustments to these parameters should only
be performed by personnel competent and authorized to do so.
to select Setup Wizard.
Supervisor Mode is entered from the Main Menu
Note: With the exception of the first ever power-up,
entry into this mode is security-protected by the Setup
Wizard Lock Code. Refer to the Lock Code View section for more details.
Hold down
Menu.
Navigating in the Setup Wizard
Press
to move forward or A to move backwards
or
Hold down
Menu
to change the value as required.
and press
and press
from to enter the Main
Press
or
to select Supervisor Mode
Press
to enter the Supervisor Mode.
Note: Entry into this mode is security-protected by the
Supervisor Mode Lock Code. Refer to the Lock Code
View section for more details.
through the screens.
Press
Confirms completion of the
Setup Wizard. Exits to Operation Mode.
The purpose of Supervisor Mode is to allow certain
users access to a lock code protected sub-set of the
main configuration parameters without providing them
with the higher level Configuration Menu unlock code.
The Setup Wizard can be selected from the Main Menu.
Press
to select each
Press
major configuration parameter in turn. Follow on-screen
prompts to alter the values.
This mode is only available if it has been configured
from the PC software. The software is used to copy up
to 50 screens from the Configuration Menus to include
in Supervisor Mode.
Adjustments to these parameters should only
be performed by personnel competent and authorised to do so.
and press
w
Enter correct code number
to access Setup Wizard.
Supervisor Mode
Manual entry to the Setup Wizard
Hold down
Menu.
w
Navigating in Supervisor Mode
to return to the Main
Press
to move forward or
through the screens.
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
Press
or
Hold down
Menu
to move backwards
to change the value as required.
and press
to return to the Main
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
21
Table 7. Supervisor Mode Screens
Configuration is entered from the Main Menu
Supervisor
Mode Unlocking
Supervisor
Mode Screens
…
and press
Hold down
Menu.
Supervisor Mode:
If Supervisor Mode is configured, enter correct code
number to continue.
from to enter the Main
Press
or
to select Configuration Menu
Press
to enter the Configuration Menu.
Note: Entry into this mode is security-protected by the
Configuration Menu Lock Code. Refer to the Unlock
Code section for more details.
to select each
Press
parameter in turn. Follow onscreen prompts to alter the
values.
Configuration Menu
Navigating the Configuration Menu
This menu can be used as an alternative to the more
limited Setup Wizard when the instrument is configured
for the first time, or when further changes are required
to the instruments characteristics. Configuration contains a number of sub-menus that allow access to all
of the available parameters. The correct settings must
be made before attempting to use the instrument in an
application. Screens marked w are also shown in the
Easy Setup Wizard.
Configuration contains sub-menus to set-up the Input;
Output; Control; Alarm; Communications; Recorder;
Display and Lock Codes. There is also an option to return the instrument to its factory default settings.
The correct settings must be made before attempting
to use the instrument in an application.
From the Configuration Menu, press
lect the required sub-menu.
Press
or
to se-
to enter the sub-menu.
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
Entry into the Configuration Menu
Note: Only parameters that are applicable to the hardware and options fitted will be displayed.
Adjustments to these parameters should only
be performed by personnel competent and authorised to do so.
Table 8. Configuration Menu Screens
Configuration Menu:
Configuration Mode Unlocking
Enter correct code number to access Configuration Mode.
Configuration Options
Select the required Configuration Sub-Menu Option from: Input; Control; Output; Alarm; Communications; Recorder; Clock; Display; Lock
Code or Reset To Defaults.
Input Configuration Sub-Menu
Table 9. Input Configuration Sub-Menu Screens
Input Configuration:
Process Variable Input Type
w From various Thermocouple, RTD and Linear inputs. - see specifications section for full details of input types available.
Engineering Units
w Select display units from: °C; °F; °K; bar; %; %RH; pH; psi or none.
Decimal Point Position
w Sets the maximum display resolution to 0; 1; 2 or 3 decimal places.
Temperature inputs are limited to 0 or 1 place. Numbers >99.999 never display more than 2 dec places, >999.99 never display more than 1
dec place and >99999 always display without a decimal place.
Multi-Point Scaling Enable
Enables or disables Linear Input Multi-Point Scaling. This feature allows up to 15 point linearization of mA or V DC input signals.
22
Scale Range Lower Limit
w For Temperature inputs, Upper & Lower Limits set the usable span.
Min span = 100 units, max span = range limits - see specs. For Linear inputs, Upper & Lower Limits define the values shown (-1999 to
9999) when input is at minimum and maximum values. Min span =
100 units. If Multi-Point Scaling is enabled, up to 15 breakpoints* can
scale input vs. displayed value between the linear input scale limits.
w *A breakpoint set at 100% input ends the sequence.
Multi-Point Scale Point(s)
Scale Range Upper Limit
CJC Enable/Disable
Enables/disables internal Thermocouple Cold Junction Compensation. If disabled, external compensation will be required for thermocouples. The default value is Enabled.
Process Variable Offset
Trims the measured process value. +Ve values add to, –Ve values
subtract from measured input. Caution: A value other than zero alters
the apparent calibration of the instrument. Use with care!
Input Filter Time
Removes unwanted signal noise. Adjustable from 0.0 (OFF) to 100.0
seconds or OFF (default = 2s). Caution: Too large a value will cause
slow response to changes in the process. Use with care!
Auxiliary Input n Type
w Sets the type of signal to be connected to the auxiliary inputs (if fitted). From: 0-10V; 2-10V; 0-5V; 1-5V, 0-20mA or 4-20mA DC. Auxiliary input B also supports >2KW Potentiometer and 0-100mV.
Auxiliary Input n Scaling Lower
Limit
w Scales the displayed a value (-9999 to 10000) when an auxiliary input
is at or below its lower limit (e.g. 4mA for a 4-20mA signal).
Auxiliary Input n Scaling Upper
Limit
w Scales the displayed a value (-9999 to 10000) when an auxiliary input
is at or above its lower limit (e.g. 20mA for a 4-20mA signal).
Auxiliary Input n Offset
Trims the displayed a value for auxiliary input A or B. +Ve values are
added to, –Ve values subtracted from the measured auxiliary input.
Calibration Reminder Enable/
Disable
Enables or disables the display of Calibration Reminder at start-up
(repeated daily thereafter), if the due date has passed – Available on
the Recorder version only
Calibration Reminder Due Date
Sets the due date for the Calibration Reminder - Available on the Recorder version only
Control Configuration Sub-Menu
Table 10. Control Configuration Sub-Menu Screens
Control Configuration:
Control Enable/Disable
Sets the method used to enable/disable the control output(s). From:
Enabled (always); Disabled (always); Enable/Disable via Digital Input
A or B, or Operator Selectable (allows control output(s) to be turned
off from Operation Mode). Caution: The instrument is not able to control the process when control is disabled. The Output Power Lower
Limit parameters are also ignored. Use with care!
Auto/Manual Mode Access
w Sets the method used to select Automatic or Manual Control. From:
Automatic (always); Manual (always); Select via Digital Input A or B, or
Operator Selectable (allows automatic or manual control to be selected from Operation Mode). Caution: In Manual Mode, the user must
monitor and alter power to correctly control the process (0 to 100%
or -100 to +100% for dual control). Manual power is not restricted by
the Output Power Limit parameters. Use with care!
Control Type
w Set to Single Control for Primary control only (e.g. Heating or Cooling only) or to Dual for Primary and Secondary Control outputs (e.g.
Heating & Cooling).
23
Primary Control Action
w Set the Primary Control Output for Reverse or Direct Action. Reverse
action applies more primary power as the process falls further below
setpoint (e.g. heating applications). Direct action applies more primary power as the process rises further above setpoint (e.g. cooling
applications).
If Dual Control is used, the secondary output action is always opposite to the Primary action
Control Status
Displays the current Process Variable and Setpoint values to aid manual tuning – This screen is Read Only.
Power Output Level
Displays the current Primary and Secondary control power levels
(each 0 to 100%) to aid manual tuning – This screen is Read Only.
Primary Proportional Band
Sets the width of the Primary Proportional Band between 0.5% and
999.9%, or select On-Off control. – This screen is Read Only during
automatic tuning.
Secondary Proportional Band
Sets the width of the Secondary Proportional Band between 0.5%
and 999.9%, or select On-Off control. – This screen is Read Only during automatic tuning.
Integral Time Constant
Sets the Integral Time Constant (Automatic Reset) from 1s to 99min
59s or OFF. – This screen is Read Only during automatic tuning.
Derivative Time Constant
Derivative Time Constant (Rate) from 1s to 99 min 59s or OFF. – This
screen is Read Only during automatic tuning.
Manual Reset (Bias)
Sets the Manual Reset (Proportional Band Bias) from 0-100% or -100
to +100% for Dual Control.
Overlap / Deadband
Sets the Overlap (+ve values) or Deadband (-ve values) between Primary & Secondary Proportional Bands when Dual Control is used.
Primary On-Off Differential
Sets the Primary On-Off control hysteresis (deadband) from 0.1 to
10.0% of Span (centred about setpoint), when Primary On-Off control
is used.
Secondary On-Off Differential
Sets the Secondary On-Off control hysteresis (deadband) from 0.1
to 10.0% of Span (centred about setpoint), when Primary PID with
Secondary On-Off control is used.
Primary & Secondary On-Off
Differential
Sets the combined Primary & Secondary On-Off Control hysteresis
(deadband) from 0.1 to 10.0% of Span. when Primary On-Off control
and Secondary On-Off control is used.
Primary Cycle Time
Sets the Primary Power Cycle Time (0.5s to 512s). For time proportioned Primary Relay, SSR Driver or Triac Control Outputs.
Secondary Cycle Time
Sets the Secondary Power Cycle Time (0.5s to 512s). For time proportioned Secondary Relay, SSR Driver or Triac Control Outputs.
Primary Power Upper Limit
Sets the Maximum Primary Output Power Limit, from 0 to 100% of
available power. This value must be higher than the lower limit. Caution: The instrument will not be able to correctly control the process
if sufficient power isn’t available to maintain setpoint. Use with care!
Primary Power Lower Limit
Minimum Primary Output Power limit, from 0 to 100%. This value
must be less than the upper limit. Caution: The instrument will not
be able to correctly control the process if the lower limit is more than
required to maintain setpoint. Use with care!
Secondary Power Upper Limit
Maximum Secondary Output Power limit, from 0 to 100%. This value
must be higher than the lower limit. Caution: The instrument will not
be able to correctly control the process if sufficient power isn’t available to maintain setpoint. Use with care!
24
Secondary Power Lower Limit
Minimum Secondary Output Power limit, from 0 to 100%. This value
must be less than the upper limit. Caution: The instrument will not
be able to correctly control the process if the lower limit is more than
required to maintain setpoint. Use with care!
Sensor Break Pre-set Power
Output
Sets the power level applied if the process input (or active RSP) is
lost. Adjustable from 0 to 100% or -100 to +100% for Dual Control.
The default value is OFF (0% power). Caution: Use a value that will
maintain safe conditions.
Setpoint Selection
w Sets the method to select the Active Setpoint. From: Local Setpoint 1
only; Alternate Setpoint only; Select via Digital Input A or B; or Operator Selectable (allows Setpoint 1 or Alternate Setpoint to be selected
from Operation Mode).
Alternate Setpoint Source
w Up to two setpoints can be used, Local Setpoint 1 plus an Alternate
The Alternate Setpoint can be selected from: Local Setpoint 2 or a
Remote Setpoint set via Auxiliary Input A or B.
Setpoint Upper Limit
The maximum allowable setpoint value. Adjustable within the Input
Span limits, but must be greater than the Setpoint Lower Limit. Applies to both local and remote setpoints. Caution: Operators can adjust the setpoint to any value between the Setpoint Upper and Lower
Limits. Use with care!
Setpoint Lower Limit
The minimum allowable setpoint value. Adjustable within the Input
Span limits, but must be less than the Setpoint Upper Limit. Applies
to both local and remote setpoints. Caution: Operators can adjust
the setpoint to any value between the Setpoint Upper and Lower Limits. Use with care!
Setpoint Ramp Editing
Enables or disables the changing of the Setpoint Ramp Rate in Operation Mode – Note: this does not turn off an active ramp. To turn of
an active ramp, set the Setpoint Ramp Rate to OFF.
Setpoint Ramp Rate
The Setpoint Ramp Rate value (1 to 9999 display units per hour or
OFF). This ramp is applied at power-up and any setpoint changes.
Local Setpoint 1 Value
Local Setpoint 1 Offset
Local Setpoint 2 Value
Local Setpoint 2 Offset
w Sets the value of Local Setpoint 1 between the Setpoint Upper and
Lower Limits.
A value added to the Setpoint 1 value (+ve values) or subtracted from
it (-ve values). Use when the instrument is a slave in multi-zone applications to achieve a zone offset. Otherwise, always set to zero.
w Sets the value of Local Setpoint 1 between the Setpoint Upper and
Lower Limits.
A value added to the Setpoint 2 value (+ve values) or subtracted from
it (-ve values). Use when the instrument is a slave in multi-zone applications to achieve a zone offset. Otherwise, always set to zero.
25
Output Configuration Sub-Menu
Table 11. Output Configuration Sub-Menu Screens
Outputs Configuration:
No Outputs Warning
Shown if the Outputs Configuration menu is entered on an instrument
without any output modules fitted.
Linear Output n Type
w Set the desired type for any Linear Outputs fitted. From: 0-5, 0-10,
1-5, 2-10V & 0-20, 4-20mA or 0-10VDC adjustable Transmitter PSU.
Adjustable 0-10V Transmitter PSU w Sets the voltage required if Linear Output n type is 0-10VDC adjustn
able Transmitter PSU.
Output n Usage
w Sets the use for each output fitted. From: Primary or Secondary Control; Alarms; Profile Events & Alarms; Retransmit Process Variable or
Setpoint. Choices offered are as appropriate for the output type fitted
(e.g. only Linear Outputs can retransmit).
Output n Alarm Selection
w When an Output Usage is Alarms, this selects which alarm(s) will
cause it to change state. From Alarm 1; 2; 3; 4; 5 or a Logical OR of
alarms 1 to 2; 1 to 3; 1 to 4 or 1 to 5. Each choice is selectable with
Direct Action (on during alarm) or Reverse Action (off during alarm).
Output n Events
w When an Output Usage is Events & Alarms, this selects which
Events(s) will cause it to change state. From: Profile Running or Profile
End; Event 1; 2; 3; 4; 5 or a Logical AND of Event n & Alarm n. Each
choice is selectable with Direct Action (on during event) or Reverse
Action (off during event). - Profiler version only
Retransmit Output n Scale Low
w Sets the displayed value at which a retransmission output should be
at its minimum level (e.g. the display value when a 4 to 20mA PV
Retransmission output will be 4mA. Adjustable from -1999 to 9999.
Retransmit Output n Scale High
w Sets the displayed value at which a retransmission output will be at its
maximum level (e.g. the display value when a 4 to 20mA PV Retransmission output will be 20mA. Adjustable from -1999 to 9999.
Alarm Configuration Sub-Menu
Table 12. Alarm Configuration Sub-Menu Screens
Alarm Configuration:
Alarm n Type
w Sets the type for each of the 5 alarms From: Unused; Process High;
Process Low; PV-SP Deviation; Band; Control Loop; Rate Of Signal
Change; PV Signal Break; Aux. Input A or B Break.
Alarm n Value
w Alarm activation point. – applicable if type is High; Low; Deviation
(+ve above, -ve below SP), Band (above or below SP) or Rate of Signal Change (a rate of more that x units per hour).
Process Alarm n Hysteresis
Deadband on “safe” side of alarm, through which signal must pass
before alarm deactivates.
Signal Change Alarm n Minimum
Duration
The minimum time that the rate of input change must be above the
alarm threshold for a Rate Of Change Alarm to change state (from on
to off, or off to on). Adjustable from 1 to 9999 secs. Caution: If the
duration is less than this time, the alarm will not activate no matter
how fast the rate of rise.
Alarm n Inhibit
Enables or disables the prevention of initial alarm activation, if the
alarm condition is true at power up. Activation only occurs once the
alarm condition has passed and then reoccurred.
26
Loop Alarm Type
Sets the source of the Loop Alarm Time. From: Automatic (2x the Integral Time Constant) or Manual (the Manual Loop Alarm Time value).
If configured, a Loop Alarm activates if no response is seen after this
time.
Manual Loop Alarm Time
The time allowed after PID power output reaches minimum or maximum), for process to begin responding.
Communications Configuration Sub-Menu
Table 13. Communications Configuration Sub-Menu Screens
Communications Configuration:
No Communications Warning
If Communications Configuration menu is entered without a communications module fitted.
Modbus RTU Parity
w From: Odd; Even or None.
Modbus RTU Data Rate
w From: 9600; 19200; 57600 or 115200 bps.
Master Mode, or Slave Address
w Slave address (1 to 255), or multi-zone Setpoint Master Mode.
Target Register In Slave
Target register for Setpoint value in attached slave controllers.
Master Mode Format
The data format required by the attached setpoint slaves. From: Integer; integer with 1 decimal place or float.
Serial Communications Write
Enable
Enables/disables writing via RS485 or Ethernet (if fitted). When disabled, all parameters are read only.
Recorder Configuration Sub-Menu
Table 14. Data Recorder Configuration Sub-Menu Screens
Recorder Configuration:
No Recorder Warning
If the Recorder Configuration menu is entered on an instrument without this option fitted.
Recording In Progress Warning
If recording in progress when Recorder Configuration entered. – Allows access to the Recording Start/Stop screen only, until the recording is stopped.
Recorder Mode
w Choose Record Until Memory Used (Stop recording when full) or
Continuous FIFO (First In - First Out) - Caution: A FIFO recording will
overwrite all previous recordings in memory, starting with the oldest
data first. Download the previous data to USB memory stick before
selecting this option.
Recording Sample Interval
w A recording of the selected data will be taken once every Sample Interval. From: Every 1; 2; 5; 10; 15; 30 Seconds, or Every 1; 2; 5; 10; 15;
30 Minutes. Note: Short intervals will reduce the maximum possible
duration of the recording.
Recorder Trigger
w The recording Start/Stop trigger method to be used. From: Operation
Mode selection; Recorder Menu selection; On Alarm(s); Digital Input
A or B state; or During Profiles.
Trigger On Alarms
Any from: Alarm n – Where n is alarms 1 to 5. Any combination of
these can be set to trigger (TRG) or not (OFF). Any active alarm set
to TRG will start the instrument recording. Note: Recording will only
stop if all alarms selected as triggers become inactive.
27
Values To Record
Any from: Process Variable value; Maximum or Minimum PV (since
the previous sample was taken); Setpoint; Primary Power or Secondary Power. Any combination of these can be set to Record (REC) or
not (OFF). Note: Recording more parameters will reduce the maximum possible duration of the recording.
Alarms & System Events To
Record
Any from: Alarm n Status or Unit turned On/Off. Caution: An alarm
state change between samples is also recorded. This uses additional
recorder memory, which may cause the recording to end sooner than
expected.
Profiler Events To Record
Any from: Profiler Event n Status. Caution: A profile event state
change between samples is also recorded. This uses additional recorder memory, which may cause the recording to end sooner than
expected.
Recorder Status Information
Shows if a recording is in progress; the recording mode; memory usage per sample; memory remaining and the recording time remaining.
The time remaining is adjusted for any alarm/events that have already
occurred, but cannot allow for any future alarms/events
Clock Configuration Sub-Menu
Table 15. Internal Clock Configuration Sub-Menu Screens
Clock Configuration:
Date Format
w Sets the format used for all displayed dates: dd/mm/yyyy (Day / Month
/ Year) or mm/dd/yyyy (Month / Day / Year). – Recorder versions only.
Set Date
w Sets the internal clock Date. – Entered in the format defined by Date
Format screen. – Recorder versions only.
Set Day Of Week
Sets the day of week used by the internal clock. – Recorder versions
only.
Set Time
Sets the internal clock Time. - In hh:mm:ss (Hours : Minutes : Seconds) format. – Recorder versions only.
Display Configuration Sub-Menu
Table 16. Display Configuration Sub-Menu Screens
Display Configuration:
Enable Custom Display Mode
Enables/disables Custom Operation Mode, if configured (this mode
can only be enabled using the PC configuration software).
Read Only Operation Mode?
Allows Operation Mode to be Read-Only or Read/Write. Screens can
be seen but values cannot be changed if set to Read-Only.
Operation Mode Bar Graph Format
From: PID Power; Control Deviation or % Recorder Memory Usage.
Trend Sample Interval
Interval between display of next value on the trend graph From: Every
1; 2; 5; 10; 15; 30 Seconds, or Every 1; 2; 5; 10; 15; 30 Minutes.
Select Trend Mode
From: PV only, PV (solid) & SP (dotted) at sample time or Max/Min PV
between samples (candle-stick graph). Alarm activity is shown above
the trend graph.
Display Color
From: Red only; Green only; Red to Green on Alarm or Green to Red
on Alarm.
Invert Display
Standard or Negative display image.
28
Display Contrast
Screen contrast (0 and 100) to improve clarity. 100 = maximum contrast.
Language
Select English or the alternate local language. The alternate language
is selected at time of order. The choice of alternate language can be
changed using the PC software.
Lock Code View
Forcing Lock Code View
Unlock Codes
Power down the instrument.
To prevent unauthorised entry, some menus are protected by a lock code. These screens are indicated
by the symbol before their names in the screen list
tables. To enter these screens, the correct code must
first be entered. The current lock codes can be viewed
and changed from the Lock Code View Configuration
sub-menu.
Re apply the power and hold down
and
for
more than 5 seconds as the start-up splash screen appears. Lock Code View will appear.
Press
to move forward or
through the screen elements.
Make note of the codes or press
their values if required.
The default unlock code for all protected menus is 10.
For security, users are recommended to change these
codes. A value between 1 and 9999 can be used, or
the lock can be set to OFF if no protection is required.
Hold down
Menu.
and press
to move backwards
or
to change
to return to the Main
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
Navigating Lock Code View
Press
to move forward or
through the screen elements.
Press
or
Hold down
Menu.
Resetting To Defaults
to move backwards
Table 18. Reset To Defaults Sub-Menu Screen
to change the value as required.
and press
Reset To Defaults:
to return to the Main
Reset To
Defaults
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
If the instrument is to be used in a new or changed
application, it is possible to reset all of the instruments
parameters back to their factory default settings. The
Easy Setup Wizard runs automatically whenever a Reset To Defaults is performed.
Table 17. Lock Code View Sub-Menu Screens
Lock Code View:
Lock Code
View 1
Setup Wizard; Configuration
Mode and Tuning Menu Lock
Codes (1-9999 or OFF).
Lock Code
View 2
Supervisor Mode; USB; Recorder and Profiler Menu Lock
Codes (1-9999 or OFF) - if fitted/configured.
Sets all parameters to their factory default values.
User must reconfigure all required settings before using the instrument in a live application.
Automatic Tuning Menu
The Automatic Tune Menu is used engage the Pre-tune
and/or Self-tune facilities to assist the user in setting
up Proportional band(s), Integral and Derivative parameter values.
Lost Lock Codes
The lock codes can be viewed or changed from Configuration Mode. In the event that the Configuration
Mode lock code itself is forgotten, the instrument can
be forced into Lock Code View from power-up, where
the codes can be checked or set to new values.
Pre-tune can be used to set PID parameters approximately. Self-tune may then be used to optimise the
tuning if required.
Pre-tune can be set to run automatically after every
power-up by enabling Auto Pre-Tune.
The TUNE indicator (LED 3)* will flash while pre-tune
is operating, and is continuously on whilst Self-tune is
29
operating. If both Pre-tune and Self-tune are engaged
the AT indicator will flash until Pre-tune is finished, and
is then continuously on.
or
Press
required.
to engage or disengage the tuning as
Note: Self-Tune will not engage if either primary or secondary control outputs are set for On-Off control.
Hold down
Menu
and press
Pre-Tune will not engage if either primary or secondary control outputs are set for On-Off control, during
setpoint ramping, if a profile is running or if the process
variable is less than 5% of the input span from the setpoint.
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
to return to the Main
*Provided the function of LED3 has not been changed
(LED functions can be altered using the PC Configuration Software).
Navigating Automatic Tuning Menu
Press
to move forward or
through the selections.
to move backwards
Table 19. Automatic Tuning Menus Screens
Automatic Tuning Menu:
Automatic Tuning Mode
Unlocking
Pre-Tune
Enter correct code number to access the Automatic Tuning Menu.
w Turns Pre-Tune on/off. Pre-Tune is disabled in On-Off Control Mode;
if the PV is less than 5% of span from SP; during Profiles or if the
Setpoint is Ramping.
Pre-Tune Status
Shows the current Pre-Tune status. Active or Inactive.
Self-Tune
Turns Self-Tune on/off. Self-Tune is disabled in On-Off Control Mode.
Self-Tune Status
Shows current Self-Tune status. Active or Inactive.
Auto Pre-Tune Enable
Enables/Disables Automatic Pre-Tune. When enabled, this attempts
to perform a Pre-Tune at every power-up. Normal Pre-Tune engagement rules are applied (see Pre-Tune above).
Profiler Setup Menu
Screens marked will not time-out automatically. They
must be completed for a valid profile to be created.
Refer to the Profiler Option section of this manual for
more details about the profiler features.
Table 20. Profiler Setup Menu Screens
Profiler Menu:
General
General Profile Configuration: Settings that apply to all profiles
Profile Run/Hold Signal
Selects the method used to Run or Hold a profile. From: Digital Input
A; Digital Input B or Key Pad Only (using the either the Profile Control
Menu or an Operation Mode screen).
Profile Abort Signal
Selects the method used to force a profile to end prematurely. From:
Digital Input A; Digital Input B or Key Pad Only (using either the Profile
Control Menu or an Operation Mode screen).
Control In Operation Mode
Enables/disables the ability to control profiles (run, hold or abort) from
Operation Mode.
Enable Edit While Running
Enables/disables the ability to edit profiles whist a profile is running
(even if selected, the current or next segment of the running profile
will not change until after the profile is restarted).
Create A Profile
Creates a new profile. A header is created first, followed by the segments – see below. A warning is displayed if the maximum number of
64 profiles or 255 segments is exceeded.
30
Profile Header Details
Profile Header: Settings that apply to the chosen profile as a whole
Enter Profile Name
Up to 16 characters can be used to name each profile
Profile Starting Point
The setpoint value to be used at the beginning of the first segment.
From: Actual Setpoint or Process Variable value at the time the profile
starts.
Profile Start Trigger
From: None (profile start is not delayed); After Delay or Day and Time
(Recorder version only).
Profile Start Time
The time (hh:mm:ss) when the profile should run. – This applies only
if Day and Time is the Profile Start Trigger. Caution: Take care not to
clash with other profiles. A Profile cannot start if another is running.
Profile Start Day(s)
The Day(s) when the profile should run. From: Mon; Tue; Wed; Thu;
Fri; Sat; Sun; Mon-Fri; Mon-Sat; Sat-Sun or All. – This applies only if
Day and Time is the Profile Start Trigger.
Profile Start Delay
The delay time, up to 99:59 (hh:mm), for a profile to begin after the
start request has been given.
Profile Recovery Method
The power-on action if profile was running at power-down (e.g. after
a power cut), or following correction of a signal break. From: Control
outputs off; Restart profile from the beginning; Maintain last profile
setpoint; Use controller setpoint; Continue profile from where it was
when power failed.
Profile Recovery Time
The Recovery Method is ignored (the profile continues from where
power failed), if power off for less than this time. Max 99:59 (hh:mm).
- Recorder version only.
Profile Abort Action
Action after profile has been forced to stop before its end. From: Control outputs off; Maintain last profile setpoint or Use controller setpoint.
Profile Cycles
The number of times the program should run each time it is started
(1-9999 or Infinite).
Profile Segment Details
Profile Segments: Settings that apply to individual profile segments
Segment Number
Shows the number of the profile segment being created from 1-255
Segment Type
Set the segment type from: Ramp Time (time to reach target SP);
Ramp Rate (rate of change towards target SP); Step (jump to target
SP), Dwell (keep current SP); Hold (hold the profile until released);
Loop (back to a previous segment); Join (join to another profile); End
(end the profile) or Repeat Sequence Then End (repeat a sequence of
joined profiles – of which this is the last). A Join, End or Repeat Sequence Then End will become the last segment in the profile.
Segment Target Setpoint
The setpoint value to be reached by the end of this segment, if the
segment type is Ramp Time, Ramp Rate or Step.
Segment Ramp Time
The time (hh:mm:ss) to reach the Segment Target Setpoint if the segment type is Ramp Time.
Segment Ramp Rate
The rate of change towards the Segment Target Setpoint if the segment type is Ramp Rate. The rate can be set from 0.001 to 9999.9
display units per hour.
Segment Dwell Time
The time (hh:mm:ss) to maintain the current setpoint if the segment
type is Dwell.
Segment Loop
Enter the segment to loop back to, and the number of times to loop
back, before continuing forward to the next segment, if the segment
type is Loop. Note: Two Loops cannot be set to cross each other.
Segment Auto-Hold Type
From: None (no auto-hold); Above Setpoint (hold if too high only);
Below Setpoint (hold if too low only) or Band (hold if too high or low).
31
Segment Details (cont’d...)
Segment Auto-Hold Band
Value
The distance from setpoint beyond which the profile is held for the
selected Auto-Hold Type. The profile continues once the process returns within this band.
Segment Hold Release
Type
Sets the method used to release the profile from hold if the segment
type is Hold. From: Digital Input A; Digital Input B; Front Keys or Time
Of Day. (Time of day on Recorder version only )
Hold Release Time
The time of day (hh:mm:ss) when a Hold Segment will release if the
Release Type is Time Of Day. Release occurs at the next occurrence
of this time.
Times To Repeat Sequence
The number of times the entire sequence of profiles should run. – if
the last segment is Repeat Sequence Then End.
Segment End Type
The action taken after the profile ends normally. From: Control outputs off; Maintain last profile setpoint; Use controller setpoint.
Select Profile To Join
Choose a profile to join to from the list provided – if the last segment
type is Join. The selected profile will start immediately the current
profile ends.
Segment Events
Select the event(s) to be active during this segment. For end segments, events selected to be active stay on until the unit exits from
profiler mode or a new profile runs.
Edit A Profile Header
Choose the profile to be edited from the list of names provided, then
alter any values as required – The profile header details are as shown
in “Create A Profile” above.
Edit A Profile Segment
Choose the profile, then the segment to be edited from the lists provided. Alter any values as required – The profile segment details are
as shown in “Create A Profile” above. Note: The last segment type
can only be set to Join, End or Repeat Sequence Then End.
Insert A Segment
Choose the profile, then the new segment’s position from the lists
provided – Enter the new segments values as required – The profile
segment details are as shown in “Create A Profile” above. Note: The
new segments type cannot be set to Join, End or Repeat Sequence
Then End.
Delete A Segment
Choose the profile, then the segment to be deleted from the lists provided. End, Join or Repeat segments cannot be deleted.
Delete A Profile
Choose the profile to be deleted from the list of names is provided.
The user is then prompted confirm that it should be deleted.
Delete All Profiles
Deletes all profiles from memory. The user is prompted to confirm that
all profiles should be deleted. Caution: Use with care!
Table 21. Profiler Control Menu Screens
Profiler Menu:
Profile Control
If a profile is running, choose from: Do Nothing, Abort Profile (end immediately); or Jump to Next Profile Segment, Hold Profile or Release
Hold.
If no profile is running, choose from: Do Nothing, Run Profile or End
Profile Control (Return to normal controller operation).
Select Active Profile
Change the active profile. Choose from the list of profile names provided. The active profile is the profile that will run, when a run instruction is given (perhaps via a digital input).
Select A Profile To Run
Choose the profile to run from the list of names provided. The profile
name and run status is then confirmed.
32
USB Menu
menu can also be accessed from the Main Menu. Refer
to the USB Interface section for more details on the use
of the USB port option.
A Notification is shown if a USB Memory Stick is inserted or removed from the USB Port. The USB Menu
will automatically be offered after insertion. The USB
Table 22. USB Menu Screens
USB Menu:
Enter correct code number to access USB Menu.
Read/Write To USB Device?
Select the required action from: Read Instrument Configuration (from
USB stick); Write Instrument Configuration (to USB stick); Read Profiles (from USB stick); Write Profiles (to USB stick) or Write Recorder
Log File (to USB stick).
Read
Write
USB Mode Unlocking
Select Profile To Write
If writing a profile to the USB Memory Stick, choose a profile to write
from the list provided.
Enter A File or Folder
Name
Enter an 8-character folder name for recorder logs, or a file name for
configurations or profiles. An extension (bct for configurations, .pfl
for profiles) is added to files automatically. Caution: Existing files/
folders with the same name will be over-written.
Writing Profile/Configuration File
An animated screen is shown while the file(s) are being written.
Caution: Do not disconnect USB device until completed!
Data loss or corruption may result.
Transfer Successful
Confirmation that the data transfer to the USB stick completed correctly. Press ∆ to continue
Transfer Failure
For write failures, check for adequate disk space on the USB stick.
Select File
Select the Configuration or Profile file to transfer from the USB stick.
Caution: A configuration read overwrites all existing instrument settings.
Reading Profile/Configuration File
An animated screen is shown while the file is being read.
Caution: Do not remove the memory stick whist this operation is in progress. Data corruption may result.
Transfer Successful
Confirmation that the data transfer from the USB stick completed
correctly. Press ∆ to continue
Transfer Failure
For read failures, check the maximum number of profiles and/or segments is not being exceeded.
Do not remove the memory stick from the USB
port whilst a Data Transfer to or from the USB
stick is in progress. Data loss or corruption
may result.
During Data Transfer, normal operation carries
on in the background, but operator access to
other screens is not possible. The transfer of a
full memory can take up to 7 minutes. Only begin a transfer when you are certain that access
(e.g. setpoint changes) will not be required.
33
Recorder Menu
figuration Mode for information about how to setup the
data to be recorded and the recording interval.
This menu controls the starting and stopping of the
Data Recorder and the deletion of previous recordings.
Refer to the Recorder Configuration sub-menu in Con-
See to the Data Recorder Option section for more details on the use of the recorder and its features.
Table 23. Recorder Menu Screens
Recorder Menu:
Recorder Mode Unlocking
Enter correct code number to access Data Recorder Menu.
Recording In Progress Warning
Shown if a recording is in progress when the Recorder Menu is entered. - Allows access to the Recording Start/Stop screen only, until
the recording is stopped.
Start/Stop Data Recording
Manually Stop, or Start a new recording. – if Log Trigger is Recorder
Menu Start/Stop.
Abort Recording
Forces a recording to Stop, overriding the selected record trigger. – if
Log Trigger is During Alarms; Digital Input A or B; or During Profile.
Recorder Status Information
Shows if a recording is in progress; the recording mode; memory usage per sample; memory remaining and the recording time remaining. The time remaining is adjusted for any alarm or events that have
already occurred, but cannot allow for future alarms or events.
Delete Recording
Clears the recorder memory. Caution: Permanently removes All
recorded data.
Product Information Mode
This is a read only mode describing the instrument and
the options fitted to it.
Hold down
Menu
Navigating Product Information Mode
Scrolling “Help Text” is shown at the bottom of the
screens to aid navigation.
Press
to move forward or
to move backwards
through the displayed information.
and press
to return to the Main
Table 24. Product Information Screens
Product Information Mode:
Input Calibration Status
Calibration status of the mVDC, VDC, mADC, RTD and Thermocouple CJC inputs. Caution: Re-calibrate the unit if any inputs are not
shown as “Calibrated”.
Calibration Check Due Date
The date re-calibration is due. – Only shown if the Calibration Reminder is enabled in the Input Configuration menu.
Option Slot n (Output n)
Information
The type of Option Modules (if any) fitted in Option Slots 1 to 4 (Outputs 1 to 4) and Option Slots A to C.
Controller Feature Information
Shows the features fitted/enabled in the instrument:
Controller Only; USB Port; Data Recorder (includes USB Port) or
Profiler.
Firmware Information
The type and version of firmware installed in the instrument.
Serial Number
The instruments serial number.
Date of Manufacture
The instrument’s Date of Manufacture
34
Service Information Mode
Navigating Product Information Mode
This is a read only mode. It provides contact information to the user about where they can obtain service,
sales or technical support for the product. Normally
this shows either the manufacturer or supplier details.
Using the PC software, the user can enter their own
details. There are 7 lines of text - each up to 26 characters in length.
There are no other screens in this mode.
Hold down
Menu.
and press
to return to the Main
Table 25. Service Contact Information Screen
Service Information Mode:
For Service Contact
Contact information for Service, Sales or Technical Support.
8 The USB Interface
The features covered in this section of the manual are
available on models fitted with the optional USB Interface or the Data Recorder (which includes the USB Interface).
If the file or folder named already exists, data
will be overwritten
Using the USB Port
The first recorder log file written is named 000001-1.
csv and placed in the new Recorder sub-folder. Stopping/starting a recording does not create a new file, but
each time the parameters being recorded are changed
a new file is created (e.g. 000002-1.csv then 000003-1.
csv etc). If any of these files would exceed the maximum spread sheet size of 65500 data lines, a new file
is created with the last digit incremented by 1 (e.g.
000001-2.csv then 000001-3.csv).
The USB Interface option allows the user to upload or
download instrument settings to or from a USB memory stick. This allows easy configuration of multiple instruments by copying from one to another, or to transfer it to or from the PC configuration software. If the
Data Recorder or Profiler options are fitted, recordings
and profile information can also be transferred via USB
memory stick. Refer to the USB Menu section for more
details.
Note: To speed up the disk operation, keep the number
of files in these folders to a minimum
USB Memory Stick Folders & Files
When a USB stick is inserted, the instrument looks for,
and if necessary creates the DEVICE, CONFIG, PROFILE and RECORDER folders. Files must be located
in these folders in order to be used. When preparing to
upload files from your PC, ensure that you save them
to the correct folder on the memory stick.
Do not remove the memory stick from the USB
port whilst a data transfer operation is in progress. Data loss or corruption may result.
DEVICE – This folder must be located in the
Root of the USB memory stick
CONFIG – Configuration files (*.bct)
PROFILE – Profile program files (*.pfl)
RECORDER – Recorder log folders/files The
user is asked for a new recorder sub-folder
name before transferring recorder data to USB.
The instrument stores the log files (*.csv) in this
folder.
35
9 The Data Recorder Option
Calibration Reminder
The features covered in this section are available on
models fitted with the Data Recorder option. This option includes a USB Interface (refer to section 8) and a
Real Time Clock (RTC) with battery backup.
A “calibration due reminder” can be shown if the date
is equal to or after the Calibration Reminder Date. The
reminder screen persists until the
key is pressed. If
due, the reminder is shown at Power-up, and repeated
every 24hrs until the reminder date is changed. The
Calibration Reminder enable/disable and Reminder
Date parameters can be set from the Input Configuration Menu.
Introduction
The Data Recorder option allows the user to make a
recording of the process over time. Recordings can be
transferred to a memory stick using the USB Port.
Recordings are stored in Comma Separated format
(.csv), suitable for use with spreadsheets, or for import
in to other software. See the USB Memory Stick Folders & Files details (in section 8) for file information.
Memory Use Bar Graph
The bar-graph shown in the main Operation Mode
screen can be set to show 0 to 100% of recorder memory used instead of the standard options of PID power
or control deviation. The Bar Graph Format is defined
in the Display Configuration Menu.
A Recorder Configuration sub-menu is added to the
Configuration Menu and Recorder Control can be optionally added to the Main Menu or Operation Mode.
The RTC also expands the profiling capabilities (refer
to section 10) and allows a “calibration due” reminder
to be shown at a date specified by the user.
Changes To Operation Mode
The Data Recorder adds the option for a Calibration
Reminder and a % memory use bar graph to the Operation Mode screen sequence.
10 The Profiler Option
Profile Components
The features covered in this section are only available
on models fitted with the Profiler (Setpoint Programmer) option. If the instrument also has the Data Recorder option fitted, its Real Time Clock is used to expand the profiling capabilities by adding Day & Time
profile start options, releasing of hold segments at a
specific time of day and changing the power fail recovery option to one based on the length of time the power
has been off. These features are explained below and
in the Profiler Setup and Profile Control menus (refer to
section 7)
The General Profile Configuration settings decide how
profiles can be Run, Held or Aborted. These settings
apply to all profiles.
Each profile has its own header information, plus 1 or
more segments.
Profile Header & Segment Information
The profile header contains information about how the
profile starts and stops, the power loss recovery action
and how many times it should be repeated.
Introduction
Note: Profile Header information is stored to memory
as the Segment creation sequence begins. No profile is
created if you exit before this point.
The Profiler option allows the user to store up to 255
profile segments, shared between a maximum of 64
Profiles. Each profile controls the value of the setpoint
over time; increasing, decreasing or holding its value
as required. If fitted, Profiler options are added to the
Main Menu as well as the Operation Mode.
Segments can be ramps, dwells, steps or special segments such as holds, ends or joins. Note: Segment information is stored as each segment is created, but the
profile remains invalid until an end or join segment is
defined.
Profiler Enabling
Controllers supplied without the Profiler option installed can be upgraded in the field by purchasing a
licence code number from your supplier. Refer to the
Field Upgrade information (Section 3) for more details.
36
Profile Starting & Standard Segments
The example profiles below contain examples of the
standard segment types required to make simple profiles or profile sequences. A Start Trigger is the instruction to begin the selected profile. Depending on the
Run/Hold Signal parameter setting in the Profile Setup
Menu, this can be from a Key-press given in the appropriate screen, a digital input signal or via a serial
communications command.
A timer start time should not clash with other profiles. A profile will not start if another
is running. Remember that delays caused by
manual holds or Auto-Hold can effect when the
previous running profile will finish.
Following a Start Trigger, profiles can start immediately,
after a delay, or from the Timer (Timer start available on
Recorder version only).
PROFILE 1
PROFILE 9
Seg. 1 Target SP
Step
Ramp (Time/Rate)
Starting Setpoint
End
Start
Trigger
Timer or Delay
Figure 37.
Dwell
Join (Profile 1 to Profile 9)
Profile Starting and Standard Segment Types
Ramps, Dwells and Step Segments each have an end
of segment Target Setpoint.
A Dwell (sometimes called a soak) holds the last segment’s value for the specified Dwell Time.
If a segment is a Ramp-Time type, the slope needed
to reach the target in the defined time will change depending on the Starting Setpoint value. For a RampRate segment, the slope is defined by the segments
Ramp Rate, so the time to reach the target setpoint will
change instead. This is of particular significance for the
first segment, since the starting value of the process
may not be known.
Step segments jump straight to the new target setpoint
value.
An End segment ends the profile sequence.
If the last segment is a Join, the join target profile will
start.
Note: The Profile sequence will abort if the join target
has been deleted.
37
Loops Segments
continues onwards. More than one Loop Segment can
be used in a profile, but they must not cross.
A Loop Segment goes back to a specified segment in
the current profile. This action is repeated for the required number of times (1 to 9999) before the profile
Loop back target segment
Example:
Runs segments 1 to 5, then
repeats segments 3 to 5 for 500
times, before continuing on to
segments 7 to 9,
x 500
End
Loop Segment
Figure 38.
Loops Segments
Profile Running / Holding vs. Hold Segments
Continue
Triggers
Hold Start
End
Run
Hold Stop
Figure 39.
Hold Segments
Run/Hold & Hold Segments
A Hold during a segment maintains the current setpoint value. Once the hold condition is stopped the
Ramp or Dwell continues. Depending on the configuration, a hold can be the started & stopped by via a keypress, breaking the signal to a Run/Hold digital input,
a serial comms command or by the Auto-Hold feature
(see below).
A Hold Segment is a pre-planned hold, programmed
into the profile. It maintains the value of the previous
segment. The profile does not continue until a Continue Trigger occurs. This can be via a key-press, a digital
input signal or after waiting for a time of day (available
on Recorder version only).
Note: A running profile will also hold while Manual
Control is selected.
38
The Auto-Hold Feature
During a Dwell, the dwell time is increase by the time
that the process is outside of the hold band in the selected direction(s). This ensures the process was at the
desired level for the required amount of time.
Each profile segment has individual Auto-Hold settings.
If utilised, these ensure that the profile and the actual
process remain synchronised. If the process does not
closely match the required setpoint by remaining within
the defined Hold Band, the profile can be held until it
returns within bounds.
During a Ramp segment, the ramp is held at the current setpoint value while the process is outside of the
hold band in the selected direction(s). The time taken
to complete the ramp is increased by the time taken by
the Auto-Hold.
The user can choose to hold the profile if the process
goes beyond the Hold Band Above The Setpoint only,
Below The Setpoint only or to Band (either side of the
setpoint). When Auto-Hold becomes active, the profile
status is shown as “Held”.
Held if Auto-Hold set to Above Setpoint or Band
Hold Band
Dwell Segment
Setpoint
Process Variable
Held if Auto-Hold set to Below Setpoint or Band
Figure 40.
Auto-Hold On A Dwell Segment
Held if Auto-Hold set to Above Setpoint or Band
Process Variable
Hold Band
Ramp Setpoint
(without AutoHold)
Ramp Setpoint
(with Auto-Hold)
Held if Auto-Hold set to Below Setpoint or Band
Figure 41.
Auto-Hold On A Ramp Segment
39
Profile Cycles & Repeat Sequences
If there is a break in the input while a program is running, the unit will go to the Pre-Set Power Value during
the break condition. Once the condition has ended it
carries out the same recovery action as specified for
power failure.
A profile can be configured to run itself 1 to 9999 times
or continuously using the Profile Cycles setting. A profile ending with Repeat Then End will run the entire
sequence of profiles again from 1 to 9999 times before
ending.
Note: Recorder versions always use option E (Continue profile from the point it had reached when the power
failed) if the Power Off Time is less than the Profile Recovery Time setting. If the power is off for more than
this time, the defined Profile Recovery Method is used.
Power/Signal Lost Recovery Actions
If there is a power cut while a profile is running, the instrument will use the defined Profile Recovery Method
once the power has been restored.
PROFILE 4
PROFILE 31
Profile 4
Profile 7
Profile 31
Cycles = 1
Example:
Runs profile 4 once,
profile 31 three times
& profile 7 once.
This sequence is
repeated ten times.
PROFILE 7
Cycles = 1
Cycles = 3
Repeat Sequence = 10
Join (Profile 4 to Profile 31)
Figure 42.
Profile Cycles & Repeats
Power On
Power Off
Run
(Start-on SP)
Repeat Then End
(times to repeat = 10)
Join (Profile 31 to Profile 7)
Power Off Time
Planned Profile
= Control Off
Controller SP
Possible Recovery Methods:
A
B
C
D
E
Abort the profile and maintain the profile value from the time the power failed.
Abort the profile and use Controller Setpoint value.
Abort the profile with the Control outputs off.
Restart the profile again from the beginning.
Continue profile from the point it had reached when the power failed
Figure 43.
End, Abort and Recovery Actions
40
Profile End Actions
Segment Type of the last profile will be carried out. The
possible end actions are explained below.
Once a running profile ends, that profiles’ Segment
End Type defines action taken by the instrument. If a
sequence of profiles has been completed, the End
Run
(Start-on SP)
Last Profile SP
Normal Profile End
Controller SP
= Control Off
Controller SP
Possible Profile End Actions:
A At profile end, maintain the Final Setpoint value of the last segment.
B At profile end, exit Profiler Mode and use the Controller Setpoint value.
C At profile end, remain in Profiler Mode with the Control outputs off.
Figure 44.
Profile End Action
Profile Abort Actions
of the Profile Setup Menu, and is common to all profiles.
If a running profile is forced to end early, the Profile
Abort Action defines action taken by the instrument.
This is set in the General Profile Configuration section
The possible options are explained below.
Last Profile SP
Run
(Start-on SP)
Profile Aborted
Controller SP
Controller SP
= Control Off
Possible Profile Abort Actions:
A Abort the profile and maintain the value of the setpoint at the time of the abort.
B Abort the profile and exit Profiler Mode using the Controller Setpoint value.
C Abort the profile and remain in Profiler Mode with the Control outputs off.
Figure 45.
Profile Abort Action
41
11 Manually Tuning Controllers
Single Control Tuning (PID with Primary
Output only)
2. Set the Setpoint to the normal operating value for
the process (or to a lower value if overshoots beyond this value might cause damage).
This technique balances the need to reach setpoint
quickly, with the wish to limit setpoint overshoot at
start-up or during process changes. It determines values for the Primary Proportional Band and the Integral
and Derivative time constants that allow the PID control algorithm to give acceptable results in most applications that use a single control device.
3. Select On-Off control (i.e. set the Primary Proportional Band to zero).
4. Switch on the process. The process variable will oscillate about the setpoint. Record the Peak-to-Peak
variation (P) of the first cycle (i.e. the difference between the highest value of the first overshoot and
the lowest value of the first undershoot), and the
time period of the oscillation (T) in minutes. See the
example diagram below - Manually Tuning PID.
This technique is suitable only for processes
that are not harmed by large fluctuations in the
process variable.
5. Calculate the PID control parameters using the formula below. P.Pb is the Primary Proportional Band,
Int.T is the Integral Time Constant, and Der.T is the
Derivative Time Constant. The Input Span is the
difference between Scale Range Lower Limit and
Scale Range Upper Limit:
1. Check that the Setpoint Upper Limit and Setpoint
Lower Limit are set to safe levels for your process.
Adjust if required.
P
x 100
Input Span
Int.T = T minutes
T
Der.T =
minutes
6
Process Variable
P.Pb =
Time
Figure 46.
Manually Tuning PID
42
Dual Control Tuning (PID with Primary and
Secondary Outputs)
PI Tuning (Valve, Damper & Speed
Controllers)
This tuning technique balances the need to reach setpoint quickly, with the wish to limit setpoint overshoot
at start-up and during process changes. It determines
values for the Primary Proportional Band, Secondary Proportional Band, Integral and Derivative time
constants that allow the PID control algorithm to give
acceptable results in most applications that use dual
control (e.g. Heat & Cool).
This tuning technique is used when controlling a
damper, a modulating valve or motor speed controller. It determines values for the Primary Proportional
Band, and Integral Time Constant. The Derivative
Time Constant is normally set to OFF. This type of
control (known as PI Control) minimises valve/motor
wear whilst giving optimal process control.
This technique is suitable only for processes
that are not harmed by large fluctuations in the
process variable.
This technique is suitable only for processes
that are not harmed by large fluctuations in the
process variable.
1. Set the setpoint to the normal operating process
value (or to a lower value if overshoot beyond this
value is likely to cause damage).
1. Tune the controller using only the Primary Control
output as described in the Single Control Tuning
section above.
2. Set controller to On/Off Control mode (i.e. set Primary Proportional Band to the minimum value).
2. Set the Secondary Proportional Band to the same
value as the Primary Proportional Band and monitor the operation of the controller in dual control
mode. If there is a tendency to oscillate as the control passes into the Secondary Proportional Band,
increase its value. If the process appears to be overdamped (slow to respond) in the region of the Secondary Proportional Band, decrease its value.
3. Set the Integral Time Constant to OFF.
4. Set the Derivative Time Constant to OFF.
5. Follow the instructions in the diagram on the following page. At each stage, allow sufficient settling
time before moving on to the next stage. P.Pb is the
Primary Proportional Band, Int.T is the Integral Time
Constant
3. When the PID tuning values have been determined,
if there is a disturbance to the process variable as
control passes from one proportional band to the
other, set the Overlap/Deadband parameter to a
positive value to introduce some overlap. Adjust
this value by trial and error until satisfactory results
are obtained.
43
Process Variable
START
Apply Power to
the load.
Does the
PV
Time
Tb
Yes
continuously
Oscillate?
No
Note the time
Are the
interval Ta
Oscillations
Yes
decaying to
zero?
Set P.Pb = 0.8%
Set Int.T = Ta
Note the period
of the decaying
No
Multiply
P.Pb
setting by 1.5
oscillations (Tb)
Multiply
P.Pb
setting by 1.5
Set Int.T = Tb
Process Variable
2
END
The controller is now tuned.
Fine-tuning may be required
to optimise the controllers
Ta
Time
Table 26. Manually Tuning Valve Control
44
Fine Tuning.
Note: Allow enough time for the controller and process
to adjust between changes.
A separate cycle time adjustment parameter is provided for the Primary and Secondary control when using
time proportioning control outputs.
4. Initially add Derivative at a value between 1/4th and
1/10th of the Integral Time value.
5. Increase the Derivative Time if the process overshoots/undershoots, increase its value a little at a
time, if the process becomes unstable, until the oscillation stops. Induce a load disturbance or make a
setpoint change to verify that the process stabilises.
If not decrease the value some more and re-test.
Note: Adjusting the cycle time affects the controllers
operation; a shorter cycle time gives control that is
more accurate, but mechanical components such as
relays will have a reduced life span.
1. Increase the width of the proportional band if the
process overshoots or oscillates excessively.
Note: When controlling a modulating valve, it is recommended that Derivative is set to OFF to avoid excessive valve activity. Derivative can cause process instability in these processes.
2. Decrease the width of the proportional band if
the process responds slowly or fails to reach setpoint.
3. To find the optimum value for the Integral Time, decrease its value until the process becomes unstable,
then increase it a little at a time, until stability has is
restored. Induce a load disturbance or make a setpoint change to verify that the process stabilises. If
not increase the value some more and re-test.
6. After making all other adjustments, if an offset exists between the setpoint and the process variable
use the Bias (manual reset) to eliminate the error:
Below setpoint - use a larger value
Above setpoint - use a smaller value
12 Serial Communications
Supported Protocols
RS485 Device Addressing
Communication with a Modbus RTU or Modbus TCP
master device is possible if the appropriate communications module is fitted into Option Slot A. ASCII is
no longer supported on the 4080. An RS485 Module is
required for Modbus RTU. An Ethernet Module is required for Modbus TCP.
The instrument must be assigned a unique device address in the range 1 to 255. This address is used to recognise Modbus Queries intended for this instrument.
With the exception of globally addressed broadcast
messages, the instrument ignores Modbus Queries
that do not match the address that has been assigned
to it.
The instrument can also act as Setpoint Master over
RS485 in multi-zone applications. In this mode the unit
continuously sends its setpoint value using Modbus
broadcast messages.
The instrument will accept broadcast messages (global
queries) using device address 0 no matter what device
address is assigned. No response messages are returned for globally addressed Queries.
For a complete description of the Modbus protocol refer
to the description provided at http://www.modbus.org/
Ethernet Configuration
All models also have a configuration socket for use
with the PC configuration software. An RS232 to TTL
lead (available from your supplier) is required in order
to use this socket.
For Modbus TCP communications (Modbus over Ethernet), the IP address can either be assigned by a Dynamic Host Configuration Protocol (DHCP), BootP or
AutoIP server on the network, or manually assigned
using the IP address allocation software tool.
A front mounted USB port is available on some models;
this can also be used to configure the instrument or to
transfer recorder or profile files via a USB memory stick.
Refer to the PC Software section of this manual for
more information setting IP addresses.
RS485 Configuration
The supported data rates 10/100BASE-T (10 or 100
Mbps) are automatically detected.
The RS485 address, bit rate and character format are
configured via the front panel from the Comms Configuration menu or by using the PC Configurator software.
Physical layer configuration settings possible are:
Data rate:
4800, 9600, 19200, 38400,
57600 or 115200 bps
Parity:
None (default), Even, Odd
Character format:
Always 8 bits per character.
Device Address:
See following.
45
Link Layer
A message for either a QUERY or RESPONSE is made
up of an inter-message gap followed by a sequence
of data characters. The inter-message gap is at least
3.5 data character times - the transmitter must not
start transmission until 3 character times have elapsed
since reception of the last character in a message, and
must release the transmission line within 3 character
times of the last character in a message.
A Query (or command) is transmitted from the Modbus
Master to the Modbus Slave. The slave instrument assembles the reply to the master. All of the instruments
covered by this manual are slave devices, and cannot
act as a Modbus Master.
MODBUS
SLAVE
MASTER
INSTRUMENT
Note:
Three character times is approximately 0.25ms at
115200 bps, 0.51ms at 57600 bps, 0.75ms at 38400
bps, 1.5ms at 19200 bps, 3ms at 9600 bps and 6ms
at 4800bps.
QUERY
Data is encoded for each character as binary data,
transmitted LSB first.
For a QUERY the address field contains the address
of the slave destination. The slave address is given
together with the Function and Data fields by the Application layer. The CRC is generated from the given
address, function and data characters.
RESPONSE
Figure 47.
For a RESPONSE the address field contains the address of the responding slave. The Function and Data
fields are generated by the slave application. The CRC
is generated from the address, function and data characters.
Modbus Link Layer
The standard MODBUS RTU CRC-16 calculation employing the polynomial 216+215+22+1 is used.
Inter-message
gap
Address 1
character
Function 1
character
Data n
characters
CRC Check
2 characters
Supported Modbus Functions
Modbus defines several function types. The following types are supported by this instrument:
Function Code
(decimal)
Modbus Meaning
Description
03 / 04
Read Holding/Input registers
Read current binary value of specified number
of parameters at given address. Up to 64 parameters can be accessed with one Query.
06
Write Single Register
Writes two bytes to a specified word address.
08
Diagnostics
Used for loopback test only.
16 (0x10 hex)
Write Multiple Registers
Writes up to 253 bytes of data to the specified
address range.
23 (0x17 hex)
Read/Write Multiple Registers
Reads and Writes 253 bytes of data to the
specified address ranges.
46
Function Descriptions
In the function descriptions below, the preceding device address value is assumed, as is the correctly
formed two-byte CRC value at the end of the QUERY
and RESPONSE frames.
The following is interpreted from the Modbus Protocol
Description obtainable from http://www.modbus.org/.
Refer to that document if clarification is required.
Function 03 / 04 - Read Holding/Input Registers
Reads current binary value of data at the specified word addresses
QUERY
Function
03 / 04
Address of 1st Word
HI
Number of Words
LO
HI
LO
RESPONSE
Function
Number of
Bytes
First Word
03 / 04
HI
Last Word
LO
HI
LO
In the response the “Number of Bytes” indicates the number of data bytes read from the instrument. E.g. if 5 words
are read, the count will be 10 (A hex). The maximum number of words that can be read is 64. If a parameter does
not exist at one of the addresses read, then a value of 0000h is returned for that word.
Function 06 - Write Single Register
Writes two bytes to a specified word address.
QUERY
Function
06
Address of Word
HI
Value to Write
LO
HI
LO
RESPONSE
Function
06
Address of Word
HI
Value to Written
LO
HI
LO
Note: The Response normally returns the same data as the Query.
Function 08 - Loopback Diagnostic Test
QUERY
Function
08
Diagnostic Code
HI =00
Value
LO=00
HI
LO
RESPONSE
Function
08
Sub-function
HI=00
Value
LO=00
HI
LO
Note: The Response normally returns the same data as the loopback Query. Other Diagnostic Codes are not supported.
47
Function 16 - Write Multiple Registers (0x10 Hex)
Writes consecutive word (two-byte) values starting at the specified address
QUERY
Function
06
1st Write
Address
HI
Number of
Number of
Words to Write Query Bytes
LO
HI
1st Query
Byte
2nd Query
Byte
Last Query
Byte
etc
LO
LO
RESPONSE
Function
1st Word Address
10
HI
Number of Words
LO
HI
LO
Note: The number of data bytes that can be written in one message is 253 bytes.
Function 23 Hex - Read / Write Multiple Registers (0x17 hex)
Reads and writes the requested number of consecutive words (two-bytes) starting at the specified addresses
QUERY
Function
17
1st Read
Address
HI
LO
Number of
Words to
Read
HI
LO
1st Write
Address
HI
Values to Write
Number of
Words to
Write
LO
HI
1st Word
LO
HI
2nd Word
LO
HI
etc
LO
Last Word
HI
LO
RESPONSE
Read Data
Function
1st Word Address
10
HI
1st Word
HI
2nd Word
LO
HI
etc
LO
Last Word
HI
LO
Note: The number of data bytes that can be written in one message is 253 bytes.
Exception Responses
When a QUERY is sent that the instrument cannot interpret, an Exception RESPONSE is returned.
Possible exception responses are:
Exception Code
Error Condition
Interpretation
00
Unused
None.
01
Illegal function
Function number out of range.
02
Illegal Data Address
Write functions: Parameter number out of range or not supported.
(for write functions only).
Read Functions: Start parameter does not exist or end parameter
greater than 65536.
03
Illegal Data Value
Attempt to write invalid data / required action not executed.
The format of an exception response is:
RESPONSE
Function
Exception Code
Original Function code with its Most as detailed above
Significant Bit (MSB) set.
Note: In the case of multiple exception codes for a single QUERY the Exception code returned is the one corresponding to the first parameter in error.
48
13 Modbus Parameters
The Modbus parameter register addresses are detailed
in the tables below.
The Modbus Address column shows the register address for each parameter in integer format. Other formats can be calculated from the Integer Only address.
The Access column indicates if a parameter is read
only (RO) or if it can also be written to (R/W). Communications writes will not be implemented if the Writing
Via Serial Comms parameter in the Communications
Configuration menu is set to Disabled.
When working in Hexadecimal, the format calculations are:
Address for Integer with 1 Decimal Place = Integer address plus 0x4000
Note: Some parameters that do not apply for a particular configuration will accept reads and writes (e.g.
attempting to scale a Linear output which has not been
fitted). Read only parameters will return an exception if
an attempt is made to write values to them.
Address for Floating Point = Integer address
multiplied by 2, plus 0x8000
When working in Decimal, the format calculations are:
Address for Integer with 1 Decimal Place = Integer address plus 16384
Data Formats
Data can be read or written in three formats: Integer
Only, Integer with 1 Decimal Place and Floating Point
Number.
Address for Floating Point = Integer address
multiplied by 2, plus 32768
Example Register Address Calculations
Calculating Parameter Register Addresses
Register Address
Calculation
Address Example:
(For Process Variable)
Data Value Returned:
If actual Value = 23.9 decimal
Address Example:
(For Selected Setpoint)
Data Value Returned:
If Value = 1 (Alternative SP)
Integer Only
Integer +1
Floating Point
(hex)
Address
Address + 0x4000
Address x 2 + 0x8000
(dec)
Address
Address + 16384
Address x 2 + 32768
(hex)
0x0407
0x4407
0x880E
(dec)
1031
17415
34830
(hex)
0x00, 0x17
0x00, 0xEF
0x41, 0xBF, 0x33, 0x33
(dec)
23
239
23.9 as floating decimal
(hex)
0x101F
0x501F
0xA03E
(dec)
4127
20511
41022
(hex)
0x00, 0x01
0x00, 0x0A
0x3F, 0x80, 0x00, 0x00
(dec)
1
10
1.0 as floating decimal
49
Universal Process Input Parameters
Modbus Address
Parameter Name
Universal Process Input
Type
Engineering Units
Maximum Display
Decimal Places
(Dec)
(Hex)
Access
10245
0x0409
R/W
1025
1026
0x0401
0x0402
R/W
R/W
Values
Value
Process Input Under Range Status
0
B Type Thermocouple
2
C Type Thermocouple
4
D Type Thermocouple
6
E Type Thermocouple
8
J Type Thermocouple
10
K Type Thermocouple
12
L Type Thermocouple
14
N Type Thermocouple
16
R Type Thermocouple
18
S Type Thermocouple
20
T Type Thermocouple
22
PtRh 20%: 40% Thermocouple
24
PT100 RTD
26
NI120 RTD
28
0 to 20mA DC
29
4 to 20mA DC
30
0 to 50mV DC
31
10 to 50mV DC
32
0 to 5V DC
33
1 to 5V DC
34
0 to 10V DC
35
2 to 10V DC
Value
Engineering Units
0
= None
1
= °C (Default for Europe)
2
= °F (Default for USA)
Value
Decimal Places
0
None (e.g. 1234)
1
One (e.g. 123.4)
2
Two (e.g. 12.34)
3
Three (e.g. 1.234)
Range Minimum
1027
0x0403
R/W
Range Maximum
1028
0x0404
R/W
Valid between input range maximum and minimum
(see Specifications Section for input details)
Process Variable Offset
1029
0x0405
R/W
Valid between scale range maximum and minimum
Filter Time Constant
1030
0x0406
R/W
Valid between 0.0 and 512.0
Process Variable
1031
0x0407
RO
The current process input value
Input Signal /Sensor Break
Flag
1032
0x0408
RO
Value
50
Process Input Break Status
0
Inactive
1
Active
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Input Signal Under Range
Flag
1033
0x0409
RO
Input Signal Over Range
Flag
1034
Cold Junction
Compensation Enable/
disable
1035
Calibration Reminder
Enable
1048
0x040A
0x040B
0x0418
Values
Value
0
Inactive
1
Active
Value
RO
R/W
R/W
Process Input Under Range Status
Process Input Over Range Status
0
Inactive
1
Active
Value
CJC Status
0
Disabled
1
Enabled (default)
Value
0
Calibration Reminder Status
Disabled
Enabled
Calibration Reminder Date
1049
0x0419
R/W
Calibration Reminder
Status
1052
0x041C
RO
Multi-point Scaling Enable
1053
0x041D
Data Format = ddmmyy where dd = day, mm = month
and yy = year (e.g. 200308 is 20th March 2008)
Value
R/W
Calibration Status
0
Calibration OK
1
Calibration Required
Value
Multi-point Scaling Status
0
Disabled
1
Enabled (only if the input type is linear)
Scale Point 1
1054
0x041E
R/W
0.1 to 100.0%
Display Point 1
1055
0x041F
R/W
Valid between scale range maximum and minimum
Scale Point 2
1056
0x0420
R/W
>Scale point 1 to 100.0%
Display Point 2
1057
0x0421
R/W
Valid between scale range maximum and minimum
Scale Point 3
1058
0x0422
R/W
>Scale point 2 to 100.0%
Display Point 3
1059
0x0423
R/W
Valid between scale range maximum and minimum
Scale Point 4
1060
0x0424
R/W
>Scale point 3 to 100.0%
Display Point 4
1061
0x0425
R/W
Valid between scale range maximum and minimum
Scale Point 5
1062
0x0426
R/W
>Scale point 4 to 100.0%
Display Point 5
1063
0x0427
R/W
Valid between scale range maximum and minimum
Scale Point 6
1064
0x0428
R/W
>Scale point 5 to 100.0%
Display Point 6
1065
0x0429
R/W
Valid between scale range maximum and minimum
Scale Point 7
1066
0x042A
R/W
>Scale point 6 to 100.0%
Display Point 7
1067
0x042B
R/W
Valid between scale range maximum and minimum
Scale Point 8
1068
0x042C
R/W
>Scale point 7 to 100.0%
Display Point 8
1069
0x042D
R/W
Valid between scale range maximum and minimum
Scale Point 9
1070
0x042E
R/W
>Scale point 8 to 100.0%
Display Point 9
1071
0x042F
R/W
Valid between scale range maximum and minimum
Scale Point 10
1072
0x0430
R/W
>Scale point 9 to 100.0%
Display Point 10
1073
0x0431
R/W
Valid between scale range maximum and minimum
Scale Point 11
1074
0x0432
R/W
>Scale point 10 to 100.0%
51
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Values
Scale Point 12
1076
0x0434
R/W
>Scale point 11 to 100.0%
Display Point 12
1077
0x0435
R/W
Valid between scale range maximum and minimum
Scale Point 13
1078
0x0436
R/W
>Scale point 12 to 100.0%
Display Point 13
1079
0x0437
R/W
Valid between scale range maximum and minimum
Scale Point 14
1080
0x0438
R/W
>Scale point 13 to 100.0%
Display Point 14
1081
0x0439
R/W
Valid between scale range maximum and minimum
Scale Point 15
1082
0x043A
R/W
>Scale point 14 to 100.0%
Display Point 15
1083
0x043B
R/W
Valid between scale range maximum and minimum
Option Slot A Parameters
Modbus Address
Parameter Name
Digital Input A Status
Option Slot A Module
Type
(Dec)
(Hex)
Access
2115
0x0845
RO
2116
0x0844
Values
Value
0
Inactive
1
Active
Value
RO
RS485 Data Rate
RS485 Parity
2117
2118
2119
0x0845
0x0846
0x0847
R/W
R/W
R/W
52
Module Fitted In Slot A
0
None Fitted
1
RS485 Communications
3
Digital Input
4
Auxiliary Input A
5
Ethernet Communications
255
RS485 Address
Digital Input A Status
Value
Error (unrecognised module)
RS485 Address
0
Modbus Master mode
1 to 255
Modbus Slave Address
Value
Baud Rate
0
4800
1
9600
2
19200 (Default)
3
38400
4
57600
5
115200
Value
Parity
0
None
1
Even
2
Odd
Modbus Address
Parameter Name
Auxiliary Input A Type
(Dec)
(Hex)
Access
2120
0x0848
R/W
Target Setpoint Address
2121
0x0849
R/W
Master Transmit Format
2123
0x084B
R/W
Comms Write
Enable/Disable
Auxiliary Input A Input
Signal Break
Auxiliary Input A Input
Signal Under Range
Auxiliary Input A Input
Signal Over Range
2124
2127
2128
2129
0x084C
0x084F
0x0850
0x0851
R/W
RO
Values
Value
0
0 to 20mA DC
1
4 to 20mA DC
2
0 to 10V DC
3
2 to 10V DC
4
0 to 5V DC
5
1 to 5V DC
Target setpoint parameter address for master mode
Value
Integer
1
Integer with 1 decimal place
2
Floating point number
Value
Communications Status
0
Writing via serial comm. disabled
1
Writing via serial comm. enabled
Value
Auxiliary Input A Break Status
0
Inactive
1
Active
Auxiliary Input A Under Range Status
0
Inactive
1
Active
Value
RO
Data Format
0
Value
RO
Auxiliary A Input Type
Auxiliary Input A Over Range Status
0
Inactive
1
Active
Option Slot B Parameters
Modbus Address
Parameter Name
Auxiliary Input B Type
(Dec)
(Hex)
Access
2080
0x0820
R/W
53
Values
Value
Auxiliary B Input Type
0
0 to 20mA DC
1
4 to 20mA DC
2
0 to 10V DC
3
2 to 10V DC
4
0 to 5V DC
5
1 to 5V DC
6
0 to 100mV DC
7
>2000 Ohm Potentiometer
Modbus Address
Parameter Name
Option Slot B Module
Type
(Dec)
(Hex)
Access
2081
0x0821
RO
Values
Value
0
None Fitted
1
Auxiliary Input B with Digital Input B
255
Auxiliary Input B Input
Signal Break
Auxiliary Input B Input
Signal Under Range
Auxiliary Input B Input
Signal Over Range
Digital Input B Status
Calibration Status
2082
2083
2084
2085
2086
0x0822
0x0823
0x0824
0x0825
0x0826
Value
RO
1
Active
Inactive
1
Active
Auxiliary Input B Over Range Status
0
Inactive
1
Active
Digital Input B Status
0
Inactive
1
Active
Value
RO
Auxiliary Input B Under Range Status
0
Value
RO
Auxiliary Input B Break Status
Inactive
Value
RO
Error (unrecognised module)
0
Value
RO
Module Fitted In Slot B
Calibration Status
0
Calibration OK
1
Calibration Required
Option Slot 1 (Output 1) Parameters
Modbus Address
Parameter Name
Option Slot 1 (Output 1)
Module Type
(Dec)
(Hex)
Access
2130
0x0852
RO
Values
Value
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
255
Linear mA/V DC Output 1
Type
Digital Output 1 Status
2131
2132
0x0853
0x0854
R/W
Value
54
Error (unrecognized module)
Linear Output 1 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Value
RO
Auxiliary B Input Type
Digital Output 1 Status
0
Inactive
1
Active
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Linear Output 1 Level
Status
2134
0x0856
RO
Linear Output 1 Function
2144
0x0860
R/W
Digital Output 1 Function
2146
0x0862
R/W
(Relays, SSR Drivers or
Triacs. Linear Outputs are
mA or VDC)
Output 1 Alarm Selection
2148
0x0864
R/W
55
Values
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value
Linear Output 1 Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
4
Retransmit Process Variable Value
Value
Digital Output 1 Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Value
Output 1 Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Output 1 Event And Alarm
Selection
2150
0x0866
R/W
Values
Value
Output 1 Event And Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Output 1 Retransmit Min.
2152
0x0868
R/W
Limited by input range maximum and minimum
Output 1 Retransmit Max.
2153
0x0869
R/W
Limited by input range maximum and minimum
Option Slot 2 (Output 2) Parameters
Modbus Address
Parameter Name
Option Slot 2 (Output 2)
Module Type
(Dec)
(Hex)
Access
2160
0x0870
RO
Values
Value
56
Module Fitted In Slot 2
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
9
Dual Relay
10
Dual SSR Driver
11
24VDC Transmitter PSU
255
Error (unrecognized module)
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Linear mA/V DC Output 2
Type
2161
0x0871
R/W
Digital Output 2 or 2A
Status
Digital Output 2B Status
2162
2163
0x0872
0x0873
RO
RO
Linear Output 2 Level
Status
2164
0x0874
RO
Linear Output 2 or 2A
Function
2174
0x087E
R/W
Digital Output 2 or 2A
Function
Digital Output 2B Function
2176
2177
0x0880
0x0881
R/W
R/W
57
Values
Value
Linear Output 2 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Value
Digital Output 2 or 2A Status
0
Inactive
1
Active
Value
Digital Output 2B Status
0
Inactive
1
Active
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value
Linear Output 2 or 2A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
4
Retransmit Process Variable Value
Value
Digital Output 2 or 2A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Value
Digital Output 2B Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Modbus Address
Parameter Name
Output 2 or 2A Alarm
Selection
Output 2B Alarm Selection
(Dec)
(Hex)
Access
2178
0x0882
R/W
2179
0x0883
R/W
58
Values
Value
Output 2 or 2A Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 2B Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Output 2 or 2A Event And
Alarm Selection
2180
0x0884
R/W
59
Values
Value
Output 2 or 2A Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Modbus Address
Parameter Name
Output 2B Event And
Alarm Selection
(Dec)
(Hex)
Access
2181
0x0885
R/W
Values
Value
Output 2B Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Output 2 Retransmit Min.
2182
0x0886
R/W
Limited by input range maximum/minimum
Output 2 Retransmit Max.
2183
0x0887
R/W
Limited by input range maximum/minimum
Option Slot 3 (Output 3) Parameters
Modbus Address
Parameter Name
Option Slot 3 (Output 3)
Module Type
(Dec)
(Hex)
Access
2192
0x0890
RO
Values
Value
60
Module Fitted In Slot 2
0
None Fitted
1
Single Relay
2
Single SSR Driver
3
Linear mA/V DC
8
Triac
9
Dual Relay
10
Dual SSR Driver
11
24VDC Transmitter PSU
255
Error (unrecognized module)
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Linear mA/V DC Output 3
Type
2193
0x0891
R/W
Digital Output 3 or 3A
Status
Digital Output 3B Status
2194
2195
0x0892
0x0893
RO
RO
Linear Output 3 Level
Status
2196
0x0894
RO
Linear Output 3 or 3A
Function
2203
0x089B
R/W
Digital Output 3 or 3A
Function
Digital Output 3B Function
2205
2206
0x089D
0x089E
R/W
R/W
61
Values
Value
Linear Output 3 Type
0
0 to 5V DC
1
0 to 10V DC
2
2 to 10V DC
3
0 to 20mA DC
4
4 to 20mA DC
5
Variable 0 to 10VDC Transmitter PSU
Value
Digital Output 3 or 3A Status
0
Inactive
1
Active
Value
Digital Output 3B Status
0
Inactive
1
Active
-2.0% to 102.0% of nominal range
(control output will over/under drive by 2%).
Value
Linear Output 3 or 3A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Retransmit Actual Setpoint Value
4
Retransmit Process Variable Value
Value
Digital Output 3 or 3A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Value
Digital Output 3B Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Modbus Address
Parameter Name
Output 3 or 3A Alarm
Selection
Output 3B Alarm Selection
(Dec)
(Hex)
Access
2207
0x089F
R/W
2208
0x08A0
R/W
62
Values
Value
Output 3 or 3A Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 3B Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Output 3 or 3A Event And
Alarm Selection
2209
0x08A1
R/W
63
Values
Value
Output 3 or 3A Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Modbus Address
Parameter Name
Output 3B Event And
Alarm Selection
(Dec)
(Hex)
Access
2210
0x08A2
R/W
Values
Value
Output 3B Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Output 3 Retransmit Min.
2211
0x08A3
R/W
Limited by input range maximum/minimum
Output 3 Retransmit Max.
2212
0x08A4
R/W
Limited by input range maximum/minimum
64
Option Slot 4 (Output 4) Parameters
Modbus Address
Parameter Name
Option Slot 4 (Output 4)
Module Type
(Dec)
(Hex)
Access
2222
0x08AE
RO
Values
Value
0
None Fitted
1
Quad Relay
255
Digital Output 4 Status
2223
0x08AF
RO
Value
0
Digital Output 4A Function
Digital Output 4B Function
Digital Output 4C Function
Digital Output 4D Function
2230
2231
2232
2233
0x08B6
0x08B7
0x08B8
0x08B9
R/W
R/W
R/W
R/W
65
Module Fitted In Slot 4
Error (unrecognised module)
Digital Output 4A, 4B, 4C & 4D Status
All outputs inactive
Bit 0
Output 4A Active
Bit 1
Output 4B Active
Bit 2
Output 4C Active
Bit 3
Output 4D Active
Value
Digital Output 4A Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Value
Digital Output 4B Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Value
Digital Output 4C Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Value
Digital Output 4D Function
0
Disabled
1
Primary Output Power
2
Secondary Output Power
3
Alarm
4
Alarm and Event
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Output 4A Alarm Selection
2234
0x08BA
R/W
Output 4B Alarm Selection
2235
0x08BB
R/W
66
Values
Value
Output 4A Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 4B Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Modbus Address
Parameter Name
Output 4C Alarm
Selection
Output 4D Alarm
Selection
(Dec)
(Hex)
Access
2236
0x08BC
R/W
2237
0x08BD
R/W
67
Values
Value
Output 4C Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Value
Output 4D Alarm Selection
0
Alarm 1. Direct Acting
1
Alarm 1. Reverse Acting
2
Alarm 2, Direct Acting
3
Alarm 2. Reverse Acting
4
Alarm 3. Direct Acting
5
Alarm 3. Reverse Acting
6
Alarm 4. Direct Acting
7
Alarm 4. Reverse Acting
8
Alarm 5. Direct Acting
9
Alarm 5. Reverse Acting
10
OR of Alarm 1 or 2. Direct
11
OR of Alarm 1 or 2. Reverse
12
OR of Alarm 1, 2, or 3. Direct
13
OR of Alarm 1, 2, or 3. Reverse
14
OR of Alarm 1, 2, 3, or 4. Direct
15
OR of Alarm 1, 2, 3, or 4. Reverse
16
OR of Alarm 1, 2, 3, 4 or 5. Direct
17
OR of Alarm 1, 2, 3, 4 or 5. Reverse
Modbus Address
Parameter Name
Output 4A Event And
Alarm Selection
(Dec)
(Hex)
Access
2238
0x08BE
R/W
68
Values
Value
Output 4A Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Modbus Address
Parameter Name
Output 4B Event And
Alarm Selection
(Dec)
(Hex)
Access
2239
0x08BF
R/W
69
Values
Value
Output 4B Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Modbus Address
Parameter Name
Output 4C Event And
Alarm Selection
(Dec)
(Hex)
Access
2240
0x08C0
R/W
70
Values
Value
Output 4C Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Modbus Address
Parameter Name
Output 4D Event And
Alarm Selection
(Dec)
(Hex)
Access
2241
0x08C1
R/W
Values
Value
Output 4D Event/Alarm Selection
0
Event 1. Direct Acting
1
Event 1. Reverse Acting
2
Event 2. Direct Acting
3
Event 2. Reverse Acting
4
Event 3. Direct Acting
5
Event 3. Reverse Acting
6
Event 4. Direct Acting
7
Event 4. Reverse Acting
8
Event 5. Direct Acting
9
Event 5. Reverse Acting
10
Profile Running. Direct Acting
11
Profile Running. Reverse Acting
12
End of Profile. Direct Acting
13
End of Profile. Reverse Acting
14
Event 1 AND Alarm 1. Direct Acting
15
Event 1 AND Alarm 1. Reverse Acting
16
Event 2 AND Alarm 2. Direct Acting
17
Event 2 AND Alarm 2. Reverse Acting
18
Event 3 AND Alarm 3. Direct Acting
19
Event 3 AND Alarm 3. Reverse Acting
20
Event 4 AND Alarm 4. Direct Acting
21
Event 4 AND Alarm 4. Reverse Acting
22
Event 5 AND Alarm 5. Direct Acting
23
Event 5 AND Alarm 5. Reverse Acting
Setpoint Parameters
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Setpoint Minimum
3944
0x0F68
R/W
Valid between Scale Range Max. and Min.
Setpoint Maximum
3945
0x0F69
R/W
Valid between Scale Range Max. and Min.
Local Setpoint 1 Value
3960
0x0F78
R/W
Valid between Setpoint Maxi. and Min.
Local Setpoint 1 Offset
3961
0x0F79
R/W
Setpoint is always limited within Setpoint Maximum
and Minimum
Local Setpoint 2 Value
3962
0x0F7A
R/W
Valid between Setpoint Maximum and Minimum
Local Setpoint 2 Offset
3963
0x0F7B
R/W
Setpoint is always limited within Setpoint Maximum
and Minimum
71
Values
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Setpoint Selection Method
4000
0x0FA0
R/W
Alternate Setpoint Source
4001
0x0FA1
R/W
Values
Value
Setpoint Selection Method
0
Local Setpoint 1 only
1
Selected by Digital Input A
2
Selected by Digital Input B
3
Alternate Setpoint only
4
Operator or Comms selectable
Value
Alternate Setpoint Source
0
Local Setpoint 2
1
Remote Setpoint from Aux. Input A
2
Remote Setpoint from Aux. Input B
Auxiliary Input A Scale
Minimum
4073
0x0FE9
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input A Scale
Maximum
4074
0x0FEA
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input A Offset
4075
0x0FEB
R/W
Setpoint is always limited within Setpoint Maximum
and Minimum
Auxiliary Input A Value
4076
0x0FEC
RO
The value of analog Auxiliary Input A
Auxiliary Input B Scale
Minimum
4078
0x0FEE
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input B Scale
Maximum
4079
0x0FEF
R/W
Valid between Setpoint Maximum and Minimum
Auxiliary Input B Offset
4080
0x0FF0
R/W
Setpoint is always limited within Setpoint Maximum
and Minimum
Auxiliary Input B Value
4081
0x0FF1
RO
The value of analog Auxiliary Input B
User Setpoint Select
4122
0x101A
R/W
Value
Setpoint Select
0
Local Setpoint 1
1
Alternate setpoint
Setpoint Ramp Rate
4123
0x101B
R/W
0 to 10000
Operator Access To Setpoint Ramp Rate
4126
0x101E
R/W
The target setpoint value when ramping
Selected Setpoint
Actual Setpoint
Value
4127
8256
0x101F
0x2040
Operator Access To Ramp Rate
0
Disabled
1
Enabled
Value
RO
0 or >10000 = Off
Selected Setpoint
0
Local Setpoint 1
1
Alternate setpoint
The current instantaneous value of the active setpoint
RO
72
Control Parameters
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Manual Control Select
Method
4299
0x10CB
R/W
Control Enable Select
Method
4300
0x10CC
R/W
Values
Value
Setpoint Selection Method
0
Automatic Control Only
1
Manual Control Only
2
User Selectable From Key Pad
3
Digital input A
4
Digital input B
Value
Control Enable Selection Method
0
Enabled Only
1
Disabled Only
2
User Selectable From Key Pad
3
Digital input A
4
Digital input B
Primary Cycle Time
4301
0x10CD
R/W
0.5 to 512.0 Seconds
Secondary Cycle Time
4302
0x10CE
R/W
0.5 to 512.0 Seconds
User Setpoint Select
4122
0x101A
R/W
Value
Setpoint Select
0
Local Setpoint 1
1
Alternate setpoint
Setpoint Ramp Rate
4123
0x101B
R/W
0 to 10000
Control type
4310
0x10D6
R/W
The target setpoint value when ramping
Control Action
4311
0x10D7
R/W
0 or >10000 = Off
Value
Control Type
0
Single Control
1
Dual Control
Value
Control Type
0
Direct Acting
1
Reverse Acting
Primary Proportional Band
4312
0x10D8
R/W
0.0 to 999.9 (% of Input Span)
Secondary Proportional
Band
4313
0x10D9
R/W
0.0 to 999.9 (% of Input Span)
Integral Time Constant
4314
0x10DA
R/W
0.0 to 5999 Seconds
Derivative Time Constant
4315
0x10DB
R/W
0.0 to 5999 Seconds
Bias
4316
0x10DC
R/W
For single control 0 to 100.
For Dual control -100 to 100
Overlap/Deadband
4317
0x10DD
R/W
-100 to 100
On/Off Differential
4320
0x10E0
R/W
0.1 to 100
Primary Power Upper limit
4321
0x10E1
R/W
10 to 100% Can not be made smaller than Primary
Lower limit + 10
Heat/Primary Power
Lower limit
4322
0x10E2
R/W
0 to 90% Can not be made larger than Heat/Primary Upper limit – 10
Cool/Secondary Upper
Power limit
4323
0x10E3
R/W
10 to 100% Can not be made smaller than Cool/
Secondary Lower limit + 10
Cool/Secondary Power
Lower limit
4324
0x10E4
R/W
0 to 90% Can not be made larger than Cool/Secondary Upper limit – 10
73
Modbus Address
Parameter Name
Pre-Tune Engage/disengage
Self-Tune Engage/disengage
Loop Alarm Type
(Dec)
(Hex)
Access
4325
0x10E5
R/W
4326
4327
0x10E6
0x10E7
R/W
R/W
Values
Value
Pre-Tune Engage/disengage
0
Pre-Tune OFF
1
Run Pre-Tune
Value
Self-Tune Engage/disengage
0
Self-Tune OFF
1
Self-Tune ON
Value
Loop Alarm Type
1
Timed
2
Automatic (2x Integral Time)
Loop Alarm Time
4328
0x10E8
R/W
1 to 5999 Seconds after output saturation
Primary Power
4329
0x10E9
RO
The current primary power (0 to 100%)
Secondary Power
4330
0x10EA
RO
The current secondary power (0 to 100%)
Combined Power
4331
0x10EB
RO
The current combined PID power (-100 to 100%)
Pre-Tune Status
4332
0x10EC
RO
Self-Tune Status
Loop Alarm status
4333
4334
0x10ED
0x10EE
Value
4335
0x10EF
R/W
Auto Pre-tune
4336
0x10F0
R/W
6144
0x1800
Inactive
1
Active
R/W
74
Self-Tune Status
0
Inactive
1
Active
Value
RO
Input Failure Preset Power
Alarm 1 Type
0
Value
RO
Pre-Tune Status
Loop Alarm Status
0
Inactive
1
Active
Power output required if input signal is lost 0 to
100% (-100% to 100% for dual control).
Value
Auto Pre-Tune
0
Disabled
1
Enabled
Value
Alarm 1 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm Parameters
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Alarm 1 Value
6145
0x1801
R/W
Limited by the input range maximum and minimum
for Alarm types 0 and 1. Limited by the input span
for alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 1 Hysteresis
6146
0x1802
R/W
Limited by the input span
Alarm 1 Inhibit Enable/
disable
6147
0x1803
R/W
Alarm 1 Status
Alarm 1 Inhibit Status
Alarm 2 Type
6148
6149
6160
0x1804
0x1805
0x1810
Values
Value
0
Disabled
1
Enabled
Value
RO
RO
Alarm 1 Status
0
Inactive
1
Active
Value
R/W
Alarm 1 Inhibit Enable
Alarm 1 Inhibit Status
0
Not Inhibited
1
Inhibited
Value
Alarm 2 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 2 Value
6161
0x1811
R/W
Limited by the input range maximum and minimum
for Alarm types 0 and 1. Limited by the input span
for alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 2 Hysteresis
6162
0x1812
R/W
Limited by the input span
Alarm 2 Inhibit Enable/
disable
6163
0x1813
R/W
Alarm 2 Status
Alarm 2 Inhibit Status
6164
6165
0x1814
0x1815
Value
0
Disabled
1
Enabled
Value
RO
75
Alarm 2 Status
0
Inactive
1
Active
Value
RO
Alarm 2 Inhibit Enable
Alarm 2 Inhibit Status
0
Not Inhibited
1
Inhibited
Modbus Address
Parameter Name
Alarm 3 Type
(Dec)
(Hex)
Access
6176
0x1820
R/W
Values
Value
Alarm 3 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 3 Value
6177
0x1821
R/W
Limited by the input range maximum and minimum
for Alarm types 0 and 1. Limited by the input span
for alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 3 Hysteresis
6178
0x1822
R/W
Limited by the input span
Alarm 3 Inhibit Enable/
disable
6179
0x1823
R/W
Alarm 3 Status
Alarm 3 Inhibit Status
Alarm 4 Type
6180
6181
6192
0x1824
0x1825
0x1830
Value
0
Disabled
1
Enabled
Value
RO
R/W
Alarm 3 Status
0
Inactive
1
Active
Value
RO
Alarm 3 Inhibit Enable
Alarm 3 Inhibit Status
0
Not Inhibited
1
Inhibited
Value
Alarm 4 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 4 Value
6193
0x1831
R/W
Limited by the input range maximum and minimum
for Alarm types 0 and 1. Limited by the input span
for alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 4 Hysteresis
6194
0x1832
R/W
Limited by the input span
Alarm 4 Inhibit Enable/
disable
6195
0x1833
R/W
Alarm 4 Status
6196
0x1834
Value
0
Disabled
1
Enabled
Value
RO
76
Alarm 4 Inhibit Enable
Alarm 4 Status
0
Inactive
1
Active
Modbus Address
Parameter Name
Alarm 4 Inhibit Status
Alarm 5 Type
(Dec)
(Hex)
Access
6197
0x1835
RO
6208
0x1840
R/W
Values
Value
Alarm 4 Inhibit Status
0
Not Inhibited
1
Inhibited
Value
Alarm 5 Type
0
Process High Alarm
1
Process Low Alarm
2
Deviation Alarm (SP-PV)
3
Band Alarm
4
Loop Alarm
5
Input/Sensor Break Alarm
6
Auxiliary Input A Break Alarm
7
Auxiliary Input B Break Alarm
Alarm 5 Value
6209
0x1841
R/W
Limited by the input range maximum and minimum
for Alarm types 0 and 1. Limited by the input span
for alarm types 2 and 3. Not used for alarms 4 to 7.
Alarm 5 Hysteresis
6210
0x1842
R/W
Limited by the input span
Alarm 5 Inhibit Enable/
disable
6211
0x1843
R/W
Alarm 5 Status
Alarm 5 Inhibit Status
6212
6213
0x1844
0x1845
RO
RO
Value
Alarm 5 Inhibit Enable
0
Disabled
1
Enabled
Value
Alarm 5 Status
0
Inactive
1
Active
Value
Alarm 5 Inhibit Status
0
Not Inhibited
1
Inhibited
Recorder & Clock Parameters
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Recording Sample Interval
7550
0x1D7E
R/W
77
Values
Value
Recording Sample Interval
0
Every Second
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
8
Every 5 Minutes
9
Every 10 Minutes
10
Every 15 Minutes
11
Every 30 Minutes
Modbus Address
Parameter Name
Recording Mode
Start Stop Recording
Data Recorder Fitted
(Dec)
(Hex)
Access
7551
0x1D7F
R/W
7552
7553
0x1D80
0x1D81
R/W
Values
Value
0
Record until memory used
1
Continuous FIFO buffer
Value
Operator Start/Stop Recording
0
Stop Recording
1
Start Recording
Value
RO
Recording Mode
Data Recorder Fitted
0
Not Fitted
1
Recorder Fitted
Memory Remaining
7554
0x1D82
RO
Memory unused remaining left, in bytes
Time Remaining
7555
0x1D83
RO
Time remaining until memory is used up, in seconds
Recorder Trigger
7563
0x1D8B
R/W
Record Process Variable
Record Maximum PV
Between Samples
Record Minimum PV Between Samples
Record Actual Setpoint
Record Primary Power
Record Secondary Power
Record Alarm 1 Status
7572
7573
7574
7575
7576
7577
7578
0x1D94
0x1D95
0x1D96
0x1D97
0x1D98
0x1D99
0x1D9A
R/W
R/W
R/W
R/W
R/W
R/W
R/W
78
Value
Recorder Trigger
0
Operator start/stop
1
Recorder Menu start/stop
2
On Alarm (see Alarm 1-5 trigger below)
3
Digital input A
4
Digital input B
5
During running of profiles
Value
Record Process Variable
0
Do Not Record PV
1
Record PV Value
Value
Record Max PV Since Last Sample
0
Do Not Record Maximum PV
1
Record Max. PV Between Samples
Value
Record Min PV Since Last Sample
0
Do Not Record Minimum PV
1
Record Min. PV Between Samples
Value
Record Actual Setpoint Value
0
Do Not Record Setpoint
1
Record Actual Setpoint
Value
Record Primary Power Value
0
Do Not Record Primary Power
1
Record Primary Power
Value
Record Secondary Power Value
0
Do Not Record Secondary Power
1
Record Secondary Power
Value
Record Change Of State For Alarm 1
0
Do Not Record Alarm 1
1
Record Alarm 1
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Record Alarm 2 Status
7579
0x1D9B
R/W
Record Alarm 3 Status
Record Alarm 4 Status
Record Alarm 5 Status
Record Power
Trigger Recording On
Alarm 1
Trigger Recording On
Alarm 2
Trigger Recording On
Alarm 3
Trigger Recording On
Alarm 4
Trigger Recording On
Alarm 5
7580
7581
7582
7583
7584
7685
7686
7687
7688
0x1D9C
0x1D9D
0x1D9E
0x1D9F
0x1DA0
0x1DA1
0x1DA2
0x1DA3
0x1DA4
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
Sample Size
7595
0x1DA5
RO
Record Event 1
7599
0x1DAF
R/W
Record Event 2
Record Event 3
7600
7601
0x1DB0
0x1DB1
R/W
R/W
79
Values
Value
Record Change Of State For Alarm 2
0
Do Not Record Alarm 2
1
Record Alarm 2
Value
Record Change Of State For Alarm 3
0
Do Not Record Alarm 3
1
Record Alarm 3
Value
Record Change Of State For Alarm 4
0
Do Not Record Alarm 4
1
Record Alarm 4
Value
Record Change Of State For Alarm 5
0
Do Not Record Alarm 5
1
Record Alarm 5
Value
Record Power Turned On/Off
0
Do Not Record Power On/Off
1
Record Power On/Off
Value
Alarm 1 To Trigger Recording
0
Off
1
Trigger On Alarm 1 (if trigger is alarm)
Value
Alarm 2 To Trigger Recording
0
Off
1
Trigger On Alarm 2 (if trigger is alarm)
Value
Alarm 3 To Trigger Recording
0
Off
1
Trigger On Alarm 3 (if trigger is alarm)
Value
Alarm 4 To Trigger Recording
0
Off
1
Trigger On Alarm 4 (if trigger is alarm)
Value
Alarm 5 To Trigger Recording
0
Off
1
Trigger On Alarm 5 (if trigger is alarm)
Size in bytes, for current setup of recording sample
Value
Record Change Of State For Event 1
0
Do Not Record Event 1
1
Record Event 1
Value
Record Change Of State For Event 2
0
Do Not Record Event 2
1
Record Event 2
Value
Record Change Of State For Event 3
0
Do Not Record Event 3
1
Record Event 3
Modbus Address
Parameter Name
Record Event 4
Record Event 5
(Dec)
(Hex)
Access
7602
0x1DB2
R/W
7603
0x1DB3
R/W
Memory Used
7605
0x1DB5
RO
Date format
7868
0x1EBC
R/W
Values
Value
Record Change Of State For Event 4
0
Do Not Record Event 4
1
Record Event 4
Value
Record Change Of State For Event 5
0
Do Not Record Event 5
1
Record Event 5
Recorder Memory Used. 0 (Empty) to 100% (Full)
Value
Display Date Format
0
dd/mm/yyyy (European Default)
1
mm/dd/yyyy (USA Default)
Time
7869
0x1EBD
R/W
Format is the number of seconds since midnight.
Date
7870
0x1EBE
R/W
Format 6 digits. Example 280308 for 28/03/2008
Real Time Clock Fitted
7871
0x1EBF
RO
Day Of The Week
7872
0x1EC0
Value
R/W
Real Time Clock Fitted
0
Not Fitted
1
Fitted
Value
Day Of Week
1
Monday
2
Tuesday
3
Wednesday
4
Thursday
5
Friday
6
Saturday
7
Sunday
Display Parameters
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
LED 1 Label
7660
0x1DEC
R/W
LED 2 Label
7661
0x1DED
R/W
LED 3 Label
7662
0x1DEE
R/W
LED 4 Label
7663
0x1DEF
R/W
80
Values
5 ASCII characters, which can re read or written
using Modbus functions 16 or 23. Valid characters
are 0 to 9, a to z, A to Z, plus ( ) - and _.
Defaults: 1 = PRI (Primary); 2 = SEC (Secondary);
3 = TUNE (Tuning); 4 = ALARM (Alarm)
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
LED 1 Usage
7664
0x1DF0
R/W
LED 2 Usage
7665
0x1DF1
R/W
81
Values
Value
LED 1 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1
5
Alarm 2
6
Alarm 3
7
Alarm 4
8
Alarm 5
9
Event 1
10
Event 2
11
Event 3
12
Event 4
13
Event 5
14
Any Event
15
Manual Control
16
Profile Running
17
Profile Ended
Value
LED 2 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1
5
Alarm 2
6
Alarm 3
7
Alarm 4
8
Alarm 5
9
Event 1
10
Event 2
11
Event 3
12
Event 4
13
Event 5
14
Any Event
15
Manual Control
16
Profile Running
17
Profile Ended
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
LED 3 Usage
7666
0x1DF2
R/W
LED 4 Usage
7667
0x1DF3
R/W
82
Values
Value
LED 3 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1
5
Alarm 2
6
Alarm 3
7
Alarm 4
8
Alarm 5
9
Event 1
10
Event 2
11
Event 3
12
Event 4
13
Event 5
14
Any Event
15
Manual Control
16
Profile Running
17
Profile Ended
Value
LED 4 Usage
0
Primary Control
1
Secondary Control
2
Tuning
3
Any Alarm
4
Alarm 1
5
Alarm 2
6
Alarm 3
7
Alarm 4
8
Alarm 5
9
Event 1
10
Event 2
11
Event 3
12
Event 4
13
Event 5
14
Any Event
15
Manual Control
16
Profile Running
17
Profile Ended
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Backlight Color
7668
0x1DF4
R/W
Display Language
7675
0x1DFB
R/W
Display Contrast
7676
0x1DFC
R/W
Invert Display
7677
0x1DFD
R/W
Values
Value
Backlight Color
0
Green to Red on Alarm
1
Red to Green on Alarm
2
Permanent Green
3
Permanent Red
Value
Language
0
Main Display Language
1
Alternate Display Language
0 to 127
Value
Invert Display
0
Normal Display
1
Inverted Display
Setup Lock Code
7678
0x1DFE
R/W
1 to 9999. Default is 10
Configuration Lock Code
7679
0x1DFF
R/W
1 to 9999. Default is 10
Tuning Lock Code
7680
0x1E00
R/W
1 to 9999. Default is 10
Supervisor Lock Code
7681
0x1E01
R/W
1 to 9999. Default is 10
Profiler Lock Code
7682
0x1E02
R/W
1 to 9999. Default is 10
USB Lock Code
7683
0x1E03
R/W
1 to 9999. Default is 10
Recorder Lock Code
7684
0x1E04
R/W
1 to 9999. Default is 10
Read Only Operation
Mode
7685
0x1E05
R/W
Bar Graph Format
Trend View Sample Interval
7686
9000
0x1E06
0x2328
R/W
R/W
83
Value
Read Only Operation Mode
0
Operation Mode Read/Write
1
Operation Mode Read Only
Value
Bar Graph Format
0
Power Output
1
Control Deviation
2
% Memory Remaining
Value
Trend Sample Interval
0
Every Second
1
Every 2 Seconds
2
Every 5 Seconds
3
Every 10 Seconds
4
Every 15 Seconds
5
Every 30 Seconds
6
Every Minute
7
Every 2 Minutes
8
Every 5 Minutes
9
Every 10 Minutes
10
Every 15 Minutes
11
Every 30 Minutes
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Values To Display In Trend
View
9001
0x2329
R/W
Values
Value
Trend View Data
0
None (trend view off)
1
Process variable only
2
Process variable and setpoint
3
Process variable maximum &
minimum since last sample
Profiler Control & Status Parameters
Modbus Address
Parameter Name
Profile Run/Hold Signal
Profile Abort Signal
(Dec)
(Hex)
Access
8192
0x2000
R/W
8193
0x2001
R/W
Values
Value
Profile Run/Hold Signal Source
0
Operator Key Press Only
1
Digital input A
2
Digital input B
Value
Profile Abort Signal Source
0
Operator Key Press Only
1
Digital input A
2
Digital input B
Active Profiler Number
8243
0x2033
R/W
Currently selected profile number (1 to 64)
Active Segment Number
8244
0x2034
RO
Currently active segment (1 to 255)
Profiler Control
Commands
8245
0x2035
R/W
Value
Profiler Command
0
Do nothing
1
Run the currently selected profile
2
Hold the currently running profile
3
Abort the currently running profile
4
Jump to the next segment
5
Release the hold
6
Exit profiler, return to controller mode
Note: The Profiler Control Commands must be followed by a Profiler Control Confirmation Action command.
Profiler Control
Confirmation Action
Enable Edit While Running
Profile Control In Operation Mode
Profile Cycles Run
8257
8262
8260
8247
0x2041
0x2046
0x2044
0x2037
R/W
R/W
R/W
RO
Value
Implement Profiler Command
0
Do Not Implement Command
1
Implement previous Profiler Command
Value
Editing Current Running Profile
0
Editing current running profile forbidden
1
Editing current running profile allowed
Value
Profile Control From Operation Mode
0
Operation Mode profile control disabled
1
Operation Mode profile control enabled
The Number of times the currently running profile
has cycled
84
Modbus Address
Parameter Name
Event 1 Status
Event 2 Status
Event 3 Status
Event 4 Status
Event 5 Status
Segment Type Status
(Dec)
(Hex)
Access
8249
0x2039
RO
8250
8251
8252
8253
8258
0x203A
0x203B
0x203C
0x203D
0x2042
Value
RO
RO
Secondary Profile Status
8232
0x2028
RO
Event 1 Active
Status Of Event 2
0
Event 2 Inactive
1
Event 2 Active
Status Of Event 3
0
Event 3 Inactive
1
Event 3 Active
Status Of Event 4
0
Event 4 Inactive
1
Event 4 Active
Value
Status Of Event 5
0
Event 5 Inactive
1
Event 5 Active
Value
RO
0x2043
1
Value
RO
8259
Event 1 Inactive
Value
RO
Status Of Event 1
0
Value
RO
Currently Active Profile
Name
Values
Segment Type Status
0
No segment
1
Setpoint ramping up
2
Step
3
Dwell
4
Held
5
Loop
6
Join
7
End
8
Setpoint ramping down
The name of the currently selected profile
Value
0
Profile running
1
Input sensor break
2
Profile not valid
3
Controller in manual mode
4
Profile finished. Profiler is maintaining the last profile setpoint
5
Profile finished with control outputs
off
6
Profile control has ended. Unit is
Controller Mode.
Delay time
8233
0x2029
RO
The current start delay time remaining
Current Profile Running
Time
8235
0x202B
RO
The elapsed time of the current running profile
85
Modbus Address
Parameter Name
(Dec)
(Hex)
Access
Current Profile Remaining
Time
8236
0x202C
RO
The remaining time for the current running profile
Current Segment Running
Time
8237
0x202D
RO
The elapsed time of the current profile segment
Current Segment Remaining Time
8238
0x202E
RO
The remaining time for the current profile segment
Total Hold Time
8239
0x202F
RO
Total time the current profile has been held
Current Segment Loops
Run
8240
0x2030
RO
The number of times the current looping segment
has looped back
Profile Setup
8198
0x2006
R/W
Refer to the Profile Setup Over Modbus information
below
Profile Setup Via Modbus
Values
5. The very last segment of the profile must be one of
the end type segments. Thereafter, no more segments can be added to the specified profile. To add
a segment to an existing profile the insert segment
command must be used.
The information in this section is intended for advanced
users writing their own software code. Most users will
create or edit profiles using the instrument keypad, or
using the the PC software (available from your supplier). Either method allows quick and easy editing of
profiles.
Instruction Sequence to create a profile at
a specified profile position
Advanced users can setup or edit profiles by writing
to the Profile Configuration parameter at address 8198
(0x2006). This can only be accessed by using Modbus
function code 23 (0x17). The instrument replies with a
status message.
If this profile number is already in use then the
profile header data is overwritten but the segments associated with it are kept.
When creating a new profile the steps below must be
followed exactly, either to create a profile at the next
available position, or at a position that you specify.
1. Determine which profile positions are being used by
using the Command Code value PS (0x50, 0x53).
This command will return a list of all the profile positions currently being used.
Each message in the sequence includes a 2 byte Command Code that tells the instrument the purpose of the
message, and therefore the meaning of the data contained in it.
2. Choose a location that is not being used and write
the profile header data using the Command Code
value WP (0x57, 0x50).
Instruction Sequence to create a profile at
the next available position
The profile number is echoed back by the instrument in
the Edit Response Message.
1. Create a profile by writing the profile header data
using the Command Code value CP (0x43, 0x50).
This starts the profile creation process by reserving
a profile memory slot. The profile number is returned
by the instrument in the Edit Response Message.
3. Write the first segment using the Command Code
value Code WS (0x57, 0x53). This command will fill
the next available segment position and link it to the
profile created in step 1.
4. Write the second segment, again using Command
Code WS. This fills the next available segment position and links it to the segment created in step 2.
2. Write the first segment using the Command Code
value Code WS (0x57, 0x53). This command will fill
the next available segment position and link it to the
profile created in step 1.
3. Write the second segment, again using Command
Code WS. This fills the next available segment position and links it to the segment created in step 2.
5. Continue writing segments until the profile is complete (whilst remaining within the overall limit of 255
segments for all profiles combined). Each of these
segments fills the next available position and links it
to the previous segment specified.
4. Continue writing segments until the profile is complete (whilst remaining within the overall limit of 255
segments for all profiles combined). Each of these
segments fills the next available position and links it
to the previous segment specified.
6. The very last segment of the profile must be one of
the end type segments. Thereafter, no more segments can be added to the specified profile. To add
a segment to an existing profile the insert segment
command must be used.
86
Instruction Sequence to edit an existing
Profile Header
2. Use the command RS to read the 1st segment’s
data
3. Use the command RS to read the 2nd segment’s
data.
When a profile header is changed, the segments associated with it remain unchanged. They must be edited
separately if required.
4. Repeat steps 2 and 3 until an end segment is
reached.
1. Determine the number of the profile to be edited.
Use the Command Code value PS (0x50, 0x53)
which returns a list of all profile positions/numbers
currently in use.
The following rules apply when creating a profile over
communications:
• Profiles must always be terminated with an end
segment.
• Segments cannot be added after an end segment has been added.
• All changes made to the selected profile are immediately saved in the instrument.
2. Write a new profile header data using the Command
Code value EP (0x45, 0x50).
The profile number is echoed back by the instrument in the Edit Response Message.
Instruction Sequence to read a profile
1. Use the command RP to read the profile header
data
Creating or Editing a Profile Header
Creating or Editing a Profile Header - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument.
Function Code
23
17
Requires the multi read/write function.
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
01
01
Write Start Address High Byte
32
20
Write Start Address Low Byte
06
06
Write Quantity Of Registers High Byte
00
00
Write Quantity Of Registers Low Byte
19
13
38 or 40
26 or 28
Byte Count
Command Code High Byte
Comments
38dec / 0x26hex if creating a profile at
the next available location.
40dec / 0x28hex if creating a profile at
a specified location, or editing a profile.
67, 69 or 87 43, 45 or 57 Create Profile (CP) = 67dec / 0x43hex
Edit Profile (EP) = 69dec / 0x45hex
Write Profile (WP) = 87dec / 0x57hex
Command Code Low Byte
80
50
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
87
Note: The profile number is not included in the message when creating
a profile at the next available position.
Profile Name Character 1
A/R
A/R
Profile Name Character 2
A/R
A/R
Profile Name Character 3
A/R
A/R
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
A/R
A/R
Profile Name Character 10
A/R
A/R
Profile Name Character 11
A/R
A/R
Profile Name Character 12
A/R
A/R
Profile Name Character 13
A/R
A/R
Profile Name Character 14
A/R
A/R
Profile Name Character 15
A/R
A/R
Profile Name Character 16
A/R
A/R
Profile Start Signal High Byte
00
00
0 = No delay, 1 = After delay, 2 = At
Profile Start Signal Low Byte
A/R
A/R
Time/day
Profile Start Time (Byte 4 - High)
Profile Start Time (Byte 3)
Profile Start Time (Byte 2)
Floating point number
Profile Start Time (Byte 1 - Low)
Profile Start Day High Byte
00
00
Profile Start Day Low Byte
A/R
A/R
Profile Starting Setpoint High
00
00
Profile Starting Setpoint Low
A/R
A/R
Profile Recovery High Byte
00
00
Profile Recovery Low Byte
A/R
A/R
1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday,
9 = Monday to Saturday,
10 = Saturday And Sunday, 11= All Week
0 = Current Setpoint, 1 = Current Process Variable Value
0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint
3 = Use controller setpoint, 4 = Continue
profile from where it was when power
failed
Profile Recovery Time (Byte 4 - high)
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Floating point number
Profile Recovery Time (Byte 1 - Low)
Profile Abort action High Byte
00
00
Profile Abort Action Low Byte
A/R
A/R
0 = Control to off
1 = Maintain last profile setpoint
2 = Use controller setpoint
Profile Cycles High Byte
A/R
A/R
1 to 9999 or 10,000 for “Infinite”
Profile Cycles Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.
88
Creating, Editing or Inserting Segments
The Edit Segment command is used to alter segments
of an existing profile.
Creating new segments is only possible when a new
profile is being created (see above for instruction for
creating a profile at the next available position, or at
a position that you specify). An error is returned if the
correct sequence is not followed.
The segment number is in relation to the profile number, e.g. to edit or insert a segment at position 3 of
profile 1 the segment number will be 3, and to edit or
insert a segment at position 3 of profile 6 the segment
number will also be 3.
The Insert Segment command is used to add segments to an existing profile (one that already has an
end segment). This inserts a new segment at the position specified.
Creating or Editing a Profile Header
Creating, Editing or Inserting Segments - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument.
Function Code
23
17
Requires the multi read/write function.
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01
Create Segment (WS) = 11dec / 0x0Bhex
Insert Segment (IS) = 12dec / 0x0Chex
Edit A Segment (ES) = 12dec / 0x0Chex
Write Start Address High
32
20
Create Segment (WS) = 22dec / 0x16hex
Insert Segment (IS) = 24dec / 0x18hex
Edit A Segment (ES) = 24dec / 0x18hex
Write Start Address Low
06
06
Create Segment (WS) = 87dec / 0x57hex
Insert Segment (IS) = 73dec / 0x49hex
Edit A Segment (ES) = 69dec / 0x45hex
Write Quantity Of Registers High
00
00
Write Quantity Of Registers Low
11 or 12
0B or 0C
Byte Count
22 or 24
16 or 18
Command Code High Byte
87, 73 or 69
57 or 49
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Position High Byte
A/R
A/R
Segment Position Low Byte
A/R
A/R
Segment Type High Byte
00
00
Segment Type Low Byte
A/R
A/R
Segment Info A (Byte 4 - High)
Segment Info A (Byte 3)
Segment Info A (Byte 2)
Floating point number
Segment Info A (Byte 1 - Low)
89
Comments
Note: The Segment Position is not included in the message when creating a
segment at the next available position.
0 = Ramp Time, 1 = Ramp Rate,
2 = Step, 3 = Dwell, 4 = Hold, 5 = Loop
6 = Join, 7 = End, 8 = Repeat sequence
then end
The meaning of the data contained in
Segment Info A depends on the type of
segment it relates to. See following.
Creating, Editing or Inserting Segments - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Segment Info B (Byte 4 - High)
Segment Info B (Byte 3)
Floating point number
Segment Info B (Byte 2)
Comments
The meaning of the data contained in
Segment Info B depends on the type of
segment it relates to. See below.
Segment Info B (Byte 1 - Low)
Auto Hold Type High Byte
A/R
A/R
Auto Hold Type Low Byte
A/R
A/R
0 = Auto-Hold Off, 1 = Hold above SP,
2 = Hold below SP,3 - Hold above and
below SP
Auto Hold Value (Byte 4 - High)
Auto Hold Value (Byte 3)
Floating point number
Auto Hold Value (Byte 2)
Auto Hold Value (Byte 1 - Low)
Events High Byte
00
00
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Events Low Byte
The status of the five events is defined
by the lowest 5 bits of the low byte. A bit
value of 1 signifies the event is on.
Bit 0 = event 1, bit 1 = event 2, bit 3 =
event 4 and bit 5 = event 4.
Segment Data
The meaning of the data contained in Segment Info A
and B depends on the type of segment it relates to. Null
is shown for unused data, these data values should be
set to zero when writing the segment data.
The Segment Data is included in the command message when creating, editing or inserting segments (see
above). It is provided in two parts (Segment Info A and
B).
Segment Info
Segment
Type
A
B
Description
Ramp Time
Time
Target setpoint
Ramp to the target setpoint “B” in the time “A”
Ramp Rate
Ramp rate
Target setpoint
Ramp to the target setpoint “B” at the ramp rate
“A”
Step
Null
Target setpoint
Step to a target setpoint “B”
Dwell
Dwell time
Null
Stay at the current setpoint for a period of time “A”
Hold
0 = Operator
Null
Wait for the operator to release the hold
1 = Time of day
Start Time
Wait until time of the day “B” in seconds since
midnight. (recorder only).
2 = Aux A digital input
Null
Wait for digital input A signal
3 = Aux B digital input
Null
Wait for digital input B signal
Loop
Number of times to
repeat 1 to 9999
Segment number
Loop to the specified segment number “B” from
this point. Repeat this “A” times. Only segments
below the current segment can be entered. Two
loops must not cross each other.
Join
Null
Profile number
On completion of this profile jump run profile “B”
90
Segment Info
Segment
Type
End
Repeat
Sequence
Then End
A
B
Description
0 = Control off
Null
Turn off all control outputs.
1 = Maintain profile
setpoint
Null
Stay at the final setpoint of the profile
2 = Use controller
setpoint
Null
Use the active controller setpoint.
0 = Outputs off
Number of times to
repeat sequence
Repeat the profile sequence number “B” times,
then turn off the control outputs
1 = Maintain profile
setpoint
Repeat the profile sequence number “B” times,
then hold the last profile setpoint.
Repeat the profile sequence number “B” times,
then use the active controller setpoint.
The instrument replies to this message with an Edit Response Message.
Deleting Profiles
Deleting a profile removes the header of the specified
profile and any segments associated with it. Delete all
profiles wipes all profiles and segments from the instrument.
An individual profile can be deleted, or all profiles can
be cleared with a single message.
Delete Profiles - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument.
Function Code
23
17
Requires the multi read/write function.
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01
Write Start Address High
32
20
Write Start Address Low
06
06
Write Quantity Of Registers High
00
00
02 or 01
02 or 01
Delete A Profile (DP) = 02dec / 0x02hex
Delete All Profiles (DA) = 01dec / 0x01hex
04 or 02
04 or 02
Delete A Profile (DP) = 04dec / 0x04hex
Delete All Profiles (DA) = 02dec / 0x02hex
68
44
80 or 65
50 or 41
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Write Quantity Of Registers Low
Byte Count
Command Code High Byte
Command Code Low Byte
Comments
Delete A Profile (DP) = 80dec / 0x50hex
Delete All Profiles (DA) = 65dec / 0x41hex
Note: The profile number is not included in the message when deleting
all profiles.
The instrument replies to this message with an Edit Response Message.
91
Delete a Segment
The delete segment command deletes the specified
segment from the specified profile. The following segments are moved up one place in the profile (e.g. if segment 6 is deleted segment 7 now becomes segment 6).
Delete A Segment - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01
Write Start Address High
32
20
Write Start Address Low
06
06
Write Quantity Of Registers High
00
00
Write Quantity Of Registers Low
03
03
Byte Count
06
06
Command Code High Byte
68
44
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Number High Byte
A/R
A/R
Segment Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.
92
Get Segments Remaining
Returns the number of unused segments remaining in
the instrument. The number will be between 0 and 255,
depending on how many have been used in the profiles
so far created.
Get Segments Remaining - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Unit Address
A/R
A/R
The ID address of the instrument as required
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High
00
00
Read Quantity Of Registers Low
01
01
Write Start Address High
32
20
Write Start Address Low
06
06
Write Quantity Of Registers High
00
00
Write Quantity Of Registers Low
01
01
Byte Count
02
02
Command Code High Byte
83
53
Command Code Low Byte
82
52
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to this message with an Edit Response Message.
Edit Response Message from Instrument
The instrument replies to each profile or segment creation, edit or delete message with an Edit Response
Message. The same format is used when replying to
the Get Segments Remaining request.
Edit Response Message - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Unit Address
A/R
A/R
The ID address of the instrument as required
Function Code
23
17
The multi read/write function
Byte Count
02
02
Command Response High Byte
A/R
A/R
Command Response Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Two data bytes containing the Command Response data (see below)
The instrument replies to this message with an Edit Response Message.
93
Command Response Data
The error code shown will be as appropriate for the request message and instrument status.
The data contained in the Edit Response Message returned after each profile or segment edit message is
shown below. The data seen can be an error code, the
number of unused segments or the profile number following a successful profile header creation/edit.
Two Byte Response
Command Response Name Low Byte High Byte
Description
Profile Number
A/R
A/R
The number of the profile created or edited
Segments Remaining
A/R
A/R
The number of unused segments remaining
Command Successfully
0x4F
0x4B
The command requested executed without error
Command Not Recognized
0xFF
0xFF
The command is not recognized
Profile Number Invalid
0xF0
0x00
The profile number specified is not available.
Profile Name Invalid
0xF0
0x01
The profile name/characters are not valid
Start Signal Invalid
0xF0
0x02
The start signal is not recognized
Start Time Invalid
0xF0
0x03
The specified time is not within range
Start Day Invalid
0xF0
0x04
The specified day is not recognized
Starting Setpoint Invalid
0xF0
0x05
The specified starting setpoint is not recognized
Profile Recovery Invalid
0xF0
0x06
The profile recovery is not recognized
Recovery Time Invalid
0xF0
0x07
The recovery time is not within limits
Abort Action Invalid
0xF0
0x08
The abort action is not recognized
Profile Cycles Invalid
0xF0
0x09
The number of profile cycles is not within limits
Segment Number Invalid
0xF0
0x0A
The segment number is not valid for this profile
Segment Type Invalid
0xF0
0x0B
The segment type is not recognized
Segment Info A Invalid
0xF0
0x0C
The segment information A not valid for segment type
defined
Segment Info B Invalid
0xF0
0x0D
The segment information B is not valid for the segment
type defined
Auto Hold Type Invalid
0xF0
0x0E
The auto hold type is not recognized
Auto Hold Value Invalid
0xF0
0x0F
The auto hold value is not within input span
Events Value Invalid
0xF0
0x10
The events are not within range
No Segments Remaining
0xF0
0x11
There are no more segments available
Write Length Invalid
0xF0
0x12
The number of parameters to be written are
invalid for the function requested
Segment Setpoint Clamped
0xF0
0x13
The setpoint value entered was out of bounds. It has
been clamped within the units setpoint limits.
94
Read a Profile Header
Read A Profile Header - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
18
12
Write Start Address High Byte
32
20
Write Start Address Low Byte
06
06
Write Quantity Of Registers High Byte
00
00
Write Quantity Of Registers Low Byte
02
02
Byte Count
04
04
Command Code High Byte
82
52
Command Code Low Byte
80
50
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to the Read a Profile Header request as follows:
Read Profile Header - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
36
24
95
Comments
Read Profile Header - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Profile Name Character 1
A/R
A/R
Profile Name Character 2
A/R
A/R
Profile Name Character 3
A/R
A/R
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
A/R
A/R
Profile Name Character 10
A/R
A/R
Profile Name Character 11
A/R
A/R
Profile Name Character 12
A/R
A/R
Profile Name Character 13
A/R
A/R
Profile Name Character 14
A/R
A/R
Profile Name Character 15
A/R
A/R
Profile Name Character 16
A/R
A/R
Profile Start Signal High Byte
00
00
Profile Start Signal Low Byte
A/R
A/R
Comments
0 = No delay, 1 = After delay, 2 = At Time/day
Profile Start Time (Byte 4 - High)
Profile Start Time (Byte 3)
Profile Start Time (Byte 2)
Floating point number
Profile Start Time (Byte 1 - Low)
Profile Start Day High Byte
1 = Monday, 2 = Tuesday, 3 = Wednesday,
4 = Thursday, 5 = Friday, 6 = Saturday,
7 = Sunday, 8 = Monday to Friday,
9 = Monday to Saturday, 10 = Saturday And
Sunday, 11= All Week
Profile Start Day Low Byte
Profile Starting Setpoint High
0 = Current Setpoint, 1 = Current Process
Variable Value
Profile Starting Setpoint Low
Profile Recovery High Byte
0 = Control to off, 1 = Restart profile,
2 = Maintain last profile setpoint
3 = Use controller setpoint, 4 = Continue profile from where it was when power failed
Profile Recovery Low Byte
Profile Recovery Time (Byte 4 - high)
Profile Recovery Time (Byte 3)
Profile Recovery Time (Byte 2)
Floating point number
Profile Recovery Time (Byte 1 - Low)
Profile Abort action High Byte
Profile Abort Action Low Byte
0 = Control to off
1 = Maintain last profile setpoint
2 = Use controller setpoint
Profile Cycles High Byte
1 to 9999 or 10,000 for “Infinite”
Profile Cycles Low Byte
96
Read Profile Header - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Comments
CRC High Byte
CRC Low Byte
Read a Segment
Read a Segment - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
11
0B
Write Start Address High Byte
22
16
Write Start Address Low Byte
06
06
Write Quantity Of Registers High Byte
00
00
Write Quantity Of Registers Low Byte
03
03
Byte Count
06
06
Command Code High Byte
82
52
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Number High Byte
A/R
A/R
Segment Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
The instrument replies to the Read a Segment Header request as follows:
Read A Segment - Response (from instrument)
Data
(Dec)
(Hex)
Unit Address
Field Name
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
02
18
Command Response High Byte
82
52
Command Response Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
Segment Number High Byte
A/R
A/R
Segment Number Low Byte
A/R
A/R
97
Comments
Read A Segment - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Segment Type High Byte
00
00
Segment Type Low Byte
A/R
A/R
0 = Ramp Time, 1 = Ramp Rate,
2 = Step, 3 = Dwell, 4 = Hold, 5 = Loop
6 = Join, 7 = End, 8 = Repeat sequence then
end
Segment Info A (Byte 4 - High)
Segment Info A (Byte 3)
Segment Info A (Byte 2)
The meaning of the data contained in Segment Info A depends on the type of segment
Floating point number it relates to. See below.
Segment Info A (Byte 1 - Low)
Segment Info B (Byte 4 - High)
Segment Info B (Byte 3)
Segment Info B (Byte 2)
The meaning of the data contained in Segment Info B depends on the type of segment
Floating point number it relates to. See below.
Segment Info B (Byte 1 - Low)
Auto Hold Type High Byte
A/R
A/R
Auto Hold Type Low Byte
A/R
A/R
0 = Auto-Hold Off, 1 = Hold above SP,
2 = Hold below SP,3 - Hold above & below SP
Auto Hold Value (Byte 4 - High)
Auto Hold Value (Byte 3)
Auto Hold Value (Byte 2)
Floating point number
Auto Hold Value (Byte 1 - Low)
Events High Byte
00
00
Events Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
98
The status of the five events are defined by
the lowest 5 bits of the low byte. A bit value
of 1 signifies the event is on.
Bit 0 = event 1, bit 1 = event 2, bit 3 = event 4
and bit 5 = event 4.
Segment Data
The meaning of the data contained in Segment Info A
and B depends on the type of segment it relates to.
Null is shown for unused data, this can be any value.
The Segment Data is included in the response to
a Read Segment request. It is provided in two parts
(Segment Info A and B).
Segment Info
Segment Type
A
B
Description
Ramp Time
Time
Target setpoint
Ramp to the target setpoint “B” in the time “A”
Ramp Rate
Ramp rate
Target setpoint
Ramp to the target setpoint “B” at the ramp rate
“A”
Step
Null
Target setpoint
Step to a target setpoint “B”
Dwell
Dwell time
Null
Stay at the current setpoint for a period of time “A”
Hold
0 = Operator
Null
Wait for the operator to release the hold
1 = Time of day
Start Time
Wait until time of the day “B” in seconds since
midnight. (recorder only).
2 = Aux A digital
input
Null
Wait for digital input A signal
3 = Aux B digital
input
Null
Wait for digital input B signal
Loop
Number of times
to repeat 1 to
9999
Segment
number
Loop to the specified segment number “B” from
this point. Repeat this “A” times. Only segments
below the current segment can be entered. Two
loops must not cross each other.
Join
Null
Profile number
On completion of this profile jump run profile “B”
End
0 = Control off
Null
Turn off all control outputs.
1 = Maintain
;profile setpoint
Null
Stay at the final setpoint of the profile
2 = Use controller
setpoint
Null
Use the active controller setpoint.
0 = Outputs off
Number of
times to repeat
sequence
Repeat the profile sequence number “B” times,
then turn off the control outputs
Repeat Sequence
Then End
1 = Maintain
profile setpoint
Repeat the profile sequence number “B” times,
then hold the last profile setpoint.
Repeat the profile sequence number “B” times,
then use the active controller setpoint.
Read Profile Name
This command returns the name of the profile defined by the profile number requested.
Read Profile Header - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
08
08
Write Start Address High Byte
32
20
99
Comments
Read Profile Header - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Write Start Address Low Byte
06
06
Write Quantity Of Registers High Byte
00
00
Write Quantity Of Registers Low Byte
02
02
Byte Count
04
04
Command Code High Byte
80
50
Command Code Low Byte
78
4E
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Comments
The instrument replies to the Read Profile Name request as follows:
Read Profile Name - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
16
10
Profile Name Character 1
A/R
A/R
Profile Name Character 2
A/R
A/R
Profile Name Character 3
A/R
A/R
Profile Name Character 4
A/R
A/R
Profile Name Character 5
A/R
A/R
Profile Name Character 6
A/R
A/R
Profile Name Character 7
A/R
A/R
Profile Name Character 8
A/R
A/R
Profile Name Character 9
A/R
A/R
Profile Name Character 10
A/R
A/R
Profile Name Character 11
A/R
A/R
Profile Name Character 12
A/R
A/R
Profile Name Character 13
A/R
A/R
Profile Name Character 14
A/R
A/R
Profile Name Character 15
A/R
A/R
Profile Name Character 16
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
100
Comments
Read Profile Memory Status
of 0x01 indicates that the position is used by a profile. Using this command in conjunction with the read
profile name command will give a directory of profile
numbers to profile names.
This command returns the status of the profile memory
used. The response to this command is to return a table of all the profile numbers that are in use. A value of
0x00 indicates that the profile position is free and value
Read Profile Name
This command returns the name of the profile defined by the profile number requested.
Read Profile Memory Status - Request (to instrument)
Data
Field Name
(Dec)
(Hex)
Comments
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
Requires the multi read/write function
Read Start Address High Byte
32
20
Read Start Address Low Byte
06
06
Read Quantity Of Registers High Byte
00
00
Read Quantity Of Registers Low Byte
32
20
Write Start Address High Byte
32
20
Write Start Address Low Byte
06
06
Write Quantity Of Registers High Byte
00
00
Write Quantity Of Registers Low Byte
02
02
Byte Count
04
04
Command Code High Byte
80
50
Command Code Low Byte
83
53
Profile Number High Byte
A/R
A/R
Profile Number Low Byte
A/R
A/R
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
Read Profile Status
The instrument replies to the Read Profile Memory Status request as follows:
Read Profile Memory Status - Response (from instrument)
Data
Field Name
(Dec)
(Hex)
Unit Address
A/R
A/R
The ID address of the instrument
Function Code
23
17
The multi read/write function
Byte Count
64
40
Profile 1 Position
0 or 1
0 or 1
Profile 2 Position
0 or 1
0 or 1
Profile 63 Position
0 or 1
0 or 1
Profile 64 Position
0 or 1
0 or 1
CRC High Byte
A/R
A/R
CRC Low Byte
A/R
A/R
etc...
101
Comments
For each of the 64 possible profile positions,
a value of 0 is returned if the position is free,
or 1 if the position is empty.
Instrument Data
Modbus Address
(Dec)
(Hex)
Access
Serial Number 1
Parameter Name
210
0x00D2
RO
Values
The first 4 digits of the instrument’s Serial number.
Serial Number 2
211
0x00D3
RO
The digits 5 to 8 of the instrument’s Serial number.
Serial Number 3
212
0x00D4
RO
The digits 9 to 11 of the instrument’s Serial number.
Serial Number 4
213
0x00D5
RO
The digits 12 to 14 of the instrument’s Serial number.
Manufacture Day
370
0x0172
RO
Date of manufacture – 1 to 31 (day of month)
Manufacture Month
371
0x0173
RO
Month of manufacture – 1 to 12
Manufacture Year
372
0x0174
RO
4 digit number = Year of manufacture (e.g. 2008)
USB Option Fitted
7503
0x1D4F
RO
Value
0
USB Option
Not Fitted
Fitted
Data Recorder Fitted
Profiler Enabled
7868
8199
0x1EBC
0x2007
RO
RO
Value
Data Recorder Fitted
0
Not Fitted
1
Fitted
Value
Profiler Enabled
0
Profiler Not Enabled
1
Profiler Enabled
Software PRL
208
0x00D0
RO
Product Revision Level – Firmware Level
Hardware PRL
207
0x00CF
RO
Product Revision Level – Hardware Level
Firmware Type
217
0x00D9
RO
Firmware major version number
Firmware Version
218
0x00DA
RO
Firmware minor version number
Contact Details 1
400
0x0190
R/W
Contact Details 2
401
0x0191
R/W
Contact Details 3
402
0x0192
R/W
7 lines of user definable text - 25 ASCII characters
per line which can re read or written using Modbus
functions 16 or 23. Valid characters are 0 to 9, a to
z, A to Z, plus ( ) - and _.
Contact Details 4
403
0x0193
R/W
Contact Details 5
404
0x0194
R/W
Contact Details 6
405
0x0195
R/W
Contact Details 7
406
0x0196
R/W
102
Example. To write “My Company Name” to line 1
send:
[ADDRESS], 16, 01, 90, 00, 08, 10, 4D, 79, 20, 43,
6F, 6D, 70, 61, 6E, 79, 20, 4E, 61, 6D, 65, [CRC]
14 Calibration
Recalibration Procedure
Recalibration is carried out in five phases as shown in
the table below; each phase corresponds to a basic
input type.
CALIBRATION IS ONLY REQUIRED FOR INSTRUMENTS IN WHICH CALIBRATION ERRORS HAVE
BEEN ENCOUNTERED. REFER TO CALIBRATION CHECK BELOW.
The 50mV phase MUST be calibrated before
the thermocouple range.
Calibration must be performed by personnel
who are technically competent and authorised
to do so.
Table 27. Input Calibration phases
DC milli-volt Calibration
50 mV
Calibration Reminder
DC voltage Calibration
10 V
Calibration of each input type is carried out during
manufacture. This can be verified from Product Information Mode. Recorder versions can provide the user
with a calibration reminder if the application requires
regular checks – see Input Configuration for details.
DC milliamps Calibration
20 mA
RTD Calibration
200 ohm
Thermocouple Calibration
K type source at 0ºC
For most applications, re-calibration is not required
during the lifetime of the instrument.
1. For optimum accuracy, power-up the instrument for
30 minutes, then toggle the power off/on to restart
the instrument.
Equipment Required For Checking or
Calibrating The Universal Input
2. During the power-up “splash screen”, press
and
together until the Calibration Status screen
is displayed.
A suitable calibration signal source is required for each
input type. To verify the accuracy of the instrument
or carry out recalibration, the listed input sources are
required. These must have better than ±0.05% of the
reading accuracy:
3. Press
to select the first calibration phase (50mV
Calibration)
4. Ensure that an accurate 50mV signal has been applied to terminals 2 (+ve) and 3 (-ve), then press
and
to initiate the calibration.
1. DC linear inputs: 0 to 50mV, 0 to 10VDC and 0 to
20mADC.
5. During calibration the message “50mV DC Input
Calibrating” will display for a few seconds. This
should be followed by the “Calibration Successful”
confirmation.
2. Thermocouple inputs - complete with 0ºC reference
facility, appropriate thermocouple functions and
compensating leads (or equivalent).
6. If the input is misconnected or an incorrect signal is
applied, the calibration will be aborted and the display will show “Failed: Signal Too Small!” or “Failed:
Signal Too Large!”.
3. RTD inputs: decade resistance box with connections for three-wire input (or equivalent).
Calibration Check
The previous calibration value will be retained.
1. Set the instrument to the required input type.
7. Press
2. Power up the instrument and connect the correct
input leads.
8. Repeat this process for each input type until all the
phases are calibrated. For each phase, ensure that
the correct input is applied, using the correct connections.
Leave powered up for at least five minutes for RTD
and DC linear inputs, and at least 30 minutes for
thermocouple inputs.
to select the next calibration phase.
9. Once all calibration phases are completed, recorder
versions will display the Calibration Reminder Date.
If required, this can be changed to the date of your
next calibration check. Ensure that Calibration Reminders are enabled in Input Configuration to receive a reminder.
3. After the appropriate delay for stabilisation, check
the calibration by connecting the appropriate input
source and checking a number of cardinal points.
The observed readings should be within the tolerances stated in the Specification (see Appendix 2)
Press
4. Repeat the test for all required input types.
and
to exit to the Main Menu
Note: Calibration Mode automatically exits if there is
no button activity for two minutes
103
15 Appendix 1 - Glossary of Terms Used
Active Setpoint
Alarm Hysteresis
The term Active Setpoint is used to describe the currently selected setpoint when the instrument is in Controller Mode. Controllers can use Local Setpoint 1 and/
or the Alternative Setpoint. Only one of the setpoints
can be active at any time. During Profiler Control, the
setpoint value is controlled by the profiler function.
An adjustable band through which the process variable must pass before the alarm will change state. This
Hysteresis is only applicable to alarms based on the
Process Value or Control Deviation, as illustrated below. The band is always on the “safe” side of an alarm
point, e.g. a high alarm’s hysteresis band is below the
high alarm value, and a low alarm’s hysteresis is above
the low alarm value. Rate Of Change Alarms have a
different type of hysteresis based on the length of time
the rate is above the threshold.
Also refer to: Actual Setpoint, Alternative Setpoint,
Controller Mode, Local Setpoints, Profiler Mode, Remote Setpoint, Setpoint, and Setpoint Selection.
Settings = 1 LSD to full span from the setpoint.
Default value = 1 LSD.
Actual Setpoint
Actual Setpoint is the effective current value of the active setpoint. This will be different to the Active Setpoint’s target value if the setpoint is ramping. The actual setpoint will rise or fall at the ramp-rate set, until it
reaches its target setpoint value. During Profiler Control, the Actual Setpoint value is controlled by the profiler function.
Refer to the Alarm Hysteresis Operation diagram on
the next page.
Also refer to: Alarm Types, Loop Alarm, Alarm Operation, LSD, Minimum Duration Of Change, Process Variable, and Rate Of Change Alarm.
Also refer to: Active Setpoint, Controller Mode, Profiler
Mode, Setpoint, Setpoint Ramp Rate and Setpoint Selection.
Alarm Configuration
A sub-menu of Configuration Mode used to adjust the
alarm parameters. (Alarm types, values, hysteresis and
inhibiting).
Also refer to: Alarm Hysteresis, Alarm Inhibit, Alarm
Operation, Alarm Types and Configuration Mode.
104
Inactive
Inactive
Active
Figure 48.
48.
8.
PROCESS HIGH
ALARM
Alarm
m Hysteresis
H stere
Hy
esis Operation
Alarm Value
Alarm Hysteresis Value
Process Variable
Process Variable
Alarm Hysteresis Value
PROCESS LOW
ALARM
Alarm Value
Inactive
Inactive
Active
Alarm Value
(from Setpoint)
Alarm Hysteresis Value
Process Variable
BAND ALARM
Setpoint
Alarm Hysteresis Value
Alarm Value
(from Setpoint)
Inactive
tiv
ve
Inactive
Inactive
Active
Active
Active
Inactive
Inactive
DEVIATION HIGH
ALARM
Alarm Value
(from Setpoint)
Alarm Hysteresis Value
Process Variable
Setpoint
Setpoint
Process Variable
Alarm Hysteresis Value
DEVIATION LOW
ALARM
Alarm Value
(from Setpoint)
Alarm Inactive
Alarm Inactive
Alarm Active
105
Alarm Operation
Also refer to: Alarm Hysteresis, Alarm Inhibit, Alarm
Types, Band Alarm Value, Deviation Alarm, Latching
Relay, Logical Alarm Combinations, Loop Alarm, Process High Alarm and Process Low Alarm.
The Process and Deviation Alarm types are illustrated,
together with the action of any associated outputs.
Output Off .
.
Alarm
Process High
Alarm
Process High
Output On
Alarm
Alarm
Reverse-Acting
Output On
Process Low
Process Variable
. Output Off
.
Alarm
Alarm On
Alarm
Alarm On
Process Variable
Value
. Output Off
. Alarm
Alarm . Value
Direct-Acting
Output Off .
Process Low
Alarm
Alarm On
Process Variable
Output On
. Alarm
Alarm. Value
Reverse-Acting
Direct-Acting
Output
Alarm On
Alarm
Output Off .
Process Variable
Alarm Value
Alarm Value
Output On
. Output Off
Alarm On
Alarm
Alarm On
Reverse-Acting
Process Variable
Output Off
Output On
Alarm On
Band
Alarm On
Alarm. Value
Direct-Acting
Band
Output On
Process Variable
Alarm Value
Alarm Value
Output Off
Deviation High
Alarm
Alarm (+ve values)
. . Output
.
Direct-Acting
Alarm Value
Deviation High
Output On
Alarm (+ve values)
Alarm
Reverse-Acting
Deviation Low
Alarm (-ve values)
Direct-Acting
Deviation Low
Alarm (-ve values)
Reverse-Acting
Alarm Value
Output On
Alarm On
Alarm On
Process Variable
. Output Off
.
Alarm On
Process Variable
. Output Off
. Alarm
Process Variable
Alarm Value
Output Off . Output On
Alarm On . Alarm
Process Variable
Alarm Value
Setpoint
Figure 49.
Alarm Operation
106
Alarm Inhibit
Settings = Enabled or Disabled. Default value = Disabled.
Alarm Inhibit prevents unwanted process or deviation
alarm activation at power-up or when the controller
setpoint is changed. The alarm activation is inhibited
until a ‘Safe’ condition is present. The alarm operates
normally from that point onwards. E.g. if inhibited, a
low alarm will not activate at power-up, until the process has first risen above the alarm point and then falls
back below.
Also refer to: Pre-Tune, Self-Tune, PID and Tuning.
Automatic Reset
- Refer to Integral Action
Auxiliary Input
Settings = Inhibit or not inhibited for each alarm.
Default value = None Inhibited.
Up to two secondary linear input modules can be installed in Option Slot A and B. These can be used as
Remote Setpoint inputs. Signals can be mA, mV, VDC
or Potentiometer. Auxiliary Input B also has a Digital
Input onboard.
Also refer to: Alarm Types and Alarm Operation.
Alarm Types
Also refer to: Alternative Setpoint, Digital Input, Linear
Input, mADC, mVDC, Remote Setpoint and VDC
There are four basic alarm types, Process Alarms, Control Deviation Alarms, Rate of Signal Change Alarms
and Event Based Alarms.
Auxiliary Input Lower Limit
Process Alarms are based on the absolute value of the
Process Variable. If the PV rises above a high alarm
value, or falls below a low alarm value, the alarm will
become active. Deviation Alarms are based on the value of the Control Deviation error. If the PV is more than
the high deviation alarm value above setpoint, or more
than the low deviation alarm value below setpoint, the
alarm will become active.
When the auxiliary input is used to provide a Remote
Setpoint (RSP), this setting defines the value of the
RSP when the auxiliary input signal is at its minimum
value (e.g. for 4 to 20mA, the value when 4mA is applied). It may be adjusted within the range -1999 to
9999. However, the RSP value is always constrained
by the setpoint upper limit and Lower Limits.
Settings = -1999 to 9999
Range Lower Limit.
Rate Of Signal Change Alarms are based on the rate of
change of the PV. If the rate of change is greater than
the alarm value for longer that the Minimum Duration
time, the alarm will activate.
Default Value = Scale
Also refer to: Auxiliary Input, Auxiliary Input Upper
Limit, Auxiliary Input Offset, Remote Setpoint, Setpoint
and Setpoint Upper Limit and Setpoint Lower Limit.
Event based alarms activate when the condition for
that alarm type is true. These can be Signal Break, Low
Memory Or Loop Alarms.
Auxiliary Input Offset
Also refer to: Alarm Operation, Band Alarm Value, Control Deviation, Deviation Alarm, Loop Alarm, Process
High Alarm, Process Low Alarm, Process Variable,
Rate Of Change Alarm, and Setpoint.
Used to adjust the value of the Auxiliary Input. Positive values are added to the auxiliary input reading,
negative values are subtracted. It is adjustable in the
range –1999 to 9999. When the auxiliary input is used
to provide a Remote Setpoint, this setting is added to
(or subtracted from) the remote setpoint value, but the
setpoint is still constrained by the etpoint upper and
lower limits.
Alternative Setpoint
The instrument can have up to two setpoints. Local
Setpoint 1 and/or an Alternative Setpoint. The Alternative Setpoint can be chosen from Local Setpoint 2 or
a remote setpoint input from Auxiliary Input A or B if
either of these are fitted. One setpoint can be chosen
as the active at using the Setpoint Selection.
Settings = ±input span Default Value = Off.
Also refer to: Auxiliary Input, Remote Setpoint, Scale
Range Upper Limit, Scale Range Lower Limit Setpoint
Lower Limit and Setpoint Upper Limit.
Also refer to: Auxiliary Input, Local Setpoints, Remote
Setpoints; Setpoint and Setpoint Select.
Auxiliary Input Type
Auto Pre-Tune
Defines the type and range of the linear input signal for
the Auxiliary Input. It can be mADC, mVDC, VDC or potentiometer (mVDC and potentiometer are only available with the Full Auxiliary input in option slot B). This
can be used as a Remote Setpoint input.
When the Auto Pre-Tune is enabled, a Pre-Tune activation is attempted at every power-up (standard PreTune activation rules apply). Auto Pre-Tune is useful
when the process to be controlled may vary significantly each time it is run. Auto Pre-Tune ensures that
the process is tuned correctly each time the process
is started. Self-Tune may also be engaged to fine-tune
the controller.
Also refer to: Remote Setpoint and Setpoint.
107
Auxiliary Input Upper Limit
Bumpless Transfer
When the auxiliary input is used to provide a Remote
Setpoint (RSP), this setting defines the value of the
RSP when the auxiliary input signal is at its maximum
value (e.g. for 4 to 20mA, the value when 20mA is applied). It may be adjusted within the range -1999 to
9999. However, the RSP value is always constrained
by the setpoint upper limit and Lower Limits.
A method used to prevent sudden changes to the correcting variable, when switching between automatic
PI or PID and Manual control modes. During a transition from PI or PID to Manual control, the initial Manual
Power value is set to the previous automatic mode
value. The operator then adjusts the value as required.
During a transition from Manual control to PI or PID,
the initial automatic value is set to the previous Manual
mode value. The correcting variable level will gradually
adjusted by the control algorithm at a rate dependant
on the integral action resulting from the Integral Time
Constant value. Since integral action is essential to
Bumpless Transfer, this feature is not available if Integral is turned off.
Settings = -1999 to 9999
Range Lower Limit.
Default Value = Scale
Also refer to: Auxiliary Input, Auxiliary Input Lower
Limit, Auxiliary Input Offset, Remote Setpoint, Setpoint
and Setpoint Upper Limit and Setpoint Lower Limit.
Band Alarm Value
Also refer to: Correcting Variable, Integral Action, Manual Mode, PI and PID.
The amount of control deviation that is acceptable before a Band Alarm is activated. If the process variable
is more than the value of this band from the actual setpoint, the alarm will be active.
Cascade Control
Applications with two or more capacities (such as
heated jackets) are inherently difficult for a single instrument to control, due to large overshoots and unacceptable lags. The solution is to cascade two or more
controllers, each with its own input, in series to form a
single regulating device. The product setpoint temperature is set on the master controller. This is compared
to the product temperature, and the master’s PID output (mA or VDC) is fed into the auxiliary input of the
slave controller as a remote setpoint input. The RSP
is scaled to suit any expected temperature. The slave
loop’s natural response time should ideally be at least
5 times faster than the master.
Settings = 1 LSD to full input span from the setpoint.
Default value = 5 LSD’s.
Also refer to: Actual Setpoint, Alarm Operation, Alarm
Types, Control Deviation, Input Span, LSD and Process
Variable.
Bar Graphs
The instrument displays a bar-graph in the base operation mode screen. These can show
PID Power Output (single control = uni-directional,
dual control = bi-directional), Control Deviation (bidirectional) or for Data Recorder version %Memory
Used (uni-directional). Bar-graphs are uni-directional
or bi-directional depending on the information to be
displayed.
In the example, the maximum input represents 400ºC,
thus restricting the jacket temperature. At start-up the
master compares the product temperature (ambient) to
its setpoint (300ºC) and gives maximum output. This
sets the maximum (400ºC) setpoint on the slave, which
is compared to the jacket temperature (ambient) giving
maximum heater output.
Also refer to: Control Deviation, Data Recorder, Display
Configuration, Operation Mode, Main Menu and PID
Bias (Manual Reset)
Used to manually bias proportional output(s) to compensate for control deviation errors due to process load
variations. Bias is expressed as a percentage of output
power. This parameter is not applicable if the Primary
output is set to ON-OFF control. If the process variable settles below setpoint use a higher Bias value to
remove the error, if the process variable settles above
the setpoint use a lower Bias value. Integral action performs a similar function automatically when using PI or
PID control.
Lower Bias values will also help to reduce overshoot at
process start up.
As the jacket temperature rises, the slave’s heater output falls. The product temperature also rises at a rate
dependant on the transfer lag between the jacket and
product. This causes the master’s PID output to decrease, reducing the ‘jacket’ setpoint on the slave, effectively reducing the output to the heater. This continues until the system becomes balanced.
Settings = 0 to 100% (-100% to +100% for dual control).
Default value = 25%.
Also refer to: Control Deviation, Integral Action, ON/
OFF Control, PI Control, PID, Proportional Control,
Process Variable, and Setpoint.
108
When tuning a cascade system, first set the master to
manual mode. Tune the slave controller using proportional control only (I & D are not normally required) then
return the master to automatic PID mode before tuning
the master. The result is quicker, smoother control with
minimum overshoot and the ability to cope with load
changes, whilst keeping the jacket temperature within
acceptable tolerances.
action, PID tuning terms, power limits, sensor break
action, local setpoint values, setpoint ramp rates and
setpoint selection).
Also refer to: Auxiliary Input, Auxiliary Input Lower Limit,
Auxiliary Input Upper Limit, Derivative Action, Integral
Action, mADC, Manual Mode, Master & Slave, Proportional Control, PID, Remote Setpoint, Remote Setpoint
Lower Limit, Remote Setpoint Upper Limit, Setpoint,
Setpoint Select, Tuning and VDC.
Control Deviation
Also refer to: Configuration Mode, Control Action, Control Enable, Local Setpoints, Manual Mode, PID, Power
Limits, Sensor Break Pre-Set Power, Setpoint Ramping, Setpoint Selection and Tuning
Control Deviation is the difference between the Process Variable value and the Actual Setpoint. The Control deviation error is equal to PV – SP. This value can
be monitored using the bar-graph, and an excessive
deviation warning can be given by using a deviation
alarm.
Clock Configuration
Also refer to: Actual Setpoint, Alarm Types, Bar Graph,
Deviation Alarm, Process Variable and Setpoint
A sub-menu of Configuration Mode used to adjust the
parameters that relate to the settings for the Real Time
Clock fitted with the data recorder option (Date, time,
day of week and date format).
Control Action
The primary power output direction. Reverse action is
typically used with heating applications as it increases
the correcting variable as the process variable falls. A
secondary output’s action is always the opposite of the
primary output.
Also refer to: Data Recorder and Configuration Mode
Communications Write Enable
Enables/disables the changing of parameter values via
the Serial Communications link, if a communication
option such as Modbus RTU (RS485) or Modbus TCP
(Ethernet) is installed. When disabled, all communications are read-only.
Settings = Reverse or Direct Default value = Reverse.
Also refer to: Control Type, Correcting Variable, Direct
Acting Control and Reverse Acting Control.
Settings = Read Only or Read/Write. Default setting =
Enabled (read/write).
Control Enable/Disable
The PID controller outputs can be temporarily turned
off by disabling the control. All other functions continue
as normal. The control enable/disable function can be
controlled from the Control Configuration sub-menu or
optionally from Operation Mode or via a digital input if
one is fitted.
Also refer to: Ethernet, Modbus RTU, Modbus TCP,
RS485 and Serial Communications
Configuration Menu
A selection of sub-menus from which the user can adjust the major instrument settings. There are sub-menus
for the Inputs, Control, Outputs, Alarms, Communications, Recorder, Clock, Display and Lock Codes. Configuration Mode is entered from the Main Menu. An unlock code is required to access this mode.
Also refer to: Configuration Menu, Digital Input, Operation Mode and PID
Control Type
This defines if a controller has Single (unidirectional)
or Dual (bidirectional) control outputs. Single outputs
have a Primary output only. This can drive the PV in one
direction (e.g. heat only, cool only, increase humidity
etc). Dual outputs have both Primary and Secondary
outputs which can force the PV to increase or decrease
(e.g. heat & cool, humidify and dehumidify etc).
Refer to the Configuration Menu information in the
Configuration & Use section.
Also refer to: Alarm Configuration, Lock Codes, Clock
Configuration, Control Configuration, Display Configuration, Input Configuration, Main Menu, Output Configuration, Recorder Configuration, Serial Communications Configuration
Settings = Single or Dual
Contactor
Default value = Single.
- Refer to Relay
Also refer to: Control Action, PID, Primary Proportional
Band, Process Variable, and Secondary Proportional
Band.
Control Configuration
Controller
A sub-menu of Configuration Mode used to adjust the
parameters that relate to the control of the process.
(Enabling control, auto/manual mode, control type and
An instrument that controls a process variable to a
target setpoint, by applying a correcting variable. The
controller uses proportional (P, PI, PD o PID) or On-Off
109
control methods.
for the Primary and Secondary control outputs
Also refer to: Correcting Variable, Indicator, Limit Controller, On-Off Control, PD Control, PI Control, PID,
Process Variable, Proportional Control, Profiler and
Setpoint.
Settings = 0.5 to 512 seconds Default value = 32
secs.
Controller Mode
Also refer to: Correcting Variable, PID, Primary Proportional Band, Proportional Control, Relay, Secondary
Proportional Band, Solenoid Valve and Time Proportioning.
The normal operating mode when profiling is not fitted
or it is not being used.
Data Recorder
Also refer to: Controller. Profiler and Profiler Mode
The Data Recorder option can record the process value, setpoint, alarms and events over time. Recordings
can be transferred to a USB memory stick or via the
serial communications options. This option includes
a USB Interface and a battery backed-up Real Time
Clock.
Correcting Variable
The amount of output from a controller used to adjust
the process variable value up or down, to remove any
control deviation. The correcting variable is commonly
referred to as the controller output power.
Refer to the Data Recorder Option section of this manual for more details.
Also refer to: Control Deviation, PID, Primary Power
Output Limit and Process Variable
Also refer to: Recorder Configuration.
CPU
Deadband
This stands for Central Processing Unit and refers to
the onboard microprocessor that controls the measurement, control, alarm and display functions of the
instrument.
Derivative Action
- Refer to Overlap/Deadband.
The Derivative Time Constant defines how the control
action responds to the rate of change in the process
variable. The power is decreased if the PV is rising,
or increased if the PV is falling. This parameter is not
available if primary control output is set to On-Off, and
it is normally set to OFF in modulating value applications as it can cause premature wear due to constant
small adjustments to the valve position.
Current Proportioning Control
Current proportioning control is used to produce the
correcting variable on units with linear output(s). It
provides 4 to 20mA, 0-20mA, 0 to 5V, 0 to 10V or 2
- 10V DC for proportional control, PI, PD or PID control modes. On-Off control cannot be used with linear
outputs.
Settings = OFF or 0 seconds to 99 minutes 59 seconds Default value = 01.15.
Also refer to: Correcting Variable, Linear Output, OnOff Control, PD, PI, PID, Proportional Control, and Time
Proportional Control.
Also refer to: Modulating Valve, On-Off Control, PD
Control, PI Control, PID, Process Variable, Tuning and
Valve Motor Drive Control.
Custom Display Mode
Deviation Alarm Value
The user can copy up to 50 Configuration Menu parameters into Operation Mode using the PC software.
It the Custom Display in enabled in the Display Configuration sub-menu, these screens follow the normal
Operation Mode screens. In this mode these screens
are not pass-code protected.
Defines the amount of control deviation considered acceptable before a deviation alarm is activated. A positive value (deviation high) sets the alarm point above
the current actual setpoint, a negative value (deviation
low) sets the alarm point below actual setpoint. If the
process variable deviates from the actual setpoint by
a margin greater than this value, the deviation alarm
becomes active. If an alarm is required if the control
deviation is either side of the setpoint, consider using a
Band alarm or a logical combination of a deviation high
and deviation low alarm.
Also refer to: Control Configuration, Display Configuration and Operation Mode
Cycle Time
For time proportioning outputs, the cycle time is used to
define the time over which the controller averages the
ON vs. OFF time, in order to provide the required correcting variable. Each Time-Proportioning output has
its own adjustable cycle time. Shorter cycle times give
better control, but at the expense of reduce life when
used with electromechanical control devices (e.g. relays or solenoid valves). There are separate cycle times
Settings = 1 LSD to full span from the setpoint D e fault value = 5 LSD’s.
Also refer to: Actual Setpoint, Alarm Operation, Alarm
Types, Band Alarm, Control Deviation, Logical Combination, Process Variable and Setpoint.
110
Digital Input
Effective Setpoint
An input that can be driven to one of two states (active
or inactive) by and external voltage or a contact opening/closing. Digital Inputs can be used to set the instrument in to different states. Possible uses are to select
Auto/Manual Mode, Active Setpoint, Control Output
Enable/disable, Profile Run/Hold/Abort, Hold Segment
Release and Recording Start/Stop.
- Refer to Actual Setpoint.
Engineering Units
Also refer to: Active Setpoint, Control Enable, Data Recording, Manual Mode, Profiling and Segment Types.
The Process Variable and Setpoint displays can assigned engineering units to describe the type of parameter connected to the process input. The engineering units for linear inputs can be: °C; °F; °K; bar; %;
%RH; pH; psi or none. For temperature inputs (RTD or
Thermocouples) they can be °C; °F or °K.
Direct Acting Control
Also refer to: Linear Input, Process Input, Process Variable RTD and Thermocouple
Direct action is required for applications where the primary control output will be used to force the process
variable down towards the setpoint. A typical application is a Chiller. When the control action is selected as
direct acting, primary proportional control outputs decrease the correcting variable as the process variable
reduces within the proportional band, and primary OnOff outputs turn off when the process variable is less
than the setpoint. The control action of a secondary
output is always the opposite of the primary output.
Ethernet
A networking technology for local area networks
(LANs). Used to link computers and other equipment
in order to control or share data and control such devices. If fitted with an Ethernet serial communications
module in Option Slot A, this instrument can connect
to a Modbus TCP master device over a wired Ethernet
LAN.
Also refer to: Modbus TCP and Serial Communications
Also refer to: Control Action, Control Type, Correcting
Variable, On-Off Control, Process Variable, Proportional Control and Reverse Acting Control.
Indicator
An instrument that displays process values, but lacks
control features. Typically, alarm outputs are available
that will activate at preset PV values.
Display Configuration
A sub-menu of Configuration Mode used to adjust the
display, and the parameters that relate to Operation
Mode (Custom display enable, read-only operation
mode, bar-graph formatting, trend setup, display color
& contrast and language selection).
Also refer to: Controller, Limit Controller and Process
Variable.
Input Configuration
Also refer to: Bar-Graphs, Configuration Mode, Custom Display Mode, Operation Mode, Main Menu and
Trend Display.
A sub-menu of Configuration Mode, used to adjust the
parameters that relate to the process and auxiliary inputs (type, engineering units, decimal position, scaling,
offset, filter auxiliary input settings etc.).
Display Languages
Also refer to: Auxiliary Input, Configuration Mode and
Process Input.
The instrument supports two languages. The main language is English. The alternate language is chosen at
time of order, but can also be changed by downloading
a new file via the PC software. Current supported languages are English, French, German, Italian, Spanish,
Russian and Czech.
Input Filter Time Constant
This parameter is used to filter out extraneous impulses affecting the process variable value. The filtered PV
is used for all PV dependent functions (display, control,
alarm etc). Use this parameter with care as it will also
slow the response to genuine process changes.
Also refer to: Display Configuration, Operation Mode,
and Main Menu.
Settings = OFF or 0.1 to 100.0 seconds. Default value
= 2.0 seconds.
Display Resolution
The maximum number of digits that can be displayed
and/or the maximum number of decimal places. Numeric values (e.g. process variable, setpoints etc) are
limited to no more than 5 digits.
Also refer to: Process Variable.
Input Range
The maximum number of decimal places is selectable
from 0 to 3 places, but the overall 5-digit limit means
that larger values may not display the full number of
decimal places. For example, values >99.999 can have
no more than 2 decimal places(e.g. 100.00).
This is the overall process variable input range and
type as selected by the Process Input Type parameter.
This range can be scaled by the Scale Range Upper &
Lower Limits.
Also refer to: LSD
111
Linear Output
Also refer to: Input Span, Process Input, Scale Range
Lower Limit and Scale Range Upper Limit.
A mVDC, mADC or voltage signal used to provide a
proportional control or retransmit output.
Input Span
Also refer to: Linear Input mVDC, mADC, Proportional
Control, Retransmit Output and VDC
The measuring and display limits, as defined by the
Scale Range Lower and Scale Range Upper Limits.
The trimmed span value is also used as the basis for
calculations that relate to the span of the instrument
(e.g. proportional bands).
Limit Controller
A safety protection device that will shut down a process at a preset “exceed condition”. Limit controllers
work independently of the normal process controller
in order to prevent possible damage to equipment or
products. A fail-safe latching relay is fitted, which cannot be reset by the operator until the process has returned to a safe condition. Limit controllers are highly
recommended for any process that could potentially
become hazardous under fault conditions.
Settings = 100 LSD’s to the full Input Range. Default
value = Input Range
Also refer to: Input Range, LSD, Primary Proportional
Band, Scale Range Lower Limit, Scale Range Upper
Limit and Secondary Proportional Band.
Integral Time Constant
Also refer to: Controller and Latching Relay.
Integral action biases proportional control output(s) to
compensate for process load variations, until the control deviation value is zero. Integral Time Constant is
also known as “Automatic Reset”. Decreasing the time
constant increases the Integral action. This parameter
is not available if the primary output is set to On-Off.
Local Setpoints
Local setpoints are target values that are stored inside
the controller. These are normally entered by from the
front keypad, but can also be set via a serial communications link.
Settings = 1 sec to 99 min 59 sec and OFF. Default
value = 05:00
The instrument can have up to two setpoints. Local
Setpoint 1 and/or an Alternative Setpoint. The Alternative Setpoint can be chosen from Local Setpoint 2 or
a remote setpoint from an auxiliary input. One setpoint
can be chosen as the active at using the Setpoint Selection.
Also refer to: Control Deviation, On-Off Control, PI
Control, PID, Primary Proportional Band, Secondary
Proportional Band, Derivative Action, and Tuning.
Latching Relay
The value of the setpoints can be adjusted between the
Setpoint Upper Limit and Setpoint Lower Limits.
A type of relay that, once it becomes active, requires
a reset signal before it will deactivate. If latching relays
are required, they can be fitted externally as slaves to
the internal (non-latching) relays of this instrument.
Also refer to: Alternative Setpoint, Auxiliary Input, Remote Setpoint, Serial Communications, Setpoint, Setpoint Lower Limit, Setpoint Upper Limit, and Setpoint
Select.
Also refer to: Relay
LED
Lock Codes
Light Emitting Diode. LED’s are used as indicator lights
(e.g. for the alarm indication, automatic tuning stats
and manual mode).
The four-digit codes required when entering the Setup
Wizard, Configuration Mode, Tuning Menu, Supervisor Mode, USB Menu, Recorder Menu and Profiler
Setup Menu. These menus can be selected from the
Main Menu. The correct code must be entered to gain
access. If unlimited access is required for any of the
menus, its lock can be turned off by setting the value
to OFF. Refer to the Lock Code View information in the
Configuration & Use section.
Also refer to: Alarm Operation, Alarm Types, Automatic
Tuning and Manual Mode.
Linear Input
A mVDC, mADC or voltage signal used to represent the
value of the process variable. This can be any variable
that can be converted into a suitable DC linear signal.
Common examples are Humitity, pressure, pH or temperature.
Settings = 1 to 9999 or OFF.
Default value = 10
Also refer to: Configuration Mode, Main Menu, Profiler
Setup Menu, Recorder Menu, Setup Wizard, Supervisor Mode, Tuning Menu and USB Menu.
Auxiliary linear inputs can also be installed, these can
be used to provide a remote setpoint.
Logical Combination of Alarms
Also refer to: Auxiliary Input, Input Range, Linear Output, mVDC, mADC, Process Variable, Remote Setpoint
and VDC.
Outputs for alarms may be combined to create a Logical OR situation. Possible OR combinations are: Alarms
1 to 2; 1 to 3; 1 to 4 or 1 to 5.
112
Outputs for alarms & events may be combined to create a Logical AND situation. Possible AND combinations are: Alarm 1 & Event 1; Alarm 2 & Event 2; Alarm
3 & Event 3; Alarm 4 & Event 4; and Alarm 5 & Event 5.
Any suitable output may be assigned as a logical output and can be configured for reverse action or direct
action. The following table explains the concept of logical OR & AND outputs.
Also refer to: Alarm Operation, Alarm Types, Output
Configuration and Profile Events
Table 28. Logical Alarm Outputs
OUTPUT
ON
OFF
OFF
OFF
OUTPUT
OFF
ON
OFF
ON
Reverse-Acting
OFF
OFF
ON
ON
ALARM 2
OFF
ON
ON
ON
ALARM 1
OUTPUT
OFF
ON
OFF
ON
Direct Acting
OFF
OFF
ON
ON
ALARM 2
ALARM 1
Logical OR: Alarm 1 OR Alarm 2
ON
ON
ON
OFF
Loop Alarm
OFF
ON
OFF
ON
Reverse-Acting
OFF
OFF
ON
ON
ALARM 2
OFF
OFF
OFF
ON
ALARM 1
OUTPUT
OFF
ON
OFF
ON
Direct Acting
OFF
OFF
ON
ON
ALARM 2
ALARM 1
Logical AND: Alarm 1 AND Alarm 2
Also refer to: Alarm Types, Control Type, Manual Loop
Alarm Time, Linear Input, LSD, Manual Mode, On-Off
Control, PID, Pre-Tune, Process Variable and Tuning.
A loop alarm detects faults in the control feedback loop,
by continuously monitoring process variable response
to the control output(s). If one of the 5 alarms is defined to be a loop alarm, it repeatedly checks if the PID
control output is at saturation. If saturation is reached
(0% or 100% power for single control type, -100% or
+100% for dual control type), an internal timer is started. Thereafter, if the output has not caused the process
variable to be corrected by a predetermined amount ‘V’
after time ‘T’ has elapsed, the alarm becomes active.
Subsequently, the alarm repeatedly checks the process variable and the PID output. When the process
variable starts to change value in the correct sense or
when the PID output is no longer at the limit, the alarm
is deactivated.
LSD
The Least Significant Digit (LSD) is the smallest incremental value that can be shown at the defined display
resolution.
Also refer to: Display Resolution.
mADC
This stands for milliamp DC. It is used in reference to
the linear DC milliamp input ranges and the linear DC
milliamp outputs. Typically, these will be 0 to 20mA or
4 to 20mA.
For PID control, the loop alarm time ‘T’ can be automatic (twice the Integral Time value) or set to a user
defined value. Correct operation with the automatic
loop alarm time depends upon reasonably accurate
PID tuning. The user defined value is always used for
On-Off control, and the timer starts as soon as an output turns on.
Also refer to: Input Range, Linear Input, Linear Output,,
mVDC, Process Variable and VDC
Main Menu
The top-level menu that allows access to operation
mode as well as all other menus. These are: configuration mode, profiler setup and recorder menus, the setup wizard, supervisor mode and the tuning and USB
menus. Most menus require an unlock code to gain
access.
The value of ‘V’ is dependent upon the input type. For
Temperature inputs, V = 2°C or 3°F. For Linear inputs,
V = 10 x LSD
The loop alarm is automatically disabled during manual control mode and during execution of a Pre-Tune.
Upon exit from manual mode or after completion of
the Pre-Tune routine, the loop alarm is automatically
re-enabled.
Refer to the Main Menu information in the Configuration & Use section.
Also refer to: Configuration Mode, Lock Codes, Operation Mode, Profiler Setup Menu, Recorder Menu, Set-
113
up Wizard, Supervisor Mode, Tuning Menu and USB
Menu.
retransmission is use, the slave controller must have a
matching a remote setpoint input. It is possible to apply an offset to each zone if the slave has a Setpoint
offset parameter or by offsetting its remote setpoint input (or adjusting the scaling of this input).
Manual Loop Alarm Time
The loop alarm time used when a loop alarm is defined
to have a manually set time or whenever On-Off control is selected. This parameter determines the duration
of the output saturation condition after which the loop
alarm will be activated.
Settings = 1 sec to 99 mins 59 sec.
= 99:59.
Cascade Control is another type of Master & Slave
application where the slaves setpoint is set using the
master controllers PID power output.
The terms Master and Slave are also used in a different
context in relation to serial communications.
Default value
Also refer to: Cascade Control, Linear Output, Retransmit Output, Remote Setpoint, Auxiliary Input Offset,
Serial Communications and Setpoint.
Also refer to: Loop Alarm, and On-Off Control.
Manual Mode
Minimum Duration Of Change
If Manual Mode is enabled/disabled (from the control
configuration sub-menu, or the Auto/manual screen in
operation mode if it is available) it allows the controller to switch between automatic and manual control
modes. Auto/Manual Mode can also be switched using
a digital input if one has been configured for this function. Switching between automatic and manual modes
is achieved using “bumpless transfer”.
A form of alarm hysteresis unique to the Rate Of Change
Alarm. It is the minimum time that the rate of change in
the process variable must be above the alarm threshold, before the alarm will change state (from on to off,
or off to on).
Settings = 1 to 9999 secs.
Default value = 1sec.
Caution: If the duration is less than this time, the alarm
will not activate no matter how fast the rate of rise.
Manual Mode operates as follows:
The setpoint legend is replaced by the word MAN and
setpoint value is replaced by a % output power value.
This value may be adjusted using the
or
keys.
The power value can be varied from 0% to 100% for
controllers using single control type, and -100% to
+100% for controllers using dual control type. It is possible to use a controller as a permanent “Manual Station” by selecting Manual Control in the control configuration sub-menu.
Also refer to: Alarm Hysteresis, Alarm Types and Rate
Of Change Alarm.
Modbus RTU
Modbus RTU is the serial communications protocol
used on instruments fitted with the RS485 Communications module into Option Slot A. Alternatively, the
Modbus TCP protocol is available if the Ethernet Communications Module is fitted.
Modbus RTU is a Master/Slave protocol. Only the Master may initiate communications. Each slave is given a
unique address, and the message contains the Modbus address of the intended slave. Only this slave will
act on the command, even though other devices might
receive it (an exception is specific broadcast commands sent to address 0 which are acted upon by all
slaves but not acknowledged).
Manual Mode should be used with care because the power output level is set by the operator, therefore the PID algorithm is no longer
in control of the process. The operator MUST
maintain the process at the desired level manually. Manual power is not limited by the Power
Output Limits.
The commands can instruct the slave to change a value in one of its registers, or ask it to send back one
or more values contained in its registers. The Modbus
RTU format follows the messages with a cyclic redundancy check (CRC) checksum to ensure that the message arrives undamaged.
Also refer to: Bumpless Transfer, Control Configuration,
Control Type, Operation Mode, PID, and Power Output
Limits.
Master & Slave Controllers
This instrument can act as a Slave or as a Setpoint
Master over RS485. In this mode the unit continuously
sends its setpoint value using Modbus broadcast messages.
The terms master and slave are used to describe the
controllers in multi-zone applications where one instrument controls the setpoint of another. These can be
simple Setpoint Master/Slave applications where the
master controller transmits its setpoint to the slaves
via serial communications, or retransmits it as an analog DC linear output signal. If serial comms are used,
the master controller must be able to act as a communications master device and the slave must have a
compatible communications option fitted. If DC linear
Refer to the Serial Communications and Modbus Parameter sections of this manual for more information.
Also refer to: Modbus TCP, RS485 and Serial Communications.
114
Modbus TCP
On-Off Control
Modbus TCP is a version of the Modbus protocol for
networks that support the Internet Protocol, such as
Ethernet. It is available if the Ethernet Communications
Module is fitted into Option Slot A.
When operating in On-Off mode, the control output(s)
will turn on or off as the process variable crosses the
setpoint in a manner similar to a central heating thermostat. Some oscillation of the process variable is inevitable when using On-Off control.
This instrument can only act as a Slave when using
Modbus TCP. A master device initiates the communications, and the instrument only acts on the command
if it has been sent to its IP address. The data model
and function calls used by Modbus TCP and RTU are
identical; only the encapsulation is different. Modbus/
TCP does not require a checksum to ensure that the
message arrives intact.
On-Off control can be implemented only with Relay,
Triac or SSR driver outputs. On-Off operation can be
assigned to the Primary output alone (secondary output not present), Primary and Secondary outputs or
Secondary output only (with the primary Output set for
time proportional or current proportional control). OnOff Control is selected by setting the corresponding
proportional band(s) to On-Off.
Refer to the Serial Communications and Modbus Parameter sections of this manual for more information.
Also refer to: On-Off Differential, PID, Process Variable,
Primary Proportional Band, Secondary Proportional
Band, Relay, Setpoint, SSR Driver, Time Proportioning
Control and Triac.
Also refer to: Ethernet, Modbus RTU and Serial Communications.
Modulating Valve
On-Off Differential (On-Off Hysteresis)
A valve that can be positioned anywhere between fully
closed and fully open by means of an incorporated motor. A typical application would be controlling temperature in a furnace heated by gas burners. This instrument
can control modulating valves that have a positioning
circuit. These require proportional (mA or VDC) control
signal from a linear output, relative to the desired valve
position. PI control is used for valve control.
A switching differential, centred about the setpoint,
when using On-Off control. Relay ‘chatter’ can be
eliminated by proper adjustment of this parameter, but
too large a value may increase process variable oscillation to unacceptable levels. On-Off differential is also
known as hysteresis or deadband.
Settings = 0.1% to 10.0% of input span. Default value
= 0.5%.
To directly control the valves ‘open’ and ‘close’ motor
windings, a special Valve Motor Drive (VMD) controller algorithm is required. This instrument does not currently support this type of algorithm.
Also refer to: Input Span, On-Off Control, Process Variable, Relay and Setpoint
Operation Mode
Also refer to: Linear Output, PI Control, Proportional
Control and Valve Motor Drive Control.
The mode used during normal operation of the instrument. It can be accessed from the Main Menu, and
is the usual mode entered at power-up. The screens
shown include a main screen with bar-graph, a trend
view, information about the process, alarms plus optionally, selection of auto/manual control, control output disabling. Recorder and profiler information can be
displayed if these features are fitted. Up to 50 configuration menu screens can be defined with the PC software, and will be shown if the Custom Display mode is
enabled in the Display Configuration sub-menu.
Multi-Point Scaling
If the process input is connected to a linear input signal, multi-point scaling can be enabled in the Input
Configuration sub-menu. This allows the linearization
of a non-linear signal.
The Scale Range Upper & Lower Limits define the values shown when the input is at minimum and maximum values, and up to 15 breakpoints can scale input
vs. displayed value between these limits. It is advisable
to concentrate these break points in the area of the
range that has the greatest amount of non-linearity, or
the area of particular interest in the application.
Refer to the Operation Mode information in the Configuration & Use section.
Also refer to: Bar-Graphs, Configuration Mode, Custom
Display Mode, Display Configuration, Main Menu, Profiler Setup Menu, Recorder Menu. and Trend Display.
Also refer to: Input Configuration, Linear Input, Process
Input, Scale Range Lower Limit and Scale Range Upper Limit.
Output Configuration
mVDC
A sub-menu of Configuration Mode used to adjust the
parameters that relate to the Outputs (Linear output
type & scaling, output usage and scaling etc).
This stands for millivolt DC. It is used in reference to the
linear DC millivolt input ranges. Typically, these will be 0
to 50mV or 10 to 50mV
Also refer to: Configuration Mode and Linear Output.
Also refer to: Auxiliary Input, Input Range, Linear Input,
mADC, Process Variable and VDC
115
Overlap/Deadband
rameter has the effect of moving the On-Off Differential
band of the Secondary Output to create the overlap or
deadband. When Overlap/Deadband = OFF, the edge
of the Secondary Output Differential band coincides
with the point at which the Primary Output = 0%.
The Overlap/Deadband parameter defines the portion
of the primary and secondary proportional bands over
which both outputs are active (called Overlap), or neither is active (called Deadband). This is adjustable in
the range -20% to +20% of the sum of the two proportional bands. Positive values = Overlap, negative
values = Deadband.
The effect of the Overlap/Deadband parameter is
shown in the following table
Settings = -20% to +20%.
Overlap/deadband is applicable if the primary output
is set for On-Off control or there is no Secondary Output. If the Secondary Output is set for On-Off, this pa-
OVERLAP
Also refer to: On-Off Differential, On-Off Control, Primary Proportional Band and Secondary Proportional
Band.
Proportional Band 1
Output Power (%)
WITH PID
Proportional Band 2
Output 1
Output 2
Output 2
Output 1
Overlap
(positive value)
DEADBAND
Output Power (%)
WITH PID
Process Variable
Proportional
Proportional
Band 1
Band 2
Output 1
Output 2
Output 2
Output 1
Process Variable
Deadband
(negative value)
Proportional
Band 1
Output 2
Output 2 ON
Proportional Band 2 = 0
Output 1
Output 2 OFF
DEADBAND
WITH ON/OFF
Output Power (%)
OVERLAP &
Output 2
Output 1
Process Variable
ON/OFF Differential
Positive values
Negative values
Overlap/Dead
.
Figure 50.
Default value = 0.
Overlap/Deadband
116
PD Control
tional Band, Process Variable, Secondary Proportional
Band, Setpoint and Tuning.
Proportional and Derivative (PD) control combines proportional control with derivative action. It is similar to
PID control, but without Integral action.
PLC This stands for Programmable Logic Controller. A microprocessor based device used in machine control. It
is particularly suited to sequential control applications,
and uses “Ladder Logic” programming techniques.
Some PLC’s are capable of basic PID control, but tend
to be expensive and often give inferior levels of control.
Also refer to: Derivative, Integral, PID Control, Proportional Control and Tuning.
PI Control
Proportional and Integral Control (PI) is most often used
for modulating valve or motor control. It combines proportional control with integral action. It is similar to PID
Control, but without derivative action that can cause
excessive valve movement.
Also refer to: PID.
Pre-Tune
The Pre-Tune facility artificially disturbs the start-up
pattern so that a first approximation of the PID values
can be made prior to the setpoint being reached. During Pre-Tune, the controller outputs full Primary Power
until the process value has moved approximately halfway to the setpoint. At that point, power is removed
(or full Secondary Power is applied for Dual Control),
thereby introducing an oscillation. Once the oscillation
peak has passed, the Pre-Tune algorithm calculates an
approximation of the optimum PID tuning terms proportional band(s), integral and derivative. The Pre-Tune
process is shown in the following diagram.
Also refer to: Derivative, Integral, Modulating Valve, PID
Control, Proportional Control and Tuning.
PID Control
Proportional Integral and Derivative control maintains
accurate and stable levels in a process (e.g. when controlling a temperature). Proportional Control avoids the
oscillation characteristic of On-Off control by continuously adjusting the correcting variable output(s) to keep
the process variable stable. Integral action eliminates
control deviation errors, and Derivative action counters
rapid process movements.
When Pre-Tune is completed, the PID control output
power is applied using the calculated values. Pre-Tune
limits the possibility of setpoint overshoot when the
controller is new or the application has been changed.
Also refer to: Control Action, Control Deviation, Control
Enable, Control Type, Controller, Correcting Variable,
Derivative Action, Integral Action, Manual Mode, OnOff Control, PD Control, PI Control, Primary Propor-
Process Variable
Setpoint
SP – Initial PV
2
Initial PV
Pre-Tune
engaged
+100% Power (HEAT output)
here
Control Power
-100% Power (Cool output)
Figure 51.
Pre-Tune Operation
117
Process Input
Pre-Tune can be selected from the Automatic Tuning
Menu. It will not engage if either primary or secondary
outputs on a controller are set for On-Off control, during setpoint/profile ramping or if the process variable is
less than 5% of the input span from the setpoint. As a
single-shot operation, Pre-Tune will automatically disengage once complete, but can be configured to run at
every power up using the Auto Pre-Tune function.
The main input used to monitor the value process to
be controlled. This is known as the Process Variable or
PV. The input circuit is a “Universal” type, supporting
all common thermocouples and PT100 RTDs as well as
DC linear mV, voltage or mA signals suitable for almost
any parameter that can be converted into a electronic
signal. Linear signals can be scaled into engineering
units using the Scale Range Lower Limit and Scale
Range Upper Limit parameters.
Also refer to: Auto Pre-Tune, Control Type, Derivative
Action, On-Off Control, Input Span, , Integral, PID, Primary Proportional Band, Process Variable, Secondary Proportional Band, Self-Tune, Setpoint, Setpoint
Ramping, and Tuning.
Also refer to: Auxiliary Inputs, Engineering Units, Input
Span, PV Offset, Process Variable , Scale Range Lower
Limit and Scale Range Upper Limit.
Power Output Limits
Process Low Alarm n Value
Used to limit the power levels of the primary and secondary control outputs. Normally the instrument can
set these outputs to any value between 0% and 100%.
If this is undesirable in a particular application, individual settings can limit the primary power upper and
lower levels and the secondary power upper and lower
levels. The upper limit values must be higher than the
lower limits. These parameters are not applicable if that
output is set for On-Off control.
An independent low alarm value parameter is available
for each alarm that is set as Process Low type. It defines the process variable value below which Alarm n
will be active.
Settings = Scale Range Upper to Lower Limit
fault Value = Scale Range Lower Limit.
Also refer to: Alarm Operation, Alarm Types, Process
Variable, Scale Range Lower Limit and Scale Range
Upper Limit.
Use with caution: The instrument will not be able to
control the process if the limits do not allow the outputs
to be set to the correct values to maintain setpoint.
Lower Limit settings = 0% and 100%
= 0%.
Default Value
Upper Limit settings = 0% and 100%
= 100%.
Default Value
D e -
Process Variable (PV)
Process Variable is the parameter that is to be controlled. It is monitored by the main process input of the
instrument, and can be any type that can be measured
by that circuit. Common types are Thermocouple or
RTD temperature probes, or pressure, level, flow etc
from transducers that convert these parameters into
DC linear input signals (e.g. 4 to 20mA). Linear signals
can be scaled into engineering units using the Scale
Range Lower Limit and Scale Range Upper Limit parameters.
Also refer to: Control Type, On-Off Control and Setpoint.
Primary Proportional Band
The portion of the input span over which the Primary
Output power level is proportional to the process variable value. Applicable if Control Type is single or dual.
For dual control a Secondary Proportional band is used
for the second output. The Control Action can be Direct
or Reverse acting.
Also refer to: Actual Setpoint, Engineering Units, Input
Span, Linear Input, Process Input, RTD, Scale Range
Lower Limit, Scale Range Upper Limit and Thermocouple.
Settings = On-Off Control or 0.5% to 999.9% Default
Value = 10%.
Process Variable Offset
Also refer to: Control Action, Control Type, On-Off Control, Input Span, Overlap/Deadband, PID, Secondary
Proportional Band, and Tuning.
The Process variable offset is used to modify the measured process variable value. Use this parameter to
compensate for errors in the displayed process variable. Positive values are added to the process variable
reading, negative values are subtracted. Caution: This
parameter is in effect, a calibration adjustment; it must
be used with care. Injudicious use could lead to the
displayed value bearing no meaningful relationship to
the actual process variable. There is no front panel indication of when this parameter is in use.
Process High Alarm n Value
An independent high alarm value parameter is available for each alarm that is set as Process High type. It
defines the process variable value above which Alarm
n will be active.
Settings = Scale Range Upper to Lower Limit Default
Value = Scale Range Upper Limit.
Settings = ±input span Default Value = Off.
Also refer to: Input Span and Process Variable.
Also refer to: Alarm Operation, Alarm Types, Process
Variable, Scale Range Lower Limit and Scale Range
Upper Limit.
118
Profile Control Menu
Profiler
If the Profiler option is fitted, a Profile Control menu
is available from the Main Menu. It allows the user to
select or run a profile, and then control that profile (run,
hold, abort, skip to next segment etc.).
A profiler controls the value of the actual setpoint over
time; increasing, decreasing or holding its value as required. This is used in applications where the rate of
rise or fall of the process variable must be closely controlled, or where a value must be maintained for a period before moving to the next value.
Refer to the Profiler Control Menu information in the
Configuration & Use section.
If the Profiler option is fitted, up to 64 profiles can
be created with a maximum of 255 profile segments
shared amongst them. Each segment can activate/deactivate the five events according to the requirements
of the process.
Also refer to: Main Menu, Profile Setup Menu, Profiler
and Profiler Mode.
Profile Events
Events are outputs that can be made active during
profile segments. There are 5 possible events, each
of which can be defined to be active or inactive for
the duration of each segment, from the Profile Setup
Menu. For end segments, events selected to be active
stay on until the unit is powered down or a new profile
runs. It is possible to link event outputs to certain alarm
outputs in a logical AND situation.
Refer to the Profiler Option section.
Also refer to: Actual Setpoint, Controller Mode, Profile
Events, Profile Control Menu, Profile Header, Profile
Segments, Profile Setup Menu and Profiler Mode.
Profiler Mode
This mode is entered when a profile is run. In profiler
mode, additional screens are added to Operation Mode
which show the status of the profile. These screens are
not seen in Controller Mode. The instrument will remain
in Profiler Mode when the profile finishes or is aborted
unless the Segment End Type/Profile Abort Action is
set to “Use Controller Setpoint”.
Also refer to: Alarm Types, Logical Combinations, Profile Segments, Profile Setup Menu, Profiler and Profiler
Mode
Profile Header
The profile header contains information about how the
profile starts and stops, the power loss recovery action
and if the profile should repeat multiple times when run.
Also refer to: Controller Mode, Profile Control Menu,
Profile Segments, Profile Setup Menu, Profiler and Setpoint.
Refer to the Profile Components information in the Profiler Option section of this manual.
Proportional Control
Also refer to: Profile Segments, Profile Setup Menu,
Profiler and Profiler Mode.
Proportional control allows the correcting variable applied to the process to be set between 0 and 100% of
the amount available. If the control type is dual, two
outputs (primary & secondary) are available, each of
which can give proportional control. When the Proportional Band(s) are correctly tuned, the process variable
is maintained at a steady value, avoiding the oscillation
characteristic of On-Off control. Proportional control is
most commonly used in conjunction with Integral and
Derivative action to give PI. PD or PID control.
Profile Segments
Segments can be ramps, dwells, steps or special segments such as holds, ends or joins. A maximum of 255
segments are possible, shared amongst up to 64 profiles.
Refer to the Profile Components information in the Profiler Option section of this manual.
Also refer to: Control Type, Correcting Variable, Derivative Action, Integral Action, On-Off Control, PD, PI, PID,
Primary Proportional Band, Process Variable, Secondary Proportional Band, Setpoint and Tuning.
Also refer to: Profile Events, Profile Setup Menu, Profiler and Profiler Mode.
Profile Setup Menu
Rate
If the Profiler option is fitted, a Profile Setup menu is
available from the Main Menu. It allows the user to set
the General Profile Configuration parameters that apply to all profiles (e.g. Run/hold and abort methods
etc), and to create or edit the Profile Header and Profile
Segment Details. Profiles can also be deleted from this
menu. This menu is protected by a lock code.
- Refer to Derivative Action.
Rate of Change Alarm
An alarm based on the rate of change in the measured
process variable. If the PV changes at a rate greater
than the alarm level, the alarm will activate. The rate
of change must be above the alarm threshold for longer than the Minimum Duration of Change time, before
the alarm will change state (from on to off, or off to
on). Caution: If the duration is less than this time, the
Refer to the Profiler Setup Menu information in the
Configuration & Use section.
Also refer to: Lock Codes, Profile Control Menu, Profile
Header, Profile Segments, Profiler and Profiler Mode.
119
alarm will not activate no matter how fast the rate of
rise.
cal Setpoints, Master & Slave, mADC, mVDC, Setpoint
and Setpoint Select, and VDC.
Also refer to: Alarm Hysteresis, Alarm Operation, Alarm
Types, Minimum Duration Of Change and Process Variable.
Retransmit Output
A linear VDC or mADC output signal, proportional to
the Process Variable or Setpoint, for use by slave controllers or external devices, such as a Chart Recorder
or PLC. The output can be scaled to transmit any portion of the input or setpoint span.
Recorder Configuration
If the Data Recorder is fitted, a Recorder Configuration sub-menu is added to Configuration Mode. This
is used to adjust the recorder parameters (Recording
mode, sample interval, trigger and values to record)
and to show the recorder status.
Also refer to: Configuration Mode, and Data Recorder
Also refer to: Input Span, Linear Output, mADC, Master & Slave, PLC, Process Variable, Retransmit Output
Scale Maximum, Retransmit Scale Minimum, Setpoint
and VDC.
Recorder Option
Retransmit Output n Scale Maximum
Scales a linear output module in slot n if it has been
selected to retransmit the PV or SP. Retransmit Scale
Maximum defines the value of the process variable, or
setpoint, at which the output will be at its maximum
value. E.g. for a 0 to 5V output, it is the PV or SP value
corresponding to 5V. If this parameter is set to a value
less than that for Retransmit Output n Scale Minimum,
the relationship between the process variable/setpoint
value and the retransmission output is reversed so that
higher PV/SP values give a lower output level.
- Refer to Data Recorder.
Recorder Menu
If the Data Recorder is fitted, a Recorder Menu is added to the Main Menu. This is used to control the recording (start, stop, delete recordings etc) and to show the
recorder status. This menu is protected by a lock code.
Refer to the Recorder Menu information in the Configuration & Use section.
Settings = -1999 to 9999
Range Upper Limit.
Also refer to: Lock Codes, Main Menu and Data Recorder
Default value = Scale
Also refer to: Process Variable, Retransmit Output, Retransmit Output n Scale Minimum, Scale Range Upper
Limit and Setpoint.
Relay
An electromechanical switch operated by a solenoid
coil. Relays are commonly fitted as internal, time proportioning controller outputs. The limited current capacity and switching cycles of internal relays means
that they are usually connected to larger external slave
relays/contactors which are capable of switching much
larger currents and are easily replaced once worn out.
A suitably rated RC snubber should be connected to
relays to protect nearby equipment from the effects of
noise generated as they switch (refer to the Noise Suppression details in the Electrical Installation section).
Retransmit Output n Scale Minimum
Also refer to: Current Proportioning Control, Latching
Relay, SSR Driver, Time Proportioning Control and Triac
Scales a linear output module in slot n if it has been
selected to retransmit the PV or SP. Retransmit Scale
Minimum defines the value of the process variable, or
setpoint, at which the output will be at its minimum
value. E.g. for a 0 to 5V output, it is the PV or SP value
corresponding to 0V. If this parameter is set to a value
greater than that for Retransmit n Output Scale Maximum, the relationship between the process variable/
setpoint value and the retransmission output is reversed so that higher PV/SP values give a lower output
level.
Remote Setpoint (RSP)
Settings = -1999 to 9999
Range Lower Limit.
If the alternative setpoint type is selected to be a remote setpoint, and the selected setpoint is the alternative setpoint, an Auxiliary Input value is used to adjust the controller setpoint. The auxiliary linear input, is
given a VDC or mADC signal, or in some cases potentiometer or mV inputs. The Remote Setpoint value is
constrained by the Setpoint Upper Limit and Setpoint
Lower Limit settings. Typical applications are Setpoint
and Cascade Control Slaves.
Default value = Scale
Also refer to: Process Variable, Retransmit Output, Retransmit Output n Scale Maximum, Scale Range Lower
Limit and Setpoint.
Also refer to: Alternative Setpoint, Auxiliary Input, Auxiliary Input Lower Limit, Auxiliary Input Type, Auxiliary
Input Upper Limit, Cascade Control, Linear Input, Lo-
120
Reset To Defaults
RTD
This Configuration sub-menu selection returns all of
the instruments settings back to their factory defaults.
It should be used with great care, as the action cannot be undone. A reset is followed automatically by
the Setup Wizard. Users must use this wizard and/or
configuration menus to set all of the parameters to the
correct values for the intended application.
Resistance Temperature Detector. A temperature sensor that changes resistance with a change in the measured temperature. This instruments process input
supports PT100 (platinum, 100Ω at 0°C) and NI120
(nickel, 120Ω at 0°C) sensors. These have positive
temperature coefficients (PTC) which means their resistance increases with higher temperatures. The temperature measured by the sensor can be displayed as
°C; °F or °K.
Also refer to: Configuration Menu, and Setup Wizard
Also refer to: Input Range, Process Input and Thermocouple.
Reverse Acting Control
Reverse control action is required for applications
where the primary control output will be used to force
the process variable up towards the setpoint. A typical application is a furnace. When the control action is
selected as reverse acting, primary proportional control
outputs decrease the correcting variable as the process variable increases within the proportional band,
and primary On-Off outputs turn off when the process
variable exceeds the setpoint. The control action of a
secondary output is always the opposite of the primary
output.
Scale Range Upper Limit
For linear inputs, this parameter is used to scale the displayed process variable. It defines the displayed value
when the process variable input is at its maximum value
(e.g. if 4 to 20mA represents 0 to 14pH, this parameter
should be set to 14). The value can be set anywhere
from -1999 to 9999 and can be set to a value less than
(but not within 100 LSDs of) the Scale Range Lower
Limit, in which case the sense of the input is reversed.
Also refer to: Control Action, Control Type, Correcting Variable, Direct Acting Control, On-Off Control and
Proportional Control.
Settings = -1999 to 9999
Default value = 1000.
For thermocouple and RTD inputs, this parameter is
used to reduce the effective span of the input. All span
related functions work from the trimmed input span.
The parameter can be adjusted within the limits of the
range, but not less than 100 LSD’s above the Scale
RS485
RS485 (also known as EIA-485) is two-wire, half-duplex, multi-drop serial communications connection.
RS485 only defines the physical layer electrical specification, not the protocol that is transmitted across it.
It uses differential signals (the voltage difference between the wires) to convey data. One polarity indicates
a logic 1, the reverse polarity indicates logic 0. The applied voltages can be between +12 V and -7 volts, but
the difference of potential must be > 0.2 volts for valid
operation. RS485 can span distances up to 1200 metres using inexpensive twisted pair wires. Data speeds
can be as high as 35 Mbit/s over 10 m and 100 kbit/s
at 1200 m.
Range Lower Limit.
Settings = Range Max to Min. Default value = Max
value of selected temperature range).
Also refer to: Engineering Units, Input Range, Input
Span, LSD, Process Variable and Scale Range Lower
Limit.
Scale Range Lower Limit
For linear inputs, this parameter is used to scale the
displayed process variable. It defines the displayed
value when the process variable input is at its minimum
value (e.g. if 4 to 20mA represents 0 to 14pH, this parameter should be set to 0). The value can be set from
-1999 to 9999 and can be set to a value higher than
(but not within 100 LSDs of) the Scale Range Upper
Limit, in which case the sense of the input is reversed.
It is recommended that the wires be connected as series of point-to-point (multi-dropped) nodes (not in a
star or ring format), with 120ohm termination resistors
connected across the wires at the two ends of the network. Without termination resistors, reflections of the
signals can cause data corruption, and electrical noise
sensitivity is increased. The master device should normally provide powered resistors, to bias the wires to
known voltages when they are not being driven by any
device. Without biasing resistors, the data lines float
and noise can be interpreted as data when actually all
devices are silent.
Settings = -1999 to 9999
Default value = 0.
For thermocouple and RTD inputs, this parameter is
used to reduce the effective range of the input. All span
related functions work from the trimmed input span.
The parameter can be adjusted within the limits of the
range, but not less than 100 LSD’s below the Scale
Range Upper Limit.
Converters between RS485 and other formats are
available to allow computers to communicate with remote devices. Repeaters can also be used to extend
the distance and/or number of nodes on a network.
Settings = Range Max to Min. Default value = Min
value of selected temperature range).
Also refer to: Engineering Units, Input Range, Input
Span, LSD, Process Variable and Scale Range Upper
Limit.
Also refer to: Modbus RTU, and Serial Communications
121
Secondary Proportional Band
Also refer to: Control Deviation, Modulating Valves. OnOff Control, Pre-Tune, PI, PID, Setpoint and Tuning.
The portion of the input span over which the Secondary Output power level is proportional to the process
variable value. The Control action for the Secondary
Output is always the opposite of the Primary output.
The Secondary Proportional Band is only applicable
when Dual Control Type is used.
Sensor Break Pre-Set Power
If a thermocouple or RTD breaks, or it is disconnected,
the instrument detects this condition within 2 seconds,
and sets the control output(s) to the value defined by
the Sensor Break Pre-Set Power Output parameter in
the Control Configuration sub-menu. Process alarms
behave as though the PV has gone high.
Settings = On-Off Control or 0.5% to 999.9% Default
Value = 10%.
Also refer to: Control Action, Control Type, On-Off Control, Input Span, Overlap/Deadband, PID, Primary Proportional Band and Tuning.
Non-zero based linear inputs (e.g. 2 to10V or 4 to
20mA, but not 0 to 20mA) can also detect a sensor
break condition, setting the power to the Pre-Set Power value. Process alarms behave as though the PV has
gone low.
Self-Tune
Self-Tune continuously optimises tuning while a controller is operating. It uses a pattern recognition algorithm, which monitors the control deviation. The diagram shows a typical application involving a process
start up, setpoint change and load disturbance.
Also refer to: Input Range, Linear Input, RTD and Thermocouple.
Serial Communications Configuration
A sub-menu of Configuration Mode used to adjust the
serial communications parameters. (Addressing, data
rate, parity, master/slave settings and write enabling).
Temperature
Setpoint 2
Also refer to: Configuration Mode, Serial Communications
Setpoint 1
Load Disturbance
Serial Communications Option
A feature that allows other devices such as PC’s, PLC’s
or a master controller to read, or change the instruments parameters via an RS485 or Ethernet network.
Setpoint Change
Full details can be found in the Serial Communications
sections of this manual.
Time
Figure
Self-Tune
Operation
Figure
52.52.
Self-Tune
Operation
Also refer to: Ethernet, Master & Slave, Modbus RTU,
Modbus TCP, PLC, RS485 and Serial Communications
Configuration.
The deviation signal is shown shaded, and overshoots
have been exaggerated for clarity. The Self-Tune algorithm observes one complete deviation oscillation
before calculating a new set of PID values. Successive
deviation oscillations cause the values to be recalculated so that the controller converges on optimal control.
When the controller is switched off, these PID terms
are stored, and are used as starting values at the next
switch on. The stored values may not always be ideal, if
for instance the controller is brand new or the application has changed. In these cases, the user can utilise
Pre-Tune to establish new initial values. Self-Tune will
then fine-tune these values as it monitors any control
deviation.
Setpoint
The target value at which the instrument attempts to
maintain the process variable, by adjusting its control
output power (the correcting variable). There can be
either one or two setpoints. Local Setpoint 1 and/or
an Alternative Setpoint. The Alternative Setpoint can
be chosen from Local Setpoint 2 or a remote setpoint
input from Auxiliary Input A or B if either of these is fitted. One setpoint can be chosen as active using the
defined Setpoint Selection method. Setpoint values are
limited by the Setpoint Upper Limit and Setpoint Lower
Limits.
Use of continuous self-tuning is not always appropriate. For example applications which are frequently
subjected to artificial load disturbances, for example
where an oven door is likely to be frequently left open
for extended periods, can lead to errors in the calculations. In addition, because Self-Tune tunes for full PID
control, it is not recommended for valve control applications, which normally require PI control.
Also refer to: Alternative Setpoint, Auxiliary Input, Correcting Variable, Local Setpoints, Process Variable,
Remote Setpoint, Scale Range Lower Limit, Setpoint
Lower Limit, Setpoint Upper Limit and Setpoint Select
Setpoint Upper Limit
The maximum value allowed for setpoints. It should
be set to keep the setpoint below a value that might
Self-Tune cannot be engaged if the instrument is set for
On-Off Control.
122
Setpoint Selection
cause damage to the process. The adjustment range
is between Scale Range Upper Limit and the Setpoint
Lower Limit. If the value is moved below the current
value of a setpoint, that setpoint will automatically adjust to keep within bounds.
Settings = Within Input Span
Range Upper Limit
There can be either one or two setpoints. These can
be Local Setpoint 1 or an Alternative Setpoint chosen
from either Local Setpoint 2 or a remote setpoint input
from Auxiliary Input A or B if these are fitted. The Setpoint Select parameter in the control sub-menu defines
whether the Active Setpoint will be the Local Setpoint
1 only, the Alternative Setpoint only or if the choice of
active setpoint will be made from a digital input or an
Operation Mode selection screen.
Default Value = Scale
Also refer to: Input Span, Scale Range Upper Limit,
Setpoint and Setpoint Lower Limit.
Also refer to: Active Setpoint, Alternative Setpoint,
Auxiliary Input, Digital Input, Local Setpoints, Remote
Setpoint, Setpoint.
Setpoint Lower Limit
The minimum value allowed for setpoints. It should be
set to keep the setpoint above a value that might cause
damage to the process. The adjustment range is between the Setpoint Upper Limit and the Scale Range
Lower Limit. If the value is moved above the current
value a setpoint, that setpoint will automatically adjust
to keep within bounds.
Settings = Within Input Span
Range Lower Limit
Setup Wizard
A sub-set of the Configuration Menu parameters chosen to allow inexperienced users to easily set the instrument up for most simple applications. The parameters shown depend on the options installed.
Default Value = Scale
The Setup Wizard runs automatically at first ever power-up or whenever a Reset To Defaults is carried out.
A partial Wizard also runs whenever option modules
have been changed. The partial wizard only shows parameters affected by the changes made. The full Setup
Wizard can also be run manually from the Main Menu
(this requires entry of an un-lock code).
Also refer to: Input Span, Scale Range Lower Limit,
Setpoint and Setpoint Upper Limit.
Setpoint Ramp Editing
Enables or disables the viewing and adjustment of the
setpoint ramp rate in Operation Mode. This parameter
does not disable the ramping SP feature; it merely removes it from Operation Mode. It can still be viewed
and adjusted in the Control Configuration sub-menu.
To turn off ramping, the ramp rate must be set to OFF.
Once completed, the Setup Wizard exits to Operation
Mode.
Experts or users with more complex applications
should select the parameters they wish to set-up from
the Configuration Menus instead of using the Wizard.
Settings = Enabled or Disabled Default Value = Disabled
Refer to the Setup Wizard information in the Configuration & Use section.
Also refer to: Control Configuration, Operation Mode,
Process Variable, Setpoint and Setpoint Ramp Rate.
Also refer to: Lock Codes, Configuration Menu, Main
Menu, Operation Mode and Reset To Defaults.
Setpoint Ramp Rate
Solid State Relay (SSR)
The rate at which the actual setpoint value will move
towards its target value, when the setpoint value is adjusted or the active setpoint is changed. With ramping
in use, the initial value of the actual setpoint at power
up, or when switching back to automatic mode from
manual control, will be equal to the current process
variable value. The actual setpoint will rise/fall at the
ramp rate set, until it reaches the target setpoint value.
Setpoint ramping is used to protect the process from
sudden changes in the setpoint, which would result in
a rapid rise in the process variable.
Settings = 1 to 9999 LSDs per hour.
= OFF
An external device manufactured using two Silicone
Controlled Rectifiers in reverse parallel. They can be
used to replace mechanical relays in most AC power
applications. Some special SSRs can switch DC, but
most cannot. As a solid-state device, an SSR does not
suffer from contact degradation when switching electrical current. Much faster switching cycle times are
also possible, leading to superior control. The instrument’s SSR Driver output provides a time-proportioned
10VDC pulse for to the SSRs signal input terminals.
This causes conduction of current from the line supply
through the SSR to the load, when the pulse is on.
Default Value
Also refer to: Cycle Time, Time Proportioning Control,
Relay, and Triac.
Also refer to: Active Setpoint, Actual Setpoint, LSD,
Manual Mode, Process Variable, Setpoint, Setpoint
Ramp Editing and Setpoint Selection.
Solenoid Valve
An electromechanical device, use to control the flow of
gases or liquids. It has just two states, open or closed.
Usually, a spring holds the valve closed until a cur123
rent is passed through the solenoid coil forces it open.
Standard process controllers with time-proportioned
or On-Off outputs can be used to control these types
of valves.
ear mA or voltage output signal can be controlled.
Solenoid valves are often used with high/low flame gas
burners. A bypass supplies some gas at all times, but
not enough to heat the process more than a nominal
amount (low flame). A controller output opens the solenoid valve when the process requires additional heat
(high flame).
Time Proportioning Control
Also refer to: Control Deviation, Linear Output, Modulating Valve, and Valve Motor Control
Time proportioning control is accomplished by cycling
the output on and off during the prescribed cycle time,
whenever the process variable is within the proportional band(s). The PID control algorithm determines the
ratio of time (on vs. off) to achieve the level of the correcting variable required to remove the control deviation error. E.g. for a 32 second cycle time, 25% power
would result in the output turning on for 8 seconds,
then off to 24 seconds. This type of output might be
used with electrical contactors, solid state relays or
solenoid valves. Time proportioning control can be implemented with Relay, Triac or SSR Driver outputs for
either primary or secondary outputs.
Also refer to: Modulating Valves, On-Off Control and
Time Proportioning Control.
Supervisor Mode
Supervisor Mode allows access to a lock code protected sub-set of the main configuration parameters.
The unlock code is different from the higher level Configuration Menu unlock code. Up to 50 Configuration
Menu parameters can be chosen for inclusion in Supervisor Mode using the PC configuration software. If
none have been chosen, this mode is disabled.
Also refer to: Control Deviation, Correcting Variable,
Current Proportioning Control, Cycle Time, PID, Primary Proportional Band, Relay, Secondary Proportional
Band, Solenoid Valve, SSR and Triac.
Refer to the Supervisor Mode information in the Configuration & Use section.
Trend Display
Also refer to: Configuration Menu and Lock Codes
Trend View is a graphical representation of recent process conditions. This feature is available on all variants.
It does not rely on the Data Recorder option, and does
not retain the stored data if the power is turned off.
The trend shows the most recent 120 out of 240 stored
data points. Its scale adjusts automatically for the best
resolution for the visible data. This data can be the process variable; process variable & setpoint (shown as a
doted line), or the minimum and maximum value of the
process variable measured since the last sample. Any
active alarm(s) are indicated above the graph. The user
can scroll the right hand cursor line back to examine
all 240 data points. The sample interval and data to
display is set in Display Configuration.
Thermocouple
A temperature sensor made from two different metals. They convert temperature difference between their
cold junction (the measuring instrument) and the hot
junction, into a small signal or a few microvolts per °C.
Thermocouples are cheap and interchangeable, but
the wires and connectors used must match the metals
used in their construction. They can measure a wide
range of temperatures; some thermocouples can withstand very high temperatures such as furnaces. The
main limitation of thermocouples is accuracy.
The temperature measured by the thermocouple can
be displayed as °C; °F or °K.
Also refer to: Alarm Types, Display Configuration, Operation Mode, and Process Variable, Setpoint.
The color codes for the common types are shown in
the Thermocouple Wire Identification Chart in the Electrical Installation Section of this manual.
Tuning
Also refer to: Engineering Units, Input Range, Process
Input and RTD.
PID Controllers must be tuned to the process in order
for them to attain the optimum level of control. Adjustment is made to the tuning terms either manually, or
by utilising the controller’s automatic tuning facilities.
Tuning is not required if the controller is configured for
On-Off Control.
Three Point Stepping Control
Modulating valves normally require a special “Three
Point Stepping” control algorithm. This which provides
an output to move the valve further open, or further
closed whenever there is a control deviation error.
When this error is zero, no further output is required to
maintain control unless load conditions change. This
type of controller is often called a Valve Motor Drive
controller. This instrument does not currently have a
three point stepping algorithm.
Also refer to: Auto Pre-Tune, Controller, Derivative Action, Integral Action, On-Off control, PID, Pre-Tune, Primary Proportional Band, Self-Tune, Secondary Proportional Band and Tuning Menu.
Tuning Menu
The Tuning Menu can be accessed from the Main
Menu. This menu is lock code protected.
However, modulating valves that have a valve positioning circuitry to adjust the valve position from a DC lin-
It gives access to the Pre-tune, Auto Pre-Tune and Self124
tune facilities. These assist with PID tuning, by setting
up Proportional band(s), Integral and Derivative parameter values. Tuning is not required for On-Off control.
If the Data Recorder option is present, the recordings
can be downloaded to the stick for transport to the users PC for analysis. If the Profiler option is present, profiles can be downloaded to the stick or upload to the
instrument using a pre-stored file that was downloaded
earlier, created using the PC software, or even taken
from another instrument.
Pre-tune can be used to set PID parameters approximately. Self-tune may then be used to optimise the tuning if required. Pre-tune can be set to run automatically
after every power-up by enabling Auto Pre-Tune.
Refer to the Automatic Tuning information in the Configuration & Use section.
Refer to the USB Menu information in the Configuration
& Use section.
Also refer to: Auto Pre-Tune, Derivative Action, Integral
Action, Lock Codes, Main Menu, On-Off control, PID,
Pre-Tune, Primary Proportional Band, Self-Tune, Secondary Proportional Band and Tuning Menu.
Valve Motor Drive Control (VMD)
Also refer to: Data Recorder, Lock Codes, Main Menu
and Profiler
This instrument can only control modulating valves that
have a valve positioning circuitry that adjusts the valve
position according to the level a DC linear mA or voltage output signal. Such valves normally require PI control instead of full PID.
Triac
A small internal solid state relay, which can be used in
place of a mechanical relay in applications switching
low power AC, up to 1 amp. Like a relay, the output
is time proportioned, but much faster switching cycle
times are also possible, leading to superior control. As
a solid-state device, a Triac does not suffer from contact degradation when switching electrical currents. A
snubber should be fitted across inductive loads to ensure reliable switch off the Triac. A triac cannot be used
to switch DC power.
Motorzed modulating valves that do not have this type
of circuit require special Valve Motor Drive controllers
which have a “Three Point Stepping” control algorithm.
Solenoid valves can also be controlled using the standard PID algorithm as they behave in a similar way to
relays, having just two states, open or closed.
Also refer to: Cycle Time, Relay, SSR and Time Proportioning Control.
Also refer to: Control Deviation, Linear Output, Modulating Valve, PI Control, PID, Relay, Solenoid Valve, and
Three Point Stepping Control.
USB Menu
VDC
If the USB option is fitted, the USB Menu can be accessed from the Main Menu. This menu is lock code
protected.
This stands for Volts DC. It is used in reference to the
linear DC Voltage input ranges. Typically, these will be
0 to 5V, 1 to 5V, 0 to 10V or 2 to 10VDC. Linear outputs
can also provide DC voltages.
The USB Menu allows the user to read or write files
to a USB memory stick. The current configuration of
the instrument can be downloaded to the stick or the
instrument can be completely reconfigured using a
pre-stored file that has been downloaded earlier, created using the PC software, or even taken from another
instrument.
Also refer to: Auxiliary Input, Input Range, Linear Input,
Linear Output, mADC and mVDC..
VMD
- Refer to Valve Motor Control.
125
16 PC Software
The primary function of the software is to create, download and store instrument configurations and profiles.
Additionally, changes can be made to the operation
of the instrument; adding extra screens into Operation Mode, enabling and configuring Supervisor Mode,
changing the contact details or the function of the front
LED’s. The software can also be used to download a
new language file or to change the start-up “splash
screen”. An on-screen simulation of the instrument can
be setup and tested on a configurable load simulator.
dress required for the Modbus TCP communications
option - refer to the IP Address Configuration section.
Using The Software
The menus and button bar are used to select the main
parameter screen or one of the other modes or functions. Hover the mouse over the parameter description
or value to view a fuller description. Consult the comprehensive help (available from the Help Menu) for information about the general software functions.
A additional software tool is available to set the IP ad-
Menus
Button Bar
Functional Groups
Parameter Address (hex)
Mode Drop Down
Figure 53.
Description
Value Range
Main Parameter Screen
The main parameter screen is used to change all of
the configuration and other settings. This screen also
allows access to the Supervisor and Enhanced Opera-
View & Device Menus
Parameter Values
tion Mode configuration screens from the Mode dropdown list. The Button bar or Device and View menus
are used to access the other software functions.
Instrument Simulation
Parameter Configuration
Figure 54.
Profile Editor
Trend
Button Bar & View Menu
126
Instrument Configuration
Parameter configuration
When creating a new configuration with the software,
the basic instrument type and the options to be fitted
to it must be defined in the Device Selection screen.
You can select these from the drop down lists or by
typing the full model number in the Order number field.
The main parameter screen contains all of the instrument settings broken down into functional groups. The
parameters can be changed in the yellow Value column. Type in a new value or select from the list offered,
as appropriate. The possible value range is show to the
left. If an invalid value is entered, it will be highlighted
in red. Parameters are “greyed out” if the are currently
inaccessible due the hardware not being fitted or if they
are disabled by other settings.
Configuring Supervisor Mode
Users can access to a lock code protected sub-set of
the configuration parameters that have been defined
from the software. Up to 50 of the parameters can be
copied into this mode. To define these screens, first
select Supervisor Mode from the mode drop-down list.
Select the functional group containing the parameter
to be added. Highlight the parameter Name and click
the Add Entry button. The Move Entry Up and Down
buttons are used to change the order which the parameters will appear in Supervisor Mode. Unwanted entries can be highlighted and deleted with the Remove
Entry button.
Note: It is important that the options selected match
those fitted to your unit.
Alternatively the complete instrument type and existing
configuration can be uploaded to the PC from your instrument, via the configuration socket or serial communications module. A previously saved configuration file
can also be opened from the file open menu or button.
Configuring Enhanced Operator Mode
Users can access sub-set of the configuration parameters at the end of the normal Operation Mode screen
sequence, that have been defined from the software.
Up to 50 parameters can be copied in a similar manner to the Supervisor Mode selection by selecting Enhanced Operation Mode from the mode drop-down
list. Note: Any parameters copied into the Enhanced
Operation mode are not password protected.
Once the required changes have been made, the configuration can then be download to the instrument or
saved to disk with a .bct file extension. The configuration file contains the device information and configuration parameter settings, including any supervisor and
enhanced operation mode screens and changes to the
LED functions. Profiles, splash screens and language
files are not saved in the .bct file. They are uploaded/
saved separately.
A hard copy of the instrument configuration and terminal wiring can be printed from the File | Print menu.
127
Functional Groups
Mode Drop Down
Add Entry
Figure 55.
Parameter List
Remove Entry
Move Down
Supervisor/Enhanced Operation Mode Configuration
Profile Creation And Editing
ment connected to the PC via the configuration socket
or serial communications module. The new profile can
be download to the instrument or saved to disk with a
.pfl file extension.
Select the Profile Editor from the button bar or view
menu. An existing profile file can be opened from the
file open menu or button, or uploaded from an instru-
New / Open / Save / Print
Header Parameters
Move Up
Selected Parameters
Upload Profile
Download Profile
Header Values
Figure 56.
Profile Directory List
Profile Editor – Header
128
Mode Drop-Down
If the option to upload a profile is chosen, a list of profiles in the connected instrument is shown. The user
can select the required profile from the list.
When downloading a profile to the instrument via the
configuration socket or over serial communications, a
list of existing profiles and empty profile slots is displayed. The user can select where to place the profile
(a warning is shown if the profile will overwrite an existing profile).
A directory of existing profiles in the instrument can
also be requested. This allows one or all of the profiles
to be deleted.
The number of free segments stil available is also
shown.
A drop-down menu in the Profile Editor switches between the Profile Header and Segment Data. Refer to
the Profiler Setup Menu and Profiler Option sections
for full details of the header and segment data.
Header data includes a 16-character profile name, options for starting the profile after a delay or at a specific
day and time, the starting setpoint, the action to take
after a power failure or profile abort and the number of
times the profile will run.
The segments are shown in Segment Data mode. The
last segment is always an End, Join or Repeat Sequence
type, and cannot be deleted. The user can select and
change any segment’s type and values, and they can
insert additional segments before the selected one. A
dynamically scaled graphic shows the segments of the
profile, with the select segment is highlighted in red.
The five profile events are shown below the graph.
Insert Segment
Un-Zoom
Insert Segment
Segment List
Profile Directory
Un-Zoom
Selected Segment (Red)
Profile Directory
Segment Values
Scaling
129
Selected Segment
Active Event
Changing the Start-up Splash Screen
will not reproduce well. A preview of the results is
shown.
The graphic shown during the instrument start-up
sequence can be changed from the main parameter
screen. Select Download Splash Screen option from
the Device menu. Choose your new graphic file (most
common file types are supported). The chosen image
will convert to monochrome and be rescaled to 160
pixels wide by 80 pixels high. For best results, the image should be simple and have an aspect ratio of 2:1.
Complex graphics with multiple colors or grayscales
Click the Download button to store it to the instrument.
Changing the Alternate Display Language
The alternate language can be changed from the main
parameter screen. Select the Download Language File
option from the Device menu. Choose the correct file
(language files have a .bin extension) and click the
Open button to store it to the instrument.
Instrument Simulation
A fully functional and interactive instrument simulation is included with the software. This is linked to a simulated
process, allowing changes to a configuration to be tested before use.
Figure 57.
4080 Simulation
Configuring The Connection
A front mounted USB port is available on some models; this can also be used to configure the instrument or
transfer profile files, via a USB memory stick.
The software can communicate with the instrument
via the RJ11 configuration socket located on the underside of the case, or via the Modbus TCP or RS485
communications options if either is fitted. Refer to the
wiring section for connection details.
The configuration lead/socket is not isolated
from the process input or SSR Driver outputs.
It is not intended for use in live applications.
The configuration socket is intended for initial configuration of the instrument before installing in the application. An RS232 to TTL lead (available from your supplier) is required connect from the PCs RS232 serial
port to this socket.
130
A communications settings screen is shown whenever
the user attempts to connect to the instrument from
the software. The settings must be correct in order for
communications to work successfully. First correctly
select Configuration Socket or Bus as the Device connector, and select the PC Serial Com port that you
have connected to
For Modbus TCP, select Ethernet (bus coupler).
If connecting via the configuration port, the Start and
Stop bits must be 1 and Data bits 8. Parity must be
None and address 1. The data bit-rate should be 4800
if Slot A is fitted with an Auxiliary input, 9600 if the Ethernet option is installed or 19,200 for a Digital Input or
if Slot A is empty.
If the instrument has an RS485 module fitted, the Address, Parity and Bit rate values must match those of
the instrument (even if you are connecting via the configuration port). The Start and Stop bits must be 1 and
Data bits 8.
If connecting via the Modbus TCP module, enter the instrument’s IP address and set the Port address to 502
USB Memory Stick Folders & Files
be in any folder of your choosing. The USB option also
limits the file name to 8 characters plus the 3 digit . bct
or .pfl extension. Longer file names will be truncated.
If a USB memory stick is to be used to transfer files
between the instruments and/or the software, the files
must be stored in specific DEVICE, CONFIG and PROFILE folders on the USB stick. When saving files from
the software to the memory stick, ensure that you save
them to the correct folder. Local storage on you PC can
When saving a file, the data will be overwritten
If the file name already exists.
DEVICE – This
Root of the USB
CONFIG – Conf
PROFILE – Pro
DEVICE – This folder must be located in the
RECORDER – R
Root of the USB memory stick
These can be cr
CONFIG – Configuration files (*.bct)
PROFILE – Profile program files (*.pfl)
RECORDER – Recorder log folders/files.
These can be created or saved from the PC
software.
131
software.
Network Configuration For Modbus TCP
Options
If your network assigns IP addresses automatically,
pressing the “Search Network” button will list any of
the Graphical Controllers connected to it.
If the instrument has the Modbus TCP communications
option fitted, an IP address must be assigned to it in order for it to communicate with the Modbus TCP master
device over your Ethernet network. The instrument can
automatically receive an IP address if your network is
set up to assign addresses to Ethernet devices connected to it. Alternatively, a fixed IP address can be
assigned to it manually.
Their Network IP Address and MAC Addresses are also
shown. For most fixed networks, only instruments that
have the same numbers in the first 3 Octets of their IP
address can be seen by the PC. In this case, use the
method detailed in the “Fixing An IP Address” section
below.
Highlight the instrument that you wish to configure in
the list and press the “Configure Selected Device Button”.
The Graphical Controller Ethernet Configuration tool is
provided in order to discover or assign the IP Address
of the instrument and configure the settings.
The Current IP address on the network is shown in the
Edit IP Address tab, as is the current configured IP address. A configured address of 0.0.0.0 means the instrument does not have a fixed address, allowing it to
receive one from the network (via a DHCP, BootP or
AutoIP server).
Setting the IP Address
Install and run the Graphical Controller Ethernet Configuration software on your PC. Connect the instrument
to your network by plugging an Ethernet cable into the
RJ45 socket on the top of the case. If your PC is not
connected to a network, the instrument can be connected to its Ethernet port directly.
Set the value to 0.0.0.0 for automatic addressing, or
set a new fixed IP address and press Apply.
Note: If this number does not match your PC’s network
addresses, further communication with the instrument
will cease.
132
Instrument Details
The Details tab can be used to confirm communications with the instrument. When opened or refreshed,
this tab collects the instruments Serial Number, Date
of Manufacture and the Contact Details information,
confirming that the Modbus TCP communications is
functioning correctly.
Fixing An IP Address
Edit Modbus Settings
*If your instruments 12 digit MAC Address isn’t know, it
can be found on a label attached to the RJ45 connector of its Ethernet module.
If your instrument cannot be found using the “Search
Network” button, the IP address can be set from the
Set IP Address option on the software’s System menu.
Enter its MAC Address* and the new IP Address (use
0.0.0.0 for automatic addressing) then press okay.
The Edit Modbus Settings tab configures the connection between the Ethernet module and the instrument’s
microprocessor. These settings MUST match with the
settings in the instruments Communications Configuration menu. A faster baud rate can be used if large
amounts of data are to be sent between the instrument
and the master, but in most cases, it is recommended
that the default settings are used.
Defaults:
Baud Rate
9600
Data Bits
Eight
Stop Bits
One
ParityNone
133
17 Appendix 2 - Specifications
Universal Input
General Input Specifications
Input Sample Rate:
Ten samples per second.
Digital Input Filter time constant
0.0 (OFF), 0.5 to 100.0 seconds in 0.5 second increments.
Input Resolution:
Always four times better than display resolution. 16 bit ADC.
Supply Voltage Influence:
Negligible effect on readings within the specified supply voltage
tolerances.
Relative Humidity Influence:
Negligible effect on readings within the specified humidity tolerance.
Temperature Stability:
0.01% of span/°C change in ambient temperature.
Input Impedance:
V DC:
47KΩ
mA DC:
5Ω
Other ranges:
Greater than 10MΩ resistive
Isolation:
Isolated from all outputs (except SSR Drivers) at 240V AC
PV Offset:
Adjustable ±input span. +ve values are added to Process Variable,
-ve values are subtracted from Process Variable
PV Display:
Displays process variable up to 5% over and 5% under span.
Thermocouple
Thermocouple Ranges Available
Sensor Type
Range in °C
Range in °F
Sensor Type
B
L
100 to 1824°C
211 to 3315°F
C
N
0 to 2315°C
32 to 4199°F
D
PtRh20%; PtRh40%
0 to 2320°C
32 to 4208°F
E
R
-240 to 1000°C -400 to 1832°F
J (default)
S
-200 to 1200°C -328 to 2192°F
K
T
-240 to 1373°C -400 to 2503°F
Note: Defaults to °F for USA units. Defaults to °C for non-USA units.
Range in °C
Range in °F
0 to 762°C
0 to 1399°C
0 to 1850°C
0 to 1759°C
0 to 1762°C
-240 to 400°C
32 to °F
32 to 2551°F
32 to 3362°F
32 to 3198°F
32 to 3204°F
-400 to 752°F
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to restrict range.
An optional decimal place can be displayed up to 999.9°C/F
Thermocouple Performance
Calibration:
Complies with BS4937, NBS125 and IEC584.
Measurement Accuracy:
±0.1% of full range span ±1LSD.
NOTE: Reduced performance for B Thermocouple from 100 to 600°C.
NOTE: PtRh 20% vs PtRh 40% Thermocouple accuracy is 0.25% and has
reduced performance below 800°C.
Linearization Accuracy:
Linearization better than better ±0.2°C (±0.05 typical) for J, K, L, N and T
thermocouples; than better than ±0.5°C for other types.
Cold Junction Compensation:
If enabled, CJC error is better than ±1°C under operating conditions.
Sensor Resistance Influence:
Thermocouple 100Ω: <0.1% of span error.
Thermocouple 1000Ω: <0.5% of span error.
Sensor Break Protection:
Break detected within two seconds. Process Control outputs go to the
pre-set power value. High and Senor Break Alarms operate.
134
Resistance Temperature Detector (RTD) Input
RTD Types & Ranges
Sensor Type
Range in °C
Range in °F
Sensor Type
Range in °C
3-Wire
PT100
-199 to 800°C
-328 to 1472°F
NI120
-80 to 240°C
Note:
Range in °F
-112 to 464°F
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to restrict range.
An optional decimal place can be displayed up to 999.9°C/F
RTD Performance
Measurement Accuracy:
Complies with BS4937, NBS125 and IEC584.
Linearization Accuracy:
Better than ±0.2°C any point (±0.05°C typical).
PT100 Input complies with BS1904 and DIN43760 (0.00385Ω/Ω/°C).
Sensor Resistance Influence:
Pt100 50Ω/lead balanced.
Automatic Lead Compensation: <0.5% of span error.
RTD Sensor Current:
150μA (approximately).
Sensor Break Protection:
Break detected within two seconds. Process Control outputs go to the
pre-set power value. High and Senor Break Alarms operate.
DC Linear Input
DC Linear Types & Ranges
Input Type
Ranges
Input Type
mA DC
V DC
0 to 20mA
4 to 20mA
mV DC
0 to 50mV
10 to 50mV
Note: Defaults to °F for USA units. Defaults to °C for non-USA units.
Ranges
0 to 5V
2 to 10V
1 to 5V
0 to 10V
The Scale Range Upper Limit and Scale Range Lower Limit parameters, can be used to restrict range.
An optional decimal place can be displayed up to 999.9°C/F
DC Linear Performance
Display Scaling:
Scalable up to –9999 to 10000 for any DC Linear input type.
Minimum Span:
100 display units.
Decimal Point Display:
Decimal point selectable from 0 to 3 places, but limits to 5 display digits
(e.g. values > 99.9 have no more than 2 decimal places).
DC Input Multi-Point
Linearization:
Up to 15 scaling values can be defined anywhere between 0.1 and 100%
of input.
Measurement Accuracy:
±0.1% of span ±1LSD.
Maximum Overload:
1A on mA input terminals, 30V on voltage input terminals.
Sensor Break Protection:
Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Break detected within two seconds. Process Control outputs go to the
pre-set power value. Low and Senor Break Alarms operate.
135
Auxiliary Inputs
Auxiliary Input Types & Ranges
Input Type
mA DC
V DC
Ranges – Auxiliary Input A
0 to 20mA
0 to 5V
2 to 10V
Input Type
mA DC
V DC
4 to 20mA
1 to 5V
0 to 10V
mV DC
Pot
Ranges – Auxiliary Input B
0 to 20mA
0 to 5V
2 to 10V
0 to 100mV
2KΩ or higher
4 to 20mA
1 to 5V
0 to 10V
10 to 50mV
Auxiliary Input Performance
Input Sampling rate:
4 per second.
Input Resolution:
16 bit ADC.
Auxiliary Input Scaling:
Scalable as a Remote Setpoint (RSP) input between –9999 and 10000,
constrained by the Setpoint Limits.
Measurement Accuracy:
±0.25% of input span ±1 LSD.
Input resistance:
mV ranges :
>10MΩ.
Voltage ranges: 47KΩ.
Curent ranges: 5Ω.
Input protection:
Voltage input: will withstand up to 5x input voltage overload without
damage or degradation of performance in either polarity.
Current input: will withstand 5x input current overload in reverse direction
and up to 1A in the normal direction.
Isolation:
Reinforced safety isolation from outputs and inputs (except to Digital
Input B).
Sensor Break Detection:
Applicable for 4 to 20mA, 1 to 5V and 2 to 10V ranges only.
Control goes to the pre-set power value if Auxiliary Input is providing the
active setpoint source.
Digital Inputs
Digital Input Functions
Function
Logic High
Ranges – Auxiliary Input B
Profile Run/Hold
Hold Running Profile
Run or release selected profile
Hold Segment Release
No Action
Release from Hold Segment
Profile Abort
No Action
Abort Running Profile
Data Recorder
Stop Recording
Start Recording
Internal Setpoint Select
Select Local Setpoint 1
Select Alternate Setpoint
Auto/Manual Control
Automatic Control Mode
Manual Control Mode
Control Outputs
Enable PID Control Outputs
Disable PID Control Outputs
The above actions apply if a digital input has been defined to control the specified function(s)
Digital Input Performance
Type:
Voltage-free or TTL-compatible.
Voltage-Free Operation:
Connection to contacts of external switch or relay:
Open = Logic High. Minimum contact resistance = 5KΩ,
Closed = Logic Low. Maximum contact resistance = 50Ω.
TTL levels:
2.0 to 24VDC = Logic High.
–0.6 to 0.8VDC = Logic Low.
Digital Input Sensitivity:
Edge Sensitive. Requires High-Low or Low-High transition to change function.
Response Time:
Response within <0.25 second of signal state change.
Isolation:
Reinforced safety isolation from inputs and other outputs.
136
Output Specifications
Output Module Types
Option Slot 1 (Output 1) Options:
Single Relay, Single SSR Driver, Triac or DC linear.
Option Slot 2 (Output 2) Options:
Single Relay, Dual Relay, Single SSR Driver, Dual SSR Driver, Triac, DC
Linear or 24VDC Transmitter Power Supply.
Option Slot 3 (Output 3) Options:
Single Relay, Dual Relay, Single SSR Driver, Dual SSR Driver, Triac, DC
Linear or 24VDC Transmitter Power Supply.
Option Slot 4 (Output 4) Options:
Quad Relay.
Single Relay Output Performance
Contact Type:
Single pole double throw (SPDT).
Contact Rating:
2A resistive at 240V AC
Lifetime:
>500,000 operations at rated voltage/current.
Isolation:
Reinforced safety isolation from inputs and other outputs.
Dual Relay Output Performance
Contact Type:
2 x Single pole single throw (SPST) with shared common.
Contact Rating:
2A resistive at 240V AC.
Lifetime:
>200,000 operations at rated voltage/current.
Isolation:
Reinforced safety isolation from inputs and other outputs.
Quad Relay Output Performance
Contact Type:
4 x Single pole single throw (SPST).
Contact Rating:
2A resistive at 240V AC.
Lifetime:
>500,000 operations at rated voltage/current.
Isolation:
Reinforced safety isolation from inputs and other outputs.
Single Dual SSR Driver Output Performance
Drive Capability:
10VDC minimum at up to 20mA load.
Isolation:
Not isolated from the universal input, Ethernet communications or other
SSR driver outputs.
Dual SSR Driver Output Performance
Drive Capability:
10VDC minimum at up to 20mA load.
Isolation:
Not isolated from the universal input, Ethernet communications or other
SSR driver outputs.
Triac Output Performance
Operating Voltage:
20 to 280Vrms @47 to 63Hz.
Current Rating:
0.01 to 1A (full cycle rms on-state @ 25°C); derates linearly above 40°C
to 0.5A @ 80°C.
Non-repetitive Surge Current:
25A peak maximum, for <16.6ms.
OFF-State dv/dt:
500V/μs Minimum at Rated Voltage.
OFF-State leakage:
1mA rms Maximum at Rated Voltage.
ON-State Voltage Drop:
1.5V peak Maximum at Rated Current.
Repetitive Peak OFF-state Volt- 600V minimum.
age, Vdrm:
Isolation:
Reinforced safety isolation from inputs and other outputs.
137
DC Linear Output Types & Ranges
Input Type
mA DC
Ranges
0 to 20mA
Input Type
V DC
4 to 20mA
Ranges
0 to 5V
2 to 10V
1 to 5V
0 to 10V
DC Linear Output Performance
Resolution:
Eight bits in 250mS
(10 bits in 1 second typical, >10 bits in >1 second typical).
Update Rate:
Every control algorithm execution (10 times per second).
Load Impedance:
0 to 20mA & 4 to 20mA:
500Ω maximum.
0 to 5V, 0 to 10V & 2 to 10V:
500Ω minimum.
Short circuit protected.
Accuracy:
±0.25% (mA @ 250Ω, V @ 2kΩ).
Degrades linearly to ±0.5% for increasing burden (to specification limits).
Over/Under Drive:
For 4 to 20mA and 2 to 10V a 2% over/underdrive is applied (3.68 to
20.32mA and 1.84 to 10.16V). When used as control output
Isolation:
Reinforced safety isolation from inputs and other outputs.
0 to 10VDC Transmitter Power
Supply*
Can be used to provide an adjustable 0.0 to 10.0V (regulated), up to
20mA output to excite external circuits & transmitters.
24V Transmitter Power Supply Performance
Power Rating
19 to 28VDC (24V nominal) up to 20mA output, to for external circuits &
transmitters.
Isolation:
Reinforced safety isolation from inputs and other outputs.
*see Linear output (above) for adjustable 0 to 10V Transmitter Power Supply
Supported Communication Methods
Type
Function
PC Configuration Socket
Direct configuration using the PC Configuration Software
RS485
Configuration and general communications using Modbus RTU.
Ethernet
Configuration and general serial communications using the Modbus TCP
protocol.
USB
Upload/download of configuration/profile files from the PC Software or
other instruments and download for Data Recordings.
PC Configuration Socket
Type:
RS232 Serial Communications
Connection
PC Configurator Cable to RJ11 socket under case.
Isolation:
Not isolated from input or SSR Driver outputs. For bench configuration
only. CAUTION: Not for use in live applications.
138
RS485
Type:
RS485 Asynchronous Serial Communications Module.
Connection
Locates in Option Slot A.
Connection via rear terminals (refer to wiring diagram).
Protocol:
Modbus RTU Slave or Modbus RTU Setpoint Broadcast Master.
Slave Address Range:
1 to 255.
Bit rate:
4800, 9600, 19200, 38400, 57600 or 115200 bps.
Bits per character:
10 or 11 (depending on parity setting) plus 1 Stop Bit
Parity:
None, even or odd (selectable).
Isolation:
240V reinforced safety isolation from all inputs and outputs.
Ethernet
Type:
Ethernet Communications Module.
Connection
Locates in Option Slot A
Connection via RJ45 connector on top of case.
Protocol:
Modbus TCP Slave only.
Supported Speed:
10BaseT or 100BaseT.
IP Address Allocation:
Via DHCP or manual configuration via PC Tool.
Isolation:
240V reinforced safety isolation from the supply, inputs and outputs (except SSR Drivers).
USB Socket
Targeted Peripheral:
USB Memory Stick.
Connection
Locates in Option Slot C. Connection via front mounted connector.
Protocol:
USB 1.1 or 2.0 compatible. Mass Storage Class.
Isolation:
Reinforced safety isolation from all inputs and outputs
Display
Display Type:
160 x 80 pixel, monochrome graphic LCD with a dual color (red/green)
backlight.
Display Area:
66.54mm (W) x 37.42mm (H).
Display Characters:
0 to 9, a to z, A to Z, plus ( ) - and _
Trend View:
120 of 240 data points shown in a scrollable window. Data is not retained
when power turned off or if time base is changed.
Trend View Data:
Displays any active alarm plus PV input (solid) & Setpoint (dotted) at
sample time or Maximum & Minimum PV input value measured between
samples (candle-stick graph).
Trend View Y-axis Scaling
The instrument automatically scales this between 2 to 100% of Input
Span for maximum resolution of displayed data.
Trend View Sample Rate:
1; 2; 5; 10; 15; 30 seconds or 1; 2; 5; 10; 15; 30 minutes.
139
Control Loop
Tuning Types:
Pre-Tune, Auto Pre-Tune, Self-Tune and Manual Tuning
Proportional Bands:
Primary & Secondary (e.g. Heat & Cool) 0.5% to 999.9% of input span in
0.1% increments, or On/Off control.
Automatic Reset
Integral Time Constant, 1s to 99min 59s and OFF
Rate
Derivative Time Constant, 1s to 99 min 59s and OFF
Manual Reset
Bias added each control algorithm execution.
Adjustable in the range 0 to 100% of output power (single output) or
-100% to +100% of output power (dual output).
Deadband/Overlap:
–20% to +20% of Primary + Secondary Proportional Band.
ON/OFF Differential:
ON/OFF switching differential 0.1% to 10.0% of input span.
Auto/Manual Control:
Selectable with “bumpless” transfer when switching between Automatic
and Manual control.
Control Cycle Times:
Selectable from 0.5 to 512 seconds in 0.1s steps.
Setpoint Range:
Limited by Setpoint Upper Limit and Setpoint Lower Limit.
Setpoint Maximum:
Limited by Scale Range Upper Limit and Setpoint Minimum.
Setpoint Minimum:
Limited by Scale Range Lower Limit and Setpoint Maximum.
Setpoint Ramp:
Ramp rate selectable 1 to 9999 LSD’s per hour and infinite.
Data Recorder Options
Recording Memory:
1Mb non-volatile flash memory (data retained when power is off).
Recording Interval:
1; 2; 5; 10; 15; 30 seconds or 1; 2; 5; 10; 15; 30 minutes.
Recording Capacity:
Dependant on sample rate and number of values recorded.
Example: 2 values can be recorded for 7 days at 10s intervals.
More values or faster sample rates reduce the maximum duration.
RTC Battery Type:
VARTA CR 1616 3V Lithium. Clock runs for >1 year without power.
RTC accuracy:
Real Time Clock error <1second per day.
Alarms
Maximum Number of Alarms:
Five “soft” alarms, each selectable for any of the supported alarm types.
Physical outputs can be assigned for each alarm.
Alarm Types:
Process High, Process Low, Band, Deviation, Rate of Signal Change (per
minute), Sensor/input Break, Loop Alarm. Band and Deviation (high or
low) alarm values are relative to the current setpoint value.
Alarm Hysteresis:
Adjustable deadband from 1 LSD to full span (in display units) for Process, Band or Deviation Alarms.
Rate Of Change Alarm hysteresis is the shortest time (1 to 9999 secs) the
rate of change must be above the threshold for the alarm activate, or fall
below the threshold to deactivate.
Combinatorial Alarms:
Logical OR of alarms 1 & 2, 1 to 3, 1 to 4 or 1 to 5 or Logical AND of
alarms 1 to 5 with Profiler Events 1 to 5, to any suitable output.
140
Profiler Options
Profile Limits:
Number of profiles = 64 maximum.
Total number of segments (all programs) = 255 maximum.
Loop Back Segments:
1 to 9999 loops back to specified segment.
Profile Cycling:
1 to 9999 or Infinite repeats per profile.
Sequence Repeats:
1 to 9999 or Infinite repeats of joined profile sequences.
Segment Types:
Ramp Up/Down over time, Ramp Rate Up/Down, Step, Dwell, Hold, Join
A Profile, End or Repeat Sequence Then End.
Time-base:
All times are specified in hh:mm:ss (Hours, Minutes & Seconds).
Segment Time:
Maximum segment time 99:59:59 hh:mm:ss. Use loop-back for longer
segments (e.g. 24:00:00 x 100 loops = 100 days).
Ramp Rate:
0.001 to 9999.9 display units per hour.
Hold Segment Release:
Release With Key-press, At Time Of Day or via a Digital Input.
Start From Value:
1st segment starts from current setpoint or current PV input value.
Delayed Start:
After 0 to 99:59 (hh:mm) time delay, or at specified day(s) & time.
Profile End Action:
Selectable from: Keep Last Profile Setpoint, Use Controller Setpoint or
Control Outputs Off.
Profile Abort Action:
Selectable from: Keep Last Profile Setpoint, Use Controller Setpoint or
Control Outputs Off.
Power/signal Loss Recovery
Action:
Selectable from: Continue Profile, Restart Profile, Keep Last Profile Setpoint, Use Controller Setpoint or Control Outputs Off.
Auto-Hold:
Off or Hold if input >Band above and/or below SP for each segment.
Profile Control:
Run, Manual Hold/Release, Abort or jump to next segment.
Profile Timing Accuracy:
0.02% Basic Profile Timing Accuracy.
±<0.5 second per Loop, End or Join segment.
Segment Events:
Events turn on for the duration of the segment. For End Segments, the
event state persists until another profile starts or the unit is powered
down.
Conditions For Use
Reference Test Conditions
Ambient Temperature:
20°C ±2°C.
Relative Humidity:
60 to 70%.
Supply Voltage:
100 to 240V AC 50Hz ±1%.
Source Resistance:
<10Ω for thermocouple input.
RTD Lead Resistance:
<0.1Ω/lead balanced (Pt100).
141
Operating Conditions
Ambient Temperatures
0°C to 55°C (operating) and -20°C to 80°C (storage).
Relative Humidity:
20% to 95% non-condensing.
Altitude:
Up to 2000m above sea level.
Supply Voltage:
Either 100 to 240V ±10% AC 50/60Hz
or 20 to 48V AC 50/60Hz & 22 to 55V DC for low voltage versions.
Power Consumption:
Mains versions:
Low voltage versions:
Source Resistance:
1000Ω maximum (thermocouple).
RTD Input Lead Resistance:
50Ω per lead maximum, balanced
24VA.
15VA / 12W.
Standards
Conformance Norms:
CE, UL, ULC.
EMC standards:
Complies with CE EN61326.
Safety Standards:
Complies with CE EN61010-1 and UL3121.
Pollution Degree 2, Installation Category II.
Front Panel Sealing:
To IP66 (IP65 front USB connector). IP20 behind the panel.
(IP ratings are not tested for or approved by UL)
Dimensions
Front Bezel Size:
1/4 DIN (96 x 96mm).
Mounting:
Plug-in with panel mounting fixing strap.
Panel Cut-out Size:
92mm x 92mm. Max panel thickness 6.0mm
Depth Behind Panel:
117mm
Ventilation
20mm gap required above, below and behind.
Weight:
0.65kg maximum.
Terminals:
Screw type (combination head).
142
18 Appendix 3 - Product Coding
4080 Advanced Temperature and Process Controller
Model 40 Series Temperature and Process Controller
4080
1/14 DIN Advanced Temperature and Process Controller
Code Unit Type
C
Controller
U
R
Controller with USB Port
Controller/Recorder with USB Port & Real Time Clock
Code Profiler Option
0
Not Fitted
P
Profiler
Code Output 1
0
None
R
Relay (2 Amp resistive at 240 VAC)
S
SSR (0/10 VDC, 500 Ω Minimum load)
A
Analog (0-10V, 0-20mA, 0-5V, 2-10V, 4-20mA)
T
Triac (1 Amp AC)
Code
Output 2 & Output 3 (Choose the Appropriate Code for Each
Out 2 Out 3 Output Type
0
0
None
R
R
Relay (2 Amp resistive at 240 VAC)
S
S
SSR (0/10 VDC, 500 Ω Minimum load)
A
A
Analog (0-10V, 0-20mA, 0-5V, 2-10V, 4-20mA)
T
T
Triac (1 Amp AC)
M
M
Duak Relay Output - 2 Amp 240 VAC, Form A, norm. open, comm term
W
W
Dual SSR Output - Non Isolated, 0/10 VDC, 500 Ω Minimum Load
P
P
Isolated POwer Supply 24 VDC, 910 Ω Minimum
Code Output 4
0
None
1
4080 -
U
P
S
S
R-
0
4 Relay Output - 2 Amp 240 Vac, Form A, norm. open, NOT
comm term
Code Feature Option A
0
None
1
RS485 (ModBus/RTU) Digital Comms
2
Digital Input (Voltage Free or TTL Input)
3
Repote Setpoint - Manual Set (RSP) Analog Input A
4
Ethernet Port - Modbus TCP Slave
Code Feature Option B
0
None
1
Enhanced Remote Setpoint & Digital Input
Code Feature Option B
0
None
1
Reserved for Future Options
Code Power Supply
0
100 - 240V AC
1
24 - 48V AC/DC
1
143
0
0
0
Typical Model Number
Limited Warranty:
Please refer to the Chromalox limited warranty applicable to this product at
http://www.chromalox.com/customer-service/policies/termsofsale.aspx.
Chromalox, Inc.
1347 Heil Quaker Boulevard
Lavergne, TN 37086
(615) 793-3900
www.chromalox.com
© 2017 Chromalox, Inc.
144