advertisement
GSLG-A
Slide Gate Operator
Installation Guide
Operator models contained in this manual conform to UL325 standard for use in
Class I, II, III, and IV applications
USA & Canada (800) 421-1587 & (800) 392-0123
(760) 438-7000 - Toll Free FAX (800) 468-1340 www.linearcorp.com
Table of Contents
Pre-installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Always Check the Gate’s Action . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Gate Operator Classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Approved Obstruction Detection Devices . . . . . . . . . . . . . . . . . . .1
Safety Information and Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Regulatory Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Wiring Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
DC Control and Accessory Wiring . . . . . . . . . . . . . . . . . . . . . . . . . .2
Mounting Pad Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Gate Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mounting Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Gate Bracket and Chain Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Operator Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Vent Plug Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Controller Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Manual Disconnect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
AC Power Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Earth Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Open and Close Limit Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . .6
Limit Nuts Rough Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Limit Nuts Fine Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Torque Limiter Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Terminal Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Operator Accessory Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Basic Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Programming Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Entering Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Exiting Programming Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Programming Keystrokes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Left or Right Hand Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Dual Gate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Auto Close Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Run Alarm and Pre-start Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Maximum Open Direction Current Setting . . . . . . . . . . . . . . . . . .12
Maximum Close Direction Current Setting . . . . . . . . . . . . . . . . . .12
WARNING
ONLY QUALIFIED TECHNICIANS
SHOULD WORK ON
LINEAR SLIDE GATE
OPERATORS
WARNING
CONTROLS INTENDED FOR USER ACTIVATION MUST BE
LOCATED AT LEAST SIX FEET (6') AWAY FROM ANY MOVING
PART OF THE GATE AND WHERE THE USER IS PREVENTED
FROM REACHING OVER, UNDER, AROUND OR THROUGH THE
GATE TO OPERATE THE CONTROLS. OUTDOOR OR EASILY
ACCESSIBLE CONTROLS SHALL HAVE A SECURITY FEATURE
TO PREVENT UNAUTHORIZED USE.
Advanced Controller Programming . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Entering Advanced Programming Mode . . . . . . . . . . . . . . . . . . . .13
Maximum Run Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Single Button Input Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Stagger Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Stagger Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Auxiliary Relay Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Reverse Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Brake Delay Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Constant Pressure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Shadow Loop Open Prevention . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Reset Cycle Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Maintenance Alert Trigger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Mid-travel Stop Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Anti-tailgate Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Radio Enable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Antenna Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Radio Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Radio Transmitter Delete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
MGT Obstacle Transmitter Learn . . . . . . . . . . . . . . . . . . . . . . . . .16
MGT Obstacle Transmitter Delete . . . . . . . . . . . . . . . . . . . . . . . . .16
Motor Type Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Loop Layout Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Safety Edge Layout Illustration #1 . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Safety Edge Layout Illustration #2 . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Photoeye Installation Illustration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Picket Gate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Track Gate Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Dual Gate Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Optional In-Cabinet Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Open Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Close Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Stop Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Single Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Fire Department Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Open Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Open Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Close Obstruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reverse Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Open Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reverse Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Shadow/reset Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Operation Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Power-up Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Idle Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Last Gate Position/Condition . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Pre-start Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Reverse Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Run Timer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Entrapment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
COMM LINK Connection Failure . . . . . . . . . . . . . . . . . . . . . . . . . .25
MGT Obstacle Transmitter Trouble . . . . . . . . . . . . . . . . . . . . . . . .25
Maximum Run Time Exceeded . . . . . . . . . . . . . . . . . . . . . . . . . . .25
How to Order Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . .26
Contacting Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Operator fails to start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Motor operates, but gate does not move . . . . . . . . . . . . . . . . . . .26
Motor sounds like it is working harder than normal . . . . . . . . . . .26
Limit switch getting out of time . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Gate stopping part way open or closed
(but no visible obstruction) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Gate staying open with automatic system . . . . . . . . . . . . . . . . . .26
Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
6-Month Preventative Maintenance . . . . . . . . . . . . . . . . . . . . . . .27
Model GSLG-A Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Single Phase Controller Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Three Phase Controller Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Gate Operator Installation Checklist . . . . . . . . . . . . . . . . . . . . . . . . . .32
GSLG-A Slide Gate Operator Installation Guide
- ii -
P1222 X10
Pre-installation Information
Before You Begin...
Before unpacking, inspect the carton for exterior damage. If you find damage, advise the delivery carrier of a potential claim. Inspect your package carefully. You can check your accessory box parts with the enclosed packing slip for your convenience. Claims for shortages will be honored for only 30 days from the date of shipment. Before installing the operator, read this manual completely to ensure all requirements for proper installation are present. Verify that the voltage to be used matches the voltage of the operator.
If you have any questions about the requirements for proper installation of this gate operator contact technical support at 800-421-1587.
Always Check the Gate’s Action
It’s very important before installing the gate operator to make sure the gate’s slides free and level throughout the entire opening distance. If the gate does not seem to operate properly, it may affect the operator performance or greatly shorten the life of the unit. The gate should also be designed so that airflow is ample to prevent wind resistance and drag.
Gate Operator Classifications
All gate operators can be divided into one of four different classifications, depending on their design and usage. Install this gate operator only when the operator is appropriate for the construction and usage class as defined below:
• Class I Residential Vehicular Gate Operator
A vehicular gate operator intended for use in a home or for one to four single family dwellings with a common garage or parking area associated with these dwellings.
• Class II Commercial / General Access Vehicular Gate Operator
A vehicular gate operator intended for use in a commercial location or building such as a multi-family housing unit of five or more single family units, hotel, retail store or other building servicing the general public.
• Class III Industrial / Limited Access Vehicular Gate Operator
A vehicular gate operator intended for use in an industrial location or building such as a factory or loading dock area or other location not intended to service the general public.
• Class IV Restricted Access Vehicular Gate Operator
A vehicular gate operator intended for use in a guarded industrial location or building such as an airport security area or other restricted access locations not servicing the general public, in which unauthorized access is prevented via supervision by security personnel.
Approved Obstruction Detection Devices
The following contact or non-contact obstruction detection devices have been approved for use with this slide gate operator as part of a
UL325 compliant installation:
• Contact Edges
Miller Edge Models: MGO20, MGR20, MGS20
• Wireless Contact Adapter
GTO Models: SGEKAC, SGEKDC, SGET, SGER
• Obstruction Input Expansion
Miller Edge Model: MIM-62
• Photoeyes
Omron Model: E3K-R10K4-NR
Miller Edge Models: RG-K-R, PG-K-R50
EMX Models: IRB-MON, IRB-RET
GSLG-A Slide Gate Operator Installation Guide
- 1 -
Safety Information and Warnings
THE FOLLOWING FORMATS ARE USED FOR SAFETY NOTES
IN THESE INSTRUCTIONS.
CAUTION
This type of warning note is used to indicate the possibility of damage to the gate or gate operator.
WARNING
This type of warning note is used to indicate possible mechanical hazards that may cause serious injuries or death.
WARNING
This type of warning note is used to indicate possible electrical shock hazards that may cause serious injuries or death.
Regulatory Warnings
Read the following before beginning to install this slide gate operator:
IMPORTANT INSTALLATION SAFETY
INSTRUCTIONS
WARNING
TO REDUCE THE RISK OF SEVERE
INJURY OR DEATH TO PERSONS,
REVIEW THESE INSTALLATION SAFETY
STEPS BEFORE PROCEEDING
1. READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS.
2. Read the yellow “Safety Instructions” brochure enclosed with the packet of information. If any pages are missing or are unreadable, or you do not have the safety instructions, please call Linear at 1-800-333-1717 to request additional copies.
3. ALL ELECTRICAL CONNECTIONS TO THE POWER SUPPLY MUST BE MADE BY
A LICENSED ELECTRICIAN AND MUST OBSERVE ALL NATIONAL AND LOCAL
ELECTRICAL CODES.
4. A separate power-disconnect switch should be located near the operator so that primary power can be turned off when necessary.
5. Install the enclosed warning signs on both sides of the gate. A minimum of two (2) WARNING SIGNS shall be installed, one on each side of the gate where easily visible.
6. Never reach between, through or around the fence to operate the gate.
7. Never connect a button station within reach of the gate or on the side of the gate operator.
8. Do not adjust the operator controller’s current sensing feature too high. It should be adjusted high enough to keep the gate from falsely triggering the sensing, but no higher than necessary for the gate to operate. DO NOT
DEFEAT THE PURPOSE OF THIS FUNCTION!
9. You must install all required safety equipment.
10. UL325 Compliance requires the use of contact edges or photoelectric controls on all automatic or remotely-controlled gate operators.
11. The operator is intended for installation only on gates used for vehicles.
Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage.
Locate the gate such that persons will not come into contact with the vehicular gate during the entire path of travel of the vehicular gate.
P1222 X10
Wiring Specifications
Refer to the following steps for details on power and accessory wiring for the operator.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES.
USE COPPER WIRE ONLY!
AC Power Wiring
1. Find the listing on this page corresponding to the model, voltage and horsepower rating of your operator.
2. The distance shown in the table is measured in feet from the operator to the power source. DO NOT EXCEED THE MAXIMUM
DISTANCE.
These calculations have been based on standard 115 V and 230 V supplies with a 10% drop allowable. If your supply is under the standard rating, the runs listed may be longer than what your application will handle, and you should not run wire too near the maximum distance for the gauge of wire you are using.
3. When large-gauge wire is used, a separate junction box (not supplied) may be needed for the operator power connection.
4. Wire length calculations are based on the National Electrical Code,
Article 430 and have been carefully determined based on motor inrush, brake solenoids, and operator requirements.
5. Connect power in accordance with local codes. The green ground wire must be properly connected.
6. Wire insulation must be suitable to the application.
7. Electrical outlets are supplied in all 115 VAC models for convenience with occasional use or low power consumption devices only. If you choose to run dedicated equipment from these devices, it will decrease the distance for maximum length and the charts will no longer be accurate.
DC Control and Accessory Wiring
1. All control devices are now 24 VDC, which can be run up to
2000 feet with 14 AWG wire.
2. Control wiring must be run in a separate conduit from power wiring.
Running them together may cause interference and faulty signals in some accessories.
3. A three-wire shielded conductor cable is required to connect two operators together for dual operation. You must use Belden 8760
Twisted Pair Shielded Cable (or equivalent) only – P/N 2500-1982, per foot). See Page 25 for details of this connection. Note: The shield wire should be connected in both the operators.
GSLG-A Slide Gate Operator Installation Guide
- 2 -
MODEL GSLG-A SINGLE PHASE POWER WIRING
VOLTS & HP
MAXIMUM DISTANCE (FEET)
SINGLE DUAL
WIRE GAUGE
115 VOLTS
1/2-HP
115 VOLTS
3/4-HP
115 VOLTS
1-HP
208 VOLTS
1/2-HP
208 VOLTS
3/4-HP
208 VOLTS
1-HP
230 VOLTS
1/2-HP
230 VOLTS
3/4-HP
230 VOLTS
1-HP
3856
544
864
1374
2184
3476
894
1422
1200
1924
3060
4864
604
958
1526
2424
716
1140
160
254
406
646
1026
760
222
354
566
900
1430
178
282
450
2264
3600
5724
710
1128
1796
2852
4538
640
1016
1616
2570
4090
1928
272
432
686
1092
1738
447
711
600
962
1830
2432
302
478
763
1212
358
570
80
127
203
323
513
380
111
177
283
450
715
89
141
255
1132
1800
2862
355
564
898
1426
2269
320
508
808
1285
2045
6
4
12
10
4
12
10
8
12
10
8
6
10
8
6
4
8
6
4
12
6
4
12
10
4
12
10
8
12
10
8
6
10
8
6
4
8
6
4
12
12
10
8
6
4
MODEL GSLG-A THREE PHASE POWER WIRING
VOLTS & HP
MAXIMUM DISTANCE (FEET)
SINGLE DUAL
WIRE GAUGE
208 VOLTS
1/2-HP
208 VOLTS
3/4-HP
208 VOLTS
1-HP
230 VOLTS
1/2-HP
230 VOLTS
3/4-HP
230 VOLTS
1-HP
460 VOLTS
1/2-HP
460 VOLTS
3/4-HP
460 VOLTS
1-HP
1804
1344
2137
3400
1084
1723
2741
840
1142
1816
2890
920
1464
2330
714
1136
1336
2124
3841
6106
9712
3279
5212
8291
2689
4274
6798
902
672
1069
1700
542
862
1371
420
571
908
1445
460
732
1165
357
568
668
1062
1921
3053
4856
1640
2606
4146
1345
2437
3399
12
10
8
12
8
12
10
8
10
8
12
10
12
10
8
12
8
12
10
8
10
8
12
10
12
10
8
P1222 X10
Mounting Pad Installation
The gate operator mounts bolted to posts secured in concrete footings. The posts support the operator and prevent it from moving during operation. For optional pad mounting instructions, see Linear drawing #2700-360.
Gate Preparation
Before installing, make sure the gate rolls or slides freely, and that all exposed rollers are properly covered. The gate must be covered with fabric with openings no larger than 2-1/4” in size, to a minimum height of 72” above ground level. On picket-style gates, if pickets are spaced less than 2-1/4” apart, mesh is optional.
Mounting Specifications
Use two 3 - 3-1/2” OD galvanized posts and secure with concrete footings as shown, length to be determined by local codes, frost line depth and soil conditions.
Attach the operator with the U-bolts, side plates and hardware provided. Four 3/16” side plates go on the outside top and bottom, two 1/2” side plates go on the inside top, and two 3/16” side plates go on the inside bottom (see the illustration at right).
To assemble the drive chain and gate brackets, refer to Page 4. Make sure that the chain sag does not exceed recommended sizes and that the chain does not come into contact with the moving parts of the gate or ground.
WARNING
The gate must be properly installed and work freely in both directions prior to the installation of the gate operator. Do not adjust the force setting to compensate for an improperly installed, improperly functioning, or damaged gate.
WARNING
The operator is intended for installation only on gates used for vehicles. Pedestrians must be supplied with a separate access opening. The pedestrian access opening shall be designed to promote pedestrian usage. Locate the gate such that persons will not come into contact with the vehicular gate during the entire path of travel of the vehicular gate.
WARNING
The gate must be installed in a location so that enough clearance is supplied between the gate and adjacent structures when opening and closing to reduce the risk of entrapment.
Figure 1. Side
Plate Installation
72”
GSLG-A Slide Gate Operator Installation Guide
Figure 2. Post Mounting Specifications
- 3 -
P1222 X10
Gate Bracket and Chain Assembly
✓ NOTE: The item numbers shown in these illustrations are for reference only. For the actual part numbers, refer to the parts lists in the rear of this manual.
Assemble a gate bracket (1) to the front edge of the gate, using two
U-bolts (2), and mounting hardware (3). Before tightening down completely, be sure the bracket is parallel to the gate. Tighten the
U-bolt hardware the rest of the way, then screw the square head bolts (4) into the threaded holes in the gate plate until they bottom out against the gate. These will help keep the bracket from twisting on the pipe.
Slide a threaded chain pin (5) through the bracket as shown, with spring (6), flat washer (10), and two hex nuts (7). Attach one end of the drive chain (8) to the chain pin using master link (9) and begin unrolling the chain toward the operator.
Remove the rain cover from the back of the slide gate operator.
Carefully thread the drive chain under the first idler, over the drive sprocket, and then under the last idler. Make sure you feed most of the chain through the idlers and sprocket before attaching the chain to the back end of the gate.
Assemble the other gate bracket on the rear edge of the gate, using the same process as the front gate bracket. Once this is done, take the other chain pin, spring and jam nuts and assemble with the end of drive chain and the other master link.
At this point you should be able to adjust the chain tension by tightening the jam nuts on each end. Approximately 1/4” to
3/8” of slack per foot of drive chain is acceptable.
Make sure the chain does not drag on the ground, across the gate rollers or the idler frame of the operator.
Additional mounting holes have been provided in the gate bracket for installer convenience.
Operator Preparation
Vent Plug Installation
In order to keep gear oil from spilling out during shipping, gear reducers used in this gate operator has either a solid plug, or a sealed vent plug, installed at the factory.
For operators with a solid plug, replace the solid plug with the vent plug provided (see Figure 5).
With the vent plug installed, remove the vent plug’s breather pin to allow the gear box to vent (see Figure 5).
END OF GATE PIPE SHOWN
REFERENCE ONLY
2
4
3
Figure 2. Mounting Gate Bracket to Gate
7
10
6
9
1
5
8
Figure 3. Chain Pin and Chain Assembly
DRIVE SPROCKET
IDLER WHEEL IDLER WHEEL
GEAR
REDUCER
REMOVE THE
SOLID PLUG
WITH AN ALLEN
WRENCH
INSTALL THE
VENT PLUG
(IF NOT ALREADY
INSTALLED)
REMOVE THE
BREATHER PIN
INSTALL THE VENT PLUG
(IF NOT ALREADY INSTALLED)
Figure 5. Vent Plug Installation
GSLG-A Slide Gate Operator Installation Guide
- 4 -
CHAIN
PATH
NOTE: IDLER CONFIGURATION
MAY APPEAR DIFFERENT DEPENDING
ON THE SLIDE OPERATOR MODEL
CHAIN
PATH
DRIVE
SPROCKET
IDLER
WHEEL
Figure 4. Chain Path
P1222 X10
Operator Setup
Controller Access
The Controller is protected by a plastic dust cover (single phase models only). To remove the dust cover, loosen the cover’s wingscrew and lift the cover off (see Figure 5).
Manual Disconnect
The manual disconnect shifter lever and the locking lever is illustrated in Figure 8. They can be found at the center and to the left inside the operator cabinet. (The handle of each has been finished in easy to spot red firm-grip coating.)
To disconnect the unit for manual operation, grasp the handle of the spring-loaded shifter lever and pull it directly toward you until the spring-loaded locking lever snaps into place behind it. This action disengages the pinned shifter block from the drive mechanism and holds the block in the disengaged position.
To re-engage the operator, move the locking lever to the right, releasing the spring-loaded shifter lever to snap back into the engaged position.
WARNING
ALL AC ELECTRICAL CONNECTIONS TO THE POWER SOURCE AND
THE OPERATOR MUST BE MADE BY A LICENSED ELECTRICIAN
AND MUST OBSERVE ALL NATIONAL AND LOCAL ELECTRICAL
CODES
AC Power Connection
All Linear gate operators are supplied with a power disconnect switch to turn on and off the power available to the operator (see
Figure 6). Following wiring specifications on Page 2, incoming power should be brought into the operator and connected to the labeled pigtails from the disconnect box. A wiring connections print can also be found on the label inside the cover of the operator.
Proper thermal protection is supplied with the operator. The motor contains a thermal overload protector to guard from overheating the motor due to overload or high-frequency operation. This overload protector will reset automatically after the motor cools down.
Earth Ground
Install a ground rod and connect it to the operator’s frame in every gate operator installation. A good earth ground is necessary to allow the Controller’s built-in surge and lightning protection circuitry to work effectively. The physical bolting of the operator to the mounting pad is not sufficient for a good earth ground.
✓ NOTE: Do not splice the ground wire. Use a single piece of solid copper
12 AWG wire between the ground rod and the operator.
1. Install an 8-foot long copper ground rod next to the operator mounting pad within three feet of the operator.
2. Use a clamp to connect a solid copper 12 AWG ground wire to the ground rod.
3. Route the ground wire to the operator.
4. Connect the ground wire to the operator’s frame.
GSLG-A Slide Gate Operator Installation Guide
- 5 -
LOOSEN KNOB
TO REMOVE
CONTROLLER
COVER
Figure 5. Controller Access
MANUAL DISCONNECT
SHIFTER LEVER
PULL TO DISENGAGE
LOCKING LEVER
PUSH TO RIGHT TO
RE-ENGAGE OPERATOR
TO MANUALLY MOVE THE GATE,
PULL SHIFTER LEVER TO
DISENGAGE THE DRIVE TRAIN
GATE LIMIT SETTINGS WILL
NOT BE AFFECTED WHEN
GATE IS MANUALLY MOVED
PULL
Figure 6. Manual Disconnect Lever
BLACK
110 VOLT
OPERATOR
POWER
DISCONNECT
BOX
WHITE
GREEN
PUSH
HOT
NEUTRAL
GROUND
BLACK
220 VOLT
OPERATOR
POWER
DISCONNECT
BOX
WHITE
GREEN
HOT
HOT
GROUND
Figure 7. Power Disconnect Box Wiring
P1222 X10
Operator Setup (Cont.)
RIGHT-HAND INSTALLATION
CLOSE LIMIT OPEN LIMIT
LEFT-HAND INSTALLATION
OPEN LIMIT CLOSE LIMIT
Open and Close Limit Adjustment
The limit nuts are not preset at the factory and must be adjusted for the gate in each installation. The limit switches are activated by two threaded nylon rotary limit nuts which are attached to a threaded limit shaft driven by a chain and sprockets from the main drive shaft. REMOVE
THE CARDBOARD FILLER BEFORE ADJUSTING THE LIMIT NUTS.
The Controller is factory setup for right hand installations. The OPEN limit switch is the one closer to the front of the operator. In left hand installations, the CLOSE limit switch is the one closer to the front of the operator (see Figure 8).
CAUTION
If the operator is installed in a left-hand installation. Set the
Controller to left-hand operation BEFORE running the operator for the fine setting of the limit nuts. Failure to do so will result in over-shooting the limit switches, and can cause damage to the operator and/or gate. Refer to programming on Page 11.
LIMIT
SHAFT
LIMIT
SWITCHES
LIMIT
NUTS
FRONT OF
OPERATOR
Figure 8. Limit Box Assembly
Limit Nuts Rough Adjustment
Before running the operator, set the limit nuts as follows:
1. With the gate connected to the gate operator in a mid-travel position, the power disconnect switch turned OFF , disconnect the operator by using the manual disconnect lever, once the operator has been disconnected, manually move the gate by hand to within a foot of its fully open position (the foot of distance is necessary to allow for coasting of the operator after the limit switch is tripped).
2. Once the gate is in this position, adjust the OPEN limit nut until it activates the limit switch for open. Press down the detent plate and rotate the nut along the threaded shaft (see Figure 9).
3. After setting the open limit, move the gate to one foot from fully closed and repeat the process for the CLOSE limit nut.
PRESS DETENT
PLATE DOWN
Limit Nuts Fine Adjustment
After finishing the rough limit nut adjustments, reposition the gate to approximately the center of travel.
1. Re-engage the operator using the disconnect handle.
2. Turn the power disconnect switch ON .
3. Stand clear of any moving parts and press the OPEN button.
4. After the gate opens, press the CLOSE button.
5. Observe the gate in both directions as it runs through each complete cycle. Adjust the open or close limit nuts again if necessary. Fine levels of adjustment can be made by adjusting a few teeth on the nut at a time. If the gate stops during travel, you may need to adjust the Open or Close Current Setting or the Maximum Run Timer (see
Pages 12-13).
Torque Limiter Adjustments
Before adjusting the torque limiter, make sure the gate is in good working condition. One person should be able to move the gate by hand. Be certain the gate moves freely and without binding throughout its travel. Torque limiters are set light at the factory and must be adjusted during installation. Adjust the torque limiter tight enough to keep it from slipping during normal operation. See Figure 10.
ROTATE
LIMIT NUT
MORE
Figure 9. Setting the Limits
LOOSEN SET SCREW ON
THE ADJUSTMENT NUT
ADJUSTMENT NUT
To adjust the torque limiter in model GSLG-A:
1. Loosen the setscrew in the adjustment nut.
2. To increase the output , turn the adjustment nut clockwise one flat, or 1/6 turn, at a time until desired output is obtained.
To reduce the output , turn the adjustment nut counterclockwise one flat, or 1/6 turn, at a time until desired output is obtained.
3. Retighten the setscrew in the adjustment nut when finished.
GSLG-A Slide Gate Operator Installation Guide
- 6 -
TIGHTEN SET SCREW
DURING TESTING
AND WHEN FINISHED !!!
LESS
TO INCREASE TORQUE
TURN ADJUSTMENT NUT
CLOCKWISE ONE FLAT
THEN RE-TEST
TO DECREASE TORQUE
TURN ADJUSTMENT NUT
COUNTERCLOCKWISE
ONE FLAT THEN RE-TEST
Figure 10. Torque Limiter Adjustment
P1222 X10
Controller Features
WHIP
ANTENNA
ANTENNA
CONNECTOR
POWER
INDICATORS
OPERATION
BUTTONS
OPERATION AND
PROGRAMMING
INDICATORS
DISPLAY
PROGRAMMING
BUTTONS
INPUT
POWER
TERMINALS
ACCESSORY
POWER
TERMINALS
RESET
BUTTON
TERMINALS
PRIMARY/
SECONDARY
COMM LINK
TERMINALS
SINGLE
INPUT
TERMINALS
FIRE DEPT
INPUT
TERMINALS
OPEN INPUT
TERMINALS
3-BUTTON
STATION
TERMINALS
SHADOW/RESET
OPEN AND CLOSE
OBSTRUCTION
INPUT TERMINALS
REVERSE
INPUT
TERMINALS
OPEN LOOP
INPUT TERMINALS
REVERSE LOOP
INPUT TERMINALS
LIMIT SWITCH
INPUT TERMINALS
SHADOW/RESET LOOP
INPUT TERMINALS
AUXILIARY
RELAY
TERMINALS
ALARM
OUTPUT
TERMINALS
AC MOTOR
OUTPUT
TERMINALS
SOLAR
PANEL
TERMINALS
MOTOR
BOARD
COVER
BATTERY
TERMINALS
PLUG-IN
LOOP
DETECTOR
CONNECTORS
GSLG-A Slide Gate Operator Installation Guide
Figure 11. Controller Features
- 7 -
P1222 X10
Indicator Descriptions
INDICATOR DEFINITION
OPERATION PROGRAMMING
24 VOLT INPUT POWER
24 VOLT DC ACCY POWER
OPEN
CLOSE
STOP
PROGRAM
REVERSE
LOCKOUT
RADIO
OPEN CURRENT
OPEN OBSTR
OPEN RELAY
OPEN LIMIT
CLOSE CURRENT
CLOSE OBSTR
CLOSE RELAY
CLOSE LIMIT
SINGLE
MAX RUN
COMM LINK
MAINT ALERT
DELAY SET
ALARM SET
LEARN
SET
MGT 2 SET
LH/RH SET
BRAKE DELAY
SET
MGT 1 SET
AUTO CLOSE SET
AC DC SET
SET
SET
SET
SET
INDICATION WHEN LIT
DURING NORMAL OPERATION
LOW VOLTAGE AC POWER IS PRESENT
LOW VOLTAGE DC POWER IS PRESENT
OPEN SIGNAL PRESENT FROM THE INTERNAL
RECEIVER OR AN EXTERNAL DEVICE CONNECTED
TO THE OPEN INPUT TERMINAL
CLOSE SIGNAL IS PRESENT FROM A DEVICE
CONNECTED TO THE CLOSE INPUT TERMINAL
STOP INPUT TERMINAL IS OPEN AND
NOT CONNECTED TO COMMON
SIGNAL FROM REVERSING DEVICE IS PRESENT
CONTROLS AND OPERATOR ARE LOCKED OUT
BECAUSE OF EXISTING TROUBLE CONDITION
BUILT-IN RECEIVER IS DETECTING A RADIO
SIGNAL FROM A REMOTE CONTROL
MOTOR CURRENT HAS EXCEEDED THE OPEN
CURRENT SETTING WHILE OPENING
OPEN OBSTRUCTION TERMINAL CONNECTED
TO COMMON BY BEAM OR SAFETY EDGE, OR
SIGNAL FROM MGT OBSTACLE TRANSMITTER
OPEN RELAY IS ACTIVATED
OPEN LIMIT SWITCH IS ACTIVATED
MOTOR CURRENT HAS EXCEEDED THE CLOSE
CURRENT SETTING WHILE CLOSING
CLOSE OBSTRUCTION TERMINAL CONNECTED
TO COMMON BY BEAM OR SAFETY EDGE, OR
SIGNAL FROM MGT OBSTACLE TRANSMITTER
CLOSE RELAY IS ACTIVATED
CLOSE LIMIT SWITCH IS ACTIVATED
SINGLE TERMINAL CONNECTED TO COMMON
BY AN EXTERNAL PUSHBUTTON OR RADIO
MAXIMUM RUN TIMER HAS BEEN EXCEEDED
DUAL OPERATOR CONNECTION DETECTED,
BLINKS IF CONNECTION HAS FAILED
MAINTENANCE IS REQUIRED ON OPERATOR
APEX FUNCTION DISPLAY INDICATIONS
INDICATION WHEN LIT
DURING PROGRAMMING
CONTROLLER IS IN PROGRAMMING MODE
SET REVERSE DELAY TIME
SET RUN ALARM AND PRE-START ALARM
TRANSMITTERS CAN BE ENTERED INTO
MEMORY (UP TO 40 TRANSMITTERS)
SET MAXIMUM OPEN CURRENT
SET MGT #2 FUNCTION
SET LEFT-HAND RIGHT-HAND OPERATION
SET MAXIMUM CLOSE CURRENT
SET MGT #1 FUNCTION
SET AUTO-CLOSE TIME
SET MOTOR TYPE
SET SINGLE BUTTON INPUT FUNCTION
SET MAXIMUM RUN TIME
SET MAINTENANCE ALERT CYCLE COUNT
"RL"
LEFT OR RIGHT
HAND OPERATION
"PM"
SINGLE OR
DUAL GATE
"AC"
AUTO CLOSE
TIMER
"RP"
RUN ALARM
PRE-START ALARM
"OC"
MAXIMUM OPEN
CURRENT
"CC"
MAXIMUM CLOSE
CURRENT
"AD"
ADVANCED
PROGRAMMING
"RT"
MAXIMUM
RUN TIMER
"SB"
SINGLE BUTTON
INPUT SETUP
"SM"
STAGGER
MODE
"ST"
STAGGER
TIME
"AR"
AUXILIARY
RELAY MODE
"RD"
REVERSE
DELAY TIME
"BD"
BRAKE
DELAY TIME
"CP"
CONSTANT
PRESSURE MODE
"SP"
SHADOW LOOP
OPEN INHIBIT
"CT"
RESET CYCLE
COUNT
"MA"
MAINTENANCE ALERT
TRIGGER
"MT"
MID-TRAVEL
STOP POSITION
"AT"
ANTI-TAILGATE
ENABLE
"RA"
RADIO
ENABLE
"TL"
LEARN
TRANSMITTERS
"TD"
DELETE
TRANSMITTERS
"ML"
LEARN MGT
TRANSMITTERS
"MD"
ERASE MGT
TRANSMITTERS
"MO"
MOTOR TYPE
SELECTION
"CL"
RESET TO
FACTORY DEFAULTS
GSLG-A Slide Gate Operator Installation Guide
- 8 -
P1222 X10
Terminal Descriptions
TERMINAL
AC N
AC
DC -
DC +
C
B
RESET
COMMON
A
COMMON
SINGLE
COMMON
FIRE DEPT
COMMON
OPEN
OPEN
CLOSE
COMMON
STOP
GROUP
24 VOLT INPUT
ACCESSORY POWER
RESET BUTTON
COMM LINK
SINGLE BUTTON INPUT
FIRE BOX INPUT
OPEN INPUT
3-BUTTON STATION INPUT
FUNCTION
FACTORY CONNECTED TO 24 VAC FROM TRANSFORMER OR 24 VDC FROM CONTINUOUS DUTY DC SUPPLY.
PROVIDES 24 VOLT DC POWER FOR ACCESSORIES. (.5A MAX)
FACTORY CONNECTED TO THE CONTROLLER’S RESET BUTTON.
FOR 3-WIRE NETWORK CONNECTION TO SECOND OPERATOR IN DUAL GATE INSTALLATIONS.
CONNECT TO NORMALLY OPEN SWITCH FOR SINGLE BUTTON OPERATION. ALTERNATES
BETWEEN OPEN-CLOSE OR OPEN-STOP-CLOSE DEPENDING ON PROGRAMMING.
CONNECT TO NORMALLY OPEN SWITCH IN FIRE BOX FOR FIRE DEPARTMENT ACCESS.
CONNECT TO NORMALLY OPEN DEVICES (KEYPAD, CARD READER, KEYSWITCH, TELEPHONE
ENTRY SYSTEM) TO OPEN THE GATE. A CONSTANT OPEN INPUT WILL OVERRIDE THE
MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.
CONNECT TO 3-BUTTON STATION FOR OPEN-CLOSE-STOP CONTROL. A CONSTANT OPEN INPUT
WILL OVERRIDE THE MID-TRAVEL STOP AND HALT THE AUTO CLOSE TIMER UNTIL RELEASED.
COM
O-OBS
OPEN
OBSTRUCTION
INPUT
CONNECT TO APPROVED OBSTRUCTION DETECTION DEVICES (GATE EDGE, PHOTO BEAM)
TO DETECT AN OBSTRUCTION DURING OPENING. WHILE GATE IS MOVING, ANY OPEN
OBSTRUCTION SIGNAL WILL CAUSE THE GATE TO STOP, REVERSE A SHORT DISTANCE, AND
THEN STOP AGAIN. AT THIS TIME THE AUTO CLOSE TIMER IS DISABLED, AND A RENEWED
INPUT WILL BE REQUIRED TO START THE GATE AGAIN. SHOULD THE GATE BE RESTARTED
AND THE OBSTACLE SIGNAL OCCUR AGAIN PRIOR TO REACHING O-OBS A LIMIT, THE
GATE WILL STOP AGAIN, LOCKOUT, AND SOUND THE CONTINUOUS TONE ALARM.
C-OBS
COM
-
+
N.O.
COM
N.C.
+
-
COM
REV
OPEN LOOP
OPEN LOOP
-
+
REVERSE LOOP
REVERSE LOOP
SHADOW/RESET LOOP
SHADOW/RESET LOOP
CLOSE
OBSTRUCTION
INPUT
REVERSE
OPEN LOOP
REVERSE LOOP
SHADOW/RESET LOOP
ALARM
AUX RELAY
24 VOLT SOLAR PANEL
24 VOLT BATTERY
CONNECT TO APPROVED OBSTRUCTION DETECTION DEVICES (GATE EDGE, PHOTO BEAM) TO
DETECT AN OBSTRUCTION DURING CLOSING. WHILE GATE IS MOVING, ANY CLOSE OBSTRUCTION
SIGNAL WILL CAUSE THE GATE TO STOP, THEN REVERSE AND TRAVEL TO THE FULL OPEN POSITION.
SHOULD A OPEN OBSTRUCTION INPUT OR AN OPEN DIRECTION INHERENT ENTRAPMENT CONDITION
OCCUR PRIOR TO THE GATE REACHING THE OPEN LIMIT, THE OPERATOR WILL LOCKOUT AND
SOUND THE CONTINUOUS TONE ALARM. IF THE AUTO CLOSE TIMER IS SET, WHEN THE CLOSE
OBSTRUCTION INPUT IS CLEARED, THE GATE WILL CLOSE WHEN THE AUTO CLOSE TIMER EXPIRES.
CONNECT TO NORMALLY OPEN DEVICES TO CAUSE A REVERSAL WHEN THE GATE IS
TRAVELING CLOSED. THE GATE WILL REVERSE TO THE FULL OPEN POSITION.
CONNECT TO OPEN LOOP/FREE EXIT LOOP. THE GATE WILL OPEN WHEN THE LOOP IS TRIGGERED,
AND REMAIN OPEN AS LONG AS THE LOOP IS TRIGGERED. REQUIRES LOOP DETECTOR.
CONNECT TO REVERSE LOOP. TRIGGERING THE LOOP WILL CAUSE A REVERSAL WHEN THE GATE IS TRAVELING
CLOSED. THE GATE WILL REVERSE TO THE FULL OPEN POSITION. REQUIRES LOOP DETECTOR.
CONNECT TO SHADOW/RESET LOOP TO KEEP THE GATE IN ITS FULLY OPEN POSITION AS LONG AS THE SIGNAL
IS PRESENT. USED TO KEEP GATE OPEN WHILE VEHICLE IS PASSING THROUGH. REQUIRES LOOP DETECTOR.
FACTORY CONNECTED TO THE ALARM BEEPER.
FOR CONNECTION TO AUXILIARY DEVICES (MAGNETIC LOCK, SOLENOID LOCK, STROBE
LIGHT) FOR ACTIVATION (OR DEACTIVATION) DURING GATE OPERATION.
NOT USED WITH THIS MODEL OPERATOR
NOT USED WITH THIS MODEL OPERATOR
GSLG-A Slide Gate Operator Installation Guide
- 9 -
P1222 X10
Operator Accessory Connections
3-BUTTON STATION TELEPHONE ENTRY PHOTOEYE FOR REVERSE
KEYPAD
PHOTOEYE FOR CLOSE OBSTRUCTION
KEYSWITCH
FIRE ACCESS SWITCH SOLENOID LOCK
EXTERNAL POWER
PHOTOEYE FOR OPEN OBSTRUCTION
SINGLE-CHANNEL RADIO RECEIVER
MAGLOCK
GATE EDGE SENSOR FOR REVERSE
TWO-CHANNEL RADIO RECEIVER
CHANNEL #1
OPEN/CLOSE
WARNING STROBE OR AUDIBLE SOUNDER
WIRELESS GATE EDGE SENSOR
MGT
TRANSMITTER
Figure 12. Operator Accessory Connections
GSLG-A Slide Gate Operator Installation Guide
- 10 -
P1222 X10
Basic Controller Programming
Programming Overview
The Controller can be programmed with various options for the operator.
The programming fields are defined as “functions” that have “options”.
To make setup easier for the installer, the Controller’s programming is divided into two groups: basic and advanced. The basic programming group contains the functions commonly used in most slide gate installations. The advanced programming group contains functions less commonly used (i.e. dual gate stagger delay, maximum run timer, etc.).
Entering Programming Mode
Enter programming mode by pressing the UP and DOWN buttons together for one second. While in programming mode the PROGRAM indicator will light.
Exiting Programming Mode
Exit programming mode at any time by pressing the UP and DOWN buttons together. The Controller will automatically exit programming mode after three minutes of inactivity.
Programming Keystrokes
(Typical Programming Method)
While in programming mode, press the UP or DOWN buttons to scroll through the programming functions. When the desired function is displayed press the ENTER button to display the currently set option for the function. When an option is displayed, the decimal points are lit.
To change the option, press and hold the ENTER button for 1 second.
To indicate that an option is ready to be changed, the display will flash.
While the display is flashing, press the UP or DOWN button to display the other options available for that function.
When the desired option is displayed, press the ENTER button to store it into memory. To select another function, press ENTER , UP , or DOWN .
Left or Right Hand Operation
The factory default is for right hand operation (operator on right side of the driveway when viewed from the inside of the gate). For left hand installations, program the Controller for left hand operation.
Dual Gate Enable
The factory default is for single gate operation. For dual gate operation, wire the two gate controllers together through the COMM LINK terminals
(see Page 25) and enable dual gate operation with this programming step.
✓ NOTE: The Mid-travel Stop feature is disabled when dual gate operation is enabled for paired units.
Auto Close Timer
The factory default turns off the Auto Close Timer. The timer can be set from 1 to 59 seconds and from 1 to 9 minutes. When the Auto Close
Timer is set, after opening, the gate will wait for the length of the Auto
Close Timer then close automatically.
GSLG-A Slide Gate Operator Installation Guide
DOWN AND UP
PRESS DOWN AND UP
BUTTONS TOGETHER
FOR ONE SECOND
ENTERING
PROGRAMMING
UP
OR
DOWN
SELECT
FUNCTION
ENTER
CURRENTLY
SET OPTION
ENTER
OPTION READY
TO CHANGE
UP
OR
DOWN
CHOOSE
OPTION
ENTER
OPTION
STORED
PRESS UP OR DOWN
TO SCROLL DISPLAY
THROUGH FUNCTIONS
PROGRAMMING
KEYSTROKES
PRESS ENTER FOR
ONE SECOND TO
SELECT OPTION
(THE DISPLAY
WILL FLASH)
PRESS UP
OR DOWN
TO CHANGE
OPTION
PRESS ENTER TO
DISPLAY CURRENTLY
SET OPTION
PRESS ENTER
TO STORE
OPTION
PRESS UP, DOWN
OR ENTER SELECT
NEXT FUNCTION
ENTER
OR
UP
OR
DOWN
SELECT
FUNCTION
FUNCTION
"RL"
LEFT HAND
RIGHT HAND
FUNCTION
"PM"
SINGLE GATE
DUAL GATE
FUNCTION
"AC"
- 11 -
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
AUTO CLOSE
TIMER
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
PROGRAM
INDICATOR
PROGRAM INDICATOR
WILL LIGHT WHEN SYSTEM
IS IN PROGRAM MODE
OPTIONS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
RIGHT HAND INSTALLATION
(OPERATOR ON RIGHT OF GATE
WHEN VIEWED FROM INSIDE)
LEFT HAND INSTALLATION
(OPERATOR ON LEFT OF GATE
WHEN VIEWED FROM INSIDE)
SINGLE GATE INSTALLATION
DUAL GATE INSTALLATION
AUTO CLOSE TIMER DISABLED
SET TIMER VALUE
1 TO 59 SECONDS
SET TIMER VALUE
1 TO 9 MINUTES
P1222 X10
Basic Controller Programming (Cont.)
Run Alarm and Pre-start Alarm
The factory default is Run Alarm on and a 3-second Pre-start Alarm.
The operator’s beeper will sound 3 seconds before the operator starts.
The options are:
• Run Alarm Off and Pre-start Alarm Off
• Run Alarm On and Pre-start Alarm Off
• Run Alarm On and Pre-start Alarm On for 1-9 Seconds
Maximum Open Direction Current Setting
To detect obstacles or mechanical problems with the gate, the operator monitors its motor current. If the open current load increases by more than the programmed maximum load range number, the operator will stop, reverse a short distance, then stop again. The Auto Close Timer will be disabled, and another open request will be required to start the operator again. If after restart, the overload or an open obstacle happens again before the open limit is reached, the operator will lockout and sound the alarm.
The maximum load range number may be adjusted by pressing and holding the “enter” button until the previously set number flashes.
Using the + and - buttons, set the programmed range number so that a minimal force (50-75 lbs.) will activate a reversal should an obstruction occur, but high enough to keep the gate moving under normal conditions without interruption.
Maximum Close Direction Current Setting
To detect obstacles or mechanical problems with the gate, the operator monitors its motor current. If the close current load increases by more than the programmed maximum load range number, the operator will stop, reverse, and travel to the full open position. Should a open obstruction input or an open direction inherent entrapment condition occur prior to the gate reaching the open limit, the operator will lockout and sound the continuous tone alarm. Another close request will be required to start the operator again. If after restart, the overload or a close obstacle happens again before the close limit is reached, the operator will lockout and sound the alarm. If the auto close timer is set, when the close obstruction input is cleared, the gate will close when the auto close timer expires.
The maximum load range number may be adjusted by pressing and holding the “enter” button until the previously set number flashes.
Using the + and - buttons, set the programmed range number so that a minimal force (50-75 lbs.) will activate a reversal should an obstruction occur, but high enough to keep the gate moving under normal conditions without interruption.
FUNCTION
"RP"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
RUN ALARM
PRE-START ALARM
FUNCTION
"OC"
MAX OPEN
CURRENT
FUNCTION
"CC"
MAX CLOSE
CURRENT
OPTIONS
RUN ALARM OFF
PRE-START ALARM OFF
RUN ALARM ON
PRE-START ALARM OFF
RUN ALARM ON
PRE-START ALARM ON FOR 1 - 9 SECONDS
OPTIONS
PRESS AND HOLD THE ENTER BUTTON
MAXIMUM LOAD RANGE NUMBER WILL BE
DISPLAYED. ADJUST TO THE PROPER VALUE
ENTER PRESS ENTER TO STORE THE VALUE
OPTIONS
PRESS AND HOLD THE ENTER BUTTON
MAXIMUM LOAD RANGE NUMBER WILL BE
DISPLAYED. ADJUST TO THE PROPER VALUE
ENTER PRESS ENTER TO STORE THE VALUE
GSLG-A Slide Gate Operator Installation Guide
- 12 -
P1222 X10
Advanced Controller Programming
Entering Advanced Programming Mode
To access and program the Advanced Programming functions, for each programming session, Advanced Programming must be enabled.
After exiting programming, the Advanced Programming functions will be available on the programming display during the next programming session unless the operator has run 50 or more cycles. After that, Advanced Programming must be enabled again.
Maximum Run Time
The factory default for the Maximum Run Time (MRT) is 99 seconds.
When the operator starts, a timer will begin counting. If a open or close limit is not reached or an obstacle or reversing input is not received before the timer expires, the operator will stop, the unit locks out and the alarm sounds. The timer can be set for 10 to 99 seconds, but should be left at 99 in most applications. Setting it too close to the actual run time may cause the time to expire with changing ambient temperature, gate conditions, etc…
If AC is present and an open or close limit is not reached or an obstacle or reversing input is not received before this timer exceeds MRT, the operator will stop, the unit locks out and the alarm sounds.
Single Button Input Setup
This function is used for selecting the operation for single button controls and radio receivers.
The factory default sets the SINGLE input terminal so successive inputs will cycle the operator in OPEN-STOP-CLOSE-STOP order.
Alternately, the SINGLE input can be set to cause the gate to OPEN unless the gate is fully open. If the gate is fully open, the input will cause the gate to CLOSE.
Stagger Mode
(Rarely used in slide gate installations)
This function is used in dual gate installations only.
The factory default sets the Stagger Mode to OFF. In dual gate installations the two operators communicate through the 3-wire COMM LINK interface.
When using the Stagger Mode, set one operator for delayed opening and the other operator for delayed closing. The Stagger Delay Time programming function (see below) sets the length of the delay.
✓ NOTE: This function will only be displayed if dual gate operation is selected.
Stagger Delay Time
(Rarely used in slide gate installations)
This function is used in dual gate installations only. The factory default sets the Stagger Time to 0 seconds (OFF). The Stagger Time sets the delay for the Stagger Mode. The Stagger Time can be set from
1-99 seconds.
✓ NOTE: This function will only be displayed if dual gate operation is selected.
FUNCTION
"AD"
ADVANCED
PROGRAMMING
FUNCTION
"RT"
MAXIMUM RUN
TIMER
FUNCTION
"SB"
SINGLE BUTTON
INPUT SETUP
FUNCTION
"SM"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
STAGGER
MODE
FUNCTION
"ST"
GSLG-A Slide Gate Operator Installation Guide
- 13 -
STAGGER
DELAY TIME
OPTIONS
ADVANCED PROGRAMMING FUNCTIONS
WILL NOT BE DISPLAYED
ADVANCED PROGRAMMING OPTIONS
WILL BE DISPLAYED
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
NOTE: ADVANCED PROGRAMMING
WILL STAY ENABLED AFTER
EXITING PROGRAMMING UNTIL
THE GATE CYCLES 50 TIMES
OPTIONS
DISPLAY SHOWS CURRENT
MAXIMUM RUN TIME SETTING
ENTER PRESS ENTER FOR 1 SECOND
WHILE DISPLAY IS FLASHING, PRESS
UP OR DOWN TO CHANGE THE
MAXIMUM RUN TIME (10-99 SECONDS)
ENTER PRESS ENTER TO STORE THE VALUE
OPTIONS
SINGLE INPUT WILL CYCLE OPERATOR
IN ORDER OF OPEN-STOP-CLOSE-STOP
SINGLE INPUT WILL OPEN OPERATOR,
IF OPERATOR IS ALREADY OPEN, SINGLE
INPUT WILL CLOSE OPERATOR
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
DISABLES STAGGER FUNCTION
SETS THIS OPERATOR FOR
DELAYED OPEN
SETS THIS OPERATOR FOR
DELAYED CLOSE
DUAL GATES
ONLY
OPTIONS
STAGGER TIMER DISABLED
SET STAGGER DELAY VALUE
1 TO 99 SECONDS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
DUAL GATES
ONLY
P1222 X10
Advanced Controller Programming (Cont.)
Auxiliary Relay Mode
The Auxiliary Relay has normally open and normally closed contacts.
The factory setting disables the Auxiliary Relay. The relay can be set for:
• Maglock: To deactivate a magnetic or solenoid gate lock, the relay will energize during any pending or actual gate motion (open only).
• M4: To deactivate a magnetic or solenoid gate lock, the relay will energize during any pending or actual gate motion (open only).
3 seconds after the gate starts to move, the relay will de-energize.
This option is used for higher current solenoid locks.
• Ticket Dispenser: The relay will energize while the gate is moving in the open direction and at the full open limit, or in an entrapment condition.
• Strobe: To activate a warning strobe light, the relay will energize during any pending or actual gate motion (either open or close).
• Alarm: The relay will energize if the gate is manually forced open from the full closed position.
Reverse Delay Time
The factory default sets the Reverse Delay to 1 second. The operator will wait the length of the delay before reversing direction. This feature will not change the reversal time when the operator is responding to an entrapment condition from an obstruction input or inherent entrapment protection sensor. The Reverse Delay can be set from 1 to 9 seconds.
Heaver gates require a longer delay to allow time for the gate to stop.
Brake Delay Time
The factory default sets the Brake Delay to no delay (0 seconds). Heavy gates may require delayed braking to allow the gate to slow down before stopping it. The operator can be set to wait the length of the delay after running before applying the brake. The Brake Delay can be set from 0 to 3 seconds.
Constant Pressure Mode
The factory default allows momentary pressure on a control station’s
OPEN or CLOSE button to cycle the operator. The controller can be set to require constant pressure on the OPEN , CLOSE , or both buttons to run the operator.
✓ NOTE: If a button is set for constant pressure, and it is released before the operator reaches the open or close limit, the operator will stop the gate at its current position.
Shadow Loop Open Prevention
If the shadow loop is triggered, it always prevents the gate from closing if the Auto Close Timer activates or a CLOSE command is given while the gate is at the full open position.
The controller can also be set to prevent the gate from opening if the shadow loop is triggered while the gate is at the close limit position.
This prevents a swing gate from opening into a vehicle if it’s parked near the gate on the inside.
GSLG-A Slide Gate Operator Installation Guide
FUNCTION
"AR"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
AUXILIARY
RELAY MODE
FUNCTION
"RD"
REVERSE
DELAY TIME
FUNCTION
"BD"
OPTIONS
OPTIONS
SET TIMER VALUE
1 TO 9 SECONDS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
SET TIMER VALUE
0 TO 3 SECONDS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
AUXILIARY RELAY DISABLED
AUXILIARY RELAY USED FOR
MAGLOCK CONTROL
AUXILIARY RELAY USED FOR
MAGLOCK OR SOLENOID CONTROL
3 SECOND DELAY TO RE-ENERGIZE
AUXILIARY RELAY USED FOR
TICKET DISPENSER CONTROL
AUXILIARY RELAY USED FOR
WARNING STROBE LIGHT
AUXILIARY RELAY USED FOR
CONNECTION TO ALARM DEVICE
BRAKE
DELAY TIME
FUNCTION
"CP"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
CONSTANT
PRESSURE MODE
FUNCTION
"SP"
SHADOW LOOP
OPEN PREVENTION
- 14 -
OPTIONS
CONSTANT PRESSURE SET TO OFF
(MOMENTARY PRESSURE ON)
OPEN BUTTON SET FOR
CONSTANT PRESSURE
CLOSE BUTTON SET FOR
CONSTANT PRESSURE
OPEN AND CLOSE BUTTONS BOTH SET
FOR CONSTANT PRESSURE
OPTIONS
STANDARD OPERATION
SHADOW LOOP INHIBITS CLOSING ONLY
OPEN INHIBIT ON, SHADOW LOOP INHIBITS
OPENING AND CLOSING
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
P1222 X10
Advanced Controller Programming (Cont.)
Reset Cycle Count
The Controller counts of the number of times the operator has been cycled full open and close. The cycle count can be displayed. The display will scroll the cycle count number, flashing two digits at a time from left to right.
To reset the Cycle Count, press and hold the ENTER button for 2 seconds while the Cycle Count is displayed.
If the Maintenance Alert has been triggered, resetting the Cycle Count will also reset the Maintenance Alert indicator.
Maintenance Alert Trigger
The Controller has a MAINT ALERT indicator that can be programmed to light when the number of activations exceeds a set number of cycles.
The factory default sets the Maintenance Alert Trigger to 10,000 cycles.
The Maintenance Alert Trigger can be programmed for 5, 10, 15, or 25 thousand cycles.
The Maintenance Cycle Count can be reset independently from the operator’s absolute Cycle Count.
Mid-travel Stop Position
The Controller can be programmed so the gate will stop at a mid-travel point instead of fully opening. This can be useful in installations where a large gate, that takes a long time to open and close fully, only needs to be opened partway to allow traffic to pass.
The factory default sets the Controller for full open operation. Alternately, the Controller can be programmed to open for 1 to 99 seconds then stop, before reaching the open limit.
When a Mid-travel Stop Position time has been programmed, the gate will still fully open if the Fire Department input is triggered, if the OPEN button is held down beyond the Mid-travel Stop Position, or a close obstruction or reverse loop input is triggered.
✓ NOTE: The Mid-travel Stop feature is disabled when dual gate operation is enabled for paired units.
Anti-tailgate Enable
The factory default sets the Anti-tailgate Enable to OFF. With this setting, during a gate cycle, after the shadow loop has been triggered by the vehicle and then has cleared after the vehicle passes, the Auto Close
Timer or a CLOSE command is required to begin closing the gate.
If the Anti-tailgate Enable is set to ON, the gate will close immediately as soon as the shadow loop has cleared. Any subsequent shadow loop triggers while the gate is closing will stop the gate. When the shadow loop clears, the gate will continue closing.
Radio Enable
The Controller contains a built-in MegaCode ® radio receiver to allow activation from up to 40 access control transmitters and two Model
MGT (gate edge) transmitters. The factory default enables the internal radio receiver. Alternately, the internal receiver can be disabled.
Antenna Installation
A local whip antenna is included for use with the operator as a remote antenna. If using a remote antenna, connect coax cable from the antenna to the ANTENNA connector.
FUNCTION
"CT"
PRESS ENTER TO START THE CYCLE COUNT DISPLAY
1ST DISPLAY 2ND DISPLAY 3RD DISPLAY 4TH DISPLAY
RESET CYCLE
COUNT
FUNCTION
"MA"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
MAINTENANCE
ALERT TRIGGER
FUNCTION
"MT"
MID-TRAVEL
STOP POSITION
FUNCTION
"AT"
ANTI-TAILGATE
ENABLE
FUNCTION
"RA"
RADIO
ENABLE
EXAMPLE ABOVE SHOWS 10,420 CYCLES
DECIMAL POINT LIT
ON 4TH DISPLAY
NOTE: PRESS ENTER FOR 2 SECONDS
WHILE THE "CT" FUNCTION IS DISPLAYED
TO RESET THE CYCLE COUNT TO ZERO
OPTIONS
DISABLES THE MAINTENANCE ALERT
FUNCTION
SETS THIS MAINTENANCE ALERT TRIGGER
FOR 5, 10, 15, OR 25 THOUSAND CYCLES
RESETS THE MAINTENANCE ALERT
INDICATOR AND SETS THE MAINTENANCE
ALERT COUNT TO ZERO
OPTIONS
MID-TRAVEL STOP DISABLED
(GATE RUNS FULL TRAVEL)
SET LENGTH OF OPENING TIME
FROM 1 TO 99 SECONDS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
ANTI-TAILGATE ENABLE OFF
GATE REQUIRES AUTO OR MANUAL CLOSE
ANTI-TAILGATE ENABLE ON
GATE CLOSES WHEN SHADOW LOOP CLEARS
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
OPTIONS
INTERNAL RADIO RECEIVER DISABLED
INTERNAL RADIO RECEIVER ENABLED
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
PRESS ENTER TO
SELECT AN OPTION
GSLG-A Slide Gate Operator Installation Guide
- 15 -
P1222 X10
Advanced Controller Programming (Cont.)
Radio Transmitter Learn
The Controller’s built-in MegaCode® radio receiver can store the IDs of up to 40 transmitters. Refer to the figure for the steps required to learn transmitters.
✓ NOTE: This function will NOT be displayed if the transmitter memory is full, or if the radio receiver is disabled.
Radio Transmitter Delete
Transmitters can be deleted from the Controller’s memory either individually, or all at the same time. Refer to the figure for the steps required to delete transmitters.
✓ NOTE: This function will NOT be displayed if no transmitters are stored in memory, or if the radio receiver is disabled.
MGT Obstacle Transmitter Learn
The Controller supports one or two Model MGT Obstacle Transmitters.
The transmitters can be programmed to function as Open Obstruction,
Close Obstruction, Reverse, or Stop. Refer to the figure for the steps required to learn MGT transmitters.
✓ NOTE: This function will NOT be displayed if two MGT transmitters are already stored in memory, or if the radio receiver is disabled.
MGT Obstacle Transmitter Delete
MGT transmitters can be deleted from the Controller’s memory either individually, or all at the same time. Refer to the figure for the steps required to delete MGT transmitters.
✓ NOTE: This function will NOT be displayed if no MGT transmitters are stored in memory, or if the radio receiver is disabled.
Motor Type Selection
The factory sets the default for the Controller to match the type of motor in the operator. If required, change the motor selection option to a different type of motor used in the operator. The only two options used with this model operator are:
• AC Motor Only
• 3 Phase AC Motor
Reset Controller to Factory Defaults
The Controller can be reset with this function. ALL PROGRAMMED
DATA WILL BE LOST , and the factory defaults will be loaded. This function will not erase radio transmitters, current sense values, or motor type. Transmitters must be deleted with the two functions above.
FUNCTION
"MD"
ENTER
ENTER
ERASE MGT
TRANSMITTERS
FUNCTION
"CL"
ENTER
WHILE "CL" IS DISPLAYED, PRESS ENTER
ALL PROGRAMMED DATA WILL BE CLEARED
AND THE FACTORY DEFAULTS WILL BE
STORED IN MEMORY.
FUNCTION
"MO"
PRESS UP OR
DOWN TO CYCLE
THROUGH OPTIONS
OPTIONS
RESET TO
FACTORY DEFAULTS
NOTE: THIS FUNCTION WILL NOT ERASE
TRANSMITTERS, CURRENT SENSE VALUES,
OR MOTOR TYPE.
GSLG-A Slide Gate Operator Installation Guide
- 16 -
PRESS ENTER TO
SELECT AN OPTION
MOTOR TYPE
SELECTION
FUNCTION
"TL"
ENTER
PRESS ENTER (ONCE FOR EACH TRANSMITTER,
UP TO 40 TRANSMITTERS TOTAL)
"TL" WILL BLINK FOR 30 SECONDS WHILE
THE CONTROLLER IS READY TO
LEARN A TRANSMITTER
ACTIVATE THE TRANSMITTER
DISPLAY WILL SHOW "- -" THEN THE
TRANSMITTER ID NUMBER - IF TRANSMITTER
IS ALREADY ENTERED, "dU" WILL BE DISPLAYED,
IF DECODE IS BAD "ERROR" WILL BE DISPLAYED
LEARN
TRANSMITTERS
FUNCTION
"TD"
DELETE
TRANSMITTERS
ENTER PRESS ENTER
"TD" WILL BLINK FOR 30 SECONDS WHILE THE CONTROLLER
IS READY TO DELETE ONE OR MORE TRANSMITTERS,
(TO EXIT WITHOUT DELETING ANY, PRESS ENTER)
UP
ENTER
OR DOWN
TO DELETE ALL TRANSMITTERS, PRESS ENTER FOR
2 SECONDS, OR TO PICK TRANSMITTERS GO TO NEXT STEP
PRESS UP OR DOWN TO SCROLL THROUGH THE LIST
OF TRANSMITTER ID NUMBERS
THE TRANSMITTER ID NUMBER IS DISPLAYED
(TO EXIT WITHOUT DELETING, PRESS ENTER)
(TO PICK A DIFFERENT TRANSMITTER ID, PRESS UP OR DOWN)
ENTER
PRESS ENTER FOR 2 SECONDS TO DELETE THE
TRANSMITTER DISPLAYED
FUNCTION
"ML"
LEARN MGT
TRANSMITTERS
ENTER
UP OR DOWN
PRESS ENTER, "ML" WILL BLINK FOR 30 SECONDS WHILE
THE CONTROLLER IS READY TO LEARN AN MGT
TRANSMITTER
ACTIVATE THE MGT TRANSMITTER, THE DISPLAY WILL
FLASH "rE" - IF THE TRANSMITTER IS ALREADY ENTERED,
"DU" WILL BE DISPLAYED, IF DECODE IS BAD "ERROR" WILL
BE DISPLAYED
PRESS UP OR DOWN TO SELECT THE MGT FUNCTION:
"rE" = REVERSE "St" = STOP
"OP" = OPEN OBSTRUCTION "CL" = CLOSE OBSTRUCTION
ENTER PRESS ENTER TO ACCEPT THE SELECTION
DISPLAY WILL SHOW "--" FOR 5 SECONDS, THEN SHOW THE
TRANSMITTER'S ID NUMBER - REPEAT STEPS FOR
SECOND MGT TRANSMITTER IF USED
PRESS ENTER
"MD" WILL BLINK FOR 30 SECONDS WHILE THE CONTROLLER
IS READY TO DELETE ALL MGT TRANSMITTERS
TO DELETE ALL MGT TRANSMITTERS, PRESS ENTER FOR
2 SECONDS, (TO EXIT WITHOUT DELETING ANY, QUICKLY
PRESS ENTER)
THE DISPLAY WILL SHOW "DELETE ALL" AND THE
CONTROLLER RETURNS TO PROGRAMMING MODE
AC MOTOR ONLY
DO NOT SELECT
NOT USED IN THIS MODEL
NOTE: SELECTION
MUST MATCH
MOTOR BOARD!
DO NOT SELECT
NOT USED IN THIS MODEL
3 PHASE AC MOTOR
DO NOT SELECT
NOT USED IN THIS MODEL
DO NOT SELECT
NOT USED IN THIS MODEL
P1222 X10
Loop Layout Illustration
LOOP SEALAN
TWIST WIRE FROM END OF LOOPS BACK TO OPERATOR AT LEAST SIX TIMES PE
GSLG-A Slide Gate Operator Installation Guide
- 17 -
SEPARATE PEDESTRIAN GATE REQUIRED 7 FEET MINIMUM DISTANCE FROM GATE
P1222 X10
Safety Edge Layout Illustration #1
REVERSING EDGE ASSY CLOSEU
SEE NOTE ITEM #1
2 EDGE 3 EDGE EXTRUSION
SLIDE GATE OPERATOR WITH RADIO RECEIVER MOUNTED INSIDE
SEE NOTE ITEM #2
NOTES: 1. WIRE THESE EDGES FOR CLOSE OBSTRUCTIO MUST BE TAKEN IN ROUTING THE WIRES SUCH THAT THEY DO NOT BECOME DAMAGED DURING NORMAL OPERATIO
SEE NOTE ITEM #1
GSLG-A Slide Gate Operator Installation Guide
- 18 -
P1222 X10
Safety Edge Layout Illustration #2
JUNCTION BOX MOUNTED TO FENCE POST
SLIDE GATE OPERATOR WIRED DIRECT TO EDGE USING JUNCTION BOX AND COIL CORD
5. IF SENSOR EDGES ARE HARD WIRED TO THE OPERATOR, CARE MUST BE TAKEN IN ROUTING THE WIRES SUCH THAT THEY DO
GSLG-A Slide Gate Operator Installation Guide
- 19 -
SEE NOTE ITEM #1
SEE NOTE ITEM #1
SEE NOTE ITEM #3
P1222 X10
Photoeye Installation Illustration
LOCATIONS FOR THE INSTALLATION OF CONTACT OR NON-CONTACT OBSTRUCTION SENSING DEVICES. OTHER AREAS OF ENTRAPMENT
GSLG-A Slide Gate Operator Installation Guide
- 20 -
SEPARATE PEDESTRIAN WALKGATE REQUIRED 7 FEET MINIMUM DISTANCE
P1222 X10
Picket Gate Installation
MESH WITH OPENINGS SMALLER THAN 2 1/4"
TO A MINIMUM HEIGHT OF 48" ABOVE GROUND OVER ENTIRE GATE LENGTH
ENTRAPMENT ZONE #3 (BEHIND GATE PHOTOEYE BEHIND GATE
TRAILING EDGES OF GATE, AND ON POST
PICKETS SPACE SMALLER THAN 2 1/4"
ENTRAPMENT ZONE #2 (BOTH SIDES OF GATE
REVERSING PHOTOEYE ACROSS DRIV
SHOWN ABOVE. OTHER AREAS OF ENTRAPMENT MAY EXIST DEPENDING ON EACH SPECIFIC INSTALLATION. REFER TO INSTALLATION MANUAL FOR ADDITIONAL DETAILS FOR THE INSTALLATION AND WIRING OF LOOPS, EDGES, AN
ENTRAPMENT ZONE #1
SEPARATE PEDESTRIAN GATE REQUIRED 7 FT. MINIMUM DISTANCE AWAY FROM GATE
GSLG-A Slide Gate Operator Installation Guide
- 21 -
P1222 X10
Track Gate Installation
BOLTED TO CHANNE
END OF TRACK GATE FOR GATE BRACKE
C-CHANNEL ATTACHED TO BACK END OF TRACK GATE (BY OTHERS
GSLG-A Slide Gate Operator Installation Guide
- 22 -
P1222 X10
Dual Gate Installations
Two operators can be used in dual gate installations. The operators communicate with each other through the 3-wire COMM LINK terminals.
When one operator activates, the COMM LINK connection signals the other operator to activate. Each operator functions independently, controlling its gate and monitoring its inputs and accessories.
A three-wire shielded conductor cable is required to connect two operators together for dual operation. Use Belden 8760 Twisted Pair
Shielded Cable (or equivalent) only – P/N 2500-1982, per foot).
✓ NOTE: The shield wire should be connected COMM LINK terminal “C” in both operators.
Three of the programming functions available are only used for dual gate installations:
• Dual Gate Enable
Dual Gate Enable must be set for all dual gate installations.
• Stagger Mode
The Stagger Mode function determines if the operator has a delayed open or a delayed close. In dual swing gate installations, typically one operator is programmed for delayed open, and the other operator is programmed for delayed close.
• Stagger Delay Time
The Stagger Time sets the length of the delay for the Stagger Mode.
See Pages 11 & 13 for details on these three dual gate programming functions.
Set the following parameters in each gate operator individually in a single gate mode before connecting the network cable and operating in dual gate mode.
4. 1. Open and Close Limit settings
5. 2. Open and Closed direction inherent entrapment protection (OC & CC)
After these parameters have been set, and each operator has been tested independently and is functioning correctly in single gate mode, then set BOTH operators to dual gate (dg) in the Paired Mode setup step under Basic Programming steps.
Optional In-Cabinet Heater
The operator can be ordered with an optional cold weather package that includes an in-cabinet heater to keep the drive train and electronics warm in cold environments.
In-cabinet heaters can also be ordered separately and should be wired to the operator as shown in Figure 14. Contact Technical
Services for heater wiring information for a specific voltage and phase of operator.
DUAL GATE
COMM LINK
WIRING SHIELD
OPERATOR #1
CONNECT
C - C
B - B
A - A
CONNECT SHIELD
WIRE AT BOTH ENDS
SHIELD
USE BELDEN 8760 TWISTED PAIR
SHIELDED CABLE OR EQUIVALENT
OPERATOR #2
Figure 13. COMM LINK Wiring
SINGLE PHASE 115V, 208V, & 230V MODELS
(All heaters have built-in switch and thermostat)
BLACK
WHITE
POWER BOX
115 VOLT HEATER (P/N 2510-262)
208/230 VOLT HEATER (P/N 2510-273)
CONNECT TO LEADS LABELED
"ACCESSORY POWER CONNECTION"
THREE PHASE 208V & 230V MODELS
208/230 VOLT HEATER (P/N 2510-273) CONTACTOR
THREE PHASE 460V MODELS
GSLG-A Slide Gate Operator Installation Guide
CONTACTOR
- 23 -
460 VOLT HEATER (P/N 2510-354)
Figure 14. In-cabinet Heater Wiring
P1222 X10
Gate Operation
Open Button
Opens the gate. If the Controller is programmed to stop opening the gate at mid-travel, a constant press of the OPEN button will override the Mid-travel Stop and completely open the gate. If the Auto Close
Timer is set, it will be suspended until the OPEN button is released.
Close Button
Closes the gate if the gate is open. Also closes the gate if the gate is in the process of opening.
Stop Button
Stops the gate from opening or closing at any time.
Single Input
Opens the gate if it’s closed and closes the gate if it’s open (openclose programming option). Activating the input while the gate is moving will reverse the gate.
Can be programmed to stop the gate while the gate is moving (openstop-close programming option).
Fire Department Input
Fully opens the gate when the input is activated. Overrides the Midtravel Stop and Auto Close Timer (if either is programmed for the gate). The gate will lockout in the open position without sounding the alarm. Press the STOP button to release the lockout.
Open Input
Functions the same as the OPEN button.
Open Obstruction
While the gate is opening, any open obstruction signal will cause the gate to stop, reverse a short distance, and then stop again. The Auto
Close Timer will be disabled, and a renewed input will be required to start the gate again. Should the gate be restarted and the obstacle signal occur again prior to reaching a limit, the gate will stop again, lockout, and sound the emergency alarm.
Close Obstruction
While the gate is closing, any close obstruction signal will cause the gate to stop, reverse, and travel to the full open position. Should a open obstruction input or an open direction inherent entrapment condition occur prior to the gate reaching the open limit, the operator will lockout and sound the continuous tone alarm. Another close request will be required to start the operator again. If after restart, the overload or a close obstacle happens again before the close limit is reached, the operator will lockout and sound the alarm. If the auto close timer is set, when the close obstruction input is cleared, the gate will close when the auto close timer expires.
Reverse Input
If the reverse input is triggered while the gate is closing, the gate will reverse to the full open position. If the Auto Close Timer is set, when the reverse input is cleared, the gate will close when the Auto Close
Timer expires.
Open Loop
Functions the same as the OPEN button.
Reverse Loop
Functions the same as the reverse input.
Shadow/reset Loop
Only used with Swing Gates. Holds the gate fully open or fully closed while triggered. If open, the gate closes immediately when cleared if
Anti-tailgate is enabled.
Operation Indications
During normal operation, the Controller’s displays will indicate current operating conditions and status.
Power-up Display
When the Controller powers up, dashes will show on the display, then the firmware version number, then the gate type (SL for slide and swing gates).
Exiting programming restarts the Controller. The power-up display will show upon the restart.
Idle Condition
While the Controller is idling, waiting for a command, the display will show circulating dashes.
Last Gate Position/Condition
When the gate moves or stops, the display will show the status for up to one minute.
• Stop is displayed as
St
• Full Close is displayed as
FC
• Full Open is displayed as
FO
• Entrapment is displayed as
En
Pre-start Delay
During the pre-start delay, the display will countdown the number of seconds remaining before the operator starts.
Reverse Delay
If the gate travel direction is reversed from a user activation or reversing device, and a reverse delay is set, the display will count down the delay time in seconds before the operator restarts.
Run Timer
While the gate is opening or closing, the number of seconds running time is displayed.
GSLG-A Slide Gate Operator Installation Guide
- 24 -
P1222 X10
Error Indications
During abnormal operation, the Controller’s displays and beeper will indicate the error condition that has occurred.
Entrapment
If an entrapment condition occurs detected by two repeated open or close obstruction triggers, the Controller will lock the operator out.
The beeper will sound constantly and the gate will not operate. To reset the Controller press the STOP button or press the RESET button on the operator’s cover.
WARNING
The Stop and/or Reset button must be located in the lineof-sight of the gate. Activation of the reset control shall not cause the operator to start.
COMM LINK Connection Failure
In dual gate installations, if there is a connection failure between the two operators, the COMM LINK indicator will blink once a second.
During this condition the gate will not operate, except if triggered by the FIRE DEPT input, which functions normally.
MGT Obstacle Transmitter Trouble
If any MGT transmitters are used with the operator, their supervision feature will alert the Controller if there is any trouble with the transmitter. MGT transmitters send hourly status reports and will send low battery reports when the transmitter has a low battery.
The MGT transmitters also have a tamper detection switch that will trigger when their case is opened.
When the Controller detects a low transmitter battery, a tamper signal, or missing transmitter status reports, the gate will still operate normally, but the beeper will change as follows:
• The Pre-start Alarm will beep twice as fast.
• The Run Alarm will beep twice as fast and continue for five minutes after the gate stops.
• The sounder will “chirp” every five seconds when the gate is idle.
Correct the trouble (close case, replace battery, or replace transmitter) to clear the obstacle transmitter trouble indications.
Maximum Run Time Exceeded
If the Maximum Run Time is exceeded, the Controller stops the operator the same as if a double obstacle has occurred in an entrapment condition. The entrapment alarm sounds constantly, and is cleared by pressing the STOP button or the RESET button on the cover. After the STOP or RESET button is pressed, because the Maximum Run Time has been exceeded, the sounder will beep twice every five seconds. The next operation of the gate will clear the indication.
CONTROLLER ERROR CAUSES AND INDICATIONS
ERROR CAUSE
TWO SAFETY REVERSALS
(ON SINGLE GATE OR ON
EITHER DUAL GATE)
ERROR INDICATION
En 00, CONTINUOUS
ALARM BEEPER, GATE
DISABLED
HOW TO CLEAR
PRESS STOP BUTTON
MAXIMUM RUN TIMER
EXCEEDED ON OPENING
MAXIMUM RUN TIMER
EXCEEDED ON CLOSING
En 01, AND MAX RUN
LED, CONTINUOUS ALARM
BEEPER, GATE DISABLED
En 02, AND MAX RUN
LED, CONTINUOUS ALARM
BEEPER, GATE DISABLED
PRESS STOP BUTTON,
CLEARS CONTINUOUS
ALARM, THEN DOUBLE
BEEP EVERY 5 SECONDS
UNTIL NEXT OPERATION
PRESS STOP BUTTON,
CLEARS CONTINUOUS
ALARM, THEN DOUBLE
BEEP EVERY 5 SECONDS
UNTIL NEXT OPERATION
COMM LINK FAILURE
En 03, AND COMM LINK
LED, CONTINUOUS ALARM
BEEPER FOR 1 MINUTE,
GATE DISABLED (EXCEPT
FOR FIRE DEPT INPUT)
PRESS STOP BUTTON,
CLEARS CONTINUOUS
ALARM
GATE FULL OPEN
RESULTING FROM FIRE
DEPT INPUT
FAIL SAFE OR FAIL
SECURE BECAUSE OF
BATTERY VOLTAGE DROP
BELOW 21.6 VDC DUE TO
AC POWER LOSS
OTHER CONTROLLER
IN ENTRAPMENT (DUAL
GATE)
LOW AC VOLTAGE AT
CONTROLLER
INPUT TRIGGERED DURING
ENTRAPMENT LOCKOUT
En 04, GATE DISABLED
En 05, GATE DISABLED
En 06, GATE DISABLED
En 07, GATE DISABLED
En 08, GATE DISABLED
PRESS STOP BUTTON
BATTERY VOLTAGE MUST
RISE ABOVE 24 VDC
CLEAR ENTRAPMENT
ON OTHER CONTROLLER
(PRESS STOP)
RESTORE AC POWER TO
NORMAL LEVEL
PRESS STOP BUTTON
COMPATIBILITY PROBLEM
EEPROM PROBLEM
DC MOTOR MISMATCH
En 09, GATE DISABLED
En 10, GATE DISABLED
En 11, GATE DISABLED
En 12, GATE DISABLED
UPDATE FIRMWARE AND
RESET BOTH PAIRED
CONTROLLERS
TRY RESET, CALL TECH.
SUPPORT
REPROGRAM MOTOR TYPE
OR CHANGE DC MOTOR
BOARD, NEXT GATE
MOVEMENT WILL RETRY
DC MOTOR CHECK
REPLACE MOTOR MOTOR FAILURE
AC POWER LOSS IN OPEN
OR CLOSE IMMEDIATE
POWER FAIL MODE
En 13 REAPPLY AC POWER
MAXIMUM RUN TIMER
EXCEEDED AFTER AC
POWER LOSS
MGT SUPERVISORY
CONDITION (TAMPER,
LOW BATTERY, MISSING
HOURLY STATUS)
En 14
FAST BEEPS DURING
PRESTART, FAST BEEP
RUN ALARM, CHIRP EVERY
5 SECONDS AT IDLE
BATTERY VOLTAGE MUST
RISE ABOVE 24 VOLTS
CLEARS WHEN MGT
CONDITION CLEARS
GSLG-A Slide Gate Operator Installation Guide
- 25 -
P1222 X10
Troubleshooting
Contacting Technical Support
For technical questions regarding Linear gate operators, contact the
Technical Services Department at:
1-800-421-1587 from 5:00 AM to 4:30 PM Pacific time
Operator fails to start
A . If the operator has been running a large number of cycles, the motor may have become too hot and tripped its thermal overload breaker . Allow the motor to cool down and the thermal overload breaker will reset automatically .
B . Make sure you have power at the master distribution panel and that the power has not been turned off .
Motor operates, but gate does not move
A . In operators with torque limiters and friction pad clutches, check for signs of slipping . You can mark the sprocket and clutch with a yellow or white grease pen and watch for the lines to move apart if slipping is taking place . Adjust the torque limiter tighter if this is the problem .
B . Check for broken chain or worn belts .
C . Check all setscrews on pulleys and sprockets and tighten them if necessary, and check for keys which may have fallen loose from keyways .
Motor sounds like it is working harder than normal
A . Make sure the gate is moving freely and without binding throughout its entire travel .
B . Check the drive chain for obstructions (if the operator has one) .
C . If the operator has an internal brake mechanism, make sure it is releasing .
Limit switch getting out of time
A . Check for proper tension on all limit chains to be sure there is no jumping taking place . Mark one tooth and its corresponding link and run the gate . If the marks have moved, the chain is skipping .
B . Check the setscrews in limit sprockets for tightness .
In rotary limit boxes, check the rotary limit nut for sloppiness or stripped threads . Replace if necessary .
Gate stopping part way open or closed
(but no visible obstruction)
A . The Controller may have received a false obstruction input triggered by current sensing set too low . Make sure the gate moves freely through its entire travel before adjusting the current sensing .
B . The Maximum Run Timer may have counted down and expired . This can be caused by having the timer set too low, if a chain or belt is broken, or if a sprocket or pulley is slipping . When the timer expires, the gate stops and the beeper will sound .
C . An obstruction signal from an accessory wired to the obstruction input may have triggered falsely . Check the control board for lit indicators for any of the following inputs: safety, shadow/reset, open obstruction, close obstruction, stop, etc . If any are lit when the operator should be running, remove all devices hooked to that function and hook them up one at a time and try to run the operator until the problem device is found . Refer to Page 8 for details on the control board indicators .
Gate staying open with automatic system
A . If there are vehicle detectors used with the operator, one of the loops or loop detectors may be sending a false signal or needs to be reset . Observe the indicators on the loop detector . Unplug the detector and try running the operator .
B . An opening or reversing device may be stuck or malfunctioning . Try disconnecting these devices and hook them back up one at a time and try running the operator until the malfunctioning device is found .
C . Make sure the close limit switch isn’t activated . If it is, the operator will think the gate is already closed .
How to Order Replacement Parts
Use the part numbers listed on the following pages.
Contact your local Linear dealer or distributor to order parts.
1 . Supply the model number and serial number of your operator .
2 . Specify the quantity of pieces needed and order by part number and name of part .
3 . State whether to ship by freight, truck, parcel post, UPS or air express .
4 . State whether transportation charges are to be prepaid or collect .
5 . Specify name and address of person or company to whom parts are to be shipped .
6 . Specify name and address of person or company to whom invoice is to be sent .
GSLG-A Slide Gate Operator Installation Guide
- 26 -
P1222 X10
Preventative Maintenance
WARNING
Always disconnect power from operator before servicing.
Keep clear of gate during operation.
General
Linear gate operators are designed for many years of trouble-free operation and, under recommended operating conditions, will require only minimal maintenance. To ensure that a unit is ready for operation at all times, and to preclude serious damage or failure, inspect the unit systematically. Proper adjustments and lubrication should be made as recommended.
Lubrication
✓ Bearings — For models which have pillow block style bearings with grease fittings, lubricate at least twice a year with a lithium complex based, petroleum oil NLGI
2 rated grease . Oilite and precision sealed bearings do not require additional lubrication .
✓ Motor — Motors have sealed ball bearings and do not require further lubrication . If bearing noise develops after several years of operation, bearings should be replaced by a motor repair company, or the motor should be replaced if necessary .
✓ Drive Chain and Sprocket — The main drive chain and sprockets should be inspected for wear, cleaned, and wiped down with a lightly oiled rag every six months .
For all gate operators, you must inspect the gate for proper operation.
The gate should move easily without binding through its entire travel. If the gate does bind, adjust or fix as required. Failure to keep the gate in good working condition will have adverse effects on the operator.
6-Month Preventative Maintenance
1. For operators which utilize torque limiting clutches, check for proper tightness. If there appears to be dust from wear on the pads, inspect the pads and replace if necessary. If the clutch cannot be adjusted tightly enough to move the gate without slipping, the pads must be replaced.
2. For operators with V-belts, inspect for wear and replace as necessary. Check for proper tension and adjust if required. Check all pulley setscrews for tightness and tighten if necessary.
3. For operators with internal chain drives, inspect chain and sprockets for wear and replace if necessary. Check for proper tension and alignment, and adjust if required. Check all hub sprocket setscrews and tighten if required.
4. Check limit switches and limit actuators (cams, limit nuts, etc.) for wear and replace as required. In rotary limit switch assemblies, wipe the limit shaft clean and apply a light coating of dry lubricant.
5. For operators with magnetic brakes, check for proper adjustment.
Brake disc must run free when the brake is engaged. For brake assemblies other than C-face style, the brake should be adjusted so that the solenoid plunger throw is between 3/8” to 1/2”. Too much throw will damage the solenoid. If the solenoid emits a loud buzzing sound when the motor is run, the brake must be adjusted.
6. In operators which have a disconnect handle, inspect disconnect handle for proper function and lubricate if necessary. Use a lithium based grease on all moving parts.
7. Inspect all nuts and bolts for proper tightness and tighten as necessary.
8. Check all reversing devices for proper function. Inspect all contact edges for wear and replace if required. Check photoeyes for proper alignment and function.
9. Check current sensing for proper adjustment when finished with inspection and maintenance.
10. Inspect the installation area. Are all the warning signs intact and visible? If they are missing or need replacing, contact Linear. Be sure there are no control stations mounted within reach of the gate.
Review safety literature with the customer and advise them to remove any such stations found.
FCC Notice
This device complies with FCC Rules Part 15 and Industry Canada
Rules & Regulations. Operation is subject to the following two conditions: (1) This device may not cause harmful interference and
(2) this device must accept any interference received, including interference that may cause undesired operation.
GSLG-A Slide Gate Operator Installation Guide
- 27 -
P1222 X10
Model GSLG-A Exploded View
GSLG-A Slide Gate Operator Installation Guide
- 28 -
P1222 X10
REF. #
1
MODEL GSLG-A MECHANICAL PARTS LIST
PART #
2120-359-BT
2120-144-BT
2120-360-BT
2300-716
DESCRIPTION
Complete Enclosure with Door Assembly
Enclosure without Door
Complete Door and Lock Assembly
Stop/Reset Button Cover
8 2210-004
42 2200-886
2
2110-788
2200-920
19 2120-132
18 2110-362
37 2100-551
38 2400-169
20 2100-1133
28 2100-910
41 2200-291
14 2200-014
11 2110-364
30 2200-549
31 2110-131
2400-133
32 2200-115
44 2510-248
2100-1760
2500-1495
33 2400-308
34 2400-017
35 2400-016
36 2400-014
16 2110-700
2300-697
2100-1731
6 2520-173L
2500-764
2100-057
2500-2192
2500-2397
5 2110-265
15 2100-573
2100-661
12 2100-1738
48 2400-501
9 2200-274
43 2100-1737
40 2200-042
2200-015
7 2120-388
7A 2100-1650
7B 2100-1661
7C 2300-390
7D 2200-817
7E 2100-1621
7F 2100-1622
7G 2400-407
7H 2400-416
7I 2100-529
C-Face Brake, 115V
C-Face Brake, 208/230/460V
Rail Assembly
Spacer Plate
Back Brace
Drive Shaft, 1”
Retaining Ring
Bearing, 1”
Pillow Block Retaining Plate
Sprocket, 48 B 15, 1” bore
Shaft Collar, 1”
Torque Limiter Assembly, 5-1/2”
Plate with Solid Pin Groove
Keyed Plate
Friction Disc (pair)
Belleville Washer
Belleville Washer Retaining Disc
Adjustment Nut
Brass Tipped Set Screw
Dowel Pin
Woodruff Key
Sprocket, 40-A-48, with Bearing
Drive Sprocket, 50-B-20, 1” Bore
Gear Reducer/Disconnect Assembly
Gear Reducer, 15:1
Shifter Lever Assembly
Shifter Lever Fulcrum Assembly
Shifter Lever Rod
Pal Nut
Locking Lever Plate
Locking Lever
Shifter and Locking Lever Spring
Shaft Collar, 1”
Sprocket, 40 A 24, with Bearing
Disconnect Collar, 1” (keyed)
Shifter Block
Key, 1/4” x 1/4” x 2-1/4”
Disconnect Spring
Stop/Reset Button & Bracket Assembly
Stop/Reset Button Mounting Bracket
Stop/Reset Button
Fender Washer, 3/8”
Flat Washer, 3/8”
Lock Washer, 3/8”
HHCS, 3/8”-16 x 1”
Idler Assembly
UHMW Idler Wheel
Idler Shaft
Rotary Limit Box Assembly
Limit Switch
Standard Limit Shaft
GSLG-A Slide Gate Operator Installation Guide
- 29 -
2200-010
2200-605
2200-006
17 2100-657-BT
24 2200-221
2200-111
25 2100-258
26 2200-306
22 2100-2007
27 2400-090
23 2400-170
21 2400-038
2500-867
4
2500-2307
2500-2308
2500-2309
2500-2310
2500-2311
2500-2312
2500-2313
2500-2314
2500-2315
2500-2336
2500-2337
2500-1926
2500-1930
2500-1931
2500-2338
2500-1932
REF. #
2200-030
2100-261
2110-162
2100-756
2200-029
2200-193
2400-203
PART #
2200-042
Limit Nut
Detent Plate
Limit Box Enclosure with Cover
Limit Box Cover only
Flange Bearing, 1/2” ID
E-Ring, 1/2”
Spring Washer, 1/2”
DESCRIPTION
Limit Drive Sprocket, 48-B-15, 1” bore
For drives up to 34 feet wide:
39 2200-008 Limit Box Sprocket, 48-B-10, 1/2” bore
2200-922 #48 Chain, 25 Links
For drives from 35 to 49 feet wide:
2200-041 Limit Box Sprocket, 48-B-15, 1/2” bore
2200-200 #48 Chain, per foot, 27 Links
For drives 50 to 65 feet wide:
2200-276 Limit Box Sprocket, 48-B-20, 1/2” bore
2200-654 #48 Chain, per foot, 29 Links required
For drives over 65 feet wide:
2200-432
2200-654
Limit Box Sprocket, 48-B-30, 1/2” bore
#48 Chain, per foot, 32 links required
#48 Master Link
#40 Chain, 37 Links
#40 Master Link
Rain Cover
#50 Roller Chain, per foot
#50 Master Link
Chain Pin
Tension Spring
Gate Bracket
Hex Nut, 1/2”
Gate U-Bolt
Mounting U-Bolt
Alarm, 24VAC
C-FACE MOTORS
1/2 HP, 115 VAC, 1 Phase
1/2 HP, 208/230 VAC, 1 Phase
3/4 HP, 115 VAC, 1 Phase
3/4 HP, 208/230 VAC, 1 Phase
1 HP, 115 VAC, 1 Phase
1 HP, 208/230 VAC, 1 Phase
1/2 HP, 208/230/460V, 3 Phase
3/4 HP, 208/230/460V, 3 Phase
1 HP, 208/230/460V, 3 Phase
CAPACITORS
Capacitor for 2500-2307 Motor
Capacitor for 2500-2308 Motor
Capacitor #1 for 2500-2309 Motor
Capacitor #2 for 2500-2309 Motor
Capacitor for 2500-2310 Motor
Capacitor for 2500-2311 Motor
Capacitor for 2500-2312 Motor
P1222 X10
Single Phase Controller Parts List
2
5
4
3
ON
115V
MODELS
ONLY
1
6
3
4
5
6
7
8
SINGLE PHASE CONTROLLER MECHANICAL PARTS LIST
REF. # PART # DESCRIPTION
1 2100-1756 Mounting Plate
2 620-101293 Apex Module
2510-422
2510-430
2100-2143
2300-1025
2510-423
2100-1781
2520-525
115V Power Box Assembly
208/230V Power Box Assembly
Power Box Mounting Strap
Apex Plastic Cover
Cover Knob Kit
Accessory Shelf
Complete Wiring Harness Assembly
7
GSLG-A Slide Gate Operator Installation Guide
- 30 -
P1222 X10
Three Phase Controller Parts List
1 3
4
2
2
3
4
5
THREE PHASE CONTROLLER MECHANICAL PARTS LIST
REF. # PART # DESCRIPTION
2520-530 Control Box Assembly (Complete) 208/230V
1 2520-531 Control Box Assembly (Complete) 460V
6
7
2110-840
2100-582
620-101293
2500-1980
2500-034
2500-767
2500-768
2500-2084
Control Box Assembly (Box only)
Cover
Apex Module
Motor Board
Power Switch
Transformer 208/230V
Transformer 460V
Contactor
7
6
5
GSLG-A Slide Gate Operator Installation Guide
- 31 -
P1222 X10
Gate Operator Installation Checklist
INSTALLER CUSTOMER
❑ ❑ 1 . The gate has been checked to make sure it is level and moves freely in both directions .
❑ ❑ 2 . Potential pinch areas have been guarded so as to be inaccessible OR have contact and/or non-contact obstruction sensing devices installed .
❑ ❑ 3 . The installer has installed one or more approved obstruction detection devices, in compliance with UL325 requirements for this installation .
❑ ❑ 4 . If pedestrian traffic is expected, a separate pedestrian gate has been installed, a minimum of seven feet from the gate . The customer has been informed that all pedestrian traffic must use the pedestrian gate .
❑ ❑ 5 . Warning signs have been installed on each side of the gate in highly visible locations .
The customer has been informed that these signs must remain at all times .
❑ ❑ 6 . There are no controls installed on the gate operator, or within seven feet of the gate .
❑ ❑ 7 . The installer has properly adjusted the obstruction sensing feature and has tested the gate to make sure that the gate stops and reverses a short distance with minimal resistance applied (40 lbs . on a swing gate at the end of the gate, 75 lbs . on a slide gate)
❑ ❑ 8 . The installer has instructed the customer in the proper use of the gate operator and reviewed all of the operational functions, obstruction sensing devices, warning beeper and reset, etc .
❑ ❑ 9 . The installer has instructed the customer in the proper use of the operator’s manual disconnect feature . The manual disconnect must never be used while the gate is in motion . The power switch must be turned off before using the manual disconnect and disengaging the operator .
❑ ❑ 10 . The installer has reviewed all safety instructions with the customer, and has left the safety instructions and owner’s information sheets for their reference .
❑ ❑ 11 . The installer has answered any questions the customer has regarding the operation of the gate operator and gate operator safety precautions .
❑ ❑ 12 . The installer has explained to the customer that a regular maintenance schedule for both the gate and the gate operator is recommended .
By signing this installation checklist, I/we hereby certify that each item listed and checked above has been covered by the installer and is clearly understood by the customer.
Customer’s Signature Date
Installer’s Signature
GSLG-A Slide Gate Operator Installation Guide
Date
- 32 -
P1222 X10
Notes
GSLG-A Slide Gate Operator Installation Guide
- 33 -
P1222 X10
GSLG-A Slide Gate Operator Installation Guide
- 34 -
P1222 X10
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 3 Before You Begin
- 3 Always Check the Gate’s Action
- 3 Gate Operator Classifications
- 3 Approved Obstruction Detection Devices
- 3 Regulatory Warnings
- 4 AC Power Wiring
- 4 DC Control and Accessory Wiring
- 5 Gate Preparation
- 5 Mounting Specifications
- 6 Vent Plug Installation
- 7 Controller Access
- 7 Manual Disconnect
- 7 AC Power Connection
- 7 Earth Ground
- 8 Open and Close Limit Adjustment
- 8 Limit Nuts Rough Adjustment
- 8 Limit Nuts Fine Adjustment
- 8 Torque Limiter Adjustments
- 13 Programming Overview
- 13 Entering Programming Mode
- 13 Exiting Programming Mode
- 13 Programming Keystrokes
- 13 Left or Right Hand Operation
- 13 Dual Gate Enable
- 13 Auto Close Timer
- 14 Run Alarm and Pre-start Alarm
- 14 Maximum Open Direction Current Setting
- 14 Maximum Close Direction Current Setting
- 15 Entering Advanced Programming Mode
- 15 Maximum Run Time
- 15 Single Button Input Setup
- 15 Stagger Mode
- 15 Stagger Delay Time
- 16 Auxiliary Relay Mode
- 16 Reverse Delay Time
- 16 Brake Delay Time
- 16 Constant Pressure Mode
- 16 Shadow Loop Open Prevention
- 17 Reset Cycle Count
- 17 Maintenance Alert Trigger
- 17 Mid-travel Stop Position
- 17 Anti-tailgate Enable
- 17 Radio Enable
- 17 Antenna Installation
- 18 Radio Transmitter Learn
- 18 Radio Transmitter Delete
- 18 MGT Obstacle Transmitter Learn
- 18 MGT Obstacle Transmitter Delete
- 18 Motor Type Selection
- 26 Open Button
- 26 Close Button
- 26 Stop Button
- 26 Single Input
- 26 Fire Department Input
- 26 Open Input
- 26 Open Obstruction
- 26 Close Obstruction
- 26 Reverse Input
- 26 Open Loop
- 26 Reverse Loop
- 26 Shadow/reset Loop
- 26 Power-up Display
- 26 Idle Condition
- 26 Last Gate Position/Condition
- 26 Pre-start Delay
- 26 Reverse Delay
- 26 Run Timer
- 27 Entrapment
- 27 COMM LINK Connection Failure
- 27 MGT Obstacle Transmitter Trouble
- 27 Maximum Run Time Exceeded
- 28 How to Order Replacement Parts
- 28 Contacting Technical Support
- 28 Operator fails to start
- 28 Motor operates, but gate does not move
- 28 Motor sounds like it is working harder than normal
- 28 Limit switch getting out of time
- 28 (but no visible obstruction)
- 28 Gate staying open with automatic system
- 29 General
- 29 Lubrication
- 29 6-Month Preventative Maintenance