CyberPower BP144VL2U01 User Manual
SMART APP ONLINE
UPS SYSTEM
INSTALLATION AND OPERATION MANUAL
BP144VL2U01
SAVE THESE INSTRUCTIONS
Please read this manual and follow the instructions for installation and operation.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
©2019 Cyber Power Systems, Inc. All rights reserved.
1
K01-0000765-01
SAFETY INSTRUCTIONS
PRODUCT SAFETY
RISK OF ELECTRIC SHOCK
See Installation Instructions Before Connecting To The Supply.
Do Not Disconnect Battery Connector Under Load.
Batteries replaceable by SERVICE PERSONNEL.
BATTERY
Do not dispose of batteries in fire as the battery may explode.
Do not open or mutilate the battery, released electrolyte is harmful to the skin and eyes.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
I
TABLE OF CONTENTS
SAFETY INSTRUCTIONS................................................................................................................................ II
Product Safety.......................................................................................................................................................................... II
INTRODUCTION................................................................................................................................................ 1
UPS Extended Battery Modules......................................................................................................................................... 1
Unpacking Procedures........................................................................................................................................................... 1
Whats In The Box......................................................................................................................................................................2
EXTENDED BATTERY MODULE INSTALLATION........................................................................................ 3
Battery Module......................................................................................................................................................................... 3
Connection With UPS............................................................................................................................................................ 4
HARDWARE INSTALLATION......................................................................................................................... 7
Rackmount Installation For 4-Post Rack.........................................................................................................................7
Rackmount Installation For 2-Post Rack........................................................................................................................ 9
Vertical/Tower Installation................................................................................................................................................ 1 0
MAINTENANCE.............................................................................................................................................. 1 1
Battery Replacement........................................................................................................................................................... 1 1
TECHNICAL SPECIFICATIONS.................................................................................................................... 1 4
TROUBLESHOOTING.................................................................................................................................... 1 5
PRODUCT REGISTRATION........................................................................................................................... 1 5
LIMITED WARRANTY................................................................................................................................... 1 6
CONFORMANCE APPROVAL...................................................................................................................... 20
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
II
INTRODUCTION
UPS EXTENDED BATTERY MODULES
Extended Battery Modules (EBMs) from CyberPower (BP144VL2U01) increase battery runtimes
during power outages. Each rack/tower convertible EBM uses 2U of rack space and can be installed
in a tower form factor to match the UPS installation. The DC plug-and-play power connectors allow to
daisy-chain additional EBMs to a UPS system. EBMs compatible with Smart App Online UPS systems
also have a built-in battery charger, providing Fast Charge Technology to quickly restore the backup
power supply. Every CyberPower EBM has a three-year warranty.
UNPACKING PROCEDURES
Information, advice, help
The Extended Battery Module is very heavy, please handle with care. Wear safety shoes and use
a hydraulic equipment lift if one is available. At least two people are required for all handling
operations, including unpacking, lifting, and installation in a rack system. Do not use the lifting straps
to carry the unit around; they are provided to manually unpack the unit only.
USE LIFTING STRAPS TO REMOVE THE UNIT FROM THE BOX.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
1
INTRODUCTION CONT.
WHATS IN THE BOX
2
1
6
12
3
7
13
ITEM
4
8
14
CONTENT
9
15
16
QTY
ITEM
5
10
17
11
18
CONTENT
19
QTY
1
EBM
1
10
Registration warranty card
1
2
IEC320 C14 to IEC320 C14
power cord
1
11
Rackmount ears
2
3
NEMA L6-30P to IEC-320-C13
power cord
1
12
Flat head screws M5X7L
8
4
BM Cable
1
13
Pan head screws M5X12L
12
14
Pan head screws M5X6L
6
15
Plastic washers
8
16
Screw hole dust covers
18
17
Rubber pads
12
1
5
Rackmount left rail
6
Rackmount right rail
1
7
Left hanging bracket
1
8
Right hanging bracket
1
18
Stand
2
9
Installation and Operation Manual
1
19
Tie plate
1
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
2
EXTENDED BATTERY MODULE
INSTALLATION
BATTERY MODULE
1
3
4
5
BATTERY OUTPUT
144V
6
8
250V~
10A
DC BREAKER
IN
AC INPUT
(Charge Only)
BM
BATTERY INPUT : 144V
FUSE
+
-
OUT
ON
OFF
AC OUTPUT
2
7
BP144VL2U01
1. EBM DC Output Cable
Use this output cable to connect the EBM to a UPS or to the next EBM.
2. EBM DC Input Connector
Use this input connector to daisy chain the next EBM. Remove the connector cover for access.
3. BM Port
Connection port for built-in battery management module on UPS and Extended Battery Module.
4. On-board Replaceable Fuse Cover
Replaceable fuse is accessible from the rear panel.
Serviceable only by qualified personnel.
5. DC Breaker
Use the DC breaker to disconnect battery output.
6. AC Fast Charge Input (IEC320 C14)
Connect to a 208V, 30A, AC power source, or connect to the AC Fast Charge output from an
upstream EBM.
7. AC Fast Charge outlet (IEC320 C13)
Use this outlet to connect to the Fast Charge AC input of a downstream EBM.
8. AC Circuit Breaker
Provides overload and fault protection.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
3
EXTENDED BATTERY MODULE
INSTALLATION CONT.
CONNECTION WITH UPS
Scenario #1: UPS with one Extended Battery Module (EBM)
Plug into a wall receptacle
Step 1: Turn off the DC breaker on the EBM.
Step 2: Loosen the two screws to remove the battery cable retention bracket of the UPS.
Step 3: Use the output cable of the EBM to connect the EBM to the UPS.
1
OF
2
F
3
Step 4: Rotate the battery cable retention bracket and tighten the two screws to fix battery cable.
Step 5: Connect the BM/ENV port from UPS rear panel to BM port marked “IN” on the rear panel of
the Extended Battery Module using the provided BM cable. Refer to illustration below.
Step 6: Use a NEMA L6-30P to IEC-320-C13 power cord to plug AC input inlet of the battery module
into a wall receptacle.
Step 7: Turn on the DC breaker of the EBM.
4
5
6
7
ON
BM / ENV
PLUG INTO
A WALL
RECEPTACLE
IN
BM
OUT
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
4
EXTENDED BATTERY MODULE
INSTALLATION CONT.
CONNECTION WITH UPS CONT.
Scenario #2: UPS with multiple Extended Battery Modules (EBMs)
Plug into a wall receptacle
Step 1: Turn off the DC breaker on the EBM.
Step 2: Loosen the two screws to remove the battery cable retention bracket of the UPS.
Step 3: Use the output cable of the EBM to connect the EBM to the UPS.
1
OF
F
2
3
Step 4: Rotate the battery cable retention bracket and tighten the two screws to fix battery cable.
Step 5: Connect the BM/ENV port from UPS rear panel to BM port marked “IN” on the rear panel
of the Extended Battery Module using the provided BM cable, and then connect another BM cable
between BM port marked “OUT” and BM port marked “IN” of another Extended Battery Module.
Refer to illustration below.
Step 6: Use a NEMA L6-30P to IEC-320-C13 power cord to plug AC input inlet of the battery module
into a wall receptacle.
Step 7: Turn on the DC breaker of the EBM.
4
5
6
7
BM / ENV
IN
BM
PLUG INTO
A WALL
RECEPTACLE
ON
OUT
IN
BM
OUT
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
5
EXTENDED BATTERY MODULE
INSTALLATION CONT.
CONNECTION WITH UPS CONT.
Step 7: Turn on the DC breaker of the 2nd EBM.
Step 8: Set the EBM number to the respective setting to match the number of installed units. To do
this via the LCD control panel, go to the Configuration Menu, then scroll to the EBM Number setting,
select the appropriate number and Save the configuration. This operation can also be done via the
RMCARD web UI or via PowerPanel® Business Edition Agent software. Please see their respective
User Manual for instructions.
EXTENDED BATTERY MODULES CONFIGURATION
Extended Battery Modules can be configured by the user to display correct estimated battery runtimes.
1.Select “Main Menu” and press the “ENTER” button to activate the “Main Menu”.
2.Press the “UP” and “DOWN” buttons to select the “SET UP” ICON.
3.Press the “ENTER” button to enter the “SET UP” function.
4.Press the “UP” and “DOWN” buttons to scroll to the “External Batt” option.
5.Press the “ENTER” button to enter the “External Batt” option.
6.Press the “UP” and “DOWN” buttons to select the “Auto” or “Manual” option.
7.(a) Select “Auto” and press the “ENTER” buttons to activate the Auto detect function.
(b) Select “Manual” and press the “UP” and “Down” buttons to select the number of EBM installed
then press the “ENTER” button to set.
8.You may be prompted “Save Change?” to save the selection, if so press the “ENTER” button to
save the setting.
9.Press the “ESC” button to cancel or return to the previous SET UP menu.
SET UP ITEMS
Auto
External Batt
Manual
AVAILABLE SETTINGS
If UPS has EQM function, the UPS will Auto detect the
external batt number.
= [0] [1] [2] [3] [4] [5] [6] [7] [8] [9] [10]
Sets the actual EBM (extended battery modules) number
to get the correct estimated runtime.
DEFAULT
SETTINGS
None
0
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
6
HARDWARE INSTALLATION
CyberPower Extended Battery Module (EBM) can be installed in a rackmount or vertical/tower
orientation. This versatility is especially important to growing organizations with changing needs
that value having the option to position an EBM on the floor or in a rackmount system. Note that
the included rack mounting hardware is only compatible with square hole racks. Please follow the
instructions below for the respective mounting methods.
RACKMOUNT INSTALLATION FOR 4-POST RACK
Caution: Important Instructions
To prevent the risk of fire or electric shock, only use the supplied hardware to attach the mounting
brackets.
Step 1: Remove the dust covers
Remove ten dust covers from the screw holes as shown below.
Step 2: Rackmount ear & hanging bracket installation
Attach two rackmount ears to the EBM using eight black M5X7L flat head screws and tighten two hanging
brackets using six silver M5X6L pan head screws.
1
2
Step 3: Rackmount rail Installation
The mounting depth of the included rackmount rails can adjust from 20.5 in to 36 in (52 cm to 91.5 cm).
Select the proper holes in the rack for positioning the EBM in the rack. The EBM takes up 2 rack units: rack
hole positions 1 through 6.
Position the guide screws on the back of the rackmount rails into the rear rack square holes to temporarily
support the rails in place.
Step 4: Adjust rackmount rails to fit your rack
Adjust the rail depth to match your rack depth. Attach each rackmount rail to your rack with two black
M5X12L pan head screws and two plastic washers at the front of the rack (square holes 1 and 4 as shown
below). Secure each rail to the rear of the rack with two black M5X12L pan head screws and two plastic washers.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
7
HARDWARE INSTALLATION CONT.
RACKMOUNT INSTALLATION FOR 4-POST RACK CONT.
3 Rack mount ear
4
5
��
6
5
��
4
3
2
��
1
position 4
position 4
position 1
Rack mount rail
position 5
position 1
position 2
Step 5: Place and secure the EBM on the rails
Slide the hanging brackets on the EBM on to the rails mounted in the rack with the front of the unit facing
toward you. Secure the EBM to your rack with four black M5X12L pan head screws at the front of the rack
(square holes 2 and 5 as shown above).
NOTE: To slide the EBM out from the rack
The EBM will be secured by a safety locking mechanism midway of pulling it out of the rack. Use both
hands to hold the EBM and press the safety locking tab to pull the EBM out.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
8
HARDWARE INSTALLATION CONT.
RACKMOUNT INSTALLATION FOR 2-POST RACK
CAUTION! Due to the weight of this unit, it is strongly recommended to install it at the
bottom of the rack.
CAUTION! Prior to installing the unit, remove internal batteries to reduce the weight of the
unit. Refer to the battery replacement section in this user manual for instructions.
CAUTION! It is strongly recommend having 2-3 people assist during the installation process.
CAUTION! It is strongly recommended that the 2 post rack be bolted to the floor prior to the
installation of the EBM.
Step 1: Remove side dust covers
Remove seven dust covers from screw holes as shown below.
Step 2: Rackmount ears installation
Attach the included rackmount ears to the center holes on the sides of the EBM using eight black
M5X7L screws as shown below.
Step 3: Secure the EBM to the rack
Secure the EBM to your rack with four black M5X12L screws at the front of the rack (square holes 2
and 5 as shown below)
1
2
3
position 5
position 2
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
9
HARDWARE INSTALLATION CONT.
VERTICAL/TOWER INSTALLATION
Step 1: Adhere rubber pads
Adhere four circular rubber pads to the left hand side of the extended battery module. This will
become the bottom side. Insert the dust covers into the open screw holes on bottom.
Step 2: Attach the base stands and attach the dust covers
Stand the EBM on its side with the rubber pads facing down. If installing the EBM together with
a UPS, remove the four dust covers first and secure the tie plate between the UPS and the EBM
using four silver M5X6L pan head screws. Adhere four circular rubber pads to each tower stand
and screw on to the EBM and UPS using four silver M5X6L pan head screws for added stability as
shown below. Insert the dust covers into the open screw holes on top.
1
2
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
10
MAINTENANCE
Storage
To store your EBM for an extended period of time, cover and store it with the battery fully charged.
Recharge the battery every three months to ensure battery life.
Battery Replacement
Please read and follow the Safety Instructions before servicing the battery. Battery replacement
should be performed by trained personnel who are familiar with the procedures and safety
precautions. Make a note of the Replacement Battery part number.
Safety Precautions
Warning: High voltage – Risk of Electric Shock
Only use replacement batteries that are certified by Cyber Power Systems. Use of incorrect battery
type is an electrical hazard that could lead to explosion, fire, electric shock, or short circuit.
Batteries contain an electrical charge that can cause severe burns. Before servicing batteries, please
remove any conductive materials such as jewelry, chains, wrist watches, and rings.
Do not open or mutilate the batteries. Electrolyte fluid is harmful to the skin/eyes and may be toxic.
To avoid electric shock, turn off and unplug the EBM from the wall receptacle before servicing the battery.
Only use tools with insulated handles. Do not lay tools or metal parts on top of the EBM or battery terminals.
Replacement Batteries
Please refer to the front side of the EBM for the model number of the correct replacement batteries.
For battery procurement, go to www.CyberPowerSystems.com, or contact your local dealer.
When the UPS LCD displays Service Battery, use PowerPanel® Business Edition Agent software or
log on to the RMCARD to perform a runtime calibration to verify battery capacity is sufficient and
acceptable.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
11
MAINTENANCE CONT.
Battery Disposal
Do Not Discard
Batteries are considered hazardous waste and must be disposed of properly. Contact your local
government for more information about proper disposal and recycling of batteries. Do not dispose
of batteries in fire.
Cyber Power Systems encourages environmentally sound methods for disposal and recycling of its
UPS products.
Please dispose and/or recycle your UPS and batteries in accordance with local regulations.
BATTERY REPLACEMENT CONT.
Step 1: Remove the front panel.
Step 2: Unscrew and open the battery access door. Loosen the two screws on the battery connectors.
Step 3: Disconnect the battery and battery management module connector.
1
2
3
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
12
MAINTENANCE CONT.
BATTERY REPLACEMENT CONT.
Step 4: Unscrew the battery retention bracket and then open it
Step 5: Pull the battery trays out slowly and then put the new battery trays into the compartment.
Step 6 : Assemble battery retention cover and the battery connectors. Tighten the battery access door.
Step 7: Install the front panels. Execute a battery test via the LCD control panel. To do this go to
the Main Menu and select the Diagnostics Icon, then select Battery Test and Activate. After Battery
test, go back to the Main Menu then select the Set UP icon, then select Batt Install Date to set the
battery installation date. This operation can also be done via PowerPanel® Business Edition Agent
or the RMCARD web interface. Please see their respective User Manuals for detailed instructions.
4
5
6
7
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
13
TECHNICAL SPECIFICATIONS
MODELS
BP144VL2U01
CONFIGURATION
AC Input Voltage
180~280 V
DC Output Voltage
144 Vdc
DC Output Current
55 A
PHYSICAL
Dimensions
L x W x H = 28.3 x 17.05 x 3.4 in (7.2 x 43.3 x 8.65 cm)
Net Weight
96.8 lb (44 Kg)
BATTERY
Specifications
(12) 12 V/9 Ah
Replacement Battery Cartridge (2) RB1290X6D
Recharge Time 0-90% (Typical) 4 hours
Hot-Swappable
Yes
Built-in Charger
Yes
ENVIRONMENT
Operating Temperature
32 °F to 104 °F ( 0 °C to 40 °C)
Operating Relative Humidity
0 to 90% Non-Condensing
SAFETY
Conformance Approvals
CE, UL1778, FCC part 15 Class A
RoHS
RoHS Compliant
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
14
TROUBLESHOOTING
PROBLEM
POSSIBLE CAUSE
SOLUTION
WARNING
BAT Disconnected
No battery power is being detected
by the UPS.
Battery Failure
UPS has failed a Battery Test.
Replace Battery
Battery will soon need to be
replaced due to insufficient runtime.
Check the battery connector and the
battery breaker.
Check the battery connector and
the battery breaker.
Contact technical support to replace
battery if under the warranty period.
Install new batteries, execute battery
test, and reset the replace battery date.
Perform a runtime calibration to
verify battery capacity is sufficient
and acceptable.
Service Battery
The Battery Replacement Date has
reached the recommended 3 year
maintenance period.
If batteries have been recently
replaced, then reset the Battery
Replacement Date using PowerPanel®
Business Edition Agent software,
RMCARD web interface or through
the LCD control panel on the UPS
(See LCD Configuration Settings).
FAULT
Over Charge
Battery is overcharged.
Charger Failure
Charger has failed.
Remove the battery connector and
check charger voltage.
Contact CyberPower for repair.
PRODUCT REGISTRATION
CyberPower requests that you complete and return the Warranty Registration Card enclosed with
the Product or register the Product at its website (www.cyberpowersystems.com/registration) to
establish that you are the Initial Customer of the Product, and therefore entitled coverage under
the Limited Warranty and the Connected Equipment Guarantee. (Registration is not required for
coverage, but note: if you do not register your purchase, you will be required to provide proof
of purchase.)
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
15
LIMITED WARRANTY
Read the following terms and conditions carefully before using the CyberPower BP144VL2U01.
By using the Product you consent to be bound by and become a party to the terms and conditions
of this Limited Warranty (together referred to as the “Warranty”). If you do not agree to the terms
and conditions of this Warranty, you should return the Product for a full refund prior to using it.
Who is Providing this Warranty?
CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product under normal use and
conditions.
What is the Period of Coverage?
This warranty covers the Product for three years.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
How Do You Get Warranty Service?
1. Before contacting CyberPower, identify Your Product model number, and the Purchase Date.
2. Email us at tech@cpsww.com or Call us at (877) 297-6937.
3. If your product requires warranty service you must provide a copy of your dated purchase
receipt or invoice.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
16
LIMITED WARRANTY CONT.
How Do You Open A Warranty Claim?
1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave.
E., STE 400, Shakopee, MN 55379, or send us an e-mail message to claims@cpsww.com for
instructions, within 10 days of the occurrence.
2. When you contact CyberPower, identify the Product, the Purchase Date, and Request a Claim Number.
3. You must provide a dated purchase receipt (or other proof of the original purchase) for the
Cyber Power unit.
4. Pack and ship the product to CyberPower and all claim forms that CyberPower provides to you.
Show the Claim Number on the shipping label or include it with the product. You must prepay all
shipping costs, you are responsible for packaging and shipment, and you must pay the cost of
the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at
CyberPower's expense, or, if CyberPower is unable to or decides not to repair or replace the
Product (if defective) within a reasonable time, CyberPower will refund to you the full purchase
price you paid for the Product (purchase receipt showing price paid is required).
Who Pays For Shipping?
We pay when we send items to you; you pay when you send items to us.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
17
LIMITED WARRANTY CONT.
What Are Some Examples Of What This Warranty Does Not Cover?
1. This Warranty does not cover any software that was damaged or needs to be replaced due to
the failure of the Product or any data that is lost as a result of the failure or the restoration of
data or records, or the reinstallation of software.
2. This Warranty does not cover or apply to: misuse, modification, operation or storage outside
environmental limits of the Product or the equipment connected to it, nor for damage while in
transit or in storage, nor if there has been improper operation or maintenance, or use with items
not designed or intended for use with the Product, such as laser printers, appliances, aquariums,
medical or life support devices, etc.
What Other Limitations Apply?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
1. This Warranty does not apply unless the Product and the equipment that was connected to it
were connected to properly wired and grounded outlets (including compliance with electrical
and safety codes of the most current electrical code), without the use of any adapters or
other connectors.
2. The Product must have been plugged directly into the power source and the equipment
connected to the Product must be directly connected to the Product and not “daisy-chained”
together in serial fashion with any extension cords, another Product or device similar to the
Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
3. The Product must have been used properly in a suitable and proper environment and in
conformance with any license, instruction manual, or warnings provided with the Product and
the equipment connected to it.
4. The Product must have been used at all times within the limitations on the Product’s VA capacity.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than
1ms) voltage spikes or impulses from lightning or other power transients. If it can be shown that
a voltage spike lasting longer than 1ms has occurred, the occurrence will be deemed outside the
rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or
Undertake Any Liability in Any Event for Any of the Following:
1. Loss of or damage to data, records, or software or the restoration of data or records, or the
reinstallation of software.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
18
LIMITED WARRANTY CONT.
What Other Limitations Apply? Cont.
2. Damage from causes other than AC Power Line Transients, spikes, or surges on properly
installed, grounded and code-compliant 120 volt power lines in the United States and Canada;
transients, surges or spikes on standard telephone land lines, PBX telephone equipment lines
or Base 10T Ethernetlines, when properly installed and connected. (This exclusion applies,
for example, to fluctuations in data transmission or reception, by CATV or RF transmission or
fluctuations, or by transients in such transmission.)
3. Damage from any circumstance described as excluded above with respect to the Product.
4. Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse,
misuse or alteration of the product.
5. CyberPower excludes any liability for personal injury under the Limited Warranty. CyberPower
excludes any liability for direct, indirect, special, incidental or consequential damages, whether
for damage to or loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited
agreement of CyberPower to provide certain warranty benefits, loss of profits, business
interruption, or loss of information or data. NOTE: Some States or Provinces do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation may not
apply to you.
6. The Product is not for use in high-risk activities or with aquariums. The Product is not designed
or intended for use in hazardous environments requiring fail-safe performance, or for use in any
circumstance in which the failure of the Product could lead directly to death, personal injury,
or severe physical or property damage, or that would affect operation or safety of any medical
or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any
express or implied warranty of fitness for High Risk Activities or with aquariums. CyberPower
does not authorize use of any Product in any High Risk Activities or with Aquariums. ANY SUCH
USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
Where Can I Get More Information?
The application of the United Nations Convention of Contracts for the International Sale of Goods is
expressly excluded.
CyberPower is the warrantor under this Limited Warranty.
For further information please feel free to contact CyberPower at
Cyber Power Systems (USA), Inc. | 4241 12th Ave E., STE 400, Shakopee, MN 55379
(877) 297-6937 | claims@cpsww.com
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
19
CONFORMANCE APPROVAL
FCC NOTICE
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference that may cause undesired operation.
WARNING!! This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference when the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case
the user will be required to correct the interference at his own expense. Shielded signal cables must
be used with this product to ensure compliance with the Class A FCC limits.
The Class A digital apparatus meets all requirements of the Canadian Interference-Causing
Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel
brouilleur du Canada.
This document is believed to be accurate, but CyberPower reserves the right to change or correct
the contents and does not assume any responsibility for omissions or errors.
Need Additional Help?
See Operation and Installation Manual provided and also available to download at
www.CyberPowerSystems.com Still Need Help? Please contact our Tech Support department with
installation, troubleshooting, or general product questions.
CyberPower Technical Support
Phone: 1-877-297-6937
Email: tech@cpsww.com
Web: www.CyberPowerSystems.com
Address: 4241 12th Avenue E., Suite 400, Shakopee, MN 55379, USA
Hours of Operation:
Monday – Friday, 7:00am – 6:00pm (CST)
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
20
Cyber Power Systems, Inc. | www.CyberPowerSystems.com
For USA and Canada | 4241 12th Ave East, Suite 400, Shakopee, MN 55379 | Toll-free: 877.297.6937
For all other regions | Please visit our website for local contact information.
Copyright © 2019 Cyber Power Systems, Inc. All rights reserved.
©2019 Cyber Power Systems (USA), Inc. All rights reserved. All other trademarks are the property of their respective owners.
21