CyberPower PDU83105 User Manual
3-Phase
Power Distribution Unit
USER'S MANUAL
Copyright © 2019 Cyber Power Systems, Inc. All rights reserved.
K01-0000699-00
Table of Contents
Model List..................................................................1
Input Plug Type........................................................1
Safety Precautions...................................................2
Introduction..............................................................3
Package Contents....................................................................3
Product Features......................................................................4
Switched Metered by Outlet/Switched
(16/20A Models)............................................................................4
Technical Specifications..............................................................5
Switched Metered by Outlet/Switched
(30/32/50/60A Models).............................................................6
Technical Specifications..............................................................7
Monitored (16/20A Models).......................................................9
Technical Specifications..............................................................10
Monitored (30/32/50/60A Models).......................................1 1
Technical Specifications..............................................................12
Basic (16/20A Models).................................................................14
Technical Specifications..............................................................15
Basic (32/50A Models)................................................................16
Technical Specifications..............................................................17
Installation Guide.....................................................18
PDU Installation.......................................................................18
Power Cord Direction Change - For Selected
PDU Models...............................................................................22
Locking Power Cord - For IEC Type PDU......................23
Output Power Cord......................................................................23
Electrical Installation..............................................................23
Network Installation...............................................................24
Operation...................................................................25
Remote Management............................................................25
Local Management.................................................................25
LED Indicators.........................................................................26
Environmental Monitoring (optional).............................26
Device Reset............................................................................26
Unattended/Automatic Shutdown..................................26
Firmware Upgrade...................................................27
Troubleshooting.......................................................31
Conformance Approvals..........................................31
FCC Warning............................................................................31
Customer Service & Warranty................................32
Product Registration.............................................................32
CyberPower International...................................................32
Limited Warranty...................................................................32
Appendix A-Hyper Terminal...................................33
Appendix B-Power Device Network Utility..........33
Overview....................................................................................33
Installation.................................................................................33
Launch Program.....................................................................35
Getting Started.......................................................................35
Advanced Settings................................................................36
Appendix C-PDU Daisy-Chain Function................38
Model List
Switched Metered by Outlet Series
PDU83101
PDU83102
PDU83103
PDU83104
PDU83105
PDU83106
PDU83107
PDU83108
PDU831 1 1
PDU83401
PDU83402
PDU83403
PDU43105
PDU43106
PDU43107
PDU43108
PDU431 1 1
PDU43401
PDU43402
PDU43403
PDU33106
PDU33107
PDU33108
PDU33109
PDU331 1 0
PDU331 1 1
PDU331 1 2
PDU33121
PDU33401
PDU33402
PDU13103
PDU13104
PDU13401
PDU13402
Switched Series
PDU43101
PDU43102
PDU43103
PDU43104
Monitored Series
PDU33101
PDU33102
PDU33103
PDU33104
PDU33105
Basic Series
PDU13101
PDU13102
Input Plug Type
NEMA L21-20P
NEMA L21-30P
NEMA L15-20P
NEMA L15-30P
IEC 309 16A
3P+N+E
IEC 309 32A
3P+N+E
IEC 309 30A
3P+E
IEC 309 60A
3P+E
Hubbell
CS8365C
IEC 309 20A
3P+N+E
IEC 309 60A
3P+N+E
1
Safety Precautions
Read the following before installing or operating the Power
Distribution Units (PDU):
•
•
•
•
•
•
•
Make sure to disconnect all power supply cords before attempting
to service or remove this unit.
As for overcurrent protection, please be noted that all PDUs with
an input current rating greater than 20A are equipped with flushmount branch circuit breakers according to bank numbers.
Use only the supplied hardware to attach the mounting brackets.
The PDU must be plugged into a three-wire, grounded outlet
on a circuit that is protected by a fuse or circuit breaker. For
20A PDU series, please use a 20A circuit protector. For 30A
PDU series, please use a 30A circuit protector. For 50A PDU
series, please use a 50A circuit protector. For 60A PDU series,
please use a 60A circuit protector. Connection to any other
type of power outlet may result in a shock hazard.
Do not use extension cords or adapters with this PDU.
Never install a PDU or associated wiring or equipment during a
lightning storm.
Ensure that the power cord, plug, and socket are in good
condition.
CAUTION!!
To prevent the risk of fire or electrocution, this PDU should be installed
in a temperature and humidity controlled indoor area free of conductive
contaminants. Do not install this PDU where excessive moisture or heat
is present.
WARNING!!
This product can expose you to harmful chemicals, including Styrene,
which is known to the State of California to cause cancer; and
Bisphenol-A, which is known to the State of California to cause birth
defects or other reproductive harm.
For more information, please visit www.P65Warnings.ca.gov.
2
Introduction
Package Contents
PDU
Mounting Brackets
with 6 (M4x5) Screws
6 (M5 x 12) Rack Mounting
Screws/Washers
6 (M3 x 6)
Cord Retention Tray
Mounting Screws
Cord Retention Tray
Cable Ties:
Qty. 40 (18 to 27 outlet PDU)
Qty. 50 (30 to 36 outlet PDU)
Qty. 70 (42 to 48 outlet PDU)
Users
Manu
al
RJ45/DB9 Serial Port
Connection Cable
Check
Registration
PowerPanel
Card
Management Software
User's Manual, Registration Card,
and Software Download Card
Before using, please check to ensure the package contains all the
items shown above. If there are missing parts, please contact your local
CyberPower technical support team for assistance.
3
Product Features:
Switched Metered by Outlet/Switched
(16/20A Models)
PDU83101
L21-20P
L21-20P
1
1
2
2
3
3
L1-L2
L1
4
4
5
5
6
7
7
L2
L2-L3
M
6
8
8
9
9
10
10
Enter
Select
Enter
Select
- Normal
- Warning
- Critical
- Normal
- Warning
- Critical
Link
Tx/Rx
Link
Out
In / ENV
Out
In / ENV
Serial
USB
Serial
USB
11
11
12
12
13
13
L3-L1
L3
14
14
B
B
15
15
16
16
17
17
L1-L2
L1
18
18
19
19
20
20
21
21
22
22
23
23
L2-L3
L2
24
24
B
B
25
25
26
26
27
27
L3-L1
L3
28
28
29
29
30
30
4
F
G
Tx/Rx
C
C
C
C
E
E
H
H
J
I
F
G
J
I
B
B
D
L
K
D
L
K
C
C
A
A
Rear Panel
IEC Type
NEMA Type
PDU83102
Front/Rear Panel Description
M
M
Product Features:
Switched Metered by Outlet/Switched
(16/20A Models)
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. Outlet Indicator (Switched Series only) - Indicates if the
outlet is providing power to connected equipment.
C. AC Output Receptacles - Provides power for connected
equipment.
D. Status Indicator - Indicates the condition of the PDU (eg.
load or environment status)
E. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
F. Ethernet Port – Used to connect PDU to the network.
G. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
H. USB Port - Used to upgrade the firmware via a flash drive.
I. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.
J. Daisy Chain (Out) Port – Used for chaining to next PDU..
K. Select Button - Used to control the LCD screen and toggle
through the available information options
L. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
M. Bracket Screw Hole - Used to secure the Mounting Pegs (preinstalled) or Mounting Brackets.
Technical Specifications
Model Name
PDU83101
PDU43101
PDU83102
PDU43102
PDU83103
PDU43103
PDU83111
PDU43111
PDU83401
PDU43401
Input
Nominal Voltage
208V
200-240V
Frequency
346-415V
50/60Hz
Maximum Input Current
16A UL (Derated)
Plug Type
NEMA L21-20P
NEMA
L15-20P
Power Cord Type
SR (12 AWG)
Power Cord Length
10 ft / 3.05 m
16A CE
IEC 309
20A Red
(3P+N+E)
IEC 309
16A Red
(3P+N+E)
Output
Nominal Voltage
120V
200-240V
Maximum Output Current
Outlet Type
16A UL (Derated)
(30) NEMA
5-20R
16A CE
(24) IEC 320 C13 (6) IEC 320 C19
Outlet Number
30
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480ft / 3500m
23oF to 140oF / -5oC to 60oC
23oF to 131oF /
-5oC to 55oC
Safety Approvals
Certifications
UL60950-1, UL62368-1. FCC Class A.
* All specifications are subject to change without notice
5
CB, CE
EN55032/24
Class A
Product Features:
Switched Metered by Outlet/Switched
(30/32/50/60A Models)
Front/Rear Panel Description
BANK 1 (20A)
B
BANK 2 (20A)
B
1
2
3
4
BANK 1 L1-L2
5
6
N
7
8
BANK 2 L2-L3
9
10
Enter
Select
- Normal
- Warning
- Critical
E
M
L
Link
Tx/Rx
Out
In / ENV
G
H
Serial
USB
I
K
J
BANK 3 (20A)
D
A
L21-30P
B
Rear Panel
IEC Type
N
C
F
11
12
13
14
BANK 3 L3-L1
C
15
16
17
18
BANK 1 L1-L2
19
20
D
21
22
23
24
BANK 2 L2-L3
C
25
26
N
27
28
BANK 3 L3-L1
29
30
6
Product Features:
Switched Metered by Outlet/Switched
(30/32/50/60A Models)
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. Circuit Breaker – Provides overload protection.
C. Outlet Indicator (switched series only) – Indicates if the
outlet is providing power to connected equipment.
D. AC Output Receptacles - Provides power for connected
equipment.
E. Status Indicator - Indicates the condition of the PDU (eg.
load or environment status).
F. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
G. Ethernet Port – Used to connect PDU to the network.
H. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
I. USB Port - Used to upgrade the firmware via a flash drive.
J. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.Select Button
- Used to control the LCD screen and toggle through the
available information options.
K. Daisy Chain (Out) Port – Used for chaining to next PDU.
L. Select Button - Used to control the LCD screen and toggle
through the available information options.
M. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
N. Bracket Screw Hole - Used to secure the Mounting Pegs
(pre-installed) or Mounting Brackets.
Technical Specifications
PDU83104
PDU43104
Model Name
PDU83105
PDU43105
PDU83106
PDU43106
Input
Nominal Voltage
200-240V
Frequency
50/60Hz
Maximum Input Current
Plug Type
24A UL (Derated)
NEMA L21-30P
NEMA L15-30P
Power Cord Type
SR (10 AWG)
Power Cord Length
10 ft/3.05 m
IEC 309 30A Blue
(3P+E)
Output
Nominal Voltage
200-240V
Maximum Output Current
Outlet Type
24A UL (Derated)
(24) IEC 320 C13 (6) IEC 320 C19
Outlet Number
30
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480 ft/3500 m
23oF to 140oF / -5oC to 60oC
23oF to 131oF /
-5oC to 55oC
Safety Approvals
Certifications
UL60950-1, UL62368-1. FCC Class A
* All specifications are subject to change without notice.
7
Product Features:
Switched Metered by Outlet/Switched
(30/32/50/60A Models)
Technical Specifications
PDU83107
PDU43107
Model Name
PDU83108
PDU43108
Input
Nominal Voltage
200-240V
Frequency
50/60Hz
Maximum Input Current
35A UL (Derated)
Plug Type
Hubbell CS8365C
IEC 309 60A Blue (3P+E)
Power Cord Type
SR (8 AWG)
Power Cord Length
10 ft/3.05 m
Output
Nominal Voltage
200-240V
Maximum Output Current
35A UL (Derated)
Outlet Type
(24) IEC 320 C13 (6) IEC 320 C19
Outlet Number
30
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480 ft/3500 m
23oF to 140oF / -5oC to 60oC
23oF to 131oF / -5oC to 55oC
Safety Approvals
Certifications
UL60950-1, UL62368-1. FCC Class A
* All specifications are subject to change without notice.
Technical Specifications
PDU83402
PDU43402
Model Name
PDU83403
PDU43403
Input
Nominal Voltage
346-415 V
Frequency
50/60Hz
Maximum Input Current
Plug Type
32A CE
35A CE
IEC 309 32A Red (3P+N+E)
IEC-309 60A Red (3P+N+E)
SR (10 AWG)
SR (8 AWG)
Power Cord Type
Power Cord Length
10 ft/3.05 m
Output
Nominal Voltage
Maximum Output Current
Outlet Type
200-240V
32A CE
35A CE
(24) IEC 320 C13 (6) IEC 320 C19
Outlet Number
30
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
11480 ft/3500 m
23oF to 131oF / -5oC to 55oC
Temperature
Safety Approvals
Certifications
CB, CE EN55032/24 Class A
* All specifications are subject to change without notice.
8
Product Features:
Monitored (16/20A Models)
PDU33101
IEC309 16A 3P+N+E
L21-20P
1
2
3
4
5
6
7
8
9
10
11
12
Enter
Select
- Normal
- Warning
- Critical
Enter
Select
- Normal
- Warning
- Critical
Tx/Rx
Link
Link
Tx/Rx
In / ENV
Out
Out
In / ENV
Serial
USB
G
I
H
Serial
USB
G
I
H
13
14
15
16
17
B
18
19
B
20
21
22
23
24
25
26
27
28
29
B
30
B
31
L
32
33
34
35
36
9
E
F
E
F
C
D
K
J
C
K
J
A
A
Rear Panel
IEC Type
NEMA Type
PDU33401
Front/Rear Panel Description
L
B
B
L
D
Product Features:
Monitored (16/20A Models)
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. AC Output Receptacles - Provides power for connected
equipment.
C. Status Indicator - Indicates the condition of the PDU (eg.
load or environment status).
D. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
E. Ethernet Port – Used to connect PDU to the network.
F. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
G. USB Port - Used to upgrade the firmware via a flash drive.
H. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.
I. Daisy Chain (Out) Port – Used for chaining to next PDU.
J. Select Button - Used to control the LCD screen and toggle
through the available information options.
K. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
L. Bracket Screw Hole - Used to secure the Mounting Pegs (preinstalled) or Mounting Brackets.
Technical Specifications
PDU33101
Model Name
PDU33121
PDU33102
PDU33104
PDU33401
PDU33103
Input
Nominal Voltage
208V
200-240V
Frequency
346-415 V
50/60Hz
Maximum Input Current
16A UL (Derated)
16A UL (Derated)
Plug Type
NEMA L21-20P
16A CE
IEC 309 16/20A Red
(3P+N+E)
NEMA L15-20P
Power Cord Type
SR (12 AWG)
Power Cord Length
10 ft/3.05 m
Output
120V
Nominal Voltage
120/208V
200-240V
120/208V
Maximum Output Current
16A UL (Derated)
16A UL (Derated)
16A CE
(36)NEMA 5-20R
Outlet Type
(24) NEMA 5-20R (6)
NEMA L6-20R
(30) IEC 320 C13 (6) IEC 320 C19
(2) NEMA 5-20R (36)
IEC 320 C13 (6) IEC 320
C19
36
30
Outlet Number
36
44
Management and Communications
Multifunction LCD Readout
Software
Voltage, Frequency, Load, Current, HW/FW Version, Network Information
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480 ft/3500 m
23oF to 140oF / -5oC to 60oC
23oF to 131oF /
-5oC to 55oC
Safety Approvals
Certifications
UL 60950-1, UL62368-1, FCC Class A
* All specifications are subject to change without notice.
10
UL 60950-1, UL62368-1,
FCC Class A
CB, CE EN55032/24
Class A
Product Features:
Monitored (30/32/50/60A Models)
Enter
Select
- Normal
- Warning
- Critical
Link
Tx/Rx
Out
In / ENV
H
Serial
USB
BANK 2 (20A)
BANK 3 (20A)
B
BANK 1 (20A)
B
F
G
J
I
M
D
L
K
A
IEC 309 30A 3P+E
B
Rear Panel
PDU33107
Front/Rear Panel Description
IEC Type
M
C
E
C
C
M
11
Product Features:
Monitored (30/32/50/60A Models)
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. Circuit Breaker – Provides overload protection.
C. AC Output Receptacles - Provides power for connected
equipment.
D. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
E. Multifunction LCD Readout - Displays various PDU
information such as power and load condition.
F. Ethernet Port – Used to connect PDU to the network.
G. ENVIROSENSOR/ Daisy Chain (In) Port (RJ45 modular port)
– Used for ENVIROSENSOR or chaining to previous PDU.
H. USB Port - Used to upgrade the firmware via a flash drive.
I. Serial Port (RJ45 modular port) - Used to connect to a PC
and control the PDU locally via SSH/Telnet.
J. Daisy Chain (Out) Port – Used for chaining to next PDU.
K. Select Button - Used to control the LCD screen and toggle
through the available information options.
L. Enter Button - Used to choose selected items, enter to next
level menu or return to previous menu.
M. Bracket Screw Hole - Used to secure the Mounting Pegs
(pre-installed) or Mounting Brackets.
Technical Specifications
PDU33108
Model Name
PDU33105
PDU33106
PDU33107
PDU33109
Input
Nominal Voltage
208V
200-240V
Frequency
50/60Hz
Maximum Input Current
Plug Type
35A UL
(Derated)
24A UL (Derated)
NEMA L21-30P
Power Cord Type
IEC 309 30A
Blue (3P+E)
NEMA L15-30P
Hubbell
CS8365C
SR (10 AWG)
Power Cord Length
SR (8 AWG)
10 ft/3.05 m
Output
Nominal Voltage
120/208V
Maximum Output Current
Outlet Type
200-240V
35A UL
(Derated)
24A UL (Derated)
(36) IEC 320
C13 (6) IEC 320
C19
(2) NEMA
(36) IEC 320
(42) IEC 320
5-20R (36) IEC
C13 (6) IEC 320 C13 (6) IEC 320
320 C13 (6) IEC
(42) IEC 320
C19
C19
320 C19
C13 (6) IEC 320
C19
Outlet Number
44
42
42
48
48
Management and Communications
Multifunction LCD Readout Voltage, Frequency, Load, Current, HW/FW Version, Network Information
Software
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480 ft/3500 m
23oF to 140oF / -5oC to 60oC
23oF to 131oF /
-5oC to 55oC
23oF to 140oF /
-5oC to 60oC
Safety Approvals
Certifications
UL60950-1, UL62368-1. FCC Class A
* All specifications are subject to change without notice.
12
Product Features:
Monitered (30/32/50/60A Models)
Technical Specifications
PDU33110
Model Name
PDU33111
PDU33402
PDU33112
Input
Nominal Voltage
200-240V
346-415V
Frequency
50/60Hz
48A UL (Derated)
Maximum Input Current
48A UL (Derated)
32A CE
35A UL (Derated)
IEC 309 60A Blue
(3P+E)
Plug Type
IEC 309 32A Red
(3P+N+E)
SR (6 AWG)
Power Cord Type
SR (6 AWG)
SR (10 AWG)
SR (8 AWG)
Power Cord Length
10 ft/3.05 m
10 ft/3.05 m
Output
Nominal Voltage
200-240V
48A UL (Derated)
Maximum Output Current
48A UL (Derated)
32A CE
35A UL (Derated)
(6) IEC 320 C13 (12) IEC 320 C19
Outlet Type
(30) IEC 320 C13
(6) IEC 320 C19
(30)IEC 320 C13
(42) IEC 320 C13 (6) IEC 320 C19
18
Outlet Number
30
36
48
Management and Communications
Multifunction LCD Readout
Software
Voltage, Frequency, Load, Current, HW/FW Version, Network Information
PowerPanel® Business Edition
Networking
Yes
Serial Port
RJ45
Sensor Capable
Optional
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
11480 ft/3500 m
23oF to 131oF / -5oC to 55oC
Temperature
Safety Approvals
Certifications
UL 60950-1, UL62368-1, FCC Class A
* All specifications are subject to change without notice.
13
CB, CE EN55032/24 Class A
Product Features:
Basic (16/20A Models)
Front/Rear Panel Description
NEMA Type
IEC Type
Rear Panel
A
C
B
C
B
B
C
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. AC Output Receptacles - Provides power for connected
equipment.
C. Bracket Screw Hole - Used to secure the Mounting Pegs (preinstalled) or Mounting Brackets.
14
Product Features:
Basic (16/20A Models)
Technical Specifications
PDU13101
Model Name
PDU13401
PDU13102
PDU13103
Input
208V
208V
Nominal Voltage
346-415V
200-240V
Frequency
50/60Hz
Maximum Input Current
Plug Type
16A UL (Derated)
16A CE
NEMA L21-20P
IEC 309 16A Red
(3P+N+E)
Power Cord Type
SR (12 AWG)
Power Cord Length
10 ft/ 3.05 m
Output
120V
Nominal Voltage
200-240 V
120/208V
200-240V
Maximum Output Current
16A UL (Derated)
16A CE
(42)NEMA 5-20R
(21) NEMA 5-20R
(6) NEMA L6-20R
Outlet Type
(36) IEC 320 C13
(6) IEC 320 C19
(36) IEC 320 C13
(6) IEC 320 C19
42
Outlet Number
27
42
42
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480 ft/ 3500 m
o
o
o
23 F to 140 F / -5 C to 60oC
23oF to 131oF / -5oC to 55oC
UL 60950-1, FCC Class A
CB, CE EN55032/24 Class A
Safety Approvals
Certifications
* All specifications are subject to change without notice.
15
Product Features:
Basic (32/50A Models)
Front/Rear Panel Description
IEC Type
Rear Panel
CS8365C
A
D
BANK 1 (20A)
B
C
D
BANK 2 (20A)
B
C
BANK 3 (20A)
B
C
D
A. AC Inlet/ AC Power Cord - Used to connect PDU to utility
power or UPS.
B. Circuit Breaker – Provides overload protection.
C. AC Output Receptacles - Provides power for connected
equipment.
D. Bracket Screw Hole - Used to secure the Mounting Pegs (preinstalled) or Mounting Brackets.
16
Product Features:
Basic (32/50A Models)
Technical Specifications
Model Name
PDU13104
PDU13402
Input
Nominal Voltage
200-240V
346-415V
Frequency
Maximum Input Current
Plug Type
Power Cord Type
50/60Hz
35A UL (Derated)
32A CE
Hubbell CS8365C
IEC 309 32A Red
(3P+N+E)
SR (8 AWG)
Power Cord Length
SR (10 AWG)
10 ft/ 3.05 m
Output
Nominal Voltage
200-240V
Maximum Output Current
35A UL (Derated)
32A CE
Outlet Type
(30) IEC 320 C13
(6) IEC 320 C19
(36) IEC 320 C13
(6) IEC 320 C19
36
42
Outlet Number
Physical
Dimensions (H x W x D)
70.5" x 2.2" x 2.2" / 1790mm x 56mm x 55mm
Environmental
Humidity
0 to 95% Non-condensing
Altitude
Temperature
11480 ft/ 3500 m
23oF to 140oF / -5oC to 60oC
23oF to 131oF / -5oC to 55oC
UL 60950-1, FCC Class A
CB,
CE E55032/
24 Class A
Safety Approvals
Certifications
* All specifications are subject to change without notice.
17
Installation Guide
PDU Installation
Step 1. PDU Mounting
Align the Keyhole Mounts to the Keyhole Slots on the rack.
Insert and slide down to lock firmly into the place.
If there is no Keyhole Slot on your rack, please choose from the
following methods that is best for your rack deployment to secure
the PDU.
Use the supplied Washers and Rack Mounting Screws to attach the
Mounting Brackets to your existing rack system.
Align the Keyhole Mounts to the Keyhole Slots on the Mounting
Brackets. Insert and slide down to lock firmly into the place.
Method 1
18
Installation Guide
Method 2
19
Installation Guide
Method 3
20
Installation Guide
Step 2. Cord Retention Tray Installation (optional)
Adjust the length of the Cord Retention Tray till the screw
hole on the Tray and PDU are aligned. Attach the Cord
Retention Tray to the PDU with the supplied Cord Retention
Tray Mounting Screws. Tighten the Cord Retention Tray with
the screw on it.
Use the provided Cable Ties to fasten each cord to the Cord
Retention Tray.
Note: If the PDUs are intended to install in a high temperature
environment, please use the Power Cords that could sustain
high temperature operation.
21
Installation Guide
Power Cord Direction Change - For Selected PDU
Models
Step 1. Remove the four screws from the power cord cover. Keep
the screws for later use.
Step 2. Rotate the power cord cover.
Step 3. Install the power cord cover back to the PDU with the four
screws.
22
Installation Guide
Locking Power Cord - For IEC Type PDU
Output Power Cord
Step 1. Align and insert the Cable Tie from the upper side of the
Fixed Stand and fasten it as shown below.
Electrical Installation
Step 1. Receptacle evaluation
Ensure that the plug type of your PDU unit matches the
receptacle type that you are using. Plug type may vary by
model.
The PDU must be plugged into a three-wire, grounded receptacle
only. The receptacle must also be connected to an appropriate branch
circuit/main with fuse or circuit breaker protection. Connection to any
other type of receptacle may result in a shock hazard.
Step 2. Plug the PDU into a compatible AC power source.
Step 3. Attach equipment
It is extremely important not to exceed the PDUs maximum
current load (as outlined in the Specifications section). In
order to determine your total load, simply use the LCD screen
on the front of the PDU to monitor the load being attached.
23
Installation Guide
Network Installation
Step 1 – Network Connection
Using an Ethernet cable, attach one end to the Ethernet
port on the front of the PDU, and the other end to a
network port.
Step 2 – Establish the PDU IP address
Assigning an IP address to the CyberPower PDU requires
the user to have an available IP address that is valid on the
respective network. If an available IP address is unknown,
contact the network administrator to obtain one.
DHCP is enabled by factory default. If the PDU does not receive
an IP address from the network's DHCP server, it will default to
192.168.20.177.
There are multiple methods for setting up the IP address on the
PDU. Please follow the instructions below for the method that is
appropriate for your application.
Please make sure the PDU is powered on during this process.
Option 1: Power Device Network Utility (recommended)
1. Download and install the Power Device Network Utility software
from www.cyberpower.com.
2. Open the Power Device Network Utility and select the PDU device
from the list and select Tools > Device Setup from the menu.
3. Configure the IP Address, Subnet Mask, and Gateway Address to
match your network settings.
4. Enter the user name and password of the PDU device at the
Authentication menu.
Note: The default username is “cyber” and the default password is
“cyber”.
Option 2: DHCP Server
1. Ask your administrator if there is DHCP server on the LAN.
2. Make sure the DHCP is Enabled.
3. Make sure the network connection is ready and power on the
PDU.
4. The PDU will obtain an IP address from the DHCP server
automatically.
Option 3: Address Resolution Protocol (ARP) Command
1. Obtain the MAC address from the sticker on the PDU.
2. Open a command prompt as an administrator and type the
following:
“arp -s [available IP address] [MAC address of PDU]”.
00-0c-15-80-00-01
Example: arp -s 192.168.20.240
IP Address
MAC Address
3. Use the Ping command to assign a size of 123 bytes to the IP.
* Type in “ping 192.168.20.240 -l 123” then press Enter.
* If the replies are received, your computer can communicate with
the IP address
Option 4: Hyper Terminal or Terminal Emulator
1. Use the included RJ45/DB9 serial port connection cable, attach one
end to the serial port on the front of the PDU, and the other end to
the PC/ server.
2. Open the Hyper Terminal software on your PC and select a name
and icon for the connection.
3. Setup the COM port settings using the values indicated in Appendix A.
4. Press Enter to enter the Authentication menu.
5. Enter the user name and password of the PDU device at the
Authentication menu.
6. Press 2 and Enter to access Network Settings to view the IP address.
Note: The default username is “cyber” and the default password is
“cyber”. For further information and configuration via Hyper
Terminal, see Appendix A- Hyper Terminal.
24
Operation
Remote Management
The remote management function provides monitoring of the PDU
operational information, controlling outlets and utilizing SNMP
functionality.
Web
Remote management can be performed via web interface. To access
the web interface, please follow the instructions below:
1. Enter the IP address of the PDU into a web browser.
2. Enter the user name and password of the PDU device at the
authentication screen.
Note: The default username is “cyber” and the default password is
“cyber”.
For additional information about the features and functionality of
CyberPower Management Console, please refer to the Intelligent
PDU Web Interface User’s Manual available for download from
www.cyberpower.com.
Telnet and SSH
The CyberPower PDU provides Telnet and Secure Shell (SSH) as Remote
Management methods. Telnet uses user name and password as basic
security while SSH has a higher security level with encryption of the
transmitted packets including user name, password, and data. Configure
the Setting of Telnet and SSH on the Web Interface. The default user
name and password is cyber; cyber.
SNMP
The CyberPower PDU supports SNMPv1 and SNMPv3 protocols.
Download the CyberPower MIB file from www.cyberpower.com and
add it to an SNMP-supported management software. Default read/
write community is public/private for SNMPv1. SNMPv3 provides a
higher security level than SNMPv1 by encrypting the transmitted packet.
Configure the settings of the SNMPv1/SNMPv3 on Web Interface.
Local Management
LCD Operation
The LCD screen provides instant information, such as voltage, current
and power, for the PDU. In addition, users can use the interface
to configure each PDU parameters and control each outlet on the
Switched PDU. The LCD detects the installation orientation of the PDU
(horizontally or vertically), therefore automatically rotates the screen to
best fit the reading direction.
A. Scroll Mode: The PDU information will display in following order
automatically when “Scroll Mode On” is configured.
Device Information
Phase L1 (input source Wye) , Phase L1-2 (input source Delta)
Phase L2 (input source Wye) , Phase L2-3 (input source Delta)
Phase L3 (input source Wye) , Phase L3-1 (input source Delta)
Voltage (Display if device input source is WYE, and has phase to phase outlet.)
Bank 1-N Information (Displays if device has N circuit breakers)
Environment Status (Displays when the ENVIROSENSOR is connected)
Alert
B. Main Menu Map
Alert
Current
Log
Device
Meter
Phase
Bank
Outlet
Immediate On
Delay On
Immediate Off
Delay Off
Reboot
Delay Reboot
Device
Control
Phase 1/2/3 or
Phase L1-2/L2-3/L3-1
Bank 1-N
Outlet 1-N
Color
Brightness
Direction
Screen off
Account (User Name
and Password)
Except TCP
To Default
LCD
Setting
Reset
Reboot
Model Name
Serial Number
Network
About
Daisy Chain (Displays when the PDUs are connected)
Hardware Version
Firmware Version
25
Operation
LED Indicators
Indicator
Status
Green
Description
The PDU status is ok.
Status
Orange
Warning.
Tx/Rx
Red
Critical.
Off
The PDU power is off.
On (Green)
The PDU power is on.
Flashing
On
Reset finished.
Indicates the PDU is connected to the
LAN.
Indicates the PDU is not connected to
the LAN.
The outlet is on and providing power.
Off
The outlet is off.
On
LINK
Outlet
Receiving/transmitting data packet.
Off
Environmental Monitoring (optional)
CyberPower PDUs along with the environmental sensor
(ENVIROSENSOR) provide temperature and humidity monitoring
in a server closet and/or datacenter remotely. To connect the
PDU with ENVIROSENSOR, use the RJ45 Ethernet Cable included
with the ENVIROSENSOR. Plug one end into the Daisy Chain (In)/
ENVIROSENSOR port on the PDU and the other end into the RJ45
port on the ENVIROSENSOR (as shown in figure below). When the
PDU correctly connects to the ENVIROSENSOR, users can see the
temperature and humidity data via the Web Interface. For further
information regarding ENVIROSENSOR configuration, please refer
to the Intelligent PDU Web Interface User’s Manual.
Device Reset
•
•
To locally reset all the settings to default, use Reset function in
the LCD screen.
To remotely reset all the settings to default, log in to the Web
interface, enter the Reset page and apply the function.
Unattended/Automatic Shutdown
PowerPanel® Business Edition (Client) software automatically
initiates a graceful shutdown on the connected computer's
operating system. PowerPanel must be installed on every computer
or server for which the shutdown is to take place. The computer will
receive a message from the PDU, and will perform the shutdown
according to the instructions provided, including shut downs at
exact times and dates.
Step 1. Computer Configuration
1. Install PowerPanel® Business Edition Client on every computer
or server that will be part of the shutdown process (Follow the
instructions in the PowerPanel® Business Edition User Manual).
2. Configure the settings in PowerPanel® Business Edition Client.
See the PowerPanel Business® Edition User Manual for detailed
instructions.
Step 2. PDU Configuration
Verify that the IP address of all computers that will be part of the
shutdown process, are included in the Client List on the web interface.
26
Operation
Step 3. Notification
Notifying the computers of potential outlet shutdown can be
accomplished using the following functions:
•
•
•
Outlets Control Menu: Performing the task of turning off or
rebooting outlets.
Scheduling Menu: Setting the PDU to perform the task of
turning off or rebooting outlets. The notification will occur
prior to the scheduled date/time.
Outlet Overload: In the event of PDU overload, notification will
be sent prior to the PDU shutting down.
Firmware Upgrade
By upgrading the Firmware, you can obtain new features and updates/
improvements to existing functionality. To ensure the firmware is
kept up to date, please regularly visit our website to see if there is
any updated firmware version available. There are three methods for
upgrading the PDU firmware. Please follow the instructions below for
the method that is appropriate for your application. There are two
files to update in order to upgrade the firmware version:
* cpsmpdumbfw_XXX.bin
* cpsmpdumbdata_XXX.bin
Note that the XXX is not part of the file name but is where the
version number in the filename is given.
Prior to performing a firmware update, please:
• Download the latest firmware from www.cyberpower.com.
• Extract the downloaded firmware file to your local “C:\” drive.
Note:
1. The FTP service needs to be enabled before attempting to
execute a firmware upgrade.
2. Please do not turn the PDU off when performing the firmware
upgrade. PDU outlets will remain powered on while the firmware
update takes place. Only the PDU LCD screen will reboot.
3. The PDU LCD screen will reboot during the firmware update
process. This DOES NOT cause the PDU outlets to reboot.
Option 1: Single Device Upgrade
Use the following steps to upgrade the firmware.
1. Open a command prompt window and navigate to “C:\”.
2. Login to the PDU with FTP command, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126
is the current IP of the PDU and 21 is the default ftp
port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
3. Upload the cpsmpdumbfw_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumbfw_XXX.bin
4. Upgrade complete, type
- ftp > quit
5. The system will reboot after you type "quit". This reboot will take
approx. 30 seconds.
6. Login to the PDU via FTP again, type
- C:\>ftp
- ftp> open 192.168.22.126 21 (for example: 192.168.22.126
is the current IP of the PDU and 21 is the default ftp
port for the PDU)
- Connected to 192.168.22.126.
- 220 CyberPower FTP Server Ready.
- User (192.168.22.126:(none)):cyber
- 331 User name okay, need password.
- Password:
- 230 User logged in, proceed.
- ftp>
7. Upload cpsmpdumbdata_XXX.bin, type
- ftp > bin
- ftp > put cpsmpdumbdata_XXX.bin
27
Firmware Upgrade
8. Upgrade complete, type
- ftp > quit
9 . The system will reboot after you type “quit”.
Note: You can check to see if the firmware upgrade is successful
by checking the “Firmware version” on the [System->About]
screen via web UI.
Option 2: Single or Multiple Device Upgrade (recommended)
Use the following steps to upgrade the firmware.
1. Download the Upgrade and Configuration Utility from
www.cyberpower.com.
2. Open Upgrade and Configuration Utility from Start > All
Programs > CyberPower Upgrade and Configuration Utility.
3. Wait for search to finish (Shown in Figure 1).
Figure 1
4. Check the checkbox to select devices listed in the Operation
View (Shown in Figure 2).
Figure 2
5. Make sure Account and Password are valid on selected devices
(Shown in Figure 3).
Figure 3
28
Firmware Upgrade
6. Select Upgrade Firmware.
7. Click Browse to locate and select the firmware and data file to be
updated (Shown in Figure 4).
Figure 4
8. Click OK in the Upgrade Firmware confirmation window (Shown
in Figure 5).
Figure 5
9. The upgrade progress bar will show in Last Action column
(Shown in Figure 6).
Figure 6
10. The result of firmware upgrade will show in Result column
(Shown in Figure 7).
29
Firmware Upgrade
Figure 7
Note: If you don’t want to wait for the firmware upgrade, you can
stop action by choosing Abort in the Action menu. However,
it’s not recommended because Abort action may cause the
device to malfunction.
Option 3: Use a USB Flash Drive
Use the following steps to upgrade the firmware.
1. Download the latest firmware from www.cyberpower.com.
2. Extract the file to the root directory of a USB flash drive with
FAT32 format. Please note that the two files below should be
available in order to complete the firmware upgrade process:
* cpsmpdumbdata_xxx.bin
* cpsmpdumbfw_xxx.bin
3. Plug the USB drive into the PDU USB port and press Enter button
on the PDU LCD screen to enter Main Menu. The USB option will
be displayed.
Main Menu
Alert
Meter
Control
Sensor
Setting
About
USB
4. Select USB and press Enter button to enter Firmware Upgrade
menu.
5. Select Main and Yes to start the upgrade process.
USB
Main
USB
USB
Firmware
Upgrade
Main
Return
Firmware
Upgrade
Confirm?
Yes
No
Firmware
Upgrade
Processing
Firmware
Upgrade
Success
6. The PDU will reboot after the process is completed.
Note: You can check to see if the firmware upgrade is successful
by checking the “Firmware version” on the [System->About]
screen via web UI.
30
Troubleshooting
Problem
Possible Cause
PDU outlets do
1. Breaker tripped
not provide power 2. Power cord is not
to connected
properly plugged
equipment
in
Amperage
displayed on
LCD screen
Overload
exceeds the units
capability
Circuit breakers
have tripped
Solution
Reset Breaker, check
the plug to insure its
connected correctly. If the
problem remains, contact
technical support.
The load indicator shows
red when overload. Reduce
the load on the PDU until
the overload is gone. If the
problem remains, contact
technical support.
1. Sustained overload
2. Excessive ambient Reset Breaker.
or internal
If the problem remains,
temperatures
contact technical support.
3. Faulty breaker
Conformance Approvals
FCC Warning
WARNING!! Changes or modifications to this unit not expressly
approved by the party responsible for compliance could void the
user's authority to operate the equipment.
WARNING!! This equipment has been tested and found to comply
with the limits for a Class A Digital Device, pursuant to Part 15 of
the FCC Rules. These limits are designed to provide reasonable
protection against harmful interference in residential installation.
This equipment generates, uses and can radiate radio frequency
energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio
communications.
However, there is no guarantee that interference will not occur
in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is
encouraged to try to correct the interference by one or more of the
following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from
that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Notice: (1) An unshielded-type power cord is required in order
to meet FCC emission limits and also to prevent interference to
the nearby radio and television reception. It is essential that only
the supplied power cord by used. (2) Use only shielded cables to
connect I/O devices to this equipment.
Note: THE MANUFACTURER IS NOT RESPONSIBLE FOR ANY
RADIO OR TV INTERFERENCE CAUSED BY UNAUTHORIZED
MODIFICATIONS TO THIS EQUIPMENT. SUCH MODIFICATIONS
COULD VOID THE USER’S AUTHORITY TO OPERATE THE
EQUIPMENT.
The Class A digital apparatus meets all requirements of the
Canadian Interference-Causing Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies
du Reglement sur le materiel brouilleur du Canada.
European Union
This is a class A product. In a domestic environment this product
may cause radio interference in which case the user may be
required to take adequate measures.
31
Customer Service & Warranty
Product Registration
Thank you for purchasing a CyberPower product. Prompt product
registration entitles coverage under the Limited Warranty and also allows the
opportunity to be notified of product enhancements, upgrades, and other
announcements.
Registration is quick and easy at www.cyberpowersystems.com/registration (for
USA and Canada) or www.cyberpower.com/registration (for all other regions).
Cyber Power International
Feel free to contact our Tech Support department with installation,
troubleshooting, or general product questions.
Cyber Power Systems, Inc.
Web: www.cyberpower.com
For USA and Canada:
4241 12th Ave East, Suite 400 Shakopee, MN55379
Toll-free: (877) 297-6937
For all other regions:
Please visit our website for local contact information.
Limited Warranty
Read the following terms and conditions carefully before using the
CyberPower PDU series. By using the Product, you consent to be bound by
and become a party to the terms and conditions of this Limited Warranty. If
you do not agree to the terms and conditions of this Warranty, you should
return the Product for a full refund prior to using it.
Who Is Providing This Warranty?
CyberPower Systems, Inc. provides this Limited Warranty.
What Does This Warranty Cover?
This warranty covers defects in materials and workmanship in the Product
under normal use and conditions.
What Is the Period of Coverage?
For USA and Canada, CyberPower provides a 3-Year warranty to the original
purchaser who owns the Product. For other regions, please contact your
local CyberPower sales team for more information.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or
otherwise transfer the Product.
How Do You Get Service?
1. You can use the contact information mentioned above for instructions.
2. When you contact CyberPower, identify the Product and the Purchase
Date.
3. You must provide a purchase receipt (or other proof of the original
purchase) and provide a description of the defect.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product. If the Product is
defective in material or workmanship, CyberPower will repair or replace it at
CyberPower's expense, or, if CyberPower is unable to or decides not to repair
or replace the Product (if defective) within a reasonable time, CyberPower
will refund to you the full purchase price you paid for the Product (purchase
receipt showing price paid is required).
Who Pays for Shipping?
We pay when we send items to you; you pay when you send items to us.
What Are Some Things This Warranty Does Not Cover?
1. This Warranty does not cover any software that is damaged or needs to be
replaced due to the failure of the Product or any data that is lost as a result
of the failure or the restoration of data or records, or the re-installation of
software.
2. This Warranty does not cover or apply to: misuse, modification, operation
or storage outside environmental limits of the Product or the equipment
connected to it, nor for damage while in transit or in storage, nor if there has
been improper operation or maintenance, or use with items not designed
or intended for use with the Product, such as laser printers, appliances,
aquariums, medical or life support devices, etc.
What Are the Limitations?
1. This Warranty does not apply unless the Product and the equipment that
was connected to it were connected to properly wired and grounded outlets
(including compliance with electrical and safety codes of the most current
electrical code), without the use of any adapters or other connectors.
2. The Product must have been plugged directly into the power source and
the equipment connected to the Product must be directly connected to the
Product and not "daisy-chained" together in serial fashion with any extension
cords, another Product or device similar to the Product, surge suppressor, or
power tap. Any such installation voids the Limited Warranty.
3. The Product and equipment connected to it must have been used properly
in a suitable and proper environment and in conformance with any license,
instruction manual, or warnings provided with the Product and the equipment
connected to it.
4. The Product must have been used at all times within the limitations on the
Product's VA capacity.
5. The sole and exclusive remedies of the Initial Customer are those provided by
this Warranty.
32
Appendix A-Hyper Terminal
Hyper Terminal software can be used for basic PDU configuration.
In order for Hyper Terminal to interact with the PDU, the PC/server
must be connected directly to the PDU via the serial port with the
included RJ45/DB9 serial port connection cable. It utilizes a textbased interface and menu system. Navigation through the interface
is done by typing the number of the menu option and pressing the
Enter key. Setup the COM port settings using the following values.
*
*
*
*
*
Bits per second: 9600
Data bits: 8
Parity: None
Stop bits: 1
Flow control: None
Note: The session will timeout and logout after 3 minutes of
inactivity. Menu options are shown below:
[Main Menu]
1. Outlet Manager (Switched PDU Series Only)
2. Network Settings
3. System Configuration
4. Account Settings
5. Configure System to Default
6. Logout
[Outlet Manager]
1. Outlet Control
2. Outlet Configuration
[Network Setting]
Physical MAC Address: 00-0C-15-40-08-A9
1. System IP: 192.168.24.20
2. Subnet Mask: 255.255.255.0
3. Default Gateway: 192.168.24.254
4. DHCP: Enabled
5. Http Port: 80
6. Http Access: Enabled
[System Configuration]
1. Date (mm/dd/yyyy) : 11/11/2011
2. Time (hh:mm:ss): 17:17:25
3. Name:PDU20SW8FNET
4. Contact: Administrator
5. Location: Server Room
[Account Setting]
1. Administrator
2. Viewer (Web Only)
[Configure System to Default]
Sure to Configure System to Default
1. Yes
2. No
Appendix B-Power Device Network Utility
Overview
The CyberPower Power Device Network Utility is an easy-to-use
interface which is used for establishing IP addresses on CyberPower
PDU devices.
Installation
Step 1. Download the Power Device Network Utility software from
www.cyberpower.com.
Step 2. Select Next in the software wizard (Shown in Figure 1).
Figure 1
33
Appendix B-Power Device Network Utility
Step 3. Choose an installation directory. Select Next (Shown in
Figure 2).
Figure 2
Step 4. Select Install to confirm the settings and install (Shown in
Figure 3).
Figure 3
Step 5. Select Finish to finalize the installation (Shown in Figure 4).
Figure 4
34
Appendix B-Power Device Network Utility
Launch Program
To launch the Power Device Network Utility and get started, select
Programs from the Start menu in Windows and locate the new
folder and icons for Power Device Network Utility. Select Power
Device Network Utility from the program folder (Shown in Figure 5).
Figure 5. Power Device Network Utility
Getting Started
The Power Device Network Utility scans the network for devices with
MAC addresses that match CyberPower network hardware. Once
found, the device(s) can then be figured with a specific IP address,
subnet mask, and gateway address. This allows the device(s) to function
properly on the network and interface with CyberPower Management
Console.
Step 1. Select the appropriate PDU device from the Equipment List
(Shown in Figure 6).
Figure 6. Equipment List
Note: If the PDU does not appear on the list, click the Refresh button to
rescan the network. If it still does not appear, ensure that the PDU
is turned on and was installed correctly.
Pressing Stop will cancel the scan/refresh process.
Note: If your computer has a software firewall installed, you may
see a Windows Security Alert message (Shown in Figure 7).
In Windows XP SP2, the default firewall alert message is shown
as Figure 7. You need to allow the Power Device Network Utility
access through the firewall. Click Unblock to allow access.
Figure 7. Windows Security Alert
35
Appendix B-Power Device Network Utility
Step 2. Assign a valid IP Address to the PDU
Option 1: Assisted Setup (recommended)
With the appropriate device selected from the Equipment
List, open the Network Settings menu (Shown in Figure 8)
[Tools=>Device Setup]. In the Device Network Setting Menu, enter
a valid IP address, subnet mask, and gateway address to setup the
PDU device.
Figure 8. Network Setting Menu (Device Setup)
Note: The DHCP option is not available for all power devices.
Step 3. Authentication
Enter the user name and password of the PDU device at the
Authentication menu (Shown in Figure 9).
Note: The default username is “cyber” and the default password is
“cyber”.
Figure 9. Authentication screen
Advanced Settings
Timeout Settings
The Timeout Setting (Shown in Figure 10). [Edit=>Timeout Settings]
is used to specify the wait time when scanning for network PDU
devices. When there are many devices on the local network, it may
take extended periods of time to locate all the devices. The timeout
function is used to limit the search time.
The default setting is 3 seconds. Valid values are 3 to 60 seconds.
Figure 10. Timeout Setting
36
New LCD PDU Daisy-Chain Function Introduction
71xxx/ 41xxx/Function
31xxx
AppendixPDU81xxx/
C-PDU Daisy-Chain
TheThe
daisy-chain
function
allows
up toup
four
to be connected
together to
daisy-chain
function
allows
toPDUs
four PDUs
to be connected
be together
monitoredto
and
from
IP address.
becontrolled
monitored
andone
controlled
from one IP address.
Ethernet
Host
Guest #1
Guest #2
Guest #3
When
PDUs
are connected,
two roles
are defined:
Host and
Guest.
to three
When
PDUs
are connected,
two roles
are defined:
Host
and Up
Guest.
Guest PDUs can be connected to one Host PDU. The Guest PDUs will be
Up to three Guest PDUs can be connected to one Host PDU. The
recognized by serial number and their order within the daisy-chain.
Guest PDUs will be recognized by serial number and their order
Note:
To perform
the daisy-chain function, the firmware version of the
within
the daisy-chain.
connected PDUs needs to be the same (v1.07 or above).
Note: To perform the daisy-chain function, the firmware version of
the connected PDUs needs to be the same (v1.08 or above).
How to connect the PDUs together?
How to
connect
the PDUs
together?
Use
one Ethernet
cable
and connect one end of it to the daisyUse one
Ethernet
andthe
connect
one end
it to
the daisy-chain
(Out) port
chain
(Out) cable
port on
Host PDU
andof
the
other
end to the daisyn the
Host(In/ENV)
PDU and the
endGuest
to the1 daisy-chain
(In/ENV)
on(as
the
chain
portother
on the
PDU to connect
theport
PDUs
Guestshown
1 PDU to
connect the PDUs (as shown below).
below).
Host PDU
Out port
Copyright © 2018 Cyber Power Systems, Inc. All rights reserved.
Guest #1 PDU
In/ENV port
WhatWhat
remote
management
protocols
are supported
in PDU daisy-chains?
remote
management
protocols
are supported
in PDU daisyCurrently
users can monitor and control daisy-chained PDUs through Web
chains?
nterface (HTTP/HTTPS) or SNMP protocols.
Currently users can monitor and control daisy-chained PDUs
Web
interface
(HTTP/HTTPS)
or SNMP
protocols.
Whatthrough
functions
on the
Web pages
does daisy-chain
support?
lease find in below table:
ummary
PDU
Log does daisy-chain
System
What functions
on the Web pages
support?
Device
Statustable:
Please find
in below
Status Records
Identification
Outlet Status
Energy Records
Summary
Device Manager
Graphing
Device Status
Outlet Manager
Outlet Control
Outlet Status
Outlet Schedule
PDU
Device Manager
Manager
How to switch between Outlet
Host and
Guest PDUs on the Web interface?
unctionality supported Outlet
by daisy-chained
Control PDUs will have the Host/ Guest #
rop down menu displayed on the Web interface (as shown below).
Outlet Schedule
Status Records
Log
Energy Records
Graphing
System
Identification
37
Summary
PDU
Log
System
Identification
Appendix
C-PDU Daisy-Chain
Function
Outlet Status
Energy Records
Device Status
Status Records
Device Manager
Graphing
Outlet Manager
How to switch
between
Outlet
ControlHost and Guest PDUs on the Web
interface? Outlet Schedule
Functionality supported by daisy-chained PDUs will have the Host/
How to switch between Host and Guest PDUs on the Web interface?
Guest
# drop down menu displayed on the Web interface (as
Functionality supported by daisy-chained PDUs will have the Host/ Guest #
shown
below).
drop down menu displayed on the Web interface (as shown below).
Can I upgrade the firmware version of the Guest PDUs through
the Host PDU?
Yes, you can upgrade the firmware using the Upgrade and
Configuration Utility, FTP (network connection required), or USB
port. Once the Hostcompletes the PDU firmware upgrade, it will
trigger its Guest PDUs to upgrade the firmware automatically. It
takes about 5 minutes for the Guest PDUs to upgrade, regardless of
Can
upgradeof
the
firmware
theI number
PDUs
in theversion
series.of the Guest PDUs through the Host PDU
Yes, you can upgrade the firmware using the Upgrade and Configuration Utilit
FTP (network connection required), or USB port. Once the Host completes th
PDU
firmware
upgrade,
it will
triggercable
its Guest
PDUs to upgrade
thePDU
firmware
What
will happen
if an
Ethernet
is disconnected
in the
automatically.
daisy-chain?It takes about 5 minutes for the Guest PDUs to upgrade,
regardless of the number of PDUs in the series.
For example, if four PDUs are connected and the cable connecting
Guest
1 and
2 is disconnected,
then Guest
2 and 3 will
no longer
be
What
will
happen
if an Ethernet cable
is disconnected
in the
PDU daisy-chai
detected
byifthe
PDU.
An event showing
that Guest
2 andGuest
3
For
example,
fourHost
PDUs
are connected
and the cable
connecting
1 and
removed will
beGuest
recorded
PDU.be
Meanwhile,
Guest
2
isare
disconnected,
then
2 andin3the
willHost
no longer
detected by
the Host
PD
An
event
showing
Guest
2 and 3 are
removed
will
recorded
in the Hos
and
3 will
createthat
a new
daisy-chain
where
Guest
2 be
becomes
a Host
PDU.
Guest 2 Guest
and 3 will
a new
daisy-chain where Guest 2
and Meanwhile,
Guest 3 becomes
1 to create
the new
Host.
becomes a Host and Guest 3 becomes Guest 1 to the new Host.
Ethernet
Host
Guest #1
Guest #2
Host
Guest #3
Guest #1
In the above example, if the disconnected Ethernet cable is re-connected, wil
In the above example, if the disconnected Ethernet cable is rethe role of the PDUs stay the same?
connected, will the role of the PDUs stay the same?
Yes, when the disconnected cable between Guest 1 and 2 is re-connected,
Yes, when
the
disconnected
between
Guest
2 and 3
will
revert to theircable
previous
roles. Guest 1 and 2 is re-
connected, Guest 2 and 3 will revert to their previous roles.
What happens if one PDU in the daisy-chain is powered off?
For example, if four PDUs are connected and Guest 1 is powered off, an event
What happens
if one
PDU
in the
daisy-chain
powered
off?Host PDU.
showing
that Guest
1, 2 and
3 are
removed
will be is
recorded
in the
Guest
2 and 3 will
not create
daisy-chain.
For example,
if four
PDUs another
are connected
and Guest 1 is powered
o, anthe
event
thatthe
Guest
2 and
3 are removed
be
Does
Hostshowing
PDU record
logs1,of
the Guest
PDUs and will
itself?
recorded
in PDU
the Host
PDU.
2 and
will not
create
another to it.
Yes,
the Host
records
theGuest
logs from
all 3Guest
PDUs
daisy-chained
daisy-chain.
Will the Logs of the Guest PDUs recorded in the Host PDU be cleared if the
Guest PDUs are removed from the Host PDU?
Does
the Host
record
logs ofeven
theafter
Guest
itself?
No,
the Logs
of thePDU
Guest
PDUs the
will remain
thePDUs
Guestand
PDUs
are remove
Yes, the Host PDU records the logs from all Guest PDUs daisy-
Does the Host PDU record the Status Records of the Guest PDUs and itself?
chained to it.
Yes, the Host PDU records the Status Records for all the PDUs in the
daisy-chain.
Willthe
the
LogsRecords
of the Guest
in the
Host
PDU
be be cleare
Will
Status
of thePDUs
Guestrecorded
PDUs logged
in the
Host
PDU
if the
Guest
PDUs are removed
from
Host PDU?
ifcleared
the Guest
PDUs
are disconnected
from the
Hostthe
PDU?
No,once
the Logs
of the
Guest
will remain
even
after the
Guest
Yes,
the Guest
PDUs
arePDUs
removed,
the Status
Records
logged
in the Host
PDUs
PDU
willare
be removed.
cleared. As long as the Host PDU does not connect to other PDUs
the Status Records of the disconnected PDU can be displayed when it is
re-connected to the Host PDU. If the38
Host PDU connects to different PDUs, th
Status Records of the removed PDU will be entirely cleared.
Appendix C-PDU Daisy-Chain Function
Does the Host PDU record the Status Records of the Guest PDUs
and itself?
Yes, the Host PDU records the Status Records for all the PDUs in
the daisy-chain.
Will the Status Records of the Guest PDUs logged in the Host
PDU be cleared if the Guest PDUs are disconnected from the Host
PDU?
Yes, once the Guest PDUs are removed, the Status Records logged
in the Host PDU will be cleared. As long as the Host PDU does not
connect to other PDUs, the Status Records of the disconnected
PDU can be displayed when it is re-connected to the Host PDU. If
the Host PDU connects to dierent PDUs, the Status Records of the
removed PDU will be entirely cleared.
Are the Guest PDUs able to connect to the network when they are
daisy-chained?
Yes, even when the PDUs are daisy-chained, the Guest PDUs are
able to connect to the network directly. Note that a Guest PDU will
require having its own Ethernet cable connected to the network.
What will happen if a 5th PDU is added to a daisy-chain?
The maximum number of PDUs that can be connected in one daisychain is 4. The daisy-chain functionality will not work until the fifth
PDU is removed.
What is the maximum recommended length of the Ethernet cable
to daisy-chain the PDUs?
50 ft (15 m)
Troubleshooting
Problem
The PDUs are
connected but the
daisy-chain function
is not working.
Possible Cause
- The firmware
version does not
support daisychain.
- The PDUs have
dierent firmware
versions.
Solution
Check the firmware
version of each PDU
and upgrade it to
v1.08 or above.
Only the Host PDU
supports
EnergyWise.
N/A
I cannot set the WoL Only the Host PDU
for Guest PDUs.
supports WoL.
N/A
I cannot set the
EnergyWise
configuration on a
Guest PDU.
39
Cyber Power Systems, Inc.
www.cyberpower.com
Copyright © 2019 Cyber Power Systems, Inc. All rights reserved.
K01-0000699-00