CyberPower | OR1000PFCRT2U | Setup guide | CyberPower OR1000PFCRT2U Setup Guide

CyberPower OR1000PFCRT2U Setup Guide
FUNCTION SETUP GUIDE
K01-0000168-00
Timing
(Sec.)
Buzzer
Indicator
Power On
2
Beep once
LED On / LCD On
Power Off
2
Beep twice
LED Off / LCD Off
Cancel Shutdown
5
Beep once
N/A
Forced Shutdown
10~20
N/A
LED Off / LCD Off
If you press the POWER button for more
than 10~20 seconds, the UPS will shutdown.
Function Setup (↓)
0.5
N/A
LED On / LCD On
The toggle frequency is set to one time per
0.5 second. Press the switch to roll down the
function menu.
Function Setup (↑)
0.5
N/A
LED On / LCD On
The toggle frequency is set to one time per
0.5 second. Press the switch to roll up the
function menu.
Disable Fault Alarm
0.5
N/A
LED On / LCD On
Press the button for 0.5 second to disable
fault alarm.
3
N/A
LED On / LCD On
In Line Mode, press the button for 3 seconds.
The UPS will perform a Self Test of the
battery.
Function
Self Test
Button
Display On/Off
2
On: Beep Once
Off: Beep Twice
LED On
LCD On/Off
Silence Alarm On/Off
2
On/Off
LED On / LCD On
Description
Press the POWER button for around 2
seconds - you will hear a constant tone (1
second) - and release after a short beep.
Press the POWER button for around 2
seconds - you will hear a constant tone (1
second) - and release after two short beeps.
If you press the POWER button for more
than 5 seconds, the UPS will remain Power
On.
Press the DISPLAY button for 2 seconds to
turn on the LCD display. The LCD display will
illuminate. Press the DISPLAY button again
for 2 seconds to turn off the LCD display.
The LCD display will be off. Note: The default
setting is in off position. The LCD display will
darken if buttons are untouched in 60
seconds.
Press the button for 2 seconds to enable or
disable audible alarm. The MUTE icon will
appear on the LCD display when audible
alarm is disabled.
Press both buttons at the same time for 3
seconds to enter programming mode. Press
the DISPLAY or SILENCE ALARM button to
rotate through the options.
Low Sensitivity (78-142Vac)
(Not recommended for computer loads.)
Sensitivity Setup
3
N/A
LED On / LCD On
Medium Sensitivity (88-139Vac)
High Sensitivity (88-136Vac)
Event Reset
Fault Reset
3
2
Beep Twice
Beep Twice
LED On / LCD On
Pressing both buttons at the same time for 3
seconds will clear the EVENT counter.
LED Off / LCD Off
This FAULT icon appears on the LCD
display if there is a problem with the UPS.
Press the POWER button for to turn off the
UPS.