CyberPower PR2200LCD User Manual
5
Replace Battery Indicator
6
Status/Tab Button
This LED is illuminated to remind users to replace the battery.
For UPS status information, press the button for 1 second. For additional information including
the use of the button as a Tab, please refer to the Function Setup Guide.
7
Setup/Enter Button
PR2200LCD / PR3000LCD
User’s Manual
Press the Setup button for 1 second to enter setup menu and then select the functions for
configuration. For more information about the Setup/Enter button, please refer to the Function
Setup Guide.
K01-0000252-01
8
Control/Up Button
Press the Control button for 1 second to enter control menu and then select the functions for
IMPORTANT SAFETY WARNINGS
configuration. This button is also used to scroll up. For more information about the Control/Up
button, please refer to the Function Setup Guide.
(SAVE THESE INSTRUCTIONS)
This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit.
9
Test/Down Button
Press the Test switch for 1 second to enter test menu and then select the functions for
Read this manual thoroughly before attempting to unpack, install, or operate your UPS.
configuration. This button is also used to scroll down. For more information about the Test/Down
CAUTION! To prevent the risk of fire or electric shock, install in a temperature and humidity controlled indoor area free of conductive
contaminants.
button, please refer to the Function Setup Guide.
(Please see specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover except to service the battery. Turn off and unplug the unit before
10
Logs/Esc Button
Press the Logs button for 1 second to view the events or logs that have been recorded.
servicing the batteries. There are no user serviceable parts inside except for the battery.
This button is also used to exit a menu. For more information about Logs/Esc button,
CAUTION! Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected.
CAUTION! The UPS must be connected to an AC power outlet with fuse or circuit breaker protection.
grounded.
please refer to the Function Setup Guide.
Do not plug into an outlet that is not
If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer
Rear Panel
1
component.
Battery and Surge Protected Outlets
The unit has ten battery powered and surge protected outlets for connected equipment to
CAUTION! To reduce the risk of fire, connect only to a circuit provided with 30 amperes maximum branch circuit over current protection in
ensure temporary uninterrupted operation of your equipment during a power failure.
accordance with the National Electric Code, ANSI/NFPA 70.
(DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not sell products for life support or medical
applications.
pump or other large electrical devices into the “Battery and Surge Protected Outlets”.
DO NOT use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or
The power demands of these devices may overload and damage the unit.)
patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric shock, do not use with or near an aquarium.
Condensation
2
Serial/USB Ports to PC
The Serial and USB ports allow connection and communication between the
from the aquarium can cause the unit to short out.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or electric shock, do not use the unit on any transportation
computer and the UPS unit. Note: Only one port can be used at a time.
3
EPO Port
such as airplanes or ships. The effect of shock or vibration caused during transit and the damp environment can cause the unit to short out.
Use the provided gray EPO cable to connect to a provided EPO contact switch.
Follow the appropriate circuit diagram to the right to wire the cable to your
INSTALLING YOUR UPS SYSTEM
EPO configuration. The EPO remote switch is a switch installed in an outside
area, connected to the unit via the Emergency Power Off cable. In case of an
INTRODUCTION
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and
performance during the lifetime of the product.
emergency, it can be used to immediately cut-off power from the UPS.
4
TVSS Ground
The TVSS GND only used for dielectric voltage-withstand test on production.
UNPACKING
5
SNMP/HTTP Network Slot
Inspect the UPS upon receipt. The box should contain the following:
Remove the cover panel to install an optional RMCARD to remotely monitor
®
(a) UPS unit (b) User’s manual (c) Emergency Power Off cable (gray) (d) PowerPanel Business Edition software CD (e) Serial cable (f) USB
A+B type cable (g) Warranty registration card (h) Function Setup Guide
and manage your UPS over a network.
6
Input Circuit Breaker
OVERVIEW
Located on the back of the UPS, the circuit breaker provides overload and
The PR2200LCD/PR3000LCD UPS provides complete power protection from utility power that isn't always consistent. The
PR2200LCD/PR3000LCD features surge protection against power surges and maintenance free batteries for long lasting battery backup during
fault protection.
7
Output Circuit Breaker
power outages. In addition to ensuring consistent power to your computer system and the
Located on the back of the UPS, the circuit breaker provides overload and fault protection.
PR2200LCD/PR3000LCD also includes software that will automatically save your open files
8
AC Input Power Cord
and shutdown your computer system during a utility power loss.
Heavy-duty power cord.
AUTOMATIC VOLTAGE REGULATOR
The PR2200LCD/PR3000LCD stabilizes inconsistent utility power voltage to nominal levels that
REPLACING THE BATTERY
are safe for equipment. Inconsistent utility power may be damaging to important data files and hardware,
but with Automatic Voltage Regulation (AVR), damaging voltage levels are corrected to safe levels.
Replacement of batteries located in an OPERATOR ACCESS AREA.
AVR
1.
When replacing batteries, replace with the same number of the following battery: CyberPower / RB12170X4 for the PR2200LCD and
automatically increases low utility power and decreases high utility power to a consistent and safe
PR3000LCD. Contact CyberPower Systems about replacement batteries.
110/120 volts.
2.
CAUTION! Risk of Energy Hazard, 12V, maximum 20 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
1.
as chains, wrist watches, and rings. High energy conducted through these materials could cause severe burns.
Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity (2200VA/1980W for PR2200LCD,
3.
CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
3000VA/2700W for PR3000LCD).
4.
CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
If the rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit
to shut down or the circuit breaker to trip.
CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING
HARDWARE INSTALLATION GUIDE
TO LOCAL REGULATIONS.
1. Your new UPS may be used immediately upon receipt. However, to ensure the battery’s maximum
charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is
BATTERY REPLACEMENT PROCEDURE:
equipped with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will
1. Turn off and unplug all connected equipment.
automatically charge whether the UPS is turned on or off.
2. Turn the UPS off and unplug it from the AC power source.
2. Note: This UPS is designed with a safety feature to keep the system from being turned on during
3. Remove the front panel of the UPS.
shipment.
4. Remove two screws from the battery compartment cover and slide the cover completely off of the unit.
The first time you turn the UPS on, you will need to have it connected to AC power or it will not power up.
5. Pull out the battery pack on the outside from the compartment. Disconnect the battery connector from the batteries.
3. With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup into the
battery power supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large
electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage
the unit.
the batteries. Pull out the battery pack on the inside from the compartment.
7. Install the replacement battery pack on the inside by connecting the wire bundle connector (composed of one red wire and one black wire)
to the connector from the battery pack. Lock the battery wires back with the cable tie.
4. Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet).
Make sure the wall branch outlet is protected by a fuse or circuit
breaker and does not service equipment with large electrical demands (e.g. air conditioner, copier, etc…).
The warranty prohibits the use of
extension cords, outlet strips, and surge strips.
5. Press the power switch to turn the unit on.
6. Before removing the battery pack on the inside, unlock the cable tie and pull out the battery wires. Disconnect the battery connector from
the connector from the battery pack. Put the battery pack on the outside back into the compartment.
9. Re-install the battery compartment cover and tighten the retaining screws.
The Power On indicator light will illuminate and the unit will “beep”.
If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at
least one piece of equipment from the battery power supplied outlets.
8. Install the replacement batteries on the outside by connecting the wire bundle connector (composed of one red wire and one black wire) to
Make sure the circuit breaker is depressed and then turn the UPS on.
10. Put the front panel back on the UPS.
11. Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge.
Note: The battery pack on the outside has a fuse, while the battery pack on the inside has not.
6. To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
7. To store the UPS for an extended period, cover it and store with the battery fully charged.
While in storage, recharge the battery every three
months to ensure battery life.
8. Insure the wall outlet and UPS are located near the equipment being attached for proper accessibility.
9. The LCD module is wall-mountable for extended distance control. Follow the steps below for installation procedure.
a. Remove the LCD module from the front panel.
b. Hang the LCD module on the wall.
c. Replacing the LCD on the UPS - To place the LCD back on the UPS, roll up the LCD cable, return it to the space between the front panel &
battery cover, and replace the LCD.
REMINDER:
Batteries are considered HAZARDOUS WASTE and must be disposed of properly.
Most retailers that sell lead-acid batteries
collect used batteries for recycling, as required by local regulations.
DEFINITIONS FOR ILLUMINATED LCD INDICATORS
Status Menu/Switch

Operation Mode

Battery Information

Load Power

Input

Load VA

Output

Load Amps

Last Self Test

Load Energy

Date & Time
DESCRIPTION
Front Panel

Estimated Runtime

NCL Output
1
Power Switch / Power On Indicator

Setup Wizard

Date & Time
Used as the master on/off switch for equipment connected to the battery power supplied outlets.

Utility Power

Battery Change Date
Online Indicator

MIN O/P Voltage

Firmware Update
This LED is illuminated when the utility power is normal and the UPS outlets are providing power, free of surges and spikes.

MAX O/P Voltage

Power Meter Reset
On Battery Indicator

LCD Auto Sleep

Back to Default
During a severe brownout or blackout, this LED is illuminated and an alarm sounds (two short beeps followed by a pause) to indicate the

Cycling Display

Delay Turn On
UPS is operating from its internal batteries.

Audible Alarm

Delay Turn Off
Fault

Temporarily Mute

Reboot Duration
This LED is illuminated if there is a problem with the UPS.

Sensitivity

Minimum Restore Capacity
BASIC OPERATION
2
3
4
Setup Menu/Switch

Charge Mode

Uptime on Battery

Low Battery Warning

Reserve Runtime

Auto Self Test

Configure NCL

NCL On/Off

Battery Calibration
Limited Warranty and Connected Equipment Guarantee
Read the following terms and conditions carefully before using the CyberPower PR2200LCD/PR3000LCD (the “Product”). By using
Control Menu/Switch

UPS On/Off
the Product you consent to be bound by and become a party to the terms and conditions of this Limited Warranty and Connected
Equipment Guarantee (together referred to as this “Warranty”). If you do not agree to the terms and conditions of this Warranty, you
Test Menu/Switch

Self Test

Alarm Test
should return the Product for a full refund prior to using it.
Who is Providing this Warranty?
CyberPower Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
Logs Menu/Switch
What Does This Warranty Cover?

Transfer Event X1-X10

Next Battery Change

Fault Event F1-F10

UPS Firmware Version

Model Name

LCD Firmware Version

Last Battery Change

Serial Number
This warranty covers defects in materials and workmanship in the Product under normal use and conditions.
It also covers
equipment that was connected to the Product and damaged because of the failure of the Product.
What is the Period of Coverage?
This warranty covers the Product for three years and connected equipment for as long as you own the Product.
For more information about functions setup, please refer to the Function Setup Guide.
Who Is Covered?
This warranty only covers the original purchaser. Coverage ends if you sell or otherwise transfer the Product.
TROUBLESHOOTING
Problem
Possible Cause
Circuit breaker button is
projecting from the back of the
unit.
The UPS does not perform
expected runtime.
How Do You Get Warranty Service?
Solution
1.
Equipment (E.G. Computer tower, Computer Monitor, Ink Jet Printer, Cable Modem, etc).
2.
Visit our web site at http://www.cpsww.com/support or Call us at (877) 297-6937.
3.
If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice.
Battery not fully charged.
Recharge the battery by leaving the UPS plugged in.
How Do You Open A Connected Equipment Claim?
Battery is worn out.
Contact CyberPower Systems about replacement batteries.
Circuit breaker has tripped due to
an overload.
1.
The UPS will not turn on.
Before contacting CyberPower, identify Your Product model number, the Purchase Date, and each item of Connected
Turn the UPS off and unplug at least one piece of equipment.
Wait 10 seconds, reset the circuit breaker by pressing the
button in, and then turn the UPS on.
Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., Suite 400, Shakopee, MN
55379, or send us an e-mail message at claims@cpsww.com for instructions, within 10 days of the occurrence.
2.
When you contact CyberPower, identify the Product, the Purchase Date, and the item(s) of Connected Equipment. Have
The on/off switch is designed to
prevent damage from rapidly
turning it off and on.
Turn the UPS off. Wait 10 seconds and then turn the UPS on.
The unit is not connected to an AC
outlet.
The unit must be connected to a 110/120V 60Hz outlet.
The battery is worn out.
Please contact CyberPower Systems about replacement
batteries.
Mechanical problem.
Please contact CyberPower Systems.
The USB / serial cable is not
connected.
Connect the USB / serial cable to the UPS unit and an open
USB / serial port on the back of the computer. You must use
the cable that came with the unit.
The USB / serial cable is connected
to the wrong port.
Check the back of the computer for an additional USB / serial
port. Move the cable to this port.
The unit is not providing battery
power.
Shutdown your computer and turn the UPS off. Wait 10
seconds and turn the UPS back on. This should reset the unit.
The serial cable is not the cable that
came with the unit.
Please use the serial cable that came with the unit for the
software.
Overload
Remove excessive load and restart the UPS.
Output Short
Please contact CyberPower Systems.
$375,000 for the PR2200LCD and PR3000LCD.
Battery Overcharge
Please contact CyberPower Systems.
Who Pays For Shipping?
Over Temperature
Please contact CyberPower Systems.
information on all applicable insurance or other resources of recovery/payment that are available to the Initial Customer and
Request a Claim Number.
3.
You must provide a dated purchase receipt (or other proof of the original purchase) and provide a description of the damage to
your connected equipment.
4.
Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the
damage to the Connected Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the
shipping label or include it with the product. You must prepay all shipping costs, you are responsible for packaging and
PowerPanel® Business Edition
is inactive (all icons are gray).
shipment, and you must pay the cost of the repair estimate.
How Long Do I Have To Make A Claim?
All claims must be made within ten days of the occurrence.
What Will We Do To Correct Problems?
CyberPower will inspect and examine the Product.
If the Product is defective in material or workmanship, CyberPower will repair or replace it at CyberPower's expense, or, if
CyberPower is unable to or decides not to repair or replace the Product (if defective) within a reasonable time, CyberPower will refund
to you the full purchase price you paid for the Product (purchase receipt showing price paid is required).
If it appears that our Product failed to protect any equipment plugged into it, we will also send you forms for making your claim for the
connected equipment.
We will repair or replace the equipment that was damaged because of the failure of our Product or pay you
the fair market value (NOT REPLACEMENT COST) of the equipment at of the time of the damage. We will use Orion Blue Book, or
another a third-party valuation guide, or eBay, craigslist, or other source to establish that amount. Our maximum liability is limited to
The Fault LED is illuminated.
We pay when we send items to you; you pay when you send items to us.
What isn’t covered by the warranty?
Additional troubleshooting information can be found under “Support” at www.cyberpower.com
1.
This Warranty does not cover any software that was damaged or needs to be replaced due to the failure of the Product or any
data that is lost as a result of the failure or the restoration of data or records, or the reinstallation of software.
2.
TECHNICAL SPECIFICATIONS
This Warranty does not cover or apply to: misuse, modification, operation or storage outside environmental limits of the Product
or the equipment connected to it, nor for damage while in transit or in storage, nor if there has been improper operation or
maintenance, or use with items not designed or intended for use with the Product, such as laser printers, appliances, aquariums,
medical or life support devices, etc.
Model
PR2200LCD
PR3000LCD
Capacity
2200VA / 1980W
3000VA / 2700W
Nominal Input Voltage
120Vac
Input Frequency
50/60Hz
What are the Limitations?
The sole and exclusive remedies of the Initial Customer are those provided by this Warranty.
1.
This Warranty does not apply unless the Product and the equipment that was connected to it were connected to properly wired
and grounded outlets (including compliance with electrical and safety codes of the most current electrical code), without the use
of any adapters or other connectors.
2.
On-Battery Output Voltage
120Vac ± 5%
On-Battery Output Wave Form
Sine Wave
Operating Temperature
+ 32°F to 104° F / 0° C to 40° C
The Product must have been plugged directly into the power source and the equipment connected to the Product must be
directly connected to the Product and not “daisy-chained” together in serial fashion with any extension cords, another Product
or device similar to the Product, surge suppressor, or power tap. Any such installation voids the Limited Warranty.
3.
The Product and equipment connected to it must have been used properly in a suitable and proper environment and in
conformance with any license, instruction manual, or warnings provided with the Product and the equipment connected to it.
4.
Operating Relative Humidity
0 to 95% non-condensing
Size (L x W x H)
20.2" x 7.7" x 17" (513 x 196 x 432mm)
The Product must have been used at all times within the limitations on the Product’s VA capacity.
The Product was designed to eliminate disrupting and damaging effects of momentary (less than 1ms) voltage spikes or impulses
Net Weight
116 lbs
Battery Type
124 lbs
CyberPower / RB12170X4
Typical Battery Recharge Time
8 hours from total discharge
Typical Battery Life
3 to 6 years, depending on number of discharge/recharge cycles
Recommended Battery
Sealed Maintenance Free Lead Acid Battery
Safety Approvals
UL1778, CSA C22.2 No 107.3, FCC/DoC Class A
from lightning or other power transients. If it can be shown that a voltage spike lasting longer than 1ms has occurred, the occurrence
will be deemed outside the rated capabilities of the Product and the Limited Warranty is void. CyberPower Does Not Cover or
Undertake Any Liability in Any Event for Any of the Following:
1.
Loss of or damage to data, records, or software or the restoration of data or records, or the reinstallation of software.
2.
Damage from causes other than AC Power Line Transients, spikes, or surges on properly installed, grounded and
code-compliant 120 volt power lines in the United States and Canada; transients, surges or spikes on standard telephone land
lines, PBX telephone equipment lines or Base 10T Ethernet lines, when properly installed and connected. (This exclusion
applies, for example, to fluctuations in data transmission or reception, by CATV or RF transmission or fluctuations, or by
transients in such transmission.)
3.
Damage from any circumstance described as excluded above with respect to the Product.
4.
Damages from fire, flood, wind, rain, rising water, leakage or breakage of plumbing, abuse, misuse or alteration of either the
product or the Connected Equipment.
5.
SYSTEM FUNCTIONAL BLOCK DIAGRAM
Input
EMI
Filter
CyberPower excludes any liability for personal injury under the Limited Warranty and Connected Equipment Guarantee.
CyberPower excludes any liability for direct, indirect, special, incidental or consequential damages, whether for damage to or
Surge
Suppressor
AVR
loss of property [EXCEPT FOR (AND ONLY FOR) the specific limited agreement of CyberPower to provide certain warranty
Output
benefits regarding "Connected Equipment" under this Warranty], loss of profits, business interruption, or loss of information or
data. NOTE: Some States or Provinces do not allow the exclusion or limitation of incidental or consequential damages, so the
Charger
AC/DC
Inverter
Normal Mode
Battery Mode
Battery
DC/A
C
above limitation may not apply to you.
6.
The Product is not for use in high-risk activities or with aquariums. The Product is not designed or intended for use in hazardous
environments requiring fail-safe performance, or for use in any circumstance in which the failure of the Product could lead
directly to death, personal injury, or severe physical or property damage, or that would affect operation or safety of any medical
or life support device (collectively, "High Risk Activities"). CyberPower expressly disclaims any express or implied warranty of
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
fitness for High Risk Activities or with aquariums. CyberPower does not authorize use of any Product in any High Risk Activities
or with Aquariums. ANY SUCH USE IS IMPROPER AND IS A MISUSE OF THE PRODUCT.
Advanced Energy-Saving Patented Bypass Technology
CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS energy costs by up to
Where Can I Get More Information?
75% compared to conventional UPS models. Even when utility power is normal, conventional UPS models
The application of the United Nations Convention of Contracts for the International Sale of Goods is expressly excluded.
constantly pass power through a transformer. By contrast, under normal conditions the advanced circuitry
CyberPower is the warrantor under this Limited Warranty.
of a GreenPower UPS™ bypasses the transformer. As a result, the power efficiency is significantly
For further information please feel free to contact CyberPower at CyberPower Systems (USA), Inc. 4241 12th Ave E., Suite 400,
increased while decreasing waste heat, using less energy, and reducing energy costs.
Shakopee, MN 55379; call us at (877) 297-6937; or send us an e-mail message at claims@cpsww.com.
When an abnormal power condition occurs, the GreenPower UPS™ automatically runs power through its
transformer to regulate voltage and provide “safe” power. Since utility power is normal over 88% of the time, the GreenPower UPS™
operates primarily in its efficient bypass mode.
CyberPower Systems encourages environmentally sound methods for disposal and recycling of its UPS products.
Please dispose and/or recycle your UPS and batteries in accordance to the local regulations of your state.
The GreenPower UPS™ is also manufactured in accordance with the Restriction on Hazardous Substances (RoHS) directive making
it one of the most environmentally-friendly on the market today.
All rights reserved. Reproduction without permission is prohibited.