Honeywell | HL-A-5 High Differential Pressure Transducer | Datasheet | Honeywell HL-A-5 High Differential Pressure Transducer Datasheet

Honeywell HL-A-5 High Differential Pressure Transducer Datasheet
Model HL-A-5
High Line Wet/Wet Differential
Pressure Transducer
DESCRIPTION
The High Line Wet/Wet Differential Pressure Model HL-A-5 is de-
A variety of standard options are available with the Model
signed to accept extreme line pressures of up to 5000 psi.* This
HL-A-5 including the traditional removable pressure adaptors
unique design features standard bonded foil strain gages on
for cleaning purposes, extended temperature ranges, alterna-
stainless steel. Liquid and gas differential pressures of 50 psid
tive pressure ports, internal amplifiers options, and electrical
to 7500 psid are measured within a 0.50 % full scale accuracy.
terminations.
FEATURES
•
0.5 % accuracy
•
Line pressure to 5000 psi
•
mV/V (standard), 4 mA to 20 mA, 0 Vdc to 5 Vdc, or 0 Vdc
to 10 Vdc output
•
Intrinsically safe available (2N option only)10
•
CE approved11
Model HL-A-5
PERFORMANCE SPECIFICATIONS
Characteristic
Measure
Pressure ranges
50, 75, 100, 150, 200, 300, 500, 750,
1000, 1500, 2000, 3000, 5000, 7500* psid
Accuracy
±0.5 % full scale
Linearity
±0.25 % full scale (typical)
Hysteresis
±0.13 % full scale (typical)
Non-repeatability
±0.07 % full scale (typical)
Output (standard)
2 mV/V (nominal)
Line pressure
2500 psi**
Resolution
Infinite
OPTION CODES
Many range/option combinations are available
in our quick-ship and fast-track manufacture
programs. Please see http://measurementsensors.
honeywell.com for updated listings.
Pressure ranges
(psid)
50, 75, 100, 150, 200, 300, 500, 750, 1000,
1500, 3000, 5000, 7500
Temperature
compensation
1a. 60 °F to 160 °F
1b. 30 °F to 130 °F
1c. 0 °F to 185 °F
1d. -20 °F to 130 °F
1e. -20 °F to 200 °F
1f. 70 °F to 250 °F
1i. -65 °F to 250 °F6
1j. 0 °C to 50 °C
1m. -25 °C to 110 °C
Internal
amplifiers
2u. Unamplified, mV/V
output
2b. 4 wire ±5 Vdc
2c. 0 Vdc to 5 Vdc
2t. 0 Vdc to 10 Vdc
2j. 4 mA to 20 mA
(three wire) output
2k. 4 mA to 20 mA
(two wire) output12
2n. (2N) 4 mA to 20
mA (two wire)
intrinsically safe12
3a. Input/output isolation8
3d. Remote buffered shunt calibration
ENVIRONMENTAL SPECIFICATIONS
Characteristic
Measure
Temperature, operating
-54 °C to 121 °C [-65 °F to 250 °F]
Temperature, compensated
15 °C to 71 °C [60 °F to 160 °F]
Temperature, effect, zero
±0.75 % full scale/100 °F
Internal amp
enhancements
Temperature, effect, span
±1 % reading/100 °F
Pressure ports 5
5a. 1/4-18 NPT female
5c. 7/16-20 UNF female (per MS33656E4)
Electrical
termination
6a. Bendix PTIH-10-6P
(or equiv.) 6 pin
(max. 250 °F)
6b. MS type connector
to mate with
MS3106-14S-6S
(max. 160 °F)1
6e. Integral cable:
Teflon (-54 °C to
245 °C)
6f. Integral cable: PVC
(-30 °C to 70 °C)
ELECTRICAL SPECIFICATIONS
Characteristic
Measure
Strain gage type
Bonded foil
Excitation (calibration)
10 Vdc
Bridge resistance
350 ohm
Shunt calibration data
Included
Elec. termination (std)
PTIH-10-6P or equivalent (hermetic
stainless)
Mating connector (not incl.)
PT06A-10-6S or equiv. (AA111)
MECHANICAL SPECIFICATIONS
Characteristic
Measure
Media
Gas, liquid
Overload-safe
50 psid to 1500 psid
2000 psi
2000 psid to 7500 psid
Full scale capacity + 2000 psi
Pressure port
1/4-18 NPT female
Wetted parts material
17-4 PH stainless steel
Case material
Stainless steel
2 Honeywell • Sensing and Control
6g. Integral cable:
Neoprene (-20 °C to
80 °C) 1
6h. Integral cable:
Silicone (-54 °C to
150 °C)
6i. Integral underwater
cable (8m [26 ft])
(max. 80°C)1
6j. 1/2-14 conduit
fitting with 1,5 m
[5 ft] of 4 conductor
PVC cable
Shunt calibration 8a. Precision internal resistor 6
Special
calibration
9a. 10 point (5 up/5 down) 20% increments @ 20 °C
9b. 20 point (10 up/10 down) 10% increments
@ 20 °C
Wetted
diaphragm
17-4 PH stainless steel
Bridge type
11a. Square bridge6
11b. Symmetrical bridge6
11c. Square & symmetrical bridge6
Zero and span
adjustment
14b. Top access to pots7
14a. No access to pots
Increased line
pressure
25b. 3000 psi line pressure
25c. 5000 psi line pressure
Interfaces
53e. Signature calibration6
53t. TEDS IEEE 1451.4 module9
High Line Wet/Wet Differential Pressure Transducer
INTERNAL AMPLIFIERS
Voltage
output:
Option 2b
Voltage
output:
Option 2c
Voltage
output:
Option 2t
Current
three-wire:
Option 2j
Current
two-wire:
Option 2k
Intrinsically safe
amp: Option
2n (2N)***
Output signal
±5 V
0 V to 5 V or
±5 V @ 5 mA
0 V to 10 V or
±10 V @ 5 mA
4 mA to 20 mA
4 mA to 20 mA
4 mA to 20 mA
Input power (voltage)
±15 V or 26 Vdc
to 32 Vdc
11 Vdc to 28 Vdc
15 Vdc to 28 Vdc
22 Vdc to 32 Vdc
9 Vdc to 32 Vdc
9 Vdc to 28 Vdc
Input power (current)
45 mA
40 mA
40 mA
65 mA
4 mA to 28 mA
4 mA to 24 mA
Freq. resp (amp)
3000 Hz
3000 Hz
3000 Hz
2500 Hz
300 Hz
2000 Hz
Power supply rej.
60 db
60 db
60 db
60 db
60 db
60 db
Operating temp.
-20 °F to 185 °F
-20 °F to 185 °F
-20 °F to 185 °F
0 °F to 185 °F
0 °F to 185 °F
-20 °F to 185 °F
Reverse voltage protection Yes
Yes
Yes
Yes
Yes
Yes
Short cir. protection
Momentary
Momentary
Momentary
Yes
Yes
Yes
Wiring code:
connector(std)2
A (+) Supply
B Output common
C Supply return
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B Output common**
C Supply return **
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B Output common**
C Supply return**
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B Output common**
C Supply return**
D (+) Output
E Shunt cal 1
F Shunt cal 2
A (+) Supply
B No connection
C No connection
D (+) Output
E Case ground
F No connection
A (+) Supply
B No connection
C No connection
D (+) Output
E Case ground
F No connection
Wiring code: cable2,3,4
R (+) Supply
Bl Output common
G Supply return
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl Output common*
G Supply return*
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl Output common*
G Supply return*
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl Output common*
G Supply return*
W (+) Output
B Shunt cal 1
Br Shunt cal 2
R (+) Supply
Bl (+) Output
W Case ground
R (+) Supply
Bl (+) Output
W Case ground
* Black and green wires are internally connected.
** Pins B and C are internally connected.
*** See Honeywell’s Web site (http://measurementsensors.honeywell.com) for the most up-to-date information regarding Intrinsically safe approvals, ref #008-0547-00.
MOUNTING DIMENSIONS AND CHARACTERISTICS
TYPICAL SYSTEM DIAGRAM
Model HL-A-5
2X
Adaptors
compatible with
1/8-27 NPT female
Mating connectors & cables
AA111 mating connector
AA112 mating connector & 6 conductor cable
(unamplified unit with sense leads but not
shunt Cal)
AA 113 mating connector & 4 conductor cable
(unamplified unit with sense leads but not
shunt Cal)
AA 115 mating connector and 5 conductor
cable for 2c, 2j or 2t amplified output
AA 116 mating connector and 3 conductor
cable for 2k or 2n(2N) amplified output
Customer supplied
Chart recorder
Alarm panel
Data acquisition
Computer
PLC
Display units
SC500
SC2001
SC3004
GM (unamplified only)
GM-A (some amplified,
see GM-A data sheet)
NK (unamplified only)
HH (unamplified only)
In-line amplifiers
(used with unamplified units only)
Amplifier
Output
Universal in-line amplifiers
UV
±5 Vdc
UV-10
±10 Vdc
UBP
0 ±5 Vdc
U3W
4 mA to 20 mA (3-wire)
DIN rail mount in-line amplifiers
DV-05
0 ±5 Vdc (3-wire)
DA-05
4 mA to 20 mA (3-wire)
DV-10
0 ±10 Vdc (3-wire)
Honeywell • Sensing and Control
3
Model HL-A-5
RANGE CODES
NOTES
Range
Code
Available
ranges
Range
Code
Available
ranges
BN
±50 psid
CT
±750 psid
BP
±75 psid
CV
±1000 psid
BR
±100 psid
DJ
±1500 psid
CJ
±150 psid
DL
±2000 psid
CL
±200 psid
DN
±3000 psid
CP
±300 psid
DR
±5000 psid
CR
±500 psid
DT
±7500 psid
WIRING CODES
Connector
Unamplified
A, B
(+) excitation
C, D
(-) excitation
E
(-) output
F
(+) output
1. Availability varies according to range.
2. Interconnecting shunt cal. 1 terminal with shunt cal. 2 terminal provides 50% (unamplified units), 75% (4 mA to 20 mA 3-wire units) or
80% (voltage amplified units of full scale output for quick calibration.
Shunt calibration comes standard with internal amplifier options 2b,
2c, 2t and 2j.)
3. O=Orange, Y=Yellow, B=Blue, Bl=Black, R=Red, Br=Brown,
W=White, G=Green. Color specifying cable and number or letter
specifying connector.
4. No mating connector necessary for cable option.
5. Some pressure port options may require axial orientation.
6. Only available with unamplified option 2u.
7. Only available with amplified options.
8. Only available with Vdc output options 2b, 2c.
9. Consult factory for TEDS availability with amplified models.
10. Range dependent; consult factory. Termination dependent; consult
factory.
11. Internal amp and termination dependent; consult factory.
Note: Unless otherwise specified on order, amplified units with 4 mA
to 20 mA output will provide 4 mA at 0 psid and 20 mA at positive full
scale and the unit will not operate in the negative direction. An available alternative is to specify 4 mA at negative full scale and 20 mA at
positive full scale. All amps add 2 in to amplifier housing.
** On units > 200 psid the sum of full scale pressure must be <= 9500
psi, on units < 200 psid consult factory
4 Honeywell • Sensing and Control
Model HL-A-5
High Line Wet/Wet Differential Pressure Transducer
Warranty. Honeywell warrants goods of its manufacture as
being free of defective materials and faulty workmanship.
Honeywell’s standard product warranty applies unless agreed
to otherwise by Honeywell in writing; please refer to your
order acknowledgement or consult your local sales office for
specific warranty details. If warranted goods are returned to
Honeywell during the period of coverage, Honeywell will repair
or replace, at its option, without charge those items it finds
defective. The foregoing is buyer’s sole remedy and is in lieu
of all warranties, expressed or implied, including those of
merchantability and fitness for a particular purpose. In no
event shall Honeywell be liable for consequential, special, or
indirect damages.
While we provide application assistance personally, through our
literature and the Honeywell web site, it is up to the customer to
determine the suitability of the product in the application.
Specifications may change without notice. The information we
supply is believed to be accurate and reliable as of this printing.
However, we assume no responsibility for its use.
WARNING
PERSONAL INJURY
• DO NOT USE these products as safety or emergency
stop devices or in any other application where failure of
the product could result in personal injury.
Failure to comply with these instructions could result in
death or serious injury.
Find out more
Honeywell serves its customers
WARNING
through a worldwide network of
MISUSE OF DOCUMENTATION
sales offices, representatives
• The information presented in this datasheet is for
reference only. DO NOT USE this document as product
installation information.
• Complete installation, operation and maintenance
information is provided in the instructions supplied with
each product.
and distributors. For application
assistance, current specifications, pricing or name of the
nearest Authorized Distributor,
contact your local sales office.
To learn more about Honeywell’s
test and measurement products,
Failure to comply with these instructions could result in
death or serious injury.
call +1-614-850-5000, visit
http://measurementsensors.
honeywell.com, or e-mail inquiries to info.tm@honeywell.com
Sensing and Control
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422 USA
www.honeywell.com/sensing
008716-2-EN IL50 GLO
December 2011
Copyright © 2011 Honeywell International Inc. All rights reserved.