Bradford White M-3-ST80R5 Jacketed Storage Tank (M-3) Manual

Bradford White M-3-ST80R5 Jacketed Storage Tank (M-3) Manual
STORAGE UNIT
A Spanish language version of these instructions is available by
contacting the manufacturer listed on the rating plate.
La version espanola de estas instrucciones se puede obtener al escribirle
a la fábrica cuyo nombre aparece in la placa de especificaciones.
INSTALLATION & OPERATING
INSTRUCTION MANUAL
THE WARRANTY ON THIS STORAGE UNIT IS IN EFFECT ONLY WHEN
THE STORAGE UNIT IS INSTALLED AND OPERATED IN ACCORDANCE
WITH LOCAL CODES AND THESE INSTRUCTIONS. THE
MANUFACTURER OF THIS STORAGE UNIT WILL NOT BE LIABLE FOR
ANY DAMAGE RESULTING FROM FAILURE TO COMPLY WITH THESE
INSTRUCTIONS. READ THESE INSTRUCTIONS THOROUGHLY BEFORE
STARTING.
For your family’s comfort, safety and convenience, it is
recommended this storage unit be installed and serviced by a
plumbing professional.
238-35768-00N REV 5/18
TABLE OF CONTENTS
General Information ................................................ 3
Installation ............................................................ 5
Locating The Storage Unit .................................. 5
Water Connections ............................................ 7
General Operation .................................................. 11
Maintenance .......................................................... 12
Typical Installations ................................................ 15
CONGRATULATIONS!
Notes ................................................................... 16
You have just purchased one of the finest storage units on the
market today!
This installation, operation and instruction manual will explain
in detail the installation and maintenance of your new Storage
Unit. We strongly recommend that you contact a plumbing
professional for the installation of this storage unit.
We require that you carefully read this manual, as well as the
enclosed warranty, and refer to it when questions arise. If you
have any specific questions concerning your warranty, please
consult the plumbing professional from whom your storage
unit was purchased. For your records we recommend that
you write the model, serial number and installation date of
your storage unit in the maintenance section in the back of
this manual.
This manual should be kept with the water heater.
2
GENERAL INFORMATION
This storage unit must be installed in accordance w ith local codes. In
the absence of local codes, install this storage unit in accordance w ith
the N.E.C. Reference Book (latest edition).
The w arranty for this storage unit is in effect only w hen the storage unit
is installed, adjusted, and operated in accordance w ith these Installation
and Operating Instructions. The manufacturer w ill not be held liable for
damage resulting from alteration and/or failure to comply w ith these
instructions.
These instructions apply only to this storage unit. Other components of
the system should be installed in accordance w ith the instructions
provided by the manufacturer.
State and local codes may supersede suggestions made in this
Installation and Operating Instruction manual.
This storage unit shall be used in conjunction w ith an existing w ater
heater or hot w ater boiler.
CAUTION
Incorrect operation of this appliance may create a hazard to life and
property and will nullify the warranty.
DANGER
Do not store or use gasoline or other flammable, combustible, or
corrosive vapors or liquids in the vicinity of this or any other
appliance.
A sacrificial anode(s) is used to extend tank life. Removal of any anode,
except for inspection and/or replacement, w ill nullify the w arranty. In
areas w here w ater is unusually active, an odor may occur at the hot
w ater faucet due to a reaction betw een the sacrificial anode and
impurities in the w ater. If this should happen, an alternative anode(s)
may be purchased from the supplier that installed this w ater heater. This
w ill minimize the odor w hile protecting the tank. Additionally, the w ater
heater should be flushed w ith appropriate dissolvers to eliminate any
bacteria.
3
General Information continued-
IMPORTANT
Before proceeding, please inspect the storage unit and it’ s components
for possible damage. DO NOT install any damaged components. If
damage is evident, please contact the supplier w here the storage unit
w as purchased or the manufacturer listed on the rating plate for
replacement parts.
Massachusetts Code Compliance:
If total tank volume exceeds 120 gallons and/or recovery rate is
200,000 btu/hr or greater, all system components shall be ASME.
Exception: Single family residences.
WARNING
This product contains one or more chemicals known to the State of
California to cause cancer, birth defects, or reproductive harm.
4
INSTALLATION
Locating The Storage Unit
WARNING
To avoid damage or injury, there shall be no materials stored against
the storage unit and proper care shall be taken to avoid unnecessary
contact (especially by children) w ith the storage unit . UNDER NO
CIRCUMSTANCES SHALL FLAMMABLE MATERIALS, SUCH AS
GASOLINE OR PAINT THINNER BE USED OR STORED IN THE VICINITY
OF THIS STORAGE UNIT OR ANY LOCATION FROM WHICH FUMES
COULD REACH THE STORAGE UNIT.
This storage unit must NOT be installed in any location where gasoline
or flammable vapors are likely to be present, unless the installation is
such to eliminate the probable ignition of gasoline or flammable vapors.
The location this storage unit is to be installed is of utmost importance.
Before installing this storage unit , consult the installation section of
these instructions. After reading these installation and operating
instructions, select a location for the storage unit w here the floor is level
and is easily accessible to a pow er supply and w ater connections. It is
recommended that the storage unit be located near the center of
greatest hot w ater usage to prevent heat loss through the pipes. DO
NOT locate the storage unit where water lines could be subjected to
freezing temperatures. Locate the storage unit so that access panels
and drain valves are accessible.
Storage unit corrosion and component failure can be caused by the
heating and breakdow n of airborne chemical vapors. Examples of some
typical compounds that are potentially corrosive are: spray can
propellants, cleaning solvents, refrigerator and air conditioning
refrigerants, sw imming pool chemicals, calcium or sodium chloride,
w axes and process chemicals. These materials are corrosive at very low
concentration levels w ith little or no odor to reveal their presence.
NOTE: DAMAGE TO THE STORAGE UNIT CAUSED BY EXPOSURE TO
CORROSIVE VAPORS IS NOT COVERED BY THE WARRANTY. DO NOT
OPERATE THE STORAGE UNIT IF EXPOSURE HAS OR WILL OCCUR.
DO NOT STORE ANY POTENTIALLY CORROSIVE COMPOUNDS IN THE
VICINITY OF THE STORAGE UNIT.
5
Locating The Storage Unit continued-
This storage unit must be located in an area w here leakage of the tank
or w ater line connections and the combination temperature and pressure
relief valve w ill not result in damage to the area adjacent to the storage
unit or to low er floors of the structure. When such locations cannot be
avoided, a suitable drain pan must be installed under the storage unit .
The drain pan must have a minimum length and w idth of at least 4 in.
(10.2 cm) greater than the diameter of the w ater heater. The drain pan,
as described above, can be purchased from your plumbing professional.
The drain pan must be piped to an adequate drain. The piping must be
at least 3/4 in (1.9 cm) in diameter and pitched for proper drainage.
This storage unit MUST be installed indoors out of the wind and
weather.
To comply w ith NSF requirements this w ater heater is to be:
a) Sealed to the floor w ith sealant, in a smooth and easily cleanable
w ay, or
b) Installed w ith an optional leg kit that includes legs and/or
extensions that provide a minimum clearance of 6 ’’ beneath the
w ater heater.
Note: For California installation this storage unit must be braced,
anchored, or strapped to avoid falling or moving during an earthquake.
See instructions for correct installation procedures. Instructions may be
obtained from the DSA Headquarters Office, 1102 Q Street, Suite 5100,
Sacramento, CA 95811.
6
Water Connections
NOTE: BEFORE PROCEEDING WITH THE INSTALLATION, CLOSE THE
MAIN WATER SUPPLY VALVE.
After shutting the main w ater supply valve, open a faucet to relieve the
w ater line pressure to prevent any w ater from leaking out of the pipes
w hile making the w ater connections to the storage unit. After the
pressure has been relieved, close the faucet. The fittings at the
circulating connections and the hot w ater outlet are dielectric w aterw ay
fittings w ith 2’’ NPT tapered male threads. Make the proper plumbing
connections betw een the storage unit and the plumbing system in the
structure. Install a shut -off valve in the cold w ater supply line.
CAUTION
If sw eat fittings are to be used, DO NOT apply heat to the nipples on
top of the storage unit. Sw eat the tubing to the adapter before fitting
the adapter to the w ater connections. It is imperative that heat is no t
applied to the nipples containing a plastic liner.
CAUTION
This storage unit does not contain a heat exchanger. Only potable
water may be allowed to enter the tank.
If this storage unit is installed in a closed w ater supply system, such as
the one having a back-flow preventer in the cold w ater supply,
provisions shall be made to control thermal expansion. DO NOT operate
this storage unit in a closed system w ithout provisions for controlling
thermal expansion. Your w ater supplier or local plumbing inspector
should be contacted on how to control this situation.
After installation of the w ater lines, open the main w ater supply valve
and fill the storage unit. While the storage unit is filling, open several
hot w ater faucets to allow air to escape from the w ater system. When
a steady stream of w ater flow s through the faucets, close them, and
check all w ater connections for possible leaks. NEVER OPERATE THE
STORAGE UNIT WITHOUT FIRST BEING CERTAIN IT IS FILLED WITH
WATER.
IMPORTANT
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED
TEMPERATURE-PRESSURE RELIEF VALVE WILL RELEASE THE
MANUFACTURER FROM ANY CLAIM WHICH MIGHT RESULT FROM
EXCESSIVE TEMPERATURE AND PRESSURES.
7
Water Connections continued-
WARNING
For protection against excessive temperatures and pressure, install
temperature and pressure protective equipment required by local
codes, but not less than a combination temperature and pressure relief
valve certified by a nationally recognized testing laboratory that
maintains periodic inspection of production of listed equipment or
materials, as meeting the Requirements for Relief Valves and
Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI
Z21.22, and the Standard CAN1-4.4 Temperature, Pressure,
Temperature and Pressure Relief Valves and Vacuum Relief Valves.
The combination temperature and pressure relief valve shall be marked
w ith a maximum set pressure, not to exceed the maximum w orking
pressure of the storage unit. The combination temperature and
pressure relief valve shall also have an hourly rated temperature steam
BTU discharge capacity not less than the hourly input rating of the
w ater heater or boiler used in conjunction w ith this storage unit.
Install the combination temperat ure and pressure relief valve into the
opening provided and marked for this purpose on the storage unit.
Note: Some models may already be equipped or supplied w ith a
combination temperature and pressure relief valve. Verify that the
combination temperat ure and pressure relief valve complies w ith local
codes. If the combination temperature and pressure relief valve does
not comply w ith local codes, replace it w ith one that does. Follow the
installation instructions above on this page.
Install a discharge line so that w ater discharged from the combination
temperature and pressure relief valve w ill exit w ithin six (6) inches
(15.3 cm) above, or any distance below the structural floor and
cannot contact any live electrical part. The discharge line is to b e
installed to allow for complete drainage of both the temperature and
pressure relief valve and the discharge line. The discharge opening
must not be subjected to blockage or freezing. DO NOT thread, plug
or cap the discharge line. It is recommended that a minimum of four
(4) inches (10.2 cm) be provided on the side of the storage unit for
servicing and maintenance of the combination temperature and
pressure relief valve.
Do not place a valve betw een the combination temperature and
pressure relief valve and the tank.
8
Water Connections continued-
WARNING
Hydrogen gas can be produced in a hot water system served by this
storage unit that has not been used for a long period of time
(generally two weeks or more). Hydrogen gas is extremely
flammable. To reduce the risk of injury under these conditions, it is
recommended that the hot water faucet be opened for several
minutes at the kitchen sink before using any electrical appliance
connected to the hot water system. If hydrogen is present, there will
probably be an unusual sound such as air escaping through the pipe
as the water begins to flow. There should be no smoking or open
flame near the faucet at the time it is open.
This storage unit can deliver scalding temperature w ater at any faucet in
the system. Be careful w henever using hot w ater to avoid scalding
injury. Certain appliances, such as dishw ashers and automatic clothes
w ashers, may require increased temperature w ater. By setting the
thermostat in the w ater heating system to obtain increased temperature
w ater required by these appliances, you might create the potential for
scald injury. To protect against injury, you should install an ASSE
approved mixing valve in the w ater system. This valve w ill reduce point
of discharge temperature by mixing cold and hot w ater in branch supply
lines. Such valves are available from the manufacturer of this storage
unit or a local plumbing supplier. Please consult w ith a plumbing
professional.













9
Water Connections continued-
10
GENERAL OPERATION
CAUTION
Under certain conditions, w ater in this w ater heater/storage unit may
become excessively hot. It is recommended that an ASSE approved
mixing valve may be installed in the outlet line to reduce the risk of
scald injury by preventing point of discharge w ater temperatures in
excess of 140° F (60° C).
Care must be taken w henever using hot w ater to avoid scalding injury.
Certain appliances require high temperature hot w ater (such as
dishw ashers and automatic clothes w ashers).
TO
1.
2.
3.
FILL THE STORAGE UNIT
Close the w ater heater drain valve by turning the knob clockw ise.
Open the cold w ater supply shut -off valve.
Open several hot w ater faucets to allow air to escape from the
system.
4. When a steady stream of w ater flow s from the faucets, the storage
unit is filled. Close the faucets and check for w ater leaks at the
storage unit drain valve, combination temperature and pressure relief
valve and the hot and cold w ater connections.
TO DRAIN THE STORAGE UNIT
1. Close the cold w ater supply shut -off valve.
2. Open the drain valve on the w ater heater by turning the knob
counter-clockw ise. The drain valve has threads on the end that w ill
allow connection of a standard hose coupling.
3. Open a hot w ater faucet to allow air to enter the system.
To refill the storage unit , refer to ‘‘ TO FILL THE STORAGE UNIT’’ .
11
MAINTENANCE
IMPORTANT
The storage unit should be inspected at a minimum of annually by a
qualified service technician for damaged components. DO NOT
operate this storage unit if any part is found damaged.
The storage unit should be drained completely to prevent freezing
w henever the building is left unoccupied during the cold w eather
months. In order to insure efficient operation and long tank life, drain
the storage unit at least once a month through the drain valve until the
w ater runs clear. Failure to do this may result in noisy operation and
lime and sediment buildup in the bottom of the tank. Check the
temperature-pressure relief valve to insure that the valve has not
become encrusted w ith lime. Lift the lever at the top of the valve
several times until the valve seats properly w ithout leaking and operates
freely.
WARNING
When lifting lever of temperature-pressure relief valve, hot w ater w ill
be released under pressure. Be certain that any released w ater does
not result in bodily injury or property damage. The magnesium anode
rod should be inspected periodically and replaced w hen necessary to
prolong tank life.
The follow ing maintenance checks should be performed by a qualified
service technician at the minimum periodic intervals suggested below .
In some installations, the maintenance interval may be more frequent
depending on the amount of use and the operating conditions of the
w ater heater. Regular inspection and maintenance of the storage unit
w ill help to insure safe and reliable operation.
1. At least once a year, check the combination temperature and
pressure relief valve to insure that the valve has not become
encrusted w ith lime. Lift the lever at the top of the temperaturepressure relief valve several times until the valve seats properly
w ithout leaking and operates freely.
2. If the combination temperature and pressure relief valve on the
appliance discharges periodically, t his may be due to thermal
expansion in a closed w ater supply system. Contact the w ater
supplier or local plumbing inspector on how to correct this situation.
Do not plug the combination temperature and pressure relief valve
outlet for any reason.
12
Maintenance continued-
WARNING
When lifting lever of temperature-pressure relief valve, hot w ater w ill
be released under pressure. Be certain that any released w ater does
not result in bodily injury or property damage.
3. Monthly, drain off a gallon of w ater from the storage unit to remove
silt and sediment.
WARNING! THIS WATER MAY BE HOT.
4. A combination sacrificial anode rod/hot w ater outlet nipple has been
installed to extend tank life. The anode rod should be inspected
periodically (every 2 years) and replaced w hen necessary to prolong
tank life. Water conditions in your area w ill influence the time
interval for inspection and replacement of the anode rod. Contact the
plumbing professional w ho installed the storage unit or the
manufacturer listed on the rating plate for anode replacement
information. The use of a w ater softener may increase the speed of
anode consumption. More frequent inspection of the anode is needed
w hen using softened (or phosphate treated) w ater.
CAUTION
FOR YOUR SAFETY, DO NOT ATTEMPT TO REPAIR ANY DAMAGED
COMPONENTS. REFER SUCH REPAIRS TO A QUALIFIED SERVICE
TECHNICIAN.
13
Maintenance continued-
Contact your local plumbing supplier or plumbing professional for
replacement parts or contact the company at the address displayed on
the rating plate of the storage unit.
For faster and better service, please provide the part name, model, and
serial number(s) of the storage unit (s) w hen ordering parts.
READ THE WARRANTY FOR A FULL EXPLANATION OF THE LENGTH
OF TIME THAT PARTS AND THE WATER HEATER ARE WARRANTED.
Manufactured under one or more of the follow ing U.S. Patents: RE.34,534;
B1 5,341,770; 4,416,222; 4,628,184; 4,669,448; 4,672,919; 4,808,356;
4,829,983; 4,861,968; 4,904,428; 5,000,893; 5,023,031; 5,052,346;
5,081,696; 5,092,519; 5,115,767; 5,199,385; 5,27 7,171; 5,372,185;
5,485,879; 5,574,822; 5,596,952; 5,660,165; 5,682,666; 5,761,379;
5,943,984; 5,954,492; 5,988,117; 6,142,216; 6,684,821; 7,063,132;
Other U.S. and Foreign patent applications pending. Current Canadian Patents:
1,272,914; 1,280,043; 1,289,832; 2,045,862; 2,092,105; 2,107,012;
2,108,186; 2,112,515
Complete the follow ing information and retain for future reference:
Model No:
Serial No:
Service Phone
Days:
Nights:
Address:
Supplier:
Supplier Phone No:
14
TYPICAL INSTALLATIONS
15
NOTES
16