ICP I-7532 Quick start guide

ICP I-7532 Quick start guide
The I-7532 CAN Bridge
Quick Start User Guide
This user guide describes how to implement the I-7532 module
into users’ applications in a quick and easy way. Therefore, it only
provides the basic concepts. If users want to know more detail
information about the I-7532, please refer to the user manual in the
product CD or visit our website as follow:
http://www.icpdas.com/products/Remote_IO/can_bus/i-7532.htm
1. Introduction ................................................................................................2
2. LED Status..................................................................................................3
3. Wire Connection ........................................................................................4
4. Terminator Resistor Setting ......................................................................5
I-7532 CAN Bridge QuickStart(ver. 1.0, 2008/08/25) ------1
1. Introduction
I-7532 is a local CAN bridge used to establish a connection
between two CAN bus system in a CAN network. The I-7532
stands by itself connecting adjacent wiring segments together as in
the case of a CAN repeater (I-7531). Not just like a CAN repeater,
I-7532 has more powerful features (Extend Network Distance and
Connect two networks with different baud rate).
I-7532 CAN Bridge QuickStart(ver. 1.0, 2008/08/25) ------2
2. LED Status
1.PWR
2.CH1 ERR , CH2 ERR
PWR LED (Red Light)
ON
Power On
OFF
Power off
ERR LED(Red Light)
When the I-7532 is active, the PWR
Flashing
(100ms)
Transmission Fail
Flashing (1sec)
Buffer overflow
ON
Bus Off
OFF
No Error
LED will turn on with red light.
(1).Transmission Fail :If the message
Flashing
Transmission
OFF
Bus Idle
FG2
CAN_L
CAN_H
CAN CH 1
11 CAN_GND
Rx LED(Green Light)
CAN_GND
FG1
CAN_H
20
3.CH1 RX, CH2 RX
CAN_L
transmission fails on channel(X), the
CAN CH 2
CH(X) ERR LED will flash continuously,
and the flashing interval is about 100
millisecond.
(2).Buffer overflow : If Tx buffer on
PWR
channel (X) had been overflow, the CH(X)
CH1 ERR
If there are messages passed
i-7532
CH1 Rx
through I-7532 from channel 1 to
CH2 ERR
ERR LED would flash continuously, and
CH2 Rx
CAN Bus Bridge
channel 2, the CH1 Rx LED will
the flashing interval is about 1 second. No
‧Support CAN 2.0A/2.0B
‧Selectable 120O terminator resistor
‧Rotary switch value & Baud :
flash once with green light, and
vice versa.
RSW
1
2
Baud
5K
10K
20K
RSW
9
A
B
Baud
3
4
5
6
7
matter the status is already fixed or not,
8
40K
50K
80K
100K 125K
C
D
E
F
200K 250K 400K 500K 600K 800K
after users click the RST button, the LED
will be off.
1M
3KV VDC Isolation on each CAN side
(B)GND
(R)VS+
FG3
RST &
Err Clear
CH2 Baud
CH1 Baud
1
10
(3).Bus Off:If the CAN bus connected to
channel (X) of I-7532 is bus off, the CH(X)
ERR LED will be ON until corrected.
5.RST & Err Clear
Reset & Error Clear Button
4.CH1 Baud, CH2 Baud
Click
Baud Switch
switch
0
1
2
3
4
5
6
7
Baud[bps]
N/A
5k
10k
20k
40k
50k
80k
100k
switch
8
9
A
B
C
D
E
F
Baud[bps]
125k
200k
250k
400k
500k
600k
800k
1M
Users can use the “Baud Switch” to change the CAN1 and CAN2 baud.
There are 15 kinds of baud can be chosen. After changing the switch
Press 3 sec
Clear Error LED
Module Reset
(1).Error Clear:Users can click this button to
clear the ERR LED status.
(2).Module Reset:If users want to restart the
I-7532, press this button until 3 sec and all of
LED on I-7532 will flash once about 0.8 sec.
value, users must reset Module to take the setting effect (press RST
button until 3 sec).
I-7532 CAN Bridge QuickStart(ver. 1.0, 2008/08/25) ------3
3. Wire Connection
CAN CH 1
1
20
CAN_H
CAN CH 1
CAN_H
POWER
Earth Ground
FG1
CAN_L
CAN_L
CAN_GND
CAN_GND
CAN_H
CAN CH 2
Earth Ground
FG3
+10VDC ~ +30VDC
Power Ground
(R)VS+
CAN_H
Earth Ground
FG2
CAN_L
CAN_GND
CAN_L
(B)GND
10
11 CAN_GND
CAN CH2
Part
Name
Description
CAN CH 1
CAN_GND
CAN_Ground, ground voltage level of CAN channel 1.
CAN_L
CAN_Low, signal line of CAN channel 1.
FG1
Frame Ground of CAN channel 1.
CAN_H
CAN_High, signal line of CAN channel 1.
CAN_GND
CAN_Ground, ground voltage level of CAN channel 2.
CAN_L
CAN_Low, signal line of CAN channel 2.
FG2
Frame Ground of CAN channel 2.
CAN_H
CAN_High, signal line of CAN channel 2.
(R)VS+
Voltage Source. It could be +10VDC ~ +30VDC.
(B)GND
Power Ground.
FG3
Frame Ground of Power.
CAN CH 2
Power
I-7532 CAN Bridge QuickStart(ver. 1.0, 2008/08/25) ------4
4. Terminator Resistor Setting
The I-7532 module includes two build-in 120Ω terminal resistors, users
can decide to enable those two terminator resistors or not.
The JP4 of I-7532 is used to adjust terminal resistor on CAN Channel 1,
and the JP3 of I-7532 is used to adjust terminal resistor on CAN Channel 2.
Before adjusting JP3 or JP4 of I-7532, users need to open the cover of
I-7532 first. Those locations of JP3 and JP4 are shown as follows:
JP4
JP3
The following connection statuses present the condition if the terminal
resistor is enabled (default) or disabled.
Disable
(Deactivate)
Enable
(Activate)
I-7532 CAN Bridge QuickStart(ver. 1.0, 2008/08/25) ------5