Generac 20kW RD02023GDSE Standby Generator Manual

Add to my manuals
2 Pages

advertisement

Generac 20kW RD02023GDSE Standby Generator Manual | Manualzz
4
NOTES:
B
SH
3
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1092 (43") WIDE X 2355 (93") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT FOR CONCRETE PAD GUIDELINES.
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF GENERATOR.
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTION INCLUDING TRANSFER SWITCH CONTROL WIRES
AND ACCESSORY RELAY CONNECTION (QTY 4)
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
7. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 24 INCHES H2O.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO MOUNTING SURFACE SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
SERVICE ITEM
2.3L
1/2
REV
A
WINDCHILL VERSION
A.1
OIL FILL CAP
RIGHT SIDE
OIL DIP STICK
RIGHT SIDE
GENERATOR AS SHOWN (STEEL ENCL)
667 [1470]
OIL FILTER
RIGHT SIDE
WITH WODDEN SHIPPING SKID
707 [1555]
OIL DRAIN HOSE
RIGHT SIDE
RADIATOR DRAIN HOSE
LEFT SIDE
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
AIR CLEANER ELEMENT EITHER SIDE
MUFFLER
FRONT
FAN BELT
EITHER SIDE
BATTERY
LEFT SIDE
1
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
2" O.D. EXHAUST
OUTLET
212 [8.3]
B
REMOVE PANEL TO ALLOW
TANK VENTS TO TERMINATE OUTSIDE
OF THE GENERATOR ENCLOSURE
(CHECK LOCAL AND
STATE CODE FOR APPLICABILITY)
INTERNAL DIVIDER PANEL
SEPARATES FUEL TANK VENTILATION
DUCT FROM THE ENGINE,
ALTERNATOR AND EXHAUST SYSTEM.
BATTERY 12 VOLT
NEGATIVE GROUND
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
TOP VIEW
LIFT OFF DOOR PROVIDES ACCESS TO:
FUEL FILL, FUEL LEVEL GAUGE,
NORMAL VENT, INNER TANK EMERGENCY
VENT, OUTER TANK EMERGENCY VENT,
OPTIONAL 90% ALARM ASSEMBLY,
OPTIONAL 5 GALLON SPILL BOX
VISE ACTION LATCH,
ONE PER DOOR, ONE LIFT-OFF
DOOR ON FRONT, RIGHT, AND LEFT SIDES
927 [36.5]
CENTER OF GRAVITY SEE NOTE 5
580 [22.8]
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
FUEL TANK
VENTILATION DUCT
CIRCUIT BREAKER
SEE NOTE 3
1276
[50.2]
OVERALL
HEIGHT
CUSTOMER ACCESS
ASSEMBLY. CONTROL
PANEL ACCESS.
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
397
[15.6]
REAR TANK COVER
SEE NOTE 4
LIFTING PROVISION (4 PLACES)
SEE NOTES 5, 8 AND CENTER OF GRAVITY DIMENSIONS
A
100
[3.9]
776 [30.6]
OVERALL WIDTH
1841 [72.5]
2050 [80.7]
OVERALL LENGTH
A
LEFT SIDE VIEW
FRONT VIEW
RIGHT SIDE VIEW
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE
OPEN PUNCHED LOUVERS TYPICAL
ON BOTH SIDES OF
FUEL TANK VENTILATION
DUCT TO PROVIDE ADEQUATE
CROSS-FLOW OF AIR VENTILATION
3
2
INSTALL PROTECTOR D2.3L G16
EXT TANK
ISSUE DATE:
SIZE
B
SCALE
10/2013
CAGE NO
DWG NO
N/A
0.050
0K4894
WT-KG
SHEET
1
REV
1 of 2
A
4
SH
3
2/2
REV
A
WINDCHILL VERSION
A.1
1
FUEL TANK
1722 [67.8]
1632 [64.2]
1310 [51.6]
231 [9.1]
INNER TANK NORMAL VENT
(2" NPT FEMALE)
FUEL
RETURN
106 [4.2]
OUTER TANK LEAK DETECTOR
FUEL
SUPPLY
127 [33.5]
USABLE CAPACITY
121 [32]
CAPACITY: LITER [GALLON]
DIMENSIONS: MM [INCH]
TANK IS LISTED TO UL142 AND ULC/ORD-C142.18
907 [35.7]
356 [14.0]
TOTAL CAPACITY
CUSTOMER OPTION
2" NPT FEMALE
OUTER TANK EMERGENCY VENT
(2" NPT FEMALE)
B
B
HIGH AND LOW VOLTAGE
STUB-UP AREA
624
[24.6] 574
TYP [22.6]
464
TYP
[18.3]
CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER
639
559
CONNECTION OPENING
[25.2]
[22.0]
292
[11.5]
105 [4.1]
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
210 [8.3]
285
[11.2]
FUEL FILL
(2" NPT FEMALE)
674
[26.5]
STUB-UP
AREA
11
[.4]
50 [2.0]
FUEL LEVEL
GAUGE/SENDER
51
[2.0]
100 [3.9]
1807 [71.1]
200 [7.9]
STUB-UP
AREA
496 [19.5]
A
110 [4.3] TYP
19 [.7]
739 [29.1] TYP
A
739 [29.1]
MOUNTING CENTERS
1368 [53.9] TYP
776 [30.6]
1950 [76.8] TYP
2050 [80.7]
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
INSTALL STUB-UP VIEW PROTECTOR D2.3L
EXT TANK
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
3
2
ISSUE DATE:
SIZE
CAGE NO
SCALE
0.075
B
DWG NO
0K4894
WT-KG
SHEET
1
REV
2 of 2
A

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Download PDF

advertisement