Generac 20kW RD02023JDSE Standby Generator Manual

Generac 20kW RD02023JDSE Standby Generator Manual
4
B
SH
3
SERVICE ITEM
2.4L
NOTES:
OIL FILL CAP
LEFT SIDE
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718 (107") LONG.
REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE, AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
AND ACCESSORY RELAY CONNECTION (QTY 4)
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
AND RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H2O.
9. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
OIL DIP STICK
LEFT SIDE
VISE ACTION LATCH,
ONE PER DOOR, ONE LIFT-OFF
DOOR PER SIDE OF GENERATOR
OIL FILTER
RIGHT SIDE
OIL DRAIN HOSE
LEFT SIDE
RADIATOR DRAIN HOSE
LEFT SIDE
AIR CLEANER ELEMENT
LEFT SIDE
MUFFLER
FRONT
FAN BELT
EITHER SIDE
BATTERY
LEFT SIDE
1/2
REV
WINDCHILL VERSION
A
A.1
1
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 6)
GENERATOR AS SHOWN (STEEL ENCL)
860 [1895]
WITH WOODEN SHIPPING SKID
905 [1995]
INTERNAL DIVIDER PANEL
SEPARATES FUEL TANK VENTALATION
DUCT FROM THE ENGINE,
ALTERNATOR AND EXHAUST SYSTEM
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
REMOVE PANEL TO ALLOW
TANK VENTS TO TERMINATE OUTSIDE
OF THE GENERATOR ENCLOSURE
(CHECK LOCAL AND
STATE CODE FOR APPLICABILITY)
B
171 [6.7]
REMOVE COVER
FOR ACCESS TO
RADIATOR FILL CAP
618 [24.3]
LIFT OFF DOOR PROVIDES ACCESS TO:
FUEL FILL, FUEL LEVEL GAUGE,
NORMAL VENT, INNER TANK EMERGENCY
VENT, OUTER TANK EMERGENCY VENT,
OPTIONAL 90% ALARM ASSEMBLY,
OPTIONAL 5 GALLON SPILL BOX
BATTERY 12 VOLT
NEGATIVE GROUND
FRONT VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
758 [29.8]
DOOR TYP
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
FUEL TANK
VENTILATION DUCT
CIRCUIT BREAKER
SEE NOTE 3
CUSTOMER ACCESS
ASSEMBLY. CONTROL
PANEL ACCESS.
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
1409
[55.5]
OVERALL
HEIGHT
REAR TANK COVER
SEE NOTE 4
254
[10.0]
LIFTING PROVISION (4 PLACES)
SEE NOTE 9 AND CENTER OF GRAVITY DIMENSIONS
A
102
[4.0]
888 [35.0]
OVERALL WIDTH
2212 [87.1]
2424 [95.4]
OVERALL LENGTH
FRONT VIEW
OPEN PUNCHED LOUVERS TYPICAL
ON BOTH SIDES OF
FUEL TANK VENTALATION
DUCT TO PROVIDE ADEQUATE
CROSS-FLOW OF AIR VENTALATION
EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE
LEFT SIDE VIEW
RIGHT SIDE VIEW
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
INSTALL CPL PROT D2.4L EXT
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
A
3
2
ISSUE DATE:
SIZE
CAGE NO
SCALE
0.050
B
DWG NO
0K4893
WT-KG
SHEET
1
REV
1 of 2
A
4
SH
3
2/2
REV
A
WINDCHILL VERSION
A.1
1
2088 [82.2]
351 [13.8]
228 [9.0]
INNER TANK NORMAL VENT
(2" NPT FEMALE)
16.7 [.66] MOUNTING HOLES
(10 PLACES) SEE NOTE 10
FUEL RETURN
FUEL SUPPLY
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
101 [4.0]
OUTER TANK LEAK DETECTOR
TANK P/N
0K07080ST03
TOTAL CAPACITY
233 [61]
USABLE CAPACITY
203 [55]
CAPACITY: LITER [GALLON]
DIMENSIONS: MM [INCH]
UL # 142 LISTED
OUTER TANK EMERGENCY VENT
(2" NPT FEMALE)
HIGH AND LOW VOLTAGE
STUB-UP AREA
B
B
CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER
CONNECTION OPENING
784 [30.9]
STUB-UP
AREA
717 [28.2]
620 [24.4] TYP
TYP
660 [26.0]
TYP
487 [19.2]
282 [11.1]
266
[10.5]
162 [6.4]
FUEL LEVEL
GAUGE/SENDER
214
[8.4]
9 [.4]
314 [12.4]
51 [2.0]
1290 [50.8] TYP
1385 [54.5] TYP
148 [5.8]
2226 [87.6]
196 [7.7]
STUB-UP
AREA
850 [33.5]
353 [13.9]
110 [4.3]
TYP
19 [.7]
851 [33.5]
TYP
655 [25.8] TYP
1208 [47.5] TYP
1761 [69.3] TYP
A
A
2314 [91.1] TYP
2424
[95.4]
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
INSTALL STUB-UP VIEW CPL PROT D2.4L
EXTENDED TANK
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
3
2
ISSUE DATE:
SIZE
CAGE NO
SCALE
0.075
B
DWG NO
0K4893
WT-KG
SHEET
1
REV
2 of 2
A