Generac 48kW RD04834ADAL Standby Generator Manual

Generac 48kW RD04834ADAL Standby Generator Manual
4
SH
3
REMOVE PANEL TO ALLOW TANK
VENTS TO TERMINATE OUTSIDE
OF THE GENERATOR ENCLOSURE
(CHECK LOCAL AND STATE
CODE FOR APPLICABILITY)
998 [39.3]
CENTER OF GRAVITY
SEE NOTE 5
3.4L
OIL FILL CAP
RIGHT SIDE
OIL DIP STICK
RIGHT SIDE
OIL FILTER
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
SERVICE ITEM
1/2
REV
A
WINDCHILL VERSION
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
GENERATOR AS SHOWN
1094 [2411]
RIGHT SIDE WITH WOODEN SHIPPING SKID
1139 [2511]
OIL DRAIN HOSE
RIGHT SIDE
RADIATOR DRAIN HOSE
LEFT SIDE
WEIGHT: KG [LBS]
DIMENSIONS: MM [INCH]
AIR CLEANER ELEMENT RIGHT SIDE
INTERNAL DIVIDER PANEL
SEPARATES FUEL TANK
VENTILATION DUCT FROM
THE ENGINE ALTERNATOR
AND EXHAUST SYSTEM
MUFFLER
FRONT
FAN BELT
EITHER SIDE
BATTERY
LEFT SIDE
REFERENCE OWNERS MANUAL FOR
PERIODIC REPLACEMENT PART LISTINGS
B
172.6 [6.8]
EXHAUST OUTLET
618.3 [24.3]
EXHAUST OUTLET
REMOVE COVER FOR ACCESS
TO RADIATOR FILL CAP
A.2
BATTERY 12 VOLT
NEGATIVE GROUND
1
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718
(107") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSURE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION,
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
9. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
TOP VIEW
RADIATOR/EXHAUST
DISCHARGE AIR
897.2 [35.3]
DOOR WIDTH
TYP
LIFT-OFF DOOR PROVIDES ACCESS TO: FUEL FILL, FUEL
LEVEL GAUGE, NORMAL VENT, INNER TANK EMERGENCY
VENT, OUTER TANK EMERGENCY VENT, OPTIONAL 90%
ALARM ASSEMBLY AND OPTIONAL 5 GALLON SPILL BOX
VISE ACTION LATCH, ONE PER
DOOR AND ONE LIFT-OFF DOOR
PER SIDE OF GENERATOR
REAR ENCLOSURE
COVER PANEL
SEE NOTE 4
B
CUSTOMER ACCESS
ASSEMBLY, CONTROL
PANEL ACCESS AND
BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
FUEL TANK
VENTILATION DUCT
CIRCUIT BREAKER
SEE NOTE 3
1690.9 [66.6]
OVERALL
HEIGHT
OPEN PUNCHED LOUVERS
TYPICAL ON BOTH
SIDES OF FUEL TANK
VENTILATION DUCT TO
PROVIDE ADEQUATE
CROSS-FLOW OF AIR
VENTILATION
REAR TANK
COVER PANEL
SEE NOTE 4
581 [22.9]
TYP
EXHAUST MUFFLER ENCLOSED
WITHIN GENERATOR ENCLOSURE
A
LIFTING PROVISIONS, SEE NOTE 5, 8
AND CENTER OF GRAVITY DIMENSION
(4 PLACES)
888.1 [35.0]
OVERALL WIDTH
181.9 [7.2]
TYP
2423.9 [95.4]
OVERALL LENGTH
REAR VIEW
LEFT SIDE VIEW
A
RIGHT SIDE VIEW
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
1625 [64.0]
TYP
3
2
INSTALL PROTECTOR D3.4L G16
132 GAL TANK
ISSUE DATE:
SIZE
B
SCALE
08/2018
CAGE NO
DWG NO
N/A
0.050
WT-KG
10000043316
SEE ABOVE SHEET
1
REV
1 of 2
A
4
SH
3
376.5 [14.8]
314 [12.4]
246.5 [9.7]
2/2
REV
A
WINDCHILL VERSION
A.2
1
INNER TANK NORMAL VENT
(3" NPT FEMALE)
INNER TANK EMERGENCY VENT
(3" NPT FEMALE)
OUTER TANK
LEAK DETECTOR
FUEL LEVEL
GAUGE/SENDER
116.6 [4.6]
FUEL TANK
OUTER TANK EMERGENCY VENT
(3" NPT FEMALE)
HIGH AND
LOW VOLTAGE
STUB-UP AREA
B
125 [4.9]
*STUB-UP
AREA
657.9 [25.9]
TYP
484.7 [19.1]
166.9 [6.6]
500 [132]
B
THIS TANK IS LISTED TO UL142 AND ULC5601
*NOTE: STUB-UP AREA FOR HIGH AND LOW
VOLTAGE CONNECTIONS, CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER CONNECTION OPENING.
279.9 [11.0]
263.9 [10.4]
TYP
524 [138.5]
USABLE CAPACITY
CAPACITY: LITER [GALLONS]
DIMENSIONS: MM [INCH]
786 [30.9]
714.9 [28.1]
TOTAL CAPACITY
FUEL FILL
(3" NPT FEMALE)
CUSTOMER OPTION
(3" NPT FEMALE)
FUEL RETURN
246.5 [9.7]
38 [1.5]
51.1 [2.0]
FUEL SUPPLY
1307.6 [51.5]
125 [4.9]
*STUB-UP
AREA
1418.4 [55.8]
2088.4 [82.2]
TYP
2159.6 [85.0]
62.4 [2.5]
253.3 [10.0]
850.1 [33.5]
TOP VIEW
REAR TANK
COVER PANEL
SEE NOTE 4
529.3 [20.8]
FUEL TANK
HEIGHT
110 [4.3]
TYP
632 [24.9]
16.7 [.66] MOUNTING HOLES
(10 PLACES)
18.5 [.7]
TYP
690 [27.2]
TYP
1216 [47.9]
TYP
851.1 [33.5]
MOUNTING CENTERS
TYP
SEE NOTE 9
888.1 [35.0]
1769 [69.6]
TYP
2322 [91.4]
TYP
A
A
REAR VIEW
2423.9 [95.4]
LEFT SIDE VIEW
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
3
2
INSTALL PROTECTOR D3.4L G16
132 GAL TANK
ISSUE DATE:
SIZE
B
SCALE
08/2018
CAGE NO
DWG NO
N/A
0.050
WT-KG
10000043316
SEE ABOVE SHEET
1
REV
2 of 2
A