Generac 50kW RD05034GDAL Standby Generator Manual

Add to my manuals
2 Pages

advertisement

Generac 50kW RD05034GDAL Standby Generator Manual | Manualzz
4
REMOVE PANEL TO
ALLOW TANK VENTS
TO TERMINATE OUTSIDE
OF THE GENERATOR
ENCLOSURE (CHECK LOCAL
AND STATE CODE FOR
APPLICABILITY)
SH
3
INTERNAL DIVIDER PANEL
SEPARATES FUEL TANK VENTILATION
DUCT FROM THE ENGINE,
ALTERNATOR AND EXHAUST SYSTEM
998 [39.3]
CENTER OF GRAVITY
SEE NOTE 5
AIR INTAKE
(BOTH SIDES)
RADIATOR/EXHAUST
DISCHARGE AIR
(BOTH SIDES)
1/2
REV
A
WINDCHILL VERSION
SERVICE ITEM
3.4L
OIL FILL CAP
RIGHT SIDE
OIL DIP STICK
RIGHT SIDE
GENERATOR AS SHOWN (STEEL ENCL)
WITH WOODEN SHIPPING SKID
OIL FILTER
RIGHT SIDE
OIL DRAIN HOSE
RIGHT SIDE
RADIATOR DRAIN HOSE
LEFT SIDE
AIR CLEANER ELEMENT
RIGHT SIDE
MUFFLER
FRONT
FAN BELT
EITHER SIDE
BATTERY
LEFT SIDE
A.1
1
WEIGHT DATA WITH EMPTY BASETANK
(SEE NOTE 5)
997 [2197]
1042 [2297]
NOTES:
1. MINIMUM RECOMMENDED CONCRETE PAD SIZE: 1194 (47") WIDE X 2718
(107") LONG. REFERENCE INSTALLATION GUIDE SUPPLIED WITH UNIT
FOR CONCRETE PAD GUIDELINES
2. ALLOW SUFFICIENT ROOM ON ALL SIDES OF THE GENERATOR FOR MAINTENANCE
AND SERVICING. THIS UNIT MUST BE INSTALLED IN ACCORDANCE WITH CURRENT
APPLICABLE NFPA 37 AND NFPA 70 STANDARDS AS WELL AS ANY OTHER FEDERAL,
STATE AND LOCAL CODES.
3. CONTROL PANEL / CIRCUIT BREAKER INFORMATION:
- SEE SPECIFICATION SHEET OR OWNERS MANUAL
- ACCESSIBLE THROUGH CUSTOMER ACCESS ASSEMBLY DOOR ON REAR OF
GENERATOR
4. REMOVE THE REAR TANK AND REAR ENCLOSRE COVER PANEL TO ACCESS
THE STUB-UP AREAS AS FOLLOWS:
- HIGH VOLTAGE CONNECTION INCLUDING AC LOAD LEAD CONDUIT CONNECTION
NEUTRAL CONNECTION, BATTERY CHARGER 120 VOLT AC (0.5 AMP MAX) CONNECTION.
- LOW VOLTAGE CONNECTIONS INCLUDING TRANSFER SWITCH CONTROL WIRES
5. CENTER OF GRAVITY AND WEIGHT MAY CHANGE DUE TO UNIT OPTIONS.
6. ENGINE SERVICE CONNECTIONS
OIL DRAIN: 3/8" NPT
EXHAUST OUTLET: 2" O.D.
7. BOTTOM OF GENERATOR SET MUST BE ENCLOSED TO PREVENT PEST INTRUSION AND
RECIRCULATION OF DISCHARGE AIR AND/OR IMPROPER COOLING AIR FLOW.
8. EXHAUST SYSTEM MAXIMUM BACK PRESSURE: 35 INCHES H2O.
9. REFERENCE OWNERS MANUAL FOR LIFTING WARNINGS.
10. MOUNTING BOLTS OR STUDS TO CONCRETE PAD SHALL BE 5/8-11 GRADE 5
(USE STANDARD SAE TORQUE SPECS)
REFERENCE OWNERS MANUAL FOR PERIODIC
REPLACEMENT PART LISTINGS.
B
173 [6.8]
618 [24.3]
LIFT-OFF DOOR PROVIDES ACCESS TO:
FUEL FILL, FUEL LEVEL GAUGE,
NORMAL VENT, INNER TANK
TOP VIEW
EMERGENCY VENT, OUTER TANK
RADIATOR/EXHAUST
EMERGENCY VENT, OPTIONAL
DISCHARGE AIR
90% ALARM ASSEMBLY,
OPTIONAL 5 GALLON SPILL
758 [29.8]
BOX
DOOR TYP
VICE ACTION LATCH,
ONE PER DOOR, LIFT-OFF
DOORS ON FRONT, RIGHT, AND LEFT SIDES
B
LIFTING PROVISIONS (4 PLACES)
SEE NOTES 5, 9, AND CENTER
OF GRAVITY DIMENSIONS
REAR ENCLOSURE COVER
PANEL
SEE NOTE 4
CIRCUIT BREAKER
SEE NOTE 3
CUSTOMER ACCESS
ASSEMBLY, CONTROL PANEL
ACCESS, BATTERY CHARGER
LOCATED WITHIN
SEE NOTE 4
1449
[57.0]
OVERALL
HEIGHT
343
[13.5]
REAR TANK COVER
SEE NOTE 4
A
OPEN PUNCHED LOUVERS TYPICAL
ON BOTH SIDES OF
FUEL TANK VENTILATION
DUCT TO PROVIDE ADEQUATE
CROSS-FLOW OF AIR VENTILATION
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
FUEL TANK
VENTILATION DUCT
EXHAUST MUFFLER ENCLOSED WITHIN
GENERATOR ENCLOSURE
182
[7.2]
888 [35.0]
OVERALL WIDTH
REAR VIEW
LEFT SIDE VIEW
RIGHT SIDE VIEW
TITLE
INSTALL CPL PROT D3.4L EXT
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
A
1625 [64.0]
2424 [95.4] OVERALL LENGTH
3
2
ISSUE DATE:
SIZE
CAGE NO
SCALE
0.050
B
DWG NO
WT-KG
0K6968
SEE ABOVE SHEET
1
REV
1 of 2
A
4
SH
3
2/2
REV
A
WINDCHILL VERSION
A.1
1
FUEL TANK
CUSTOMER OPTION
(2" FEMALE NPT)
INNER TANK NORMAL VENT
(2" NPT FEMALE)
351 [13.8]
OUTER TANK LEAK DETECTOR
OUTER TANK EMERGENCY VENT
(2" NPT FEMALE)
B
233 [61]
209 [55]
CAPACITY: LITER [GALLONS]
DIMENSIONS: MM [INCH]
THIS TANK IS LISTED TO UL142 AND ULC/ORD C142.18
INNER TANK EMERGENCY VENT
(2" NPT FEMALE)
101 [4.0]
TOTAL CAPACITY
USABLE CAPACITY
HIGH AND LOW VOLTAGE
STUB-UP AREA
B
CIRCUIT BREAKER,
NEUTRAL AND CUSTOMER
CONNECTION OPENING
FUEL LEVEL
GAUGE/SENDER
786 [30.9]
STUB-UP
AREA
660 [26.0]
125
[4.9]
FUEL RETURN
FUEL FILL
(2" NPT FEMALE)
FUEL SUPPLY
38
[1.5]
121 [4.8]
2226 [87.6]
51
[2.0]
196 [7.7]
STUB-UP
AREA
REMOVABLE
STUB-UP COVER
394 [15.5]
16.7 [.66] MOUNTING HOLES
(10 PLACES)
110 [4.3] TYP
19
[.7]
690 [27.2] TYP
A
1216 [47.9] TYP
851 [33.5] TYP
A
888 [35.0]
1769 [69.6] TYP
2322 [91.4] TYP
TITLE
DRAWING CREATED FROM PRO/ENGINEER
3D FILE. ECO MODIFICATION TO BE
APPLIED TO SOLID MODEL ONLY.
INSTALL CPL PROT D3.4L EXT
GENERAC POWER SYSTEMS OWNS THE COPYRIGHT OF THIS DRAWING
WHICH IS SUPPLIED IN CONFIDENCE AND MUST NOT BE USED FOR
ANY PURPOSE OTHER THAN FOR WHICH IT IS SUPPLIED WITHOUT
THE EXPRESS WRITTEN CONSENT OF GENERAC POWER SYSTEMS.
c GENERAC POWER SYSTEMS 2013
ELECTRONICALLY APPROVED
INSIDE WINDCHILL
4
3
2
ISSUE DATE:
SIZE
CAGE NO
SCALE
0.075
B
DWG NO
WT-KG
0K6968
SEE ABOVE SHEET
1
REV
2 of 2
A