DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
TECHNICAL GUIDE
SINGLE PACKAGE
AIR CONDITIONER / ELECTRIC HEAT
16 SEER – R-410A – 460V - 3 PHASE
3 THRU 5 NOMINAL TONS
MODELS: PCE6*36 THRU 60
• Operating Efficiency - The 3-4 ton PCE6 air conditioner
models are rated at 16.0 SEER and 12.5 EER for cooling
operation.
The 5 ton PCE6 air conditioner model is rated at 16.0 SEER
and 12.0 EER for cooling operation.
All PCE6 models utilize a multi-stage compressor for maximum comfort and efficiency.
• On Site Flexibility - All model sizes use a compact design
cabinet. Field convertible duct connections from side shot to
down shot allows the installer to have greater flexibility with
less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
®
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 1-Year limited parts warranty.
Standard 5-Years limited compressor warranty.
• Utility Connections Made Easy - Electric utility access provided through the bottom or the side of the unit. Utility connections can be made quickly and with a minimum amount of
field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
Continued on next page.
*See limited warranty certificate in User’s Information Manual for details.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5324339-YTG-E-0918
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder paint finish ensures less fading when exposed to sunlight, and provides superior corrosion resistance (1000 hour
salt spray tested).
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from
all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• Attractive Appearance - A single-piece top cover containing
a top-discharge condenser fan arrangement requires less
square footage on installation and provides a wider variety of
installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design.
• Fan System - All models operate over a wide range of
design conditions with an enhanced ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Dehumidification/Humidity Switch Input - This model unit
features a built in de-humidification feature for advanced
dehumidification during cooling operation. The unit indoor
blower control is designed to work with a humidity control
that closes when the humidity is below the set-point. The
control is open when the humidity is above the set-point. This
humidity control may be referred to as a humidistat or dehumidistat.
To use this feature, the control HUM STAT jumper must be
set to YES and a humidistat is connected from the low voltage R and HUM color coded leads. During cooling operation
if the humidity level is above the humidistat set point, the
indoor blower speed is reduced by approximately 15%.
2
• Simple Control Circuit - Field thermostat wiring connect to
color coded leads using twist on wire connections. Cooling
controls use a contactor and a 2nd stage 24 VAC to 24 VDC
rectifier for simple application and troubleshooting. Mate-nlock plug connectors are used. Enhanced ECM indoor
blower control is managed by a multi-stage indoor blower
control board that includes field adjustable speed tap jumpers for maximum flexibility and product application. The
electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate
access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of scroll bypass
and a temperature sensor which protect the compressor if
undesirable operating conditions occur.
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• Loss of Charge Switch - All models include a loss of charge
switch to provide safe shutdown of compressor.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils will use tin-coated
copper tubing with aluminum fins for effective heat transfer.
• Electric Heat - All PCE models use 6HK electric heat, which
are available in 460V/3/60 from 10 kW to 25 kW. Single point
field wiring kits are available for all applications.
• Low Maintenance - Long life, permanently lubricated indoor
and outdoor fan motor bearings need no annual maintenance, adding greater reliability to the unit. Slide-out blower
assembly and indoor coil assembly can be easily removed
for cleaning.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
indoor coils, blower, controls/electric heat kits, filters, etc.
that makes servicing easy. Removing these panels allow
easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
• Filter Frame Kit - All 3 phase PCE6 units include a filter
frame kit, which is shipped inside the unit from production.
Field installation is required.
• Filters - All 3 phase PCE6 units include an applicable number of 1" washable filters, which are shipped inside the unit
from production. Field installation is required. Three filters
are required for B base units.
Johnson Controls Unitary Products
5324339-YTG-E-0918
NOMENCLATURE
PCE
4
A
24
50
2
X
1
A
1
2
3
4
5
6
7
8
9
1. Model Family
5. Gas Heating Input BTU/Hr x 1000
PCG - packaged A/C with gas heat,
050 = 50,000 BTU/Hr. input, blank = electric heat
PHG - packaged heat pump with gas heat,
6. Voltage-Phase-Frequency
PCE - packaged A/C with electric heat,
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
PHE - packaged heat pump with electric heat,
2. Nominal Cooling Efficiency
7. NOx Approval
4 = 14 SEER, 6 = 16 SEER, etc.
X = low-NOx, blank = not low-Nox
3. Cabinet Size
8. Generation Level
A = small 35 x 51, B = large 45 x 51
1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000
9. Revision Level
24 = 24,000 BTU, etc.
A = original release, B = second release
Examples:
PCE6B4221A is a packaged A/C with electric heat, 16 SEER, 3-1/2 ton, large cabinet, 230 volt, single phase, low-NOx model (first generation, first release).
COMPONENT LOCATION
287'225)$102725
287'225)$1
287'225&2,/
%HKLQG3DQHO
&2,/*8$5'3$1(/
(&0)$102725
&21752/%2$5'
&217$&725
7;9
&$3$&,725
75$16)250(5
&2035(6625
%/2:(502725
237,21$/
(/(&75,&+($7.,7
,1'225&2,/
,1'225%/2:(5
5(029$%/(
%$6(5$,/6
$
UNIT LIMITATIONS
Model
Unit Voltage
All Models
Johnson Controls Unitary Products
460-3-60
Min
432
Unit Limitations
Applied Voltage
Max
504
Outdoor DB Temp
Max (°F)
125
3
5324339-YTG-E-0918
ACCESSORIES
• Economizer for Downflow Applications
(S1-2EE04710024, S1-2EE04710124) - Modulating integrated economizer provides simultaneous operation between
mechanical cooling and economizer operation. Independent
blade design insures proper control and less than 1% leak
rate. Includes hood and mesh bird screen filter integrated into
the hood, dry bulb sensor, and barometric relief damper. Separate field accessories of single/dual enthalpy kits are also
available.
• Economizer for Horizontal Applications
(S1-2EE04710224, S1-2EE04710324) - Modulating integrated economizer provides simultaneous operation between
the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1%
leak rate. Includes hood and mesh bird screen filter integrated into hood and dry bulb sensor. Separate field accessories of single enthalpy and dual enthalpy are available.
• Barometric Relief Hood (S1-1RD0501) - Used in conjunction with a horizontal economizer, the Barometric Relief Hood
helps to equalize the building pressure that is caused by the
fresh air that is introduced through the economizer fresh air
hood.
• Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) Sensor replaces supply air temperature dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature of indoor supply air
plus the enthalpy content of the outdoor air.
• Duct/Unit Mount CO2 Kit (S1-2AQ04700924) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Wall Mount CO2 Kit (S1-2AQ04701024) - Sensor kit detects
CO2 levels automatically and overrides the economizer when
CO2 levels rise above the preset limits.
• Supply Air Temperature Sensor Kit (S1-TE-63616E-2D) Outdoor supply air temperature sensor kit used with economizers.
• Filter/Frame Kit (Kit provided)
(S1-1FF0602, S1-1FF0601) - Kit contains the necessary hardware to field install return air filters into the base unit. The filter
rack is suitable for either 1" or 2" filters.
• Filter (S1-02647812000) - Washable 1” filter. Three filters
are required for B base units. Washable filters are included
inside shipped units for field installation.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
4
•
•
•
•
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed for assembly through hinge pins in each
corner. Kit also provides seal strip to assure air tight seal.
These are 14 inch high roof curbs.
Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PCE6
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous
generation applications. Refer to the PCE6 price pages for
more details.
• Electric Heat (Optional) - All PCE models use 6HK electric
heat kits, which are available in 460V/3/60 from 10 kW to 25
kW. Single point field wiring kits are available for all applications.
• Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) - Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return
applications and unit mounted down supply/return applications. Includes hood and screen assembly.
• Low Ambient Temperature Kit (S1-2LA04701024) - Kit provides necessary hardware to convert unit to operate in cooling cycle down to 0º F. Standard unit operation 45º F.
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
• Thermostat (S1-THXU280*) - Compatible thermostat controls are available through accessory sourcing. For optimum
performance, these outdoor units are fully compatible with the
York Hx™ Touchscreen Thermostat (S1-THXU****) available
through Source1. For more information, see the thermostat
section of the Product Equipment Catalog.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic non power stealing and electromechanical thermostats. All units require the use of a multistage conventional thermostat.
* For additional kit numbers refer to the price pages.
Johnson Controls Unitary Products
5324339-YTG-E-0918
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. These packaged cooling and heating air
conditioners are designed for outdoor installation. Only utility
and duct connections are required at the point of installation. Air
Conditioning units provide electric cooling and electric heating,
with field installed electric heat kits from 10 kW to 25 kW for
heating operation.
DESCRIPTION
Units shall be factory-assembled, single packaged, Air
Conditioners with Electric Cooling/Electric Heating units,
designed for outdoor installation. They shall have built in, equal
size, field convertible duct connections for supply/return or
horizontal supply/return. The units shall be factory wired, piped,
charged with R-410A Refrigerant and factory tested prior to
shipment. All models shall be rated in accordance with DOE
and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed to the UL 1995/CAN/CSA
No. 236-M90 standards.
• Operating Efficiency - All models shall be rated at a minimum of 16.0 SEER and 12.0 EER for cooling and heating
operation rated in accordance with DOE requirements.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the condenser
coil muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. Sound ratings as tested
under AHRI test procedures shall be less than 77 dbA for all
models.
UNIT CABINET
Unit cabinet shall be a single piece design, with drip edges and
no-seam corners to provide optimum water integrity. Unit shall
have a rigidly mounted condenser coil guard to provide
protection from objects and personnel after installation. Indoor
blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
factory furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit.
• Durable Finish - The cabinet shall be is made of G90 galvanized steel with a powder paint coating for appearance and
protection. The pre-treated galvanized steel shall provide a
better paint-to-steel bond, which resists corrosion and rust
creep. Powder paint finish shall provide superior corrosion
resistance (1000 hour salt spray tested).
Johnson Controls Unitary Products
• On Site Flexibility - All model sizes shall use a compact
design cabinet. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Attractive Appearance - A single-piece top cover containing
a top-discharge condenser fan arrangement shall be used
which requires less square footage on installation and provides a wider variety of installations. The one-piece design
adds greater water integrity. Rounded corners with water drip
edges add to the attractive appearance and prevent water
penetration.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Utility Connections Made Easy - Electric utility access shall
be provided through the bottom or the side of the unit. Utility
connections should be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
indoor coils, blower, controls/electric heat kits, filters, etc.
that makes servicing easy. Removing these panels allow
easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a high efficiency
brushless DC motor (constant torque) also known as an
enhanced ECM motor.
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated ball bearings and internally protected
against overload conditions.
5
5324339-YTG-E-0918
REFRIGERANT COMPONENTS
CONTROLS
• Protected Compressor - The compressor shall be a fully
hermetic type, direct drive compressor, that is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of scroll bypass
and a temperature thermal overload sensor which protect the
compressor if undesirable operating conditions occur. The
hermetic motor shall be suction gas cooled and have a voltage range of +/- 10% of the unit nameplate voltage. Compressors shall have internal isolation and sound muffling to
minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
• Simple Control Circuit - Field thermostat wiring connects to
color coded leads using twist on wire connections. Cooling
controls use contactor and relays for simple application and
troubleshooting. Mate-n-lock plug connectors are used.
Enhanced ECM indoor blower control is managed by a multistage indoor blower control board that includes field adjustable speed tap jumpers for maximum flexibility and product
application. The electrical control box is not located in the
compressor compartment. The controls are mounted to allow
the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system
operating pressures. All wiring internal to the unit is color/
number coded.
• Indoor Coils - Indoor coils shall be of the direct expansion,
draw through design and have aluminum plate fins mechanically bonded to seamless internally enhanced tin-coated
copper tubes with all joints brazed.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Outdoor Coils - Outdoor coils shall have aluminum plate
fins mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed, and be a draw through
design.
Refrigerant Circuit and Refrigerant Safety Components
shall include: Thermal expansion devices (TXV's) shall be
factory mounted and provided, Filter/strainer to eliminate any
foreign matter, reversing valves to control refrigerant flow.
6
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• Factory Testing - Installation time and costs are reduced by
easy power and control wiring connections. All units are
completely wired, charged with R-410A and tested prior to
shipment. Test stations using a state-of-the-art computerized
process system shall be used to insure product quality.
Refrigerant charge and component part numbers are verified
via computer bar code scans during assembly. Vital run test
statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties
are monitored and recorded by the system to insure unit performance. This data could be provided by serial number
tracking if requested.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 460V/3/60 from 10 kW to 25 kW.
Single point field wiring kits are available for all applications.
Electric heat kits must be certified to UL 1995 standard
requirements.
Johnson Controls Unitary Products
5324339-YTG-E-0918
PHYSICAL DATA
MODELS:
NOMINAL TONNAGE:
COMPONENT
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
AHRI net capacity (MBH)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
Dimensions (inches)
Length
Width
Height
Operating WT. (lbs.)
Compressors
Type
Stages
Outdoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Indoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Outdoor Fan Data
Fan diameter (Inch)
Type
Drive type
No. speeds
Motor HP each
RPM
Nominal total CFM
Direct Drive Indoor Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
Filters
Filter Size
Quantity - Size
Johnson Controls Unitary Products
PCE6B36
3.0
PCE6B48
4.0
PCE6B60
5.0
36.5
36.0
12.5
16.0
1200
3.0
R410A
11-8
49.1
45.5
12.0
16.0
1600
3.6
R410A
13-8
60.0
58.0
12.0
16.0
2000
4.6
R410A
14-0
51-1/4
45-3/4
49
460
51-1/4
45-3/4
53
483
51-1/4
45-3/4
55
500
Scroll
2
Scroll
2
Scroll
2
19.5
2
22
3/8
Interlaced
23.8
2
22
3/8
Interlaced
25.9
2
22
3/8
Interlaced
6.3
3
16
3/8
Interlaced
TXV
6.3
3
16
3/8
Interlaced
TXV
6.3
4
16
3/8
Interlaced
TXV
26
Prop
Direct
1
26
Prop
Direct
1
26
Prop
Direct
1
1/3
850
3200
1/3
850
3200
1/3
850
3200
11 x 10
Centrifugal
1/2
1400 Max
48
11 x 10
Centrifugal
1
1400 Max
48
11 x 10
Centrifugal
1
1400 Max
48
B
B
B
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. A=20 x 10 (2 each), B=20 x 10 (3 each)
7
5324339-YTG-E-0918
COOLING PERFORMANCE DATA - 3 TON (LOW SPEED)
PACKAGED UNIT MODEL NO. PCE6B36
INDOOR MODEL NO.
CONDENSER
ID CFM
600
IDDB
80
80
75
ENTERING AIR
IDWB
57
62
62
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
34.8
34.1
2.35
33.2
32.4
2.56
31.5
30.7
2.77
30.2
29.1
3.03
28.8
27.4
3.29
25.6
23.7
3.61
22.5
20.1
3.92
19.4
16.5
4.23
41.4
28.8
2.20
39.0
27.6
2.40
36.6
26.4
2.61
34.7
25.1
2.90
32.7
23.9
3.20
28.5
21.5
3.55
24.4
19.1
3.88
20.4
16.8
4.22
41.7
25.1
2.19
39.2
23.7
2.39
36.7
22.2
2.59
34.1
21.0
2.86
31.5
19.8
3.13
27.8
17.5
3.49
24.2
15.2
3.84
20.6
13.0
4.19
80
67
80
72
80
57
80
62
800
75
62
80
67
80
72
80
57
80
62
1000
75
62
80
67
80
72
46.0
25.4
2.16
43.6
24.2
2.36
41.2
22.9
2.57
38.9
21.6
2.84
36.6
20.4
3.11
32.8
18.5
3.48
29.1
16.6
3.83
25.5
14.7
4.19
49.1
20.5
2.13
47.3
19.5
2.33
45.5
18.4
2.52
42.3
17.0
2.78
39.2
15.7
3.05
35.3
13.9
3.41
31.6
12.1
3.77
27.9
10.4
4.13
37.3
36.8
2.30
35.4
34.8
2.51
33.5
32.9
2.71
31.6
30.9
2.98
29.6
28.8
3.24
26.1
25.0
3.56
22.6
21.3
3.87
19.2
17.6
4.17
41.2
32.1
2.16
38.8
30.7
2.37
36.3
29.4
2.57
34.0
28.3
2.85
31.7
27.1
3.13
27.7
24.1
3.49
23.8
21.1
3.83
20.0
18.1
4.18
41.5
27.8
2.16
38.8
26.3
2.36
36.1
24.8
2.56
33.4
23.5
2.83
30.6
22.2
3.09
26.8
19.8
3.46
23.0
17.6
3.82
19.3
15.4
4.18
44.6
26.7
2.13
42.6
25.9
2.34
40.7
25.0
2.54
38.3
24.0
2.80
36.0
23.0
3.07
31.7
20.8
3.44
27.5
18.7
3.79
23.2
16.6
4.15
47.3
21.0
2.11
45.7
20.3
2.31
44.2
19.6
2.50
41.2
18.2
2.76
38.1
16.8
3.02
33.9
14.8
3.39
29.8
12.9
3.74
25.7
11.0
4.10
39.7
39.4
2.25
37.6
37.3
2.46
35.4
35.1
2.66
33.0
32.7
2.92
30.5
30.2
3.19
26.5
26.3
3.50
22.7
22.5
3.81
18.9
18.7
4.11
41.0
35.4
2.13
38.5
33.9
2.33
36.0
32.4
2.53
33.3
31.4
2.80
30.7
30.4
3.06
26.9
26.7
3.43
23.2
23.0
3.78
19.6
19.4
4.14
41.2
30.6
2.13
38.4
28.9
2.33
35.6
27.3
2.54
32.7
25.9
2.80
29.8
24.5
3.06
25.7
22.2
3.44
21.8
20.0
3.80
17.9
17.7
4.17
43.1
28.0
2.11
41.7
27.6
2.31
40.2
27.2
2.51
37.8
26.4
2.77
35.4
25.6
3.03
30.5
23.2
3.40
25.8
20.9
3.76
21.0
18.5
4.12
45.4
21.5
2.09
44.2
21.2
2.29
42.9
20.8
2.48
40.0
19.4
2.74
37.1
17.9
2.99
32.4
15.8
3.36
27.9
13.7
3.72
23.4
11.7
4.07
COOLING PERFORMANCE DATA - 3 TON (HIGH SPEED)
PACKAGED UNIT MODEL NO. PCE6B36
CONDENSER
ID CFM
1000
IDDB
80
80
75
ENTERING AIR
IDWB
57
62
62
TEMPERATURE
80
67
80
72
80
57
80
62
1200
75
62
80
67
80
72
80
57
80
62
1400
75
62
80
67
80
72
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
43.2
27.7
2.07
41.6
26.7
2.27
40.1
25.7
2.47
37.4
24.6
2.73
34.8
23.4
2.99
31.6
22.0
3.38
28.4
20.5
3.76
25.3
19.1
4.14
46.6
0.6
2.09
44.3
11.6
2.29
41.9
22.5
2.48
40.3
20.5
2.74
38.7
18.5
3.00
35.7
17.1
3.40
32.8
15.8
3.78
29.9
14.4
4.16
41.2
38.3
2.11
39.6
36.8
2.31
38.0
35.3
2.51
36.1
33.4
2.77
34.2
31.5
3.03
31.0
29.2
3.43
28.0
27.0
3.82
25.0
24.7
4.21
42.8
35.5
2.12
40.4
34.7
2.32
38.1
33.9
2.52
35.6
32.5
2.78
33.1
31.2
3.04
30.1
28.7
3.43
27.1
26.4
3.82
24.1
24.0
4.20
41.7
30.0
2.12
36.6
28.6
2.74
31.5
27.3
3.36
32.1
26.5
3.20
32.7
25.7
3.03
29.5
24.0
3.43
26.4
22.4
3.81
23.3
20.9
4.19
45.6
29.9
2.15
43.6
29.1
2.35
41.5
28.2
2.55
38.8
27.0
2.81
36.0
25.8
3.07
32.5
24.3
3.46
29.1
22.8
3.84
25.7
21.4
4.21
48.4
12.8
2.17
46.6
17.9
2.37
44.7
22.9
2.57
42.6
21.3
2.83
40.4
19.8
3.09
37.0
18.3
3.48
33.7
16.9
3.86
30.4
15.5
4.24
43.8
40.6
2.20
42.1
39.0
2.40
40.4
37.4
2.61
38.3
35.3
2.87
36.2
33.2
3.13
32.7
30.7
3.52
29.3
28.2
3.90
25.9
25.7
4.29
44.6
38.7
2.20
42.2
38.0
2.40
39.8
37.3
2.61
37.1
35.7
2.87
34.3
34.1
3.13
31.2
30.9
3.52
28.1
27.9
3.90
25.0
24.8
4.29
43.5
32.5
2.20
41.2
31.7
2.40
38.9
30.9
2.59
36.3
29.5
2.85
33.7
28.1
3.11
30.2
26.3
3.51
26.8
24.5
3.88
23.4
22.8
4.26
48.0
32.0
2.24
45.5
31.4
2.44
43.0
30.8
2.64
40.1
29.5
2.90
37.2
28.2
3.15
33.5
26.6
3.54
29.8
25.2
3.91
26.1
23.7
4.29
50.2
25.0
2.25
48.9
24.1
2.46
47.5
23.3
2.67
44.8
22.2
2.92
42.1
21.1
3.17
38.3
19.6
3.56
34.6
18.1
3.94
30.9
16.6
4.31
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
8
38.5
36.0
2.02
37.1
34.6
2.21
35.6
33.3
2.41
33.9
31.6
2.68
32.2
29.8
2.94
29.4
27.8
3.34
26.7
25.7
3.74
24.1
23.7
4.13
41.0
32.3
2.04
38.7
31.4
2.24
36.3
30.5
2.43
34.1
29.4
2.69
31.9
28.2
2.95
29.0
26.5
3.35
26.1
24.8
3.73
23.3
23.1
4.11
40.0
27.5
2.03
32.0
25.6
3.08
24.1
23.7
4.13
27.9
23.5
3.54
31.7
23.2
2.95
28.8
21.8
3.35
25.9
20.4
3.73
23.1
18.9
4.11
Johnson Controls Unitary Products
5324339-YTG-E-0918
COOLING PERFORMANCE DATA - 4 TON (LOW SPEED)
PACKAGED UNIT MODEL NO. PCE6B48
CONDENSER
ID CFM
900
IDDB
80
80
75
ENTERING AIR
IDWB
57
62
62
TEMPERATURE
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
34.3
32.3
1.67
32.4
30.4
1.86
30.4
28.6
2.05
27.3
26.2
2.39
24.2
23.8
2.72
21.9
21.5
3.15
19.6
19.3
3.56
17.3
17.0
3.98
37.4
28.7
1.64
34.5
27.4
1.83
31.6
26.0
2.03
29.1
23.9
2.36
26.7
21.8
2.68
23.6
20.3
3.16
20.6
18.8
3.63
17.6
17.4
4.10
36.3
24.7
1.65
34.1
21.0
1.85
32.0
17.4
2.04
28.2
18.1
2.43
24.5
18.8
2.82
20.8
17.0
3.22
17.1
15.1
3.60
13.5
13.3
3.98
80
67
80
72
80
57
80
62
1100
75
62
80
67
80
72
80
57
80
62
1300
75
62
80
67
80
72
41.1
24.9
1.63
38.7
23.5
1.79
36.3
22.1
1.96
34.0
20.8
2.37
31.6
19.4
2.78
27.3
19.1
3.16
23.2
18.8
3.53
19.1
18.6
3.91
45.6
20.0
1.49
43.8
18.9
1.73
42.0
17.8
1.97
39.1
16.5
2.30
36.1
15.1
2.63
32.6
13.6
3.06
29.2
12.2
3.47
25.7
10.7
3.89
37.5
34.8
1.63
35.2
32.8
1.85
33.0
30.7
2.07
29.4
28.0
2.41
25.8
25.4
2.74
23.1
22.7
3.17
20.4
20.1
3.58
17.7
17.4
3.99
39.7
32.1
1.61
36.8
30.2
1.83
33.9
28.2
2.05
31.1
26.6
2.38
28.2
25.0
2.72
24.7
22.5
3.17
21.2
20.0
3.61
17.8
17.5
4.05
38.7
27.2
1.62
36.6
23.2
1.84
34.5
19.1
2.06
29.9
19.9
2.42
25.3
20.8
2.78
21.1
18.0
3.20
16.9
15.3
3.60
12.7
12.5
4.00
43.6
27.2
1.59
41.0
25.8
1.82
38.4
24.4
2.05
35.7
22.9
2.39
33.1
21.5
2.74
29.0
21.1
3.14
25.0
20.8
3.53
21.0
20.4
3.92
48.0
21.8
1.52
46.2
20.7
1.76
44.5
19.6
2.01
41.2
18.0
2.33
37.9
16.4
2.65
33.9
14.7
3.09
30.1
13.0
3.51
26.3
11.4
3.93
40.6
37.4
1.58
38.1
35.1
1.84
35.5
32.9
2.10
31.4
29.9
2.43
27.4
26.9
2.76
24.2
23.9
3.18
21.2
20.9
3.59
18.2
17.9
4.00
42.1
35.5
1.58
39.1
33.0
1.82
36.2
30.5
2.06
33.0
29.3
2.41
29.7
28.2
2.75
25.7
24.6
3.18
21.8
21.1
3.60
17.9
17.6
4.01
41.1
29.8
1.58
39.1
25.3
1.83
37.1
20.8
2.08
31.6
21.8
2.41
26.2
22.8
2.74
21.3
19.0
3.18
16.6
15.4
3.60
11.9
11.8
4.02
46.2
29.6
1.56
43.3
28.1
1.84
40.4
26.6
2.13
37.5
25.1
2.42
34.6
23.6
2.70
30.6
23.2
3.12
26.8
22.7
3.53
22.9
22.3
3.93
50.3
23.6
1.55
48.7
22.5
1.79
47.0
21.5
2.04
43.4
19.5
2.36
39.7
17.6
2.68
35.3
15.7
3.12
31.1
13.9
3.54
26.8
12.1
3.97
COOLING PERFORMANCE DATA - 4 TON (HIGH SPEED)
PACKAGED UNIT MODEL NO. PCE6B48
CONDENSER
ID CFM
1400
IDDB
80
80
75
ENTERING AIR
IDWB
57
62
62
TEMPERATURE
80
67
80
72
80
57
80
62
1600
75
62
80
67
80
72
80
57
80
62
1800
75
62
80
67
80
72
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
56.6
35.0
2.93
54.8
33.8
3.11
52.9
32.6
3.29
49.4
31.2
3.72
45.9
29.7
4.15
41.7
27.8
4.65
37.7
26.0
5.14
33.6
24.2
5.62
59.6
27.8
2.75
58.3
27.0
3.13
56.9
26.1
3.51
53.8
24.6
3.77
50.7
23.1
4.03
46.5
21.2
4.58
42.4
19.3
5.12
38.2
17.5
5.66
47.9
47.2
2.76
44.9
44.3
3.03
42.0
41.5
3.29
40.1
39.4
3.64
38.1
37.4
4.00
34.0
33.4
4.51
30.0
29.6
5.00
26.0
25.8
5.50
54.3
43.3
2.80
51.7
35.9
3.06
49.1
28.6
3.32
45.6
33.1
3.67
42.2
37.6
4.01
37.9
34.8
4.54
33.8
32.1
5.06
29.6
29.4
5.58
55.6
36.8
2.80
52.7
37.0
3.06
49.9
37.3
3.33
46.8
34.1
3.66
43.6
30.9
4.00
39.0
26.2
4.47
34.5
21.7
4.94
30.1
17.1
5.40
56.8
35.0
2.92
54.8
34.7
3.15
52.9
34.3
3.38
49.2
32.8
3.77
45.5
31.2
4.15
41.3
29.3
4.65
37.2
27.6
5.13
33.2
25.8
5.62
59.9
28.0
2.82
58.7
31.7
3.16
57.5
35.5
3.51
54.0
29.8
3.81
50.5
24.1
4.11
46.1
22.0
4.63
41.8
20.1
5.14
37.5
18.1
5.66
49.2
48.7
2.86
46.1
45.3
3.13
43.0
41.9
3.39
39.9
39.1
3.74
36.8
36.2
4.09
33.4
32.9
4.59
30.1
29.8
5.09
26.8
26.6
5.58
54.3
45.2
2.88
52.1
31.7
3.06
49.9
18.2
3.25
46.1
28.9
3.67
42.3
39.7
4.09
38.3
36.5
4.60
34.5
33.5
5.09
30.7
30.4
5.58
55.6
38.2
2.87
53.3
40.0
3.14
51.0
41.8
3.41
47.2
37.2
3.75
43.4
32.6
4.08
38.9
25.1
4.52
34.5
17.9
4.95
30.1
10.6
5.39
56.9
35.0
2.90
54.9
35.5
3.19
52.8
36.0
3.47
48.9
34.4
3.81
45.1
32.7
4.15
40.9
30.9
4.65
36.8
29.1
5.13
32.7
27.3
5.62
60.1
28.1
2.89
59.1
36.5
3.20
58.1
44.9
3.50
54.2
34.9
3.85
50.3
25.0
4.19
45.7
22.9
4.68
41.2
20.8
5.17
36.7
18.8
5.65
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
46.5
45.7
2.66
43.8
43.3
2.93
41.1
41.0
3.19
40.3
39.8
3.55
39.4
38.6
3.91
34.6
34.0
4.42
29.9
29.5
4.91
25.2
25.0
5.41
Johnson Controls Unitary Products
54.3
41.3
2.72
51.2
40.2
3.06
48.2
39.1
3.39
45.2
37.3
3.66
42.2
35.5
3.93
37.5
33.1
4.49
33.0
30.7
5.03
28.4
28.4
5.58
55.5
35.4
2.72
52.2
34.1
2.98
48.8
32.9
3.24
46.3
31.1
3.58
43.8
29.3
3.92
39.1
27.4
4.43
34.6
25.5
4.92
30.1
23.6
5.41
9
5324339-YTG-E-0918
COOLING PERFORMANCE DATA - 5 TON (LOW SPEED)
PACKAGED UNIT MODEL NO. PCE6B60
CONDENSER
ID CFM
1100
IDDB
80
80
75
ENTERING AIR
IDWB
57
62
62
TEMPERATURE
80
67
80
72
80
57
80
62
1300
75
62
80
67
80
72
80
57
80
62
1500
75
62
80
67
80
72
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
55.7
36.5
1.74
52.1
34.9
2.11
48.5
33.3
2.48
44.8
31.4
2.74
41.0
29.5
3.00
36.5
27.4
3.46
32.1
25.4
3.91
27.7
23.4
4.35
59.9
30.0
1.90
57.3
28.5
2.08
54.8
26.9
2.26
50.8
25.1
2.61
46.9
23.2
2.96
42.1
21.2
3.43
37.4
19.2
3.87
32.7
17.2
4.32
47.1
47.1
1.87
44.3
44.3
2.15
41.6
41.6
2.43
38.3
38.3
2.78
35.0
35.0
3.13
31.3
31.3
3.62
27.8
27.8
4.10
24.3
24.3
4.58
53.0
47.5
1.87
49.4
45.6
2.15
45.8
43.8
2.42
41.8
40.9
2.77
37.8
37.8
3.13
34.3
34.3
3.59
30.9
30.9
4.03
27.5
27.5
4.47
51.7
40.0
1.88
48.4
38.1
2.20
45.1
36.2
2.51
41.5
34.2
2.87
37.8
32.2
3.23
33.6
29.6
3.66
29.4
27.1
4.07
25.3
24.6
4.49
57.4
39.4
1.84
53.9
37.8
2.16
50.3
36.2
2.48
46.3
34.3
2.79
42.3
32.3
3.10
37.3
30.1
3.56
32.5
28.0
4.01
27.6
25.9
4.46
61.8
31.6
1.92
59.6
30.2
2.14
57.4
28.7
2.36
53.0
26.8
2.71
48.5
25.0
3.07
43.3
22.7
3.53
38.3
20.6
3.98
33.2
18.4
4.43
49.5
49.5
1.98
46.6
46.6
2.25
43.7
43.7
2.52
40.1
40.1
2.87
36.5
36.5
3.22
32.7
32.7
3.69
28.9
28.9
4.13
25.1
25.1
4.58
54.9
51.8
1.98
51.2
49.9
2.24
47.4
47.4
2.51
43.0
43.0
2.88
38.6
38.6
3.25
34.6
34.6
3.70
30.6
30.6
4.13
26.7
26.7
4.57
53.0
43.3
1.99
50.1
41.2
2.25
47.1
39.1
2.52
43.2
37.0
2.88
39.3
34.9
3.24
34.5
32.0
3.70
29.9
29.2
4.14
25.2
25.2
4.59
59.2
42.4
1.94
55.7
40.8
2.22
52.1
39.2
2.49
47.9
37.2
2.84
43.6
35.1
3.20
38.1
32.9
3.66
32.8
30.7
4.11
27.5
27.5
4.56
63.8
33.3
1.94
61.9
31.9
2.20
60.1
30.4
2.45
55.1
28.6
2.81
50.2
26.7
3.17
44.6
24.3
3.63
39.1
21.9
4.09
33.7
19.6
4.54
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
44.6
44.6
1.77
42.1
42.1
2.05
39.6
39.6
2.34
36.5
36.5
2.69
33.4
33.4
3.04
30.0
30.0
3.56
26.7
26.7
4.07
23.4
23.4
4.57
51.1
43.1
1.77
47.6
41.4
2.05
44.2
39.6
2.33
40.6
37.6
2.67
37.0
35.5
3.02
34.0
32.8
3.48
31.1
30.3
3.93
28.3
27.7
4.38
50.5
36.8
1.77
46.8
35.0
2.14
43.1
33.3
2.51
39.8
31.4
2.87
36.4
29.5
3.23
32.7
27.2
3.62
29.0
25.0
4.00
25.3
22.8
4.39
COOLING PERFORMANCE DATA - 5 TON (HIGH SPEED)
PACKAGED UNIT MODEL NO. PCE6B60
CONDENSER
ID CFM
1600
IDDB
80
80
75
ENTERING AIR
IDWB
57
62
62
TEMPERATURE
80
67
80
72
80
57
80
62
1800
75
62
80
67
80
72
80
57
80
62
2000
75
62
80
67
80
72
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
T.C.
S.C.
K.W.
71.8
46.7
3.21
68.4
44.9
3.34
65.1
43.0
3.47
60.5
41.0
3.95
55.9
39.1
4.44
50.9
36.9
4.96
46.0
34.7
5.46
41.1
32.6
5.96
77.1
37.2
2.93
74.2
35.7
3.37
71.3
34.2
3.81
67.1
32.2
4.02
62.8
30.3
4.23
57.9
28.2
4.84
53.1
26.2
5.43
48.2
24.2
6.01
61.3
61.3
3.03
55.7
55.7
3.30
50.1
50.1
3.57
47.8
47.8
3.94
45.4
45.4
4.30
40.7
40.7
4.82
36.1
36.1
5.32
31.5
31.5
5.82
70.6
59.6
3.08
66.1
42.9
3.34
61.6
26.2
3.60
57.3
38.2
3.96
53.0
50.1
4.31
48.1
46.3
4.87
43.4
42.6
5.42
38.6
38.6
5.96
67.6
49.6
3.08
63.2
51.1
3.35
58.8
52.5
3.61
55.3
47.0
3.96
51.8
41.5
4.30
47.1
33.0
4.77
42.5
24.7
5.23
37.9
16.4
5.68
73.5
49.1
3.28
69.9
47.3
3.48
66.3
45.5
3.68
61.5
43.3
4.10
56.7
41.2
4.52
51.6
39.0
5.04
46.7
36.9
5.54
41.8
34.7
6.04
77.7
38.2
3.14
75.5
46.7
3.51
73.4
55.3
3.89
68.6
43.3
4.17
63.9
31.4
4.44
58.7
29.3
5.00
53.8
27.2
5.54
48.8
25.1
6.09
63.5
63.5
3.26
57.2
57.2
3.53
50.9
50.9
3.80
46.8
46.8
4.16
42.8
42.8
4.52
38.9
38.9
5.03
35.1
35.1
5.54
31.4
31.4
6.04
72.3
63.4
3.30
68.1
31.9
3.42
64.0
0.3
3.55
59.2
26.7
4.04
54.3
53.0
4.53
49.5
48.7
5.04
44.9
44.5
5.54
40.2
40.2
6.04
68.8
52.2
3.30
64.7
56.8
3.56
60.6
60.6
3.83
56.8
52.7
4.17
53.0
43.9
4.51
48.3
29.1
4.92
43.8
14.7
5.33
39.3
0.3
5.74
75.1
51.5
3.34
71.3
49.8
3.62
67.4
48.0
3.90
62.4
45.7
4.25
57.4
43.3
4.60
52.3
41.1
5.11
47.4
39.0
5.61
42.5
36.8
6.11
78.3
39.1
3.35
76.9
57.8
3.66
75.4
75.4
3.97
70.2
54.5
4.32
64.9
32.6
4.66
59.6
30.4
5.17
54.4
28.2
5.66
49.3
26.1
6.16
55 / 45
65 / 55
75 / 63
85 / 69
95 / 75
105 / 83
115 / 89
125 / 95
10
59.2
59.2
2.80
54.3
54.3
3.07
49.3
49.3
3.33
48.7
48.7
3.71
48.0
48.0
4.09
42.5
42.5
4.60
37.0
37.0
5.10
31.6
31.6
5.60
68.9
55.8
2.86
64.1
53.9
3.25
59.2
52.0
3.65
55.4
49.6
3.87
51.6
47.2
4.10
46.6
43.9
4.71
41.8
40.7
5.29
37.0
37.0
5.88
66.5
47.0
2.87
61.7
45.4
3.13
57.0
43.7
3.39
53.9
41.4
3.74
50.7
39.1
4.09
45.9
36.8
4.61
41.3
34.7
5.12
36.6
32.5
5.63
Johnson Controls Unitary Products
5324339-YTG-E-0918
&2,/*8$5'
+,*+92/7$*(
23(1,1*´
&
+,*+92/7$*(
23(1,1*´
+($76(&7,21
$&&(663$1(/
&2035(6625
$&&(663$1(/
&21'(16$7(
'5$,1
%/2:(5
$&&(66
3$1(/
%
$
/2:92/7$*(23(1,1*´
&21752/+($7
$&&(663$1(/
$
UNIT DIMENSIONS & ACCESS LOCATIONS
Model
Dimensions - in inches
B
45-3/4
45-3/4
45-3/4
A
51-1/4
51-1/4
51-1/4
PCE6B36
PCE6B48
PCE6B60
C
49
53
55
UNIT CLEARANCES
Direction
Top1
Side Opposite Ducts
Duct Panel
Distance (in.)
36
36
0
Direction
Power Entry (Right Side)
Left Side
Bottom2,3
Distance (in.)
36
24
1
NOTES:
1. Minimum Clearance of 1inch all sides of supply air duct for the first 3 feet of duct for 20 & 25 kW., zero inches thereafter. For all other heaters, zero inch clearance
all sides for entire length of duct.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obscure outdoor air discharge outlet.
3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch between combustible roof curb material and this supply air
duct.
INDOOR BLOWER SPECIFICATIONS
Motor
Model
HP
1/2
1
1
PCE6B36
PCE6B48
PCE6B60
RPM
Variable
Variable
Variable
EFF.
0.8
0.8
0.8
SF
1.0
1.0
1.0
Frame
48
48
48
SOUND PERFORMANCE
Model
(Tons)
Sound Rating1
dB (A)
PCE6B36
PCE6B48
PCE6B60
74
74
76
125
58.5
63.5
72.3
250
61.8
63.9
65.0
Octave Band Centerline Frequency (Hz)
500
1000
2000
65.4
66.5
60.7
62.3
65
64
63.9
64
60
4000
54.8
54.1
55.5
8000
49.8
46.6
49.0
NOTES:
1. Rated in accordance with AHRI Standard 270.
Johnson Controls Unitary Products
11
5324339-YTG-E-0918
ELECTRICAL DATA - 460-3-60 - SINGLE SOURCE POWER
Compressor
Model
RLA LRA MCC
OD
ID
Fan Blower
Motor Motor
FLA
FLA
PCE6B36 5.7
38.0
8.9
0.87
1.9
PCE6B48 6.4
41.0 10.0
0.87
3.3
PCE6B60 7.6
52.0 11.9
0.87
3.3
Max
Max
Max
Fuse2 or
Fuse2 or
Fuse2 or
Breaker MCA1
Breaker MCA1 Breaker
Electric Heat Option
MCA1
Size3
(Unit
Size3
Unit
Size3
Heater
Heater (Total (Total
Less (Unit Less (Heater (Heater
Heater Kit4
kW Stages Amps Unit)
Unit)
Heater) Heater)
Only)
Only)
none
---9.9
15
9.9
15
--6HK06501046
8.8
1
11
13.4
15
9.9
15
13.8
15
6HK06501546 13.2
1
16.6
18.9
20
9.9
15
20.7
25
none
---12.2
15
12.2
15
--6HK06501046
8.8
1
11
15.2
20
12.2
15
13.8
15
6HK06501546 13.2
1
16.6
20.7
25
12.2
15
20.7
25
6HK06501846 15.9
1
20
24.1
25
12.2
15
24.9
25
6HK06502046 17.6
1
22.1
26.2
30
12.2
15
27.6
30
none
---13.7
20
13.7
20
--6HK06501046
8.8
1
11
15
20
13.7
20
13.8
15
6HK06501546 13.2
1
16.6
20.5
25
13.7
20
20.7
25
6HK06501846 15.9
1
20
23.9
25
13.7
20
24.9
25
6HK06502046 17.6
1
22.1
26
30
13.7
20
27.6
30
6HK06502546
22
1
27.6
31.5
35
13.7
20
34.5
35
NOTES: Single-source power MCA and MOP requirements are given here for reference if the unit is to be installed with a field-installed single-point power modification.
1.
2.
3.
4.
MCA = Minimum Circuit Ampacity.
Maximum Over Current Protection per standard UL 1995.
Fuse or HACR circuit breaker to be field installed.
Single Point Connection Required.
ELECTRICAL DATA FOR - 460-3-60 MULTI SOURCE POWER
Compressor
Model
RLA LRA MCC
OD
Blower
Fan
Motor
Motor
FLA
FLA
PCE6B36
5.7
38.0
8.9
0.87
1.9
PCE6B48
6.4
41.0 10.0
0.87
3.3
PCE6B60
7.6
52.0 11.9
0.87
3.3
12
MCA
Amps
Electric Heat Option
Heater Kit
none
6HK06501046
6HK06501546
none
6HK06501046
6HK06501546
6HK06501846
6HK06502046
none
6HK06501046
6HK06501546
6HK06501846
6HK06502046
6HK06502546
Heater
Stages
kW
--8.8
1
13.2
1
--8.8
1
13.2
1
15.9
1
17.6
1
--8.8
1
13.2
1
15.9
1
17.6
1
22.0
1
Heater
Amps
-11.0
16.6
-11.0
16.6
20.0
22.1
-11.0
16.6
20.0
22.1
27.6
Max Fuse or
Breaker Size
CIRCUIT #1
Unit Minus Heaters
9.9
15
9.9
15
9.9
15
12.2
15
12.2
15
12.2
15
12.2
15
12.2
15
13.7
20
13.7
20
13.7
20
13.7
20
13.7
20
13.7
20
MCA
Amps
Max Fuse or
Breaker Size
CIRCUIT #2
Heaters
--13.8
15
20.7
25
--13.8
15
20.7
25
24.9
25
27.6
30
--13.8
15
20.7
25
24.9
25
27.6
30
34.5
35
Johnson Controls Unitary Products
5324339-YTG-E-0918
SINGLE POINT WIRING KIT PART NUMBERS
Unit Model Number
Voltage
PCE6B3641
460-3-60
PCE6B4841
460-3-60
PCE6B6041
460-3-60
Heater Kit
6HK06501046
6HK06501546
6HK06501046
6HK06501546
6HK06501846
6HK06502046
6HK06501046
6HK06501546
6HK06501846
6HK06502046
6HK06502546
Single-Point Wiring Kit
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK036
S1-2SPWK037
Unit Fuse Size (Amps)
15
15
15
15
15
15
20
20
20
20
20
Heater Fuse Size (Amps)
15
25
15
25
25
30
15
25
25
30
35
"D"
CENTER OF
GRAVITY
COMPRESSOR
"C"
"A"
FRONT
OF UNIT
Y
"B"
X
A0295-001-TG
WEIGHTS AND DIMENSIONS
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
Shipping
Operating
X
Y
A
B
C
D
PCE6B36
466
461
32
13
167
131
130
38
PCE6B48
488
483
30
19
158
125
130
75
PCE6B60
505
500
30
20
157
134
140
74
Johnson Controls Unitary Products
13
5324339-YTG-E-0918
RECOMMENDED BLOWER SPEED FOR ELECTRIC HEAT
Model
PCE6B36
PCE6B48
PCE6B60
10
C (ML)
D (LO)
D (LO)
Heater kW
18
-B (MH)
C (ML)
15
A (HI)
C (ML)
D (LO)
20
-A (HI)
B (MH)
25
--A (HI)
NOTE: The recommended HEAT speed selections above will give approximately a 45 degree temperature rise at 0.3" static with 460V power supply. If lower or higher
heating airflow is desired, or if duct static or voltage are different than specified, other speed taps may be used.
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION
Model
Jumper Position
High Cool
36
Low Cool
Heat
High Cool
48
Low Cool
Heat
High Cool
60
Low Cool
Heat
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
0.1
SCFM
1621
1507
1410
1224
1060
1017
974
813
1264
1147
1003
902
1893
1785
1703
1654
1304
1265
1200
1304
1423
1304
1125
1000
2305
2186
2007
1935
1675
1523
1369
1413
1762
1479
1369
1209
0.2
SCFM
1531
1418
1288
1137
964
919
875
721
1179
1056
904
802
1845
1737
1649
1596
1225
1183
1116
1225
1351
1225
1039
912
2255
2144
1963
1887
1627
1463
1307
1352
1724
1418
1307
1147
0.3
SCFM
1454
1339
1209
1052
879
830
780
617
1092
972
813
700
1804
1694
1595
1535
1152
1109
1039
1152
1281
1152
957
820
2215
2101
1919
1840
1566
1405
1251
1295
1661
1361
1251
1084
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1371
1299
1223
1138
1268
1200
1130
1059
1132
1054
982
904
824
748
978
902
795
706
623
538
570
487
742
650
688
595
517
436
509
404
323
237
1017
942
865
787
895
815
735
657
552
470
724
632
602
504
429
348
1672
1625
1764
1717
1650
1597
1547
1501
1436
1385
1546
1491
1370
1315
1483
1427
1072
998
893
842
839
789
1026
950
952
874
757
707
1072
998
893
842
1056
1002
1211
1143
1072
998
893
842
870
791
672
623
529
481
733
652
2164
2103
2074
2024
1956
1930
2059
2003
1873
1828
1781
1731
1788
1754
1702
1645
1512
1473
1423
1374
1350
1302
1248
1196
1196
1141
1082
1024
1130
1073
1240
1187
1526
1478
1608
1574
1306
1256
1201
1147
1196
1141
1082
1024
897
835
1022
957
0.8
SCFM
1039
981
831
682
459
415
371
171
735
578
400
292
1576
1452
1327
1252
785
733
652
785
941
785
564
418
1965
1886
1693
1609
1324
1143
964
1015
1429
1092
964
777
0.9
SCFM
966
911
755
611
397
344
291
81
662
511
327
201
1528
1392
1264
1187
731
681
599
731
883
731
507
354
1910
1837
1646
1560
1278
1089
907
959
1390
1037
907
722
1.0
SCFM
869
837
691
549
331
276
222
81
598
450
258
201
1473
1335
1200
1118
648
596
512
648
804
648
416
255
1867
1796
1606
1519
1234
1044
849
905
1341
989
849
669
NOTES:
1. Airflow tested with dry coil conditions, without air filters, at 460 volts
2. Applications above 0.8" w.c. external static pressure are not recommended.
3. Brushless DC high efficiency enhanced ECM blower motor used for all indoor blower assemblies.
4. Minimal variations in airflow performance data results from using downflow duct applications. Data above may be used in those cases.
5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
14
Johnson Controls Unitary Products
5324339-YTG-E-0918
ADDITIONAL STATIC RESISTANCE
Size (Tons)
36 (3.0)
48 (4.0)
60 (5.0)
CFM
Wet Indoor Coil
Economizer1
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
BOTTOM DUCT DIMENSIONS (Inches)
Filter/Frame Kit
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
'
9,(:/22.,1*83
$7%277202)81,7
&
$
5(7851
$,5'8&7
(
%
+2/(´ IRUKLJKYROWDJH
$
6833/<
$,5'8&7
+2/(´ IRU
ORZYROWDJH
)
Model
36, 48, 60
A
14
$
B
13.5
C
5
D
3.5
E
47.5
F
42
REAR DUCT DIMENSIONS (Inches)
127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
HOHFWULFDOOLQHV
NOTES:
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not
to exceed 300 ft/min.
5(7851
$,5'8&7
6833/<
$,5'8&7
$
Model
36, 48, 60
Johnson Controls Unitary Products
$
%
A
13.6
$
B
14
15
5324339-YTG-E-0918
UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A0324-001
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
CONTROL WIRING TO
INDOOR THERMOSTAT
16
A0390-001
Johnson Controls Unitary Products
5324339-YTG-E-0918
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF
CONDENSATE
DRAIN
ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT
Johnson Controls Unitary Products
SUPPLY
AIR DUCT
A0389-001
17
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2018 by Johnson Controls, Inc. All rights reserved.
York International Corp.
5005 York Drive
Norman, OK 73069
5324339-YTG-E-0918
Supersedes: 5324339-YTG-D-1117