DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
TECHNICAL GUIDE
SINGLE PACKAGE
AIR CONDITIONER / GAS HEAT
14 SEER – R-410A – 3 PHASE
3 THRU 5 NOMINAL TONS - 208/230V
50 THRU 125 MBH HEAT INPUT
MODELS: PCG4*36 THRU 60
• Operating Efficiency - All PCG4 model gas units provide a
minimum AFUE of 81.0% in heating and 14.0 SEER, 11.0
EER rating for cooling operation. All models meet California
Low-Nox requirements of 40 ng/joule emission level for Air
Quality Management Districts.
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
• Utility Connections Made Easy - Gas and electric utility
access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
®
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Standard 1-Year limited parts warranty.
Standard 5-Years limited compressor warranty.
Lifetime gas heat exchanger warranty with registration.
See limited warranty certificate in User’s Information Manual for details.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the evaporator coil to collect
and drain all condensate, preventing build-up of stagnant
condensate. The condensate pan conforms to ASHRAE 6289 standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder paint finish insure less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).
Continued on next page.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5564039-YTG-A-1018
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from
all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• More Attractive Appearance - A single-piece top cover
containing a top-discharge outdoor fan arrangement requires
less square footage on installation and provides a wider variety of installations. The one-piece design adds greater water
integrity. Rounded corners with water drip edges add to the
attractive appearance.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping. This
allows compact location on multi-unit applications.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. This design strategically places embossments in the pan for optimum strength
and rigidity.
• Fan System - All models operate over a wide range of
design conditions with a standard ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Simple Control Circuit - A low voltage gas heat printed circuit board contains a status/diagnostic indicator light. Field
thermostat wiring connects to color coded leads using twist
on wire connections. Cooling controls use contactor and
relays for simple application and troubleshooting. Mate-nlock plug connectors are used. The electrical control box is
not located in the compressor compartment. The controls are
mounted to allow the separate access panel to be removed
for trouble shooting and maintenance without affecting the
normal system operating pressures. All wiring internal to the
unit is color/number coded.
2
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur.
• Pressure Switches - A high pressure switch is standard in
all units. When abnormal conditions are sensed through the
pressure switch, the unit will lock out preventing any further
operation until reset or problem is corrected.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils use tin-coated copper
tubing with aluminum fins for effective heat transfer.
• Heat Exchangers - Gas heat exchangers use corrosionresistant, stainless-steel tubular construction to provide longlife, trouble-free operation. Gas heat exchangers are offered
with lifetime warranties as standard with registration.
• Post Purge Induced Draft Combustion - Exhausts combustion products from the heat exchanger upon completion
of the heating cycle to prolong the heat exchanger life.
• Spark To Burner Ignition - No pilot assembly required,
which provides more consistent ignition in gas heating mode.
This ignition is highly reliable, durable and eliminates nuisance lockouts.
• Multi Port In-shot Burners - No field adjustment is required
to mix the air and gas for natural gas or propane use. These
burners are constructed of high-grade corrosion-resistant,
aluminized steel.
• Low Maintenance - Long life, permanently lubricated outdoor and evaporator fan motor bearings need no annual
maintenance, adding greater reliability to the unit. Slide-out
blower assembly can be easily removed for cleaning.
• Easy Service Access - Individual access panels covering
the electrical and gas controls makes servicing easy. Removing this panel will allow easy removal of the blower assembly
for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
• Filter Frame Kit - All 3 phase units include a filter frame kit,
which is shipped inside the unit from production. Field installation is required.
• Filters - All 3 phase units include an applicable number of 1"
washable filters, which are shipped inside the unit from production. Field installation is required. Two filters are required
for A base units. Three filters are required for B base units.
Johnson Controls Unitary Products
5564039-YTG-A-1018
NOMENCLATURE
PCG
1
4
2
A
3
24
4
050
5
1. Model Family
PCG - packaged A/C with gas heat,
PCE - packaged A/C with electric heat,
PHE - packaged heat pump with electric heat
3
X
1
6
7
8
5. Gas Heating Input BTU/Hr x 1000
050 = 50,000 BTU/Hr. input, blank = electric heat
6. Voltage-Phase-Frequency
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
7. NOx Approval
X = low-NOx, blank = not low-Nox
8. Generation Level
1 = first generation
9. Revision Level
A = original release, B = second release
A
9
2. Nominal Cooling Efficiency
4 = 14 SEER, 6 = 16 SEER, etc.
3. Cabinet Size
A = small 35 x 51, B = large 45 x 51
4. Nominal Air Conditioning Cooling Capacity
24 = Nominal Capacity, etc.
Examples:
PCG4B421002X1A is a packaged A/C with gas heat, 14 SEER, 3-1/2 ton, large cabinet, three-stage heat, 100,000 BTU gas heat, 230 volt, three
phase, low-NOx model (first generation, first release)
COMPONENT LOCATION
FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)
CONTROL BOARD
TRANSFORMER
BLOWER MOTOR
HIGH VOLTAGE
CONTACTOR
TXV
PRESSURE SWITCH
INDOOR COIL
DRAFT INDUCER BLOWER
INDOOR BLOWER
GAS VALVE
COMPRESSOR
GAS HEAT
EXCHANGER
REMOVABLE
BASE RAILS
BURNER
ASSEMBLY
A0297-001
UNIT LIMITATIONS
Model
A36
A42
B48
B60
Unit Voltage
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
Johnson Controls Unitary Products
Min
187
187
187
187
Unit Limitations
Applied Voltage
Max
252
252
252
252
Outdoor DB Temp
Max (°F)
125
125
125
125
3
5564039-YTG-A-1018
ACCESSORIES
• Propane Conversion Kit (S1-1NP0703, S1-1NP0704) - Kit
includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural
gas to propane.
• Economizer for Downflow Applications
(S1-2EE04710024, S1-2EE04710124) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor, and barometric
relief damper. Separate field accessories of single enthalpy
and dual enthalpy are also available.
• Economizer for Horizontal Applications
(S1-2EE04710224, S1-2EE04710324) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood and dry bulb sensor. Separate field
accessories of single enthalpy and dual enthalpy are also
available.
• Barometric Relief Hood (S1-1RD0501) - Used in conjunction with a horizontal economizer, the Barometric Relief
Hood helps to equalize the building pressure that is caused
by the fresh air that is introduced through the economizer
fresh air hood.
• Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) Sensor replaces dry bulb sensor standard in economizer kit.
Provides improved economizer operation by sensing the dry
bulb temperature from outdoors plus the enthalpy content of
the outdoor air.
• Duct/Unit Mount CO2 Kit (S1-2AQ04700924) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Wall Mount CO2 Kit (S1-2AQ04701024) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Supply Air Temperature Sensor Kit (S1-TE-63616E-2D) Outdoor supply air temperature sensor kit used with economizers.
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Loss of Charge Switch (S1-2LC00024) - Kit provides Loss
of Charge sensor and wiring to provide safe shutdown of
compressor.
• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
• Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 14 inch high roof curbs.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PCG4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCG4 price pages
for more details.
• Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.
• Filter/Frame Kit (Kit provided)
(S1-1FF0602, S1-1FF0601) - Kit contains the necessary
hardware to field install return air filters into the base unit.
The filter rack is suitable for either 1" or 2" filters.
• Thermostat - Compatible thermostat controls are available
through accessory sourcing. For optimum performance,
these outdoor units are fully compatible with the York Hx™
Touchscreen Thermostat available through Source1. For
more information, see the thermostat section of the Product
Equipment Catalog.
• Filter (S1-02647812000) - Washable 1” filter. Two filters are
required for A base units. Three filters are required for B
base units. Washable filters are included inside shipped units
for field installation.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat/single
stage cool thermostats - with or without the economizer.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
• Low Ambient Kit (S1-2LA04701024) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
4
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
Johnson Controls Unitary Products
5564039-YTG-A-1018
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. Package units give you the flexibility and
choices you need in today’s market. These packaged cooling/
heating air conditioners are designed for outdoor installation.
Only utility and duct connections are required at the point of
installation. The single-stage gas fired heaters have stainless
steel tubular heat exchangers and spark to burner ignition.
They are available in natural gas with field conversion to
propane.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heating units, designed for outdoor installation.
For SEER ratings, refer to technical literature. They shall have
built in, equal size, field convertible duct connections for supply/
return or horizontal supply/return. The units shall be factory
wired, piped, charged with R-410A Refrigerant and factory
tested prior to shipment. All unit wiring shall be both numbered
and color coded. All models shall be rated in accordance with
DOE and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed and classified to ANSI
Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of G-90 galvanized, powderpainted steel, certified at 1000 hours salt spray test per ASTMB117 standards. The unit top shall be a single piece design,
with drip edges and no-seam corners to provide optimum water
integrity. Unit shall have a rigidly mounted outdoor coil guard to
provide protection from objects and personnel after installation.
Indoor blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit. Condensate pan shall be internally sloped and
conform to ASHRAE 62-89 self-draining standards, with 3/4”
NPT female ridged mount connection.
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.
Johnson Controls Unitary Products
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of +/- 10% of the unit
nameplate voltage.
b. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
Coils:
a. Indoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced tin-coated copper tubes with all joints brazed.
b. Indoor coil shall be of the direct expansion, draw through
design.
c. Outdoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
d. Outdoor coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Thermal expansion devices (TXV's) shall be factory
mounted and provided.
b. Filter/strainer to eliminate any foreign matter.
GAS HEATING SECTION
Heat exchanger and exhaust system shall be constructed of
corrosion-resistant materials and shall be designed with
induced draft combustion with post purge logic and redundant
main gas valve. The heat exchanger shall be of the tubular
type, constructed of stainless steel for corrosion resistance and
allowing minimum mixed air entering temperature of 40ºF.
Burners shall be of the in-shot type, constructed of
aluminumized steel. All gas piping shall enter the unit cabinet at
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(s) (manual reset).
d. Flame proving controls.
All gas heat models will meet the California requirement for
emissions of less than 40 nanograms per Joule.
5
5564039-YTG-A-1018
PHYSICAL DATA
COMPONENT
NOMINAL TONNAGE
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
AHRI net capacity (MBH)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI Gas Heat Performance
Heating model
Heat input (K Btu)
Heat output (K Btu)
AFUE%
No. burners
No. stages
Temperature Rise Range (°F)
Max. Static Pressure w.c.
Max. Outlet Air Temp. (°F)
Gas piping connection (in.)
Dimensions (inches)
Length
Width
Height
Operating WT. (lbs.)
Compressors
Type
Outdoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Indoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Outdoor Fan Data
Fan diameter (Inch)
Type
Drive type
No. speeds
Motor HP each
RPM
Nominal total CFM
Direct Drive Indoor Fan Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
Filter
Filter Size
Quantity - Size
6
50
50.0
40
81.0
2
1
35-65
394
PCG4A36
3.0
PCG4A42
3.5
37.2
34.6
11.0
14.0
1200
3.2
R410A
8-8
43.5
41.0
11.0
14.0
1400
3.8
R410A
9-4
75
100
75.0
100.0
60
80
81.0
81.0
3
4
1
1
40-70
0.5
180
1/2
51-1/4
35-3/4
47
401
405
75
100
75.0
100.0
60
80
81.0
81.0
3
4
1
1
40-70
0.5
180
1/2
51-1/4
35-3/4
49
441
443
MODELS
PCG4B48
4.0
PCG4B60
5.0
47.7
45.5
11.0
14.0
1600
4.2
R410A
11-3
65
65.0
52
81.0
2
1
460
55.0
52.5
11.0
14.0
2000
4.8
R410A
12-0
100
100.0
80
81.0
3
1
40-70
0.5
180
1/2
125
125.0
100
81.0
4
1
51-1/4
45-3/4
49
468
473
65
65.0
52
81.0
2
1
477
100
100.0
80
81.0
3
1
40-70
0.5
180
1/2
51-1/4
45-3/4
51
481
Scroll
Scroll
Scroll
Scroll
15.1
2
22
3/8
Interlaced
16.9
2
22
3/8
Interlaced
19.5
2
22
3/8
Interlaced
21.5
2
22
3/8
Interlaced
4.6
3
16
3/8
Interlaced
TXV
4.6
3
16
3/8
Interlaced
TXV
6.3
3
16
3/8
Interlaced
TXV
6.3
3
16
3/8
Interlaced
TXV
24
Prop
Direct
1
1/4
850
2400
24
Prop
Direct
1
1/4
850
2400
26
Prop
Direct
1
1/3
850
3200
26
Prop
Direct
1
1/3
850
3200
11 x 10
Centrifugal
1/2
1200 Max
48
11 x 10
Centrifugal
3/4
1200 Max
48
11 x 10
Centrifugal
3/4
1200 Max
48
11 x 10
Centrifugal
1
1200 Max
48
A
B
B
A
3/4
125
125.0
100
81.0
4
1
488
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters. For internal filter use, a filter rack kit is included with all three phase models. Consult the instructions
supplied with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.
Johnson Controls Unitary Products
5564039-YTG-A-1018
COOLING PERFORMANCE DATA - 3 TON
PACKAGED UNIT MODEL NO. PCG4A36
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
36.0 38.3
55 / 45
S.C.
34.5 30.6
K.W.
1.82 1.83
T.C.
34.6 36.4
65 / 55
S.C.
33.2 29.8
K.W.
2.01 2.02
T.C.
33.2 34.6
75 / 63
S.C.
32.0 28.9
K.W.
2.20 2.20
T.C.
31.7 32.6
85 / 69
S.C.
30.4 26.9
K.W.
2.46 2.44
T.C.
30.1 30.6
95 / 75
S.C.
28.8 25.0
K.W.
2.72 2.67
T.C.
29.0 28.3
105 / 83
S.C.
27.5 23.9
K.W.
2.91 2.92
T.C.
27.9 26.0
115 / 89
S.C.
26.3 22.9
K.W.
3.11 3.16
T.C.
26.8 23.8
125 / 95
S.C.
25.1 21.9
K.W.
3.30 3.39
1000
75
62
40.3
27.6
1.83
37.4
26.0
2.02
34.5
24.5
2.21
32.2
23.3
2.47
29.8
22.2
2.73
27.8
20.9
2.95
25.9
19.6
3.17
24.0
18.3
3.39
80
67
44.9
27.9
1.83
42.6
26.8
2.03
40.3
25.7
2.22
37.8
24.6
2.48
35.3
23.4
2.74
32.8
21.8
2.96
30.4
20.3
3.19
28.0
18.7
3.41
80
72
48.1
22.6
1.85
46.1
21.6
2.04
44.0
20.7
2.23
41.2
19.3
2.49
38.4
17.9
2.74
36.1
16.9
2.97
33.9
15.9
3.20
31.7
14.9
3.42
80
57
38.9
37.1
1.89
37.3
35.6
2.09
35.7
34.1
2.28
34.0
32.4
2.53
32.3
30.8
2.79
31.1
29.4
2.95
30.0
28.1
3.10
28.9
26.8
3.25
80
62
40.4
33.8
1.90
38.3
32.9
2.09
36.3
32.0
2.28
34.0
30.3
2.53
31.7
28.6
2.77
29.6
27.1
3.01
27.4
25.8
3.24
25.3
24.4
3.47
1200
75
62
42.1
29.9
1.90
39.4
28.5
2.09
36.6
27.2
2.28
33.8
25.8
2.54
31.0
24.3
2.80
28.9
22.9
3.02
26.8
21.6
3.24
24.8
20.2
3.46
80
67
46.8
30.2
1.91
44.2
28.9
2.10
41.7
27.7
2.30
38.9
26.5
2.55
36.2
25.3
2.81
33.8
23.8
3.04
31.4
22.3
3.26
29.0
20.9
3.48
80
72
49.8
23.9
1.92
47.9
23.4
2.11
46.1
22.9
2.30
42.8
21.1
2.56
39.6
19.3
2.82
37.1
18.2
3.05
34.7
17.2
3.27
32.3
16.2
3.49
80
57
41.8
39.6
1.97
40.0
37.9
2.16
38.1
36.1
2.36
36.3
34.5
2.61
34.5
32.8
2.87
33.3
31.3
2.98
32.1
29.9
3.10
31.0
28.5
3.21
80
62
42.5
37.1
1.97
40.2
36.1
2.16
37.9
35.2
2.36
35.4
33.7
2.61
32.8
32.2
2.87
30.8
30.4
3.10
28.9
28.6
3.32
26.9
26.9
3.55
1400
75
62
43.9
32.2
1.98
41.3
31.0
2.17
38.7
29.9
2.36
35.4
28.2
2.61
32.1
26.5
2.87
29.9
25.0
3.10
27.8
23.5
3.32
25.6
22.1
3.54
80
67
48.8
32.5
1.99
45.9
31.1
2.18
43.1
29.7
2.37
40.1
28.4
2.63
37.1
27.2
2.88
34.7
25.8
3.11
32.3
24.4
3.33
30.0
23.1
3.55
80
72
51.5
25.1
1.99
49.8
25.1
2.19
48.2
25.0
2.38
44.5
22.8
2.63
40.8
20.7
2.89
38.1
19.6
3.12
35.5
18.5
3.35
33.0
17.4
3.57
80
67
51.8
34.4
2.38
48.9
32.8
2.62
46.0
31.3
2.87
42.7
28.5
3.18
39.3
25.8
3.48
34.9
24.5
3.90
30.7
23.1
4.30
26.5
21.8
4.70
80
72
57.3
28.7
2.38
54.1
27.5
2.61
51.0
26.2
2.84
47.6
24.5
3.15
44.1
22.8
3.47
39.4
20.9
3.90
34.7
19.0
4.31
30.1
17.2
4.73
80
57
46.5
45.5
2.42
44.4
43.7
2.55
42.2
41.9
2.67
39.3
39.2
2.98
36.5
36.5
3.29
32.5
32.5
3.72
28.7
28.7
4.14
24.9
24.9
4.57
80
62
48.6
42.1
2.44
45.6
40.5
2.68
42.6
38.8
2.93
40.0
36.1
3.24
37.4
33.3
3.54
33.0
30.3
3.97
28.8
27.4
4.38
24.5
24.5
4.79
1400
75
62
48.5
36.2
2.43
45.6
34.4
2.66
42.6
32.7
2.89
39.3
31.0
3.20
35.9
29.4
3.51
31.5
26.9
3.94
27.2
24.4
4.35
22.9
22.0
4.76
80
67
53.7
37.0
2.45
50.5
35.3
2.70
47.4
33.6
2.94
43.8
31.2
3.24
40.2
28.9
3.54
35.5
27.0
3.97
30.9
25.2
4.37
26.4
23.3
4.78
80
72
59.6
30.7
2.47
56.1
29.2
2.71
52.5
27.6
2.94
48.8
25.9
3.26
45.1
24.1
3.57
40.0
22.1
3.99
35.0
20.1
4.41
30.1
18.1
4.82
80
57
49.4
47.8
2.50
46.6
45.5
2.73
43.8
43.3
2.97
40.7
40.4
3.28
37.6
37.6
3.59
33.3
33.3
4.01
29.2
29.2
4.43
25.1
25.1
4.84
80
62
50.2
45.0
2.52
47.0
43.2
2.76
43.9
41.4
3.00
41.8
37.7
3.30
39.7
33.9
3.60
34.8
31.0
4.03
30.1
28.2
4.45
25.4
25.4
4.86
1600
75
62
50.2
38.5
2.51
47.0
36.4
2.74
43.7
34.3
2.97
40.1
32.8
3.28
36.5
31.3
3.59
31.8
28.4
4.01
27.3
25.6
4.42
22.8
22.8
4.83
80
67
55.5
39.6
2.53
52.1
37.7
2.77
48.7
35.9
3.01
44.9
33.9
3.31
41.1
32.0
3.60
36.1
29.5
4.03
31.1
27.2
4.45
26.2
24.8
4.87
80
72
61.9
32.6
2.56
58.0
30.8
2.80
54.1
29.0
3.04
50.0
27.3
3.36
46.0
25.5
3.67
40.6
23.3
4.09
35.3
21.2
4.50
30.1
19.1
4.91
COOLING PERFORMANCE DATA - 3.5 TON
PACKAGED UNIT MODEL NO. PCG4A42
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
43.7 46.9
55 / 45
S.C.
43.1 39.2
K.W.
2.35 2.36
T.C.
42.2 44.1
65 / 55
S.C.
41.9 37.7
K.W.
2.36 2.61
T.C.
40.6 41.3
75 / 63
S.C.
40.6 36.3
K.W.
2.38 2.86
T.C.
38.0 38.2
85 / 69
S.C.
38.0 34.5
K.W.
2.69 3.17
T.C.
35.4 35.1
95 / 75
S.C.
35.4 32.7
K.W.
3.00 3.48
T.C.
31.7 31.2
105 / 83
S.C.
31.7 29.6
K.W.
3.44 3.90
T.C.
28.2 27.4
115 / 89
S.C.
28.2 26.7
K.W.
3.86 4.31
T.C.
24.7 23.7
125 / 95
S.C.
24.7 23.7
K.W.
4.29 4.71
Johnson Controls Unitary Products
1200
75
62
46.8
33.9
2.36
44.1
32.5
2.59
41.4
31.0
2.82
38.4
29.3
3.13
35.4
27.6
3.44
31.2
25.4
3.86
27.1
23.3
4.28
23.0
21.2
4.69
7
5564039-YTG-A-1018
COOLING PERFORMANCE DATA - 4 TON
PACKAGED UNIT MODEL NO. PCG4B48
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
50.7 55.0
55 / 45
S.C.
48.2 44.8
K.W.
2.48 2.52
T.C.
48.0 52.0
65 / 55
S.C.
44.3 43.2
K.W.
2.76 2.79
T.C.
45.4 49.0
75 / 63
S.C.
40.3 41.7
K.W.
3.04 3.06
T.C.
42.9 45.4
85 / 69
S.C.
38.3 39.8
K.W.
3.41 3.42
T.C.
40.4 41.8
95 / 75
S.C.
36.4 38.0
K.W.
3.79 3.79
T.C.
36.7 37.6
105 / 83
S.C.
32.3 34.7
K.W.
4.30 4.30
T.C.
33.1 33.6
115 / 89
S.C.
28.4 31.6
K.W.
4.80 4.80
T.C.
29.5 29.5
125 / 95
S.C.
24.5 28.4
K.W.
5.30 5.29
1400
75
62
54.4
38.3
2.51
51.2
36.7
2.79
48.1
35.0
3.06
44.9
33.2
3.42
41.7
31.4
3.78
37.5
29.7
4.29
33.3
28.0
4.79
29.2
26.4
5.30
80
67
59.4
38.5
2.54
57.1
37.1
2.81
54.9
35.7
3.08
51.3
33.7
3.44
47.7
31.8
3.80
43.5
30.0
4.32
39.4
28.4
4.83
35.3
26.7
5.33
80
72
65.3
30.4
2.56
62.8
29.6
2.83
60.3
28.7
3.11
56.4
27.3
3.46
52.4
25.9
3.82
47.8
23.9
4.34
43.4
21.9
4.85
39.0
19.9
5.35
80
57
53.0
49.3
2.56
50.3
46.3
2.83
47.5
43.4
3.10
44.8
41.4
3.47
42.1
39.4
3.85
38.1
34.3
4.36
34.1
29.4
4.87
30.2
24.5
5.37
80
62
56.8
48.2
2.59
53.6
46.6
2.85
50.4
45.1
3.12
46.6
42.4
3.49
42.7
39.7
3.85
38.4
36.1
4.36
34.3
32.5
4.86
30.1
29.0
5.36
1600
75
62
56.1
41.0
2.58
52.9
39.3
2.85
49.6
37.6
3.12
46.1
35.7
3.48
42.6
33.8
3.83
38.0
31.1
4.35
33.6
28.6
4.86
29.2
26.0
5.36
80
67
61.2
40.7
2.61
58.7
39.4
2.88
56.2
38.1
3.14
52.5
36.3
3.50
48.7
34.5
3.86
44.3
32.6
4.38
40.0
30.7
4.89
35.7
28.8
5.39
80
72
67.2
31.9
2.62
64.4
30.8
2.89
61.6
29.7
3.17
57.7
28.4
3.53
53.8
27.0
3.89
48.9
24.9
4.41
44.2
22.9
4.91
39.5
20.9
5.41
80
57
55.4
50.3
2.64
52.5
48.4
2.90
49.6
46.4
3.16
46.7
44.4
3.53
43.9
42.4
3.90
39.5
36.4
4.43
35.2
30.5
4.93
30.9
24.6
5.44
80
62
58.6
51.5
2.65
55.2
50.0
2.92
51.8
48.4
3.18
47.7
44.9
3.55
43.6
41.4
3.91
39.2
37.4
4.42
35.0
33.5
4.92
30.7
29.6
5.42
1800
75
62
57.9
43.6
2.64
54.5
41.9
2.91
51.1
40.2
3.18
47.2
38.2
3.54
43.4
36.2
3.89
38.6
32.6
4.41
33.8
29.1
4.92
29.1
25.6
5.42
80
67
63.1
42.9
2.67
60.3
41.7
2.94
57.5
40.5
3.21
53.6
38.9
3.57
49.7
37.3
3.92
45.1
35.1
4.44
40.6
33.0
4.95
36.1
31.0
5.45
80
72
69.1
33.4
2.68
66.0
32.1
2.95
62.9
30.8
3.23
59.1
29.4
3.59
55.2
28.1
3.95
50.0
26.0
4.47
45.0
23.9
4.97
40.0
21.9
5.47
80
67
73.0
43.7
3.00
69.7
43.2
3.31
66.4
42.7
3.63
61.8
40.5
4.04
57.1
38.2
4.44
51.1
36.0
5.01
45.3
33.8
5.57
39.5
31.6
6.12
80
72
79.5
36.0
3.03
75.7
34.9
3.35
72.0
33.7
3.67
67.1
31.6
4.07
62.3
29.4
4.48
55.2
26.7
5.05
48.3
24.0
5.60
41.4
21.3
6.15
80
57
70.4
66.7
3.15
66.2
62.8
3.46
62.1
59.0
3.78
58.7
56.2
4.19
55.3
53.5
4.61
52.5
50.0
5.22
49.8
46.6
5.80
47.1
43.1
6.39
80
62
70.4
57.0
3.17
66.4
55.9
3.48
62.5
54.7
3.79
57.8
52.2
4.21
53.0
49.7
4.62
47.6
44.0
5.19
42.3
38.4
5.75
36.9
32.9
6.30
1800
75
62
69.3
48.8
3.18
65.1
46.7
3.49
60.9
44.7
3.80
56.6
43.1
4.21
52.3
41.5
4.62
45.6
37.3
5.19
39.0
33.3
5.74
32.5
29.2
6.30
80
67
74.8
46.3
3.21
71.0
45.4
3.52
67.1
44.5
3.84
62.3
42.5
4.24
57.5
40.4
4.65
51.0
37.8
5.22
44.7
35.3
5.77
38.3
32.8
6.32
80
72
80.8
37.1
3.24
76.5
35.7
3.56
72.2
34.3
3.88
67.4
32.8
4.28
62.6
31.2
4.68
55.2
28.1
5.25
47.9
25.0
5.80
40.7
21.9
6.35
80
57
72.7
70.1
3.36
68.4
65.3
3.68
64.0
60.6
3.99
60.0
57.5
4.41
56.1
54.4
4.82
52.8
50.4
5.40
49.7
46.6
5.96
46.6
42.7
6.52
80
62
71.7
59.2
3.38
67.5
58.3
3.69
63.2
57.5
4.00
58.4
55.0
4.42
53.7
52.5
4.83
47.9
45.8
5.40
42.3
39.4
5.95
36.8
32.9
6.51
2000
75
62
70.5
51.4
3.38
65.9
48.9
3.69
61.4
46.3
4.01
57.0
45.1
4.42
52.5
43.8
4.83
45.2
38.3
5.40
38.1
33.1
5.95
31.0
27.8
6.50
80
67
76.6
48.8
3.42
72.3
47.6
3.73
67.9
46.3
4.04
62.9
44.5
4.45
57.9
42.6
4.86
50.9
39.7
5.42
44.0
36.9
5.97
37.2
34.1
6.52
80
72
82.2
38.2
3.45
77.4
36.5
3.77
72.5
34.9
4.08
67.7
33.9
4.48
62.9
33.0
4.88
55.1
29.5
5.45
47.5
26.0
6.00
39.9
22.6
6.55
COOLING PERFORMANCE DATA - 5 TON
PACKAGED UNIT MODEL NO. PCG4B60
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
68.0 69.1
55 / 45
S.C.
63.3 54.8
K.W.
2.93 2.97
T.C.
64.1 65.4
65 / 55
S.C.
60.3 53.4
K.W.
3.25 3.27
T.C.
60.2 61.8
75 / 63
S.C.
57.4 52.0
K.W.
3.56 3.58
T.C.
57.4 57.1
85 / 69
S.C.
55.0 49.4
K.W.
3.98 4.00
T.C.
54.5 52.4
95 / 75
S.C.
52.6 46.9
K.W.
4.40 4.42
T.C.
52.1 47.2
105 / 83
S.C.
49.5 42.1
K.W.
5.03 4.99
T.C.
49.8 42.2
115 / 89
S.C.
46.6 37.5
K.W.
5.65 5.54
T.C.
47.5 37.1
125 / 95
S.C.
43.6 32.8
K.W.
6.27 6.09
8
1600
75
62
68.1
46.2
2.97
64.3
44.6
3.28
60.5
43.1
3.59
56.2
41.1
4.01
52.0
39.2
4.42
45.9
36.3
4.99
40.0
33.4
5.54
34.1
30.6
6.09
Johnson Controls Unitary Products
5564039-YTG-A-1018
81,77233$1(/
&251(53267
,1'225&2,/
&2,/*8$5'
+,*+92/7$*(
23(1,1*´
&
+,*+92/7$*(
23(1,1*´
&20%867,21$,5,17$.(
+($7(;&+$1*(5$&&(663$1(/
&2035(6625
$&&(663$1(/
)/8((;+$867+22'
&21'(16$7(
'5$,1
%/2:(5
$&&(66
3$1(/
$
%
/2:92/7$*(23(1,1*´
*$66833/<+2/(´:,7+
*5200(723(1,1*2)´
&21752/+($7
$&&(663$1(/
$
UNIT DIMENSIONS
Model
A36
A42
B48
B60
A
51-1/4
51-1/4
51-1/4
51-1/4
Dimensions
B
35-3/4
35-3/4
45-3/4
45-3/4
C
47
49
49
51
UNIT CLEARANCES1,2
Direction
Top3
Side Opposite Ducts
Duct Panel
1.
2.
3.
4.
Distance (in.)
36
36
0
Direction
Power Entry (Right Side)
Left Side
Bottom4
Distance (in.)
36
24
1
A 1" clearance must be provided between any combustible material and the supply air duct work.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
Units may be installed on combustible floors made from class A, B or C roof covering materials.
Johnson Controls Unitary Products
9
5564039-YTG-A-1018
INDOOR BLOWER SPECIFICATIONS
Motor
Model
HP
1/3
1/2
1/3
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
3/4
1
1
1
24050
24075
30050
30075
36050
36075
36100
42075
42100
48065
48100
48125
60065
60100
60125
RPM
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
EFF.
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
SF
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Frame
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
SOUND PERFORMANCE
Model
(Tons)
Sound Rating1
dB (A)
A36
A42
B48
B60
74
74
74
76
125
58.5
63.5
63.5
72.3
250
61.8
63.9
63.9
65.0
Octave Band Centerline Frequency (Hz)
500
1000
2000
65.4
66.5
60.7
62.3
65.0
64.0
62.3
65.0
64.0
63.9
64.0
60.0
4000
54.8
54.1
54.1
55.5
8000
49.8
46.6
46.6
49.0
1. Rated in accordance with AHRI Standard 270.
ELECTRICAL DATA
Model
36050, 36075
36100
42075, 42100
48065, 48100, 48125
60065, 60100, 60125
Compressor
Voltage
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
208/230-3-60
OD Fan
Motor
Supply
Blower Motor
RLA
LRA
MCC
FLA
FLA
10.4
10.4
13.5
13.7
16.0
73.0
73.0
88.0
83.1
110.0
16.3
16.3
21.1
21.4
24.9
1.3
1.3
1.3
1.7
1.7
3.8
5.4
5.4
5.4
7.0
MCA1
(Amps)
18.1
18.1
23.6
24.2
28.7
Max Fuse2/
Breaker3 Size
(Amps)
25
25
35
35
40
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
10
Johnson Controls Unitary Products
5564039-YTG-A-1018
"D"
CENTER OF
GRAVITY
COMPRESSOR
"C"
"A"
FRONT
OF UNIT
Y
"B"
X
A0295-001-TG
WEIGHTS AND DIMENSIONS
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
36050
36075
36100
42075
Shipping
399
406
410
446
Operating
394
401
405
441
X
28
28
28
28
Y
15
15
15
15
A
141
135
139
145
B
107
115
113
112
C
94
103
99
99
D
78
74
80
85
42100
48065
48100
48125
60065
60100
60125
448
465
473
478
482
486
493
443
460
468
473
477
481
488
28
28
28
28
29
28
27
15
15
15
15
15
15
15
148
189
169
164
174
177
151
110
116
139
145
142
140
167
96
93
115
124
124
117
141
89
117
100
95
92
102
84
Johnson Controls Unitary Products
11
5564039-YTG-A-1018
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION
Model
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
851
790
730
674
1042
995
942
889
1126
1084
1032
980
1186
1144
1097
1049
1389
1345
1305
1262
1090
1046
993
941
1126
1084
1032
980
1186
1144
1097
1049
1222
1179
1133
1086
1389
1345
1305
1262
1217
1178
1134
1082
1293
1251
1208
1163
1423
1386
1346
1302
1530
1495
1454
1414
1810
1757
1705
1653
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
1003
1180
1259
1314
1506
1225
1259
1314
1348
1506
1342
1425
1554
1658
1966
0.2
SCFM
952
1133
1209
1271
1471
1174
1209
1271
1306
1471
1302
1368
1503
1599
1914
0.3
SCFM
904
1085
1166
1229
1403
1131
1166
1229
1259
1403
1260
1332
1465
1588
1862
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
1315
1436
1458
1573
1966
1436
1544
1573
1681
1935
1046
1295
1620
1798
2146
1620
1694
1798
1835
2146
1620
1798
1266
1382
1406
1523
1914
1382
1492
1523
1640
1887
1009
1250
1564
1722
2085
1564
1630
1722
1758
2085
1564
1722
1229
1342
1365
1484
1862
1342
1455
1484
1599
1834
980
1213
1517
1669
2025
1517
1580
1669
1703
2025
1517
1669
1194
1304
1327
1445
1810
1304
1416
1445
1557
1788
946
1172
1466
1620
1960
1466
1530
1620
1653
1960
1466
1620
1156
1262
1286
1408
1757
1262
1376
1408
1517
1743
915
1133
1418
1572
1872
1418
1482
1572
1604
1872
1418
1572
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
60065
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
60100
Medium (3)
Medium/High (4)
High (5)
Continued on next page.
1922
2001
2146
1073
1329
2054
2195
2445
1730
1858
2054
2195
2445
1863
1952
2085
1043
1292
1998
2144
2388
1682
1807
1998
2144
2388
1804
1890
2025
1009
1250
1934
2098
2306
1628
1749
1934
2098
2306
1754
1839
1960
988
1223
1890
2049
2293
1592
1710
1890
2049
2293
1724
1820
1872
963
1192
1843
2003
2235
1552
1667
1843
2003
2235
36050
36075
36100
42075
42100
48065
48100
48125
12
Motor Speed
0.8
SCFM
633
834
928
998
1216
888
928
998
1036
1216
1034
1113
1257
1373
1.0
SCFM
551
724
824
896
1124
782
824
896
936
1124
938
1013
1167
1291
1117
1220
1244
1367
1705
1220
1336
1367
1478
1701
878
1087
1360
1527
1862
1360
1430
1527
1558
1862
1360
1080
1179
1203
1327
1653
1179
1294
1327
1436
1651
844
1045
1308
1480
1798
1308
1380
1480
1511
1798
1308
1600
1036
1131
1155
1279
1600
1131
1248
1279
1393
1591
779
964
1206
1413
1735
1206
1292
1413
1442
1735
1206
1496
948
1035
1059
1183
1496
1035
1156
1183
1307
1471
649
802
1002
1280
1609
1002
1116
1280
1304
1609
1002
1527
1658
1742
1862
941
1165
1801
1955
2178
1517
1629
1801
1955
2178
1480
1612
1696
1798
917
1136
1757
1883
2129
1479
1589
1757
1883
2129
1413
1559
1651
1735
892
1105
1710
1868
2077
1439
1546
1710
1868
2077
1280
1453
1561
1609
842
1043
1616
1838
1973
1359
1460
1616
1838
1973
Johnson Controls Unitary Products
5564039-YTG-A-1018
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION (Continued)
1.
2.
3.
4.
5.
Model
Motor Speed
60125
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
2063
2130
2195
2275
2445
0.2
SCFM
2008
2084
2144
2252
2388
0.3
SCFM
1943
2032
2098
2169
2306
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1899
1851
1809
1763
1983
1927
1951
1860
2049
2003
1955
1883
2154
2112
2065
1989
2293
2235
2178
2129
0.8
SCFM
1717
1815
1868
1976
2077
1.0
SCFM
1625
1725
1838
1950
1973
0.8
SCFM
1.0
SCFM
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
AIRFLOW PERFORMANCE - BOTTOM DUCT APPLICATION
Model
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
861
807
757
700
Low (1)
0.1
SCFM
1008
0.2
SCFM
962
0.3
SCFM
916
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
1190
1262
1324
1517
1231
1270
1317
1358
1517
1340
1409
1527
1663
1930
1332
1457
1451
1568
1978
1455
1566
1148
1223
1282
1475
1186
1225
1286
1317
1475
1299
1368
1492
1585
1892
1295
1419
1412
1524
1937
1414
1532
1106
1181
1245
1447
1146
1189
1245
1275
1447
1264
1334
1470
1594
1853
1263
1376
1371
1491
1891
1379
1492
1055
1137
1202
1400
1103
1140
1198
1238
1400
1224
1291
1419
1601
1805
1222
1340
1339
1464
1837
1335
1455
1008
1091
1161
1357
1069
1098
1151
1197
1357
1182
1253
1385
1521
1760
1185
1299
1296
1425
1785
1294
1416
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
48065
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
48100
Medium (3)
Medium/High (4)
High (5)
Continued on next page.
1565
1675
1946
1032
1272
1611
1892
2131
1598
1663
1789
1931
2131
1530
1641
1909
999
1236
1574
1777
2058
1548
1612
1733
1814
2058
1491
1606
1863
970
1204
1518
1771
1998
1502
1568
1670
1808
1998
1458
1578
1815
938
1165
1494
1701
1949
1454
1522
1650
1736
1949
1419
1535
1771
910
1129
1439
1639
1892
1410
1476
1596
1673
1892
36050
36075
36100
42075
Motor Speed
42100
Johnson Controls Unitary Products
955
1044
1112
1318
1030
1046
1110
1148
1318
1182
1201
1343
1480
1696
1148
1253
1257
1383
1725
1254
914
994
1067
1275
977
1008
1064
1105
1275
1097
1173
1299
1440
1625
1110
1215
1211
1345
1656
1212
650
863
952
1018
1232
912
960
1024
1057
1232
1049
1128
1250
1400
1553
1063
1160
1165
1296
1604
1160
550
761
868
920
1146
781
866
943
961
1146
953
1038
1152
1320
1409
967
1051
1072
1200
1502
1056
1372
1381
1495
1721
879
1081
1405
1617
1840
1362
1422
1578
1650
1840
1333
1336
1455
1654
843
1037
1357
1565
1788
1307
1370
1535
1597
1788
1280
1290
1412
1595
808
968
1266
1489
1728
1251
1297
1483
1519
1728
1174
1198
1326
1477
737
829
1083
1336
1608
1139
1152
1379
1362
1608
13
5564039-YTG-A-1018
AIRFLOW PERFORMANCE - BOTTOM DUCT APPLICATION (Continued)
Model
48125
60065
60100
60125
1.
2.
3.
4.
5.
14
Motor Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
1598
1766
1912
2105
2131
1026
1263
1987
2114
2369
1655
1766
1987
2114
2369
0.2
SCFM
1548
1703
1875
2014
2058
999
1230
1933
2050
2308
1612
1720
1933
2050
2308
0.3
SCFM
1502
1656
1805
2006
1998
989
1192
1861
2047
2249
1596
1667
1861
2047
2249
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
1973
2024
2123
2191
2369
1924
1983
2075
2154
2308
1905
1937
2019
2117
2249
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1454
1410
1362
1307
1611
1566
1518
1469
1787
1750
1713
1672
1931
1898
1845
1793
1949
1892
1840
1788
950
907
907
886
1165
1167
1101
1099
1817
1820
1715
1725
1974
1899
1889
1920
2183
2126
2088
2034
1531
1461
1462
1429
1629
1632
1539
1537
1817
1820
1715
1725
1974
1899
1889
1920
2183
2126
2088
2034
1826
1889
1970
2075
2183
1743
1886
1978
2002
2126
1744
1843
1862
1995
2088
1703
1799
1849
2028
2034
0.8
SCFM
1251
1419
1636
1739
1728
862
1071
1651
1866
1990
1391
1498
1651
1866
1.0
SCFM
1139
1319
1564
1631
1608
816
1015
1504
1758
1902
1316
1421
1504
1758
1990
1660
1759
1804
1974
1990
1902
1574
1679
1714
1866
1902
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
5564039-YTG-A-1018
ADDITIONAL STATIC RESISTANCE
Size (Tons)
A36 (3.0)
A42 (3.5)
B48 (4.0)
B60 (5.0)
CFM
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
BOTTOM DUCT DIMENSIONS (Inches)
1
Wet Indoor Coil Economizer
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
Filter/Frame Kit
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.
'
9,(:/22.,1*83
$7%277202)81,7
´
´
&
5(7851
$,5'8&7
$
+2/(´
(
ZLWK´JURPPHW
RSHQLQJIRUJDVSLSH
%
+2/(´
IRUKLJK
YROWDJH
6833/<
$,5'8&7
$
+2/(´ IRU
ORZYROWDJH
)
Model
36, 42
48, 60
A
10
14
B
21.5
13.5
$
C
5
5
D
4.5
3.5
E
47.5
47.5
F
32
42
REAR DUCT DIMENSIONS (Inches)
127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
HOHFWULFDODQGJDVOLQHV
5(7851
$,5'8&7
6833/<
$,5'8&7
$
Model
36, 42
48, 60
Johnson Controls Unitary Products
$
%
A
9.6
13.6
$
B
22
14
15
5564039-YTG-A-1018
UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A032
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
TO GAS
SUPPLY LINE
16
CONTROL WIRING TO
INDOOR THERMOSTAT
A0325-001
Johnson Controls Unitary Products
5564039-YTG-A-1018
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO GAS
SUPPLY LINE
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT
Johnson Controls Unitary Products
SUPPLY
AIR DUCT
A0326-001
17
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2018 by Johnson Controls, Inc. All rights reserved.