York PCG4 User manual

York PCG4 User manual
5564033-YTG-A-0918
DESCRIPTION
These packaged cooling/heating air conditioners are designed
for outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
TECHNICAL GUIDE
SINGLE PACKAGE
AIR CONDITIONER / GAS HEAT
14 SEER – R-410A – 1 PHASE
2 THRU 5 NOMINAL TONS - 208/230V
50 THRU 125 MBH HEAT INPUT
MODELS: PCG4*24 THRU 60
• Operating Efficiency - All PCG4 model gas units provide a
minimum AFUE of 81.0% in heating and 14.0 SEER, 11.0
EER rating for cooling operation. All models meet California
Low-Nox requirements of 40 ng/joule emission level for Air
Quality Management Districts.
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A and tested prior to shipment. Test stations using a
state-of-the-art computerized process system are used to
insure product quality. Refrigerant charge and component
part numbers are verified via computers during assembly.
Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas
system safeties are monitored and recorded by the system to
insure unit performance. Equal size side supply and return
duct connections allow easy connection of ducts to match
low crawl spaces without transition pieces.
• Utility Connections Made Easy - Gas and electric utility
access provided through the bottom or the side of the unit.
Utility connections can be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
®
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Years limited parts and compressor warranty
Lifetime gas heat exchanger warranty with registration.
* Extended warranty requires online registration within 90 days of purchase for
replacement or closing for new home purchase. See limited warranty certificate
in User’s Information Manual for details.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder paint finish insures less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).
Continued on next page.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5564033-YTG-A-0918
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protect the
unit during shipment. The rails provide fork lift access from
all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• Pressure Switches - A high pressure switch is standard in
all units. It is an automatic reset switch. When discharge
pressure reaches 650 psi, the compressor will de-energize
until pressure reaches 450 psi.
• More Attractive Appearance - A single-piece top cover
containing a top-discharge outdoor fan arrangement requires
less square footage on installation and provides a wider variety of installations. The one-piece design adds greater water
integrity. Rounded corners with water drip edges add to the
attractive appearance.
• Heat Exchangers - Gas heat exchangers use corrosionresistant, stainless-steel tubular construction to provide longlife, trouble-free operation. Gas heat exchangers are offered
with lifetime warranties as standard with registration.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping. This
allows compact location on multi-unit applications.
• Outdoor Coil Grille - All models utilize a stamped slotted
design that provides superior impact protection against small
objects during transit and after installation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. This design strategically places embossments in the pan for optimum strength
and rigidity.
• Fan System - All models operate over a wide range of
design conditions with a standard ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed is factory-set and can be field-adjusted to
a second speed. The heating speed is factory set to maintain
mid point rise at the units heating input, but can be field
adjusted. This allows maximum comfort conditions.
• Simple Control Circuit - A low voltage gas heat printed circuit board contains a status/diagnostic indicator light. Field
thermostat wiring connects to color coded leads using twist
on wire connections. Cooling controls use contactor and
relays for simple application and troubleshooting. Mate-nlock plug connectors are used. The electrical control box is
not located in the compressor compartment. The controls are
mounted to allow the separate access panel to be removed
for trouble shooting and maintenance without affecting the
normal system operating pressures. All wiring internal to the
unit is color/number coded.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improve heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils use tin-coated copper
tubing with aluminum fins for effective heat transfer.
• Post Purge Induced Draft Combustion - Exhausts combustion products from the heat exchanger upon completion
of the heating cycle to prolong the heat exchanger life.
• Spark To Burner Ignition - No pilot assembly required,
which provides more consistent ignition in gas heating mode.
This ignition is highly reliable and durable and eliminates nuisance lockouts.
• Multi Port In-shot Burners - No field adjustment is required
to mix the air and gas for natural gas or propane use. These
burners are constructed of high-grade corrosion-resistant,
aluminized steel.
• Low Maintenance - Long life, permanently lubricated outdoor and evaporator fan motor bearings need no annual
maintenance, adding greater reliability to the unit. Slide-out
blower assembly can be easily removed for cleaning.
• Easy Service Access - Individual access panels covering
the electrical and gas controls makes servicing easy. Removing this panel will allow easy removal of the blower assembly
for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
• Loss of Charge Sensor (S1-2LC00024) - Kit provides Loss
of Charge sensor and wiring to provide safe shutdown of
compressor.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PHE4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCE4 price pages
for more details.
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of high pressure relief valve and a temperature sensor which protect the
compressor if undesirable operating conditions occur.
2
Johnson Controls Unitary Products
5564033-YTG-A-0918
NOMENCLATURE
PCG
4
A
24
50
2
X
1
A
1
2
3
4
5
6
7
8
9
1. Model Family
5. Gas Heating Input BTU/Hr x 1000
PCG - packaged A/C with gas heat,
050 = 50,000 BTU/Hr. input, blank = electric heat
PHG - packaged heat pump with gas heat,
6. Voltage-Phase-Frequency
PCE - packaged A/C with electric heat,
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
PHE - packaged heat pump with electric heat
2. Nominal Cooling Efficiency
7. NOx Approval
4 = 14 SEER, 6 = 16 SEER, etc.
X = low-NOx, blank = not low-Nox
3. Cabinet Size
8. Generation Level
A = small 35 x 51, B = large 45 x 51
1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000
9. Revision Level
24 = 24,000 BTU, etc.
A = original release, B = second release
Examples:
PCG4B421002X1A is a packaged A/C with gas heat, 14 SEER, 3-1/2 ton, large cabinet, single-stage heat, 100,000 BTU gas heat, 230 volt, single
phase, low-NOx model (first generation, first release)
COMPONENT LOCATION
FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
(Behind Panel)
CONTROL BOARD
TRANSFORMER
BLOWER MOTOR
HIGH VOLTAGE
CONTACTOR
TXV
PRESSURE SWITCH
INDOOR COIL
DRAFT INDUCER BLOWER
INDOOR BLOWER
GAS VALVE
COMPRESSOR
GAS HEAT
EXCHANGER
REMOVABLE
BASE RAILS
BURNER
ASSEMBLY
A0297-001
UNIT LIMITATIONS
Model
A24
A30
A36
A42
B48
B60
Unit Voltage
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Johnson Controls Unitary Products
Min
187
187
187
187
187
187
Unit Limitations
Applied Voltage
Max
252
252
252
252
252
252
Outdoor DB Temp
Max (°F)
125
125
125
125
125
125
3
5564033-YTG-A-0918
ACCESSORIES
• Propane Conversion Kit (S1-1NP0703, S1-1NP0704) - Kit
includes burner orifices, gas valve conversion and installation instructions necessary to field convert unit from natural
gas to propane.
• Economizer for Downflow Applications
(S1-2EE04710024, S1-2EE04710124) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor, and barometric
relief damper. Separate field accessories of single enthalpy
and dual enthalpy are also available.
• Economizer for Horizontal Applications
(S1-2EE04710224, S1-2EE04710324) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor. Separate field
accessories of single enthalpy and dual enthalpy are also
available.
• Barometric Relief Hood (S1-1RD0501) - Used in conjunction with a horizontal economizer, the Barometric Relief
Hood helps to equalize the building pressure that is caused
by the fresh air that is introduced through the economizer
fresh air hood.
• Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) Sensor replaces supply air temperature dry bulb sensor
standard in economizer kit. Provides improved economizer
operation by sensing the dry bulb temperature of indoor supply air plus the enthalpy content of the outdoor air.
• Duct/Unit Mount CO2 Kit (S1-2AQ04700924) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Wall Mount CO2 Kit (S1-2AQ04701024) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Supply Air Temperature Sensor Kit (S1-TE-63616E-2D) Outdoor supply air temperature sensor kit used with economizers.
• Filter/Frame Kit (S1-1FF0602, S1-1FF0601) - Kit contains
the necessary hardware to field install return air filters into
the base unit. The filter rack is suitable for either 1" or 2" filters.
• Filter (S1-02647812000) - Washable 1" filter. Two filters are
required for A base units. Three filters are required for B
base units.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
4
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
• Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 14 inch high roof curbs.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PCG4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PCG4 price pages
for more details.
• Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications. Includes hood and screen assembly.
• Transformer Kit (S1-2EC06700124) - Kit provides necessary hardware to provide single phase models from factory
furnished 40 VA transformer capability to 75 VA transformer
capability. (Required on installations with economizer or
motorized damper).
• Loss of Charge Switch (S1-2LC00024) - Kit provides Loss
of Charge switch and wiring to provide safe shutdown of
compressor.
• Low Ambient Kit (S1-2LA04701024) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0ºF. Standard unit operation 45ºF.
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
• Thermostat (S1-THXU280*) - Compatible thermostat controls are available through accessory sourcing. For optimum
performance, these outdoor units are fully compatible with
the York Hx™ Touchscreen Thermostat (S1-THXU280*)
available through Source1. For more information, see the
thermostat section of the Product Equipment Catalog.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic and electro-mechanical thermostats. All units can operate with single stage heat/single
stage cool thermostats - with or without the economizer.
* For additional kit numbers refer to the price pages.
Johnson Controls Unitary Products
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. Package units give you the flexibility and
choices you need in today’s market. These packaged cooling/
heating air conditioners are designed for outdoor installation.
Only utility and duct connections are required at the point of
installation. The single-stage gas fired heaters have stainless
steel tubular heat exchangers and spark to burner ignition.
They are available in natural gas with field conversion to
propane.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heating units, designed for outdoor installation.
For SEER ratings, refer to technical literature. They shall have
built in, equal size, field convertible duct connections for supply/
return or horizontal supply/return. The units shall be factory
wired, piped, charged with R-410A Refrigerant and factory
tested prior to shipment. All unit wiring shall be both numbered
and color coded. All models shall be rated in accordance with
DOE and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed and classified to ANSI
Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of G-90 galvanized, powderpainted steel, certified at 1000 hours salt spray test per ASTMB117 standards. The unit top shall be a single piece design,
with drip edges and no-seam corners to provide optimum water
integrity. Unit shall have a rigidly mounted outdoor coil guard to
provide protection from objects and personnel after installation.
Indoor blower section shall be insulated with foil-faced or foam
insulation, fastened to prevent insulation from entering the air
stream. Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for truck access and proper
sealing on roof curb applications. Base rails shall be easily
removable, when required to lower unit height. Filters shall be
field installed, furnished and be accessible through a removable
access door, sealed airtight. Units vertical discharge and return
duct configuration shall be designed to fit between standard 24”
O.C. beams without modification to building structure, duct work
and base unit. Condensate pan shall be internally sloped and
conform to ASHRAE 62-89 self-draining standards, with 3/4”
NPT female ridged mount connection.
Indoor Blower Assembly - Fan shall be direct drive design.
Fan wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
air volume. Bearings shall be sealed and permanently
lubricated for longer life and no maintenance. Fan assembly
shall be a slide-out design for easy removal and cleaning.
Indoor blower motors shall be equipped with a standard high
efficiency brushless DC motor (constant torque) also known as
a standard ECM motor.
Johnson Controls Unitary Products
5564033-YTG-A-0918
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally protected with internal high-pressure relief and over temperature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of +/- 10% of the unit
nameplate voltage.
b. Shall have internal isolation and sound muffling to minimize vibration and noise, and be externally isolated on a
dedicated, independent mounting.
Coils:
a. Indoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced tin-coated copper tubes with all joints brazed.
b. Indoor coil shall be of the direct expansion, draw through
design.
c. Outdoor coils shall have aluminum plate fins mechanically
bonded to seamless internally enhanced copper tubes
with all joints brazed.
d. Outdoor coil shall be draw through design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Thermal expansion devices (TXVs) shall be factory
mounted and provided.
b. Filter/strainer to eliminate any foreign matter.
GAS HEATING SECTION
Heat exchanger and exhaust system shall be constructed of
corrosion-resistant materials and shall be designed with
induced draft combustion with post purge logic and redundant
main gas valve. The heat exchanger shall be of the tubular
type, constructed of stainless steel for corrosion resistance and
allowing minimum mixed air entering temperature of 40 ºF.
Burners shall be of the in-shot type, constructed of
aluminumized steel. All gas piping shall enter the unit cabinet at
a single location through either the side or bottom, without any
field modifications. An integrated control board shall provide
timed control of indoor fan functioning and burner ignition.
Heating section shall be provided with the following minimum
protection:
a. Primary high-temperature limit switch.
b. Induced draft pressure switch.
c. Flame roll out switch(s) (manual reset).
d. Flame proving controls.
All gas heat models will meet the California requirement for
emissions of less than 40 nanograms per Joule (California
requirement on single phase models only).
5
5564033-YTG-A-0918
PHYSICAL DATA
COMPONENT
PCG4A30
2.5
PCG4A36
3.0
MODELS
PCG4A42
3.5
PCG4B48
PCG4B60
NOMINAL TONNAGE
4.0
5.0
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
23.7
30.1
37.2
43.5
47.7
57.0
AHRI net capacity (MBH)
22.8
29.0
34.6
41.0
45.5
55.0
EER
11.2
11.2
11.2
11.2
11.2
11.2
SEER
14.0
14.0
14.0
14.0
14.0
14.0
Nominal CFM
800
1000
1200
1400
1600
2000
System power (KW)
2.1
2.6
3.2
3.8
4.2
4.8
Refrigerant type
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant charge (lb-oz)
6-0
9-0
8-8
9-4
11-3
12-0
AHRI Gas Heat Performance
Heating model
50
75
50
75
50
75
100
75
100
65
100 125
65
100 125
Heat input (K Btu)
50.0 75.0 50.0 75.0 50.0 75.0 100.0 75.0 100.0 65.0 100.0 125.0 65.0 100.0 125.0
Heat output (K Btu)
40
60
40
60
40
60
80
60
80
52
80
100
52
80
100
AFUE %
81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0 81.0
No. burners
2
3
2
3
2
3
4
3
4
2
3
4
2
3
4
No. stages
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Temperature Rise Range (°F)
40-70
40-70
35-65
40-70
40-70
40-70
40-70
Max. Static Pressure w.c.
0.5
0.5
0.5
0.5
0.5
0.5
Max. Outlet Air Temp. (°F)
180
180
180
180
180
180
Gas piping connection (in.)
1/2
1/2
1/2
1/2
1/2
1/2
Dimensions (inches)
Length
51-1/4
51-1/4
51
51
51
51
Width
35-3/4
35-3/4
35-3/4
35-3/4
45-3/4
45-3/4
Height
47
47
47
49
49
51
Operating WT. (lbs.)
341 351 386 390 394 401 405 441 443 460 468 473 477 481 488
Compressors
Type
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
Outdoor Coil Data
Face area (Sq. Ft.)
15.1
15.1
15.1
16.9
19.5
21.5
Rows
1
2
2
2
2
2
Fins per inch
22
22
22
22
22
22
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Indoor Coil Data
Face area (Sq. Ft.)
4.6
4.6
4.6
4.6
6.3
6,3
Rows
2
3
3
3
3
3
Fins per inch
16
16
16
16
16
16
Tube diameter
3/8
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Interlaced
Refrigerant control
TXV
TXV
TXV
TXV
TXV
TXV
Outdoor Fan Data
Fan diameter (Inch)
24
24
24
24
26
26
Type
Prop
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Direct
No. speeds
1
1
1
1
1
1
Motor HP each
1/4
1/4
1/4
1/4
1/3
1/3
RPM
850
850
850
850
850
850
2400
Nominal total CFM
2400
2400
2400
3200
3200
Direct Drive Indoor Fan Data
Fan Size (Inch)
11 x 8
11 x 8
11 x 10
11 x 10
11 x 10
11 x 10
Type
Centrifugal Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor HP each
1/3
1/2
1/3
1/2
1/2
3/4
3/4
3/4
1
RPM
1200 Max
1200 Max
1200 Max
1200 Max
1200 Max
1200 Max
Frame size
48
48
48
48
48
48
Filters
Filter Size
A
A
A
A
B
B
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filQuantity - Size
ters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.
6
PCG4A24
2.0
Johnson Controls Unitary Products
5564033-YTG-A-0918
COOLING PERFORMANCE DATA - 2 TON
PACKAGED UNIT MODEL NO. PCG4A24
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
23.2 24.3
55 / 45
S.C.
22.6 19.3
K.W.
1.15 1.14
T.C.
22.2 23.7
65 / 55
S.C.
21.7 19.1
K.W.
1.28 1.28
T.C.
21.3 23.0
75 / 63
S.C.
20.8 18.9
K.W.
1.41 1.42
T.C.
20.2 21.8
85 / 69
S.C.
19.9 18.2
K.W.
1.59 1.60
T.C.
19.0 20.7
95 / 75
S.C.
18.9 17.6
K.W.
1.78 1.78
T.C.
17.3 18.7
105 / 83
S.C.
16.9 16.5
K.W.
2.05 2.05
T.C.
15.6 16.7
115 / 89
S.C.
15.0 15.5
K.W.
2.31 2.32
T.C.
14.0 14.8
125 / 95
S.C.
13.1 14.4
K.W.
2.58 2.59
600
75
62
23.9
16.4
1.15
23.2
16.2
1.28
22.4
16.0
1.42
21.6
15.8
1.49
20.8
15.5
1.56
19.1
14.1
1.91
17.4
12.8
2.24
15.7
11.4
2.57
80
67
25.1
15.8
1.15
24.7
15.7
1.29
24.4
15.7
1.43
23.2
15.1
1.61
22.1
14.5
1.79
20.1
13.7
2.05
18.2
12.8
2.30
16.2
12.0
2.55
80
72
25.6
12.5
1.15
25.6
12.3
1.29
25.5
12.1
1.42
24.5
11.6
1.61
23.5
11.2
1.79
22.1
10.4
2.05
20.7
9.7
2.31
19.3
8.9
2.56
80
57
24.2
23.8
1.17
23.4
22.9
1.30
22.5
22.0
1.43
21.4
21.0
1.62
20.4
20.0
1.80
18.6
18.2
2.07
16.9
16.4
2.33
15.1
14.7
2.59
80
62
25.5
21.1
1.16
24.8
21.2
1.30
24.2
21.3
1.44
23.1
20.8
1.62
21.9
20.3
1.80
19.9
18.6
2.07
18.0
17.0
2.33
16.0
15.4
2.59
800
75
62
24.5
18.0
1.30
24.3
18.2
1.28
24.1
18.4
1.26
23.2
18.1
1.39
22.2
17.9
1.51
20.4
16.4
1.88
18.6
15.1
2.24
16.8
13.7
2.59
80
67
26.1
17.1
1.17
25.8
17.2
1.31
25.6
17.3
1.45
24.8
17.0
1.63
24.0
16.7
1.81
21.8
15.8
2.07
19.6
15.0
2.32
17.5
14.2
2.58
80
72
27.1
13.4
1.18
27.1
13.4
1.31
27.2
13.4
1.45
26.0
12.8
1.63
24.8
12.3
1.82
23.5
11.6
2.08
22.3
10.9
2.34
21.0
10.2
2.59
80
57
25.3
25.0
1.19
24.5
24.1
1.33
23.7
23.1
1.46
22.7
22.1
1.64
21.7
21.2
1.82
19.9
19.5
2.09
18.1
17.9
2.35
16.3
16.2
2.60
80
62
26.7
22.9
1.19
26.0
23.3
1.33
25.4
23.7
1.47
24.3
23.4
1.64
23.1
23.1
1.82
21.1
20.8
2.09
19.2
18.6
2.34
17.2
16.3
2.60
1000
75
62
25.1
19.6
1.46
25.5
20.1
1.28
25.9
20.7
1.11
24.8
20.5
1.29
23.7
20.3
1.47
21.7
18.8
1.85
19.8
17.3
2.23
18.0
15.9
2.61
80
67
27.1
18.4
1.19
26.9
18.6
1.33
26.8
18.9
1.47
26.4
18.9
1.65
25.9
18.8
1.83
23.5
17.9
2.09
21.1
17.1
2.35
18.7
16.3
2.60
80
72
28.5
14.4
1.20
28.7
14.5
1.34
28.9
14.7
1.47
27.5
14.1
1.66
26.2
13.4
1.84
25.0
12.8
2.11
23.8
12.1
2.36
22.7
11.5
2.62
80
67
37.3
23.0
1.38
35.8
22.3
1.53
34.4
21.6
1.68
31.7
20.1
1.89
29.0
18.6
2.10
26.4
17.6
2.39
23.9
16.6
2.67
21.4
15.7
2.95
80
72
40.5
18.7
1.39
39.1
18.1
1.55
37.6
17.5
1.71
35.5
16.5
1.92
33.4
15.5
2.12
30.5
14.4
2.41
27.6
13.2
2.68
24.8
12.0
2.96
80
57
34.6
33.8
1.43
33.0
32.2
1.59
31.4
30.6
1.76
29.5
28.8
1.97
27.6
27.0
2.18
25.5
25.1
2.46
23.5
23.2
2.74
21.4
21.3
3.02
80
62
36.1
30.2
1.43
34.3
29.7
1.59
32.6
29.2
1.75
30.6
27.9
1.96
28.6
26.7
2.17
25.8
24.4
2.46
23.1
22.1
2.74
20.4
19.9
3.02
1000
75
62
36.5
25.8
1.44
34.5
25.1
1.58
32.6
24.4
1.72
29.8
20.6
1.93
27.1
16.8
2.14
24.3
16.9
2.44
21.6
16.9
2.73
19.0
17.0
3.02
80
67
38.9
25.1
1.45
37.6
25.0
1.60
36.3
24.8
1.76
33.4
23.2
1.96
30.5
21.5
2.17
27.6
20.4
2.46
24.8
19.4
2.74
22.0
18.3
3.02
80
72
41.8
19.8
1.46
40.3
19.3
1.62
38.9
18.9
1.77
36.7
17.9
1.98
34.5
16.9
2.19
31.3
15.7
2.48
28.3
14.5
2.75
25.2
13.3
3.03
80
57
37.3
36.9
1.50
35.4
34.8
1.67
33.5
32.7
1.83
31.5
30.9
2.04
29.5
29.1
2.25
27.1
26.8
2.53
24.8
24.6
2.81
22.5
22.3
3.09
80
62
37.8
33.4
1.50
35.8
32.9
1.66
33.8
32.5
1.82
32.0
31.1
2.03
30.1
29.6
2.24
27.1
26.5
2.53
24.2
23.4
2.80
21.3
20.3
3.08
1200
75
62
38.2
28.2
1.51
36.2
27.6
1.67
34.3
27.0
1.83
31.0
22.6
2.04
27.7
18.1
2.24
24.7
18.2
2.53
21.8
18.2
2.81
18.9
18.3
3.08
80
67
40.5
27.2
1.52
39.3
27.6
1.67
38.1
28.1
1.83
35.1
26.2
2.03
32.0
24.4
2.24
28.8
23.2
2.52
25.7
22.1
2.80
22.5
21.0
3.08
80
72
43.0
21.0
1.52
41.6
20.6
1.68
40.1
20.3
1.84
37.9
19.3
2.05
35.6
18.3
2.26
32.2
17.0
2.55
28.9
15.8
2.82
25.6
14.6
3.10
COOLING PERFORMANCE DATA - 2.5 TON
PACKAGED UNIT MODEL NO. PCG4A30
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
31.9 34.4
55 / 45
S.C.
30.6 27.0
K.W.
1.36 1.37
T.C.
30.6 32.9
65 / 55
S.C.
29.6 26.4
K.W.
1.52 1.52
T.C.
29.3 31.4
75 / 63
S.C.
28.5 25.9
K.W.
1.68 1.68
T.C.
27.5 29.2
85 / 69
S.C.
26.7 24.8
K.W.
1.90 1.89
T.C.
25.6 27.0
95 / 75
S.C.
25.0 23.8
K.W.
2.11 2.10
T.C.
23.9 24.5
105 / 83
S.C.
23.4 22.3
K.W.
2.40 2.39
T.C.
22.1 22.0
115 / 89
S.C.
21.8 20.8
K.W.
2.67 2.67
T.C.
20.4 19.4
125 / 95
S.C.
20.3 19.4
K.W.
2.95 2.95
Johnson Controls Unitary Products
800
75
62
34.7
23.5
1.37
32.8
22.7
1.49
30.9
21.9
1.61
28.7
18.7
1.82
26.4
15.5
2.04
23.9
15.6
2.35
21.5
15.6
2.65
19.1
15.7
2.95
7
5564033-YTG-A-0918
COOLING PERFORMANCE DATA - 3 TON
PACKAGED UNIT MODEL NO. PCG4A36
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
36.0 38.3
55 / 45
S.C.
34.5 30.6
K.W.
1.82 1.83
T.C.
34.6 36.4
65 / 55
S.C.
33.2 29.8
K.W.
2.01 2.02
T.C.
33.2 34.6
75 / 63
S.C.
32.0 28.9
K.W.
2.20 2.20
T.C.
31.7 32.6
85 / 69
S.C.
30.4 26.9
K.W.
2.46 2.44
T.C.
30.1 30.6
95 / 75
S.C.
28.8 25.0
K.W.
2.72 2.67
T.C.
29.0 28.3
105 / 83
S.C.
27.5 23.9
K.W.
2.91 2.92
T.C.
27.9 26.0
115 / 89
S.C.
26.3 22.9
K.W.
3.11 3.16
T.C.
26.8 23.8
125 / 95
S.C.
25.1 21.9
K.W.
3.30 3.39
1000
75
62
40.3
27.6
1.83
37.4
26.0
2.02
34.5
24.5
2.21
32.2
23.3
2.47
29.8
22.2
2.73
27.8
20.9
2.95
25.9
19.6
3.17
24.0
18.3
3.39
80
67
44.9
27.9
1.83
42.6
26.8
2.03
40.3
25.7
2.22
37.8
24.6
2.48
35.3
23.4
2.74
32.8
21.8
2.96
30.4
20.3
3.19
28.0
18.7
3.41
80
72
48.1
22.6
1.85
46.1
21.6
2.04
44.0
20.7
2.23
41.2
19.3
2.49
38.4
17.9
2.74
36.1
16.9
2.97
33.9
15.9
3.20
31.7
14.9
3.42
80
57
38.9
37.1
1.89
37.3
35.6
2.09
35.7
34.1
2.28
34.0
32.4
2.53
32.3
30.8
2.79
31.1
29.4
2.95
30.0
28.1
3.10
28.9
26.8
3.25
80
62
40.4
33.8
1.90
38.3
32.9
2.09
36.3
32.0
2.28
34.0
30.3
2.53
31.7
28.6
2.77
29.6
27.1
3.01
27.4
25.8
3.24
25.3
24.4
3.47
1200
75
62
42.1
29.9
1.90
39.4
28.5
2.09
36.6
27.2
2.28
33.8
25.8
2.54
31.0
24.3
2.80
28.9
22.9
3.02
26.8
21.6
3.24
24.8
20.2
3.46
80
67
46.8
30.2
1.91
44.2
28.9
2.10
41.7
27.7
2.30
38.9
26.5
2.55
36.2
25.3
2.81
33.8
23.8
3.04
31.4
22.3
3.26
29.0
20.9
3.48
80
72
49.8
23.9
1.92
47.9
23.4
2.11
46.1
22.9
2.30
42.8
21.1
2.56
39.6
19.3
2.82
37.1
18.2
3.05
34.7
17.2
3.27
32.3
16.2
3.49
80
57
41.8
39.6
1.97
40.0
37.9
2.16
38.1
36.1
2.36
36.3
34.5
2.61
34.5
32.8
2.87
33.3
31.3
2.98
32.1
29.9
3.10
31.0
28.5
3.21
80
62
42.5
37.1
1.97
40.2
36.1
2.16
37.9
35.2
2.36
35.4
33.7
2.61
32.8
32.2
2.87
30.8
30.4
3.10
28.9
28.6
3.32
26.9
26.9
3.55
1400
75
62
43.9
32.2
1.98
41.3
31.0
2.17
38.7
29.9
2.36
35.4
28.2
2.61
32.1
26.5
2.87
29.9
25.0
3.10
27.8
23.5
3.32
25.6
22.1
3.54
80
67
48.8
32.5
1.99
45.9
31.1
2.18
43.1
29.7
2.37
40.1
28.4
2.63
37.1
27.2
2.88
34.7
25.8
3.11
32.3
24.4
3.33
30.0
23.1
3.55
80
72
51.5
25.1
1.99
49.8
25.1
2.19
48.2
25.0
2.38
44.5
22.8
2.63
40.8
20.7
2.89
38.1
19.6
3.12
35.5
18.5
3.35
33.0
17.4
3.57
80
67
51.8
34.4
2.38
48.9
32.8
2.62
46.0
31.3
2.87
42.7
28.5
3.18
39.3
25.8
3.48
34.9
24.5
3.90
30.7
23.1
4.30
26.5
21.8
4.70
80
72
57.3
28.7
2.38
54.1
27.5
2.61
51.0
26.2
2.84
47.6
24.5
3.15
44.1
22.8
3.47
39.4
20.9
3.90
34.7
19.0
4.31
30.1
17.2
4.73
80
57
46.5
45.5
2.42
44.4
43.7
2.55
42.2
41.9
2.67
39.3
39.2
2.98
36.5
36.5
3.29
32.5
32.5
3.72
28.7
28.7
4.14
24.9
24.9
4.57
80
62
48.6
42.1
2.44
45.6
40.5
2.68
42.6
38.8
2.93
40.0
36.1
3.24
37.4
33.3
3.54
33.0
30.3
3.97
28.8
27.4
4.38
24.5
24.5
4.79
1400
75
62
48.5
36.2
2.43
45.6
34.4
2.66
42.6
32.7
2.89
39.3
31.0
3.20
35.9
29.4
3.51
31.5
26.9
3.94
27.2
24.4
4.35
22.9
22.0
4.76
80
67
53.7
37.0
2.45
50.5
35.3
2.70
47.4
33.6
2.94
43.8
31.2
3.24
40.2
28.9
3.54
35.5
27.0
3.97
30.9
25.2
4.37
26.4
23.3
4.78
80
72
59.6
30.7
2.47
56.1
29.2
2.71
52.5
27.6
2.94
48.8
25.9
3.26
45.1
24.1
3.57
40.0
22.1
3.99
35.0
20.1
4.41
30.1
18.1
4.82
80
57
49.4
47.8
2.50
46.6
45.5
2.73
43.8
43.3
2.97
40.7
40.4
3.28
37.6
37.6
3.59
33.3
33.3
4.01
29.2
29.2
4.43
25.1
25.1
4.84
80
62
50.2
45.0
2.52
47.0
43.2
2.76
43.9
41.4
3.00
41.8
37.7
3.30
39.7
33.9
3.60
34.8
31.0
4.03
30.1
28.2
4.45
25.4
25.4
4.86
1600
75
62
50.2
38.5
2.51
47.0
36.4
2.74
43.7
34.3
2.97
40.1
32.8
3.28
36.5
31.3
3.59
31.8
28.4
4.01
27.3
25.6
4.42
22.8
22.8
4.83
80
67
55.5
39.6
2.53
52.1
37.7
2.77
48.7
35.9
3.01
44.9
33.9
3.31
41.1
32.0
3.60
36.1
29.5
4.03
31.1
27.2
4.45
26.2
24.8
4.87
80
72
61.9
32.6
2.56
58.0
30.8
2.80
54.1
29.0
3.04
50.0
27.3
3.36
46.0
25.5
3.67
40.6
23.3
4.09
35.3
21.2
4.50
30.1
19.1
4.91
COOLING PERFORMANCE DATA - 3.5 TON
PACKAGED UNIT MODEL NO. PCG4A42
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
43.7 46.9
55 / 45
S.C.
43.1 39.2
K.W.
2.35 2.36
T.C.
42.2 44.1
65 / 55
S.C.
41.9 37.7
K.W.
2.36 2.61
T.C.
40.6 41.3
75 / 63
S.C.
40.6 36.3
K.W.
2.38 2.86
T.C.
38.0 38.2
85 / 69
S.C.
38.0 34.5
K.W.
2.69 3.17
T.C.
35.4 35.1
95 / 75
S.C.
35.4 32.7
K.W.
3.00 3.48
T.C.
31.7 31.2
105 / 83
S.C.
31.7 29.6
K.W.
3.44 3.90
T.C.
28.2 27.4
115 / 89
S.C.
28.2 26.7
K.W.
3.86 4.31
T.C.
24.7 23.7
125 / 95
S.C.
24.7 23.7
K.W.
4.29 4.71
8
1200
75
62
46.8
33.9
2.36
44.1
32.5
2.59
41.4
31.0
2.82
38.4
29.3
3.13
35.4
27.6
3.44
31.2
25.4
3.86
27.1
23.3
4.28
23.0
21.2
4.69
Johnson Controls Unitary Products
5564033-YTG-A-0918
COOLING PERFORMANCE DATA - 4 TON
PACKAGED UNIT MODEL NO. PCG4B48
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
50.7 55.0
55 / 45
S.C.
48.2 44.8
K.W.
2.48 2.52
T.C.
48.0 52.0
65 / 55
S.C.
44.3 43.2
K.W.
2.76 2.79
T.C.
45.4 49.0
75 / 63
S.C.
40.3 41.7
K.W.
3.04 3.06
T.C.
42.9 45.4
85 / 69
S.C.
38.3 39.8
K.W.
3.41 3.42
T.C.
40.4 41.8
95 / 75
S.C.
36.4 38.0
K.W.
3.79 3.79
T.C.
36.7 37.6
105 / 83
S.C.
32.3 34.7
K.W.
4.30 4.30
T.C.
33.1 33.6
115 / 89
S.C.
28.4 31.6
K.W.
4.80 4.80
T.C.
29.5 29.5
125 / 95
S.C.
24.5 28.4
K.W.
5.30 5.29
1400
75
62
54.4
38.3
2.51
51.2
36.7
2.79
48.1
35.0
3.06
44.9
33.2
3.42
41.7
31.4
3.78
37.5
29.7
4.29
33.3
28.0
4.79
29.2
26.4
5.30
80
67
59.4
38.5
2.54
57.1
37.1
2.81
54.9
35.7
3.08
51.3
33.7
3.44
47.7
31.8
3.80
43.5
30.0
4.32
39.4
28.4
4.83
35.3
26.7
5.33
80
72
65.3
30.4
2.56
62.8
29.6
2.83
60.3
28.7
3.11
56.4
27.3
3.46
52.4
25.9
3.82
47.8
23.9
4.34
43.4
21.9
4.85
39.0
19.9
5.35
80
57
53.0
49.3
2.56
50.3
46.3
2.83
47.5
43.4
3.10
44.8
41.4
3.47
42.1
39.4
3.85
38.1
34.3
4.36
34.1
29.4
4.87
30.2
24.5
5.37
80
62
56.8
48.2
2.59
53.6
46.6
2.85
50.4
45.1
3.12
46.6
42.4
3.49
42.7
39.7
3.85
38.4
36.1
4.36
34.3
32.5
4.86
30.1
29.0
5.36
1600
75
62
56.1
41.0
2.58
52.9
39.3
2.85
49.6
37.6
3.12
46.1
35.7
3.48
42.6
33.8
3.83
38.0
31.1
4.35
33.6
28.6
4.86
29.2
26.0
5.36
80
67
61.2
40.7
2.61
58.7
39.4
2.88
56.2
38.1
3.14
52.5
36.3
3.50
48.7
34.5
3.86
44.3
32.6
4.38
40.0
30.7
4.89
35.7
28.8
5.39
80
72
67.2
31.9
2.62
64.4
30.8
2.89
61.6
29.7
3.17
57.7
28.4
3.53
53.8
27.0
3.89
48.9
24.9
4.41
44.2
22.9
4.91
39.5
20.9
5.41
80
57
55.4
50.3
2.64
52.5
48.4
2.90
49.6
46.4
3.16
46.7
44.4
3.53
43.9
42.4
3.90
39.5
36.4
4.43
35.2
30.5
4.93
30.9
24.6
5.44
80
62
58.6
51.5
2.65
55.2
50.0
2.92
51.8
48.4
3.18
47.7
44.9
3.55
43.6
41.4
3.91
39.2
37.4
4.42
35.0
33.5
4.92
30.7
29.6
5.42
1800
75
62
57.9
43.6
2.64
54.5
41.9
2.91
51.1
40.2
3.18
47.2
38.2
3.54
43.4
36.2
3.89
38.6
32.6
4.41
33.8
29.1
4.92
29.1
25.6
5.42
80
67
63.1
42.9
2.67
60.3
41.7
2.94
57.5
40.5
3.21
53.6
38.9
3.57
49.7
37.3
3.92
45.1
35.1
4.44
40.6
33.0
4.95
36.1
31.0
5.45
80
72
69.1
33.4
2.68
66.0
32.1
2.95
62.9
30.8
3.23
59.1
29.4
3.59
55.2
28.1
3.95
50.0
26.0
4.47
45.0
23.9
4.97
40.0
21.9
5.47
80
67
73.0
43.7
3.00
69.7
43.2
3.31
66.4
42.7
3.63
61.8
40.5
4.04
57.1
38.2
4.44
51.1
36.0
5.01
45.3
33.8
5.57
39.5
31.6
6.12
80
72
79.5
36.0
3.03
75.7
34.9
3.35
72.0
33.7
3.67
67.1
31.6
4.07
62.3
29.4
4.48
55.2
26.7
5.05
48.3
24.0
5.60
41.4
21.3
6.15
80
57
70.4
66.7
3.15
66.2
62.8
3.46
62.1
59.0
3.78
58.7
56.2
4.19
55.3
53.5
4.61
52.5
50.0
5.22
49.8
46.6
5.80
47.1
43.1
6.39
80
62
70.4
57.0
3.17
66.4
55.9
3.48
62.5
54.7
3.79
57.8
52.2
4.21
53.0
49.7
4.62
47.6
44.0
5.19
42.3
38.4
5.75
36.9
32.9
6.30
1800
75
62
69.3
48.8
3.18
65.1
46.7
3.49
60.9
44.7
3.80
56.6
43.1
4.21
52.3
41.5
4.62
45.6
37.3
5.19
39.0
33.3
5.74
32.5
29.2
6.30
80
67
74.8
46.3
3.21
71.0
45.4
3.52
67.1
44.5
3.84
62.3
42.5
4.24
57.5
40.4
4.65
51.0
37.8
5.22
44.7
35.3
5.77
38.3
32.8
6.32
80
72
80.8
37.1
3.24
76.5
35.7
3.56
72.2
34.3
3.88
67.4
32.8
4.28
62.6
31.2
4.68
55.2
28.1
5.25
47.9
25.0
5.80
40.7
21.9
6.35
80
57
72.7
70.1
3.36
68.4
65.3
3.68
64.0
60.6
3.99
60.0
57.5
4.41
56.1
54.4
4.82
52.8
50.4
5.40
49.7
46.6
5.96
46.6
42.7
6.52
80
62
71.7
59.2
3.38
67.5
58.3
3.69
63.2
57.5
4.00
58.4
55.0
4.42
53.7
52.5
4.83
47.9
45.8
5.40
42.3
39.4
5.95
36.8
32.9
6.51
2000
75
62
70.5
51.4
3.38
65.9
48.9
3.69
61.4
46.3
4.01
57.0
45.1
4.42
52.5
43.8
4.83
45.2
38.3
5.40
38.1
33.1
5.95
31.0
27.8
6.50
80
67
76.6
48.8
3.42
72.3
47.6
3.73
67.9
46.3
4.04
62.9
44.5
4.45
57.9
42.6
4.86
50.9
39.7
5.42
44.0
36.9
5.97
37.2
34.1
6.52
80
72
82.2
38.2
3.45
77.4
36.5
3.77
72.5
34.9
4.08
67.7
33.9
4.48
62.9
33.0
4.88
55.1
29.5
5.45
47.5
26.0
6.00
39.9
22.6
6.55
COOLING PERFORMANCE DATA - 5 TON
PACKAGED UNIT MODEL NO. PCG4B60
ID CFM
CONDENSER
ENTERING AIR
IDDB
80
80
TEMPERATURE
IDWB
57
62
T.C.
68.0 69.1
S.C.
63.3 54.8
55 / 45
K.W.
2.93 2.97
T.C.
64.1 65.4
S.C.
60.3 53.4
65 / 55
K.W.
3.25 3.27
T.C.
60.2 61.8
S.C.
57.4 52.0
75 / 63
K.W.
3.56 3.58
T.C.
57.4 57.1
S.C.
55.0 49.4
85 / 69
K.W.
3.98 4.00
T.C.
54.5 52.4
S.C.
52.6 46.9
95 / 75
K.W.
4.40 4.42
T.C.
52.1 47.2
S.C.
49.5 42.1
105 / 83
K.W.
5.03 4.99
T.C.
49.8 42.2
S.C.
46.6 37.5
115 / 89
K.W.
5.65 5.54
T.C.
47.5 37.1
S.C.
43.6 32.8
125 / 95
K.W.
6.27 6.09
Johnson Controls Unitary Products
1600
75
62
68.1
46.2
2.97
64.3
44.6
3.28
60.5
43.1
3.59
56.2
41.1
4.01
52.0
39.2
4.42
45.9
36.3
4.99
40.0
33.4
5.54
34.1
30.6
6.09
9
5564033-YTG-A-0918
81,77233$1(/
&251(53267
,1'225&2,/
&2,/*8$5'
+,*+92/7$*(
23(1,1*´
&
+,*+92/7$*(
23(1,1*´
&20%867,21$,5,17$.(
+($7(;&+$1*(5$&&(663$1(/
&2035(6625
$&&(663$1(/
)/8((;+$867+22'
&21'(16$7(
'5$,1
%/2:(5
$&&(66
3$1(/
$
&21752/+($7
$&&(663$1(/
%
/2:92/7$*(23(1,1*´
*$66833/<+2/(´:,7+
*5200(723(1,1*2)´
$
UNIT DIMENSIONS
Model
A24
A30
A36
A42
B48
B60
A
51-1/4
51-1/4
51-1/4
51-1/4
51-1/4
51-1/4
Dimensions - in inches
B
35-3/4
35-3/4
35-3/4
35-3/4
45-3/4
45-3/4
C
47
47
47
49
49
51
Distance (in.)
36
36
0
Direction
Power Entry (Right Side)
Left Side
Bottom4
Distance (in.)
36
24
1
UNIT CLEARANCES1 2
Direction
Top3
Side Opposite Ducts
Duct Panel
1.
2.
3.
4.
10
A 1" clearance must be provided between any combustible material and the supply air duct work.
The products of combustion must not be allowed to accumulate within a confined space and recirculate.
Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.
Units may be installed on combustible floors made from class A, B or C roof covering materials.
Johnson Controls Unitary Products
5564033-YTG-A-0918
INDOOR BLOWER SPECIFICATIONS
Motor
Model
HP
1/3
1/2
1/3
1/2
1/2
1/2
3/4
3/4
3/4
3/4
3/4
3/4
1
1
1
24050
24075
30050
30075
36050
36075
36100
42075
42100
48065
48100
48125
60065
60100
60125
RPM
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
Variable
EFF.
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
SF
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Frame
48
48
48
48
48
48
48
48
48
48
48
48
48
48
48
SOUND PERFORMANCE
Model
(Tons)
Sound Rating1
dB (A)
A24
A30
A36
A42
B48
B60
75
75
74
74
74
76
125
62.4
60.5
58.5
63.5
63.5
72.3
250
61.5
61.6
61.8
63.9
63.9
65.0
Octave Band Centerline Frequency (Hz)
500
1000
2000
64.2
67.0
61.0
64.8
66.9
60.9
65.4
66.5
60.7
62.3
65.0
64.0
62.3
65.0
64.0
63.9
64.0
60.0
4000
57.3
56.0
54.8
54.1
54.1
55.5
8000
49.6
49.7
49.8
46.6
46.6
49.0
1. Rated in accordance with AHRI Standard 270.
ELECTRICAL DATA
Model
24050
24075
30050
30075
36050, 36075
36100
42075, 42100
48065, 48100, 48125
60065, 60100, 60125
Compressor
Voltage
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
OD Fan
Motor
Supply
Blower Motor
RLA
LRA
MCC
FLA
FLA
12.8
12.8
14.1
14.1
16.7
16.7
17.9
21.8
24.4
58.3
58.3
73.0
73.0
79.0
79.0
112.0
117.0
144.2
20.0
20.0
22.0
22.0
26.0
26.0
28.0
34.0
38.0
0.7
0.7
0.8
0.8
1.3
1.3
1.3
1.7
1.7
2.6
3.8
2.6
3.8
3.8
5.4
5.4
5.4
7.0
MCA1
(Amps)
19.3
20.5
21.0
22.2
26.0
27.6
29.1
34.4
39.2
Max Fuse2/
Breaker3 Size
(Amps)
30
30
35
35
40
40
45
50
60
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Johnson Controls Unitary Products
11
5564033-YTG-A-0918
"D"
CENTER OF
GRAVITY
COMPRESSOR
"C"
"A"
FRONT
OF UNIT
Y
"B"
X
A0295-001-TG
WEIGHTS & DIMENSIONS
Model
24050
24075
30050
30075
36050
36075
36100
42075
42100
48065
48100
48125
60065
60100
60125
12
Weight (lbs.)
Shipping
346
356
391
395
399
406
410
446
448
465
473
478
482
486
493
Operating
341
351
386
390
394
401
405
441
443
460
468
473
477
481
488
Center of Gravity
X
28
28
28
28
28
28
28
28
28
28
28
28
29
28
27
Y
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
4 Point Load Location (lbs.)
A
120
124
139
146
141
135
139
145
148
189
169
164
174
177
151
B
95
96
99
93
107
115
113
112
110
116
139
145
142
140
167
C
81
81
90
82
94
103
99
99
96
93
115
124
124
117
141
D
71
76
84
95
78
74
80
85
89
117
100
95
92
102
84
Johnson Controls Unitary Products
5564033-YTG-A-0918
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION
Model
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
567
517
470
415
674
628
579
530
676
631
583
533
865
823
778
739
1035
996
960
925
750
705
664
613
850
803
759
713
1039
993
949
906
1224
1185
1146
1107
1331
1318
1281
1241
554
512
461
411
779
735
692
650
868
826
787
747
958
918
874
837
1018
978
941
903
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
732
818
823
994
1148
887
978
1171
1349
1487
700
906
992
1075
1136
0.2
SCFM
667
771
774
948
1108
847
941
1114
1297
1462
657
868
951
1032
1089
0.3
SCFM
624
723
721
906
1071
802
898
1074
1265
1392
599
825
911
1000
1053
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
1076
1102
1191
1201
1370
1003
1180
1259
1314
1506
1225
1259
1314
1348
1506
1342
1425
1554
1658
1966
1315
1436
1020
1048
1140
1225
1329
952
1133
1209
1271
1471
1174
1209
1271
1306
1471
1302
1368
1503
1599
1914
1266
1382
984
1010
1112
1187
1283
904
1085
1166
1229
1403
1131
1166
1229
1259
1403
1260
1332
1465
1588
1862
1229
1342
943
974
1076
1151
1271
851
1042
1126
1186
1389
1090
1126
1186
1222
1389
1217
1293
1423
1530
1810
1194
1304
903
934
1038
1118
1209
790
995
1084
1144
1345
1046
1084
1144
1179
1345
1178
1251
1386
1495
1757
1156
1262
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
42100
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
48065
Medium (3)
Medium/High (4)
High (5)
Continued on next page.
1458
1573
1966
1436
1544
1573
1681
1935
1046
1295
1620
1798
2146
1406
1523
1914
1382
1492
1523
1640
1887
1009
1250
1564
1722
2085
1365
1484
1862
1342
1455
1484
1599
1834
980
1213
1517
1669
2025
1327
1445
1810
1304
1416
1445
1557
1788
946
1172
1466
1620
1960
1286
1408
1757
1262
1376
1408
1517
1743
915
1133
1418
1572
1872
24050
24075
30050
30075
36050
36075
36100
Motor Speed
42075
Johnson Controls Unitary Products
0.8
SCFM
369
482
505
700
901
563
667
864
1063
1201
365
608
712
800
1.0
SCFM
277
386
448
622
853
463
575
780
975
1121
273
524
642
726
859
890
1000
1080
1176
730
942
1032
1097
1305
993
1032
1097
1133
1305
1134
1208
1346
1454
1705
1117
819
850
958
1041
1143
674
889
980
1049
1262
941
980
1049
1086
1262
1082
1163
1302
1414
1653
1080
869
779
810
919
1002
1109
633
834
928
998
1216
888
928
998
1036
1216
1034
1113
1257
1373
1600
1036
801
699
730
841
924
1041
551
724
824
896
1124
782
824
896
936
1124
938
1013
1167
1291
1496
948
1220
1244
1367
1705
1220
1336
1367
1478
1701
878
1087
1360
1527
1862
1179
1203
1327
1653
1179
1294
1327
1436
1651
844
1045
1308
1480
1798
1131
1155
1279
1600
1131
1248
1279
1393
1591
779
964
1206
1413
1735
1035
1059
1183
1496
1035
1156
1183
1307
1471
649
802
1002
1280
1609
13
5564033-YTG-A-0918
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION (Continued)
Model
48100
48125
60065
60100
60125
1.
2.
3.
4.
5.
14
Motor Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
0.1
SCFM
1620
1694
1798
1835
2146
1620
1798
1922
2001
2146
1073
1329
2054
2195
2445
1730
0.2
SCFM
1564
1630
1722
1758
2085
1564
1722
1863
1952
2085
1043
1292
1998
2144
2388
1682
0.3
SCFM
1517
1580
1669
1703
2025
1517
1669
1804
1890
2025
1009
1250
1934
2098
2306
1628
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
1858
2054
2195
2445
2063
2130
2195
2275
2445
1807
1998
2144
2388
2008
2084
2144
2252
2388
1749
1934
2098
2306
1943
2032
2098
2169
2306
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1466
1418
1360
1308
1530
1482
1430
1380
1620
1572
1527
1480
1653
1604
1558
1511
1960
1872
1862
1798
1466
1418
1360
1308
1620
1572
1527
1480
1754
1724
1658
1612
1839
1820
1742
1696
1960
1872
1862
1798
988
963
941
917
1223
1192
1165
1136
1890
1843
1801
1757
2049
2003
1955
1883
2293
2235
2178
2129
1592
1552
1517
1479
1710
1890
2049
2293
1899
1983
2049
2154
2293
1667
1843
2003
2235
1851
1927
2003
2112
2235
1629
1801
1955
2178
1809
1951
1955
2065
2178
1589
1757
1883
2129
1763
1860
1883
1989
2129
0.8
SCFM
1206
1292
1413
1442
1735
1206
1413
1559
1651
1735
892
1105
1710
1868
2077
1.0
SCFM
1002
1116
1280
1304
1609
1002
1280
1453
1561
1609
842
1043
1616
1838
1973
1439
1546
1710
1868
2077
1717
1815
1868
1976
2077
1359
1460
1616
1838
1973
1625
1725
1838
1950
1973
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
5564033-YTG-A-0918
AIRFLOW PERFORMANCE - BOTTOM DUCT APPLICATION
Model
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
611
560
491
445
720
677
622
559
828
781
735
686
902
861
817
775
1085
1051
1013
975
782
734
685
630
879
834
787
735
1056
1016
975
935
1248
1211
1174
1127
1367
1369
1299
1264
575
520
467
410
795
745
706
658
900
855
811
770
995
949
908
864
1061
1020
978
938
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
754
867
951
1024
1204
899
1033
1186
1357
1480
726
928
1021
1109
1170
0.2
SCFM
710
815
908
982
1159
869
960
1133
1322
1439
676
886
983
1071
1134
0.3
SCFM
665
773
868
942
1121
827
924
1095
1284
1404
622
841
942
1029
1096
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
1076
1104
1205
1285
1406
1008
1190
1262
1324
1517
1231
1270
1317
1358
1517
1340
1409
1527
1663
1930
1332
1457
1042
1063
1170
1251
1375
962
1148
1223
1282
1475
1186
1225
1286
1317
1475
1299
1368
1492
1585
1892
1295
1419
1009
1025
1136
1213
1341
916
1106
1181
1245
1447
1146
1189
1245
1275
1447
1264
1334
1470
1594
1853
1263
1376
969
987
1098
1179
1306
861
1055
1137
1202
1400
1103
1140
1198
1238
1400
1224
1291
1419
1601
1805
1222
1340
930
947
1060
1141
1271
807
1008
1091
1161
1357
1069
1098
1151
1197
1357
1182
1253
1385
1521
1760
1185
1299
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
42100
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
48065
Medium (3)
Medium/High (4)
High (5)
Continued on next page.
1451
1568
1978
1455
1566
1565
1675
1946
1032
1272
1611
1892
2131
1412
1524
1937
1414
1532
1530
1641
1909
999
1236
1574
1777
2058
1371
1491
1891
1379
1492
1491
1606
1863
970
1204
1518
1771
1998
1339
1464
1837
1335
1455
1458
1578
1815
938
1165
1494
1701
1949
1296
1425
1785
1294
1416
1419
1535
1771
910
1129
1439
1639
1892
24050
24075
30050
30075
36050
36075
36100
Motor Speed
42075
Johnson Controls Unitary Products
0.8
SCFM
391
505
631
721
938
575
685
891
1087
1226
376
607
729
826
1.0
SCFM
283
397
521
613
864
465
585
803
1007
1150
308
505
647
750
890
908
1025
1104
1236
757
955
1044
1112
1318
1030
1046
1110
1148
1318
1182
1201
1343
1480
1696
1148
849
869
985
1065
1198
700
914
994
1067
1275
977
1008
1064
1105
1275
1097
1173
1299
1440
1625
1110
899
808
830
943
1027
1163
650
863
952
1018
1232
912
960
1024
1057
1232
1049
1128
1250
1400
1553
1063
821
726
752
859
951
1093
550
761
868
920
1146
781
866
943
961
1146
953
1038
1152
1320
1409
967
1253
1257
1383
1725
1254
1372
1381
1495
1721
879
1081
1405
1617
1840
1215
1211
1345
1656
1212
1333
1336
1455
1654
843
1037
1357
1565
1788
1160
1165
1296
1604
1160
1280
1290
1412
1595
808
968
1266
1489
1728
1051
1072
1200
1502
1056
1174
1198
1326
1477
737
829
1083
1336
1608
15
5564033-YTG-A-0918
AIRFLOW PERFORMANCE - BOTTOM DUCT APPLICATION (Continued)
Model
48100
48125
60065
60100
60125
1.
2.
3.
4.
5.
16
Motor Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
0.1
SCFM
1598
1663
1789
1931
2131
1598
1766
1912
2105
2131
1026
1263
1987
2114
2369
1655
0.2
SCFM
1548
1612
1733
1814
2058
1548
1703
1875
2014
2058
999
1230
1933
2050
2308
1612
0.3
SCFM
1502
1568
1670
1808
1998
1502
1656
1805
2006
1998
989
1192
1861
2047
2249
1596
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
1766
1987
2114
2369
1973
2024
2123
2191
2369
1720
1933
2050
2308
1924
1983
2075
2154
2308
1667
1861
2047
2249
1905
1937
2019
2117
2249
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
1454
1410
1362
1307
1522
1476
1422
1370
1650
1596
1578
1535
1736
1673
1650
1597
1949
1892
1840
1788
1454
1410
1362
1307
1611
1566
1518
1469
1787
1750
1713
1672
1931
1898
1845
1793
1949
1892
1840
1788
950
907
907
886
1165
1167
1101
1099
1817
1820
1715
1725
1974
1899
1889
1920
2183
2126
2088
2034
1531
1461
1462
1429
1629
1817
1974
2183
1826
1889
1970
2075
2183
1632
1820
1899
2126
1743
1886
1978
2002
2126
1539
1715
1889
2088
1744
1843
1862
1995
2088
1537
1725
1920
2034
1703
1799
1849
2028
2034
0.8
SCFM
1251
1297
1483
1519
1728
1251
1419
1636
1739
1728
862
1071
1651
1866
1990
1.0
SCFM
1139
1152
1379
1362
1608
1139
1319
1564
1631
1608
816
1015
1504
1758
1902
1391
1498
1651
1866
1990
1660
1759
1804
1974
1990
1316
1421
1504
1758
1902
1574
1679
1714
1866
1902
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
5564033-YTG-A-0918
ADDITIONAL STATIC RESISTANCE
Size (Tons)
024 (2.0)
030 (2.5)
036 (3.0)
042 (3.5)
048 (4.0)
060 (5.0)
CFM
500
600
700
800
900
1000
1100
1200
700
800
900
1000
1100
1200
1300
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
Wet Indoor Coil Economizer1 Filter/Frame Kit
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.01
0.02
0.04
0.06
0.08
0.10
0.13
0.16
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
2. Filter pressure drop based on standard filter media tested at velocities not to
exceed 300 ft/min.
BOTTOM DUCT DIMENSIONS (Inches)
'
´
&
$
5(7851
$,5'8&7
+2/(´
(
ZLWK´JURPPHW
RSHQLQJIRUJDVSLSH
%
+2/(´
$
IRUKLJK
YROWDJH
6833/<
$,5'8&7
+2/(´ IRU
ORZYROWDJH
)
Model
24, 30, 36, 42
48, 60
A
10
14
B
21.5
13.5
$
C
5
5
D
4.5
3.5
E
47.5
47.5
F
32
42
REAR DUCT DIMENSIONS (Inches)
127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
HOHFWULFDODQGJDVOLQHV
5(7851
$,5'8&7
6833/<
$,5'8&7
$
Model
24, 30, 36, 42
48, 60
Johnson Controls Unitary Products
9,(:/22.,1*83
$7%277202)81,7
´
$
%
A
9.6
13.6
$
B
22
14
17
5564033-YTG-A-0918
UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A0324-001
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
TO GAS
SUPPLY LINE
18
CONTROL WIRING TO
INDOOR THERMOSTAT
A0325-001
Johnson Controls Unitary Products
5564033-YTG-A-0918
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF
CONDENSATE
DRAIN
MANUAL GAS
SHUTOFF VAVLE
ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO GAS
SUPPLY LINE
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT
Johnson Controls Unitary Products
SUPPLY
AIR DUCT
A0326-
19
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2018 by Johnson Controls, Inc. All rights reserved.
York International Corp.
5005 York Drive
Norman, OK 73069
5564033-YTG-A-0918
Supersedes: 5005562-YTG-H-1017
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement