York PHE4 User manual

York PHE4 User manual
5005568-YTG-H-1017
DESCRIPTION
These packaged cooling/heating heat pumps are designed for
outdoor installation. Only utility and duct connections are
required at the point of installation.
FEATURES
TECHNICAL GUIDE
SINGLE PACKAGE
HEAT PUMP / ELECTRIC HEAT
14 SEER – R-410A – 1 PHASE
2 THRU 5 NOMINAL TONS - 208/230V
MODELS: PHE4*24 THRU 60
• Operating Efficiency - All PHE4 heat pump models are
rated at 14.0 SEER, 11.0 EER and 8.0 HSPF for cooling and
heating operation.
• On Site Flexibility - All model sizes use a compact design
cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
• Lower Installation Cost - Installation time and costs are
reduced by easy power and control wiring connections. The
small base dimension means less space is required on the
ground or roof. All units are completely wired, charged with
R-410A refrigerant and tested prior to shipment. Test stations using a state-of-the-art computerized process system
are used to insure product quality. Refrigerant charge and
component part numbers are verified via computers during
assembly. Vital run test statistics such as system pressure,
motor currents, air velocity and temperature, unit vibration,
and gas system safeties are monitored and recorded by the
system to insure unit performance. Equal size side supply
and return duct connections allow easy connection of ducts
to match low crawl spaces without transition pieces.
• Utility Connections Made Easy - Electric utility access provided through the bottom or the side of the unit. Utility connections can be made quickly and with a minimum amount of
field labor. A field supplied and field installed electrical disconnect switch must be installed.
®
Due to continuous product improvement, specifications
are subject to change without notice.
Visit us on the web at
www.upgnet.com and www.york.com
Additional rating information can be found at:
www.ahridirectory.org
WARRANTY SUMMARY*
Extended 10-Years limited parts and compressor warranty
* Extended warranty requires online registration within 90 days of purchase for
replacement or closing for new home purchase. See limited warranty certificate
in User’s Information Manual for details.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Durable Finish - The cabinet is made of G90 galvanized
steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel provides a better paintto-steel bond, which resists corrosion and rust creep. Powder paint finish insure less fading when exposed to sunlight,
and provides superior corrosion resistance (1000 hour salt
spray tested).
Continued on next page.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
5005568-YTG-H-1017
• Full Perimeter Base Rails - The easily removable base rails
provide a solid foundation for the entire unit and protects the
unit during shipment. The rails provide fork lift access from
all sides, and rigging holes are also provided so that an overhead crane can be used to place the units on a roof. On
applications where the unit is placed on a pad, the base will
keep the unit off the pad to deter corrosion. On applications
where height is limited, the base rails may be removed by
removing 2 screws in each corner.
• Attractive Appearance - A single-piece top cover containing
a top-discharge outdoor fan arrangement requires less
square footage on installation and provides a wider variety of
installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance and provide cut protection to the installer
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design.
• Low Maintenance - Long life, permanently lubricated outdoor and indoor fan motor bearings need no annual maintenance, adding greater reliability to the unit. Slide-out blower
assembly and indoor coil assembly can be easily removed
for cleaning or service.
• Fan System - All models operate over a wide range of
design conditions with a standard ECM indoor fan motor.
These units easily match all types of applications and provide greater on-site flexibility to match comfort requirements.
The cooling speed and heating speeds are factory set at test
design conditions but can be field adjusted. This allows maximum comfort capabilities.
• Simple Control Circuit - A printed circuit board contains a
status/diagnostic indicator light. Field thermostat wiring connects to color coded leads using twist on wire connections.
Cooling controls use contactor and relays for simple application and troubleshooting. Mate-n-lock plug connectors are
used. The electrical control box is not located in the compressor compartment. The controls are mounted to allow the
separate access panel to be removed for trouble shooting
and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number
coded.
• Protected Compressor - The compressor is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of scroll bypass
and a temperature thermal overload sensor which protect the
compressor if undesirable operating conditions occur.
• Pressure Switches - A high pressure switch is standard in
all units. When abnormal conditions are sensed through the
pressure switch, the unit will lock out preventing any further
operation until reset or problem is corrected.
• Exclusive Coil Design - Grooved copper tubes and
enhanced aluminum fin construction improves heat transfer
for maximum efficiency and durability for long-lasting durability and efficient operation. Indoor coils will use tin-coated
copper tubing with aluminum fins for effective heat transfer.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 230v/1/60 from 2 kW to 25 kW.
Most kits stageable above 10 kW. Single phase single point
field wiring kits are available for all applications except 25kW.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
indoor coils, blower, controls/electric heat kits, filters, etc.
that makes servicing easy. Removing these panels allow
easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting.
• Replacement Parts - The installer requires no special training to replace any of the components of these units and the
number of new components have been reduced to minimize
the inventory of unique parts.
• Controls - Demand defrost curves pre-loaded into defrost
control for optimized performance based on unit capacities.
• Loss of Charge Switch - All models include a loss of charge
switch to provide safe shutdown of compressor.
2
Johnson Controls Unitary Products
5005568-YTG-H-1017
NOMENCLATURE
PHE
4
A
24
2
1
1
2
3
4
6
8
1. Model Family
5. Gas Heating Input BTU/Hr x 1000
PHE - packaged heat pump with electric heat,
050 = 50,000 BTU/Hr. input, blank = electric heat
PCG - packaged A/C with gas heat,
6. Voltage-Phase-Frequency
PHG - packaged heat pump with gas heat,
2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60
PCE - packaged A/C with electric heat
2. Nominal Cooling Efficiency
7. NOx Approval
4 = 14 SEER, 6 = 16 SEER, etc.
X = low-NOx, blank = not low-Nox
3. Cabinet Size
8. Generation Level
A = small 35 x 51, B = large 45 x 51
1 = first generation
4. Nominal Air Conditioning Cooling Capacity BTUx1000
9. Revision Level
24 = 24,000 BTU, etc.
A = original release, B = second release
Examples:
PHE4B4221A is a packaged heat pump, 14 SEER, 3-1/2 ton, large cabinet, 230 volt, 1-phase model, (first generation, first release).
A
9
COMPONENT LOCATION
FAN MOTOR
OUTDOOR FAN
COIL GUARD PANEL
OUTDOOR COIL
AMBIENT
TEMPERATURE
SENSOR
CONTROL BOARD
OUTDOOR TXV
CAPACITOR
REVERSING
VALVE
INDOOR TXV
TRANSFORMER
COMPRESSOR
BLOWER MOTOR
OPTIONAL
ELECTRIC HEAT KIT
INDOOR COIL
INDOOR BLOWER
REMOVABLE
BASE RAILS
A0380-001
UNIT LIMITATIONS
Model
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
PHE4B4821
PHE4B6021
Unit Voltage
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
Johnson Controls Unitary Products
Min
187
187
187
187
187
187
Unit Limitations
Applied Voltage
Max
252
252
252
252
252
252
Outdoor DB Temp
Max (°F)
125
125
125
125
125
125
3
5005568-YTG-H-1017
ACCESSORIES
• Economizer for Downflow Applications
(S1-2EE04710024, S1-2EE04710124) - Modulating integrated economizer provides simultaneous operation
between mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into the hood, dry bulb sensor and relief damper.
Separate field accessories of single/dual enthalpy kits are
also available.
• Economizer for Horizontal Applications
(S1-2EE04710224, S1-2EE04710324) - Modulating integrated economizer provides simultaneous operation
between the mechanical cooling and economizer operation.
Independent blade design insures proper control and less
than 1% leak rate. Includes hood and mesh bird screen filter
integrated into hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy
are available.
• Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) Sensor replaces dry bulb sensor standard in economizer kit.
Provides improved economizer operation by sensing the dry
bulb temperature from outdoors plus the enthalpy content of
the outdoor air.
• Duct/Unit Mount CO2 Kit (S1-2AQ04700924) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Wall Mount CO2 Kit (S1-2AQ04701024) - Sensor kit
detects CO2 levels automatically and overrides the economizer when CO2 levels rise above the preset limits.
• Supply Air Temperature Sensor Kit (S1-TE-63616E-2D) Outdoor supply air temperature sensor kit used with economizers.
• Filter/Frame Kit (S1-1FF0602, S1-1FF0601) - Kit contains
the necessary hardware to field install return air filters into
the base unit. The filter rack is suitable for either 1" or 2" filters.
• Filter (S1-02647812000) - Washable 1" filter. Two filters are
required for A base units. Three filters are required for B
base units.
• Motorized Fresh Air Damper
(S1-2MD04705224, S1-2MD04705124) - Designed for duct
mounted side supply/return and unit mounted down supply/
return applications. Damper capable of providing 0% through
50% of outdoor air (field supplied). Closes on power loss,
includes hood and screen assembly.
• Rectangle to Round (Horizontal) Adapter
(S1-1AK0110, S1-1AK0111) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit over current horizontal duct
openings on the base unit. Transition is from rectangle to 12"
round for the 1AK0110 kit and from rectangle to 14" round for
the 1AK0111 kit.
• Rectangle to Round (Downflow) Adapter
(S1-1AK0108, S1-1AK0109) - Kit includes one supply and
one return air rectangle to round duct adapter. Adapters are
preformed and designed to fit into current downflow duct
4
openings on the roof curb. Transition is from rectangle to 16"
round for the 1AK0108 kit and from rectangle to 18" round for
the 1AK0109 kit.
• Roof Curbs (S1-1RC0503, S1-1RC0501) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed to be assembled through hinge pins in
each corner. Kit also provides seal strip to assure an air tight
seal. These are 8 inch high roof curbs.
• Roof Curbs (S1-1RC0504, S1-1RC0502) - NRCA approved
curbs provide proper fit to base unit for rooftop installations.
Curbs are designed for assembly through hinge pins in each
corner. Kit also provides seal strip to assure air tight seal.
These are 14 inch high roof curbs.
• Transition Curb Kits (S1-1TC01*) - Adapter kits to allow
field use of pre-existing installed roof curbs to match PHE4
footprint to Affinity roof curbs, Carrier, Trane, or Goodman
curb footprints. Curb adapters are optional for current generation Carrier replacements but are recommended for previous generation applications. Refer to the PHE4 price pages
for more details.
• Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) Provides 0% through 50% outdoor air capability (field adjustable). Designed for duct mounted side supply/return applications and unit mounted down supply/return applications.
Includes hood and screen assembly.
• Loss of Charge Switch (S1-2LC00024) - Kit provides Loss
of Charge switch and wiring to provide safe shutdown of
compressor.
• Low Ambient Kit (S1-2LA04701024) - Kit provides necessary hardware to convert unit to operate in cooling cycle
down to 0º F. Standard unit operation 45º F.
• Transformer Kit (S1-2EC06700124) - Kit provides necessary hardware to provide single phase models from factory
furnished 40 VA transformer capability to 75 VA transformer
capability. (Required on installations with economizer or
motorized damper).
• Base Rail Hole Cover Kit (S1-1HC0101) - Kit provides necessary hardware to close off openings in base rails to block
off openings, i.e. prevent animal entrance.
• Single Point Wiring Kits for 6HK Electric Heat Applications (S1-SPWK*) - Kit provides field option for connecting
electrical power supplies to the field installed 6HK kits to
allow single point connections for single phase electric heat
applications with the exception of 25kW kits.
• Thermostat (S1-THXU280*) - Compatible thermostat controls are available through accessory sourcing. For optimum
performance, these outdoor units are fully compatible with
the York Hx™ Touchscreen Thermostat (S1-THXU280*)
available through Source1. For more information, see the
thermostat section of the Product Equipment Catalog.
• Wall Thermostat - The units are designed to operate with
standard, 24-volt electronic non power stealing and electromechanical thermostats. All units can operate with single
stage heat/single stage cool thermostats - with or without the
economizer.
* For additional kit numbers refer to the price pages.
Johnson Controls Unitary Products
5005568-YTG-H-1017
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility. These packaged cooling/heating air
conditioners are designed for outdoor installation. Only utility
and duct connections are required at the point of installation.
Heat pumps provide electric cooling and electric heating, with
field installed electric heat kits from 5 kW to 25 kW for backup
supplemental heating operation.
DESCRIPTION
Units shall be factory-assembled, single packaged, Heat
Pumps with Electric Cooling/Electric Heating units, designed for
outdoor installation. They shall have built in, equal size, field
convertible duct connections for downflow supply/return or
horizontal supply/return. The units shall be factory wired, piped,
and charged with R-410A Refrigerant and factory tested prior to
shipment. All models shall be rated in accordance with DOE
and AHRI test procedures for both heating and cooling
operation. Units shall be CSA listed to the UL 1995/CAN/CSA
No. 236-M90 standards.
• Operating Efficiency - All heat pump models shall be rated
at a minimum of 14.0 SEER, 11.0 EER and 8.0 HSPF for
cooling and heating operation.
• Low Operating Sound Level - The upward air flow carries
the normal operating noise up and away from the living area.
The rigid top panel effectively isolates noise. Isolator
mounted compressor and the rippled fins of the outdoor coil
muffle the normal fan motor and compressor operating
sounds. The unique formed base pan also aids in sound
attenuation with its structural design. Sound ratings as tested
under AHRI test procedures shall be less than 77 dbA for all
models.
UNIT CABINET
Unit cabinet shall be a single piece design, with drip edges and
no-seam corners to provide optimum water integrity. Unit shall
have a rigidly mounted outdoor coil guard to provide protection
from objects and personnel after installation. Indoor blower
section shall be insulated with foil-faced or foam insulation,
fastened to prevent insulation from entering the air stream.
Cabinet panels shall be separate, easily removable for
servicing and maintenance. Unit shall be built on a formed,
design base pan, with embossments at critical points to add
strength and rigidity and to aid in minimizing sound. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, for fork truck access and
proper sealing on roof curb applications. Base rails shall be
easily removable, when required to lower unit height. Filters
shall be field installed, furnished and be accessible through a
removable access door, sealed airtight. Units vertical discharge
and return duct configuration shall be designed to fit between
standard 24” O.C. beams without modification to building
structure, duct work and base unit.
• On Site Flexibility - All model sizes shall use a compact
design cabinet in one of two footprints. This provides installer
flexibility for placing the proper capacity unit on curbs or pads
with the smallest footprint after the internal load has been
determined. Field convertible duct connections from side
shot to down shot allows the installer to have greater flexibility with less inventory.
Johnson Controls Unitary Products
• Durable Finish - The cabinet shall be is made of G90 galvanized steel with a powder paint coating for appearance and
protection. The pre-treated galvanized steel shall provide a
better paint-to-steel bond, which resists corrosion and rust
creep. Powder paint finish insure less fading when exposed
to sunlight, and provides superior corrosion resistance (1000
hour salt spray tested).
• Attractive Appearance - A single-piece top cover containing
a top-discharge outdoor fan arrangement shall be used
which requires less square footage on installation and provides a wider variety of installations. The one-piece design
adds greater water integrity. Rounded corners with water drip
edges add to the attractive appearance and prevent water
penetration.
• Convertible Airflow Design - The bottom duct openings are
covered when they leave the factory, ready to be used for a
side supply/side return application. If a bottom supply/bottom
return application is desired, simply remove the two panels
from the bottom of the unit and place them in the side supply/
side return duct openings. No panel cutting is required and
no accessory panel is necessary. Convertible airflow design
allows maximum field flexibility and minimum inventory.
• Utility Connections Made Easy - Electric utility access shall
be provided through the bottom or the side of the unit. Utility
connections should be made quickly and with a minimum
amount of field labor. A field supplied and field installed electrical disconnect switch must be installed.
• Easy Service Access - Individual access panels are provided in access to all major components - compressors,
indoor coils, blower, controls/electric heat kits, filters, etc.
that makes servicing easy. Removing these panels allow
easy removal of the components such as the blower assembly for maintenance and ease of troubleshooting.
• Top Discharge - The top-discharge outdoor fan does not
disrupt neighboring areas or dry out vegetation surrounding
the unit. The warm air from the top mounted fan is blown up
and away from the structure and any landscaping.
• Outdoor Coil Grille - All models utilize a stamped slotted
design which provides superior impact protection against
small objects during transit and after installation.
Indoor Blower Assembly - Blower shall be direct drive design.
Blower wheel shall be double-inlet type with forward-curved
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Design shall use constant torque
motors. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Fan assembly shall be a
slide-out design for easy removal and cleaning. Indoor blower
motors shall be equipped with a standard high efficiency
brushless DC motor (constant torque) also known as a standard
ECM motor.
Outdoor Fan Assembly - The outdoor fan shall be of the
direct-driven propeller type, discharge air vertically, have
aluminum blades riveted to corrosion resistant steel spider
bracket and shall be statically balanced for smooth operation.
The outdoor fan motor shall be totally enclosed with
permanently lubricated bearings and internally protected
against overload conditions.
5
5005568-YTG-H-1017
REFRIGERANT COMPONENTS
CONTROLS
• Protected Compressor - The compressor shall be a fully
hermetic type, direct drive compressor, that is internally protected against high pressure and temperature. This is
accomplished by the simultaneous operation of operation of
scroll bypass valve and a temperature thermal overload sensor which protect the compressor if undesirable operating
conditions occur. The hermetic motor shall be suction gas
cooled and have a voltage range of +/- 10% of the unit nameplate voltage. Compressors shall have internal isolation and
sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.
• Simple Control Circuit - A printed circuit board contains a
status/diagnostic indicator light. Field thermostat wiring connects to color coded leads using twist on wire connections.
Cooling controls use contactor and relays for simple application and troubleshooting. Mate-n-lock plug connectors are
used. The electrical control box is not located in the compressor compartment. The controls are mounted to allow the
separate access panel to be removed for trouble shooting
and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number
coded.
• Indoor Coils - Indoor coils shall be of the direct expansion,
draw through design and have aluminum plate fins mechanically bonded to seamless internally enhanced tin-coated
copper tubes with all joints brazed.
• Controls - Demand defrost curves pre-loaded into defrost
control for optimized performance based on unit capacities.
• Condensate Pan - A corrosion-resistant, long-lasting, watertight pan is positioned below the indoor coil to collect and
drain all condensate, preventing build-up of stagnant condensate. The condensate pan conforms to ASHRAE 62-89
standards (Ventilation for Acceptable Indoor Air Quality).
• Condensate Drain - The 3/4 inch NPT female connection is
rigidly mounted to assure proper fit and leak tight seal.
• Outdoor Coils - Outdoor coils shall have aluminum plate
fins mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed, and be a draw through
design.
• Refrigerant Circuit and Refrigerant Safety Components
shall include: Thermal expansion devices (TXV's) shall be
factory mounted and provided, Filter/strainer to eliminate any
foreign matter, reversing valves to control refrigerant flow.
6
• Pressure Switches - A high pressure switch is standard in
all units. When abnormal conditions are sensed through the
pressure switch, the unit will lock out preventing any further
operation until reset or problem is corrected.
• Factory Testing - Installation time and costs are reduced by
easy power and control wiring connections. All units are
completely wired, charged with refrigerant R-410A refrigerant and tested prior to shipment. Test stations using a stateof-the-art computerized process system shall be used to
insure product quality. Refrigerant charge and component
part numbers are verified via computer bar code scans
during assembly. Vital run test statistics such as system
pressure, motor currents, air velocity and temperature, unit
vibration, and gas system safeties are monitored and
recorded by the system to insure unit performance. This data
could be provided by serial number tracking if necessary.
• Electric Heat - All electric heat models use 6HK electric
heat, which are available in 230v/1/60 from 2 kW to 25 kW,
230v/3/60 10kW to 25kW, and 460v/3/60 10kW to 25kW.
Most kits stageable above 10 kW. Single point accessory kits
are available for single phase models. Single phase single
point field wiring kits are available for all applications except
25kW. Electric heat kits must be certified to UL 1995 standard requirements.
Johnson Controls Unitary Products
5005568-YTG-H-1017
PHYSICAL DATA
COMPONENT
NOMINAL TONNAGE:
AHRI Cooling Performance
Gross Capacity @ AHRI A point (MBH)
AHRI net capacity (MBH)
EER
SEER
Nominal CFM
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
AHRI Heating Performance
47 Capacity Rating (MBH)
System Power (kW/COP)
17 F Capacity Rating (MBH)
HSPF (BTU/Watts-hr.)
Dimensions (inches)
Length
Width
Height
Operating WT. (lbs.)
Compressors
Type
Outdoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Indoor Coil Data
Face area (Sq. Ft.)
Rows
Fins per inch
Tube diameter
Circuitry Type
Refrigerant control
Outdoor Fan Data
Fan diameter (Inch)
Type
Drive type
No. speeds
Motor HP each
RPM
Nominal total CFM
Direct Drive Indoor Blower Data
Fan Size (Inch)
Type
Motor HP each
RPM
Frame size
Filters
Filter size
Quantity - Size
Johnson Controls Unitary Products
MODELS
PHE4B3621
PHE4B4221
3.0
3.5
PHE4A2421
2.0
PHE4A3021
2.5
PHE4B4821
4.0
PHE4B6021
5.0
24.1
23.8
11.0
14.0
800
1.8
R410A
8-5
30.1
29.6
11.0
14.0
1000
2.2
R410A
9-8
36.4
35.8
11.0
14.0
1200
2.8
R410A
11-13
42.3
41.5
11.0
14.0
1400
3.2
R410A
13-0
48.2
47.0
11.0
14.0
1600
3.7
R410A
12-13
59.9
58.0
11.0
14.0
1800
4.7
R410A
15-8
22.0
3.7
12.0
8.0
27.2
3.6
14.8
8.0
33.8
3.6
19.6
8.0
38.0
3.6
22.0
8.0
45.5
3.7
26.0
8.0
56.0
3.6
32.0
8.0
51-1/4
35-3/4
47
377
51-1/4
35-3/4
49
392
51-1/4
45-3/4
49
448
51-1/4
45-3/4
49
471
51-1/4
45-3/4
53
496
51-1/4
45-3/4
55
523
Scroll
Scroll
Scroll
Scroll
Scroll
Scroll
15.1
2
22
3/8
Interlaced
TXV
16.9
2
22
3/8
Interlaced
TXV
19.4
2
22
3/8
Interlaced
TXV
19.4
2
22
3/8
Interlaced
TXV
23.8
2
22
3/8
Interlaced
TXV
25.9
2
22
3/8
Interlaced
TXV
4.6
3
16
3/8
Interlaced
TXV
4.6
3
16
3/8
Interlaced
TXV
6.3
3
16
3/8
Interlaced
TXV
6.3
3
16
3/8
Interlaced
TXV
6.3
3
16
3/8
Interlaced
TXV
6.3
4
16
3/8
Interlaced
TXV
24
Prop
Direct
1
1/10
850
2400
24
Prop
Direct
1
1/8
850
2400
26
Prop
Direct
1
1/3
850
3200
26
Prop
Direct
1
1/3
850
3200
26
Prop
Direct
1
1/3
850
3200
26
Prop
Direct
1
1/3
850
3200
11 x 8
Centrifugal
1/2
1200 Max
48
11 x 8
Centrifugal
1/2
1200 Max
48
11 x 10
Centrifugal
1/2
1200 Max
48
11 x 10
Centrifugal
3/4
1200 Max
48
11 x 10
Centrifugal
3/4
1200 Max
48
11 x 10
Centrifugal
1
1200 Max
48
A
A
B
B
B
B
Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable filters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for
replacement filter sizes. Filter sizes: A=20x20, B=20x30.
7
5005568-YTG-H-1017
COOLING PERFORMANCE DATA - 2 TON
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PHE4A2421
80
57
24.9
23.5
0.98
24.2
22.5
1.10
23.4
21.5
1.21
22.3
20.4
1.36
21.2
19.4
1.51
19.3
17.8
1.71
17.4
16.2
1.91
15.6
14.7
2.11
80
62
28.3
19.9
0.98
26.9
19.2
1.09
25.4
18.5
1.21
23.5
17.7
1.35
21.7
16.8
1.50
19.5
15.9
1.71
17.4
15.1
1.91
15.3
14.3
2.12
600
75
62
28.3
18.0
0.98
26.9
17.0
1.08
25.5
16.1
1.19
23.7
15.2
1.34
21.9
14.4
1.49
19.7
13.2
1.70
17.5
12.2
1.90
15.4
11.1
2.11
80
67
31.8
17.8
0.98
30.0
16.9
1.09
28.2
16.0
1.20
26.4
15.1
1.35
24.6
14.3
1.50
22.5
13.4
1.71
20.5
12.5
1.91
18.4
11.6
2.11
80
72
34.8
15.0
0.97
33.1
14.1
1.08
31.5
13.2
1.20
29.5
12.4
1.35
27.5
11.6
1.50
24.7
10.5
1.71
22.1
9.5
1.91
19.4
8.5
2.11
80
57
28.3
26.5
1.03
27.2
25.3
1.15
26.1
24.2
1.27
24.7
22.8
1.41
23.4
21.4
1.56
20.9
19.4
1.76
18.6
17.5
1.96
16.2
15.5
2.16
80
62
30.6
23.4
1.03
29.0
22.6
1.15
27.5
21.9
1.26
25.3
20.7
1.41
23.1
19.5
1.55
20.8
18.2
1.76
18.6
16.9
1.96
16.4
15.7
2.17
800
75
62
31.0
20.7
1.03
29.2
19.6
1.14
27.3
18.5
1.25
25.2
17.4
1.40
23.1
16.3
1.54
20.6
15.2
1.75
18.2
14.1
1.96
15.8
13.0
2.16
80
67
34.5
20.2
1.03
32.3
19.4
1.14
30.1
18.7
1.25
28.2
17.6
1.40
26.2
16.6
1.55
23.5
15.5
1.76
20.8
14.4
1.96
18.2
13.2
2.16
80
72
36.9
16.1
1.02
35.2
15.4
1.14
33.6
14.8
1.25
31.4
14.0
1.40
29.2
13.1
1.55
26.2
11.9
1.76
23.3
10.7
1.96
20.4
9.5
2.16
80
57
31.6
29.5
1.08
30.2
28.1
1.20
28.8
26.8
1.32
27.1
25.1
1.47
25.5
23.4
1.61
22.5
21.0
1.82
19.7
18.7
2.01
16.8
16.4
2.21
80
62
32.8
26.8
1.08
31.2
26.0
1.20
29.5
25.2
1.31
27.0
23.7
1.46
24.5
22.1
1.60
22.1
20.4
1.81
19.8
18.8
2.02
17.5
17.1
2.22
1000
75
62
33.8
23.4
1.08
31.4
22.2
1.19
29.1
21.0
1.31
26.7
19.6
1.45
24.4
18.2
1.59
21.6
17.1
1.81
18.9
16.1
2.01
16.2
15.0
2.22
80
67
37.1
22.6
1.08
34.6
22.0
1.19
32.0
21.4
1.31
29.9
20.2
1.45
27.8
18.9
1.60
24.4
17.6
1.81
21.2
16.2
2.01
18.0
14.9
2.21
80
72
39.0
17.1
1.07
37.3
16.8
1.19
35.6
16.4
1.31
33.3
15.5
1.45
30.9
14.7
1.60
27.7
13.3
1.81
24.6
11.9
2.01
21.5
10.5
2.21
80
67
37.2
22.6
1.50
35.6
21.7
1.67
34.0
20.7
1.84
31.6
19.8
2.04
29.2
18.9
2.24
26.0
17.3
2.53
22.8
15.7
2.80
19.7
14.2
3.08
80
72
42.9
18.8
1.51
39.8
17.4
1.67
36.8
16.0
1.84
35.0
15.3
2.04
33.2
14.7
2.25
29.6
13.4
2.54
26.1
12.2
2.81
22.6
10.9
3.09
80
57
32.8
32.2
1.50
31.2
30.7
1.66
29.6
29.3
1.82
27.4
27.1
2.03
25.2
25.0
2.23
22.6
22.4
2.52
20.0
19.9
2.80
17.5
17.4
3.08
80
62
35.3
28.9
1.50
33.5
28.3
1.66
31.7
27.8
1.83
29.5
26.4
2.03
27.3
25.0
2.23
23.8
22.2
2.52
20.4
19.5
2.80
16.9
16.8
3.07
1000
75
62
35.8
24.8
1.50
33.7
23.8
1.66
31.5
22.8
1.82
28.9
21.8
2.03
26.3
20.8
2.23
22.8
18.7
2.51
19.4
16.6
2.79
16.1
14.6
3.07
80
67
39.4
24.4
1.50
37.6
23.9
1.67
35.8
23.4
1.84
33.1
22.3
2.04
30.5
21.2
2.24
27.1
19.4
2.53
23.7
17.6
2.80
20.4
15.9
3.08
80
72
45.4
20.1
1.51
42.7
19.1
1.67
40.0
18.1
1.84
37.4
17.2
2.05
34.8
16.3
2.25
30.8
14.7
2.54
27.0
13.2
2.81
23.1
11.6
3.09
80
57
35.3
35.1
1.50
33.4
33.2
1.66
31.5
31.3
1.83
29.1
28.9
2.03
26.7
26.5
2.24
24.0
23.8
2.53
21.3
21.2
2.81
18.7
18.6
3.09
80
62
37.2
31.7
1.50
35.4
31.4
1.66
33.6
31.1
1.83
30.9
29.5
2.03
28.1
27.9
2.24
24.6
24.4
2.53
21.1
21.0
2.80
17.7
17.5
3.08
1200
75
62
37.8
27.1
1.51
35.5
26.1
1.67
33.2
25.2
1.83
30.3
24.2
2.03
27.4
23.1
2.23
23.6
20.7
2.51
19.9
18.4
2.79
16.1
16.0
3.07
80
67
41.6
26.2
1.51
39.6
26.1
1.67
37.6
26.1
1.84
34.7
24.8
2.04
31.8
23.5
2.24
28.2
21.5
2.53
24.6
19.6
2.80
21.1
17.6
3.08
80
72
47.9
21.5
1.51
45.5
20.9
1.68
43.2
20.3
1.85
39.8
19.1
2.05
36.5
17.9
2.25
32.1
16.0
2.54
27.9
14.2
2.81
23.6
12.3
3.09
COOLING PERFORMANCE DATA - 2.5 TON
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
8
PHE4A3021
80
57
30.3
29.3
1.50
29.0
28.3
1.66
27.6
27.3
1.82
25.6
25.4
2.02
23.6
23.4
2.23
21.1
21.0
2.52
18.7
18.6
2.80
16.3
16.2
3.08
80
62
33.5
26.1
1.50
31.7
25.3
1.66
29.9
24.5
1.83
28.1
23.3
2.03
26.4
22.1
2.23
22.9
20.1
2.51
19.6
18.1
2.79
16.2
16.1
3.07
800
75
62
33.8
22.5
1.50
31.8
21.5
1.66
29.9
20.5
1.82
27.5
19.5
2.02
25.2
18.6
2.23
22.1
16.7
2.51
19.0
14.9
2.79
16.0
13.1
3.07
Johnson Controls Unitary Products
5005568-YTG-H-1017
COOLING PERFORMANCE DATA - 3 TON
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PHE4B3621
80
57
40.4
40.0
1.97
37.9
37.9
2.17
35.4
35.4
2.36
33.1
33.1
2.63
30.7
30.7
2.89
27.8
27.8
3.26
25.1
25.1
3.63
22.3
22.3
3.99
80
62
43.9
34.9
1.98
41.2
33.7
2.18
38.5
32.5
2.39
35.4
30.8
2.65
32.2
29.1
2.91
28.4
26.7
3.28
24.8
24.3
3.64
21.1
21.1
4.00
1000
75
62
43.9
30.5
1.98
41.4
29.1
2.17
38.9
27.6
2.36
35.8
26.1
2.63
32.7
24.6
2.89
28.7
22.7
3.27
24.9
20.9
3.63
21.1
19.0
4.00
80
67
47.3
29.3
1.98
45.1
28.4
2.18
42.8
27.4
2.39
39.7
25.9
2.65
36.6
24.3
2.91
32.2
22.5
3.28
27.9
20.7
3.63
23.7
18.9
3.99
80
72
46.7
22.4
1.98
47.2
22.3
2.18
47.6
22.1
2.39
44.4
20.7
2.65
41.1
19.4
2.91
36.6
17.6
3.28
32.3
15.8
3.64
27.9
14.1
4.00
80
57
43.3
42.9
2.06
40.4
40.4
2.26
37.5
37.5
2.46
34.7
34.7
2.72
32.0
32.0
2.98
28.8
28.8
3.35
25.7
25.7
3.72
22.6
22.6
4.08
80
62
45.1
40.4
2.07
42.4
38.1
2.27
39.8
35.7
2.48
36.5
34.0
2.74
33.1
32.2
3.00
29.1
28.8
3.37
25.2
25.2
3.73
21.3
21.3
4.09
1200
75
62
45.4
32.6
2.07
42.6
32.7
2.27
39.8
32.9
2.47
36.6
30.0
2.73
33.4
27.1
2.98
29.0
24.6
3.36
24.7
22.2
3.73
20.5
19.8
4.09
80
67
47.7
31.2
2.07
46.0
30.6
2.28
44.2
29.9
2.48
40.7
28.2
2.74
37.1
26.5
3.00
32.3
24.6
3.37
27.7
22.8
3.72
23.0
21.0
4.08
80
72
47.3
23.3
2.07
47.8
23.5
2.28
48.4
23.7
2.48
45.2
22.3
2.74
42.1
21.0
3.00
37.1
19.0
3.37
32.2
17.1
3.73
27.3
15.3
4.09
80
57
46.2
45.9
2.16
42.8
42.8
2.36
39.5
39.5
2.56
36.4
36.4
2.81
33.4
33.4
3.07
29.8
29.8
3.44
26.4
26.4
3.81
22.9
22.9
4.17
80
62
46.2
45.9
2.16
43.7
42.5
2.36
41.1
39.0
2.57
37.5
37.1
2.83
33.9
33.9
3.09
29.7
29.7
3.46
25.6
25.6
3.82
21.5
21.5
4.18
1400
75
62
46.8
34.6
2.16
43.8
36.4
2.37
40.7
38.2
2.58
37.4
33.9
2.83
34.1
29.6
3.08
29.3
26.5
3.45
24.5
23.6
3.82
19.8
19.8
4.18
80
67
48.2
33.0
2.16
46.9
32.7
2.37
45.7
32.5
2.58
41.6
30.6
2.83
37.6
28.7
3.09
32.5
26.8
3.46
27.4
24.9
3.81
22.4
22.4
4.17
80
72
47.8
24.3
2.16
48.5
24.7
2.37
49.1
25.2
2.58
46.0
23.9
2.83
43.0
22.6
3.09
37.5
20.5
3.46
32.1
18.5
3.82
26.8
16.4
4.18
80
67
53.3
33.0
2.28
52.0
32.9
2.51
50.7
32.7
2.74
46.5
30.7
3.04
42.4
28.7
3.35
37.2
26.6
3.76
32.2
24.7
4.16
27.1
22.7
4.56
80
72
55.3
25.6
2.28
55.3
25.6
2.52
55.4
25.5
2.76
51.5
24.0
3.05
47.6
22.5
3.35
42.4
20.4
3.76
37.4
18.4
4.17
32.3
16.5
4.58
80
57
47.6
47.6
2.37
44.8
44.8
2.60
41.9
41.9
2.82
38.5
38.5
3.12
35.2
35.2
3.41
32.0
32.0
3.83
28.9
28.9
4.23
25.8
25.8
4.63
80
62
51.3
42.5
2.37
48.6
42.1
2.60
45.8
41.8
2.82
41.6
39.1
3.12
37.5
36.4
3.41
33.1
32.5
3.83
28.8
28.7
4.24
24.6
24.6
4.64
1400
75
62
51.2
36.2
2.37
48.7
35.8
2.60
46.3
35.3
2.82
41.9
33.0
3.12
37.6
30.6
3.42
32.1
27.5
3.83
26.8
24.5
4.23
21.5
21.5
4.63
80
67
54.1
34.4
2.38
52.9
34.9
2.61
51.8
35.3
2.85
47.2
33.0
3.14
42.7
30.8
3.44
37.1
28.5
3.85
31.6
26.3
4.25
26.1
24.1
4.65
80
72
56.6
26.5
2.38
56.2
26.7
2.62
55.8
26.8
2.86
52.2
25.4
3.15
48.6
23.9
3.45
42.8
21.7
3.86
37.1
19.7
4.26
31.5
17.6
4.66
80
57
49.5
49.5
2.47
46.4
46.4
2.70
43.4
43.4
2.93
39.9
39.9
3.22
36.5
36.5
3.51
33.3
33.3
3.93
30.1
30.1
4.33
27.0
27.0
4.73
80
62
52.3
44.6
2.47
49.8
45.0
2.69
47.3
45.4
2.92
42.7
42.0
3.22
38.1
38.1
3.51
34.1
34.1
3.93
30.1
30.1
4.34
26.2
26.2
4.74
1600
75
62
52.1
37.9
2.46
49.7
38.0
2.69
47.3
38.1
2.92
42.6
35.5
3.22
38.0
32.9
3.51
32.2
29.0
3.92
26.6
25.1
4.32
21.0
21.0
4.72
80
67
54.9
35.9
2.47
53.9
36.9
2.71
52.9
37.9
2.95
47.9
35.4
3.24
43.0
32.9
3.53
36.9
30.4
3.95
31.0
28.0
4.35
25.1
25.1
4.75
80
72
57.9
27.4
2.47
57.0
27.8
2.71
56.2
28.2
2.95
52.9
26.7
3.25
49.7
25.3
3.55
43.2
23.1
3.96
36.9
20.9
4.36
30.6
18.7
4.75
COOLING PERFORMANCE DATA - 3.5 TON
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PHE4B4221
80
57
45.8
45.8
2.26
43.1
43.1
2.49
40.3
40.3
2.72
37.1
37.1
3.02
34.0
34.0
3.31
30.8
30.8
3.73
27.7
27.7
4.13
24.6
24.6
4.53
Johnson Controls Unitary Products
80
62
50.4
40.4
2.27
47.4
39.3
2.50
44.4
38.2
2.73
40.6
36.1
3.02
36.8
34.1
3.31
32.1
30.4
3.73
27.5
26.9
4.14
23.0
23.0
4.54
1200
75
62
50.3
34.5
2.28
47.8
33.5
2.51
45.3
32.6
2.73
41.2
30.4
3.03
37.2
28.3
3.33
32.0
26.1
3.74
27.0
24.0
4.14
21.9
21.8
4.53
9
5005568-YTG-H-1017
COOLING PERFORMANCE DATA - 4 TON
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
65 / 55
S.C.
K.W.
T.C.
75 / 63
S.C.
K.W.
T.C.
85 / 69
S.C.
K.W.
T.C.
95 / 75
S.C.
K.W.
T.C.
105 / 83
S.C.
K.W.
T.C.
115 / 89
S.C.
K.W.
T.C.
125 / 95
S.C.
K.W.
PHE4B4821
80
57
48.0
48.0
2.63
45.0
45.0
2.90
42.0
42.0
3.16
39.3
39.3
3.53
36.6
36.6
3.91
33.2
33.2
4.40
29.9
29.9
4.89
26.5
26.5
5.37
80
62
51.3
44.1
2.64
48.1
41.5
2.92
44.9
38.9
3.21
41.4
36.4
3.56
37.9
34.0
3.91
34.2
32.3
4.40
30.7
30.6
4.89
27.1
27.1
5.37
1400
75
62
52.4
37.9
2.63
48.9
35.6
2.90
45.4
33.3
3.16
41.9
31.0
3.52
38.5
28.6
3.87
34.7
26.9
4.38
31.1
25.2
4.87
27.5
23.5
5.36
80
67
56.5
40.8
2.66
54.0
37.5
2.94
51.6
34.2
3.22
48.2
32.0
3.57
44.8
29.8
3.93
41.0
27.7
4.43
37.3
25.6
4.91
33.6
23.6
5.39
80
72
64.4
33.6
2.70
60.8
31.0
2.96
57.2
28.4
3.22
53.7
26.1
3.58
50.1
23.8
3.95
46.0
21.9
4.44
42.1
20.1
4.92
38.2
18.3
5.40
80
57
50.6
50.6
2.77
47.3
47.3
3.03
44.1
44.1
3.30
41.1
41.1
3.66
38.1
38.1
4.03
34.4
34.4
4.53
30.8
30.8
5.02
27.2
27.2
5.50
80
62
53.7
47.6
2.77
50.1
44.8
3.05
46.4
41.9
3.32
42.8
39.4
3.68
39.1
36.9
4.04
35.4
34.8
4.53
31.7
31.7
5.01
28.1
28.1
5.49
1600
75
62
54.5
40.5
2.77
50.9
38.1
3.03
47.3
35.7
3.30
43.5
33.2
3.65
39.7
30.8
4.01
35.9
28.9
4.51
32.1
27.1
5.00
28.3
25.2
5.48
80
67
60.0
42.6
2.80
56.8
39.6
3.07
53.5
36.6
3.35
49.9
34.3
3.70
46.4
32.0
4.06
42.2
29.7
4.56
38.1
27.5
5.04
34.0
25.3
5.52
80
72
66.5
35.0
2.82
62.7
32.6
3.09
59.0
30.1
3.35
55.3
27.7
3.72
51.5
25.3
4.08
47.3
23.4
4.57
43.3
21.5
5.05
39.2
19.7
5.53
80
57
53.1
53.1
2.91
49.7
49.7
3.17
46.2
46.2
3.43
42.9
42.9
3.79
39.7
39.7
4.16
35.7
35.7
4.66
31.8
31.8
5.15
27.9
27.9
5.64
80
62
56.1
51.0
2.90
52.0
48.0
3.17
47.9
45.0
3.44
44.1
42.4
3.81
40.4
39.8
4.17
36.5
36.5
4.66
32.8
32.8
5.14
29.0
29.0
5.62
1800
75
62
56.7
43.2
2.90
53.0
40.6
3.16
49.3
38.0
3.43
45.2
35.5
3.79
41.0
33.0
4.15
37.0
31.0
4.64
33.1
29.0
5.12
29.1
27.0
5.60
80
67
63.6
44.3
2.93
59.5
41.7
3.21
55.4
39.0
3.48
51.7
36.6
3.84
48.0
34.2
4.19
43.4
31.7
4.69
38.9
29.4
5.17
34.4
27.1
5.65
80
72
68.5
36.4
2.95
64.7
34.2
3.22
60.8
31.9
3.49
56.8
29.4
3.85
52.9
26.9
4.20
48.6
24.9
4.70
44.4
22.9
5.18
40.3
21.0
5.66
80
67
68.6
55.3
3.41
67.4
49.0
3.77
66.2
42.6
4.14
61.5
40.5
4.60
56.7
38.4
5.05
50.1
36.5
5.71
43.6
34.6
6.35
37.1
32.8
6.99
80
72
81.4
37.3
3.45
77.8
36.9
3.82
74.3
36.5
4.18
69.1
33.4
4.64
63.8
30.2
5.10
57.4
27.7
5.75
51.1
25.2
6.39
44.9
22.8
7.02
80
57
65.3
65.3
3.54
62.3
62.3
3.87
59.2
59.2
4.20
55.1
55.1
4.67
51.1
51.1
5.14
46.5
46.5
5.83
42.1
42.1
6.49
37.7
37.7
7.16
80
62
74.6
49.2
3.59
64.4
48.6
4.06
54.1
47.9
4.53
52.4
48.3
4.85
50.6
48.6
5.17
45.1
43.9
5.84
39.9
39.3
6.50
34.6
34.6
7.15
1800
75
62
70.4
50.6
3.56
65.8
48.5
3.90
61.2
46.4
4.25
56.2
44.1
4.70
51.2
41.8
5.15
44.7
38.2
5.82
38.5
34.7
6.47
32.3
31.2
7.12
80
67
70.6
60.0
3.57
69.2
53.0
3.93
67.8
46.1
4.30
62.7
43.8
4.76
57.5
41.6
5.22
50.2
39.0
5.88
43.0
36.4
6.52
35.9
33.8
7.16
80
72
80.6
38.1
3.61
78.2
37.8
3.98
75.8
37.6
4.35
70.5
34.8
4.81
65.3
32.0
5.26
58.2
29.4
5.91
51.4
26.9
6.55
44.6
24.4
7.18
80
57
69.1
69.1
3.72
65.6
65.6
4.05
62.1
62.1
4.39
57.8
57.8
4.85
53.5
53.5
5.31
48.6
48.6
5.99
43.8
43.8
6.66
39.0
39.0
7.32
80
62
74.7
52.1
3.74
62.1
48.7
4.37
49.5
45.4
5.01
50.6
48.6
5.17
51.7
51.7
5.33
46.0
46.0
6.00
40.5
40.5
6.66
35.0
35.0
7.31
2000
75
62
72.3
54.2
3.72
67.4
52.0
4.06
62.5
49.8
4.41
57.4
47.3
4.87
52.4
44.8
5.32
45.4
40.4
5.99
38.6
36.2
6.63
31.8
31.8
7.28
80
67
72.6
64.6
3.73
71.1
57.1
4.10
69.5
49.5
4.47
63.9
47.1
4.93
58.3
44.8
5.39
50.3
41.4
6.04
42.5
38.1
6.68
34.8
34.8
7.32
80
72
79.7
38.9
3.76
78.5
38.8
4.14
77.3
38.7
4.52
72.0
36.2
4.97
66.7
33.8
5.42
59.1
31.1
6.07
51.7
28.5
6.71
44.3
25.9
7.34
COOLING PERFORMANCE DATA - 5 TON
PACKAGED UNIT MODEL NO.
ID CFM
CONDENSER
IDDB
ENTERING AIR
TEMPERATURE
IDWB
T.C.
55 / 45
S.C.
K.W.
T.C.
S.C.
65 / 55
K.W.
T.C.
S.C.
75 / 63
K.W.
T.C.
S.C.
85 / 69
K.W.
T.C.
S.C.
95 / 75
K.W.
T.C.
S.C.
105 / 83
K.W.
T.C.
S.C.
115 / 89
K.W.
T.C.
S.C.
125 / 95
K.W.
10
PHE4B6021
80
57
61.5
61.5
3.37
58.9
58.9
3.69
56.3
56.3
4.01
52.5
52.5
4.49
48.6
48.6
4.97
44.5
44.5
5.66
40.5
40.5
6.33
36.5
36.5
7.00
80
62
74.6
46.4
3.44
66.6
48.4
3.75
58.7
50.4
4.06
54.1
47.9
4.53
49.5
45.4
5.01
44.3
41.6
5.68
39.2
37.9
6.34
34.1
34.1
6.99
1600
75
62
68.4
47.0
3.40
64.2
45.0
3.74
60.0
42.9
4.09
55.0
40.8
4.54
50.0
38.8
4.99
44.1
35.9
5.66
38.4
33.2
6.31
32.7
30.4
6.97
Johnson Controls Unitary Products
5005568-YTG-H-1017
HEATING PERFORMANCE DATA - 2 TON
PACKAGED UNIT MODEL NO. PHE4A2421
AIR TEMP.
ENTERING
OUTDOOR COIL
60
47
40
30
17
10
AIR TEMP.
ENTERING
INDOOR COIL
60
70
80
60
70
80
60
70
80
60
70
80
60
MBH
28.1
26.7
25.3
23.4
22.3
21.3
20.7
19.8
18.8
17.1
16.7
16.2
13.6
600
COP
4.56
3.92
3.39
4.00
3.42
2.96
3.61
3.09
2.66
3.08
2.69
2.38
2.57
KW
1.80
1.99
2.18
1.71
1.91
2.10
1.67
1.87
2.06
1.62
1.80
1.99
1.54
70
80
60
70
80
12.7
11.8
12.2
11.4
10.5
2.14
1.80
2.36
1.97
1.65
1.73
1.91
1.51
1.68
1.86
MBH
29.3
27.8
26.4
24.1
23.0
21.9
21.4
20.4
19.4
17.6
17.0
16.3
13.9
ID CFM
800
COP
5.06
4.34
3.75
4.31
3.70
3.20
3.87
3.32
2.87
3.28
2.83
2.47
2.65
KW
1.69
1.87
2.05
1.63
1.82
2.00
1.61
1.79
1.97
1.57
1.75
1.93
1.52
MBH
30.5
29.0
27.5
24.9
23.7
22.5
22.0
21.0
20.0
18.2
17.3
16.4
14.1
1000
COP
5.63
4.82
4.16
4.66
4.00
3.46
4.16
3.58
3.10
3.48
2.98
2.57
2.75
KW
1.58
1.76
1.93
1.56
1.73
1.90
1.54
1.71
1.88
1.53
1.69
1.86
1.50
12.9
12.0
12.1
11.3
10.4
2.22
1.87
2.37
1.99
1.67
1.69
1.87
1.49
1.66
1.82
13.1
12.2
12.1
11.3
10.4
2.31
1.95
2.38
2.01
1.70
1.66
1.82
1.48
1.63
1.79
KW
2.06
2.27
2.48
2.03
2.23
2.44
2.00
2.21
2.43
1.94
MBH
36.6
35.0
33.5
30.1
28.7
27.2
26.7
25.3
23.9
21.6
1200
COP
5.29
4.62
4.05
4.41
3.81
3.31
3.95
3.39
2.93
3.26
KW
2.02
2.22
2.41
1.99
2.20
2.40
1.97
2.18
2.38
1.93
2.14
2.35
1.87
2.08
2.29
1.84
2.03
2.21
20.7
19.7
15.9
14.5
13.2
13.6
12.4
11.2
2.83
2.47
2.47
2.06
1.71
2.13
1.77
1.47
2.13
2.32
1.88
2.06
2.24
1.86
2.04
2.22
HEATING PERFORMANCE DATA - 2.5 TON
PACKAGED UNIT MODEL NO. PHE4A3021
AIR TEMP.
ENTERING
OUTDOOR COIL
60
47
40
30
17
10
AIR TEMP.
ENTERING
INDOOR COIL
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
Johnson Controls Unitary Products
MBH
34.6
33.3
32.0
29.1
27.7
26.2
25.5
24.3
23.0
21.2
800
COP
4.82
4.19
3.67
4.13
3.55
3.07
3.69
3.15
2.71
3.17
KW
2.10
2.32
2.55
2.06
2.27
2.49
2.02
2.25
2.48
1.95
MBH
35.6
34.2
32.8
29.6
28.2
26.7
26.1
24.8
23.5
21.4
ID CFM
1000
COP
5.05
4.40
3.86
4.27
3.68
3.19
3.82
3.27
2.82
3.22
20.3
19.3
16.3
14.3
12.4
13.7
12.7
11.7
2.74
2.38
2.55
2.00
1.55
2.20
1.84
1.54
2.16
2.37
1.86
2.10
2.33
1.81
2.01
2.21
20.5
19.5
16.1
14.5
12.8
13.6
12.5
11.4
2.78
2.42
2.51
2.03
1.63
2.16
1.81
1.51
11
5005568-YTG-H-1017
HEATING PERFORMANCE DATA - 3 TON
PACKAGED UNIT MODEL NO. PHE4B3621
AIR TEMP.
ENTERING
OUTDOOR COIL
AIR TEMP.
ENTERING
INDOOR COIL
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
47
40
30
17
10
MBH
41.6
39.9
38.2
35.3
33.8
32.3
31.5
30.1
28.7
26.8
25.3
23.9
20.1
18.7
17.3
17.6
16.1
14.7
1000
COP
4.67
4.08
3.58
4.14
3.59
3.13
3.76
3.26
2.84
3.29
2.82
2.43
2.54
2.16
1.84
2.28
1.90
1.59
KW
2.60
2.86
3.11
2.49
2.75
3.01
2.45
2.70
2.95
2.38
2.62
2.87
2.31
2.52
2.74
2.25
2.48
2.70
MBH
42.7
40.9
39.1
35.8
34.2
32.7
32.0
30.5
29.1
27.0
25.6
24.1
20.3
18.4
16.5
17.6
16.3
14.9
ID CFM
1200
COP
4.87
4.25
3.73
4.23
3.67
3.21
3.83
3.33
2.91
3.31
2.85
2.47
2.54
2.11
1.75
2.26
1.89
1.59
KW
2.56
2.81
3.06
2.47
2.72
2.97
2.44
2.68
2.92
2.38
2.62
2.86
2.33
2.54
2.76
2.28
2.50
2.72
MBH
43.8
41.9
40.0
36.3
34.7
33.0
32.4
31.0
29.5
27.2
25.8
24.4
20.4
18.0
15.7
17.7
16.4
15.0
1400
COP
5.08
4.42
3.88
4.33
3.76
3.29
3.90
3.40
2.97
3.33
2.88
2.50
2.54
2.06
1.65
2.23
1.89
1.60
KW
2.52
2.77
3.01
2.45
2.69
2.93
2.42
2.66
2.90
2.39
2.62
2.84
2.35
2.56
2.77
2.31
2.52
2.74
MBH
49.1
46.9
44.7
40.7
38.5
36.3
35.7
33.4
31.1
27.9
26.4
25.0
22.0
19.8
17.5
17.0
16.0
14.9
ID CFM
1400
COP
4.36
3.83
3.38
3.75
3.27
2.86
3.31
2.82
2.41
2.65
2.30
2.00
2.13
1.76
1.45
1.65
1.44
1.26
KW
3.29
3.58
3.86
3.16
3.44
3.71
3.15
3.46
3.77
3.08
3.36
3.64
3.02
3.28
3.53
3.01
3.24
3.46
MBH
50.1
47.8
45.4
41.2
39.0
36.8
36.1
33.6
31.1
30.3
27.0
23.8
22.5
19.6
16.7
16.4
15.3
14.1
1600
COP
4.33
3.82
3.38
3.68
3.22
2.83
3.22
2.75
2.35
2.76
2.27
1.86
2.08
1.68
1.33
1.51
1.31
1.14
KW
3.38
3.65
3.92
3.27
3.54
3.80
3.27
3.57
3.87
3.20
3.47
3.74
3.16
3.41
3.65
3.16
3.38
3.60
HEATING PERFORMANCE DATA - 3.5 TON
PACKAGED UNIT MODEL NO. PHE4B4221
AIR TEMP.
ENTERING
OUTDOOR COIL
60
47
40
30
17
10
12
AIR TEMP.
ENTERING
INDOOR COIL
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
MBH
48.1
46.0
43.9
40.1
38.0
35.9
35.3
33.2
31.1
25.5
25.8
26.1
21.6
20.0
18.4
17.6
16.7
15.8
1200
COP
4.38
3.84
3.38
3.83
3.32
2.89
3.41
2.90
2.47
2.52
2.32
2.16
2.19
1.86
1.57
1.80
1.58
1.39
KW
3.21
3.50
3.79
3.06
3.34
3.63
3.02
3.35
3.67
2.95
3.24
3.53
2.87
3.14
3.41
2.85
3.09
3.32
Johnson Controls Unitary Products
5005568-YTG-H-1017
HEATING PERFORMANCE DATA - 4 TON
PACKAGED UNIT MODEL NO. PHE4B4821
AIR TEMP.
ENTERING
OUTDOOR COIL
AIR TEMP.
ENTERING
INDOOR COIL
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
47
40
30
17
10
MBH
56.5
54.9
53.3
48.4
46.7
45.0
43.3
40.5
37.8
37.5
35.2
32.9
28.4
27.2
26.0
25.8
24.1
22.4
1400
COP
4.87
4.29
3.80
4.33
3.77
3.32
3.94
3.36
2.88
3.50
2.93
2.47
2.71
2.33
2.02
2.53
2.13
1.80
KW
3.39
3.74
4.09
3.27
3.62
3.97
3.21
3.52
3.84
3.13
3.51
3.88
3.06
3.41
3.76
2.98
3.30
3.62
MBH
57.8
56.0
54.2
49.2
47.4
45.6
43.8
41.7
39.7
37.0
34.7
32.3
28.2
27.0
25.9
25.5
24.0
22.6
ID CFM
1600
COP
4.95
4.37
3.89
4.37
3.82
3.36
3.96
3.44
3.00
3.40
2.88
2.45
2.66
2.30
2.00
2.43
2.09
1.80
KW
3.41
3.74
4.07
3.29
3.62
3.96
3.23
3.55
3.86
3.18
3.52
3.86
3.09
3.43
3.77
3.05
3.36
3.66
MBH
59.0
57.0
55.1
49.9
48.1
46.2
44.3
42.9
41.5
36.6
34.2
31.8
28.0
26.9
25.8
25.1
24.0
22.9
1800
COP
5.03
4.46
3.98
4.42
3.87
3.41
3.98
3.51
3.12
3.31
2.83
2.42
2.61
2.27
1.99
2.34
2.05
1.81
KW
3.43
3.74
4.05
3.30
3.63
3.95
3.25
3.57
3.89
3.23
3.53
3.84
3.13
3.46
3.79
3.12
3.41
3.70
MBH
71.2
68.4
65.5
58.7
56.5
54.3
52.8
50.4
48.1
38.2
37.9
37.7
32.5
30.5
28.5
29.9
28.2
26.5
ID CFM
1800
COP
4.54
3.98
3.51
3.93
3.44
3.03
3.61
3.13
2.73
2.77
2.49
2.25
2.41
2.04
1.74
2.21
1.90
1.65
KW
4.59
5.03
5.46
4.36
4.80
5.25
4.28
4.71
5.13
4.03
4.46
4.88
3.94
4.36
4.78
3.96
4.32
4.69
MBH
72.2
69.1
66.1
59.0
56.8
54.6
53.0
51.1
49.1
38.2
36.3
34.4
35.4
33.4
31.5
29.8
28.0
26.2
2000
COP
4.57
4.02
3.56
3.88
3.42
3.03
3.54
3.13
2.77
2.68
2.35
2.06
2.48
2.16
1.88
2.12
1.83
1.59
KW
4.61
5.03
5.44
4.44
4.86
5.26
4.38
4.78
5.17
4.15
4.51
4.88
4.17
4.53
4.88
4.11
4.46
4.82
HEATING PERFORMANCE DATA - 5 TON
PACKAGED UNIT MODEL NO. PHE4B6021
AIR TEMP.
ENTERING
OUTDOOR COIL
60
47
40
30
17
10
AIR TEMP.
ENTERING
INDOOR COIL
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
60
70
80
Johnson Controls Unitary Products
MBH
70.2
67.6
65.0
58.4
56.3
54.1
52.5
49.8
47.0
38.2
39.5
40.9
29.5
27.6
25.6
30.1
28.4
26.8
1600
COP
4.50
3.94
3.48
3.98
3.46
3.03
3.69
3.15
2.70
2.87
2.63
2.45
2.33
1.92
1.59
2.31
1.98
1.71
KW
4.55
5.01
5.46
4.28
4.76
5.23
4.17
4.63
5.09
3.89
4.38
4.88
3.71
4.19
4.69
3.79
4.19
4.57
13
5005568-YTG-H-1017
&2,/*8$5'
+,*+92/7$*(
23(1,1*´
&
+,*+92/7$*(
23(1,1*´
+($76(&7,21
$&&(663$1(/
&2035(6625
$&&(663$1(/
&21'(16$7(
'5$,1
%/2:(5
$&&(66
3$1(/
%
$
/2:92/7$*(23(1,1*´
&21752/+($7
$&&(663$1(/
$
UNIT DIMENSIONS
Model
A
51-1/4
51-1/4
51-1/4
51-1/4
51-1/4
51-1/4
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
PHE4B4821
PHE4B6021
Dimensions
B
35-3/4
35-3/4
45-3/4
45-3/4
45-3/4
45-3/4
C
47
49
49
49
53
55
UNIT CLEARANCES
Direction
Top1
Side Opposite Ducts
Duct Panel
Distance (in.)
36
36
0
Direction
Right Side
Left Side
Bottom 2, 3
Distance (in.)
36
24
1
1. Minimum Clearance of 1inch all sides of supply air duct for the first 3 foot of duct for 20 & 25 kW., zero inches there after. For all other heaters, zero inch clearance
all sides for entire length of duct.
2. Units must be installed outdoors. Over hanging structure or shrubs should not obscure outdoor air discharge outlet.
3. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
Note: For units applied with a roof curb, the minimum clearance may be reduced from 1 inch to 1/2 inch? between combustible roof curb material and this supply air
duct.
ELECTRIC HEAT MINIMUM SUPPLY AIR
Model
Voltage
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
PHE4B4821
PHE4B6021
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
208/230-1-60
14
Minimum Blower Speed for Electric Heat
Heater kW
2
5
8
10
13
15
18
20
25
Low #1 Low #1 Med. Low #2 Med. #3
Med. Hi #4
----Low #1 Low #1 Low #1 Med. Low #2 Med #3
High #5
---Low #1 Low #1 Low #1
Low #1 Med. Low #2 High #5
----Low #1 Low #1
Low #1
Low #1 Med. Low #2 Med. Hi #4
High #5
--Low #1 Low #1
Low #1
Low #1
Low #1 Med. Low #2 Med. High #4
--Low #1 Low #1
Low #1
Low #1
Low #1
Low #1
Med. Low #2 Med. High #4
Johnson Controls Unitary Products
5005568-YTG-H-1017
INDOOR BLOWER SPECIFICATIONS
Motor
Model
HP
1/2
1/2
1/2
3/4
3/4
1
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
PHE4B4821
PHE4B6021
RPM
Variable
Variable
Variable
Variable
Variable
Variable
EFF.
0.8
0.8
0.8
0.8
0.8
0.8
SF
1.0
1.0
1.0
1.0
1.0
1.0
Frame
48
48
48
48
48
48
COOLING SOUND PERFORMANCE
Model
(Tons)
Sound Rating1
dB (A)
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
PHE4B4821
PHE4B6021
72.4
68.7
73.2
73.6
125
61.8
58.3
61.8
62.4
250
60.5
58.8
63.2
59.0
74.0
74.1
62.0
65.9
62.0
61.8
125
64.7
57.5
60.1
62.4
66.0
61.6
250
59.2
58.0
62.5
58.3
63.3
59.4
Octave Band Centerline Frequency (Hz)
500
1000
2000
63.1
62.5
57.1
56.6
57.3
54.0
60.5
64.4
58.9
61.5
64.9
60.3
60.9
60.8
64.7
63.5
60.1
58.7
4000
51.8
48.4
53.4
55.8
8000
44.0
43.0
45.9
50.6
56.6
55.5
49.2
48.3
4000
49.2
47.6
53.0
54.4
56.4
55.1
8000
43.2
49.7
46.0
47.9
48.9
51.4
1. Rated in accordance with AHRI Standard 270.
HEATING SOUND PERFORMANCE
Model
(Tons)
Sound Rating1
dB (A)
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
PHE4B4821
PHE4B6021
70.3
69.0
72.8
73.6
74.6
73.7
Octave Band Centerline Frequency (Hz)
500
1000
2000
59.8
58.1
54.3
58.0
63.8
53.2
60.4
64.5
58.8
61.5
65.7
59.7
61.1
64.6
60.2
60.5
63.6
58.7
1. Rated in accordance with AHRI Standard 270.
Johnson Controls Unitary Products
15
5005568-YTG-H-1017
ELECTRICAL DATA - 208/230-1-60 SINGLE SOURCE POWER
SINGLE POINT CONNECTION KIT REQUIRED
Model
Compressor
RLA
LRA
MCC
OD Fan Blower
Motor Motor
FLA
FLA
PHE4A024
10
62
16
0.7
3.8
PHE4A030
14
73
22
0.6
3.8
PHE4B036
17
79
26
1.7
3.8
PHE4B042
18
112
28
1.7
5.4
PHE4B048
22
117
34
1.7
5.4
PHE4B060
24
144
38
1.7
7
1.
2.
3.
4.
16
Electric Heat Option
Heater Kit4
none
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
none
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
none
6HK16500206
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
none
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
none
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
none
6HK16500506
6HK16500806
6HK16501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
Heater kW
208
-1.8
3.6
5.8
7.2
9.4
-1.8
3.6
5.8
7.2
9.4
10.8
-1.8
3.6
5.8
7.2
9.4
10.8
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
230
-2.2
4.4
7.1
8.8
11.5
-2.2
4.4
7.1
8.8
11.5
13.2
-2.2
4.4
7.1
8.8
11.5
13.2
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
Stages
-1
1
1
1
2
-1
1
1
1
2
2
-1
1
1
1
2
2
-1
1
1
2
2
2
2
-1
1
1
2
2
2
2
-1
1
1
2
2
2
2
Heater Amps
208
-8.7
17.3
27.9
34.6
45.2
-8.7
17.3
27.9
34.6
45.2
51.9
-8.7
17.3
27.9
34.6
45.2
51.9
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
-17.3
27.9
34.6
45.2
51.9
62.5
69.2
230
-9.6
19.1
30.9
38.3
50.0
-9.6
19.1
30.9
38.3
50.0
57.4
-9.6
19.1
30.9
38.3
50.0
57.4
-19.1
30.9
38.3
50.0
57.4
69.1
76.5
-19.1
30.9
38.3
50.0
57.4
69.1
76.5
-19.1
30.9
38.3
50.0
57.4
69.1
76.5
MCA1
Max Fuse2 or
Amps
Breaker Size3
208
17.4
28.2
39.0
52.2
60.6
73.9
22.0
32.8
43.7
56.9
65.3
78.5
86.9
26.4
37.2
48.0
61.2
69.6
82.9
91.3
29.5
51.1
64.3
72.7
86.0
94.4
107.6
116.0
34.4
56.0
69.2
77.6
90.8
99.3
112.5
120.9
39.2
60.8
74.1
82.5
95.7
104.1
117.3
125.7
230
17.4
29.3
41.3
56.0
65.2
79.9
22.0
34.0
45.9
60.6
69.9
84.5
93.8
26.4
38.3
50.3
65.0
74.2
88.9
98.1
29.5
53.4
68.1
77.3
92.0
101.2
115.9
125.1
34.4
58.3
72.9
82.2
96.9
106.1
120.8
130.0
39.2
63.1
77.8
87.0
101.7
110.9
125.6
134.9
208
25
35
40
60
70
80
35
40
50
60
70
80
90
40
50
60
70
70
90
100
45
60
70
80
90
100
110
125
50
70
80
90
100
100
125
125
60
80
90
90
100
110
125
150
230
25
35
45
60
70
80
35
45
50
70
70
90
100
40
50
60
70
80
90
100
45
60
70
80
100
110
125
150
50
70
80
90
100
110
125
150
60
80
90
100
110
125
150
150
MCA = Minimum Circuit Ampacity.
Maximum Over Current Protection per standard UL 1995.
Fuse or HACR circuit breaker size installed at factory or field installed.
Single Point Connection Kit required.
Johnson Controls Unitary Products
5005568-YTG-H-1017
ELECTRICAL DATA FOR - 208-1-60 MULTI SOURCE POWER
Model
Compressor
RLA LRA MCC
OD Fan Blower
Motor Motor
FLA
FLA
Multi Source: Compressor
Circuit and Heat Circuits
A24
10
45
14
0.7
3.8
A30
14
57
15
0.6
3.8
B36
17
78
23
1.7
3.8
B42
18
112
28
1.7
5.4
B48
22
117
34
1.7
5.4
Electric Heat Option
Multi Source
Heater kW
Heater Amps
Heater Kit
Stages
208
208
208 208 208 208 208 208 208 208
Circuit #1 Compressor Circuit
Circuit #2 Heat
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Multi Source:
Amps
Amps
Amps
Amps
Circuit #2 Heat
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK26501306
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK26501306
6HK26501506
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK26501306
6HK26501506
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
-1.8
3.6
5.8
7.2
9.4
9.4
-1.8
3.6
5.8
7.2
9.4
10.8
9.4
10.8
-1.8
3.6
5.8
7.2
9.4
10.8
9.4
10.8
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
9.4
10.8
13.0
14.4
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
9.4
10.8
13.0
14.4
Circuit #3 Heat
--1
8.7
1
17.3
1
27.9
1
34.6
2
45.2
1
45.2
--1
8.7
1
17.3
1
27.9
1
34.6
2
45.2
2
51.9
1
45.2
1
51.9
--1
8.7
1
17.3
1
27.9
1
34.6
2
45.2
2
51.9
1
45.2
2
51.9
1
-1
17.3
1
27.9
1
34.6
2
45.2
2
51.9
2
62.5
2
69.2
1
45.2
1
51.9
1
62.5
1
69.2
--1
17.3
1
27.9
1
34.6
2
45.2
2
51.9
2
62.5
2
69.2
1
45.2
1
51.9
1
62.5
2
69.2
Circuit #1
17.4 25
17.4 25
17.4 25
17.4 25
17.4 25
17.4 25
17.4 25
22.0 35
22.0 35
22.0 35
22.0 35
22.0 35
22.0 35
22.0 35
22.0 35
22.0 35
26.4 40
26.4 40
26.4 40
26.4 40
26.4 40
26.4 40
26.4 40
26.4 40
26.4 40
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
29.5 45
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
34.4 50
Circuit #2
--10.8 15
21.6 25
34.9 40
43.3 45
37.7 40
56.5 60
--10.8 15
21.6 25
34.9 40
43.3 45
37.7 40
43.3 50
56.5 60
64.9 70
--10.8 15
21.6 25
34.9 40
43.3 45
37.7 40
43.3 50
56.5 60
64.9 70
--21.6 25
34.9 40
43.3 45
56.5 40
43.3 50
52.1 40
43.3 45
56.5 60
64.9 70
78.1 80
86.5 90
--21.6 25
34.9 40
43.3 45
56.5 40
43.3 50
52.1 40
43.3 45
56.5 60
64.9 70
78.1 80
86.5 90
Circuit #3
----------18.8 20
------------18.8 20
21.6 25
--------------18.8 20
21.6 25
------------21.6 20
21.6 25
26.0 40
43.3 45
----------------21.6 20
21.6 25
26.0 40
43.3 45
---------
Circuit #4
---------------------------------------------------------------------------------------------------
For notes, see end of table on next page.
Johnson Controls Unitary Products
17
5005568-YTG-H-1017
ELECTRICAL DATA FOR - 208-1-60 MULTI SOURCE POWER (Continued)
Model
Compressor
RLA LRA MCC
OD Fan Blower
Motor Motor
FLA
FLA
Multi Source: Compressor
Circuit and Heat Circuits
B60
24
144
38
1.7
7.0
Electric Heat Option
Multi Source
Heater kW
Heater Amps
Heater Kit
Stages
208
208
208 208 208 208 208 208 208 208
Circuit #1 Compressor Circuit
Circuit #2 Heat
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Multi Source:
Amps
Amps
Amps
Amps
Circuit #2 Heat
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
6HK16502506
6HK26502506
-3.6
5.8
7.2
9.4
10.8
13.0
14.4
9.4
10.8
13.0
14.4
18.0
18.0
Circuit #3 Heat
--1
17.3
1
27.9
1
34.6
2
45.2
2
51.9
2
62.5
2
69.2
1
45.2
1
51.9
1
62.5
1
69.2
3
86.5
1
86.5
Circuit #1
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
39.2 60
Circuit #2
--21.6 25
34.9 40
43.3 45
56.5 40
43.3 50
52.1 40
43.3 45
56.5 60
64.9 70
78.1 80
86.5 90
43.3 45
108.2 110
Circuit #3
--------21.6 20
21.6 25
26.0 40
43.3 45
--------43.3 45
---
Circuit #4
------------------------21.6 25
---
1. MCA = Minimum Circuit Ampacity.
2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse.
ELECTRICAL DATA FOR 230-1-60 MULTI SOURCE POWER
Model
Compressor
RLA LRA MCC
OD Fan Blower
Motor Motor
FLA
FLA
Multi Source: Compressor
Circuit and Heat Circuits
A24
10
45
14
0.7
3.8
A30
14
57
15
0.6
3.8
B36
17
78
23
1.7
3.8
Electric Heat Option
Multi Source
Heater kW
Heater Amps
Heater Kit
Stages
230
230
230 230 230 230 230 230 230 230
Circuit #1 Compressor Circuit
Circuit #2 Heat
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Multi Source:
Amps
Amps
Amps
Amps
Circuit #2 Heat
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK26501306
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK26501306
6HK26501506
none
6HK(0,1)6500206
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK26501306
6HK26501506
-2.2
4.4
7.1
8.8
11.5
11.5
-2.2
4.4
7.1
8.8
11.5
13.2
11.5
13.2
-2.2
4.4
7.1
8.8
11.5
13.2
11.5
13.2
Circuit #3 Heat
--1
9.6
1
19.1
1
30.9
1
38.3
2
50.0
1
50.0
--1
9.6
1
19.1
1
30.9
1
38.3
2
50.0
2
57.4
1
50.0
1
57.4
--1
9.6
1
19.1
1
30.9
1
38.3
2
50.0
2
57.4
1
50.0
2
57.4
Circuit #1
17.4
25
17.4
25
17.4
25
17.4
25
17.4
25
17.4
25
17.4
25
22.0
35
22.0
35
22.0
35
22.0
35
22.0
35
22.0
35
22.0
35
22.0
35
22.0
35
26.4
40
26.4
40
26.4
40
26.4
40
26.4
40
26.4
40
26.4
40
26.4
40
26.4
40
Circuit #2
--12.0
15
23.9
25
38.6
40
47.8
50
41.7
45
62.5
70
--12.0
15
23.9
25
38.6
40
47.8
50
41.7
45
47.8
50
62.5
70
71.7
80
--12.0
15
23.9
25
38.6
40
47.8
50
41.7
45
47.8
50
62.5
70
71.7
80
Circuit #3
----------20.8
25
------------20.8
25
23.9
25
--------------20.8
25
23.9
25
-----
Circuit #4
---------------------------------------------------
For notes, see end of table on next page.
18
Johnson Controls Unitary Products
5005568-YTG-H-1017
ELECTRICAL DATA FOR 230-1-60 MULTI SOURCE POWER
Model
Compressor
RLA LRA MCC
OD Fan Blower
Motor Motor
FLA
FLA
Multi Source: Compressor
Circuit and Heat Circuits
B42
18
112
28
1.7
5.4
B48
22
117
34
1.7
5.4
B60
24
144
38
1.7
7.0
Electric Heat Option
Multi Source
Heater kW
Heater Amps
Heater Kit
Stages
230
230
230 230 230 230 230 230 230 230
Circuit #1 Compressor Circuit
Circuit #2 Heat
MCA1
MCA1
MCA1
MCA1
MOP2
MOP2
MOP2
MOP2
Multi Source:
Amps
Amps
Amps
Amps
Circuit #2 Heat
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
none
6HK(0,1)6500506
6HK(0,1)6500806
6HK(0,1)6501006
6HK16501306
6HK16501506
6HK16501806
6HK16502006
6HK26501306
6HK26501506
6HK26501806
6HK26502006
6HK16502506
6HK26502506
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
11.5
13.2
15.9
17.6
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
11.5
13.2
15.9
17.6
-4.4
7.1
8.8
11.5
13.2
15.9
17.6
11.5
13.2
15.9
17.6
22.0
22.0
Circuit #3 Heat
1
-1
19.1
1
30.9
1
38.3
2
50.0
2
57.4
2
69.1
2
76.5
1
50.0
1
57.4
1
69.1
1
76.5
--1
19.1
1
30.9
1
38.3
2
50.0
2
57.4
2
69.1
2
76.5
1
50.0
1
57.4
1
69.1
2
76.5
--1
19.1
1
30.9
1
38.3
2
50.0
2
57.4
2
69.1
2
76.5
1
50.0
1
57.4
1
69.1
1
76.5
3
95.7
1
95.7
Circuit #1
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
29.5
45
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
34.4
50
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
39.2
60
Circuit #2
--23.9
25
38.6
40
47.8
50
62.5
45
47.8
50
57.6
45
47.8
50
62.5
70
71.7
80
86.4
90
95.7 100
--23.9
25
38.6
40
47.8
50
62.5
45
47.8
50
57.6
45
47.8
50
62.5
70
71.7
80
86.4
90
95.7 100
--23.9
25
38.6
40
47.8
50
62.5
45
47.8
50
57.6
45
47.8
50
62.5
70
71.7
80
86.4
90
95.7 100
47.8
50
119.6 125
Circuit #3
--------23.9
25
23.9
25
28.8
45
47.8
50
----------------23.9
25
23.9
25
28.8
45
47.8
50
----------------23.9
25
23.9
25
28.8
45
47.8
50
--------47.8
50
---
Circuit #4
------------------------------------------------------------------------23.9
25
---
1. MCA = Minimum Circuit Ampacity.
2. MOP = Maximum Over Current Protection device; must be HACR type circuit breaker or time delay fuse.
SINGLE POINT WIRING KIT
Single Point Kit P/N
Unit Model Number
Breaker Size
Heat Kit
S1-2SPWK006
S1-2SPWK002
S1-2SPWK007
S1-2SPWK003
S1-2SPWK004
S1-2SPWK005
PHE4A24
PHE4A30
PHE4B36
PHE4B42
PHE4B48
PHE4B60
25 Amp
35 Amp
40 Amp
45 Amp
50 Amp
60 Amp
up to 13 kW
up to 15 kW
up to 15 kW
up to 20 kW
up to 20 kW
up to 20 kW
Johnson Controls Unitary Products
19
5005568-YTG-H-1017
"D"
CENTER OF
GRAVITY
COMPRESSOR
"C"
"A"
FRONT
OF UNIT
X
Y
"B"
A0295-001-TG
WEIGHTS & DIMENSIONS
Model
Weight (lbs.)
Center of Gravity
4 Point Load Location (lbs.)
PHE4A2421
PHE4A3021
PHE4B3621
PHE4B4221
Shipping
382
397
453
476
Operating
377
392
448
471
X
29
29
29
30
Y
15
15
15
15
A
133
127
158
164
B
88
101
108
119
C
86
99
101
111
D
75
70
86
82
PHE4B4821
PHE4B6021
501
528
496
523
29
30
15
15
168
177
130
136
119
128
84
87
20
Johnson Controls Unitary Products
5005568-YTG-H-1017
AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION
Model
24
30
36
42
48
60
1.
2.
3.
4.
5.
Motor Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
791
849
927
999
1176
768
941
1026
1112
1176
1108
1283
1362
1403
1623
0.2
SCFM
739
801
882
958
1143
715
898
987
1076
1143
1050
1225
1308
1347
1569
0.3
SCFM
727
789
871
948
1133
702
887
977
1067
1133
984
1168
1252
1290
1519
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
1436
1544
1573
1681
1935
1620
1694
1798
1835
2146
1730
1858
2054
2195
2445
1382
1492
1523
1640
1887
1564
1630
1722
1758
2085
1682
1807
1998
2144
2388
1342
1455
1484
1599
1834
1517
1580
1669
1703
2025
1628
1749
1934
2098
2306
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
668
614
564
518
733
683
635
590
819
772
727
683
899
855
812
769
1092
1052
1014
976
642
586
536
490
836
789
744
701
930
886
844
802
1023
982
942
902
1092
1052
1014
976
921
857
791
726
1115
1054
993
924
1199
1142
1079
1015
1235
1177
1118
1058
1470
1418
1362
1306
1304
1416
1445
1557
1788
1466
1530
1620
1653
1960
1592
1710
1890
2049
2293
1262
1376
1408
1517
1743
1418
1482
1572
1604
1872
1552
1667
1843
2003
2235
1220
1336
1367
1478
1701
1360
1430
1527
1558
1862
1517
1629
1801
1955
2178
1179
1294
1327
1436
1651
1308
1380
1480
1511
1798
1479
1589
1757
1883
2129
0.8
SCFM
439
512
607
696
908
409
625
729
832
908
660
860
979
995
1.0
SCFM
279
356
456
549
771
248
475
584
692
771
528
733
905
869
1246
1131
1248
1279
1393
1591
1206
1292
1413
1442
1735
1439
1546
1710
1868
2077
1125
1035
1156
1183
1307
1471
1002
1116
1280
1304
1609
1359
1460
1616
1838
1973
Airflow tested with dry coil conditions, without air filters, at 230 volts.
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
21
5005568-YTG-H-1017
AIRFLOW PERFORMANCE - BOTTOM DUCT APPLICATION
Model
24
30
36
42
48
60
1.
2.
3.
4.
5.
22
Motor Speed
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
0.1
SCFM
791
851
938
1069
1207
768
943
1039
1190
1207
1127
1306
1354
1397
1634
0.2
SCFM
755
813
905
978
1182
730
911
1013
1099
1182
1082
1265
1315
1348
1591
0.3
SCFM
745
801
890
969
1185
720
900
998
1090
1185
1021
1205
1259
1297
1548
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
Low (1)
Low/Medium (2)
Medium (3)
Medium/High (4)
High (5)
1455
1566
1565
1675
1946
1598
1663
1789
1931
2131
1655
1766
1987
2114
2369
1414
1532
1530
1641
1909
1548
1612
1733
1814
2058
1612
1720
1933
2050
2308
1379
1492
1491
1606
1863
1502
1568
1670
1808
1998
1596
1667
1861
2047
2249
External Static Pressure (Inches WC)
0.4
0.5
0.6
0.7
SCFM
SCFM
SCFM
SCFM
686
632
585
537
743
692
648
603
836
788
745
702
921
872
830
787
1122
1106
1066
1023
659
604
555
508
847
800
759
716
949
905
865
825
1048
1002
963
923
1122
1106
1066
1023
952
889
825
759
1154
1094
1029
963
1212
1153
1093
1024
1256
1195
1135
1077
1497
1446
1382
1309
1335
1455
1458
1578
1815
1454
1522
1650
1736
1949
1531
1629
1817
1974
2183
1294
1416
1419
1535
1771
1410
1476
1596
1673
1892
1461
1632
1820
1899
2126
1254
1372
1381
1495
1721
1362
1422
1578
1650
1840
1462
1539
1715
1889
2088
1212
1333
1336
1455
1654
1307
1370
1535
1597
1788
1429
1537
1725
1920
2034
0.8
SCFM
455
524
623
713
952
424
641
748
853
952
689
892
990
1014
1.0
SCFM
290
367
465
565
810
258
490
596
713
810
549
751
920
888
1250
1160
1280
1290
1412
1595
1251
1297
1483
1519
1728
1391
1498
1651
1866
1990
1131
1056
1174
1198
1326
1477
1139
1152
1379
1362
1608
1316
1421
1504
1758
1902
Airflow tested with dry coil conditions, without air filters, at 230 volts
Applications above 0.8" w.c. external static pressure are not recommended.
Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.
Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.
Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.
Johnson Controls Unitary Products
5005568-YTG-H-1017
ADDITIONAL STATIC RESISTANCE
Size (Tons)
24 (2.0)
30 (2.5)
36 (3.0)
42 (3.5)
48 (4.0)
60 (5.0)
CFM
500
600
700
800
900
1000
1100
1200
700
800
900
1000
1100
1200
1300
700
800
900
1000
1100
1200
1300
1400
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
BOTTOM DUCT DIMENSIONS (Inches)
1
Wet Indoor Coil Economizer
0.01
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.02
0.03
0.04
0.05
0.06
0.07
0.07
0.08
0.09
0.09
0.00
0.00
0.00
0.01
0.01
0.01
0.01
0.02
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.00
0.01
0.01
0.01
0.01
0.02
0.03
0.04
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.02
0.02
0.02
0.03
0.04
0.04
0.04
0.04
0.05
0.05
Filter/Frame Kit
0.01
0.02
0.04
0.06
0.08
0.10
0.13
0.16
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.04
0.06
0.08
0.10
0.13
0.16
0.17
0.18
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.04
0.04
0.05
0.05
0.06
0.07
0.08
0.09
0.10
0.11
'
9,(:/22.,1*83
$7%277202)81,7
&
$
5(7851
$,5'8&7
(
%
+2/(´ IRUKLJKYROWDJH
$
+2/(´ IRU
ORZYROWDJH
6833/<
$,5'8&7
)
Model
24, 30
36, 42, 48, 60
A
10
14
B
21.5
13.5
$
C
5
5
D
4.5
3.5
E
47.5
47.5
F
32
42
REAR DUCT DIMENSIONS (Inches)
127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI
HOHFWULFDOOLQHV
6833/<
$,5'8&7
5(7851
$,5'8&7
$
Model
24, 30
36, 42, 48, 60
$
%
A
9.6
13.6
$
B
22
14
1. The pressure drop through the economizer is greater for 100% outdoor air
than for 100% return air. If the resistance of the return air duct is less than
0.25 IWG, the unit will deliver less CFM during full economizer operation.
Filter pressure drop based on standard filter media tested at velocities not
to exceed 300 ft/min.
Johnson Controls Unitary Products
23
5005568-YTG-H-1017
UNIT TYPICAL DUCT APPLICATIONS
ROOF CURB
INSTALLATION
REAR DUCT
ROOF CURB
INSTALLATION
BOTTOM DUCT
SLAB ON
GROUND
INSTALLATION
A0324-001
UNIT TYPICAL SLAB ON GROUND INSTALLATION
TO POWER SUPPLY
RETURN
AIR DUCT
SUPPLY
AIR DUCT
FIELD-SUPPLIED
DISCONNECT
SWITCH
CONDENSATE
DRAIN
CONTROL WIRING TO
INDOOR THERMOSTAT
24
A0390-001
Johnson Controls Unitary Products
5005568-YTG-H-1017
UNIT TYPICAL ROOF CURB INSTALLATION
ROOF
CONDENSATE
DRAIN
ROOF CURB
FIELD-SUPPLIED
DISCONNECT
SWITCH
TO POWER SUPPLY
CONTROL WIRING TO
INDOOR THERMOSTAT
RETURN
AIR DUCT
Johnson Controls Unitary Products
SUPPLY
AIR DUCT
A0389-001
25
NOTES
Subject to change without notice. Published in U.S.A.
Copyright © 2017 by Johnson Controls, Inc. All rights reserved.
York International Corp.
5005 York Drive
Norman, OK 73069
5005568-YTG-H-1017
Supersedes: 5005568-YTG-G-0717
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project