York PHG4 User manual

York PHG4 User manual

TECHNICAL GUIDE

SINGLE PACKAGE HEAT PUMP / GAS HEAT 14 SEER – R-410A – 208/230V - 1 PHASE 2 THRU 5 NOMINAL TONS 50 THRU 125 MBH HEAT INPUT

MODELS: PHG4*24 THRU 60 Due to continuous product improvement, specifications are subject to change without notice.

Visit us on the web at

www.upgnet.com and www.york.com

Additional rating information can be found at:

www.ahridirectory.org

WARRANTY SUMMARY*

Extended 10-Years limited parts and compressor warranty Lifetime gas heat exchanger warranty with registration.

* Extended warranty requires online registration within 90 days of purchase for replacement or closing for new home purchase. See limited warranty certificate in User’s Information Manual for details.

5127524-YTG-E-1017

DESCRIPTION

These packaged duel fuel cooling/gas heating/heat pumps are designed for outdoor installation. Only utility and duct connections are required at the point of installation.

• • • • • • • •

FEATURES

Operating Efficiency

- All PHG4 models provide a minimum AFUE of 81.0% in gas heating and 14.0 SEER, 11.0 EER and 8.0 HSPF ratings for heat pump cooling/heating opera tion. All models meet California Low-Nox requirements of 40 ng/joule emission level for Air Quality Management Districts.

On Site Flexibility -

All model sizes use a compact design cabinet in one of two footprints. This provides installer flexi bility for placing the proper capacity unit on curbs or pads with the smallest footprint after the internal load has been determined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibil ity with less inventory.

Lower Installation Cost -

Installation time and costs are reduced by easy power and control wiring connections. The small base dimension means less space is required on the ground or roof. All units are completely wired, charged with R-410A refrigerant and tested prior to shipment. Test sta tions using a state-of-the-art computerized process system are used to insure product quality. Refrigerant charge and component part numbers are verified via computers during assembly. Vital run test statistics such as system pressure, motor currents, air velocity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit performance. Equal size side supply and return duct connections allow easy connection of ducts to match low crawl spaces without transition pieces.

Utility Connections Made Easy -

Gas and electric utility access provided through the bottom or the side of the unit. Utility connections can be made quickly and with a minimum amount of field labor. A field supplied and field installed elec trical disconnect switch must be installed.

Convertible Airflow Design -

The bottom duct openings are covered when they leave the factory, ready to be used for a side supply/side return application. If a bottom supply/bottom return application is desired, simply remove the two panels from the bottom of the unit and place them in the side supply/ side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.

Condensate Pan -

A corrosion-resistant, long-lasting, water tight pan is positioned below the indoor coil to collect and drain all condensate, preventing build-up of stagnant con densate. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality).

Condensate Drain -

The 3/4 inch NPT female connection is rigidly mounted to assure proper fit and leak tight seal.

Durable Finish -

The cabinet is made of G90 galvanized steel with a powder paint coating for appearance and protec tion. The pre-treated galvanized steel provides a better paint to-steel bond, which resists corrosion and rust creep. Pow der paint finish insures less fading when exposed to sunlight, and provides superior corrosion resistance (1000 hour salt spray tested).

Continued on next page.

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

5127524-YTG-E-1017 • • • • • • •

Full Perimeter Base Rails -

The easily removable base rails provide a solid foundation for the entire unit and protects the unit during shipment. The rails provide fork lift access from all sides, and rigging holes are also provided so that an over head crane can be used to place the units on a roof. On applications where the unit is placed on a pad, the base will keep the unit off the pad to deter corrosion. On applications where height is limited, the base rails may be removed by removing 2 screws in each corner.

More Attractive Appearance -

A single-piece top cover containing a top-discharge outdoor fan arrangement requires less square footage on installation and provides a wider vari ety of installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance.

Top Discharge -

The top-discharge outdoor fan does not disrupt neighboring areas or dry out vegetation surrounding the unit. The warm air from the top mounted fan is blown up and away from the structure and any landscaping. This allows compact location on multi-unit applications.

Outdoor Coil Grille -

All models utilize a stamped slotted design which provides superior impact protection against small objects during transit and after installation.

Low Operating Sound Level -

The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates noise. Isolator mounted compressor and the rippled fins of the outdoor coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound attenuation with its structural design. This design strategi cally places embossments in the pan for optimum strength and rigidity.

Fan System -

All models operate over a wide range of design conditions with a standard ECM indoor fan motor. These units easily match all types of applications and pro vide greater on-site flexibility to match comfort requirements. The cooling speed is factory-set and can be field-adjusted to a alternate speed. The heating speed is factory set to main tain mid point rise at the units heating input, but can be field adjusted. This allows maximum comfort conditions.

Simple Control Circuit -

A low voltage gas heat printed cir cuit board contains a status/diagnostic indicator light. Field thermostat wiring connects to color coded leads using twist on wire connectors. Cooling controls use contactor and relays for simple application and troubleshooting. Mate-n lock plug connectors are used. The electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.

• • • • • • • • • • • •

Controls -

Demand defrost curves are pre-loaded into the demand defrost control for optimized performance based on unit capabilities.

Protected Compressor -

The compressor is internally pro tected against high pressure and temperature. This is accomplished by the simultaneous operation of high pres sure internal relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur.

Pressure Switches -

A high pressure switch is standard in all units. When abnormal conditions are sensed through the pressure switch, the unit will lock out preventing any further operation until reset or problem is corrected.

Exclusive Coil Design -

Grooved copper tubes and enhanced aluminum fin construction improves heat transfer for maximum efficiency and durability for long-lasting durabil ity and efficient operation. Indoor coils use tin-coated copper tubing with aluminum fins for effective heat transfer.

Heat Exchangers -

Gas heat exchangers use corrosion resistant, stainless-steel tubular construction to provide long life, trouble-free operation. Gas heat exchangers are offered with lifetime warranties as standard with registration.

Post Purge Induced Draft Combustion -

Exhausts com bustion products from the heat exchanger upon completion of the heating cycle to prolong the heat exchanger life.

Spark To Burner Ignition -

No pilot assembly required, which provides more consistent ignition in gas heating mode. This ignition system is highly reliable, durable and eliminates nuisance lockouts.

Multi Port In-shot Burners -

No field adjustment is required to mix the air and gas for natural gas or propane use. These burners are constructed of high-grade corrosion-resistant, aluminumized steel.

Low Maintenance -

Long life, permanently lubricated out door and indoor fan motor bearings need no annual mainte nance, adding greater reliability to the unit. Slide-out blower assembly can be easily removed for cleaning.

Easy Service Access -

Individual access panels covering the electrical and gas controls, compressor, and blower sec tion makes servicing easy. Removing this panel will allow easy removal of the blower assembly for maintenance and ease of troubleshooting.

Replacement Parts -

The installer requires no special train ing to replace any of the components of these units and the number of new components have been reduced to minimize the inventory of unique parts.

Loss of Charge Switch -

All models include a loss of charge switch to provide safe shutdown of compressor.

2 Johnson Controls Unitary Products

5127524-YTG-E-1017

NOMENCLATURE

PHG 1 4 2 A 3 1. Model Family

PHG - packaged heat pump with gas heat, PCG - packaged A/C with gas heat, PCE - packaged A/C with electric heat, PHE - packaged heat pump with electric heat

24 4 050 5 2 6 X 7 6. Voltage-Phase-Frequency 1 8 5. Gas Heating Input BTU/Hr x 1000

050 = 50,000 BTU/Hr. input, blank = electric heat 2 = 208/230-1-60, 3=208/230-3-60, 4 = 460-3-60

A 9 2. Nominal Cooling Efficienc

y 4 = 14 SEER, 6 = 16 SEER, etc.

3. Cabinet Size

A = small 35 x 51, B = large 45 x 51

7. NOx Approval

X = low-NOx, blank = not low-NOx

8. Generation Level

1 = first generation

4. Nominal Air Conditioning Cooling Capacity

24 = Nominal Capacity, etc.

9. Revision Level

A = original release, B = second release

Examples:

PHG4B421002X1 is a dual fuel, 14 SEER, 3-1/2 ton, large cabinet, single-stage heat, 100,000 BTU gas heat, 230 volt, single phase, low-NOx model (first generation, first release)

COMPONENT LOCATION

FAN MOTOR OUTDOOR FAN COIL GUARD PANEL OUTDOOR COIL (Behind Panel) BLOWER MOTOR TXV INDOOR COIL INDOOR BLOWER COMPRESSOR REMOVABLE BASE RAILS

UNIT LIMITATIONS

Model

PHG4A24 PHG4A30 PHG4B36 PHG4B42 PHG4B48 PHG4B60

Unit Voltage

208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 CONTROL BOARD TRANSFORMER HIGH VOLTAGE CONTACTOR PRESSURE SWITCH DRAFT INDUCER BLOWER GAS HEAT EXCHANGER GAS VALVE BURNER ASSEMBLY A0444-001

Min

187 187 187 187 187 187

Unit Limitations Applied Voltage Max

252 252 252 252 252 252

Outdoor DB Temp Max (°F)

125 125 125 125 125 125 Johnson Controls Unitary Products 3

5127524-YTG-E-1017

ACCESSORIES

• • • •

Propane Conversion Kit (S1-1NP0702, S1-1NP0701) -

Kit includes burner orifices, gas valve conversion and installa tion instructions necessary to field convert unit from natural gas to propane.

Economizer for Downflow Applications (S1-2EE04710024, S1-2EE04710124) -

Modulating inte grated economizer provides simultaneous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available.

Economizer for Horizontal Applications (S1-2EE04710224, S1-2EE04710324) -

Modulating inte grated economizer provides simultaneous operation between the mechanical cooling and economizer operation. Independent blade design insures proper control and less than 1% leak rate. Includes hood and mesh bird screen filter integrated into the hood, dry bulb sensor and relief damper. Separate field accessories of single enthalpy and dual enthalpy are also available.

Single/Dual Enthalpy Sensor (S1-HE-6863-0N00WS) -

Sensor replaces supply air temperature dry bulb sensor standard in economizer kit. Provides improved economizer operation by sensing the dry bulb temperature of indoor sup ply air plus the enthalpy content of the outdoor air.

• •

• Supply Air Temperature Sensor Kit (S1-TE-63616E-2D) -

Outdoor supply air temperature sensor kit used with econo mizers. •

Filter/Frame Kit (S1-1FF0602, S1-1FF0601) -

Kit contains the necessary hardware to field install return air filters into the base unit. The filter rack is suitable for either 1" or 2" fil ters.

Duct/Unit Mount CO2 Kit (S1-2AQ04700924) -

Sensor kit detects CO2 levels automatically and overrides the econo mizer when CO2 levels rise above the preset limits.

Wall Mount CO2 Kit (S1-2AQ04701024) -

Sensor kit detects CO2 levels automatically and overrides the econo mizer when CO2 levels rise above the preset limits.

Filter (S1-02647812000) -

Washable 1" filter. Two filters are required for A base units. Three filters are required for B base units.

Motorized Fresh Air Damper (S1-2MD04705224, S1-2MD04705124) -

Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.

Rectangle to Round (Horizontal) Adapter (S1-1AK0110, S1-1AK0111) -

Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit over current horizontal duct openings on the base unit. Transition is from rectangle to 12" round for the 1AK0110 kit and from rectangle to 14" round for the 1AK0111 kit.

• • • • •

Rectangle to Round (Downflow) Adapter (S1-1AK0108, S1-1AK0109) -

Kit includes one supply and one return air rectangle to round duct adapter. Adapters are preformed and designed to fit into current downflow duct openings on the roof curb. Transition is from rectangle to 16" round for the 1AK0108 kit and from rectangle to 18" round for the 1AK0109 kit.

Roof Curbs (S1-1RC0503, S1-1RC0501) -

NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure an air tight seal. These are 8 inch high roof curbs.

Roof Curbs (S1-1RC0504, S1-1RC0502) -

NRCA approved curbs provide proper fit to base unit for rooftop installations. Curbs are designed to be assembled through hinge pins in each corner. Kit also provides seal strip to assure an air tight seal. These are 14 inch high roof curbs.

Transition Curb Kits (S1-1TC01*) -

Adapter kits to allow field use of pre-existing installed roof curbs to match PHG4 footprint to Affinity roof curbs, Carrier, Trane, or Goodman curb footprints. Curb adapters are optional for current gener ation Carrier replacements but are recommended for previ ous generation applications. Refer to the PHG4 price pages for more details.

Manual Outdoor Damper (S1-1FA0502, S1-1FA0501) -

Provides 0% through 50% outdoor air capability (field adjust able). Designed for duct mounted side supply/return applica tions. Includes hood and screen assembly.

• Thermostat (S1-THXU280*) -

Compatible thermostat con trols are available through accessory sourcing. For optimum performance, these outdoor units are fully compatible with the York Hx™ Touchscreen Thermostat (S1-THXU280*) available through Source1. For more information, see the thermostat section of the Product Equipment Catalog.

Wall Thermostat -

The units are designed to operate with standard, 24-volt electronic and electro-mechanical thermo stats. All units can operate with single stage heat/single stage cool thermostats - with or without the economizer.

• • •

Loss of Charge Switch (S1-2LC00024) -

Kit provides Loss of Charge switch and wiring to provide safe shutdown of compressor.

Low Ambient Kit (S1-2LA04701024) -

Kit provides neces sary hardware to convert unit to operate in cooling cycle down to 0º F. Standard unit operation 45º F.

Base Rail Hole Cover Kit (S1-1HC0101) -

Kit provides nec essary hardware to close off openings in base rails to block off openings, i.e. prevent animal entrance.

*

For additional kit numbers refer to the price pages.

4 Johnson Controls Unitary Products

GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by Unitary Products in an ISO 9001 certified facility. Package units give you the flexibility and choices you need in today’s market. These packaged cooling/ heating air conditioners are designed for outdoor installation. Only utility and duct connections are required at the point of installation. The single-stage gas fired heaters have stainless steel tubular heat exchangers and spark to burner ignition. They are available in natural gas with field conversion to propane.

DESCRIPTION

Units shall be factory-assembled, single packaged, Heat Pumps with Electric Cooling/Gas Heating units, designed for outdoor installation. They shall have built in, equal size, field convertible duct connections for supply/return or horizontal supply/return. The units shall be factory wired, piped, charged with R-410A Refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All models shall be rated in accordance with DOE and AHRI test procedures for both heating and cooling operation. Units shall be CSA listed and classified to ANSI Z21.47/CAN/ CSA 2.3 standards and UL 1995/CAN/CSA No. 236-M90 standards.

• •

Operating Efficiency -

All Heat Pump models shall be rated at 14.0 SEER, 11.0 EER, and 8.0 HSPF for heat pump cool ing and heating operation. All models shall be rated at 81.0% AFUE for gas heating operation.

Low Operating Sound Level -

The upward air flow carries the normal operating noise up and away from the living area. The rigid top panel effectively isolates noise. Isolator mounted compressor and the rippled fins of the outdoor coil muffle the normal fan motor and compressor operating sounds. The unique formed base pan also aids in sound attenuation with its structural design. Sound ratings as tested under AHRI test procedures shall be less than 77 dbA for all models.

UNIT CABINET

Unit cabinet shall be a single piece design, with drip edges and no-seam corners to provide optimum water integrity. Unit shall have a rigidly mounted outdoor coil guard to provide protection from objects and personnel after installation. Indoor blower section shall be insulated with foil-faced or foam insulation, fastened to prevent insulation from entering the air stream. Cabinet panels shall be separate, easily removable for servicing and maintenance. Unit shall be built on a formed, design base pan, with embossments at critical points to add strength and rigidity and to aid in minimizing sound. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, for truck access and proper sealing on roof curb applications. Base rails shall be easily removable, when required to lower unit height. Filters shall be field installed and field provided and be accessible through a removable access door, sealed airtight. Units vertical discharge and return duct configuration shall be designed to fit between standard 24” O.C. beams without modification to building structure, duct work and base unit. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards, with 3/4” NPT female ridged mount connection.

5127524-YTG-E-1017 • • • • •

Durable Finish -

The cabinet shall be is made of G90 galva nized steel with a powder paint coating for appearance and protection. The pre-treated galvanized steel shall provide a better paint-to-steel bond, which resists corrosion and rust creep. Powder paint finish shall provide superior corrosion resistance (1000 hour salt spray tested).

On Site Flexibility -

All model sizes shall use a compact design cabinet in one of two footprints. This provides installer flexibility for placing the proper capacity unit on curbs or pads with the smallest footprint after the internal load has been determined. Field convertible duct connections from side shot to down shot allows the installer to have greater flexibil ity with less inventory.

Attractive Appearance -

A single-piece top cover containing a top-discharge outdoor fan arrangement shall be used which requires less square footage on installation and pro vides a wider variety of installations. The one-piece design adds greater water integrity. Rounded corners with water drip edges add to the attractive appearance and prevent water penetration.

Convertible Airflow Design -

The bottom duct openings are covered when they leave the factory, ready to be used for a side supply/side return application. If a bottom supply/bottom return application is desired, simply remove the two panels from the bottom of the unit and place them in the side supply/ side return duct openings. No panel cutting is required and no accessory panel is necessary. Convertible airflow design allows maximum field flexibility and minimum inventory.

Utility Connections Made Easy -

Electric utility access shall be provided through the bottom or the side of the unit. Utility connections should be made quickly and with a minimum amount of field labor. A field supplied and field installed elec trical disconnect switch must be installed.

• • •

Easy Service Access -

Individual access panels are pro vided in access to all major components - compressors, indoor coils, blower, controls/gas heating section, filters, etc. that makes servicing easy. Removing these panels allow easy removal of the components such as the blower assem bly for maintenance and ease of troubleshooting.

Top Discharge -

The top-discharge outdoor fan does not disrupt neighboring areas or dry out vegetation surrounding the unit. The warm air from the top mounted fan is blown up and away from the structure and any landscaping.

Outdoor Coil Grille -

All models utilize a stamped slotted design which provides superior impact protection against small objects during transit and after installation.

Indoor Blower Assembly -

Fan shall be direct drive design. Blower wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. Fan assembly shall be a slide-out design for easy removal and cleaning. Indoor blower motors shall be equipped with a standard high efficiency brushless DC motor (constant torque) also known as a standard ECM motor.

Johnson Controls Unitary Products 5

5127524-YTG-E-1017

Outdoor Fan Assembly -

The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider bracket and shall be statically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings and internally protected against overload conditions.

REFRIGERANT COMPONENTS

Protected Compressor -

The compressor shall be a fully hermetic type, direct drive compressor, that is internally pro tected against high pressure and temperature. This is accomplished by the simultaneous operation of high pres sure internal relief valve and a temperature sensor which protect the compressor if undesirable operating conditions occur. The hermetic motor shall be suction gas cooled and have a voltage range of +/- 10% of the unit nameplate volt age. Compressors shall have internal isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

• • •

Indoor Coils -

Indoor coils shall be of the direct expansion, draw through design and have aluminum plate fins mechani cally bonded to seamless internally enhanced tin-coated copper tubes with all joints brazed.

Condensate Pan -

A corrosion-resistant, long-lasting, water tight pan is positioned below the indoor coil to collect and drain all condensate, preventing build-up of stagnant con densate. The condensate pan conforms to ASHRAE 62-89 standards (Ventilation for Acceptable Indoor Air Quality).

Condensate Drain -

The 3/4 inch NPT female connection is rigidly mounted to assure proper fit and leak tight seal.

Outdoor Coils -

Outdoor coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed, and be a draw through design.

Refrigerant Circuit and Refrigerant Safety Components shall include:

Thermal expansion devices (TXV's) shall be factory mounted and provided, Filter/strainer to eliminate any foreign matter, reversing valves to control refrigerant flow.

GAS HEATING SECTION

Heat exchanger and exhaust system shall be constructed of corrosion-resistant materials and shall be designed with induced draft combustion with post purge logic and redundant main gas valve. The heat exchanger shall be of the tubular type, constructed of stainless steel for corrosion resistance and Burners shall be of the in-shot type, constructed of aluminumized steel. All gas piping shall enter the unit cabinet at a single location through either the side or bottom, without any field modifications. An integrated control board shall provide timed control of indoor fan functioning and burner ignition. Heating section shall be provided with the following minimum protection: a. Primary high-temperature limit switch.

b. Induced draft pressure switch.

c. Flame roll out switch(s) (manual reset).

d. Flame proving controls.

All gas heat models will meet California requirement for emissions of less than 40 nanograms per Joule (California requirement on single phase models only).

CONTROLS

• •

Simple Control Circuit -

Field thermostat wiring connects to color coded leads using twist on wire connections. Cooling controls use contactor and relays for simple application and troubleshooting. Mate-n-lock plug connectors are used. Heating controls consist of direct spark ignition control and demand defrost heat pump control. The electrical control box is not located in the compressor compartment. The controls are mounted to allow the separate access panel to be removed for trouble shooting and maintenance without affecting the normal system operating pressures. All wiring internal to the unit is color/number coded.

Pressure Switches -

A high pressure switch is standard in all units. When abnormal conditions are sensed through the pressure switch, the unit will lock out preventing any further operation until reset or problem is corrected.

Factory Testing -

Installation time and costs are reduced by easy power and control wiring connections. All units are completely wired, charged with R-410A and tested prior to shipment. Test stations using a state-of-the-art computerized process system shall be used to insure product quality. Refrigerant charge and component part numbers are verified via computer bar code scans during assembly. Vital run test statistics such as system pressure, motor currents, air veloc ity and temperature, unit vibration, and gas system safeties are monitored and recorded by the system to insure unit per formance. This data could be provided by serial number tracking if requested.

Spark To Burner Ignition -

No pilot assembly required, which provides more consistent ignition in gas heating mode. This ignition is highly reliable, durable and eliminates nuisance lockouts.

6 Johnson Controls Unitary Products

PHYSICAL DATA

MODELS: NOMINAL TONNAGE: COMPONENT AHRI Cooling Performance

Gross Capacity @ AHRI A point (MBH) AHRI net capacity (MBH) EER SEER Nominal CFM System power (kW) Refrigerant type Refrigerant charge (lb-oz)

AHRI Heat Pump Heating Performance

47 Capacity Rating (MBH) System Power (kW/COP) 17 F Capacity Rating (MBH) HSPF (BTU/Watts-hr.)

AHRI Gas Heat Performance

Heating model Heat input (K Btu) Heat output (K Btu) AFUE % No. burners No. stages Max. Static Pressure WC

PHG4A24 2.0

R410A 50 50.0

40 24.1

23.8

11.0

14.0

800 1.8

8-5 22.0

3.7

12.0

8.0

75 75.0

60 81.0

2 1 40-70 0.5

180 81.0

3 1 1/2 Gas piping connection (inch)

Dimensions (inches)

Length Width Height Operating WT (lbs)

Compressors

Type

Outdoor Coil Data

Face area (Sq Ft) Rows Fins per inch Tube diameter Circuitry Type Refrigerant Control

Indoor Coil Data

Face area (Sq Ft) Rows Fins per inch Tube diameter Circuitry Type Refrigerant control

Outdoor Fan Data

Fan diameter (Inches) Type Drive type No. speeds Motor HP each RPM Nominal total CFM

Direct Drive Indoor Fan Data

Fan Size (Inches) Type Motor HP each RPM Frame size

Filters

Filter Size Quantity - Size 51-1/4 35-3/4 47 394 404 Scroll 15.1

2 22 3/8 Interlaced TXV 4.6

3 16 3/8 Interlaced TXV 24 Prop Direct 1 1/10 850 2400 11 x 8 Centrifugal 1/3 1/2 1200 Max 48

PHG4A30 2.5

30.1

29.6

11.0

14.0

1000 2.2

R410A 9-8 27.2

3.6

14.8

8.0

50 50.0

40 75 75.0

60 81.0

2 1 40-70 0.5

180 81.0

3 1 1/2 51-1/4 35-3/4 49 449 453 Scroll 16.9

2 22 3/8 Interlaced TXV 4.6

3 16 3/8 Interlaced TXV 24 Prop Direct 1 1/8 850 2400 11 x 8 Centrifugal 1/3 1/2 1200 Max 48

PHG4B36 3.0

36.4

35.8

11.0

14.0

1200 2.8

R410A 11-13 33.8

3.6

19.6

8.0

65 65.0

52 100 100.0

80 81.0

2 1 40-70 0.5

180 81.0

3 1 1/2 51-1/4 45-3/4 49 498 505 Scroll 19.4

2 22 3/8 Interlaced TXV TXV 3 16 3/8 Interlaced TXV 26 Prop Direct 1 1/3 850 3200 11 x 10 Centrifugal 1/2 3/4 1200 Max 48

PHG4B42 3.5

42.3

41.5

11.0

14.0

1400 3.2

R410A 13-0 38.0

3.6

22.0

8.0

65 65.0

52 100 100.0

80 81.0

2 1 40-70 0.5

180 81.0

3 1 1/2 51-1/4 45-3/4 49 532 534 Scroll 19.4

2 22 3/8 Interlaced TXV 6.3

3 16 3/8 Interlaced TXV 26 Prop Direct 1 1/3 850 3200 11 x 10 Centrifugal 3/4 1200 Max 48 65 65.0

52 81.0

2 1 551

PHG4B48 4.0

48.2

47.0

11.0

14.0

1600 3.7

R410A 12-13 45.5

3.7

25.4

8.0

100 125 100.0 125.0

80 100 81.0

3 1 40-70 0.5

180 81.0

4 1 1/2 51-1/4 45-3/4 53 559 Scroll 23.8

2 22 3/8 Interlaced TXV 6.3

3 16 3/8 Interlaced TXV 26 Prop Direct 1 1/3 850 3200 11 x 10 Centrifugal 3/4 1200 Max 48 5127524-YTG-E-1017 564 65 65.0

52 81.0

2 1 577

PHG4B60 5.0

59.9

58.0

11.0

14.0

2000 4.7

R410A 15-8 56.0

3.6

31.7

8.0

100 125 100.0 125.0

80 100 81.0

3 1 40-70 0.5

180 81.0

4 1 1/2 51-1/4 45-3/4 55 581 Scroll 51.8

2 22 3/8 Interlaced TXV 6.3

4 16 3/8 Interlaced TXV 26 Prop Direct 1 1/3 850 3200 11 x 10 Centrifugal 1 1200 Max 48 588 A A B B B B Field-supplied external filters must be sized so as not to exceed 300 fpm air velocity through disposable fil ters. For internal filter use, a filter rack kit is available. Consult the instructions supplied with that kit for replacement filter sizes. Filter sizes: A=20x20, B=20x30.

Johnson Controls Unitary Products 7

5127524-YTG-E-1017 8

COOLING PERFORMANCE DATA - 2 TON

PACKAGED UNIT MODEL NO.

PHG4A24 CONDENSER ENTERING AIR TEMPERATURE 55 / 45 65 / 55 75 / 63 85 / 69 95 / 75 105 / 83 115 / 89 125 / 95 80 57

24.9

23.5

0.98

24.2

22.5

1.10

23.4

21.5

1.21

22.3

20.4

1.36

21.2

19.4

1.51

19.3

17.8

1.71

17.4

16.2

1.91

15.6

14.7

2.11

ID CFM IDDB IDWB T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

80 62

28.3

19.9

0.98

26.9

19.2

1.09

25.4

18.5

1.21

23.5

17.7

1.35

21.7

16.8

1.50

19.5

15.9

1.71

17.4

15.1

1.91

15.3

14.3

2.12

COOLING PERFORMANCE DATA - 2.5 TON

PACKAGED UNIT MODEL NO.

CONDENSER ENTERING AIR TEMPERATURE ID CFM IDDB IDWB 55 / 45 T.C.

S.C.

K.W.

T.C.

65 / 55 75 / 63 85 / 69 S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

95 / 75 105 / 83 115 / 89 125 / 95 T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

PHG4A30 80 57

30.3

29.3

1.50

29.0

28.3

1.66

27.6

27.3

1.82

25.6

25.4

2.02

23.6

23.4

2.23

21.1

21.0

2.52

18.7

18.6

2.80

16.3

16.2

3.08

800 75 62

33.8

22.5

1.50

31.8

21.5

1.66

29.9

20.5

1.82

27.5

19.5

2.02

25.2

18.6

2.23

22.1

16.7

2.51

19.0

14.9

2.79

16.0

13.1

3.07

80 62

33.5

26.1

1.50

31.7

25.3

1.66

29.9

24.5

1.83

28.1

23.3

2.03

26.4

22.1

2.23

22.9

20.1

2.51

19.6

18.1

2.79

16.2

16.1

3.07

80 67

37.2

22.6

1.50

35.6

21.7

1.67

34.0

20.7

1.84

31.6

19.8

2.04

29.2

18.9

2.24

26.0

17.3

2.53

22.8

15.7

2.80

19.7

14.2

3.08

80 67

31.8

17.8

0.98

30.0

16.9

1.09

28.2

16.0

1.20

26.4

15.1

1.35

24.6

14.3

1.50

22.5

13.4

1.71

20.5

12.5

1.91

18.4

11.6

2.11

600 75 62

28.3

18.0

0.98

26.9

17.0

1.08

25.5

16.1

1.19

23.7

15.2

1.34

21.9

14.4

1.49

19.7

13.2

1.70

17.5

12.2

1.90

15.4

11.1

2.11

80 72

34.8

15.0

0.97

33.1

14.1

1.08

31.5

13.2

1.20

29.5

12.4

1.35

27.5

11.6

1.50

24.7

10.5

1.71

22.1

9.5

1.91

19.4

8.5

2.11

80 57

28.3

26.5

1.03

27.2

25.3

1.15

26.1

24.2

1.27

24.7

22.8

1.41

23.4

21.4

1.56

20.9

19.4

1.76

18.6

17.5

1.96

16.2

15.5

2.16

80 62

30.6

23.4

1.03

29.0

22.6

1.15

27.5

21.9

1.26

25.3

20.7

1.41

23.1

19.5

1.55

20.8

18.2

1.76

18.6

16.9

1.96

16.4

15.7

2.17

800 75 62

31.0

20.7

1.03

29.2

19.6

1.14

27.3

18.5

1.25

25.2

17.4

1.40

23.1

16.3

1.54

20.6

15.2

1.75

18.2

14.1

1.96

15.8

13.0

2.16

80 67

34.5

20.2

1.03

32.3

19.4

1.14

30.1

18.7

1.25

28.2

17.6

1.40

26.2

16.6

1.55

23.5

15.5

1.76

20.8

14.4

1.96

18.2

13.2

2.16

80 72

36.9

16.1

1.02

35.2

15.4

1.14

33.6

14.8

1.25

31.4

14.0

1.40

29.2

13.1

1.55

26.2

11.9

1.76

23.3

10.7

1.96

20.4

9.5

2.16

80 57

31.6

29.5

1.08

30.2

28.1

1.20

28.8

26.8

1.32

27.1

25.1

1.47

25.5

23.4

1.61

22.5

21.0

1.82

19.7

18.7

2.01

16.8

16.4

2.21

80 62

32.8

26.8

1.08

31.2

26.0

1.20

29.5

25.2

1.31

27.0

23.7

1.46

24.5

22.1

1.60

22.1

20.4

1.81

19.8

18.8

2.02

17.5

17.1

2.22

1000 75 62

33.8

23.4

1.08

31.4

22.2

1.19

29.1

21.0

1.31

26.7

19.6

1.45

24.4

18.2

1.59

21.6

17.1

1.81

18.9

16.1

2.01

16.2

15.0

2.22

80 67

37.1

22.6

1.08

34.6

22.0

1.19

32.0

21.4

1.31

29.9

20.2

1.45

27.8

18.9

1.60

24.4

17.6

1.81

21.2

16.2

2.01

18.0

14.9

2.21

80 72

39.0

17.1

1.07

37.3

16.8

1.19

35.6

16.4

1.31

33.3

15.5

1.45

30.9

14.7

1.60

27.7

13.3

1.81

24.6

11.9

2.01

21.5

10.5

2.21

80 72

42.9

18.8

1.51

39.8

17.4

1.67

36.8

16.0

1.84

35.0

15.3

2.04

33.2

14.7

2.25

29.6

13.4

2.54

26.1

12.2

2.81

22.6

10.9

3.09

80 57

32.8

32.2

1.50

31.2

30.7

1.66

29.6

29.3

1.82

27.4

27.1

2.03

25.2

25.0

2.23

22.6

22.4

2.52

20.0

19.9

2.80

17.5

17.4

3.08

80 62

35.3

28.9

1.50

33.5

28.3

1.66

31.7

27.8

1.83

29.5

26.4

2.03

27.3

25.0

2.23

23.8

22.2

2.52

20.4

19.5

2.80

16.9

16.8

3.07

1000 75 62

35.8

24.8

1.50

33.7

23.8

1.66

31.5

22.8

1.82

28.9

21.8

2.03

26.3

20.8

2.23

22.8

18.7

2.51

19.4

16.6

2.79

16.1

14.6

3.07

80 67

39.4

24.4

1.50

37.6

23.9

1.67

35.8

23.4

1.84

33.1

22.3

2.04

30.5

21.2

2.24

27.1

19.4

2.53

23.7

17.6

2.80

20.4

15.9

3.08

80 72

45.4

20.1

1.51

42.7

19.1

1.67

40.0

18.1

1.84

37.4

17.2

2.05

34.8

16.3

2.25

30.8

14.7

2.54

27.0

13.2

2.81

23.1

11.6

3.09

80 57

35.3

35.1

1.50

33.4

33.2

1.66

31.5

31.3

1.83

29.1

28.9

2.03

26.7

26.5

2.24

24.0

23.8

2.53

21.3

21.2

2.81

18.7

18.6

3.09

80 62

37.2

31.7

1.50

35.4

31.4

1.66

33.6

31.1

1.83

30.9

29.5

2.03

28.1

27.9

2.24

24.6

24.4

2.53

21.1

21.0

2.80

17.7

17.5

3.08

1200 75 62

37.8

27.1

1.51

35.5

26.1

1.67

33.2

25.2

1.83

30.3

24.2

2.03

27.4

23.1

2.23

23.6

20.7

2.51

19.9

18.4

2.79

16.1

16.0

3.07

80 67

41.6

26.2

1.51

39.6

26.1

1.67

37.6

26.1

1.84

34.7

24.8

2.04

31.8

23.5

2.24

28.2

21.5

2.53

24.6

19.6

2.80

21.1

17.6

3.08

80 72

47.9

21.5

1.51

45.5

20.9

1.68

43.2

20.3

1.85

39.8

19.1

2.05

36.5

17.9

2.25

32.1

16.0

2.54

27.9

14.2

2.81

23.6

12.3

3.09

Johnson Controls Unitary Products

5127524-YTG-E-1017

COOLING PERFORMANCE DATA - 3 TON

PACKAGED UNIT MODEL NO.

PHG4B36 CONDENSER ENTERING AIR TEMPERATURE 55 / 45 65 / 55 75 / 63 85 / 69 95 / 75 105 / 83 115 / 89 125 / 95 ID CFM IDDB IDWB T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

80 57

40.4

40.0

1.97

37.9

37.9

2.17

35.4

35.4

2.36

33.1

33.1

2.63

30.7

30.7

2.89

27.8

27.8

3.26

25.1

25.1

3.63

22.3

22.3

3.99

1000 75 62

43.9

30.5

1.98

41.4

29.1

2.17

38.9

27.6

2.36

35.8

26.1

2.63

32.7

24.6

2.89

28.7

22.7

3.27

24.9

20.9

3.63

21.1

19.0

4.00

80 62

43.9

34.9

1.98

41.2

33.7

2.18

38.5

32.5

2.39

35.4

30.8

2.65

32.2

29.1

2.91

28.4

26.7

3.28

24.8

24.3

3.64

21.1

21.1

4.00

COOLING PERFORMANCE DATA - 3.5 TON

PACKAGED UNIT MODEL NO. PHG4B42 CONDENSER ENTERING AIR TEMPERATURE ID CFM IDDB IDWB 80 57 80 62 55 / 45 T.C.

S.C.

K.W.

T.C.

45.8

45.8

2.26

43.1

50.4

40.4

2.27

47.4

65 / 55 75 / 63 85 / 69 S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

43.1

2.49

40.3

40.3

2.72

37.1

37.1

3.02

39.3

2.50

44.4

38.2

2.73

40.6

36.1

3.02

95 / 75 105 / 83 115 / 89 125 / 95 T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

34.0

34.0

3.31

30.8

30.8

3.73

27.7

27.7

4.13

24.6

24.6

4.53

36.8

34.1

3.31

32.1

30.4

3.73

27.5

26.9

4.14

23.0

23.0

4.54

1200 75 62

50.3

34.5

2.28

47.8

33.5

2.51

45.3

32.6

2.73

41.2

30.4

3.03

37.2

28.3

3.33

32.0

26.1

3.74

27.0

24.0

4.14

21.9

21.8

4.53

80 67

53.3

33.0

2.28

52.0

32.9

2.51

50.7

32.7

2.74

46.5

30.7

3.04

42.4

28.7

3.35

37.2

26.6

3.76

32.2

24.7

4.16

27.1

22.7

4.56

80 67

47.3

29.3

1.98

45.1

28.4

2.18

42.8

27.4

2.39

39.7

25.9

2.65

36.6

24.3

2.91

32.2

22.5

3.28

27.9

20.7

3.63

23.7

18.9

3.99

Johnson Controls Unitary Products

80 72

46.7

22.4

1.98

47.2

22.3

2.18

47.6

22.1

2.39

44.4

20.7

2.65

41.1

19.4

2.91

36.6

17.6

3.28

32.3

15.8

3.64

27.9

14.1

4.00

80 57

43.3

42.9

2.06

40.4

40.4

2.26

37.5

37.5

2.46

34.7

34.7

2.72

32.0

32.0

2.98

28.8

28.8

3.35

25.7

25.7

3.72

22.6

22.6

4.08

80 62

45.1

40.4

2.07

42.4

38.1

2.27

39.8

35.7

2.48

36.5

34.0

2.74

33.1

32.2

3.00

29.1

28.8

3.37

25.2

25.2

3.73

21.3

21.3

4.09

1200 75 62

45.4

32.6

2.07

42.6

32.7

2.27

39.8

32.9

2.47

36.6

30.0

2.73

33.4

27.1

2.98

29.0

24.6

3.36

24.7

22.2

3.73

20.5

19.8

4.09

80 67

47.7

31.2

2.07

46.0

30.6

2.28

44.2

29.9

2.48

40.7

28.2

2.74

37.1

26.5

3.00

32.3

24.6

3.37

27.7

22.8

3.72

23.0

21.0

4.08

80 72

47.3

23.3

2.07

47.8

23.5

2.28

48.4

23.7

2.48

45.2

22.3

2.74

42.1

21.0

3.00

37.1

19.0

3.37

32.2

17.1

3.73

27.3

15.3

4.09

80 57

46.2

45.9

2.16

42.8

42.8

2.36

39.5

39.5

2.56

36.4

36.4

2.81

33.4

33.4

3.07

29.8

29.8

3.44

26.4

26.4

3.81

22.9

22.9

4.17

80 62

46.2

45.9

2.16

43.7

42.5

2.36

41.1

39.0

2.57

37.5

37.1

2.83

33.9

33.9

3.09

29.7

29.7

3.46

25.6

25.6

3.82

21.5

21.5

4.18

1400 75 62

46.8

34.6

2.16

43.8

36.4

2.37

40.7

38.2

2.58

37.4

33.9

2.83

34.1

29.6

3.08

29.3

26.5

3.45

24.5

23.6

3.82

19.8

19.8

4.18

80 67

48.2

33.0

2.16

46.9

32.7

2.37

45.7

32.5

2.58

41.6

30.6

2.83

37.6

28.7

3.09

32.5

26.8

3.46

27.4

24.9

3.81

22.4

22.4

4.17

80 72

47.8

24.3

2.16

48.5

24.7

2.37

49.1

25.2

2.58

46.0

23.9

2.83

43.0

22.6

3.09

37.5

20.5

3.46

32.1

18.5

3.82

26.8

16.4

4.18

80 72

55.3

25.6

2.28

55.3

25.6

2.52

55.4

25.5

2.76

51.5

24.0

3.05

47.6

22.5

3.35

42.4

20.4

3.76

37.4

18.4

4.17

32.3

16.5

4.58

80 57

47.6

47.6

2.37

44.8

44.8

2.60

41.9

41.9

2.82

38.5

38.5

3.12

35.2

35.2

3.41

32.0

32.0

3.83

28.9

28.9

4.23

25.8

25.8

4.63

80 62

51.3

42.5

2.37

48.6

42.1

2.60

45.8

41.8

2.82

41.6

39.1

3.12

37.5

36.4

3.41

33.1

32.5

3.83

28.8

28.7

4.24

24.6

24.6

4.64

1400 75 62

51.2

36.2

2.37

48.7

35.8

2.60

46.3

35.3

2.82

41.9

33.0

3.12

37.6

30.6

3.42

32.1

27.5

3.83

26.8

24.5

4.23

21.5

21.5

4.63

80 67

54.1

34.4

2.38

52.9

34.9

2.61

51.8

35.3

2.85

47.2

33.0

3.14

42.7

30.8

3.44

37.1

28.5

3.85

31.6

26.3

4.25

26.1

24.1

4.65

80 72

56.6

26.5

2.38

56.2

26.7

2.62

55.8

26.8

2.86

52.2

25.4

3.15

48.6

23.9

3.45

42.8

21.7

3.86

37.1

19.7

4.26

31.5

17.6

4.66

80 57

49.5

49.5

2.47

46.4

46.4

2.70

43.4

43.4

2.93

39.9

39.9

3.22

36.5

36.5

3.51

33.3

33.3

3.93

30.1

30.1

4.33

27.0

27.0

4.73

80 62

52.3

44.6

2.47

49.8

45.0

2.69

47.3

45.4

2.92

42.7

42.0

3.22

38.1

38.1

3.51

34.1

34.1

3.93

30.1

30.1

4.34

26.2

26.2

4.74

1600 75 62

52.1

37.9

2.46

49.7

38.0

2.69

47.3

38.1

2.92

42.6

35.5

3.22

38.0

32.9

3.51

32.2

29.0

3.92

26.6

25.1

4.32

21.0

21.0

4.72

80 67

54.9

35.9

2.47

53.9

36.9

2.71

52.9

37.9

2.95

47.9

35.4

3.24

43.0

32.9

3.53

36.9

30.4

3.95

31.0

28.0

4.35

25.1

25.1

4.75

80 72

57.9

27.4

2.47

57.0

27.8

2.71

56.2

28.2

2.95

52.9

26.7

3.25

49.7

25.3

3.55

43.2

23.1

3.96

36.9

20.9

4.36

30.6

18.7

4.75

9

5127524-YTG-E-1017

COOLING PERFORMANCE DATA - 4 TON

PACKAGED UNIT MODEL NO.

CONDENSER ENTERING AIR TEMPERATURE ID CFM IDDB IDWB 55 / 45 T.C.

S.C.

K.W.

T.C.

65 / 55 75 / 63 85 / 69 S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

95 / 75 105 / 83 115 / 89 125 / 95 T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

PHG4B48 80 57

48.0

48.0

2.63

45.0

45.0

2.90

42.0

42.0

3.16

39.3

39.3

3.53

36.6

36.6

3.91

33.2

33.2

4.40

29.9

29.9

4.89

26.5

26.5

5.37

1400 75 62

52.4

37.9

2.63

48.9

35.6

2.90

45.4

33.3

3.16

41.9

31.0

3.52

38.5

28.6

3.87

34.7

26.9

4.38

31.1

25.2

4.87

27.5

23.5

5.36

80 62

51.3

44.1

2.64

48.1

41.5

2.92

44.9

38.9

3.21

41.4

36.4

3.56

37.9

34.0

3.91

34.2

32.3

4.40

30.7

30.6

4.89

27.1

27.1

5.37

COOLING PERFORMANCE DATA - 5 TON

PACKAGED UNIT MODEL NO.

CONDENSER ENTERING AIR TEMPERATURE ID CFM IDDB IDWB 55 / 45 T.C.

S.C.

K.W.

65 / 55 T.C.

S.C.

K.W.

T.C.

75 / 63 85 / 69 95 / 75 S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

105 / 83 115 / 89 125 / 95 T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

T.C.

S.C.

K.W.

PHG4B60 80 57

61.5

61.5

3.37

58.9

58.9

3.69

56.3

56.3

4.01

52.5

52.5

4.49

48.6

48.6

4.97

44.5

44.5

5.66

40.5

40.5

6.33

36.5

36.5

7.00

1600 75 62

68.4

47.0

3.40

64.2

45.0

3.74

60.0

42.9

4.09

55.0

40.8

4.54

50.0

38.8

4.99

44.1

35.9

5.66

38.4

33.2

6.31

32.7

30.4

6.97

80 62

74.6

46.4

3.44

66.6

48.4

3.75

58.7

50.4

4.06

54.1

47.9

4.53

49.5

45.4

5.01

44.3

41.6

5.68

39.2

37.9

6.34

34.1

34.1

6.99

80 67

68.6

55.3

3.41

67.4

49.0

3.77

66.2

42.6

4.14

61.5

40.5

4.60

56.7

38.4

5.05

50.1

36.5

5.71

43.6

34.6

6.35

37.1

32.8

6.99

80 67

56.5

40.8

2.66

54.0

37.5

2.94

51.6

34.2

3.22

48.2

32.0

3.57

44.8

29.8

3.93

41.0

27.7

4.43

37.3

25.6

4.91

33.6

23.6

5.39

80 72

64.4

33.6

2.70

60.8

31.0

2.96

57.2

28.4

3.22

53.7

26.1

3.58

50.1

23.8

3.95

46.0

21.9

4.44

42.1

20.1

4.92

38.2

18.3

5.40

80 57

50.6

50.6

2.77

47.3

47.3

3.03

44.1

44.1

3.30

41.1

41.1

3.66

38.1

38.1

4.03

34.4

34.4

4.53

30.8

30.8

5.02

27.2

27.2

5.50

80 62

53.7

47.6

2.77

50.1

44.8

3.05

46.4

41.9

3.32

42.8

39.4

3.68

39.1

36.9

4.04

35.4

34.8

4.53

31.7

31.7

5.01

28.1

28.1

5.49

1600 75 62

54.5

40.5

2.77

50.9

38.1

3.03

47.3

35.7

3.30

43.5

33.2

3.65

39.7

30.8

4.01

35.9

28.9

4.51

32.1

27.1

5.00

28.3

25.2

5.48

80 67

60.0

42.6

2.80

56.8

39.6

3.07

53.5

36.6

3.35

49.9

34.3

3.70

46.4

32.0

4.06

42.2

29.7

4.56

38.1

27.5

5.04

34.0

25.3

5.52

80 72

66.5

35.0

2.82

62.7

32.6

3.09

59.0

30.1

3.35

55.3

27.7

3.72

51.5

25.3

4.08

47.3

23.4

4.57

43.3

21.5

5.05

39.2

19.7

5.53

80 57

53.1

53.1

2.91

49.7

49.7

3.17

46.2

46.2

3.43

42.9

42.9

3.79

39.7

39.7

4.16

35.7

35.7

4.66

31.8

31.8

5.15

27.9

27.9

5.64

80 62

56.1

51.0

2.90

52.0

48.0

3.17

47.9

45.0

3.44

44.1

42.4

3.81

40.4

39.8

4.17

36.5

36.5

4.66

32.8

32.8

5.14

29.0

29.0

5.62

1800 75 62

56.7

43.2

2.90

53.0

40.6

3.16

49.3

38.0

3.43

45.2

35.5

3.79

41.0

33.0

4.15

37.0

31.0

4.64

33.1

29.0

5.12

29.1

27.0

5.60

80 67

63.6

44.3

2.93

59.5

41.7

3.21

55.4

39.0

3.48

51.7

36.6

3.84

48.0

34.2

4.19

43.4

31.7

4.69

38.9

29.4

5.17

34.4

27.1

5.65

80 72

68.5

36.4

2.95

64.7

34.2

3.22

60.8

31.9

3.49

56.8

29.4

3.85

52.9

26.9

4.20

48.6

24.9

4.70

44.4

22.9

5.18

40.3

21.0

5.66

80 72

81.4

37.3

3.45

77.8

36.9

3.82

74.3

36.5

4.18

69.1

33.4

4.64

63.8

30.2

5.10

57.4

27.7

5.75

51.1

25.2

6.39

44.9

22.8

7.02

80 57

65.3

65.3

3.54

62.3

62.3

3.87

59.2

59.2

4.20

55.1

55.1

4.67

51.1

51.1

5.14

46.5

46.5

5.83

42.1

42.1

6.49

37.7

37.7

7.16

80 62

74.6

49.2

3.59

64.4

48.6

4.06

54.1

47.9

4.53

52.4

48.3

4.85

50.6

48.6

5.17

45.1

43.9

5.84

39.9

39.3

6.50

34.6

34.6

7.15

1400 75 62

70.4

50.6

3.56

65.8

48.5

3.90

61.2

46.4

4.25

56.2

44.1

4.70

51.2

41.8

5.15

44.7

38.2

5.82

38.5

34.7

6.47

32.3

31.2

7.12

80 67

70.6

60.0

3.57

69.2

53.0

3.93

67.8

46.1

4.30

62.7

43.8

4.76

57.5

41.6

5.22

50.2

39.0

5.88

43.0

36.4

6.52

35.9

33.8

7.16

80 72

80.6

38.1

3.61

78.2

37.8

3.98

75.8

37.6

4.35

70.5

34.8

4.81

65.3

32.0

5.26

58.2

29.4

5.91

51.4

26.9

6.55

44.6

24.4

7.18

80 57

69.1

69.1

3.72

65.6

65.6

4.05

62.1

62.1

4.39

57.8

57.8

4.85

53.5

53.5

5.31

48.6

48.6

5.99

43.8

43.8

6.66

39.0

39.0

7.32

80 62

74.7

52.1

3.74

62.1

48.7

4.37

49.5

45.4

5.01

50.6

48.6

5.17

51.7

51.7

5.33

46.0

46.0

6.00

40.5

40.5

6.66

35.0

35.0

7.31

1200 75 62

72.3

54.2

3.72

67.4

52.0

4.06

62.5

49.8

4.41

57.4

47.3

4.87

52.4

44.8

5.32

45.4

40.4

5.99

38.6

36.2

6.63

31.8

31.8

7.28

80 67

72.6

64.6

3.73

71.1

57.1

4.10

69.5

49.5

4.47

63.9

47.1

4.93

58.3

44.8

5.39

50.3

41.4

6.04

42.5

38.1

6.68

34.8

34.8

7.32

80 72

79.7

38.9

3.76

78.5

38.8

4.14

77.3

38.7

4.52

72.0

36.2

4.97

66.7

33.8

5.42

59.1

31.1

6.07

51.7

28.5

6.71

44.3

25.9

7.34

10 Johnson Controls Unitary Products

5127524-YTG-E-1017

HEATING PERFORMANCE DATA - 2 TON

PACKAGED UNIT MODEL NO PHG4A24 AIR TEMP. ENTERING OUTDOOR UNIT AIR TEMP. ENTERING INDOOR COIL MBH 60 47 40 30 17 10 60 70 80 60 70 80 60 70 80 60 70 80 80 60 70 80 60 70

28.1

26.7

25.3

23.4

22.3

21.3

20.7

19.8

18.8

17.1

16.7

16.2

13.6

12.7

11.8

12.2

11.4

10.5

600 COP

4.56

3.92

3.39

4.00

3.42

2.96

3.61

3.09

2.66

3.08

2.69

2.38

2.57

2.14

1.80

2.36

1.97

1.65

HEATING PERFORMANCE DATA - 2.5 TON

PACKAGED UNIT MODEL NO PHG4A30 AIR TEMP. ENTERING OUTDOOR UNIT 60 47 40 30 17 10 AIR TEMP. ENTERING INDOOR COIL 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 MBH

34.6

33.3

32.0

29.1

27.7

26.2

25.5

24.3

23.0

21.2

20.3

19.3

16.3

14.3

12.4

13.7

12.7

11.7

800 COP

4.82

4.19

3.67

4.13

3.55

3.07

3.69

3.15

2.71

3.17

2.74

2.38

2.55

2.00

1.55

2.20

1.84

1.54

KW

1.80

1.99

2.18

1.71

1.91

2.10

1.67

1.87

2.06

1.62

1.80

1.99

1.54

1.73

1.91

1.51

1.68

1.86

MBH

29.3

27.8

26.4

24.1

23.0

21.9

21.4

20.4

19.4

17.6

17.0

16.3

13.9

12.9

12.0

12.1

11.3

10.4

ID CFM 800 COP

5.06

4.34

3.75

4.31

3.70

3.20

3.87

3.32

2.87

3.28

2.83

2.47

2.65

2.22

1.87

2.37

1.99

1.67

KW

1.69

1.87

2.05

1.63

1.82

2.00

1.61

1.79

1.97

1.57

1.75

1.93

1.52

1.69

1.87

1.49

1.66

1.82

MBH

30.5

29.0

27.5

24.9

23.7

22.5

22.0

21.0

20.0

18.2

17.3

16.4

14.1

13.1

12.2

12.1

11.3

10.4

1000 COP

5.63

4.82

4.16

4.66

4.00

3.46

4.16

3.58

3.10

3.48

2.98

2.57

2.75

2.31

1.95

2.38

2.01

1.70

KW

1.58

1.76

1.93

1.56

1.73

1.90

1.54

1.71

1.88

1.53

1.69

1.86

1.50

1.66

1.82

1.48

1.63

1.79

KW

2.10

2.32

2.55

2.06

2.27

2.49

2.02

2.25

2.48

1.95

2.16

2.37

1.86

2.10

2.33

1.81

2.01

2.21

MBH

35.6

34.2

32.8

29.6

28.2

26.7

26.1

24.8

23.5

21.4

20.5

19.5

16.1

14.5

12.8

13.6

12.5

11.4

ID CFM 1000 COP

5.05

4.40

3.86

4.27

3.68

3.19

3.82

3.27

2.82

3.22

2.78

2.42

2.51

2.03

1.63

2.16

1.81

1.51

KW

2.06

2.27

2.48

2.03

2.23

2.44

2.00

2.21

2.43

1.94

2.14

2.35

1.87

2.08

2.29

1.84

2.03

2.21

MBH

36.6

35.0

33.5

30.1

28.7

27.2

26.7

25.3

23.9

21.6

20.7

19.7

15.9

14.5

13.2

13.6

12.4

11.2

1200 COP

5.29

4.62

4.05

4.41

3.81

3.31

3.95

3.39

2.93

3.26

2.83

2.47

2.47

2.06

1.71

2.13

1.77

1.47

KW

2.02

2.22

2.41

1.99

2.20

2.40

1.97

2.18

2.38

1.93

2.13

2.32

1.88

2.06

2.24

1.86

2.04

2.22

Johnson Controls Unitary Products 11

5127524-YTG-E-1017

HEATING PERFORMANCE DATA - 3 TON

PACKAGED UNIT MODEL NO PHG4B36 AIR TEMP. ENTERING OUTDOOR UNIT AIR TEMP. ENTERING INDOOR COIL 60 47 40 30 17 10 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 MBH

41.6

39.9

38.2

35.3

33.8

32.3

31.5

30.1

28.7

26.8

25.3

23.9

20.1

18.7

17.3

17.6

16.1

14.7

1000 COP

4.67

4.08

3.58

4.14

3.59

3.13

3.76

3.26

2.84

3.29

2.82

2.43

2.54

2.16

1.84

2.28

1.90

1.59

HEATING PERFORMANCE DATA - 3.5 TON

PACKAGED UNIT MODEL NO PHG4B42 AIR TEMP. ENTERING OUTDOOR UNIT 60 47 40 30 17 10 AIR TEMP. ENTERING INDOOR COIL 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 MBH

48.1

46.0

43.9

40.1

38.0

35.9

35.3

33.2

31.1

25.5

25.8

26.1

21.6

20.0

18.4

17.6

16.7

15.8

1200 COP

4.38

3.84

3.38

3.83

3.32

2.89

3.41

2.90

2.47

2.52

2.32

2.16

2.19

1.86

1.57

1.80

1.58

1.39

KW

2.60

2.86

3.11

2.49

2.75

3.01

2.45

2.70

2.95

2.38

2.62

2.87

2.31

2.52

2.74

2.25

2.48

2.70

MBH

42.7

40.9

39.1

35.8

34.2

32.7

32.0

30.5

29.1

27.0

25.6

24.1

20.3

18.4

16.5

17.6

16.3

14.9

ID CFM 1200 COP

4.87

4.25

3.73

4.23

3.67

3.21

3.83

3.33

2.91

3.31

2.85

2.47

2.54

2.11

1.75

2.26

1.89

1.59

KW

2.56

2.81

3.06

2.47

2.72

2.97

2.44

2.68

2.92

2.38

2.62

2.86

2.33

2.54

2.76

2.28

2.50

2.72

MBH

43.8

41.9

40.0

36.3

34.7

33.0

32.4

31.0

29.5

27.2

25.8

24.4

20.4

18.0

15.7

17.7

16.4

15.0

1400 COP

5.08

4.42

3.88

4.33

3.76

3.29

3.90

3.40

2.97

3.33

2.88

2.50

2.54

2.06

1.65

2.23

1.89

1.60

KW

2.52

2.77

3.01

2.45

2.69

2.93

2.42

2.66

2.90

2.39

2.62

2.84

2.35

2.56

2.77

2.31

2.52

2.74

KW

3.21

3.50

3.79

3.06

3.34

3.63

3.02

3.35

3.67

2.95

3.24

3.53

2.87

3.14

3.41

2.85

3.09

3.32

MBH

49.1

46.9

44.7

40.7

38.5

36.3

35.7

33.4

31.1

27.9

26.4

25.0

22.0

19.8

17.5

17.0

16.0

14.9

ID CFM 1400 COP

4.36

3.83

3.38

3.75

3.27

2.86

3.31

2.82

2.41

2.65

2.30

2.00

2.13

1.76

1.45

1.65

1.44

1.26

KW

3.29

3.58

3.86

3.16

3.44

3.71

3.15

3.46

3.77

3.08

3.36

3.64

3.02

3.28

3.53

3.01

3.24

3.46

MBH

50.1

47.8

45.4

41.2

39.0

36.8

36.1

33.6

31.1

30.3

27.0

23.8

22.5

19.6

16.7

16.4

15.3

14.1

1600 COP

4.33

3.82

3.38

3.68

3.22

2.83

3.22

2.75

2.35

2.76

2.27

1.86

2.08

1.68

1.33

1.51

1.31

1.14

KW

3.38

3.65

3.92

3.27

3.54

3.80

3.27

3.57

3.87

3.20

3.47

3.74

3.16

3.41

3.65

3.16

3.38

3.60

12 Johnson Controls Unitary Products

5127524-YTG-E-1017

HEATING PERFORMANCE DATA - 4 TON

PACKAGED UNIT MODEL NO PHG4B48 AIR TEMP. ENTERING OUTDOOR UNIT AIR TEMP. ENTERING INDOOR COIL 60 47 40 30 17 10 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 MBH

56.5

54.9

53.3

48.4

46.7

45.0

43.3

40.5

37.8

37.5

35.2

32.9

28.4

27.2

26.0

25.8

24.1

22.4

1400 COP

4.87

4.29

3.80

4.33

3.77

3.32

3.94

3.36

2.88

3.50

2.93

2.47

2.71

2.33

2.02

2.53

2.13

1.80

HEATING PERFORMANCE DATA - 5 TON

PACKAGED UNIT MODEL NO PHG4B60 AIR TEMP. ENTERING OUTDOOR UNIT 60 47 40 30 17 10 AIR TEMP. ENTERING INDOOR COIL 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 60 70 80 MBH

70.2

67.6

65.0

58.4

56.3

54.1

52.5

49.8

47.0

38.2

39.5

40.9

29.5

27.6

25.6

30.1

28.4

26.8

1600 COP

4.50

3.94

3.48

3.98

3.46

3.03

3.69

3.15

2.70

2.87

2.63

2.45

2.33

1.92

1.59

2.31

1.98

1.71

KW

4.55

5.01

5.46

4.28

4.76

5.23

4.17

4.63

5.09

3.89

4.38

4.88

3.71

4.19

4.69

3.79

4.19

4.57

KW

3.39

3.74

4.09

3.27

3.62

3.97

3.21

3.52

3.84

3.13

3.51

3.88

3.06

3.41

3.76

2.98

3.30

3.62

MBH

57.8

56.0

54.2

49.2

47.4

45.6

43.8

41.7

39.7

37.0

34.7

32.3

28.2

27.0

25.9

25.5

24.0

22.6

ID CFM 1600 COP

4.95

4.37

3.89

4.37

3.82

3.36

3.96

3.44

3.00

3.40

2.88

2.45

2.66

2.30

2.00

2.43

2.09

1.80

KW

3.41

3.74

4.07

3.29

3.62

3.96

3.23

3.55

3.86

3.18

3.52

3.86

3.09

3.43

3.77

3.05

3.36

3.66

MBH

59.0

57.0

55.1

49.9

48.1

46.2

44.3

42.9

41.5

36.6

34.2

31.8

28.0

26.9

25.8

25.1

24.0

22.9

1800 COP

5.03

4.46

3.98

4.42

3.87

3.41

3.98

3.51

3.12

3.31

2.83

2.42

2.61

2.27

1.99

2.34

2.05

1.81

KW

3.43

3.74

4.05

3.30

3.63

3.95

3.25

3.57

3.89

3.23

3.53

3.84

3.13

3.46

3.79

3.12

3.41

3.70

MBH

71.2

68.4

65.5

58.7

56.5

54.3

52.8

50.4

48.1

38.2

37.9

37.7

32.5

30.5

28.5

29.9

28.2

26.5

ID CFM 1800 COP

4.54

3.98

3.51

3.93

3.44

3.03

3.61

3.13

2.73

2.77

2.49

2.25

2.41

2.04

1.74

2.21

1.90

1.65

KW

4.59

5.03

5.46

4.36

4.80

5.25

4.28

4.71

5.13

4.03

4.46

4.88

3.94

4.36

4.78

3.96

4.32

4.69

MBH

72.2

69.1

66.1

59.0

56.8

54.6

53.0

51.1

49.1

38.2

36.3

34.4

35.4

33.4

31.5

29.8

28.0

26.2

2000 COP

4.57

4.02

3.56

3.88

3.42

3.03

3.54

3.13

2.77

2.68

2.35

2.06

2.48

2.16

1.88

2.12

1.83

1.59

KW

4.61

5.03

5.44

4.44

4.86

5.26

4.38

4.78

5.17

4.15

4.51

4.88

4.17

4.53

4.88

4.11

4.46

4.82

Johnson Controls Unitary Products 13

5127524-YTG-E-1017 &251(53267 81,77233$1(/ ,1'225&2,/ &2,/*8$5' +,*+92/7$*( 23(1,1*´ +,*+92/7$*( 23(1,1*´ &2035(6625 $&&(663$1(/ & &20%867,21$,5,17$.( +($7(;&+$1*(5$&&(663$1(/ )/8((;+$867+22' &21'(16$7( '5$,1 %/2:(5 $&&(66 3$1(/ $ &21752/+($7 $&&(663$1(/ % /2:92/7$*(23(1,1*´ *$66833/<+2/(´:,7+ *5200(723(1,1*2)´ $

UNIT DIMENSIONS AND ACCESS LOCATIONS

Model

PHG4A24 PHG4A30 PHG4B36 PHG4B42 PHG4B48 PHG4B60

A

51-1/4 51-1/4 51-1/4 51-1/4 51-1/4 51-1/4

Dimensions B

35-3/4 35-3/4 45-3/4 45-3/4 45-3/4 45-3/4

C

47 49 49 49 53 55

UNIT CLEARANCES

1 2 Direction

Top 3 Side Opposite Ducts Duct Panel

Distance (in.)

36 36 0

Direction

Power Entry (Right Side) Left Side Bottom 4

Distance (in.)

36 24 1 1. A 1" clearance must be provided between any combustible material and the supply air duct work.

2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.

3. Units must be installed outdoors. Over hanging structure or shrubs should not obstruct condenser air discharge outlet.

4. Units may be installed on combustible materials made from wood or class A, B or C roof covering materials only if factory base rails are left in place as shipped.

14 Johnson Controls Unitary Products

5127524-YTG-E-1017

INDOOR BLOWER SPECIFICATIONS

Model

PHG4A24 PHG4A30 PHG4B36 PHG4B42 PHG4B48 PHG4B60

HP

1/2 1/2 1/2 3/4 3/4 1

RPM

Variable Variable Variable Variable Variable Variable

Motor EFF.

0.8

0.8

0.8

0.8

0.8

0.8

SF

1.0

1.0

1.0

1.0

1.0

1.0

Frame

48 48 48 48 48 48

SOUND PERFORMANCE - COOLING

Model (Tons)

PHG4A24 PHG4A30 PHG4B36 PHG4B42 PHG4B48 PHG4B60

Sound Rating dB (A)

72.4

68.7

73.2

73.6

74.0

74.1

1

1. Rated in accordance with AHRI Standard 270.

125

61.8

58.3

61.8

62.4

62.0

65.9

SOUND PERFORMANCE -

HEATING Model (Tons)

PHG4A24 PHG4A30 PHG4B36 PHG4B42 PHG4B48 PHG4B60

Sound Rating dB (A)

70.3

69.0

72.8

73.6

74.6

73.7

1

1. Rated in accordance with AHRI Standard 270.

125

64.7

57.5

60.1

62.4

66.0

61.6

250

59.2

58.0

62.5

58.3

63.3

59.4

250

60.5

58.8

63.2

59.0

62.0

61.8

ELECTRICAL DATA

Model Voltage

24050 24075 30050 30075 36065 36100 42065, 42100 48065, 48100, 48125 60065, 60100, 60125 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 1. Minimum Circuit Ampacity.

2. Maximum Over Current Protection per standard UL 1995.

3. Fuse or HACR circuit breaker size field installed.

RLA

10.0

10.0

14.0

14.0

17.0

17.0

18.0

22.0

24.0

Compressor LRA

62.0

62.0

73.0

73.0

79.0

79.0

112.0

117.0

144.0

MCC

16.0

16.0

22.0

22.0

26.0

26.0

28.0

34.0

38.0

Octave Band Centerline Frequency (Hz) 500 1000 2000

63.1

56.6

62.5

57.3

57.1

54.0

60.5

61.5

60.9

60.8

64.4

64.9

64.7

63.5

58.9

60.3

60.1

58.7

Octave Band Centerline Frequency (Hz) 500 1000 2000

59.8

58.0

58.1

63.8

54.3

53.2

60.4

61.5

61.1

60.5

64.5

65.7

64.6

63.6

58.8

59.7

60.2

58.7

OD Fan Motor FLA

0.7

0.7

0.6

0.6

1.7

1.7

1.7

1.7

1.7

Supply Blower Motor FLA

2.6

3.8

2.6

3.8

3.8

5.4

5.4

5.4

7.0

MCA 1 (Amps)

15.8

17.0

20.7

21.9

26.8

28.4

29.6

34.6

38.7

4000

51.8

48.4

53.4

55.8

56.6

55.5

4000

49.2

47.6

53.0

54.4

56.4

55.1

8000

44.0

43.0

45.9

50.6

49.2

48.3

8000

43.2

49.7

46.0

47.9

48.9

51.4

Max Fuse 2 / Breaker 3 Size (Amps)

25 25 30 35 40 45 45 50 60 Johnson Controls Unitary Products 15

5127524-YTG-E-1017 "D" CENTER OF GRAVITY COMPRESSOR "A" "C" FRONT OF UNIT

WEIGHTS & DIMENSIONS

Model

24050 24075 30050 30075 36065 36100 42065 42100 48065 48100 48125 60065 60100 60125

Weight (lbs.) Shipping

399 409 454 458 503 510 537 539 556 564 569 582 586 593

Operating

394 404 449 453 498 505 532 534 551 559 564 577 581 588 X

Center of Gravity X

28 28 28 28 29 29 29 29 28 28 29 29 28 27

Y

15 15 15 15 14 14 14 14 14 14 14 14 14 15 "B" Y A0295-001-TG

A

131 135 155 161 176 178 190 191 199 194 193 199 201 202

4 Point Load Location (lbs.) B

101 103 108 102 122 123 132 133 137 141 146 151 152 151

C

86 86 96 90 104 109 112 109 106 117 126 127 123 125

D

76 80 90 100 96 95 98 101 109 107 99 100 105 110 16 Johnson Controls Unitary Products

5127524-YTG-E-1017

Model Motor Speed

24050 24075 30050 30075 36065 36100 Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) 42065 42100 Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) 48065 Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) 48100 Medium/High (4) High (5) Continued on next page.

0.1

SCFM

732 818 823 994 1148 887 978 1171 1349 1487 700 906 992 1075 1136 1076 1102 1191 1201 1370 1225 1259 1314 1348 1506 1342 1425 1554 1658 1743 1315 1436 1458 1573 1743 1436 1544 1573 1681 1743 1046 1295 1620 1798 2146 1620 1694 1798 1835 2146

0.2

SCFM

667 771 774 948 1108 847 941 1114 1297 1462 657 868 951 1032 1089 1020 1048 1140 1225 1329 1174 1209 1271 1306 1471 1302 1368 1503 1599 1697 1266 1382 1406 1523 1697 1382 1492 1523 1640 1697 1009 1250 1564 1722 2085 1564 1630 1722 1758 2085 1650 1229 1342 1365 1484 1650 1342 1455 1484 1599 1650 980 1213 1517 1669 2025 1517 1580 1669 1703 2025 1000 1053 984 1010 1112 1187 1283 1131 1166 1229 1259 1403 1260 1332 1465 1588

0.3

SCFM External Static Pressure (Inches WC) 0.4

0.5

0.6

SCFM SCFM SCFM 0.7

SCFM

624 723 721 906 567 674 676 865 517 628 631 823 470 579 583 778 415 530 533 739 1071 802 898 1074 1265 1392 599 825 911 1035 750 850 1039 1224 1331 554 779 868 996 705 803 993 1185 1318 512 735 826 960 664 759 949 1146 1281 461 692 787 925 613 713 906 1107 1241 411 650 747 958 1018 943 974 1076 1151 1271 1090 1126 1186 1222 1389 1217 1293 1423 1530 918 978 903 934 1038 1118 1209 1046 1084 1144 1179 1345 1178 1251 1386 1495 874 941 859 890 1000 1080 1176 993 1032 1097 1133 1305 1134 1208 1346 1454 837 903 819 850 958 1041 1143 941 980 1049 1086 1262 1082 1163 1302 1414 1604 1194 1304 1327 1445 1604 1304 1416 1445 1557 1604 946 1172 1466 1620 1960 1466 1530 1620 1653 1960 1557 1156 1262 1286 1408 1557 1262 1376 1408 1517 1557 915 1133 1418 1572 1872 1418 1482 1572 1604 1872 1511 1117 1220 1244 1367 1511 1220 1336 1367 1478 1511 878 1087 1360 1527 1862 1360 1430 1527 1558 1862 1463 1080 1179 1203 1327 1463 1179 1294 1327 1436 1463 844 1045 1308 1480 1798 1308 1380 1480 1511 1798

0.8

SCFM

369 482 505 700 901 563 667 864 1063 1201 365 608 712 800 869 779 810 919 1002 1109 888 928 998 1036 1216 1034 1113 1257 1373 1418 1036 1131 1155 1279 1418 1131 1248 1279 1393 1418 779 964 1206 1413 1735 1206 1292 1413 1442 1735

1.0

SCFM

277 386 448 622 853 463 575 780 975 1121 273 524 642 726 801 699 730 841 924 1041 782 824 896 936 1124 938 1013 1167 1291 1328 948 1035 1059 1183 1328 1035 1156 1183 1307 1328 649 802 1002 1280 1609 1002 1116 1280 1304 1609 Johnson Controls Unitary Products 17

5127524-YTG-E-1017

AIRFLOW PERFORMANCE - SIDE DUCT APPLICATION (Continued)

Model

48125 60065 60100 60125

Motor Speed

Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) 1730 1858 2054 2195 2445 2063 2130 2195 2275 2445

0.1

SCFM

1620 1798 1922 2001 2146 1073 1329 2054 2195 2445

0.2

SCFM

1564 1722 1863 1952 2085 1043 1292 1998 2144 2388 1682 1807 1998 2144 2388 2008 2084 2144 2252 2388

0.3

SCFM

1517

External Static Pressure (Inches WC) 0.4

0.5

0.6

SCFM

1466

SCFM

1418

SCFM

1360 1669 1804 1890 2025 1009 1250 1934 2098 2306 1628 1749 1934 2098 2306 1943 2032 2098 2169 2306 1620 1754 1839 1960 988 1223 1890 2049 2293 1592 1710 1890 2049 2293 1899 1983 2049 2154 2293 1572 1724 1820 1872 963 1192 1843 2003 2235 1552 1667 1843 2003 2235 1851 1927 2003 2112 2235 1527 1658 1742 1862 941 1165 1801 1955 2178 1517 1629 1801 1955 2178 1809 1951 1955 2065 2178 1. Airflow tested with dry coil conditions, without air filters, at 230 volts 2. Applications above 0.8" w.c. external static pressure are not recommended.

3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.

4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.

5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.

0.7

SCFM

1308 1479 1589 1757 1883 2129 1763 1860 1883 1989 2129 1480 1612 1696 1798 917 1136 1757 1883 2129 1439 1546 1710 1868 2077 1717 1815 1868 1976 2077

0.8

SCFM

1206 1413 1559 1651 1735 892 1105 1710 1868 2077 1359 1460 1616 1838 1973 1625 1725 1838 1950 1973

1.0

SCFM

1002 1280 1453 1561 1609 842 1043 1616 1838 1973

Model Motor Speed

24050 24075 30050 Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) 30075 Low/Medium (2) Medium (3) Medium/High (4) High (5) Continued on next page.

1186 1357 1480 726 928 1021 1109 1170 1076

0.1

SCFM

754 867 951 1024 1204 899 1033 1104 1205 1285 1406

0.2

SCFM

710 815 908 982 1159 869 960 1133 1322 1439 676 886 983 1071 1134 1042 1063 1170 1251 1375

0.3

SCFM External Static Pressure (Inches WC) 0.4

SCFM 0.5

SCFM 0.6

SCFM 0.7

SCFM

665 773 868 942 611 720 828 902 560 677 781 861 491 622 735 817 445 559 686 775 1121 827 924 1095 1284 1404 622 1085 782 879 1056 1248 1367 575 1051 734 834 1016 1211 1369 520 1013 685 787 975 1174 1299 467 975 630 735 935 1127 1264 410 841 942 1029 1096 1009 1025 1136 1213 1341 795 900 995 1061 969 987 1098 1179 1306 745 855 949 1020 930 947 1060 1141 1271 706 811 908 978 890 908 1025 1104 1236 658 770 864 938 849 869 985 1065 1198 891 1087 1226 376 607 729 826 899 808

0.8

SCFM

391 505 631 721 938 575 685 830 943 1027 1163

1.0

SCFM

283 397 521 613 864 465 585 803 1007 1150 308 505 647 750 821 726 752 859 951 1093 18 Johnson Controls Unitary Products

AIRFLOW PERFORMANCE - BOTTOM DUCT APPLICATION (Continued)

Model

36065 36100 42065 42100 48065 48100 48125 60065 60100 60125

Motor Speed

Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5) Low (1) Low/Medium (2) Medium (3) Medium/High (4) High (5)

0.1

SCFM

1231 1270 1317 1358 1517 1340 1409 1527 1663 1711 1332 1457 1451 1568 1711 1455 1566 1565 1675 1711 1032 1272 1611 1892 2131 1598 1663 1789 1931 2131 1598 1766 1912 2105 2131 1026 1263 1987 2114 2369 1655 1766 1987 2114 2369 1973 2024 2123 2191 2369

0.2

SCFM

1186 1225 1286 1317 1475 1299 1368 1492 1585 1677 1295 1419 1412 1524 1677 1414 1532 1530 1641 1677 999 1236 1574 1777 2058 1548 1612 1733 1814 2058 1548 1703 1875 2014 2058 999 1230 1933 2050 2308 1612 1720 1933 2050 2308 1924 1983 2075 2154 2308 1998 1502 1656 1805 2006 1998 989 1192 1861 2047 2249 1596 1667 1861 2047 1491 1643 1379 1492 1491 1606 1643 970 1204 1518 1771 1998 1502 1568 1670 1808

0.3

SCFM External Static Pressure (Inches WC) 0.4

0.5

0.6

SCFM SCFM SCFM 0.7

SCFM

1146 1189 1245 1275 1103 1140 1198 1238 1069 1098 1151 1197 1030 1046 1110 1148 977 1008 1064 1105 1447 1264 1334 1470 1594 1643 1263 1376 1371 1400 1224 1291 1419 1601 1600 1222 1340 1339 1357 1182 1253 1385 1521 1560 1185 1299 1296 1318 1182 1201 1343 1480 1503 1148 1253 1257 1275 1097 1173 1299 1440 1466 1110 1215 1211 1464 1600 1335 1455 1458 1578 1600 938 1165 1494 1701 1949 1454 1522 1650 1736 1425 1560 1294 1416 1419 1535 1560 910 1129 1439 1639 1892 1410 1476 1596 1673 1383 1503 1254 1372 1381 1495 1503 879 1081 1405 1617 1840 1362 1422 1578 1650 2249 1905 1937 2019 2117 2249 1949 1454 1611 1787 1931 1949 950 1165 1817 1974 2183 1531 1629 1817 1974 2183 1826 1889 1970 2075 2183 1892 1410 1566 1750 1898 1892 907 1167 1820 1899 2126 1461 1632 1820 1899 2126 1743 1886 1978 2002 2126 1840 1362 1518 1713 1845 1840 907 1101 1715 1889 2088 1462 1539 1715 1889 2088 1744 1843 1862 1995 2088 1. Airflow tested with dry coil conditions, without air filters, at 230 volts 2. Applications above 0.8" w.c. external static pressure are not recommended.

3. Brushless DC high efficiency standard ECM blower motor used for all indoor blower assemblies.

4. Minimal variations in airflow performance data results from operating at 208 volts. Data above may be used in those cases.

5. Heating applications tested at 0.50" w.c. esp, and cooling applications tested at 0.30" w.c.esp per standards.

1345 1466 1212 1333 1336 1455 1466 843 1037 1357 1565 1788 1307 1370 1535 1597 1788 1307 1469 1672 1793 1788 886 1099 1725 1920 2034 1429 1537 1725 1920 2034 1703 1799 1849 2028 2034 Johnson Controls Unitary Products 5127524-YTG-E-1017 19

1.0

SCFM

781 866 943 961 1146 953 1038 1152 1320 1343 967 1051 1072 1200 1343 1056 1174 1198 1326 1343 737 829 1083 1336 1608 1139 1152 1379 1362 1608 1139 1319 1564 1631 1608 816 1015 1504 1758 1902 1316 1421 1504 1758 1902 1574 1679 1714 1866 1902

0.8

SCFM

912 960 1024 1057 1232 1049 1128 1250 1400 1425 1063 1160 1165 1296 1425 1160 1280 1290 1412 1425 808 968 1266 1489 1728 1251 1297 1483 1519 1728 1251 1419 1636 1739 1728 862 1071 1651 1866 1990 1391 1498 1651 1866 1990 1660 1759 1804 1974 1990

5127524-YTG-E-1017 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

CFM

500 600 700 800 900 1000 1100 1200 700 800 900 1000 1100 1200 1300 700 800 900 1000 1100 1200 1300 1400 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

ADDITIONAL STATIC RESISTANCE

Size (Tons)

24 (2.0) 30 (2.5) 36 (3.0) 42 (3.5) 48 (4.0) 60 (5.0) 0.02

0.02

0.02

0.03

0.04

0.04

0.04

0.04

0.05

0.05

0.02

0.02

0.02

0.03

0.04

0.04

0.04

0.04

0.05

0.05

Economizer 1

0.00

0.00

0.00

0.01

0.01

0.01

0.01

0.02

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.00

0.01

0.01

0.01

0.01

0.02

0.03

0.04

0.02

0.02

0.02

0.03

0.04

0.04

0.04

0.04

0.05

0.05

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.09

0.09

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.09

0.09

Wet Indoor Coil

0.01

0.01

0.01

0.02

0.03

0.04

0.05

0.06

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.02

0.03

0.04

0.05

0.06

0.07

0.07

0.08

0.09

0.09

0.04

0.04

0.05

0.05

0.06

0.07

0.08

0.09

0.10

0.11

0.04

0.04

0.05

0.05

0.06

0.07

0.08

0.09

0.10

0.11

Filter/Frame Kit

0.01

0.02

0.04

0.06

0.08

0.10

0.13

0.16

0.04

0.06

0.08

0.10

0.13

0.16

0.17

0.04

0.06

0.08

0.10

0.13

0.16

0.17

0.18

0.04

0.04

0.05

0.05

0.06

0.07

0.08

0.09

0.10

0.11

1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Filter pressure drop based on standard filter media tested at velocities not to exceed 300 ft/min.

BOTTOM DUCT DIMENSIONS (Inches)

' ´ 9,(:/22.,1*83 $7%277202)81,7 ´ & $ % $

Model

24, 30 36, 42, 48, 60 5(7851 $,5'8&7 +2/( ´ ZLWK´JURPPHW RSHQLQJIRUJDVSLSH 6833/< $,5'8&7 +2/( ´ IRUKLJK YROWDJH +2/( ´IRU ORZYROWDJH

A

10 14

B

21.5

13.5

)

C

5 5

REAR DUCT DIMENSIONS (Inches)

6833/< $,5'8&7 $

Model

24, 30 36, 42, 48, 60 $

A

9.6

13.6

% (

D

4.5

3.5

E

47.5

47.5

$

F

32 42 127(6HH)LJXUHWLWOHG³8QLW'LPHQVLRQV´IRUVLGHKROHVL]HVRI HOHFWULFDODQGJDVOLQHV 5(7851 $,5'8&7 $

B

22 14 20 Johnson Controls Unitary Products

5127524-YTG-E-1017

UNIT TYPICAL DUCT APPLICATIONS

ROOF CURB INSTALLATION REAR DUCT ROOF CURB INSTALLATION BOTTOM DUCT SLAB ON GROUND INSTALLATION A032

UNIT TYPICAL SLAB ON GROUND INSTALLATION

CONDENSATE DRAIN MANUAL GAS SHUTOFF VAVLE Johnson Controls Unitary Products TO GAS SUPPLY LINE TO POWER SUPPLY RETURN AIR DUCT CONTROL WIRING TO INDOOR THERMOSTAT SUPPLY AIR DUCT FIELD-SUPPLIED DISCONNECT SWITCH A0325-001 21

UNIT TYPICAL ROOF CURB INSTALLATION

CONDENSATE DRAIN MANUAL GAS SHUTOFF VAVLE TO GAS SUPPLY LINE TO POWER SUPPLY CONTROL WIRING TO INDOOR THERMOSTAT RETURN AIR DUCT ROOF CURB FIELD-SUPPLIED DISCONNECT SWITCH SUPPLY AIR DUCT ROOF A0326 Subject to change without notice. Published in U.S.A.

Copyright © 2017 by Johnson Controls, Inc. All rights reserved.

York International Corp.

5005 York Drive Norman, OK 73069

5127524-YTG-E-1017 Supersedes: 5127524-YTG-D-0817

Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement